DG 05 001-E 05-12 THESEUS InstallationAndCommissioningGuide
DG 05 001-E 05-12 THESEUS InstallationAndCommissioningGuide
DG 05 001-E 05-12 THESEUS InstallationAndCommissioningGuide
KG
Engine & Turbine Management
Am Haselbach 1
D-79677 Schönau/Germany
HEINZMANN®
Engine & Turbine Management
THESEUS
Copyright 2005-2012 by Heinzmann GmbH & Co. KG. All rights reserved.
This document may not be reproduced or handed on to third parties.
HEINZMANN shall not be held liable for any indirect and direct
damage nor for any incidental and consequential damage that results
from application of any of the examples, data or miscellaneous
information as given in this manual.
HEINZMANN shall not provide any guarantee for the design and
planning of the overall technical system. This is a matter of the operator
its planners and its specialist engineers. They are also responsible for
checking whether the performances of our devices match the intended
purpose. The operator is also responsible for a correct initial start-up of
the overall system.
Table of Contents
Table of Contents
Page
2 General ................................................................................................................................. 17
2.1 Proper and intended Use ................................................................................................ 17
2.2 General System Description .......................................................................................... 18
2.2.1 Measuring Function ............................................................................................... 19
2.2.2 Inputs and Outputs ................................................................................................. 19
2.2.3 ISO 9141 Interface for HEINZMANN Communication ....................................... 19
2.2.4 CAN Communication ............................................................................................ 20
2.2.5 RS-485 / Modbus Communication ........................................................................ 20
2.2.6 Real-Time Clock and permanent Memory ............................................................ 20
2.2.7 Status Indication .................................................................................................... 21
2.2.8 DcDesk 2000, ARGOS, PANOPTES .................................................................... 21
2.2.9 Speed Control ........................................................................................................ 21
2.2.9.1 HEINZMANN Speed Governors ................................................................... 21
2.2.9.2 Speed Governors made by other Manufacturers ............................................ 21
2.2.9.3 Integrated Speed Governor ............................................................................ 21
2.3 Firmware........................................................................................................................ 22
2.3.1 HEINZMANN's Basic Software ............................................................................ 22
2.3.2 Custom Firmware .................................................................................................. 22
2.4 Sources of complemental Information .......................................................................... 23
2.5 Conventions ................................................................................................................... 24
2.6 Parameter Lists .............................................................................................................. 24
2.7 Level .............................................................................................................................. 25
5 Specifications ....................................................................................................................... 45
5.1 Dimensional Drawing .................................................................................................... 48
5.2 Mechanical Installation.................................................................................................. 49
5.3 Additional Equipment ................................................................................................... 49
5.3.1 Retrofit Kit for Marine Applications ..................................................................... 49
5.3.2 CAN Repeater CR-01 ............................................................................................ 50
5.3.3 Load Share Interfaces DGM-IF01 and DGM-IF02 ............................................... 51
7 Functions of DGM-02.......................................................................................................... 89
7.1 Operating Mode Automatic or Manual ......................................................................... 89
7.2 Integrated Speed Governor ............................................................................................ 90
7.2.1 Setup of Analogue/PWM Outputs for Fuel Actuator Position Setpoint ................ 91
7.2.2 Test of the Actuator Positioning Function ............................................................. 93
7.2.3 Speed Governor Parameters................................................................................... 93
7.2.4 Speed Control for Generator Application .............................................................. 94
7.2.5 Speed Setpoint Determination ............................................................................... 94
7.2.5.1 Setpoint in Automatic Mode .......................................................................... 95
7.2.5.2 Setpoint in Manual Mode via digital Potentiometer ...................................... 95
7.2.6 Speed Ramp ........................................................................................................... 96
7.2.7 Droop ..................................................................................................................... 97
7.2.8 Starting Fuel Limitation ......................................................................................... 98
7.2.8.1 Fixed Starting Fuel Limitation ....................................................................... 99
7.2.8.2 Variable Starting Fuel Limitation ................................................................ 100
7.2.8.3 Temperature-dependent Starting Fuel Limitation ........................................ 102
7.2.8.4 Starting Sequence with Starting Speed Ramp .............................................. 104
7.2.8.5 Forced Actuator Opening ............................................................................. 106
7.2.9 Fuel Limitation Function ..................................................................................... 106
7.2.9.1 Speed-dependent Fuel Limitation ................................................................ 107
7.3 Offset Signal to external Speed Governor ................................................................... 109
7.3.1 Connection via HEINZMANN-CAN .................................................................. 110
7.3.2 Connection via Analogue Signal ......................................................................... 110
7.3.3 Connection via Raise/Lower Signals ................................................................... 111
7.3.4 Connection via CAN using SAE-J1939 Protocol ................................................ 113
7.4 Offset Signal to AVR .................................................................................................. 113
7.4.1 Connection via Analogue Signal ......................................................................... 114
7.4.2 Connection via Raise/Lower Signals ................................................................... 115
7.5 Start-Stop Sequence ..................................................................................................... 117
7.5.1 General Information ............................................................................................. 118
7.5.2 Overview of Start-Stop Phase and Phase of Generator Control .......................... 120
7.5.3 Output Parameters for Starting and Stopping ...................................................... 121
Safety instructions are not only denoted by a signal word but also by
hazard warning triangles. Hazard warning triangles can contain different
symbols to illustrate the danger. However, the symbol used is no substitute
for the actual text of the safety instructions. The text must therefore
always be read in full!
This symbol does not refer to any safety instructions but offers important
notes for better understanding the functions that are being discussed.
They should by all means be observed and practiced.
1.3 Before Putting an Installation into Service after Maintenance and Repair
Works
Check, if all slackened screw connections have been tightened again!
Make sure the control linkage has been reattached and all cables have been
reconnected.
Make sure all safety devices of the installation are in perfect order and are working
properly!
2 General
For a Digital Generator Management System of the DGM-02 series components from the
following selection will be used, depending on the customer's requirements.
THESEUS control unit in different versions, depending on the required configuration,
DcDesk 2000 PC program as the most flexible solution to configure and display data,
ARGOS as a Human-Machine-Interface (HMI),
PANOPTES as a Human-Machine-Interface (HMI),
HEINZMANN speed governors or speed governors made by other manufacturers,
HEINZMANN actuators,
Interface DGM-IF01 only for an analogue active load sharing and DGM-IF02 for an
analogue active and reactive load sharing to provide a simple load sharing between
generators or integration of older installations into the digital load sharing via the CAN
device communication,
CAN-Repeater CR-01 for the electrical isolation of HEINZMANN control units to CAN
Bus lines.
A written opinion from the manufacturer must always be procured in the event of any
obscurities, queries or missing statement.
The digital control unit THESEUS DGM-02 must not be used for any safety
function! Safety functions always have to be realised by alternative systems!
THESEUS DGM-02 may be applied redundant!
there are various versions of firmware available. Consequently, the configuration may
vary.
2.3 Firmware
The control unit's software is conceived both for universal applicability and a wide range
of functions. This means that the firmware contains many more functions than those
actually used for a specific application. Both the configuration of the input/output channels
of the control unit and the activation and parameter setting of functions may be carried out
by the customer.
Each control unit contains a boot loader (see also 14.5 Boot Loader) for loading the
firmware into the unit. HEINZMANN usually delivers the devices with so-called
HEINZMANN basic software that contains the standard delivery functions.
Proceeding from this basic software customized firmware variants can be made available
on request.
The software version number xx.y.zz or xxxx.yy.zz is displayed in parameter
3842 SoftwareVersion and consists of the following elements:
Customer number xx or xxxx
Variant y or yy
Modification index zz.
The present manual is based on the HEINZMANN's basic software with the
version number 0000.yy.25.
The available variants of HEINZMANN's basic software can be learned from Table
4: Overview of available Versions.
The diverse possibilities to control the speed of the prime mover coupled to the generator
by means of HEINZMANN governors are described in numerous other publications that
can be ordered from HEINZMANN.
2.5 Conventions
Throughout this manual the following typographic conventions have been adopted:
100 Gain Parameter names (identifiers) will always be represented by a
number and a name printed in italics. No difference is made
between the four 2.6 Parameter Lists
100 Gain An arrow preceding a parameter name will signify that this
parameter is explained in detail in some other section. For a brief
description see the chapter 15 Parameter Description. In this
chapter you will also find references to the pages containing a
detailed discussion of the respective parameter.
<100> In diagrams, numbers enclosed by pointed brackets are used to
indicate that the position thus marked corresponds to a parameter
number.
[500..501] There are certain parameters for which the limits of their respective
value ranges cannot be specified explicitly in the chapter
15 Parameter Description, but have to be communicated to the
control as values of specific parameters. For any such parameters
with variable value ranges, the parameter numbers defining their
specific range limits are enclosed in square brackets.
2.5 Conventions An arrow followed by italicized text refers to a chapter where the
respective function is described in more detail.
2.7 Level
The control serves primarily to determine the operational performance of the overall set
including engine and generator, or the mere generator with regard to speed, power etc. The
parameterization of the fundamental settings of a set should be left to the manufacturer's or
plant engineering company. This task requires access to all of the parameters. On the other
hand, it is quite sufficient for the user of a set to be shown or output only part of the
available parameters, i.e. the really necessary ones. This is why the parameters of
HEINZMANN controls are organized in a system of six user levels. In this way a clearer
overview is obtained and any accidental modifications are avoided by excluding certain
parameters.
Level 1:
The user can view almost only parameters of the measuring values list. These are e.g.
operating and measured values, setpoint and actual values, as well as status values and
alarms.
Level 2:
In addition to other parameters, users can modify the dynamic parameters and dynamic
map of the integrated speed governor, as well as the dynamic parameters of the
synchronizing governor and active power controller, as well as the voltage and reactive
power controller.
Level 3:
The engine start parameters can be modified.
Level 4:
In addition to other settings, comprehensive changes can be made to parameters of the
analogue inputs and outputs, sensors and the start-stop sequence.
Level 5:
This level is meant for parameters which are required for customer-specific software
modifications or upgrades.
Level 6:
This level allows any intervention into the functions of the control devices. Such as
assignments of inputs and outputs, communication and fundamental settings of
controllers and circuit breakers.
As can be seen from this survey any superior level is a proper superset of the previous
level. For each individual parameter the respective level is listed in the section
15 Parameter Description. The maximum level is determined by the diagnostics device
used (PC or handheld programmer) and cannot be changed. However, the option of
reducing the currently valid level by means of a special menu item of the PC programme or
via parameter 1800 Level is provided, thus allowing to reduce the number of visible
parameters and functions at any given time.
adjustment it is not necessary to know the precise interrelation between the parameter
numbers and the points of the characteristic or map since a special input section has been
provided offering assistance with regard to the peculiarities of parameterizing
characteristics and maps. This feature will prove very helpful to avoid erroneous inputs.
DcDesk 2000 is being continuously updated and enhanced by additional functions.
HEINZMANN recommend the use of DcDesk 2000 for testing and initial commissioning.
Similarly, when servicing the system, DcDesk 2000 will prove a decisive advantage for
diagnosis and troubleshooting.
3.4 ARGOS
The display and control panel ARGOS (please refer also to /3/) features a menu
command structure and can be used either for continuous display of measuring values or
for parameter setting.
The measuring values shown on the display are entered stably in the control unit and
cannot be changed.
In addition, the device is equipped with light emitting diodes that can be assigned
configuring the control unit with ARGOS itself or with DcDesk 2000.
For the arrangement of the LEDs please refer to Figure 1. LED 1 is orange, LED 5 is red
and all the remaining ones are green.
LED 2 LED 6
LED 1 LED 5
The LEDs can be marked by inserting small strips of paper under the transparent covering.
The control units are equipped with several inputs that can be configured at
the user's option. The number of functions that can be activated by external
switches is, however, considerably larger than the number of inputs. Therefore,
depending on the device version and on customer demands, the digital inputs
can be assigned to different functions. In the following chapters, it is presumed
that with regard to any function that is to be activated or switched over by
external switches, the respective switch has been accordingly implemented
and/or activated via a communication module.
x-values
y-values x index 0 x index 1 x index 2 x index 3 x index 4
If the current values in direction of the x- and/or y-axes are outside the domain of the map
as defined by the base points, the respective border value of the map will be used instead.
DcDesk 2000's graphic display shows this.
If it should prove necessary to restrict dependence to only one direction this can be
achieved by setting the base points for the other direction to their minimum value. In other
words, if there is functional dependence only in direction of the y-axis, all x index values
are to be set to minimum value. The base points for z will then be those of the series with
x-index 0.
HEINZMANN recommend to use 3.3 DcDesk 2000 for parameterizing maps and
characteristics as this programme will take care of all particulars to be paid attention to and
will simplify parameterization considerably. Thus, the above table is included in DcDesk
2000 in identical form and offers easy access to any of the base points. Furthermore, the
characteristics and maps can be represented graphically by this tool.
A reset will clear any data that has not been saved in the control's permanent
memory. It is, therefore, imperative that before executing a reset all data be
transferred to the control's permanent memory if this data is to be preserved.
Certain functions of the control unit require a reset for activation. These are mostly
functions that serve the purpose to put the control into some other operating state, or
parameters that cannot be modified during operation for safety reasons. The parameters
and functions belonging to this category will be explained in detail in the respective
chapters.
Since during each reset the control is de-energized for a short time, a reset
may be executed only when the engine is not running!
Application
Generator-to-Busbar Group-to-Group
Circuit Breaker
Input / Output (I /O)
Generator Powermeasurement
- Supervision Communication
- Voltage Control Protections
- Reactive Power Control Documentation
Synchronization
Wattless Switching
Special Functions Control of Customer Generation
- Sync to Shore Control of Powerfactor
Group-to-Mains
Access to Mains
Mains Failure
Control of Import / Export
Power Management
BASIC
MEDIUM
EXTENDED GROUP
Version
Figure 2: Overview of DGM-02 Versions and their Applications
The THESEUS control unit distinguishes between automatic mode and manual mode of
operation. The generator management features are only available in automatic operation. In
manual operation the THESEUS control unit is passive, except for the protective functions,
which are provided when these have been activated for manual operation. The auto mode can
be switched off by the operating staff or is excluded by other exterior circumstances.
4.1 Generator-to-Busbar
Simply speaking, a generating set is composed of a prime mover, a generator and a circuit
breaker to a busbar. These components can be controlled and monitored with the
THESEUS control unit. For these applications the BASIC, MEDIUM and EXTENDED
versions can be generally employed, depending on the size of the installation.
Version
BASIC MEDIUM EXTENDED
The BASIC variant is supplied with fixed settings for input and output connections in order
to ensure an easy and quick installation and commissioning. These assignments are printed
on the cover of the unit to allow installation without a customized wiring diagram. This
zero engineering philosophy does still provide sufficient flexibility to cover most
applications. A general wiring diagram is available under number ESK2645.
The MEDIUM variant comes with several well-proven standard sets of assignments to
keep the amount of project related engineering at an acceptable level.
The EXTENDED version is meant for very sophisticated applications. It provides wide-
ranging means of configuration for any type of application.
The scope of functions on the three versions is almost identical. It is based on the essential
parts for operating a prime mover and a generator.
verification of the current speed and control signals. For this purpose, the digital signals
must be linked via relay with the operating units of the engine, such as the connection of
the crank, a fuel lock or a coolant pump. The time periods allocated to the various
processes are either fixed or not known. In the latter case, a timeout is scheduled in
order to check if the process has been carried out successfully or to abort the process by
an error message.
The firmware can also be configured for diesel and gas-driven engines by the proper
setting.
The use of the starting and stopping sequence is optional. The use of only one partial
sequence is possible, too.
Speed Speed
Governor M Governor M
AVR G AVR G
3~ 3~
DGM-02 DGM-02
CAN
Busbar
Local
Load
Version GROUP
Plant size medium - big
Generator voltage up to 30 kV
Voltage connection direct/indirect
External phase transformers (PT) yes
Configuration of inputs and outputs user-configurable
Logically combined digital outputs yes
HZM-CAN yes
Modbus optional
Technical project support complete
4.2.1 Group-to-Group
If a system is composed of several sets which are switching on two separate busbars and
therefore show a group structure, the two busbars can be tied together and separated,
resp., with a circuit breaker which is controlled by a THESEUS control unit. The circuit
breaker of this Group-to-Group application can be closed by synchronizing one group to
the next. After a smooth loading and unloading process both the circuit breaker as well
as the generator groups can be operated in load sharing and then separated again.
Finally the circuit breaker can be opened with no load.
Circuit breaker, status control, close, open.
Synchronization by engine speed control of a group and regulation of the generator
voltages of the generators in one group.
Smooth loading and unloading of the group generators via ramp functions, until
both groups are load sharing or the group circuit breaker is wattless.
Protective functions to prevent inadmissible loads by monitoring the operating data
and tripping the circuit breaker, if necessary.
Special attention must be paid to the CAN communication. As the only application the
control unit is being linked with two CAN Buses coming from each group (see also
12 Bus Protocols). The control units of the DGM-02 series for the generators at the
'A' and 'B' busbars are linked by two separate CAN lines, i.e. one CAN line, each. Both
CAN lines are connected at the Group-to-Group device with CAN port 1 (busbar 'A')
and CAN port 2 (busbar 'B'). Since there is no connection between these two data buses,
the sets and their assigned node numbers cannot be seen from the other bus,
respectively. Consequently, identical node numbers may be allocated to both buses. The
other group, resp., is regarded as a generator, and the individual output of the generators
is replaced by the group output when load sharing setpoint values are generated.
The following Figure 4: Island Parallel Operation with Group-to-Group shows the
control unit DGM-02-GROUP in a Group-to-Group application for coupling two
busbars.
Local Local
Load Load
4.2.2 Group-to-Mains
If a plant has access to the grid and is intended for mains parallel operation, you can
employ a THESEUS control unit with a Group-to-Mains configuration, in order to
control the circuit breaker and to regulated the power output via the circuit breaker as
import or export power.
Circuit breaker, status control, close, open.
Synchronization of the active groups by engine speed control and regulation of the
generator voltages.
Smooth loading and unloading of the group generators via ramp functions, and
control of an import or export power output or pre-setting a base load setpoint value.
Protective functions to prevent inadmissible loads by monitoring the operating data
and tripping the circuit breaker, if necessary.
Especially in parallel operation: the detection of a power failure and separation of
the circuit breaker as well as the automatic re-synchronization.
The CAN communication via CAN port 1 of the control unit needs only to be linked to
the bus line pertaining to the control units of the relevant busbar. Setpoint values which
are output by a Group-to-Mains control unit are looped through by a Group-to-Group
control unit to the load sharing users of the second busbar.
The following Figure 5: Mains Parallel Operation with Group-to-Mains shows the
control unit DGM-02-GROUP in a Group-to-Mains application for coupling a busbar
with the grid.
Speed Speed
Governor M Governor M
AVR G AVR G
3~ 3~
DGM-02 DGM-02
DGM-02- CAN
GROUP
Mains Busbar
Local
Load
The second section (variant) of the software version number does help to identify the
version of the DGM-02 according to the pattern described in Table 4.
As shown in the table (*1), a CAN implementation of the SAE-J1939 protocol is available.
However, due to the specific nature of the generator-related parts of this protocol,
customers are requested to seek assistance of a HEINZMANN project engineer to find the
suitable software version.
HEINZMANN-CAN
GROUP-TO-GROUP
Customer Module
GROUP-TO-MAINS
SAE-J1939 MTU
Speed Governor
SAE-J1939
EXTENDED
Integrated
DeviceNet
CANopen
MEDIUM
Modbus
BASIC
00 10 20 30 - - X - - - - *1
Variant of the software
01 11 21 - - X X - - - -
- 12 22 32 33 - - X - X -
- 13 23 - - X - X - X -
04 14 24 34 - - - - X - -
05 15 25 - - X - - X - -
- 51 61 - - - - X - X X
5 Specifications
General
Operating voltage
nominal 24 Vdc (18…33 Vdc)
reduced function range 9…18 Vdc
Residual ripple 10 % maximum at 100 Hz
Power consumption maximum 5 W
Operating temperature -40 °C to +70 °C
Storage temperature -55 °C to +85 °C
Air humidity up to 70 %, not condensing
Display
Status indicator 8 LEDs
Error display 7-segment, 2-digit
Relay output
Voltage / current rating 24 Vdc / 8 A
240 Vac / 8 A
1
only available for DGM-02-EXTENDED and DGM-02-GROUP, by using potential transformer up to 30 kV
2
by using current transformer up to 7500 A
3
test voltage: 650 Vac at 50 Hz for 60 s
Communication
CAN connection 1 (floating) ISO 11898, CAN2.0B (extended ID)
insulation voltage 500 Vac3
CAN connection 2 ISO 11898, CAN2.0B (extended ID)
Interface HEINZMANN communication ISO 9141 (RS-232) up to 57.6 kBaud
Modbus RS-485 (floating), optional EIA/TIA-485/422 up to 19.2 kBaud
insulation voltage 500 Vac3
RS-232, optional EIA/TIA-232
Environmental Tests
EMC immunity EN/IEC 61000-6-2:2005 (Part -4-1, -4-2,
-4-3, -4-4, -4-5, -4-6, -4-8)
EN/IEC 61326-1:2006
EMC emission EN/IEC 61000-6-4:2007
EN 5501:2009
FCC Code of Federal Regulations:
CFR47, Part 15, Sections 15.107 and
15.109
Safety requirements for electrical equipment
for measurement, control and laboratory use EN/IEC 61010-1
Climate, vibration IEC 60068-2-1, -2-2, -2-6, -2-30
High voltage IEC 60947-2
Insulation IEC 60092-504
Marine Approval
Lloyd's Register EMEA Type Approval Certificate No. 07/20036
Det Norske Veritas Type Approval Certificate No. A-12355
Order number
HZM number 620-00-057-00
General
Output voltage 0…6 V
Output impedance 15.5 k
Order number
HZM Number 602-00-036-00
General
Output voltage -6…6 V
Output impedance 15.5 k
Order number
HZM number 602-00-036-01
T 2A
51 50
(USE 2A FUSE!)
GND
+
24VDC
The current power supply value can be read from the measured value 3600 PowerSupply.
With power supply values lower than 18 V down to 9 V for example caused by break-
down of the starter battery during cranking the engine the following functions may be
limited: sensor supply 24 V, analogue output AO5 and relay output DO13.
The digital inputs are used as on/off or toggle switches for switching functions
11 Switching Functions. The switching functions can be configured to be high-active, i.e.
active with the switch closed, or low-active, i.e. active with the switch opened.
Apart from the DGM-02 BASIC (see also 4 Versions and Applications), all versions of
DGM-02 allow a completely flexible assignment between hardware I/Os and internal I/O
functions.
Since the input signals are being debounced by the control circuit it is
necessary that they be applied for at least 20 ms to be detected. In general, any
switching function will be active only for the time the switch input is active.
The below described digital input assignments to the following switch functions result
from the above Table 6: Digital Inputs for the BASIC version. These assignments are
already pre-set in the firmware and cannot be altered in the BASIC version.
2810 SwGCB_Closed see section 7.6 Circuit Breaker I/Os
2811 SwGCB_Open see section 7.6 Circuit Breaker I/Os
2812 SwMCB_Closed see section 7.6 Circuit Breaker I/Os
1
fixed assignment of digital inputs to the switching function
+24Vdc
GND
75 74 73 72 71 70 69 68
DI11
DI12
DI10
DI9
DI1
DI2
DI5
DI6
DI7
DI8
DI3
DI4
+24V 0V +24V 0V +24V 0V +24V 0V +24V 0V +24V 0V +24V 0V +24V 0V
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
+24Vdc
GND
2
fixed assignment of the control signal to the digital output
The below described control signal assignments to the digital outputs result from the above
Table 7: Digital Outputs for the BASIC version. These assignments are already pre-set
in the firmware and cannot be altered in the BASIC version.
12602 GCB_RelayCloseOn see section 7.6 Circuit Breaker I/Os
12603 GCB_RelayOpenOn see section 7.6 Circuit Breaker I/Os
12382 AVROffsetIncPulse see section 7.4 Offset Signal to AVR
12384 AVROffsetDecPulse see section 7.4 Offset Signal to AVR
22035 RelayFuelOn see section 7.5 Start-Stop Sequence
22033 RelayCrankOn see section 7.5 Start-Stop Sequence
22034 RelayIgnitionOn see section 7.5 Start-Stop Sequence
12480 RelayAnalogLSLineOn see section 7.11 Analogue Load Share Line
3801 CommonAlarm see section 14.3 Alarm Display
3800 EmergencyAlarm see section 14.3 Alarm Display
3
alternatively also as PWM output
The configuration options as digital or PWM output can be learned from the following
Table 8: Configurable Digital Outputs.
4
modifications to these parameters will be activated only following a storage and a reset
+24Vdc
67 66 65 64 63 62 61 60 59 58 57 56
+24V +24V +24V +24V +24V +24V +24V +24V +24V +24V +24V +24V
DO11
DO1
DO12
DO10
DO9
DO8
DO7
DO6
DO5
DO4
DO3
DO2
Figure 11: Connection of Digital Outputs
The PWM outputs can be used for energizing the power output stages or transmitting
signals.
5
alternatively also as a digital output
lower and upper output values are entered into the parameters as a percentage of the
value range of the relevant output parameters.
If the entire value range is required, the minimum value is to be set to 0 % and the
maximum value to 100 %.
Parameterizing Example:
Actual speed 2000 Speed is to be read out via a PWM output 1, restricted to the range
from 500 rpm to 1500 rpm. As the values of this parameter have a range from 0 to
4000 rpm, output will have to be adapted:
500
1603 PWMOut1_ValueMin 100% 12.5%
4000
1500
1604 PWMOut1_ValueMax 100% 37.5% .
4000
Number Parameter Value Unit
1600 PWMOut1_Assign 2000
1603 PWMOut1_ValueMin 12.5 %
1604 PWMOut1_ValueMax 37.5 %
4800 DigitalOut9_PWMOrDO 1
SPEED
[rpm]
1500
output parameter
500
0 5 95 PWM RATIO
[%]
Value range of the
PWM output
Analogue input 1 AI1 (V/C) Load Setpoint 76, 77, 78, 79 0…5 V or
4…20 mA
Analogue input 2 AI2 (V/C) AI2 (V/C) 80, 81, 82, 83 0…5 V or
4…20 mA
Analogue input 3 AI3 (V/C) AI3 (V/C) 84, 85, 86, 87 0…5 V or
4…20 mA
Analogue input 4 AI4 (V) Sharing In6 --, 11, 12, 13 0…5 V
Analogue input 5 AI5 (V) AI5 (V) --, 14, 15, 16 0…5 V
Analogue input 6 AI6 (V) AI6 (V) --, 17, 18, 19 0…5 V
Analogue input 7 AI7 (IS-C) AI7 (IS-C) --, --, 88, 89 4…20 mA
floating
Temperature input7 TI1 Temperature --, --, 20, 21 PT 1000
The configuration options can be learned from the following Table 11: Configurable
Analogue Inputs.
6
fixed assignment of the analogue input 4 to the sensor
7
due to the design as a two-conductor connection the absolute precision depends on the length and cross section
of the conductors
8
modifications to these parameters will be activated only following a storage and a reset
The signal lines must be shielded up to the device connection. The signal
lines shielding have to be connected to protective earth (PE) at one point in
the switchgear cabinet or at the mounting plate.
Optional supply
Optional supply
4..20mA
0..5V
GND
GND
470
470
89 88 87 86 85 84 83 82 81 80 79 78 77 76
+24V
+24V
+24V
GND
GND
GND
+5V
+5V
+5V
+
-
IN
IN
IN
AI7(IS-C)
AI3(V/C)
AI2(V/C)
AI1(V/C)
AI4(V)
AI5(V)
AI6(V)
TI1
GND
GND
GND
GND
+5V
+5V
+5V
IN
IN
IN
IN
11 12 13 14 15 16 17 18 19 20 21
and percentage of the sensor range. To enable the control to operate with the physical
value transmitted by the sensor, it is necessary that the control be provided with two
reference values informing it about the relation between the electrically measured
values and the actual physical quantities. The two reference values are the sensor output
values associated with the minimum and maximum measuring values as described in
10.4 Measuring Ranges of Sensors. With this information, the control is capable of
normalizing the measured values and of displaying them specified in per cent of the
sensor range or directly in terms of their physical values.
4,8
40 (5%) 1,0
40 (5%)
18700 Error threshold
16000
Each of the voltage/current inputs is associated with a low reference value (parameters
1510 AnalogIn1_RefLow to 1570 AnalogIn7_RefLow) and a high reference value
(parameters 1511 AnalogIn1_RefHigh to 1571 AnalogIn7_RefHigh).
Parameterizing Example:
An oil pressure sensor has been connected to input 4. Its measuring range is supposed to
be from 0.5 bar to 3.5 bar and is to be converted into voltages ranging from 1.0 V to
4.8 V. At minimum voltage the parameter 3541 AI4_Value will indicate a value of
9,000 digits and at maximum voltage a value of 35,000 digits. The parameter 3540 AI4
will display the actual measurement as related to the reference values in per cent, and
the parameter 2912 OilPressure will read the converted measuring value in bar.
Number Parameter Value Unit
912 AssignOilPressure 4
988 OilPressSensorLow 0.5 bar
989 OilPressSensorHigh 3.5 bar
1540 AnalogIn4_RefLow 9000
Time constant:
8
[ s] 0.125 s
64
can be used to define inadmissible operating ranges by which the control can
recognize that the sensor is at fault. The error limits are indicated in digits, just like
the reference values.
The parameters 1512 AnalogIn1_ErrorLow to 1582 TempIn1_ErrorLow define the
lower error limits. The parameters 1513 AnalogIn1_ErrorHigh to
1583 TempIn1_ErrorHigh determine the upper error limits.
Parameterizing Example:
The oil pressure sensor connected to analogue input 4 normally supplies measuring
values ranging between 9,000 and 35,000 digits. In case of a short circuit or a cable
break the measurements will be below or above these values, respectively. The
ranges below 7,000 digits and above 38,000 are defined as inadmissible by the
following parameters:
Number Parameter Value Unit
912 AssignOilPressure 4
1540 AnalogIn4_RefLow 9000
1541 AnalogIn4_RefHigh 35000
1542 AnalogIn4_ErrorLow 7000
1543 AnalogIn4_ErrorHigh 38000
4912 ChanTypOilPressure 0
These error limits should not be chosen too close to the minimum and maximum
values in order to prevent natural fluctuations of the values measured by the sensors
from being mistaken as errors. On the other hand, it must be ensured that short
circuits or cable breaks are unambiguously recognized as such.
Once an error is detected, the sensor error parameter (error flag) associated with the
analogue input is set. For the actions to be taken in the event that any such error
occurs, please refer to chapter 14.7 Error Parameter List. If an analogue input is
not used due to not being assigned to a sensor it will not be monitored for errors.
Parameter Meaning
Parameter Meaning
35x0 AIx current measuring value in %
35x1 AIx_Value current measuring value in digits
55x2 AnalogInx_TempLin selection of linearization characteristic
Parameter Meaning
Any inputs that have not been assigned a sensor (see also 10 Sensors), will not be
monitored for errors, and indicate only the measuring value 35x1 AIx_Value resp.
3581 TI1_Value.
9
fixed assignment of the parameter to the analogue output
The configuration options can be learned from the following Table 15: Configurable
Analogue Outputs.
The signal lines must be shielded up to the device connection. The signal
lines shielding have to be connected to protective earth (PE) at one point in
the switchgear cabinet or at the mounting plate.
AO5(200mA)
AO1(IS-V±)
AO3(V/C)
AO4(V/C)
AO2(V±)
GND
GND
GND
OUT
OUT
OUT
OUT
+
-
0V
24 25 26 27 28 29 30 31 32 33
PE
Signal
GND
10
modifications to these parameters will be activated only following a storage and a reset
The PC programme 3.3 DcDesk 2000 allows to enter output ranges in the
parameter's specific measurement unit.
Parameterizing Example:
Current speed 2000 Speed is to be read out via analogue output 3 as a current signal of
4…20 mA. The output range shall be restricted to 500 rpm through 1500 rpm, i.e.
500 rpm correspond to 4 mA and 1500 rpm to 20 mA. Since the values of this
parameter have a range from 0 to 4000 rpm, output will have to be adjusted
accordingly:
500
1653 AnalogOut3_ValueMin 100% 12.5%
4000
1500
1654 AnalogOut3_ValueMax 100% 37.5% .
4000
CURRENT
[mA]
Parameterizing Example:
The actual speed 2000 Speed is to be output as a current signal 4…20 mA via analogue
output 3. The only range being 500 rpm to 1500 rpm, which means that 500 rpm
correspond to 4 mA and 1500 rpm correspond to 20 mA. The maximum output range is
approx. 0…25 mA, resulting in:
4
1651 AnalogOut3_RefLow 100 % 16%
25
20
1652 AnalogOut3_RefHigh 100 % 80%
25
Number Parameter Value Unit
1650 AnalogOut3_Assign 2000
1651 AnalogOut3_RefLow 16.0 %
1652 AnalogOut3_RefHigh 80.0 %
1653 AnalogOut3_ValueMin 12.5 %
1654 AnalogOut3_ValueMax 37.5 %
5650 AnlogOut3_CurrOrVolt 1
Because of component tolerances the output range may vary slightly from
control unit to control unit even when parameter values are the same. In
order to achieve a precise output, re-measure the output range with a multi-
meter and adjust the parameters correspondingly. When parameters are
copied from one control unit to another one, these configuration values
should be left aside.
The signal lines must be shielded up to the device connection. The signal lines
shielding have to be connected to protective earth (PE) at one point in the
switchgear cabinet or at the mounting plate.
PICK-UP
GND
IN
22 23
PE
The current speed 2000 Speed corresponds to 2001 SpeedPickUp1, if a speed pickup is
connected. This speed value is used as a basis for all the functions, such as the
integrated speed governor, fuel limitations etc. The not filtered speed is only used for
indication.
The measured speeds are filtered with a special process to eliminate engine
speed variations due to the coefficient of cyclic variation.
If no speed pickup is connected or if there is an error of the pickup pending, the current
speed 2000 Speed is either
1) allocated with the speed value 2004 SpeedViaCAN, which is transmitted by a
HEINZMANN speed governor via CAN communication (may also be adequate for
the complete functionality of the start-stop sequence) or
2) allocated with a speed value calculated from the generator frequency
(2006 AlternatorSpeed).
The active source for the actual speed value can be read from the display value
2005 ActivePickUp (0 = Pickup, 3 = CAN communication, 4 = Generator frequency).
When using a DGM-02 version with 7.2 Integrated Speed Governor, the parameter
4006 AlternatorSpeedOn has to be activated if the speed value calculated from the
generator frequency should be used as redundant speed.
A change to the teeth number will only be activated after 3.2 Saving Data
and a subsequent 3.10 Reset of Control Unit.
terminals. When using the analogue load share line for a busbar, please make sure to use a
comparable allocation.
On the Group-to-Mains unit, connect the mains voltages to the (BUS) terminals and the
busbar voltages to the (GEN) terminals.
Both Y (why) and (delta) applications are accepted. All phase connections must be
completely implemented. The connection of the neutral conductor is optional.
The Figure 18 shows the basic connection of the three-phase measuring lines (3 times
generator voltage, 3 times generator current and 3 times busbar voltage) for a generator
control in the Generator-to-Busbar application.
Busbar
(BUS)
DGM-02
(GEN)
G G
3~
G
3~
3~
Figure 18: 3-Phase Voltage and 3-Phase Current Sensing for Generator Control
The Figure 19 shows the three-phase measuring schematic (3 times busbar voltage,
3 times busbar current and 3 times mains voltage) for the Group-to-Mains application.
DGM-02
(GEN)
(BUS)
Mains Busbar
G G
3~ 3~
Figure 19: 3-Phase Voltage and 3-Phase Current Sensing for Group-to-Mains Application
The Figure 20 shows the three-phase measuring schematic (3 times busbar voltage 'A',
3 times busbar current 'A' and 3 times busbar voltage 'B') for the Group-to-Group
application. For Group-to-Group application the correct use of the CAN connections is
also shown.
(GEN)
(BUS)
DGM-02
CAN connection group ‘A’ CAN connection group ‘B’
(CAN1)
(CAN2)
G G G G
3~ 3~ 3~ 3~
Figure 20: 3-Phase Voltage and 3-Phase Current Sensing for Group-to-Group Application
11
terminal only useable for DGM-02-EXTENDED and DGM-02-GROUP
The following parameters are available for indicating the current frequency:
12001 FrequencyNet_L1 Frequency of the busbar connected at the BUS
terminals for phase L1 (ff. for L2 and L3)
12004 FrequencyNetAvg_L1 Average frequency of the busbar connected at
the BUS terminals for phase L1
12006 FrequencyNetRaw_L1 Unfiltered frequency of the busbar connected
at the BUS terminals for phase L1 (ff. for L2
and L3)
12011 FrequencyGeneratorL1 Frequency of the generator or the busbar
connected at the GEN terminals for phase L1
(ff. for L2 and L3)
12016 FrequencyGenRaw_L1 Unfiltered frequency of the generator or the
busbar connected at the GEN terminals for
phase L1 (ff. for L2 and L3)
and the following parameters are available for indicating the current voltage values:
12101 VoltageBus_L1 Phase voltage of the busbar connected at the
BUS terminals for phase L1 (ff. for L2 and L3)
12104 VoltageBus_1_2 Phase-to-phase voltage L1/L2 of the busbar
connected at the BUS terminals (ff. for L2/L3
and L3/L1)
12111 VoltageBusRel_1_2 Relative phase-to-phase voltage L1/L2 of the
busbar connected at the BUS terminals (ff. for
L2/L3 and L3/L1) related to the rated value
12121 VoltageGen_L1 Phase voltage of the generator or the busbar
connected at the GEN terminals for phase L1
(ff. for L2 and L3)
12124 VoltageGen_1_2 Phase-to-phase voltage L1/L2 of the generator
or the busbar connected at the GEN terminals
(ff. for L2/L3 and L3/L1)
12131 VoltageGenRel_1_2 Relative phase-to-phase voltage L1/L2 of the
generator or the busbar connected at the GEN
terminals (ff. for L2/L3 and L3/L1) related to
the rated value
Parameterizing Example:
An medium-voltage unit with a rated voltage of 4.16 kV phase-to-phase and a rated
frequency of 60 Hz is connected via voltage transformer and 120 V secondary voltage
to terminals 1A, 2A and 3A (L1…L3) on the generator side, and to terminals 97A, 96A
and 95A (L1…L3) on the busbar side. The PT-ratio through the external voltage
transformers results from:
U primary 4160V
10300 PT_Ratio 34.67 .
U secondary 120V
When using external phase transformers the above described measured values indicate
the current voltage values of the secondary circuit. The current voltage values of the
primary circuit are output by the following parameters:
The same applies if different sets of phase transformers are used for the generator side
and for the busbar side. But with rated voltage of the BUS terminals
10302 PT_RatioBUS not be configured when the voltage level is not different.
Parameterizing Example:
Phase transformers are used at the terminals 1A, 2A and 3A (L1…L3) on the generator
side which transform 6.3 kV primary voltage into 100 V secondary voltage. Against it
the PTs at the terminals 97A, 96A and 95A (L1…L3) on the busbar side transform
6.0 kV into 100 V. The rated voltage of the plant should be 6.3 kV. This results in the
following basic settings for voltage measurement:
The following parameters indicate the actual current and power values:
12141 Current_L1 Phase current L1 of the secondary side (ff. for
L2 and L3)
12147 CurrentPrim_L1 Phase current L1 of the primary side (ff. for L2
and L3)
12151 CurrentRel_L1 Relative phase current related to the rated
value (ff. for L2 and L3)
12200 Power Total effective power (secondary side)
12201 PowerReactive Total reactive power (secondary side)
12202 PowerApparent Total apparent power (secondary side)
12203 cosPhi Total value of power factor (cosine of phase
difference )
12204 sinPhi Overall value sine of phase difference
12205 PowerRelative Relative effective power related to the rated
value
12206 PowerReactiveRelativ Relative reactive power related to the rated
value
12208 PowerPrim Effective power (primary side)
12209 PowerReactivePrim Reactive power (primary side)
12210 PowerApparentPrim Apparent power (primary side)
12211 Power_L1 Effective power (secondary side) Phase L1 (ff.
for L2 and L3)
12221 PowerReactive_L1 Reactive power (secondary side) Phase L1 (ff.
for L2 and L3)
12231 PowerApparent_L1 Apparent power (secondary side) Phase L1 (ff.
for L2 and L3)
12241 PowerPrim_L1 Effective power (primary side) Phase L1 (ff.
for L2 and L3)
7 Functions of DGM-02
3204 SpeedGovAutoPossible 1
13000 ErrAutoNotAvailable 0
Skip paragraph, if your unit does not include the integrated speed governor
option. For set-up of a signal to an external speed governor, refer to
7.3 Offset Signal to external Speed Governor.
Others
Figure 22: Control Structure for DGM-02 w/o integrated Speed Governor Function
Speed Down
Idle/Rated
Speed Up
Others
DGM-02 Actuator or
Speed equivalent
Voltage Sync / Load Offset Fuel Rack Position/
Speed Control Fuel Control
Current Control Demand Injection Time
(+-5%)
Figure 23: Control Structure for DGM-02 with integrated Speed Governor Function
If the control unit is equipped with the integrated speed governor function, it provides a
position setpoint signal for any kind of active fuel actuator (positioner). Signals available
are analogue in the range of -5 Vdc…+5 Vdc (isolated, i.e. can also be used as 0…10 Vdc),
4…20 mA, 0…200 mA, or PWM. The possibilities are shown in Table 18: Position
Setpoint Output to Positioner and Figure 24: Options to Connect a Positioner.
AO5(200mA)
AO4(V/C)
AO2(V±)
GND
GND
OUT
OUT
OUT
0V
26 27 30 31 32 33
PE PE PE
output 2 is designed for a maximum range of -5…+5 V the lower reference parameter
(see also 6.6.3 Value Range of Output Parameters) must be adapted correspondingly.
Number Parameter Value Unit
1645 AnalogOut2_Assign 2330
1646 AnalogOut2_RefLow 50.0 %
1647 AnalogOut2_RefHigh 100.0 %
1648 AnalogOut2_ValueMin 0.0 %
1649 AnalogOut2_ValueMax 100.0 %
Parameterizing Example 2)
Current signal 4…20 mA:
Instead of the voltage signal from the above example, a current signal of 4…20 mA, and
analogue output 4 should be used. For this purpose, analogue output 4 must be
configured as a current output (refer also to Table 15: Configurable Analogue
Outputs). Besides, the reference values (see also 6.6.3 Value Range of Output
Parameters) must be adjusted, because the maximum range of output is 0…25 mA.
Number Parameter Value Unit
1655 AnalogOut4_Assign 2330
1656 AnalogOut4_RefLow 16.0 %
1657 AnalogOut4_RefHigh 80.0 %
1658 AnalogOut4_ValueMin 0.0 %
1659 AnalogOut4_ValueMax 100.0 %
5655 AnlogOut4_CurrOrVolt 1
Parameterizing Example 3)
Current signal 0…200 mA:
If the positioner needs to be energized with a current signal of 0…200 mA, analogue
output 5 must be used.
Number Parameter Value Unit
1660 CurrentOut5_Assign 2330
1661 CurrentOut5_RefLow 0.0 %
1662 CurrentOut5_RefHigh 100.0 %
1663 CurrentOut5_ValueMin 0.0 %
1664 CurrentOut5_ValueMax 100.0 %
Parameterizing Example 4)
PWM signal:
For energizing the active positioner, a PWM signal should be provided. The position
setpoint is to be transmitted with a pulse-pause-ratio of 5…95 % via PWM output 1. For
this purpose, configure the digital output 9 to output a PWM signal (refer also to
Table 8: Configurable Digital Outputs).
Parameter Meaning
Parameter Meaning
6350 to 6359 PIDMap:P(y) Power values for PID map
6200 to 6299 PIDMap:Corr(z) Correction values for PID map
The "engine stop" function (speed setpoint = 0) is no setpoint in the true sense of
meaning, but it is of priority compared to all other functions while observing the start-
stop sequence.
The parameter 3802 EngineStopRequest serves to indicate that the engine is being
stopped by some internal or external stop command. External engine stop is executed by
means of the switch 2820 SwStopRequest while for an internal engine stop the shutdown
command is issued by the control itself (e.g. in case of overspeed, see also
6.7.4 Overspeed Monitoring). The parameter 3803 EngineStopped is provided to
indicate that the engine has stopped.
The switch function 2831 SwIdleSpeed allows to select the lower idle speed
10 SpeedMin for the speed setpoint. This function is being used when the engine is to be
run at the lower idle speed for warming it up or cooling it down.
Even when the engine is running at rated speed only, the minimum and maximum
speeds (10 SpeedMin and 12 SpeedMax) must have been set to reasonable values since
by synchronization and load control a speed offset will be generated and added to rated
speed.
As an orientation, minimum and maximum speeds should differ from rated speed by at
least 5 %.
signals for changing the setpoint consist of pulses, these pulses must have a duration
of at least 20 ms in order to be detected by the control circuit. The control electronics
will respond to pulses for changing the setpoint only when the engine is running.
Setpoint changes will be possible until either maximum or minimum speed is
attained. Furthermore, speed will be increased only if fuel quantity has not yet
attained maximum limitation, and likewise decreased only, when fuel quantity has
not yet attained minimum limitation. The current Offset value of the digital
potentiometer can be learned from the parameter 2041 DigitalPotOffset. With the
engine standing, the accumulated offset will be cleared.
Activation:
4230 SpeedRampOn 1
7.2.7 Droop
Droop (also called proportional band) of an engine is defined as the permanent speed
drop when the engine takes on load. The manual mode, i.e. the non-isochronous
operation requires a droop.
In isochronous operation (automatic mode) without droop (internally deactivated), any
fuel quantity may be set with a pre-defined fixed speed setpoint. When using droop,
however, there is a close interrelation between speed and fuel quantity. In this case, the
pre-defined speed setpoint corresponds to that for the pre-set reference point (full load
or zero load). Depending on current load, droop is used to calculate an offset which
after being added to the given speed setpoint will yield the actual speed setpoint for the
control unit.
Activation of droop is achieved for the manual mode by setting the parameter
4120 DroopOn = 1. In automatic mode the droop is generally not used.
The reference point for the droop is determined by the parameter
4122 Droop@ZeroOrFullLoad. The full load point if used whenever the parameter is 0
but the zero load point becomes active when the parameter is 1.
The following relation holds:
n0 nV
XP 100%
nV
Example:
Full-load speed: 1500 rpm
Zero-load speed: 1560 rpm
1560 1500
120 Droop = 100 % 4%
1500
Any adjustment of droop refers to the rated speed as set by 17 SpeedRated. Thus, e.g.
for a rated speed of 1500 rpm, a droop of 120 Droop = 4 % will yield a speed change of
60 rpm.
This speed change will apply to the working range between full-load and zero-load. The
full-load reference value is the rated load of 10330 LoadRated.
The speed offset as calculated from droop can be viewed by the parameter
2040 DroopOffset. This offset is added to the speed setpoint value after the ramp
2032 SpeedSetpRamp thus yielding the speed setpoint 2031 SpeedSetp for the control
unit.
Each engine start (also on variants without integrated speed governor) is counted in
2250 EngineStartCounter. Operating hours of the running engine or the generating set
are recorded in 3871 OperatingHourMeter, 3872 OperatingMinuteMeter and
3873 OperatingSecondMeter (also on variants without integrated speed governor).
The current engine states are indicated by the following parameters:
3802 EngineStopRequest A request for stopping the engine is being
applied, the running engine stops, engine start
is not possible
3803 EngineStopped Engine stopped
3804 EngineStarting Engine is being started
3805 EngineRunning Engine is running
SPEED
[rpm]
Maximum speed
<12>
Set speed 1
Speed range
<2031>
of engine
Set speed
Minimum speed
<10>
Start speed 2
<256> Current speed
Start speed 1
<255>
TIME [s]
ACTUATOR POSITION
[%]
Start fuel 1
<260>
TIME [s]
Phase
<3830>
0 3 4 5,6,7
If within the time defined by 265 StartDuration1 the engine should not start-off with
starting fuel set to 260 StartFuel1, the control will increase the fuel quantity to
261 StartFuel2 for the time defined in 266 StartDuration2. This fuel quantity is
sustained until the engine starts off or cranking is aborted.
On reaching speed as set by 256 StartSpeed2, the control recognizes that the engine
is running. At this point, there is a change-over to the externally applied speed
setpoint 2031 SpeedSetp. The starting quantity, however, with which the engine had
started off, is sustained as a fuel limitation for the duration set by 251 LimitsDelay.
After that, the control passes over to using the governor's normal limiting functions.
Parameterizing Example:
The engine is supposed to start using the initially pre-defined maximum starting fuel
quantity of 60 %. At speeds of 10 rpm and higher the engine is to be recognized as
being cranked, and at a speed of 400 rpm as being running. If the engine is not
running after 3 seconds, the initially pre-defined maximum starting fuel quantity is
raised until it reaches a maximum starting fuel quantity of 90 % after further 7
seconds. The starting fuel quantity limitation stays on this level if the engine has not
started to run yet. Once the engine has started off, starting quantity limitation is
supposed to be active for 5 more seconds.
Number Parameter Value Unit
250 StartType 2
251 LimitsDelay 5 s
255 StartSpeed1 10 rpm
256 StartSpeed2 400 rpm
260 StartFuel1 60 %
261 StartFuel2 90 %
265 StartDuration1 3 s
266 StartDuration2 7 s
SPEED
[rpm]
Maximum speed
<12>
Set speed 1
<2031>
Speed range
of engine
Set speed
Minimum speed
<10>
Start speed 2
<256> Current speed
Start Speed 1
<255>
TIME [s]
ACTUATOR POSITION
[%]
Start fuel 2
<261>
Start fuel 1
<260>
TIME [s]
Phase 0 1 2 3 4 5,6,7
<3830>
ACTUATOR POSITION
[%]
Start Fuel 2
<261>
Start Fuel 1
<260>
Starting Temperature of cold Engine Starting Temperature of warm Engine TEMPERATURE [°C]
<271> <270>
As long as the cold engine's temperature is below 271 StartTempCold the starting
fuel quantity 261 StartFuel2 is released. As engine temperature increases, starting
fuel is decreased, until at the temperature set in 270 StartTempWarm the starting fuel
defined in 260 StartFuel1 is reached (see Figure 27: Temperature-dependent
Starting Fuel).
On attaining 255 StartSpeed1 the control will, as before, recognize that the engine is
being cranked, and on reaching 256 StartSpeed2 that the engine is running. At this
point, there is a change-over to the externally applied speed setpoint 2031 SpeedSetp
(see Figure 28: Temperature-dependent Starting Fuel Limitation). The starting
quantity, however, with which the engine had started off, is sustained as a fuel
limitation for the duration set by 251 LimitsDelay. After that, the control passes over
to using the control unit's normal limiting functions.
Parameterizing Example:
The engine is supposed to start at an engine temperature of -10 °C with temperature-
dependent maximum starting injection quantity of 70 %. If the engine temperature is
higher during start-up, the starting injection quantity is to be reduced accordingly. If,
however, engine temperature has already risen above 40 °C, starting fuel quantity is
no longer to be reduced, but to be held at 50 %. Furthermore, on reaching a speed of
10 rpm the engine is to be recognized as being cranked, and at 400 rpm as being
running. Once the engine has started off, starting quantity limitation is supposed to
be active for 5 more seconds.
Number Parameter Value Unit
250 StartType 3
251 LimitsDelay 5 s
THESEUS Installation & Commissioning Guide 103
7 Functions of DGM-02
SPEED
[rpm]
Maximum speed
<1 2>
Set speed 1
<2 031>
Speed range
of engine
Set speed
Minimum speed
<1 0>
Start speed 1
<2 55>
TIME [s]
ACTUATOR POSITION
[%]
Start fuel 2
<2 61>
Start fuel 1
<2 60>
TIME [s]
Phase 0 3 4 5,6,7
<3 830 >
When starting the engine now and on attaining speed 255 StartSpeed1, the control
recognizes that the engine is being cranked, and the speed setpoint is raised from
0 rpm to speed 257 StartSpeed3 (see Figure 29: Starting Behaviour when Starting
Speed Ramp is enabled). The parameterized speed must lie between the speed at
which the control recognizes that the engine is being cranked 256 StartSpeed2 and
the minimum speed 10 SpeedMin. If engine start-off is detected the speed setpoint is
increased by the ramping rate as pre-defined by 240 StartSpeedRampUp until the
externally applied speed setpoint is attained. Actual speed will follow these changes
of set speed.
The starting is independent of the normal 7.2.6 Speed Ramp. It is only used to start
the engine, and its priority is superior to that of the normal speed ramp. If both the
starting speed and the normal speed ramps are enabled, the set normal speed ramp
will remain inactive until after engine start the desired speed has been reached via the
starting speed ramp.
SPEED
[rpm]
Maximum speed
<12>
speed range
Speed setpoint 1
Engine
<2031>
Set speed
Minimum speed
<10>
Range for
Starting speed 3 starting speed 3
<257> <257>
Starting speed 2
<256>
Actual speed
Starting speed 1
<255>
TIME [s]
Parameterizing Example:
In addition to the settings in the preceding examples, the speed setpoint is to ramp
after start-off from 600 rpm to the externally applied setpoint by a ramping rate of
100 rpm/s. To achieve this, the following parameters must be additionally
programmed:
Number Parameter Value Unit
240 StartSpeedRampUp 100 rpm/s
257 StartSpeed3 600 rpm
4240 StartSpeedRampOn 1
ACTUATOR POSITION
[%]
100
90
80
70
60
50
40
30
20
10
Parameterizing Example:
Parameterization is to be made for a full-load characteristic consisting of 6 pairs:
Number Parameter Value Unit Number Parameter Value Unit
6700 SpeedLimit:n(0) 500 rpm 6750 SpeedLimit:f(0) 60 %
6701 SpeedLimit:n(1) 700 rpm 6751 SpeedLimit:f(1) 70 %
6702 SpeedLimit:n(2) 1100 rpm 6752 SpeedLimit:f(2) 80 %
6703 SpeedLimit:n(3) 1500 rpm 6753 SpeedLimit:f(3) 86 %
6704 SpeedLimit:n(4) 2100 rpm 6754 SpeedLimit:f(4) 82 %
6705 SpeedLimit:n(5) 2500 rpm 6755 SpeedLimit:f(5) 75 %
6706 SpeedLimit:n(6) 0 rpm 6756 SpeedLimit:f(6) 0 %
: : : : : :
6709 SpeedLimit:n(9) 0 rpm 6759 SpeedLimit:f(9) 0 %
Activation:
4700 SpeedLimitOn 1
For speeds below the first of the parameterized speed values, the control will limit
actuator travel to the first of the parameterized fuel values. Thus in the above
example, actuator travel is limited to 60 % for the range from 0 to 500 rpm.
Likewise, for speeds beyond the last of the parameterized speed values (in the above
example 2,500 rpm) actuator travel will remain limited to the last parameterized fuel
value (in the above example 75 %).
If this is not desirable, an additional pair of values should be programmed with the
fuel value set to 0 %. This will be a counterpart of the absolute limit line as known
from other controls (dashed line in Figure 30: Speed-dependent Fuel Limitation).
Number Parameter Value Unit Number Parameter Value Unit
6706 SpeedLimit:n(6) 2510 rpm 6756 SpeedLimit:f(6) 0 %
The parameter
2713 SpeedLimitActive = 0 Speed-dependent fuel limitation currently not
enabled
2713 SpeedLimitActive = 1 Speed-dependent fuel limitation currently
enabled
permits to check upon whether or not this limitation is currently in effect. The actual
limiting value is indicated by the parameter 2703 FuelLimitSpeed.
ACTUATOR POSITION
[%]
100
Lowering
by 2%
<701>
98
Activation:
4701 SpeedLimitTempOn 1
Skip paragraph, if your system does include the integrated speed governor
option. For set-up of a signal to a positioner, refer to 7.2 Integrated Speed
Governor.
For synchronization and load control, DGM-02 must be able to manipulate the generator
speed within a certain range around rated speed (usually +/-5 %). Therefore, the DGM-02
provides an offset or speed bias signal 12360 SpeedOffset, which can be sent to the speed
governor via several ways.
The speed offset value can also be filtered before transmission to the speed governor. The
filter value is adjusted with the parameter 10360 SpeedOffsetFilter. A value of "1" signifies
that there will be no filtering. The time constant of the filter can be derived by the
following equation:
filtering value
[ s]
64
AO5(200mA)
AO4(V/C)
AO2(V±)
GND
GND
OUT
OUT
OUT
0V
26 27 30 31 32 33
PE PE PE
The use and setting of the analogue outputs is described in detail in the chapter
6.6 Analogue Outputs. For the PWM outputs, see chapter 6.4 PWM Outputs. For
examples of the required settings, please refer to section 7.2.1 Setup of
Analogue/PWM Outputs for Fuel Actuator Position Setpoint.
Deviating from the settings described it is absolutely necessary in this case to assign the
offset signal for speed correction 12360 SpeedOffset to the parameters
1645 AnalogOut2_Assign, 1655 AnalogOut4_Assign, 1660 CurrentOut5_Assign or
1600 PWMOut1_Assign.
+24Vdc
Kdown K up
64 63
+24V +24V
DO9
DO8
Figure 33: Raise/Lower Signals to Speed Governor
The generation of the raise/lower signals which are transmitted to an external speed
governor for the pulse output to increase or decrease the speed are generated via a three-
step controller.
The setpoint for the three-step controller is the sum of the rated speed 17 SpeedRated
and the offset signal for the speed correction 12360 SpeedOffset. The actual value is the
speed 2000 Speed. Based on the comparison of setpoint and actual value the step
controller generates three conditions:
1) The difference between setpoint and actual value is within the dead band
10212 SpeedDeadBand, and no raise or lower signal is output.
12362 SpeedOffsetIncPulse = 0
12364 SpeedOffsetDecPulse = 0
2) The difference between setpoint and actual value is greater than zero and no longer
within the parameterized dead band. For the pulse time 10210 SpeedPulseHighTime
the three-step controller issues the raise signal, once the pulse time has elapsed the
no-pulse time 10211 SpeedPulseLowTime is issued, where the raise signal is
cancelled.
12362 SpeedOffsetIncPulse = 1/0
12364 SpeedOffsetDecPulse = 0
3) The difference between setpoint and actual value is smaller than zero and no longer
within the parameterized dead band. The three-step controller outputs the lower
signal for the parameterized pulse time. Once the pulse time has elapsed, there is a
no-pulse time, in which the lower signal is cancelled.
12362 SpeedOffsetIncPulse = 0
12364 SpeedOffsetDecPulse = 1/0
Parameterizing Example:
Within a dead band of +/-1 rpm no speed change is to be performed. The desired pulse-
pause-ratio is 2 seconds to 1 second. For the transmission to the speed governor, use
digital outputs 8 and 9 according to Figure 33: Raise/Lower Signals to Speed
Governor and Table 23: Raise/Lower Signals to Speed Governor.
Number Parameter Value Unit
10210 SpeedPulseHighTime 2.00 s
10211 SpeedPulseLowTime 1.00 s
10212 SpeedDeadBand 1.0 rpm
4800 DigitalOut9_PWMOrDO 0
8870 DigitalOut8:Par(0) 12362
8880 DigitalOut9:Par(0) 12364
AO1(IS-V±)
+
-
24 25
PE
AVR
The use and setting of the analogue outputs is described in detail in the chapter
6.6 Analogue Outputs.
Parameterizing Example:
The offset signal for voltage correction (indicator value 12380 AVROffset) is to be
transmitted to the AVR via an analogue connection. For this purpose, use the isolated
analogue output 1 according to Figure 34: Analogue Signal to AVR and Table 24:
Offset Signal Output to AVR. The offset signal has a value range of -100 % to 100 %.
Correspondingly, the output is to supply a voltage of -5 V to 5 V.
Number Parameter Value Unit
1640 AnalogOut1_Assign 12380
1641 AnalogOut1_RefLow 0.0 %
1642 AnalogOut1_RefHigh 100.0 %
1643 AnalogOut1_ValueMin 0.0 %
1644 AnalogOut1_ValueMax 100.0 %
Differing from the usual, the value range of -100 % to 100 % is to be mapped on an
output voltage of 0 V to 5 V. In this application, with an offset signal of 0 % a voltage
of 2.5 V is being output.
Number Parameter Value Unit
1641 AnalogOut1_RefLow 50.0 %
+24Vdc
Kdown K up
59 58
+24V +24V
DO4
DO3
The generation of the raise/lower signals which are transmitted to the AVR for the pulse
output to increase or decrease the voltage are generated via a three-step controller.
Based on the comparison of setpoint and actual value the three-step controller generates
three conditions:
1) The difference between setpoint and actual value is within the dead band
10232 AVR_DeadBand and no raise or lower signal is being output.
12382 AVROffsetIncPulse = 0
12384 AVROffsetDecPulse = 0
2) The difference between setpoint and actual value is greater than zero and no longer
within the parameterized dead band. For the pulse time 10230 AVR_PulseHighTime
the three-step controller issues the raise signal, once the pulse time has elapsed the
no-pulse time 10231 AVR_PulseLowTime is issued, where the raise signal is
cancelled again.
12382 AVROffsetIncPulse = 1/0
12384 AVROffsetDecPulse = 0
3) The difference between setpoint and actual value is smaller than zero and no longer
within the parameterized dead band. The three-step controller outputs the lower
signal for the parameterized pulse time. Once the pulse time has elapsed, there is a
no-pulse time, in which the lower signal is cancelled.
12382 AVROffsetIncPulse = 0
12384 AVROffsetDecPulse = 1/0
An exception is made for voltage matching during the synchronization process. The
voltage adjustment would be slowed down unsuitable if the dead band is used. For this
reason the three-step controller is used in this phase of operation as a pure two-step
controller by not considering the parameterized dead band.
Parameterizing Example:
Within a dead band of +/-0.5 % there should be no voltage change through the AVR.
The desired pulse-pause-ratio is 2 seconds to 0.5 seconds. For the transmission to the
AVR, use digital outputs 3 and 4 according to Figure 35: Raise/Lower Signals to AVR
and Table 25: Raise/Lower Signals to AVR.
Number Parameter Value Unit
10230 AVR_PulseHighTime 2.00 s
10231 AVR_PulseLowTime 0.50 s
10232 AVR_DeadBand 0.5 %
8820 DigitalOut3:Par(0) 12382
8830 DigitalOut4:Par(0) 12384
1 Pre Start
2 Crank
3 Ignition On
4 Fuel On
5 Speed Ramp Up
Stop
6 Speed Gonernor
GENERATOR
7 Sync 10 Sync
8 Min Load 11 Min Load
9 Load Ramp On 12 Load Ramp On Load
10 Load Control 13 Load Share
14 Single Island Un Load
11 Load Ramp Off 15 Load Ramp Off
16 Load Limit Un Sync
17 Sync To Mains
12 Cool Down
13 Fuel Off
14 Ingnition Off
15 Interlock
Generator phases:
Generator start:
Synchronization, loading with load ramp up to load setpoint or load sharing.
Generator stop:
Unloading with load ramp to minimum load, un-synchronizing and separation of
circuit breaker.
Engine stop phases:
Engine stop:
Cool down engine on rated speed or idle speed, and/or terminate diesel or gas
supply immediately and ignition off. The stop process is also controlled by various
timers.
Prevent any re-start before re-start timeout has elapsed.
All the actions of the start-stop sequence are triggered by switch functions or via
ARGOS operating functions which are converted into commands to "Start",
"Synchronize", "Load", "Unload", "Un-synchronize" and "Stop". The commands are
self-latching and will be carried out until the process has been successfully terminated
or a time-out has elapsed. The timeout causes an error message. The self-latching of
synchronization can be deactivated using 14322 SyncNoLatch.
The commands for the individual sequences are handled based on the following priority
scheme (see Table 26).
Decrease Increase
Priority
A call for any step of the sequence requiring other steps to be finished does
automatically initiate these steps.
Examples:
Synchronizing includes engine start, if engine is in standstill.
Loading includes synchronizing, if breaker is open.
A call for a step of the shutdown sequence overrules corresponding steps of the starting
sequence.
Examples:
Unloading cancels loading.
Un-sync cancels loading or synchronization, respectively.
22034 RelayIgnitionOn Diesel engines: not relevant during "wash out", cranking, running and
Gas engines: To release ignition cool down
22035 RelayFuelOn To release fuel supply during cranking, running and cool down
22036 RelaySyncOn To activate external synchronizer during synchronization
22037 RelayLoadOn To activate external load control while circuit breaker is closed and load
released
22038 RelayExcitationOn To release excitation of alternator at engine speeds above 90 % of rated
speed
22039 RelayIdleOn To activate the low idle speed when starting and before ending the
(minimum speed) operation of the engine
3802 EngineStopRequest Stop signal to external speed when engine shall be stopped
controllers or engine management
systems
The status of the mains circuit breaker is used as a basis for determining an information
about the operating mode (island or mains parallel). The operating mode effects on the
other hand the calculation of power setpoint value (see also 7.8.1 Generator in Island
or Mains Parallel Operation).
On the simply designed one-pole connection it is sufficient to connect one digital input
(see also 6.2 Digital Inputs) with a status contact of the circuit breaker, in the example
this is shown as a normally open (NO) contact (see Figure 37: Basic Connections for
Breaker Signals). The switch functions for open or closed status must be assigned in an
inverted manner.
+24Vdc
Kopen Kclose
57 56
+24V +24V
DO2
DO1
DI1
DI2
+24V 0V +24V 0V
34 35 36 37
MCBclosed
GCBclosed
+24Vdc
GND
Circuit Breaker Auxiliary Contacts
Parameterizing Example:
The status signals of the circuit breakers should be connected following Table 32:
Basic Connections for Breaker Signals. The transient recovery time of the relevant
measured variables provided after a status modification is one second.
Number Parameter Value Unit
810 FunctGCB_Closed 1
811 FunctGCB_Open -1
812 FunctMCB_Closed 2
813 FunctMCB_Open -2
10604 GCB_ChangeStateDecay 1.0 s
On the more complicated two-pole connection two digital inputs are connected with one
status contact, each, in our example a normally open (NO) contact, of the circuit breaker
(see Figure 38: Full Scope of Breaker I/Os).
The synchronization can be initiated without any connection taking place by using the
switch function 2824 SwGCB_Inhibit also shown in the following context. The voltage
and phase angle adjustment is maintained for an indefinite time up to the switch is reset
by readjustment. The synchronization check by the timer 22017 SyncTimer is also
stopped during this period.
+24Vdc
Kopen Kclose
92 91 90
57 56
DO13 COM
NO
NC
+24V +24V
DO2
DO1
DI1
DI2
DI5
DI3
DI4
+24V 0V +24V 0V +24V 0V +24V 0V +24V 0V
34 35 36 37 38 39 40 41 42 43
GCBclo sed
GCBop en
MCBclo sed
MCBop en
GCBInhi bit
+24Vdc
GND
Circuit Breaker Auxiliary Contacts Control Input
Parameterizing Example:
The status signals of the circuit breakers should be connected following Table 33:
Full Scope of Breaker I/Os. The circuit breakers need approx. 0.2 seconds to change
from an open to a closed status. The selected fly-time takes the future delays due to
aging into account. The transient recovery time of the relevant measured variables
provided after a status modification is one second, each.
Number Parameter Value Unit
810 FunctGCB_Closed 1
811 FunctGCB_Open 2
812 FunctMCB_Closed 3
813 FunctMCB_Open 4
824 FunctGCB_Inhibit 5
10601 GCB_FlyTime 0.40 s
10604 GCB_ChangeStateDecay 1.0 s
10621 MCB_FlyTime 0.40 s
10624 MCB_ChangeStateDecay 1.0 s
measured three-phase current (see also 6.8 Voltage, Current and Load
Measurement).
This additional information is used to determine the switching status, if the status
error message 13001 ErrGCB_Status is set. If a current greater than 1 % of the
nominal value is measured on all three phases the circuit breaker is to be accepted as
closed (12604 GCB_StateClosed = 1). Thus a generating set or also a Group-to-
Group and/or a Group-to-Mains unit remains completely in operation and available
despite the status error message.
Activation
14320 CB_OutPulsedOrPerman 0
Activation
14320 CB_OutPulsedOrPerman 0
When the circuit breaker is dynamically activated with pulsed signals two digital
outputs are supplied with signals to close (12602 GCB_RelayCloseOn) and open
(12603 GCB_RelayOpenOn). The pulse length of the signals is configured with the
parameter 10602 GCB_SwitchPulseLimit.
Parameterizing Example:
The generator circuit breaker is to be activated dynamically with pulse signals. The
pulses for closing and opening should last 0.4 seconds. Otherwise the same time
sequences as in the above example apply.
Number Parameter Value Unit
8800 DigitalOut1:Par(0) 12602
8810 DigitalOut2:Par(0) 12603
10601 GCB_FlyTime 0.5 s
10602 GCB_SwitchPulseLimit 0.4 s
Activation
14320 CB_OutPulsedOrPerman 1
Activation
14320 CB_OutPulsedOrPerman 1
The most reasonable and most commonly used version is a combination of a single
status signal from each circuit breaker and two pulsed signals to open and close the
breaker (see Figure 37: Basic Connections for Breaker Signals).
The following Figure 39 shows the type of action of the release relay with the pulsed
activation of the circuit breaker in a simplified way. As soon as a malfunction occurs
the main circuit of the breaker is opened.
L1
90
THESEUS
Terminals
Release Relay
Relay State ‘released’ 91
Circuit Breaker
Relay ‘Open’ with Lock Function
GCB State is opened Breaker State open
or closed
GCB
Relay ‘Close’
GCB State is opened
or closed N
G L1
DGM-02
L2 L3
3~
24V
Digital Out
<12495>
DGM-02
GCB L1
Power Busbar
L2
L3
L1 L2 L3
Power Busbar Mains Busbar
Local
Load
Mains Busbar
For the supplementary mains circuit breaker (MCB) is available only the dynamic
activation exclusively. Apart from that, the procedure of parameterization using the
parameters identified by MCB
10621 MCB_FlyTime Mains circuit breaker fly-time, time until
status change must have been carried out
10622 MCB_SwitchPulseLimit Pulse length of the output switching signals
12622 MCB_RelayCloseOn Signal to close
12623 MCB_RelayOpenOn Signal to open
is the same as described in section 7.6.2 Activation of the Circuit Breaker. The status
contacts of the mains circuit breaker are connected as described in section 7.6.1 Status
of the Circuit Breaker.
The operation is carried out via switch functions 2870 SwSyncToMains,
2871 SwOpenMainsCB and, if necessary 2872 SwMCB_Inhibit, which must be assigned
correspondingly. Very essential is the changeover of the voltage measuring input from
the busbar voltage to the mains busbar voltage. For this purpose, the status signal
12495 DblSyncAlternativeCB needs to be assigned to a digital output. The changeover
must be implemented by means of a relay. The complete functionality must be activated
via 14490 DblSync_OptionOn.
Proceeding from a generator which is run in single island mode a synchronizing
command to the mains is being used for switching over the voltage measuring input to
the mains voltage, with the switching input remaining set. The phase of generator
control branches into phase 17 which causes the 7.7 Synchronization of the generator
to the mains to start. The earliest connection is possible when the balancing conditions
have been obtained, depending on the time of occurrence (see also 7.13.2 Obligatory
and Optional Protections) and after the initializing time has expired
12491 DblSyncInitTimer, adjustable with parameter 10491 DblSyncInitTime.
After the connection has taken place, the two timers which perform identical functions
12493 DblSyncMaxParalTimr1 and 12494 DblSyncMaxParalTimr2, adjustable via
parameter 10493 DblSyncMaxParalTime1 and 10494 DblSyncMaxParalTime2, start to
run. Once the pre-set time has elapsed, the binary values which are indicated
12496 DblSyncMaxParalOver1 and 12497 DblSyncMaxParalOver2 are set for external
control purposes.
In order to take account of subsequent transient reactions and setting times when the
switching conditions of the circuit breaker are changed 12492 DblSyncDecayTimer,
adjustable via parameter 10492 DblSyncDecayTime, is used for suppressing the
monitoring routines.
7.7 Synchronization
Coupling generators in parallel can be implemented with various synchronization methods.
In any case the frequency, phase and voltage must be matching. The following deviations
before a connection in parallel are regarded as permissible:
Frequency deviation a max. 2 % from rated frequency,
Phase angle error is a max. +/-15° between the zero crossings of the voltages and
Potential difference a max. 10 % from rated voltage.
A detailed description of the built-in check and monitoring of the synchronous conditions
can be found in 7.13 Protections. The setting of the dynamics and optimization of
controller parameters is described in detail in chapter 8.2 Synchronizing Governor.
The assignment of the three-phase voltage terminals GEN and BUS to the CAN
terminals can be changed by using the parameter 14326 GENBusRefToCan2Or1. By
default the GEN terminals are being used for the busbar voltage of the generating sets,
whose CAN Bus is connected to CAN-1.
Parameterizing Example 1:
The group of generator sets whose CAN Bus is connected at CAN-1 is always named as
group 1. The busbar voltage of group 1 is connected to the GEN terminals. The
reference group should be the group 2 which is accordingly connected to CAN-2 and
the BUS terminals.
Number Parameter Value Unit
Indication:
2825 SwActOnGroup2Or1 0
Activation:
14326 GENBusRefToCan2Or1 0
Parameterizing Example 2:
The group of generator sets whose CAN Bus is connected at CAN-1 is always named as
group 1. The busbar voltage of group 1 is connected to the BUS terminals. Accordingly
the group 2 is connected to CAN-2 and the GEN terminals. The reference group should
be selectable with the switch function which is assigned to the digital input 10. The
group 1 should be the reference group with a high signal at the input, so the group 2 is
be controlled.
Number Parameter Value Unit
825 FunctActOnGroup2Or1 10
Indication:
2825 SwActOnGroup2Or1 0/1
Activation:
14326 GENBusRefToCan2Or1 1
After the synchronization the phase 11 "Minimum Load" is reached and the load is
controlled to the setpoint value 12331 LoadLimitMin which is similar to a lower
limitation of the power range. This value must be adjusted to a sufficient level using
parameter 10331 LoadMin to prevent the generator from being reverse powered, i.e. that
it will not be driven as an engine by other sources. On the other side, the value must be
small enough to ensure that no noticeable power contribution is generated.
Once a loading command has been carried out, phase 13 "Load Sharing" is obtained.
The load setpoint is determined dependent on the generator being operated in island
mode, e.g. together with another set, or if the generator is connected to the mains.
In mains parallel operation the base load value 12354 LoadSetpBaseLoad is to be used
as the setpoint value and the generator supplies a fixed power. The base load value can
be supplied from different sources (see Figure 41).
Forced Base
Yes No
Load?
<2823>
Setpoint
No Channel Yes
2 or 1?
<2873>
Analogue Analogue
Setpoint 1 No No Setpoint 2
available? available?
Yes Yes
<900> <905>
<12354>
The following Figure 42 shows how the load setpoint is determined in phase 13
"Load Sharing" of the generator control.
Automatic
Yes
Mode?
<3201>
Setpoint via
Yes No
PC?
<14020>
Mains Parallel
Yes No
Operation?
<12690>
Remote
Setpoint
activated?
Yes No
<2840> & <12691>
<12331> <12332>
<12352>
Load Ramp
activated?
Yes No
Load Setpoint
Ramp
<10332> <10333>
<12351>
Load Governor
The upper load limit can be set via 12332 LoadLimitMax. The setting options are
described in section 7.9 Load Limitation. In such a case of overload and limited
setpoint value the phase branches into phase 16 "Load Limitation" of the generator
control.
Parameter Meaning
Parameter Meaning
circuit breaker is controlled but the sum of the effective power produced by the entire
power plant, regardless of the instantaneous local load and the number of running
generators.
The gross load setpoint for the entire power plant is pre-set with the sensor value
2907 GrossLoadSetpoint. The operation mode is turned on in the Group-to-Mains
device with the switch function 2879 SwGrossLoadSetpOn. The sum of the currently
effective power produced by the entire power plant can be taken from the display
value 13500 LoadPlant_Total.
If there is no load limit, it is possible and also permissible to exceed the rated value limited
in time. In such cases, however, the generator temperature should be monitored with the
de-rating function which is activated via 14070 LoadDeRateTempOn. The load reduction is
entered as function of temperature into the curve starting at 17900 DeRateTemperature and
17920 DeRateMaxLoad.
THESEUS Installation & Commissioning Guide 145
7 Functions of DGM-02
A load limitation to defined values may be of advantage and can be implemented by pre-
setting via parameter or load limit adjuster.
A load limitation may also occur due to a fuel limitation at the speed governor for various
reasons. A message is issued as soon as it is connected via CAN.
Automatic
Yes
Mode?
<3201>
Circuit Breaker
No Yes
closed?
<12604>
Sync Mains Parallel
Yes No Yes
Command? Operation?
No
<22816> <12690>
Voltage
VAr Control PF Control
Balancing Yes Yes
activated? activated?
activated?
<10342> <10343>
<12375>
<12206> <12203>
y w off off w y
<12131>
y
No Generator Voltage
w
Governor
off
<12380> oder
<12382> <12384>
Parameter Meaning
Parameter Meaning
2838 SwPFDec Switch function: Decrease power factor setpoint
value via DOWN key
2839 SwAVRStandbyCtrl Switch function: Stand-by voltage control
2901 PFSetpoint External power factor setpoint pre-setting
(analogue setpoint value or via communication
module)
3201 GenCtrlAutoOrManual Indication automatic or manual mode of
operation
12111 VoltageBusRel_1_2 Relative voltage of busbar connected on the bus
end
12131 VoltageGenRel_1_2 Relative generator voltage
12203 cosPhi Current power factor
12206 PowerReactiveRelativ Current relative reactive generator power
12375 AVR_PFSetpSelect Selected power factor setpoint value
12604 GCB_StateClosed State circuit breaker closed
12661 Bus_DeadBars Indication dead busbar
12690 MainsParallel Indication mains parallel operation
13950 Load_kVAr_Total Plant average value of relative single reactive
power values
22816 CmdSyncActive Indication synchronization command active
14050 AVR_VoltMatchOn Activation of voltage balancing
14051 AVR_PFControlOn Activation of power factor control
14052 AVR_VARControlOn Activation of VAr control
14053 AVR_PFSetpFixedOrExt Selection: power factor setpoint value as fixed
value or external pre-setting
The setting of the dynamics and optimization of controller parameters is described in detail
in chapter 8.4 Voltage/VAr Governor.
DGM-IF01 and DGM-IF02 are isolated load share interfaces, which allow to connect to
analogue equipment from HEINZMANN or others, as long as the maximum voltage range
of the load share lines does not exceed 0…6 Vdc or -6…6 Vdc respectively.
65
AO3(V/C)
AI4(V)
+24V
DO10
GND
GND
OUT
+5V
IN
11 12 13 28 29
PE
+24Vdc
GND
The signal lines must be shielded up to the device connection. The signal lines
shielding have to be connected to protective earth (PE) at one point in the
switchgear cabinet or at the mounting plate.
Each interface needs one available analogue output and one available analogue input both
with a voltage range of 0…5V as well as one available digital output for connection to the
DGM-02 control unit. With the interface between DGM-02 and each load share line a
galvanic separation is realized as well as the conversion of the voltage levels to the level of
the load share line in the relationship 5 V to 6 V. Connection and disconnection on each
load share line takes place with the appropriate switching signal.
For the load share lines result ideal-prove the following voltage levels, whose setting is
supplemented and described in the following parameterizing example.
Table 38: Voltage Levels Analogue Active Load Sharing with DGM-IF01 / DGM-IF02
Parameterizing Example:
Parameterization has to be carried out according to Figure 44: Connection of Analogue
Load Share Interface DGM-IF01 / DGM-IF02 and Table 39: Analogue Active Load
Sharing by DGM-IF01 / DGM-IF02. To do so, the analogue output 3 is configured as
voltage output and the relative active generator power 12205 PowerRelative is assigned to
it as the load signal for the analogue load share line. Via analogue input 4 the load signal
from the analogue load share line is read in as a sensor value 2903 AnalogLSLineIn and is
1
is valid for applications with DGM-IF01
2
is valid for applications with DGM-IF02
used as the load setpoint. The required connecting signal 12480 RelayAnalogLSLineOn for
the load sharing relay is connected to digital output 10.
Since the range of the load measurement 12205 PowerRelative is -200 %…200 %, only the
upper half of this range must be scaled to the actual output to accommodate a ratio of
0…5 Vdc1 or 2.5…5 Vdc2 corresponding 0…200 % load.
Number Parameter Value Unit
903 AssignAnalogLSLineIn 4
1540 AnalogIn4_RefLow 0 / 327602
1
Table 40: Voltage Levels Analogue Reactive Load Sharing with DGM-IF02
Parameterizing Example:
Parameterization has to be carried out according to Table 41: Analogue Reactive Load
Sharing by DGM-IF02. To do so, the analogue output 4 is configured as voltage output and
the relative reactive generator power 12206 PowerReactiveRelativ is assigned to it as the
reactive load signal for the analogue load share line. Via analogue input 5 the reactive load
signal from the analogue load share line is read in as a sensor value
2906 AnalogVArSLineIn and is used as the reactive load setpoint. The required connecting
signal 12481 RelayAnlogVArSLineOn for the load sharing relay is connected to digital
output 9.
The range of the reactive load measurement 12206 PowerReactiveRelativ
is -200 %…200 % and corresponds to the entire range from capacitive and inductive
reactive power.
Number Parameter Value Unit
906 AssignAnalogVArSLIn 5
1550 AnalogIn5_RefLow 0
1551 AnalogIn5_RefHigh 65520
1655 AnalogOut4_Assign 12206
1656 AnalogOut4_RefLow 0.0 %
1657 AnalogOut4_RefHigh 100.0 %
1658 AnalogOut4_ValueMin 0.0 %
1659 AnalogOut4_ValueMax 100.0 %
5655 AnlogOut4_CurrOrVolt 0
8880 DigitalOut9:Par(0) 12481
Based on the applications of the THESEUS control unit both, the busbar at the BUS
measuring input (Generator-to-Busbar, Group-to-Group) and the busbar at the GEN
measuring input (Group-to-Group, Group-to-Mains) is continuously examined for the
"Dead Busbar" condition. Evaluation is carried out with regard to frequency = 0 Hz and
underflow of parameterized, permissible residual voltage by the measured voltage.
The confirmation for closing the circuit breaker is divided into an enable by switch input
and an automatic priority matching via CAN, if a CAN communication is possible. The
enabling through switch connection is a precondition for the priority matching and the
connection in general. Based on the application for this the following switch functions are
available:
2841 SwDeadBusClsConf close confirmation onto de-energized BUS
busbar and
2842 SwDeadGenClsConf close confirmation onto de-energized GEN
busbar.
The priority matching is automatically performed via CAN communication (see also
12.1.3 CAN Communication THESEUS with THESEUS) and is activated when at least
one THESEUS control unit receives a synchronization command. The activity of the
automatic priority matching can be seen from the displayed values
12611 GCB_DeadBusClsInit, 12612 GCB_DeadBusClsConf and 12613 GCB_DeadBusClosing.
The automatic priority matching can be disabled as needed for specific applications and
under certain conditions with the parameter 14610 DBCConfirmViaCanOn = 0.
A connection onto dead busbar always requires that the energized busbar is in relation to
the nominal frequency within the limits of +/-5 % for a generator application or +/-10 %
for a group application and in relation to the nominal voltage within the limits of +/-10 %.
In a Group-to-Group application may be the case that both busbars GEN and BUS are de-
energized. It may be the need on the one hand to allow an interconnection, or on the other
hand the requirement to exclude the connection. An appropriate setting can be made with
the parameter 14325 DeadToDeadBusbarOn. But the functionality still requires the
confirmation via switch function and the priority matching via CAN.
Of course, depending on the type of application a closing to the busbars of the voltage
sources, such as generator (Generator-to-Busbar) and mains (Group-to-Mains) is ruled out
by the firmware and non-existence of the corresponding switch inputs.
7.13 Protections
DGM-02 provides a wide range functions for standard generator set protection, which can
be used as a cost-efficient means of protecting small generators or as backup for separate
protection relays in bigger and more sophisticated applications.
The protections are designed in conformity with ANSI and G 59 standards.
Apart from the synchronization check (phase window and voltage matching), all in-built
protection relays are by default de-activated. Depending on the requirements of the
application, the customer can have some or all of them active as warnings (alarm) or circuit
breaker trips.
P / kW
Overload
Over
Over
phi
Curre
Curre
i
nt 2
nt 1
Q / kVAr
Reverse Power 1
Reverse Power 2
Loss of Excitation
Over Excitation
breaker. In case the alarm is configured to be a trip, it will trip the DGM-02's on-
board "Release" relay (see also 7.6.3 Release / Trip Relay) and activate the "Open
Breaker" signal 12603 GCB_RelayOpenOn instantaneously (see also
7.6.2 Activation of the Circuit Breaker).
Prot_Value
Prot_Hyst
Prot_triggd
(Err_Triggd)
Prot_trippd
(Err_Trip)
t/s
Prot_Timer (TRIP)
In order to set up a protective function with graded threshold values and different delay
times (low/long and high/short) the reverse power, as well as overcurrent functions are
double.
Parameter Meaning
Parameter Meaning
12800 VoltMatchTriggered Voltage differences are below the threshold
and thus within the accepted sync-window:
Synchronous condition "voltage matched"
triggered and delay time started
12850 VoltMatchLocked Voltage differences are still within the
accepted sync-window and delay time has
expired:
Synchronous condition "voltage matched"
locked to close the circuit breaker
automatically
Parameter Meaning
Parameter Meaning
Parameter Meaning
10702 ProtTimeOverLoad Delay time up to tripping error, if
protection as trip activated and
12802 OverLoadTriggered be set
10752 ProtValueOverLoad Threshold, trigger value
10802 ProtHystOverLoad Value of hysteresis
12702 ProtTimerOverLoad Indication of delay time
12802 OverLoadTriggered Relative power is above the threshold:
Overload protection triggered and delay
time started
12852 OverLoadTripped Protection still triggered and delay time has
expired:
Circuit breaker has tripped due to overload
13012 ErrOverLoadTrigger Warning indication that protection
triggered
13032 ErrOverLoadTrip Error indication that protection has tripped
14702 ProtOverLoadOn Activation of protection
14752 OverLoadTripOrWarn Selection of reaction at overload:
Protection trip or warning only
Parameter Meaning
Parameter Meaning
12853 RevPower1Tripped Protection still triggered and delay time has
12854 RevPower2Tripped expired:
Circuit breaker has tripped due to reverse
power stage 1 or stage 2
13013 ErrRevPower1Trigger Warning indication that protection
13014 ErrRevPower2Trigger triggered
13033 ErrRevPower1Trip Error indication that protection has tripped
13034 ErrRevPower2Trip
14703 ProtRevPower1On Activation of protection
14704 ProtRevPower2On
14753 RevPower1TripOrWarn Selection of reaction at reverse power:
14754 RevPower2TripOrWarn Protection trip or warning only
Parameter Meaning
Parameter Meaning
14755 OverExcitTripOrWarn Selection of reaction at over-excitation:
Protection trip or warning only
Parameter Meaning
Parameter Meaning
Parameter Meaning
10707 ProtTimeOverCurr1 Delay time up to tripping error, if
10708 ProtTimeOverCurr2 protection as trip activated and
12807 OverCurr1Triggered or
12808 OverCurr2Triggered be set
10757 ProtValueOverCurr1 Threshold, trigger value
10758 ProtValueOverCurr2
10807 ProtHystOverCurr1 Value of hysteresis
10808 ProtHystOverCurr2
12707 ProtTimerOverCurr1 Indication of delay time
12708 ProtTimerOverCurr2
12807 OverCurr1Triggered One 3-phase current is above the threshold:
12808 OverCurr2Triggered Overcurrent / time protection stage 1 or
stage 2 triggered and corresponding delay
time started
12857 OverCurr1Tripped Protection still triggered and delay time has
12858 OverCurr2Tripped expired:
Circuit breaker has tripped due to
overcurrent / time stage 1 or stage 2
13017 ErrOverCurr1Trigger Warning indication that protection
13018 ErrOverCurr2Trigger triggered
13037 ErrOverCurr1Trip Error indication that protection has tripped
13038 ErrOverCurr2Trip
14707 ProtOverCurr1On Activation of protection
14708 ProtOverCurr2On
14757 OverCurr1TripOrWarn Selection of reaction at overcurrent / time:
14758 OverCurr2TripOrWarn Protection trip or warning only
Parameter Meaning
Parameter Meaning
12809 SCCurrentTriggered One 3-phase current is above the threshold:
Overcurrent / instant (short circuit)
protection triggered and delay time started
12859 SCCurrentTripped Protection still triggered and delay time has
expired:
Circuit breaker has tripped due to
overcurrent / instant (short circuit)
13019 ErrSCCurrentTrigger Warning indication that protection
triggered
13039 ErrSCCurrentTrip Error indication that protection has tripped
14709 ProtSCCurrentOn Activation of protection
14759 SCCurrentTripOrWarn Selection of reaction at overcurrent / instant
(short circuit): Protection trip or warning
only
Parameter Meaning
Parameter Meaning
13020 ErrOverFreqTrigger Warning indication that protection
13021 ErrUnderFreqTrigger triggered
13040 ErrOverFreqTrip Error indication that protection has tripped
13041 ErrUnderFreqTrip
14710 ProtOverFreqOn Activation of protection
14711 ProtUnderFreqOn
14760 OverFreqTripOrWarn Selection of reaction at over- or under-
14761 UnderFreqTripOrWarn frequency: Protection trip or warning only
Parameter Meaning
Parameter Meaning
Parameter Meaning
Parameter Meaning
12814 OverROCOF_Triggered Rate of change of one frequency is above
the threshold:
Loss of mains protection due to excessive
RoCoF triggered and delay time started
12864 OverROCOF_Tripped Protection still triggered and delay time has
expired:
Circuit breaker has tripped due to excessive
RoCoF
13024 ErrOvrROCOF_Trigger Warning indication that protection
triggered
13044 ErrOverROCOF_Trip Error indication that protection has tripped
14714 ProtOverROCOF_On Activation of protection
14764 OverROCOF_TripOrWarn Selection of reaction at excessive RoCoF:
Protection trip or warning only
Parameter Meaning
Parameter Meaning
14715 ProtVectorShiftOn Activation of protection
14765 VectorShftTripOrWarn Selection of reaction at vector shift:
Protection trip or warning only
Table 56: Parameters for Loss of Mains Protection due to Vector Shift
Parameter Meaning
Parameter Meaning
Parameter Meaning
Parameter Meaning
12819 UnderCurrTriggered One 3-phase current is below the threshold:
Undercurrent protection triggered and
delay time started
12869 UnderCurrTripped Protection still triggered and delay time has
expired:
Circuit breaker has tripped due to
undercurrent
13029 ErrUnderCurrTrigger Warning indication that protection
triggered
13049 ErrUnderCurrTrip Error indication that protection has tripped
14719 ProtUnderCurrOn Activation of protection
14769 UnderCurrTripOrWarn Selection of reaction at undercurrent:
Protection trip or warning only
Parameter Meaning
Parameter Meaning
14768 PowrSupplyTripOrWarn Selection of reaction at power supply
deviation: Protection trip or warning only
Parameter Meaning
The temperature alarm thresholds are being set with the parameters
510 CoolantTempWarnLimit and 511 AuxCoolTempWarnLimit. The required
monitoring function must be activated in accordance with the parameters
4510 CoolantTempWarnOn and/or 4511 AuxCoolantTempWarnOn. If the current
coolant temperature or the current auxiliary coolant temperature exceeds the
corresponding alarm threshold, a warning message is output by setting the parameter
3032 ErrCoolantTempWarn = 1 and/or 3033 ErrAuxCoolTempWarn = 1. If the
temperature falls below the warning threshold by more than 5 °C the parameter is set to
0 again, and the error is cleared.
The temperature shutdown threshold is being set with the parameter
513 CoolantTempEcyLimit. If the monitoring function is activated by setting
4513 CoolantTempEcyOn the coolant temperature (2913 CoolantTemp) will be
monitored with respect to the shutdown threshold. If the shutdown threshold is
exceeded an emergency shutdown of the engine will be performed and indicated by the
parameter 3035 ErrCoolantTempEcy = 1. The beginning of the monitoring of the
coolant temperature shutdown can be delayed after the engine is started with the
parameter 512 CoolTempStartDelay.
Parameterizing Example:
The monitoring of the coolant temperature should provide a warning at 90 °C.
Number Parameter Value Unit
510 CoolantTempWarnLimit 90 °C
Indication
2913 CoolantTemp 90 °C
3032 ErrCoolantTempWarn 0/1
Activation
4510 CoolantTempWarnOn 1
Parameterizing Example:
Number Parameter Value Unit
520 OilTempLimit 90 °C
Indication
2911 OilTemp 90 °C
3034 ErrOilTempWarn 0/1
Activation
4520 OilTempWarnOn 1
Indication:
2916 ExhaustTemp 650 °C
3041 ErrExhaustTempWarn 0/1
Activation:
4515 ExhaustTempWarnOn 1
If oil pressure remains below the oil pressure warning characteristic for a period longer
than defined by 501 OilPressWarnDelay, a warning message will be output by the
parameter 3030 ErrOilPressWarn = 1. This oil pressure warning is automatically
cleared as soon as oil pressure returns to a value above the oil pressure warning
characteristic.
If oil pressure remains below the emergency stop characteristic for a period longer than
pre-set by 502 OilPressEcyDelay an engine emergency shutdown will be executed and
indicated by the parameter 3031 ErrOilPressEcy = 1.
The messages issued by the control are displayed by the following parameters:
3030 ErrOilPressWarn 0 = oil pressure above warning characteristic
1 = oil pressure below warning characteristic
3031 ErrOilPressEcy 0 = oil pressure above emergency stop
characteristic
1 = oil pressure below emergency stop
characteristic
The values for the oil pressure characteristics are stored at these parameter positions:
6500 to 6509 OilPressWarn:n(x): speed values for oil pressure warning curve
6520 to 6529 OilPressWarn:p(x): oil pressure values for oil pressure warning
curve
6550 to 6559 OilPressEcy:n(x): speed values for oil pressure emergency stop
curve
6570 to 6579 OilPressEcy:p(x): oil pressure values for oil pressure emergency
stop curve
Parameterization is to be conducted according to 3.7 Parameterization of
Characteristics. 10 pairs of values are available for each curve.
The characteristics are activated by setting the following parameters:
4500 OilPressWarnCurveOn = 1 for the oil pressure warning characteristic
4501 OilPressEcyCurveOn = 1 for the oil pressure emergency stop
characteristic.
OIL PRESSURE
[bar]
6
Normal working range
5
Warning characteristic
4
Emergency shutdown
Warning characteristic
3
Emergency shutdown
1
Parameterizing Example:
The oil pressure warning characteristic and the oil pressure emergency stop
characteristic are to be parameterized using 3 pairs of values for each. No monitoring is
provided below minimum speed of 700 rpm. This is achieved by setting the first values
of both characteristics to 0 bar. For values beyond the last parameterized speed value (in
this example index 3) the oil pressure value associated with this last value shall be
retained. Oil pressure monitoring is supposed to become active after a time delay of 45
seconds. When pressure has been below the oil warning characteristic for more than 3
seconds a warning is to be issued. If pressure remains below the oil pressure emergency
stop characteristic for more than 1 second, an emergency shutdown is to be executed.
Number Parameter Value Unit
500 OilPressStartDelay 45.0 s
501 OilPressWarnDelay 3.0 s
502 OilPressEcyDelay 1.0 s
Activation
4500 OilPressWarnCurveOn 1
4501 OilPressEcyCurveOn 1
6535
to 6539 CoolPressWarn:p(x): pressure values for coolant warning
characteristic (internal cooling circuit)
6540
to 6544 AuxCoolPrssWarn:n(x): speed values for auxiliary coolant warning
characteristic (external cooling circuit)
6545
to 6549 AuxCoolPrssWarn:p(x): pressure values for auxiliary coolant warning
characteristic (external cooling circuit)
Parameterization is to be conducted according to 3.7 Parameterization of
Characteristics. To parameterize the characteristics, 5 pairs of values are available for
each.
The characteristics are activated by setting the following parameters:
4505 CoolPressWarnCurveOn = 1 coolant pressure warning curve
4507 AuxCoolPrssWrnCrveOn = 1 auxiliary coolant pressure warning curve.
Parameterizing Example:
The coolant pressure monitoring should be active after a time delay of 20 seconds when
the engine is running. If the coolant pressure or the auxiliary coolant pressure falls
below its warning characteristic by more than 10 seconds the corresponding warning
indication should be issued.
The engine will run both at rated speed (1000 rpm) and at minimum speed (450 rpm)
for warm-up at low idle speed. The minimum allowable coolant pressure is be 1.8 bar in
the internal cooling circuit and 1.4 bar in the external cooling circuit at rated speed. A
value of 0.5 bar is be sufficient for both coolant pressures at minimum speed.
Number Parameter Value Unit
505 CoolPressStartDelay 20.0 s
506 CoolPressWarnDelay 10.0 s
Indication
2000 Speed 1000 rpm
2917 CoolantPressure 2.15 bar
2918 AuxCoolantPressure 1.90 bar
3044 ErrCoolantPressWarn 0/1
3046 ErrAuxCoolPressWarn 0/1
Activation
4505 CoolPressWarnCurveOn 1
4507 AuxCoolPrssWrnCrveOn 1
Indication
2919 FuelPressure 1.25 bar
3042 ErrFuelPressWarn 0/1
Activation
4530 FuelPressureWarnOn 1
is obtained again, for example by a re-fill, the warning is reset to 0 and the error is
cancelled.
The current coolant level is indicated via parameter 2914 CoolantLevel and the function
is activated via parameter 4525 CoolLevelWarnOn.
Parameterizing Example:
Number Parameter Value Unit
525 CoolLevelLowerLimit 75.0 %
526 CoolLevelUpperLimit 80.0 %
Indication
2914 CoolantLevel 90 %
3036 ErrCoolLevelWarn 0/1
Activation
4525 CoolLevelWarnOn 1
Indication:
2921 GenTempStator1 35.2 °C
2922 GenTempStator2 37.1 °C
2923 GenTempStator3 35.4 °C
3048 ErrGenTempWarn 0/1
Activation:
4540 GeneratorTempWarnOn 1
Parameter Meaning
Parameterizing Example:
The warning indication 13070 ErrLoadControlDiff is to be displayed in the case of a
lasting load offset of larger than 5 % and after 30 seconds. With a hysteresis of 1 % the
control deviation must become smaller than 4 % to be back in the acceptable range.
Number Parameter Value Unit
10740 ChckTimeLoadCtrlDiff 30.00 s
10790 ChkValueLoadCtrlDiff 5.0 %
10840 ChckHystLoadCtrlDiff 1.0 %
Activation
14740 ChckLoadCtrlDiffOn 1
Parameter Meaning
Parameter Meaning
14731 ChckLowLoadSw1On Activation of load switching points for low
14732 ChckLowLoadSw2On load
Parameter Meaning
3
Static Random Access Memory
7.16.1 Time
The real-time clock supplies the time (time stamp) when faults are recorded in the error
memory, as well as the current date and time for parameters indication. When the unit
leaves the factory, the clock is stopped. This is indicated by 3062 ErrRTCNotRunning.
The clock is set during the commissioning via 3.3 DcDesk 2000 by carrying out the
menu item "Control Unit / Real Time Clock Control Unit" by taking over the system
time of the computer.
7.16.3 Lifetime
As long as the device is alive the buffer battery is being saved and the lifetime of the
component, which is only limited due to the battery capacity, will be much higher than
the lifetime assured in the data sheet in power-off condition. It is specified to 7 years.
While the device is under voltage the only way to know the ageing condition of the
battery is to turn the unit off and on. This should be done at certain longer intervals
under operating conditions. If the battery's loading condition should be exhausted so far
that the error message 3061 ErrRTCBatteryLow is indicated, the component needs to be
replaced, because a long-term data retention will be jeopardized in off-load condition,
even if there is no urgency. However, the test does not give any evidence of the residual
load or the residual time of functioning.
The error message 3060 ErrRTCNotAvailable is shown when the component does no
longer respond. In this case, the cause will be a completely unloaded buffer battery if no
fault can be detected on the component placement.
Current
Skip paragraph, if your unit does not include the integrated speed governor
option. For dynamics adjustment procedure of external speed governors, refer
to separate instructions.
The structure of the integrated PID speed governor is comparable to other HEINZMANN
digital speed governors (please refer also to /1/ ARCHIMEDES – HELENOS - ORION –
PANDAROS – PRIAMOS, Digital Basic Systems, Control devices for conventional
injection with actuators, Manual No. DG 07 001-e). Therefore, test and adjustment of
dynamics is similar.
Make sure, the internal overspeed threshold (see also 6.7.4 Overspeed Monitoring),
parameter no. 21 SpeedOver, is set to a value of 5…15 % above rated engine speed
(according to supplied engine data).
After that, the engine is started and run up to the operating point where the setting has to
be made. This is usually the rated speed (17 SpeedRated) and the zero load condition.
Synchronization must be inhibited temporarily by selecting the manual mode (see also
7.1 Operating Mode Automatic or Manual). Please wait until the operating
temperature has been reached before making any setting. The PID parameters should be
optimized as follows:
Increase the P-factor 100 Gain by 1 % steps, until the engine tends to become
unstable (fast periodical speed changes). Then, decrease the P-factor again until the
speed oscillations disappear or are reduced to a moderate level.
Increase the I-factor 101 Stability until the engine passes over to long-waved speed
oscillations. Having reached the limit of stable operation, leave the setting as it is
and move on to the next step.
Increase the D-factor 102 Derivative until the speed oscillations disappear. If the
oscillations cannot be eliminated by the D-factor, the I-factor will have to be
reduced.
Try to avoid large Derivative values, for they may lead to excessive fuel actuator
drive current (causing vibrations and heat, reducing actuator lifetime). For
verification of suitable settings, check actuator movements (visually or by touching
the linkage; in case of EFI control, check deviation of fuel injection).
With these values set, disturb engine speed manually1 for a short moment and observe
the transient response. Continue to modify the PID parameters until the transient
response is satisfactory.
The fuel setpoint value as determined by the control circuit is indicated by the
parameter 2110 FuelSetpSpeedGov. This value is limited by 7.2.9 Fuel Limitation
Function and will then yield the fuel setpoint 2350 FuelQuantity.
Check load acceptance and load shed using a load bank or island load, if available.
Otherwise, go mains parallel and open the circuit breaker running at various load levels
starting at low load. Adapt PID values in order to meet specifications (speed, frequency,
time). If PID values are different from those found in idle operation, a PID map may be
required.
Although it is called PID map the correction will change only gain and
stability (P and I) parameters.
1
To disturb control:
push fuel linkage by hand (small engines),
apply load steps, if possible OR
apply speed steps by temporarily disadjusting rated speed 17 SpeedRated (small steps only!).
The values for the stability map are stored under the following parameter numbers:
6100 to 6109 PIDMap:n(x): Speed values for stability map
6150 to 6159 PIDMap:f(y): Fuel quantity values for stability map
6200 to 6299 PIDMap:Corr(z): Correction values for stability map.
Especially for gas engines it is not advisable to relate the PID map to fuel quantities
because of the gas pressure governor. In this case it is advisable to use the speed- and
power-dependent (12205 PowerRelative) PID map
6100 to 6109 PIDMap:n(x): Speed values for stability map
6350 to 6359 PIDMap:P(y): Power values for stability map
6200 to 6299 PIDMap:Corr(z): Correction values for stability map.
In case of general activation of the map with 4100 PIDMapOn = 1, the map type is
selected by
4101 PIDMapPowOrFuel = 0 dependent on speed and fuel quantity
4101 PIDMapPowOrFuel = 1 dependent on speed and power.
10 base points each are available for correction implying a maximum number of 100
correction values. A base point consists of a speed value and a fuel quantity value and
of the respective correction value. For adjacent correction values the intermediary
values are interpolated by the control. If PID correction is performed in dependence of
either speed or fuel quantity alone, any unused values must be set to zero (see also
3.8 Parameterization of Maps).
If the current working point of the engine lies outside the map as specified by the
mapping parameters, the control will calculate the value which is located on the border
of the map and take this as the associated correction value.
The actual correction value which is being used to correct the PID parameters with
regard to the current working point can be viewed by the parameter
2100 PID_CorrFactor. With this correction value the parameters 100 Gain for the P-
factor and 101 Stability for I-factor can be changed in per cent values and fed to the
control circuit. The stability map is activated by means of the parameter
4100 PIDMapOn.
In the examples below, correction of PID parameters will be explained using two
correction values for each case and correspondingly four values for the characteristic
map.
PID CORRECTION
VALUES Setting of PID values
(Correction value = 100)
Correction value
<6200>
Parameterizing Example:
Number Parameter Value Unit
6100 PIDMap:n(0) 700 rpm
6101 PIDMap:n(1) 1500 rpm
6102 PIDMap:n(2) 0 rpm
: : :
6109 PIDMap:n(9) 0 rpm
6150 PIDMap:f(0) 0 %
: : :
6159 PIDMap:f(9) 0 %
6200 PIDMap:Corr(0) 60 %
6201 PIDMap:Corr(1) 100 %
Activation
4100 PIDMapOn 1
PID CORRECTION
VALUES
Setting of PID values
(Correction Value = 100 %)
Correction value
<6201>
Correction
of values
PID value without
correction
<6200>
Parameterizing Example:
Number Parameter Value Unit
6100 PIDMap:n(0) 0 rpm
: : :
6109 PIDMap:n(9) 0 rpm
6150 PIDMap:f(0) 20 %
6151 PIDMap:f(1) 80 %
6152 PIDMap:f(2) 0 %
: : :
6159 PIDMap:f(9) 0 %
6200 PIDMap:Corr(0) 100 %
6210 PIDMap:Corr(10) 150 %
Activation
4100 PIDMapOn 1
Power
Figure 51: Performance Graph of Gas Engine in Dependence of Throttle Valve Position
With gas engines, it is of particular importance that PID correction be carried out in
dependence of load. The foregoing diagram Figure 51 depicts the performance
curve versus throttle valve position. The lower domain is characterized by a fast
increase of power output, while in the upper domain there is only a modest rise. For
optimum control, these facts must particularly be taken into account.
PID CORRECTION
VALUES Setting of PID values
(Correction Value = 100 %)
Correction value
<6 201>
Correction
of values
As explained in the previous section, adjustment of PID values is done for no-load
and correction for full-load. For a majority of applications, the inflexion points for
actuator travel can be set to 35 % and 60 %. It may, however, prove necessary to
readjust these values with regard to specific requirements.
Parameterizing Example:
Number Parameter Value Unit
6100 PIDMap:n(0) 0 rpm
: : :
6109 PIDMap:n(9) 0 rpm
6150 PIDMap:f(0) 35 %
6151 PIDMap:f(1) 60 %
6152 PIDMap:f(2) 0 %
: : :
6159 PIDMap:f(9) 0 %
6200 PIDMap:Corr(0) 100 %
6210 PIDMap:Corr(10) 200 %
Activation
4100 PIDMapOn 1
PID CORRECTION
VALUES
Parameterizing Example:
PID values in a range between 1495 rpm and 1505 rpm are to be reduced to 50 % of
their values, each. From 1490 rpm to 1495 rpm, as well as from 1505 rpm to 1510 rpm
linear interpolation of PID adaptation is carried out. Outside this speed range there will
be no lowering.
Number Parameter Value Unit
17 SpeedRated 1500 rpm
110 StaticCorrFactor 50 %
111 StaticCorrRange 5 rpm
Activation
4110 StaticCorrOn 1
Example:
Number Parameter Value Unit
10100 SyncGain 50.0 %
10103 SyncPFormat 11
the same
Number Parameter Value Unit
10100 SyncGain 25.0 %
10103 SyncPFormat 10
Parameter Meaning
10103 SyncPFormat 11
10104 SyncIFormat 9
10105 SyncDFormat 0
10106 FreqCtrlDevFormat 5
Adjustment procedure:
8) Increase 10100 SyncGain, if synchronization takes too long. Reduce parameter, if
synchronization is fast, but generator phase angle does not remain stable after matching
(fast changes).
9) Increase 10101 SyncStability, if generator phase angle takes too long to enter the
synchronous window. Decrease parameter value, if generator phase angle does not
remain stable after matching (slow changes). Modify 10102 SyncDerivative instead, if
sync time shall not be extended.
10) Use (increase) 10102 SyncDerivative, if generator phase angle is not stable, but
10101 SyncStability cannot be reduced (sync time extension). Otherwise leave
parameter value at 0 %.
11) For checking the settings abort the synchronizing process with the un-sync command
(2819 SwUnSyncRequest), then after the phases have gapped re-start with the
synchronizing command.
All required protection functions 7.13 Protections in particular the parameters for
monitoring the phase-angle adjustment (sync check) must be adjusted and activated before
releasing the circuit breaker (2824 SwGCB_Inhibit = 0).
Synchronizing a group of generator sets requires a DGM-02-GROUP unit. Its PID values
depend on the generating set group's structure and will be different from a single
generating set's DGM-02 PID settings.
Parameter Meaning
There are two ways to set up the load control function: island parallel and mains parallel
operation. At least one more running generating set is required for island parallel
operation. A load bank or a variable consumer up to at least 50 % load will be helpful in
island operation. These conditions are not necessary for mains parallel setup.
Be sure, synchronization is working properly (see also 7.7 Synchronization and
8.2 Synchronizing Governor) and 7.13 Protections are set and activated. Adjust load
ramp rates refer to 8.5 Ramps.
Run other generating set(s) with load (more than 50 % of the new generating set's
rated power).
Synchronize new generating set and go online.
Load new generating set up to 25 % by increasing the speed setpoint (+1 %).
Read actual load indication of DGM-02:
12208 PowerPrim for primary load readout to compare with an external/separate
load indication (which is known to be correct).
OR
Go online with 3.3 DcDesk 2000 and select the menu item "Graphic /
Generator management / Load mode / Effective power" to compare to
FLUKE-meter readings taken directly on the DGM-02's terminals.
In case of difference: check CT and VT wiring and DGM-02 settings.
Increase load up to 50 % and check again.
A temporary short-circuit of a single CT input must reduce the overall load
measured in DGM-02 by 33 % and the phase load of the according phase by
100 %. Otherwise, the VT and CT wiring order are to be checked.
Unload, un-sync the new generating set and stop the engine.
Set speed governor of new generating set back to 0 % droop.
2) Re-activate DGM-02 load control signal.
3) Start the engine and bring it to rated speed.
4) Select another generating set (or a group of sets) for island parallel load sharing.
5) Synchronize the new generating set and go parallel.
6) Check load sharing in DGM-02:
Go online with 3.3 DcDesk 2000 and select the menu item "Graphic / Generator
management / Load sharing". Generating sets sharing load are displayed in green
colour. The load distribution must be equal between the sets and stable.
7) If the new generating set is running stable, but does not reach equal power with the
other sets:
Increase the value of 10200 LoadGain, until the load sharing is correct.
8) If the load distribution is working, but unstable:
Reduce the value of 10200 LoadGain, until the load sharing is stabilized.
In island parallel operation, the dynamics of load sharing increase with the
number of on-line generators. Therefore, care must be taken when increasing
the value of parameter 10200 LoadGain for one generator and then copying
this setting to the others in the group.
9) If there is a remaining kW error or a load drift vs. time on the new generating set,
increase 10201 LoadStability, until the error is within an acceptable range, or the drift
is eliminated (n. a. in island parallel mode).
In isochronous load sharing, the integral part of the load control is only used
during ramping or while a load limitation is active. Therefore, care must be
taken when increasing the value of parameter 10201 LoadStability while the
generator is sharing load, since the changes will only take effect and can cause
instability, at the next ramping or load limitation.
For each of these three jobs a PID or only P controller is set up in DGM-02. They are
acting together in a proper way and adjust the generator's AVR by controlling its setpoint
value. The AVR being part of the generator is merely providing a basic voltage setting.
Depending on the signal transmission the voltage governor is either designed as a PID
controller (see also 7.4.1 Connection via Analogue Signal) or as a three-position
controller (see also 7.4.2 Connection via Raise/Lower Signals). For the reactive power
governor and power factor governor subordinated in the cascade structure the proportional
factor is the only setting option.
The following Table 69: Parameters Voltage and Reactive Load Governor includes the
parameters which are required for setting the PID values. The relation of prescalers and
corresponding factors is described in chapter 8.2 Synchronizing Governor.
Parameter Meaning
Make sure that the synchronizing of the phase (see also 7.7 Synchronization and
8.2 Synchronizing Governor) is working properly and the 7.13 Protections have been
adjusted and activated.
Preparation for setting the PID parameters of the voltage governor, when the generator's
AVR is influenced by an analogue offset signal:
1) If there are no voltage control PID values available from previous installations, set PID
parameters as follows before optimizing the first time:
Number Parameter Value Unit
10220 AVR_Gain 10.0 %
10221 AVR_Stability 5.0 %
10222 AVR_Derivative 0.0 %
10223 AVR_PFormat 8
10224 AVR_IFormat 5
10225 AVR_DFormat 0
In case of using digital outputs driving Raise/Lower signals for AVR manipulation,
prepare the setting of the pulse times in the following way:
1) If there are no pulse times for the voltage control available from previous installations,
set the parameters as follows before optimizing the first time:
Number Parameter Value Unit
10220 AVR_Gain 0.0 %
10230 AVR_PulseHighTime 0.50 s
10231 AVR_PulseLowTime 1.00 s
10232 AVR_DeadBand 0.0 %
factor correspondingly, in order to reduce the influence on the setpoint of the voltage
governor.
8.5 Ramps
Alternators and prime movers should be protected from sudden large speed and load
changes. Governor performance may also be optimized using speed and load setpoint
ramps with adjustable ramp rates.
Different values for the ramp speed upward and downward can be adjusted with the
DGM-02. In addition there is the possibility to select between two sets of parameters for
ramp speed values by using a switch function. The switch function
2877 SwLoadRamp2Or1 selects the load ramp values 10336 LoadRampUp2 or
10332 LoadRampUp1 for the upward ramp and 10337 LoadRampDown2 or
10333 LoadRampDown1 for the downward ramp.
The upward ramp can normally be faster, since the generator usually behaves more
stable, when taking on load. In turn, a slow downward ramp helps to avoid excessive
reactive current and load at minimum load. Moreover, some applications require
generators to be on load quickly, whereas unloading is not time critical at all.
If the DGM-02 is given a base load setpoint via binary speed raise/lower inputs, the
maximum ramping speed is the lower out of 10332 LoadRampUp1 /
10336 LoadRampUp2 and 10334 LoadStepMan or out of 10333 LoadRampDown1 /
10337 LoadRampDown2 and 10334 LoadStepMan respectively.
Parameterizing Example:
Both parameter sets for load ramp upward and downward are to be used. The parameter
set no. 2 is to make only short ramp times possible, in order to load up the generator
faster in critical situations. A change over switch is connected to digital input 6.
Number Parameter Value Unit
877 FunctLoadRamp2Or1 6
10332 LoadRampUp1 4.0 %/s
10333 LoadRampDown1 2.0 %/s
10336 LoadRampUp2 20.0 %/s
10337 LoadRampDown2 5.0 %/s
Activation
14030 LoadRampOn 1
9 Operation
be helpful. In turn, these settings may need decreasing, should the frequency tend to
become unstable at load changes.
A load limitation leading to insufficient running capacity of generating power
compared to the current electrical load.
While a sufficient number of engines are usually run to cover for the expected
demand, it is possible, that out of these some are limited to a certain maximum
power output below their rating (see also 7.9 Load Limitation). This fact may be
missed by supervisory controls or operators. These sets are sharing load up to the set
limit, but not above it. As long as there is still an adequate overall generating
capacity, an effect as described above for ramping may be noticed. If the applied
load is excess of the available power, a large frequency drop and/or installed
overload protections may indicate this situation.
9.2.1 Group-to-Group
The load sharing and VAr sharing of both groups is carried via two completely separate
electrical systems. These can either be analogue or CAN load sharing lines. Even with
both groups in parallel, these lines are not connected to each other. The advantages of
this principle are:
Faults in one side of the system do not affect the other side.
This allows a greater overall physical length of load sharing lines.
Groups can be cascaded one after another without limitation.
Proceeding from an island operation with two generator groups and two load sharing
lines via CAN Bus, one group is selected as the reference group by configuring the
respective other group to a controlled group. This is the group which the Group-to-
Group device will influence by the relevant control during synchronization and when
unloading the circuit breaker. This allows the controlled group, which is operated in
parallel under load, to be synchronized to the leading group and to be controlled after
the bus tie circuit breaker has been closed in such a way that the circuit breaker
continues to be wattless in phase 11 "Minimum Load".
Only after phase 13 "Load Sharing" is reached the control will be terminated, and the
group device is connecting crosswise to one side as another load sharing generator, with
the average values of the other side. Apart from that, the Group-to-Group control unit is
behaving absolutely passive in this operating phase.
9.2.2 Group-to-Mains
A Group-to-Mains device can control the energy flow in the overall system via the
circuit breaker to the grid. For this purpose it carries out the following jobs:
Synchronize generators and generator groups under load to the grid.
Control the mains circuit breaker wattless or unload it for opening.
Control the import or export of electrical power of a plant.
Pre-set a base load setpoint value for all the generators.
The Group-to-Mains device can make a connection to the grid even with the generators
in progress, both at the busbar section of the network access and at further busbar
sections which are connected via Group-to-Group sets by synchronizing all the
generators via the corresponding control to the reference of the grid frequency.
In the phase 11 "Minimum Load" the power is controlled to the adjusted minimum
value via the mains circuit breaker equivalent to the generator control.
After a command for loading and obtaining the phase 13 "Load Sharing" the switch
function 2840 SwBaseLdOrImpExp = 0 is usually used, dependent on the sign of the
adjusted import/export setpoint to control the power of the available generators in such
a way that the corresponding power flow will be achieved. In any case, the relation
THESEUS Installation & Commissioning Guide 213
9 Operation
between the capacity of the running generators and the existing local load should be
involved when setting the setpoint value.
As long as the running capacity due to an insufficient number of generators or a
generator load limitation is below the local demand the system runs in a base load-type
mode of operation with the peaks in load demand being covered by import. However, if
the running capacity is in excess of the local demand, the desired level of export can be
controlled through the group control unit provided that there is a sufficient spare
capacity.
It is also possible to limit the import to a maximum permissible value, e.g. in the sense
of peak shaving. A generator in stand-by would be limited to the minimum load until
the still admissible import value would be exceeded.
Finally, via 2840 SwBaseLdOrImpExp = 1 all the generators can be operated with a
fixed base load setpoint value, e.g. to support the grid during peak-load periods. The
setting is equivalent to the adjustment of the Generator-to-Busbar device.
After an unloading command, the circuit breaker is unloaded and a return to phase 11
"Minimum Load" is obtained. In this condition, the circuit breaker can be opened
mostly wattless.
For the power control via Group-to-Mains device to become effective, the switch
function 2840 SwSetpRemoteOrBaseLd = 1 must be activated in those generator control
devices which are to be remote controlled.
In the Group-to-Mains set the function 14312 PosMeasureImpOrExp can be used to
obtain a changeover of the agreed representation of the measured power values, i.e.
positive for import or export. This function is available for adapting the setpoint and
actual values to the external devices.
10 Sensors
In all HEINZMANN control units there is a strict distinction between analogue or PWM
inputs on one side and sensors on the other. This means that generator, engine or application
control is determined by the current values read by sensors, but where those sensors take their
values from is configured separately.
Parameterizing Example:
The signal for setpoint adjuster 1 is received from an analogue potentiometer, and setpoint
adjuster 2 is operating by a PWM signal. Oil pressure is received from a periphery module
via the HZM-CAN Bus.
Number Parameter Value Unit
4900 ChanTypPowerSetp1 0
4905 ChanTypPowerSetp2 1
4912 ChanTypOilPressure 2
Parameterizing Example:
Setpoint adjuster 1 (indication parameter 2900) is to be connected to analogue input 1,
setpoint adjuster 2 (indication parameter 2905) to PWM input 1, and the oil pressure sensor
(indication parameter 2912) to HZM-CAN periphery module input 3. For the other sensors
remaining unused the value 0 is to be entered.
Number Parameter Value Unit
900 AssignPowerSetpoint1 1
905 AssignPowerSetpoint2 1
912 AssignOilPressure 3
4900 ChanTypPowerSetp1 0
4905 ChanTypPowerSetp2 1
4912 ChanTypOilPressure 2
Parameterizing Example:
An oil pressure sensor with a measuring range from 0.5 bar to 3.5 bar.
Number Parameter Value Unit
988 OilPressSensorLow 0.5 bar
989 OilPressSensorHigh 3.5 bar
The below table lists both the parameters where the substitute values are stored and the
associated parameters for selecting operation by default value or by the last valid value.
For setpoint and sensor inputs, the parameters 5040 …HoldOrReset offer the option to
decide how the control is to react if an error clears itself (e.g. loose contact in wiring). If
the respective parameter is set to "1" the error will be regarded to be latching. Therefore,
there will be no reaction by the control when the sensor measurement is back within the
valid range. If the parameter is set to "0" the error will be reset and operation continues
using the signal coming from the sensor.
11 Switching Functions
In HEINZMANN control units a strict distinction is made between external switches and
internal switching functions. This means that generator, engine or application control is being
determined by the current values read by switching functions but where those switching
functions take their values from is configured separately.
Normally, they will be influenced by digital inputs but in specific applications they can be
assigned their values also by serial or CAN protocols. This is why it will be necessary to
configure the switching functions and to specify the sources they are receiving their actual
states from.
For each switching function there are up to four parameters defining the external source and
the current value. The last three digits of the four parameter numbers are identical for any one
specific switching function.
Parameters Meaning
810 Funct… Assigning a digital input number
(own hardware or HZM-CAN periphery module)
2810 Sw… Indication of current value of switching function
20810 Comm… Assigning an input number of a communication module
24810 ChanTyp… Assigning a channel type of the external source
For switching functions which respond to a pulse the switching pulse needs to
be a minimum 20 ms in order to be identified by the control circuit.
Parameterizing Example:
Closing the switch at input no. 8 is to initiate a changeover to manual mode. While the
switch is open, the device is in automatic mode. Closing the switch (at edge change) at
input no. 7 is to delete the current error messages.
Number Parameter Value Unit
828 FunctErrorReset 7
829 FunctAutoMode -8
830 FunctManualMode 8
Which switching functions are addressed by which bit of the communications telegrams is
determined by the manufacturer of the sending module and must be agreed with him. The
switching functions received from the communications module are then simply numbered
from "1" onwards and the respective number is entered in the assignment parameters
starting from 20810 Comm…. These assignment parameters are parallel to the indication
parameters for switching functions that start from 2810 Sw….
Assignment of "0" to 20810 Comm… means that the respective switching function is not
addressed by a communications module (but possibly by a digital input, see also
11.2 Assignment of Digital Inputs). For communication purposes, such a switching
function will always have the value "0".
For safety reasons, a function must be activated consciously via a communications module.
For this reason, the switching functions addressed by communications modules can be only
high-active, i.e. become active on receipt of a "1", as opposed to digital inputs (see also
11.2 Assignment of Digital Inputs). When the connection to the communication module
is interrupted, the switching function automatically adopts the value "0".
"Or" , where the expression preceding "Or" will be valid when the value of the switching
function is "1" and where the expression following "Or" will be valid when the switching
function has the value "0".
If no communication module is enabled in the current firmware, the value of the switching
function is determined exclusively by digital input. The parameters starting from
20810 Comm… and 24810 ChanTyp… do not exist.
If, on the other hand, a communication module must be taken into account, then each
switching function can be addressed either by a digital input or by the communications
module or even by both. This allows for instance local and remote control in parallel.
1. Digital input only
Parameter 20810 Comm… must be set to "0".
When 810 Funct… = 0, then the switching function always has the value "0",
otherwise it has the current value of the digital input (possibly with inverted
activity).
2. Communication module only
Parameter 810 Funct… must be set to "0" and 24810 ChanTyp… >= 3.
If 20810 Comm… = 0, then the switching function always has the value "0",
otherwise it has the current value of the received telegram. When the connection to
the communication module is interrupted, the switching function automatically
adopts the value "0".
3. Both digital input and communication module
Parameter 810 Funct… is not equal "0", 20810 Comm… is greater than "0" and
24810 ChanTyp… >= 3.
The current value from the digital input (possibly inverted) and from the
communications module are linked by OR. The switching function will therefore be
"0" only if both sources send the value "0"; it will be "1" if at least one source sends
the value "1". When the connection to the communication module is interrupted, the
switching function automatically adopts the value "0" for this transmission path. In
this case, the digital input alone decides on the overall value.
12 Bus Protocols
The THESEUS control unit has two integrated CAN interfaces and may be equipped
additionally with a plug-on extension which provides an RS 485 interface for Modbus
communication (RTU-Slave).
The first CAN port (CAN-1, isolated) is intended for the HEINZMANN-CAN protocol as a
standard, i.e. the communication with other HEINZMANN devices is usually carried out via
this port (see Figure 54).
The second CAN port (CAN-2) is generally meant for communicating with super ordinated
systems, in general with devices made by external manufacturers, which are responsible for
the control and monitoring of the entire plant. For ensuring the communication the different
kinds of standardized bus protocols (see Table 78) have been implemented, which can be
selected according to the variant being used (see also 4 Versions and Applications).
The Group-to-Group application is an exception. In this case the second CAN port is also
intended for the HEINZMANN-CAN protocol, in order to allow a communication with the
CAN Bus of the second Group to be performed.
CAN2_GND
CAN1_GND
55 54 53 52
HIGH
HIGH
LOW
LOW
CAN1(IS)
CAN2
Figure 54: CAN Connections
CR-01
CAN-2 High
GND CAN-2 Low
CAN-1 High
CAN-1 Low
CAN2_GND
CAN1_GND
55 54 53 52
HIGH
HIGH
LOW
LOW
CAN1(IS)
CAN2
The CAN-1 port is generally electrically isolated to ensure a high operating safety of the CAN
communication. Thereby ground loops with unwanted balancing currents and interference
potential can be avoided when the spatial mounting of the control units of the THESEUS
series is far away. The shield of the CAN-1 network cable is linked to the DGM-02 terminal
CAN1_GND as illustrated, and needs to be linked once with the PE in the network.
The CAN-2 port has no electrical isolation. In applications, where devices are connected to
the second CAN port over long distances or where devices are fed from different power
supplies, it is recommended to isolate the DGM-02 from the bus by using a CAN repeater
CR-01 (see Figure 55). It is particularly important to retain the galvanic separation by using
the CAN repeater, if the second CAN port is used for the Group-to-Group application.
Every independent CAN Bus must be closed at the two cable ends by means of a resistance
similar to the characteristic wave impedance of the line. With the "TERM." switch on every
THESEUS control unit a resistance of 120 ohms can be switched on for closing a line of a
common cable type for CAN-1 and CAN-2, respectively.
The shield of every line must be one-time connected to earth potential if the connected
devices have all a galvanic separation. If there are any devices clipped to the bus without
galvanic separation the shield may not be connected with potential earth (PE), but must be
connected to the terminal GND (0 V).
It is possible to have up to 31 devices of each type connected to the network. Their real
maximum number will in most cases depend on the network's capacity of utilization. Each
device of the same type is assigned a different node number. The device identifier (DC,
GC, ...) appears in all related parameter names.
In generator plants, every THESEUS control unit communicates with its speed governor
(GC DC), while the THESEUS control units are simultaneously doing the load sharing
(GC GC) and further THESEUS control units are responsible for the group and grid
functions (GC GC).
CAN communication to another device is established only if both the sending device
type and the receiving device type are enabled with all nodes required. Connections to
one of the diagnostic devices (device type PC) on the other hand are ready to receive at
all times.
4400 CanCommDCOn = 1 Device type speed governor enabled
4401 CanCommGCOn = 1 Device type THESEUS enabled
4406 CanCommCMOn = 1 Device type customer module enabled
The transmitter and receiver buffers are monitored for overrun for each device type and
indicated by the parameters 2401 CanTxBufferState and 2402 CanRxBufferState. The
messages must be received within a certain time window, otherwise the error
2403 CanRxTimeout will be set. The error 2404 CanTypeMismatch signals a
configuration fault due to a second participant with identical device number and
identical device type being connected to the network. If there is overrun of the
transmitter or receiver buffer, only this error will be indicated and communication
continues though one message or more might not have been sent or received. If due to
transmitter buffer overrun the messages could not be transmitted the opposite station
will signal the timeout error.
Generally, the error 2403 CanRxTimeout will be set whenever there is no answer from
the opposite station. Though in this event messages will continue to be transmitted to
the opposite station there will a change-over to certain emergency operations with
regard to content.
Especially for the Group-to-Group application of the GROUP variant the above
parameters are doubled and available separately for both CAN ports:
2401 Can1TxBufferState Status of transmit buffer per device type at
port 1
2402 Can1RxBufferState Status of receive buffer per device type at
port 1
2403 Can1RxTimeout Status of reception timeout monitoring per
device type at port 1
2404 Can1TypeMismatch Status of device type monitoring (double node
numbers) at port 1
2501 Can2TxBufferState Status of transmit buffer per device type at
port 2
2502 Can2RxBufferState Status of receive buffer per device type at
port 2
2503 Can2RxTimeout Status of reception timeout monitoring per
device type at port 2
2504 Can2TypeMismatch Status of device type monitoring (double node
numbers) at port 2
If the control device is generally prepared to communicate via one of the two CAN
ports will be shown in the parameters 2405 Can1_Online and 2407 Can2_Online.
no data is sent and/or will be sent after the logoff. Yet, data is perfectly received and the
CAN Bus is monitored in both operating conditions. The awake state is the condition
required for the system to be switched over to the automatic mode with the CAN
communication activated (see also 7.1 Operating Mode Automatic or Manual).
By setting the function parameter 4431 CanGCSetWakeUp from 0 to 1 or at edge
change (rising edge) of the switch function 2826 SwCanGCSetWakeUp the active CAN
communication is performed and consequently, also the change to the awake condition.
For going back to the sleep mode, set the function parameter 4432 CanGCSetSleep from
0 to 1 or at edge change (rising edge) of the switch function 2827 SwCanGCSetSleep.
The remaining bus nodes receive a log-off command and notice the termination of the
active CAN communication without any error message, instead of a node failure with
error message.
Via parameters 2412 CanGCRxOkNode31to16 and 2413 CanGCRxOkNode15to01 it
can be verified if the connection has been established. The bit which corresponds to the
node number of the THESEUS control unit is set while the connection is active.
Every active THESEUS control unit is transmitting the relative power data
12205 PowerRelative and 12206 PowerReactiveRelativ cyclically at short intervals to
all the other GC type bus nodes. These values are represented as a power image of the
total plant installation in the parameters 13901 Load_kW_Gen_1 ff. for the relative
active power and 13951 Load_kVAr_Gen_1 ff. for the relative reactive power.
During the real generator operation a process of rejections and permissions is taking
place among the devices on a bus whenever a circuit breaker closing to a non-energized
busbar is required (see also 7.12 Connection to Dead Busbar). This prevents any
simultaneous, un-synchronized connection.
for sensors and switching functions, the value "7" must be entered. The SAE-J1939
connection to HEINZMANN control devices is described extensively in the publication
/11/ SAE-J1939, Implementation, Manual No. DG 06 004-e.
For detailed information, error analysis and trouble-shooting instructions, please refer to
/7/, /8/ or /10/ respectively.
13 Data Management
The control provides various parameters for information on control device type, software
version, hardware version, etc.
14 Error Handling
14.1 General
The HEINZMANN digital controls of the THESEUS series provide an integrated error
monitoring system, distinguishing between two types of alarms, which are common (or
non-critical) and fatal (or critical). They can be issued via digital outputs (see also
6.3.2 Assignment of Indication Values to Digital Outputs) and linked with an optical or
acoustic signal. The alarms are usually output inverted (low-active, fail-safe) and
interpreted as "Healthy" signals which would also lead to alarm indications in case of
missing power supply or interrupted connections.
Besides, it is possible to make a first diagnosis via the two-digit 14.8 Seven-Segment
Display.
can be put into an error free state by a 3.10 Reset of Control Unit, but will immediately
begin to report any errors that are currently active.
+24Vdc
Alternative:
Indication Lamps
67 66
+24V +24V
DO11
DO12
Figure 56: Connections for Alarm Signals
When the parameter 5100 NoStoreSErrOn is set to "1" and the error memory
is then cleared, no errors will be stored in the error memory before the next
3.10 Reset of Control Unit. This feature is meant to provide the possibility of
shipping a control with customer specific data in an error-free state without
having to stimulate the inputs with the correct values. The parameter 5100
itself cannot be stored.
The entire boot loader tests and the subsequent initialization of the main
programme will take about 500 ms.
A configuration error can be deleted with the command "Clear error" but this does not
correct the cause of the error. Most configuration errors are checked only when the control
device starts. Therefore a reset will be necessary after the parameters have been changed
and saved in the control device.
The following tables give an overview of the error codes and their meaning. It depends on
the version of the control device software whether one of the mentioned communications
protocols is supported or less. In other words, not all the errors mentioned here will occur
in a specific control unit.
3000 ConfigurationError
Cause: - Configuration error.
Response: - Error message.
Action: - Check and correct control unit configuration, save parameters and reset
control unit.
Reference: 14.6 Configuration Errors
Response: with option 7.2 Integrated Speed Governor and without redundancy:
(4006 AlternatorSpeedOn = 0):
- Error message and emergency alarm (3800 EmergencyAlarm).
- Emergency shutdown1.
with option 7.2 Integrated Speed Governor and with redundancy:
(4006 AlternatorSpeedOn = 1):
- Error message and common alarm (3801 CommonAlarm).
- The current speed for the control is calculated from the frequency.
without above option:
- Error message and common alarm (3801 CommonAlarm).
- The current speed is calculated from the frequency, or the CAN speed is
used which is transmitted by the HEINZMANN speed governor.
Action: - Check distance between speed pickup and gear rim.
- Check preferred direction of pickup.
- Check cable to speed pickup.
- Check speed pickup, replace if necessary.
Reference: 6.7.3 Speed Pickup Monitoring
1
An emergency shutdown is always combined with the circuit breaker being tripped, by resetting the release for
the circuit breaker which causes the breaker to be opened immediately, as well as a request to stop the engine
(3802 EngineStopRequest).
3087 ErrMainCheckSum
Cause: - Check-sum of control programme is wrong.
Response: - Control unit cannot be put into operation.
Action: - Re-start control unit by a 3.10 Reset of Control Unit.
- Notify HEINZMANN.
Reference: 14.5.1 Boot Loader Starting Tests
Note: This error will only be displayed by the boot loader.
3089 ErrWatchdog
Cause: - Internal computing error, so-called "watchdog error".
Response: - Control unit cannot be put into operation.
- Emergency shutdown1.
for 3000…3099,
for 23000…23099.
The second sequence shows the last two digits of error numbers "00"…"99". If there is
more than one error at the same time, they will be displayed one by one, with the next error
numbers discriminated by the initial letter "c". If no error is active, the number "00" is
shown.
The points in the display are used to signalize the detection of a speed by the speed pickup
and of a frequency by the generator. Down on the right of the two digits of the display, a
point can be noticed when the engine is at a standstill. Once the control unit detects a speed
via a connected speed pickup, the left-hand point is turned off. The right-hand point is shut
off when a generator frequency is detected.
In the case of an exception error the values of the exception error parameter (3095 to 3099,
see also 14.7 Error Parameter List) are output on the display. Depending on the type of
fault it may happen that no communication is possible with the control unit. However, the
seven-segment display still allows to perform a certain diagnosis.
An "E" with one segment is followed by a number which corresponds to the
value of parameter 3095 ExceptionNumber.
15 Parameter Description
15.1 General
In the below Table 94: Parameter Groups the different parameter groups are listed in
adjacent columns. This table gives an overview as to which numeric ranges correspond to
which functions. In the following four chapters ( 15.2 List 1: Parameters, 15.3 List 2:
Measurements, 15.4 List 3: Functions, and 15.5 List 4: Curves) every single parameter
is listed along with a short description and a page reference to the respective chapters in the
manual.
For each parameter the defined level is indicated. Only such parameters are visible on a
servicing tool like DcDesk 2000 or a handheld programmer whose level is not high than
the one of the tool.
Parameters are marked by (RESET) which require a saving and a reset of the control unit
for activation after they were changed (see also 3.2 Saving Data and 3.10 Reset of
Control Unit).
If some parameters are valid only for a specific version of the THESEUS control unit, this
is indicated in italic type beside the parameter name with the corresponding designation
BASIC, MEDIUM, EXTENDED and GROUP (GROUP-TO-GROUP and GROUP-TO-
MAINS).
In the same place references to other manuals are indicated, if they contain a full
description of the respective parameters.
For characteristic curves and maps only the first field parameter is included and the
parameter numbers are indicated with the complement "ff" (and following).
Groups of parameters with the same name and subsequent numbering like
1510 AnalogIn1_RefLow, 1520 AnalogIn2_RefLow,… (lower reference for the respective
analogue input) are listed only under the first number with the complement "ff". The
number in the parameter name is substituted with "x" or "y".
Parameters are marked by the -symbol which effect the 13.4 Check-Sum over
Parameter Values of the Configuration.
100 Stability, Droop 2100 Stability, Droop 4100 Stability, Droop 6100 PID Map
(Speed Governor) (Speed Governor) (Speed Governor) (Speed Governor)
200 Ramp, Start 2200 4200 Ramp (Speed Governor) 6200 PID Map
(Speed Governor) (Speed Governor)
500 Oil Pressure, 2500 4500 Oil Pressure, Temperatures 6500 Oil Pressure Monitoring
Temperatures (Engine Control)
(Engine Control)
800 Switch Assignment, 2800 Switch Assignment, 4800 Digital Inputs, Digital 6800
Digital Outputs Digital Outputs Outputs
900 Setpoint Adjuster, 2900 Setpoint Adjuster, 4900 Setpoint Adjuster, Sensor 6900
Sensor Sensor
1000 Error Handling 3000 Current Errors 5000 Error Handling 7000
1500 Analogue Inputs 3500 Analogue Inputs 5500 Analogue Inputs 7500
1600 PWM Outputs, 3600 Internal Measurements 5600 Analogue Outputs 7600
Analogue Outputs
10200 Load, Power Factor, 12200 Power, Power Factor 14200 16200
Reactive Load Governor
10300 Voltage, Current, Power, 12300 Load, Synchronizing, 14300 Voltage, Current, GCB, 16300
Load, Power Factor Speed Offset, AVR Frequency, Synchronizing
10400 Double Synchronizing 12400 Load Sharing, VAr 14400 Double Synchronizing 16400
Sharing, Double
Synchronizing
10600 GCB, MCB, Load, 12600 GCB, MCB, Frequency, 14600 Generator Protections 16600
Power Factor Voltage, Synchronizing
Status
10700 Generator Protections, 12700 Generator Protections, 14700 Generator Protections, 16700
Load Switching Points Load Switching Points Load Switching Points
11700 Power Counter 13700 Power Counter, 15700 Operating Data 17700
Operating Data, Factory
Calibration Data
20000 Start-Stop Sequence 22000 Start-Stop Sequence 24000 Start-Stop Sequence 26000
29000 CANopen
29200 Modbus
29400 DeviceNet
29600 SAE-J1939
817 FunctLoadRequest
Level: 6 Switch assignment to function "Load Request"
Range: -12..12
Fixed for DGM-02-BASIC: 3
Page(s): 126
818 FunctUnLoadRequest
Level: 6 Switch assignment to function "Unload Request"
Range: -12..12
Fixed for DGM-02-BASIC: 4
Page(s): 126
819 FunctUnSyncRequest
Level: 6 Switch assignment to function "Un-sync Request"
Range: -12..12
Fixed for DGM-02-BASIC: 4
Page(s): 126
820 FunctStopRequest BASIC, MEDIUM, EXTENDED
Level: 6 Switch assignment to function "Engine Stop Request"
Range: -12..12
Fixed for DGM-02-BASIC: 4
Page(s): 124
821 FunctEmergencyStop
Level: 6 Switch assignment to function "Emergency Stop"
Range: -12..12
Page(s): 124
822 FunctForcedLoadLimit BASIC, MEDIUM, EXTENDED
Level: 6 Switch assignment to function "Forced Load Limit"
Range: -12..12
823 FunctForcedBaseLoad BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 6 Switch assignment to function "Forced Base Load"
Range: -12..12
824 Funct*CB_Inhibit
Level: 6 Switch assignment to function " Circuit Breaker Inhibit"
Range: -12..12 * = G: Generator (BASIC, MEDIUM, EXTENDED)
Fixed for DGM-02-BASIC: 5 * = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
825 FunctActOnGroup2Or1 GROUP-TO-GROUP
Level: 6 Switch assignment to function "Act on Group at CAN-2 or
Range: -12..12 Group at CAN-1"
826 FunctCanGCSetWakeUp
Level: 6 Switch assignment to function "CAN Communication for
Range: -12..12 Type GC Wake Up"
827 FunctCanGCSetSleep
Level: 6 Switch assignment to function "CAN Communication for
Range: -12..12 Type GC Set Sleep"
828 FunctErrorReset
Level: 6 Switch assignment to function "Error Reset"
Range: -12..12
Fixed for DGM-02-BASIC: 11
829 FunctAutoMode
Level: 6 Switch assignment to function "Auto Mode"
Range: -12..12
Fixed for DGM-02-BASIC: 12
830 FunctManualMode
Level: 6 Switch assignment to function "Manual Mode"
Range: -12..12
Fixed for DGM-02-BASIC: -12
831 FunctIdleSpeed BASIC, MEDIUM, EXTENDED
Level: 6 (only with speed governor option)
Range: -12..12 Switch assignment to function "Idle Speed"
832 FunctSpeedInc BASIC, MEDIUM, EXTENDED
Level: 6 (only with speed governor option)
Range: -12..12 Switch assignment to function "Speed Increment"
833 FunctSpeedDec BASIC, MEDIUM, EXTENDED
Level: 6 (only with speed governor option)
Range: -12..12 Switch assignment to function "Speed Decrement"
834 FunctForcedStart BASIC, MEDIUM, EXTENDED
Level: 6 (only with speed governor option)
Range: -12..12 Switch assignment to function "Forced Start"
835 FunctLoadInc BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 6 Switch assignment to function "Load Increment"
Range: -12..12
836 FunctLoadDec BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 6 Switch assignment to function "Load Decrement"
Range: -12..12
837 FunctPFInc BASIC, MEDIUM, EXTENDED
Level: 6 Switch assignment to function "Power Factor Increment"
Range: -12..12
838 FunctPFDec BASIC, MEDIUM, EXTENDED
Level: 6 Switch assignment to function "Power Factor Decrement"
Range: -12..12
839 FunctAVRStandbyCtrl BASIC, MEDIUM, EXTENDED
Level: 6 Switch assignment to function "AVR Voltage Stand-by
Range: -12..12 Control"
840 FunctRemoteOrBaseLd BASIC, MEDIUM, EXTENDED
Level: 6 Switch assignment to function "Remote or Base Load"
Range: -12..12
840 FunctBaseLdOrImpExp GROUP-TO-MAINS
Level: 6 Switch assignment to function "Base Load or Import/Export"
Range: -12..12
841 FunctDeadBusClsConf BASIC, MEDIUM, EXTENDED, GROUP-TO-GROUP
Level: 6 Switch assignment to function "Dead Bus Close
Range: -12..12 Confirmation"
842 FunctDeadGenClsConf GROUP
Level: 6 Switch assignment to function "Dead Gen Bus Close
Range: -12..12 Confirmation"
1512 AnalogInx_ErrorLow
ff. Level: 4 Low error limit of analogue input x
Range: 0..65520 x = 1…7
Page(s): 69, 69
1513 AnalogInx_ErrorHigh
ff. Level: 4 High error limit of analogue input x
Range: 0..65520 x = 1…7
Page(s): 69, 69
1514 AnalogInx_Filter
ff. Level: 4 Filter value of analogue input x
Range: 1..255 x = 1…7
Page(s): 68, 69
1582 TempIn1_ErrorLow
Level: 4 Low error limit of temperature input
Range: 0..65520
Page(s): 69, 70
1583 TempIn1_ErrorHigh
Level: 4 High error limit of temperature input
Range: 0..65520
Page(s): 69, 70
1584 TempIn1_Filter
Level: 4 Filter value of temperature input
Range: 1..255
Page(s): 68, 70
1600 PWMOutx_Assign
ff. Level: 4 Function assignment to PWM output x
Range: -29999..29999 x = 1…4
Page(s): 61, 111
1601 PWMOutx_RefLow
ff. Level: 4 Minimum value of PWM output x
Range: 0..100 % x = 1…4
Page(s): 62
1602 PWMOutx_RefHigh
ff. Level: 4 Maximum value at PWM output x
Range: 0..100 % x = 1…4
Page(s): 62
1603 PWMOutx_ValueMin
ff. Level: 4 Minimum value at PWM output x by per cent of value range
Range: 0..100 % of output parameter
Page(s): 61 x = 1…4
1604 PWMOutx_ValueMax
ff. Level: 4 Maximum value at PWM output x by per cent of value range
Range: 0..100 % of output parameter
Page(s): 61 x = 1…4
1625 PWMOutFrequency
Level: 6 Frequency of PWM outputs
Range: 128..500 Hz
Page(s): 62
1640 AnalogOut1_Assign
Level: 4 Function assignment to analogue output 1
Range: -29999..29999
Fixed for DGM-02-BASIC: 12380
Page(s): 72
1641 AnalogOut1_RefLow
Level: 4 Minimum value of analogue output 1
Range: 0..100 %
Page(s): 74
1642 AnalogOut1_RefHigh
Level: 4 Maximum value of analogue output 1
Range: 0..100 %
Page(s): 74
1643 AnalogOut1_ValueMin
Level: 4 Minimum value at analogue output 1 by per cent of value
Range: 0..100 % range of output parameter
Page(s): 73
1644 AnalogOut1_ValueMax
Level: 4 Maximum value at analogue output 1 by per cent of value
Range: 0..100 % range of output parameter
Page(s): 73
1645 AnalogOut2_Assign
Level: 4 Function assignment to analogue output 2
Range: -29999..29999
Fixed for DGM-02-BASIC: 12360
Page(s): 111
1646 AnalogOut2_RefLow
Level: 4 Minimum value of analogue output 2
Range: 0..100 %
1647 AnalogOut2_RefHigh
Level: 4 Maximum value of analogue output 2
Range: 0..100 %
1648 AnalogOut2_ValueMin
Level: 4 Minimum value for analogue output 2 by per cent of value
Range: 0..100 % range of output parameter
1649 AnalogOut2_ValueMax
Level: 4 Maximum value at analogue output 2 by per cent of value
Range: 0..100 % range of output parameter
1650 AnalogOut3_Assign
Level: 4 Function assignment to analogue output 3
Range: -29999..29999
Fixed for DGM-02-BASIC: 12205
1651 AnalogOut3_RefLow
Level: 4 Minimum value of analogue output 3
Range: 0..100 %
1652 AnalogOut3_RefHigh
Level: 4 Maximum value of analogue output 3
Range: 0..100 %
1653 AnalogOut3_ValueMin
Level: 4 Minimum value for analogue output 3 by per cent of value
Range: 0..100 % range of output parameter
1654 AnalogOut3_ValueMax
Level: 4 Maximum value at analogue output 3 by per cent of value
Range: 0..100 % range of output parameter
1655 AnalogOut4_Assign
Level: 4 Function assignment to analogue output 4
Range: -29999..29999
Page(s): 111
1656 AnalogOut4_RefLow
Level: 4 Minimum value of analogue output 4
Range: 0..100 %
1657 AnalogOut4_RefHigh
Level: 4 Maximum value of analogue output 4
Range: 0..100 %
1658 AnalogOut4_ValueMin
Level: 4 Minimum value for analogue output 4 by per cent of value
Range: 0..100 % range of output parameter
1659 AnalogOut4_ValueMax
Level: 4 Maximum value at analogue output 4 by per cent of value
Range: 0..100 % range of output parameter
1660 CurrentOut5_Assign
Level: 4 Function assignment to analogue output 5
Range: -29999..29999
Fixed for DGM-02-BASIC: 12360
Page(s): 73, 111
1661 CurrentOut5_RefLow
Level: 4 Minimum value of analogue output 5
Range: 0..100 %
Page(s): 74
1662 CurrentOut5_RefHigh
Level: 4 Maximum value of analogue output 5
Range: 0..100 %
Page(s): 74
1663 CurrentOut5_ValueMin
Level: 4 Minimum value for analogue output 5 by per cent of value
Range: 0..100 % range of output parameter
Page(s): 73
1664 CurrentOut5_ValueMax
Level: 4 Maximum value at analogue output 5 by per cent of value
Range: 0..100 % range of output parameter
Page(s): 73
1800 Level
Level: 1 User level
Range: 1..7
Page(s): 26
1876 ValueStep (Only for handheld programmer)
Level: 2 Step width of value changes
Range: 0..65535
10001 FrequencyNominal
Level: 4 Rated frequency
Range: 45..65 Hz
Page(s): 83, 252
10002 SyncCheckFreqDiff
Level: 4 Allowed frequency difference during synchronization process
Range: 0..100 Hz
Page(s): 137
10100 SyncGain
Level: 2 Gain for synchronization
Range: 0..100 %
Page(s): 196, 197
10101 SyncStability
Level: 2 Stability for synchronization
Range: 0..100 %
Page(s): 196, 197
10102 SyncDerivative
Level: 2 Derivative for synchronization
Range: 0..100 %
Page(s): 196, 197
10103 SyncPFormat
Level: 6 Adjustment factor for synchronization gain (decrease by "1"
Range: 0..16 to double the effect of the 10100 SyncGain setting)
Page(s): 196
10104 SyncIFormat
Level: 6 Adjustment factor for synchronization stability (decrease by
Range: 0..16 "1" to double the effect of the 10101 SyncStability setting)
Page(s): 196
10105 SyncDFormat
Level: 6 Adjustment factor for synchronization derivative (decrease
Range: 0..16 by "1" to double the effect of the 10102 SyncDerivative
Page(s): 196 setting)
10106 FreqCtrlDevFormat
Level: 6 Normalization of the frequency control deviation (100 %
Range: 1..5 control deviation correspond to 1…5 Hz)
Page(s): 196
10200 LoadGain
Level: 2 Gain for load control
Range: 0..100 %
Page(s): 198, 200, 209
10201 LoadStability
Level: 2 Stability for load control
Range: 0..100 %
Page(s): 198, 201, 209
10202 LoadDerivative
Level: 2 Derivative for load control
Range: 0..100 %
Page(s): 198, 201
10203 LoadPFormat
Level: 6 Adjustment factor for load control gain (decrease by "1" to
Range: 0..16 double the effect of the 10200 LoadGain setting)
Page(s): 198
10204 LoadIFormat
Level: 6 Adjustment factor for load control stability (decrease by "1"
Range: 0..16 to double the effect of the 10201 LoadStability setting)
Page(s): 198
10205 LoadDFormat
Level: 6 Adjustment factor for load control derivative (decrease by "1"
Range: 0..16 to double the effect of the 10202 LoadDerivative setting)
Page(s): 198
10206 LoadStabFadeGain BASIC, MEDIUM, EXTENDED
Level: 6 Gain for rate of reduction of stability part of load control after
Range: 0..100 % de-activation (e.g. at change from ramping or mains parallel
Page(s): 198 to island parallel)
10210 SpeedPulseHighTime BASIC, MEDIUM, EXTENDED
Level: 2 Pulse duration for speed setpoint manipulation by raise/lower
Range: 0..100 s signals
Page(s): 112
10211 SpeedPulseLowTime BASIC, MEDIUM, EXTENDED
Level: 2 Pulse break for speed setpoint manipulation by raise/lower
Range: 0..100 s signals
Page(s): 112
10212 SpeedDeadBand BASIC, MEDIUM, EXTENDED
Level: 2 Dead band of speed deviation, if deviation within dead band
Range: 0..2000 1/min around the rated speed no raise/lower signals will be
Page(s): 112 generated
10220 AVR_Gain
Level: 2 Gain for AVR offset signal control
Range: 0..100 %
Page(s): 203, 204
10221 AVR_Stability
Level: 2 Stability for AVR offset signal control
Range: 0..100 %
Page(s): 203, 205
10222 AVR_Derivative
Level: 2 Derivative for AVR offset signal control
Range: 0..100 %
Page(s): 203, 205
10223 AVR_PFormat
Level: 6 Adjustment factor for AVR gain (decrease by "1" to double
Range: 0..16 the effect of the 10220 AVR_Gain setting)
Page(s): 203
10224 AVR_IFormat
Level: 6 Adjustment factor for AVR stability (decrease by "1" to
Range: 0..16 double the effect of the 10221 AVR_Stability setting)
Page(s): 203
10225 AVR_DFormat
Level: 6 Adjustment factor for AVR derivative (decrease by "1" to
Range: 0..16 double the effect of the 10222 AVR_Derivative setting)
Page(s): 203
10230 AVR_PulseHighTime BASIC, MEDIUM, EXTENDED
Level: 2 Pulse duration for AVR manipulation by raise/lower signals
Range: 0..100 s
Page(s): 116, 205
10231 AVR_PulseLowTime BASIC, MEDIUM, EXTENDED
Level: 2 Pulse break for AVR manipulation by raise/lower signals
Range: 0..100 s
Page(s): 116, 205
10232 AVR_DeadBand BASIC, MEDIUM, EXTENDED
Level: 2 Dead band AVR deviation, if deviation within dead band
Range: 0..200 % around the rated voltage no raise/lower signals will be
Page(s): 115, 205 generated
10240 PF_Gain BASIC, MEDIUM, EXTENDED
Level: 2 Gain for power factor control
Range: 0..100 %
Page(s): 203, 205
10243 PF_PFormat BASIC, MEDIUM, EXTENDED
Level: 6 Adjustment factor for power factor gain (decrease by "1" to
Range: 0..16 double the effect of the 10240 PF_Gain setting)
Page(s): 203
10250 VAR_Gain BASIC, MEDIUM, EXTENDED
Level: 2 Gain for reactive load control (VAr sharing)
Range: 0..100 %
Page(s): 203, 205
10253 VAR_PFormat BASIC, MEDIUM, EXTENDED
Level: 6 Adjustment factor for reactive load gain (decrease by "1" to
Range: 0..16 double the effect of the 10250 VAR_Gain setting)
Page(s): 203
10300 PT_Ratio
Level: 6 Transformation ratio of voltage phase transformers
Range: 1..500
Fixed for DGM-02-BASIC and DGM-
02-MEDIUM: 1
Page(s): 83
10301 VoltHarmonics_Filter
Level: 6 Filter value of 3-phase voltage inputs
Range: 1..3
Page(s): 88
10302 PT_RatioBUS EXTENDED, GROUP-TO-MAINS
Level: 6 Transformation ratio of voltage phase transformers at BUS
Range: 0..500 terminals
Page(s): 85 0: 10300 PT_Ratio will be used
10305 ExternalPhaseDiff EXTENDED, GROUP-TO-MAINS
Level: 6 Compensation value for an external phase difference between
Range: -180..180 °el GEN and BUS terminal voltage
Page(s): 138
10310 CT_Ratio
Level: 6 Transformation ratio of current transformers
Range: 1..7500
Page(s): 86
10311 CurrHarmonics_Filter
Level: 6 Filter value of 3-phase current inputs
Range: 1..3
Page(s): 88
10321 VoltageRated
Level: 1 Rated voltage at primary side
Range: 0..60000 V
Page(s): 83, 147
10322 CurrentRated
Level: 1 Rated current at primary side
Range: 0..10000 A
Page(s): 86
10323 VoltageRatedBUS
Level: 1 Rated voltage at primary side at BUS terminals
Range: 0..60000 V 0: 10321 VoltageRated will be used
Page(s): 85
10330 LoadRated
Level: 2 Rated effective (kW) load at primary side
Range: 0..30000 kW
Page(s): 86, 97
10331 LoadMin
Level: 4 Minimum load for load setpoint range
Range: -200..200 % (min. load setting after breaker closure; breaker opening
Page(s): 141, 144 threshold after ramp down)
10332 LoadRampUp1
Level: 4 Change rate for upward load ramp, if
Range: 0..200 %/s 2877 SwLoadRamp2Or1 = 0
Page(s): 207, 209, 268 (load increase per second, parameter set 1)
10333 LoadRampDown1
Level: 4 Change rate for downward load ramp, if
Range: 0..200 %/s 2877 SwLoadRamp2Or1 = 0
Page(s): 207, 209, 269 (load decrease per second, parameter set 1)
10334 LoadStepMan BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 4 Alteration rate of load setpoint when using load
Range: 0..200 %/s increase/decrease switches
Page(s): 142, 207
10336 LoadRampUp2
Level: 4 Change rate for upward load ramp, if
Range: 0..200 %/s 2877 SwLoadRamp2Or1 = 1
Page(s): 207, 268 (load increase per second, parameter set 2)
10337 LoadRampDown2
Level: 4 Change rate for downward load ramp, if
Range: 0..200 %/s 2877 SwLoadRamp2Or1 = 1
Page(s): 207, 269 (load decrease per second, parameter set 2)
10604 *CB_ChangeStateDecay
Level: 6 Time during which effects of circuit breaker status change are
Range: 0..1000 s tolerated (e.g. build-up of voltage readings after closure onto
Page(s): 127 dead bars)
* = G: Generator (BASIC, MEDIUM, EXTENDED)
* = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
10621 MCB_FlyTime BASIC, MEDIUM, EXTENDED
Level: 6 Mains circuit breaker fly-time, time until status change must
Range: 0..100 s have been carried out (Double synchronization: total of signal
Page(s): 127, 135, 263 travel to mains circuit breaker, needed time for status change
and signal travel of feedback)
10622 MCB_SwitchPulseLimit MEDIUM, EXTENDED
Level: 6 Double synchronization: Pulse length for activation of the
Range: 0..100 s mains circuit breaker
Page(s): 135, 263
10624 MCB_ChangeStateDecay BASIC, MEDIUM, EXTENDED
Level: 6 Time during which effects of mains circuit breaker status
Range: 0..1000 s change are tolerated (e.g. build-up of voltage readings after
Page(s): 127 closure onto dead bars)
10630 AutoResyncLockTime GROUP-TO-MAINS
Level: 6 Hold Off time for re-synchronization interlock after mains
Range: 0..1000 s are re-established
Page(s): 140
10651 LoadSetpointPC BASIC, MEDIUM, EXTENDED
Level: 4 Load setpoint set by PC (for manual load adjustment via
Range: 0..200 % DcDesk 2000)
Page(s): 142, 202
10652 BaseLoadForced BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 4 Fixed load setpoint for base load operation (to be activated by
Range: 0..200 % 2823 SwBaseLoadForced)
Page(s): 143
10653 LoadLimitForced BASIC, MEDIUM, EXTENDED
Level: 4 Fixed load limitation setpoint for switchable load limit (to be
Range: 0..200 % activated by 2822 SwLoadLimitForced)
Page(s): 145
10654 ImpExpSetpointFix GROUP-TO-MAINS
Level: 4 Fixed import/export setpoint (if sensor for import/export
Range: -30000..30000 kW setpoint not assigned)
Page(s): 144
10660 AVR_PFForced BASIC, MEDIUM, EXTENDED
Level: 4 Fixed power factor setpoint for mains parallel operation
Range: 0..1 without setpoint input (to be activated by
Page(s): 147 14053 AVR_PFSetpFixedOrExt)
10700 ProtTimeVoltMatch
Level: 6 Delay or holding time for the synchronous condition "voltage
Range: 0..100 s matched"
Page(s): 138, 158
10701 ProtTimeSyncCheck
Level: 6 Delay or holding time for the synchronous condition "phase
Range: 0..100 s matched"
Page(s): 137, 159
10702 ProtTimeOverLoad
Level: 6 Delay time for overload protection
Range: 0..100 s
Page(s): 160
10703 ProtTimeRevPower1
Level: 6 Delay time for reverse power protection stage 1
Range: 0..100 s
Page(s): 160
10704 ProtTimeRevPower2
Level: 6 Delay time for reverse power protection stage 2
Range: 0..100 s
Page(s): 160
10705 ProtTimeOverExcit
Level: 6 Delay time for over-excitation protection
Range: 0..100 s
Page(s): 161
10706 ProtTimeExcitLoss
Level: 6 Delay time for excitation loss protection
Range: 0..100 s
Page(s): 162
10707 ProtTimeOverCurr1
Level: 6 Delay time for overcurrent / time protection stage 1
Range: 0..100 s
Page(s): 163
10708 ProtTimeOverCurr2
Level: 6 Delay time for overcurrent / time protection stage 2
Range: 0..100 s
Page(s): 163
10709 ProtTimeSCCurrent
Level: 6 Delay time for overcurrent / instant (short circuit) protection
Range: 0..100 s
Page(s): 163
10710 ProtTimeOverFreq
Level: 6 Delay time for over-frequency protection
Range: 0..100 s
Page(s): 164
10711 ProtTimeUnderFreq
Level: 6 Delay time for under-frequency protection
Range: 0..100 s
Page(s): 164
10712 ProtTimeOverVolt
Level: 6 Delay time for overvoltage protection
Range: 0..100 s
Page(s): 165
10713 ProtTimeUnderVolt
Level: 6 Delay time for undervoltage protection
Range: 0..100 s
Page(s): 166
10714 ProtTimeOverROCOF
Level: 6 Delay time for loss of mains protection due to RoCoF - rate
Range: 0..100 s of change of frequency (df/dt)
Page(s): 166
10715 ProtTimeVectorShift
Level: 6 Delay time for loss of mains protection due to vector shift
Range: 0..100 s
Page(s): 167
10716 ProtTimeCurrentSymm
Level: 6 Delay time for current balance protection (difference between
Range: 0..100 s any two phases)
Page(s): 168
10717 ProtTimeVoltageSymm
Level: 6 Delay time for voltage balance protection (difference
Range: 0..100 s between any two phases)
Page(s): 169
10718 ProtTimePowerSupply
Level: 6 Delay time for protection due to power supply deviation
Range: 0..100 s
Page(s): 170
10719 ProtTimeUnderCurr
Level: 6 Delay time for undercurrent protection
Range: 0..100 s
Page(s): 169
10720 ProtTimePhaseCheck
Level: 6 Delay or holding time for the additional phase difference
Range: 0..100 s check
Page(s): 171
10731 ChckTimeLowLoadSw1
Level: 6 Delay time for checking the load switching point 1 for low
Range: 0..1000 s load
Page(s): 181
10732 ChckTimeLowLoadSw2
Level: 6 Delay time for checking the load switching point 2 for low
Range: 0..1000 s load
Page(s): 181
10733 ChckTimeHighLoadSw1
Level: 6 Delay time for checking the load switching point 1 for high
Range: 0..1000 s load
Page(s): 182
10734 ChckTimeHighLoadSw2
Level: 6 Delay time for checking the load switching point 2 for high
Range: 0..1000 s load
Page(s): 182
10740 ChckTimeLoadCtrlDiff
Level: 6 Delay time for checking the load control deviation
Range: 0..100 s
Page(s): 180
10750 ProtValueVoltMatch
Level: 6 Trigger value for maximum voltage difference to be accepted
Range: 0..200 % for the synchronous condition "voltage matched"
Page(s): 138, 158
10751 ProtValueSyncCheck
Level: 6 Trigger value for maximum phase difference to be accepted
Range: 0..180 °el for the synchronous condition "phase matched"
Page(s): 137, 159
10752 ProtValueOverLoad
Level: 6 Trigger value for overload protection
Range: 0..200 %
Page(s): 160
10753 ProtValueRevPower1
Level: 6 Trigger value for reverse power protection stage 1
Range: -200..0 %
Page(s): 160
10754 ProtValueRevPower2
Level: 6 Trigger value for reverse power protection stage 2
Range: -200..0 %
Page(s): 160
10755 ProtValueOverExcit
Level: 6 Trigger value for over-excitation protection
Range: 0..200 %
Page(s): 161
10756 ProtValueExcitLoss
Level: 6 Trigger value for excitation loss protection
Range: -200..0 %
Page(s): 162
10757 ProtValueOverCurr1
Level: 6 Trigger value for overcurrent / time protection stage 1
Range: 0..200 %
Page(s): 163
10758 ProtValueOverCurr2
Level: 6 Trigger value for overcurrent / time protection stage 2"
Range: 0..200 %
Page(s): 163
10759 ProtValueSCCurrent
Level: 6 Trigger value for overcurrent / instant (short circuit)
Range: 0..200 % protection
Page(s): 163
10760 ProtValueOverFreq
Level: 6 Trigger value for over-frequency protection
Range: 0..100 Hz
Page(s): 164
10761 ProtValueUnderFreq
Level: 6 Trigger value for under-frequency protection
Range: 0..100 Hz
Page(s): 164
10762 ProtValueOverVolt
Level: 6 Trigger value for overvoltage protection
Range: 0..200 %
Page(s): 165
10763 ProtValueUnderVolt
Level: 6 Trigger value for undervoltage protection
Range: 0..200 %
Page(s): 166
10764 ProtValueOverROCOF
Level: 6 Trigger value for loss of mains protection due to
Range: 0..50 Hz/s RoCoF - rate of change of frequency (df/dt)
Page(s): 166
10765 ProtValueVectorShift
Level: 6 Trigger value for loss of mains protection due to vector shift
Range: 0..180 °el
Page(s): 167
10766 ProtValueCurrentSymm
Level: 6 Trigger value for current balance protection (difference
Range: 0..200 % between any two phases)
Page(s): 168
10767 ProtValueVoltageSymm
Level: 6 Trigger value for voltage balance protection (difference
Range: 0..200 % between any two phases)
Page(s): 169
10768 ProtValuePowerSupply
Level: 6 Trigger value for protection due to power supply deviation
Range: 0..55 V
Page(s): 170
10769 ProtValueUnderCurr
Level: 6 Trigger value for undercurrent protection
Range: 0..200 %
Page(s): 169
10770 ProtValuePhaseCheck
Level: 6 Trigger value for the additional phase difference check
Range: 0..180 °el
Page(s): 171
10781 ChckValueLowLoadSw1
Level: 6 Trigger value of the load switching point 1 for low load
Range: 0..200 %
Page(s): 181
10782 ChckValueLowLoadSw2
Level: 6 Trigger value of load switching point 2 for low load
Range: 0..200 %
Page(s): 181
10783 ChckValueHighLoadSw1
Level: 6 Trigger value of load switching point 1 for high load
Range: 0..200 %
Page(s): 182
10784 ChckValueHighLoadSw2
Level: 6 Trigger value of load switching point 2 for high load
Range: 0..200 %
Page(s): 182
10790 ChkValueLoadCtrlDiff
Level: 6 Trigger value for checking the load control deviation
Range: 0..200 %
Page(s): 180
10800 ProtHystVoltMatch
Level: 6 Hysteresis for loss of the synchronous condition "voltage
Range: 0..200 % matched"
Page(s): 158
10801 ProtHystSyncCheck
Level: 6 Hysteresis for loss of for the synchronous condition "phase
Range: 0..180 °el matched"
Page(s): 159
10802 ProtHystOverLoad
Level: 6 Hysteresis for overload protection
Range: 0..200 %
Page(s): 160
10803 ProtHystRevPower1
Level: 6 Hysteresis for reverse power protection stage 1
Range: 0..200 %
Page(s): 160
10804 ProtHystRevPower2
Level: 6 Hysteresis for reverse power protection stage 2
Range: 0..200 %
Page(s): 160
10805 ProtHystOverExcit
Level: 6 Hysteresis for over-excitation protection
Range: 0..200 %
Page(s): 161
10806 ProtHystExcitLoss
Level: 6 Hysteresis for excitation loss protection
Range: 0..200 %
Page(s): 162
10807 ProtHystOverCurr1
Level: 6 Hysteresis for overcurrent / time protection stage 1
Range: 0..200 %
Page(s): 163
10808 ProtHystOverCurr2
Level: 6 Hysteresis for overcurrent / time protection stage 2
Range: 0..200 %
Page(s): 163
10809 ProtHystSCCurrent
Level: 6 Hysteresis for overcurrent / instant (short circuit) protection
Range: 0..200 %
Page(s): 163
10810 ProtHystOverFreq
Level: 6 Hysteresis for over-frequency protection
Range: 0..100 Hz
Page(s): 164
10811 ProtHystUnderFreq
Level: 6 Hysteresis for under-frequency protection
Range: 0..100 Hz
Page(s): 164
10812 ProtHystOverVolt
Level: 6 Hysteresis for overvoltage protection
Range: 0..200 %
Page(s): 165
10813 ProtHystUnderVolt
Level: 6 Hysteresis for undervoltage protection
Range: 0..200 %
Page(s): 166
10814 ProtHystOverROCOF
Level: 6 Hysteresis for loss of mains protection due to RoCoF - rate of
Range: 0..50 Hz/s change of frequency (df/dt)
Page(s): 166
10815 ProtHystVectorShift
Level: 6 Hysteresis for loss of mains protection due to vector shift
Range: 0..180 °el
Page(s): 167
10816 ProtHystCurrentSymm
Level: 6 Hysteresis for current balance protection (difference between
Range: 0..200 % any two phases)
Page(s): 168
10817 ProtHystVoltageSymm
Level: 6 Hysteresis for voltage balance protection (difference between
Range: 0..200 % any two phases)
Page(s): 169
10818 ProtHystPowerSupply
Level: 6 Hysteresis for protection due to power supply deviation
Range: 0..55 V
Page(s): 170
10819 ProtHystUnderCurr
Level: 6 Hysteresis for undercurrent protection
Range: 0..200 %
Page(s): 169
10820 ProtHystPhaseCheck
Level: 6 Hysteresis for the additional phase difference check
Range: 0..180 °el
Page(s): 171
10831 ChckHystLowLoadSw1
Level: 6 Hysteresis of the load switching point 1 for low load
Range: 0..200 %
Page(s): 181
10832 ChckHystLowLoadSw2
Level: 6 Hysteresis of the load switching point 2 for low load
Range: 0..200 %
Page(s): 181
10833 ChckHystHighLoadSw1
Level: 6 Hysteresis of the load switching point 1 for high load
Range: 0..200 %
Page(s): 182
10834 ChckHystHighLoadSw2
Level: 6 Hysteresis of the load switching point 2 for high load
Range: 0..200 %
Page(s): 182
10840 ChckHystLoadCtrlDiff
Level: 6 Hysteresis for checking the load control deviation
Range: 0..200 %
Page(s): 180
11700 PowerPulseRate
Level: 4 Amount of power / reactive power to be produced or
Range: 1..999 kWh consumed between two power pulses at
Page(s): 183 13703 ProducedPowerPulse
13707 ProducPowerReacPulse
13713 ConsumedPowerPulse
13717 ConsumPowerReacPulse
20000 EngineStartMaxTime BASIC, MEDIUM, EXTENDED
Level: 4 Maximum time allowed for completion of all applicable
Range: 0..1000 s starting procedures
Page(s): 122, 268
20001 PreStartTime BASIC, MEDIUM, EXTENDED
Level: 4 Maximum time, after which external pre-start devices must
Range: 0..1000 s give healthy feedback if digital input function
Page(s): 123, 267 2843 SwPreStartHealthy is assigned
20002 CrankTime BASIC, MEDIUM, EXTENDED
Level: 4 Time span for dry cranking of engine with ignition off
Range: 0..1000 s n/a for diesel engines
Page(s): 123, 268
20003 IgnitionTime BASIC, MEDIUM, EXTENDED
Level: 4 Time span for dry cranking of engine with ignition on
Range: 0..1000 s n/a for diesel engines
Page(s): 123, 268
20004 CrankAttemptTime BASIC, MEDIUM, EXTENDED
Level: 4 Time span for crank attempts with fuel supply on
Range: 0..1000 s
Page(s): 123, 268
2412 CanGCRxOkNode31to16
Level: 1 HZM-CAN: activity indication of DGM-02 with node
Range: 0000..FFFF Hex number 16…31
Page(s): 233, 236
2413 CanGCRxOkNode15to01
Level: 1 HZM-CAN: activity indication of DGM-02 with node
Range: 0000..FFFF Hex number 1…15
Page(s): 233, 236
2422 CanCMNodeState31to16
Level: 1 HZM-CAN: activity indication of customer module with
Range: 0000..FFFF Hex node number 16…31
Page(s): 233
2423 CanCMNodeState15to01
Level: 1 HZM-CAN: activity indication of customer module with
Range: 0000..FFFF Hex node number 1…15
Page(s): 233
2424 CanPCRxOkNode31to16
Level: 1 HZM-CAN: activity indication of PC with node number
Range: 0000..FFFF Hex 16…31
Page(s): 233
2425 CanPCRxOkNode15to01
Level: 1 HZM-CAN: activity indication of PC with node number
Range: 0000..FFFF Hex 1…15
Page(s): 233
2431 CanGCNodeExist31to16
Level: 4 Bit pattern of DGM-02 recognized on CAN and, hence
Range: 0000..FFFF Hex expected to communicate
(numbers 16…31)
2432 CanGCNodeExist15to01
Level: 4 Bit pattern of DGM-02 recognized on CAN and, hence
Range: 0000..FFFF Hex expected to communicate
(numbers 1…15)
2435 CanGCSleepModeOn
Level: 1 Communication on CAN inactive
Range: 0..1
Page(s): 235
2437 CanGCAwakeModeOn
Level: 1 Communication on CAN active
Range: 0..1
Page(s): 235
2501 Can2TxBufferState GROUP-TO-GROUP
Level: 1 State of CAN-2 sending buffer
Range: 0000..FFFF Hex (indication of buffer overflow per device type)
Page(s): 235
2502 Can2RxBufferState GROUP-TO-GROUP
Level: 1 State of CAN-2 receiving buffer
Range: 0000..FFFF Hex (indication of buffer overflow per device type)
Page(s): 235
2818 SwUnLoadRequest
Level: 1 Switch condition of digital input function "Unload Request"
Range: 0..1
Page(s): 55, 126, 224
2819 SwUnSyncRequest
Level: 1 Switch condition of digital input function "Un-sync Request"
Range: 0..1
Page(s): 55, 126, 131, 197, 224
2820 SwStopRequest BASIC, MEDIUM, EXTENDED
Level: 1 Switch condition of digital input function "Engine Stop
Range: 0..1 Request"
Page(s): 55, 94, 124, 224
2821 SwEmergencyStop
Level: 1 Switch condition of digital input function "Emergency Stop"
Range: 0..1
Page(s): 124, 224, 267
2822 SwLoadLimitForced BASIC, MEDIUM, EXTENDED
Level: 1 Switch condition of digital input function "Forced Load
Range: 0..1 Limit"
Page(s): 145, 224
2823 SwBaseLoadForced BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 1 Switch condition of digital input function "Forced Base
Range: 0..1 Load"
Page(s): 143, 224
2824 Sw*CB_Inhibit
Level: 1 Switch condition of digital input function "Circuit Breaker
Range: 0..1 Inhibit"
Page(s): 55, 129, 197, 204, 224, 264 * = G: Generator (BASIC, MEDIUM, EXTENDED)
* = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
2825 SwActOnGroup2Or1 GROUP-TO-GROUP
Level: 1 Switch condition of digital input function " Act on Group at
Range: 0..1 CAN-2 or Group at CAN-1"
Page(s): 138, 144, 224
2826 SwCanGCSetWakeUp
Level: 1 Switch condition of digital input function "CAN
Range: 0..1 Communication for Type GC Wake Up"
Page(s): 224, 236
2827 SwCanGCSetSleep
Level: 1 Switch condition of digital input function "CAN
Range: 0..1 Communication for Type GC Set Sleep"
Page(s): 224, 236
2828 SwErrorReset
Level: 1 Switch condition of digital input function "Error Reset"
Range: 0..1
Page(s): 55, 224, 243
2829 SwAutoMode
Level: 1 Switch condition of digital input function "Auto Mode"
Range: 0..1
Page(s): 55, 89, 224
2830 SwManualMode
Level: 1 Switch condition of digital input function "Manual Mode"
Range: 0..1
Page(s): 55, 89, 224
2831 SwIdleSpeed BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Switch condition of digital input function "Idle Speed"
Page(s): 94, 224
2832 SwSpeedInc BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Switch condition of digital input function "Speed Increment"
Page(s): 94, 95, 224
2833 SwSpeedDec BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Switch condition of digital input function "Speed Decrement"
Page(s): 94, 95, 224
2834 SwForcedStart BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Switch condition of digital input function "Forced Start"
Page(s): 106, 224
2835 SwLoadInc BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 1 Switch condition of digital input function "Load Increment"
Range: 0..1
Page(s): 143, 224
2836 SwLoadDec BASIC, MEDIUM, EXTENDED, GROUP-TO-MAINS
Level: 1 Switch condition of digital input function "Load Decrement"
Range: 0..1
Page(s): 143, 224
2837 SwPFInc BASIC, MEDIUM, EXTENDED
Level: 1 Switch condition of digital input function "Power Factor
Range: 0..1 Increment"
Page(s): 147, 225
2838 SwPFDec BASIC, MEDIUM, EXTENDED
Level: 1 Switch condition of digital input function "Power Factor
Range: 0..1 Decrement"
Page(s): 148, 225
2839 SwAVRStandbyCtrl BASIC, MEDIUM, EXTENDED
Level: 1 Switch condition of digital input function "AVR Voltage
Range: 0..1 Stand-by Control"
Page(s): 148, 225
2840 SwSetpRemoteOrBaseLd BASIC, MEDIUM, EXTENDED
Level: 1 Switch condition of digital input function "Remote or Base
Range: 0..1 Load"
Page(s): 143, 144, 214, 225
2840 SwBaseLdOrImpExp GROUP-TO-MAINS
Level: 1 Switch condition of digital input function "Base Load or
Range: 0..1 Import/Export"
Page(s): 144, 213, 225
3078 ErrRAMTest
Level: 1 Error reported during RAM test
Range: 0..1
Page(s): 259
3080 ErrOperationalData
Level: 1 Error reported on storing operational data
Range: 0..1
Page(s): 259
3081 Err5VReference
Level: 1 Error indication of 5 V reference voltage
Range: 0..1
Page(s): 259
3082 ErrADC
Level: 1 Error indication of A-D converter
Range: 0..1
Page(s): 260
3085 ErrVoltage
Level: 1 Error indication of power supply
Range: 0..1
Page(s): 260
3090 ErrData
Level: 1 Error indication of data set
Range: 0..1
Page(s): 261
3091 ErrLogical
Level: 1 Error indication of data set structure
Range: 0..1
Page(s): 261
3092 ErrConfiguration
Level: 1 Configuration error
Range: 0..1
Page(s): 248, 261
3093 ErrStack
Level: 1 Error indication "stack overflow"
Range: 0..1
Page(s): 261
3094 ErrIntern
Level: 1 Error indication of internal software fault
Range: 0..1
Page(s): 262
3095 ExceptionNumber
Level: 1 Error number for software fault
Range: 0..255
Page(s): 262, 271
3096 ExceptionAddr1High
Level: 1 High byte of extended error number 1 of software faults
Range: 0000..FFFF Hex
Page(s): 262, 272
3097 ExceptionAddr1Low
Level: 1 Low byte of extended error number 1 of software faults
Range: 0000..FFFF Hex
Page(s): 262, 272
3098 ExceptionAddr2High
Level: 1 High byte of extended error number 2 of software faults
Range: 0000..FFFF Hex
Page(s): 262, 272
3099 ExceptionAddr2Low
Level: 1 Low byte of extended error number 2 of software faults
Range: 0000..FFFF Hex
Page(s): 262, 272
3101 SErr…
ff. Level: 1 Sentinel for the occurrence of…
Range: 0..255 Related current errors see 3001 ff.
3195 SExceptionNumber
Level: 1 Marker for the occurrence of
Range: 0..255 3095 ExceptionNumber
3196 SExceptionAddr1High
Level: 1 Marker for the occurrence of
Range: 0000..FFFF Hex 3096 ExceptionAddr1High
3197 SExceptionAddr1Low
Level: 1 Marker for the occurrence of
Range: 0000..FFFF Hex 3097 ExceptionAddr1Low
3198 SExceptionAddr2High
Level: 1 Marker for the occurrence of
Range: 0000..FFFF Hex 3098 ExceptionAddr2High
3199 SExceptionAddr2Low
Level: 1 Marker for the occurrence of
Range: 0000..FFFF Hex 3099 ExceptionAddr2Low
3201 GenCtrlAutoOrManual
Level: 1 Operation mode of generator controls:
Range: 0..1 1: Automatic (i.e. isochronous)
Page(s): 89, 143, 148 0: Manual (i.e. droop) mode
3202 SpeedGovAutoOrManual BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Operation mode of integrated speed governor:
Page(s): 89 1: Automatic (i.e. isochronous)
0: Manual (i.e. droop) mode
3203 GenCtrlAutoPossible BASIC, MEDIUM, EXTENDED
Level: 1 Availability of automatic mode operation of generator
Range: 0..1 controls
Page(s): 89
3204 SpeedGovAutoPossible BASIC, MEDIUM, EXTENDED
Level: 1 Availability of automatic mode operation of speed controls
Range: 0..1
Page(s): 89, 236
3510 Aix
ff. Level: 1 Normalized value of analogue input x
Range: 0..100 % x = 1…7
Page(s): 70
3511 AIx_Value
ff. Level: 1 Un-normalized value of analogue input x
Range: 0..65520 x = 1…7
Page(s): 70
3573 AI7_AdjGain
Level: 6 Factory calibration value: Gain adjustment for analogue input
Range: 0..200 % 7
3580 TI1
Level: 1 Normalized value of temperature input
Range: -100..1000 °C
Page(s): 70
3581 TI1_Value
Level: 1 Un-normalized value of temperature input
Range: 0..65520
Page(s): 70
3600 PowerSupply
Level: 1 Current value of power supply voltage
Range: 0..55 V
Page(s): 53, 170, 260
3601 5V_Reference
Level: 1 Current value of internal 5 V supply
Range: 0..10 V
Page(s): 259
3602 CurrentOut5Feedback
Level: 4 Current value of current output 5
Range: 0..100 %
3603 ADC:Ref_Middle
Level: 4 Current value of middle A-D converter reference
Range: 0..65535
Page(s): 260
3604 ADC:Ref_Low
Level: 4 Current value of low A-D converter reference
Range: 0..65535
Page(s): 260
3605 ADC:Ref_High
Level: 4 Current value of high A-D converter reference
Range: 0..65535
Page(s): 260
3640 AnalogOut1_AdjOffset
Level: 6 Factory calibration value: Offset adjustment for analogue
Range: 0..4095 output 1
3641 AnalogOut1_AdjGain
Level: 6 Factory calibration value: Gain adjustment for analogue
Range: 0..100 % output 1
3645 AnalogOut2_AdjOffset
Level: 6 Factory calibration value: Offset adjustment for analogue
Range: 0..4095 output 2
3646 AnalogOut2_AdjGain
Level: 6 Factory calibration value: Gain adjustment for analogue
Range: 0..100 % output 2
3800 EmergencyAlarm
Level: 1 Indication of emergency shutdown alarm due to fatal error
Range: 0..1 (Critical Alarm)
Page(s): 57, 244, 252
3801 CommonAlarm
Level: 1 Indication of common alarm (Non-critical Alarm)
Range: 0..1
Page(s): 57, 244, 252
3802 EngineStopRequest BASIC, MEDIUM, EXTENDED
Level: 1 Indication when engine is stopped by internally or externally
Range: 0..1 executed engine stop (with speed governor option) or is to be
Page(s): 95, 98, 122, 171, 252 stopped (external speed governor)
3803 EngineStopped BASIC, MEDIUM, EXTENDED
Level: 1 Indication when engine is stopped
Range: 0..1
Page(s): 95, 98, 124
3804 EngineStarting BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Indication when engine is started
Page(s): 98
3805 EngineRunning BASIC, MEDIUM, EXTENDED
Level: 1 Indication when engine is running
Range: 0..1
Page(s): 98, 123
3806 EngineReleased BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..1 Indication when injection is released
Page(s): 99
3811 LED_1_On
Level: 1 Current display status of LED 1
Range: 0..1 (On-board LED indication "Power On" Indication of
supply voltage)
3812 LED_2_On
Level: 1 Current display status of LED 2
Range: 0..1 (On-board LED indication "Gen. Voltage" Indication of
live generator bars)
3813 LED_3_On
Level: 1 Current display status of LED 3
Range: 0..1 (On-board LED indication "Mains Voltage" Indication of
live busbars)
3814 LED_4_On
Level: 1 Current display status of LED 4
Range: 0..1 (On-board LED indication "Gen. Breaker" Indication of
generator circuit breaker status)
3815 LED_5_On
Level: 1 Current display status of LED 5
Range: 0..1 (On-board LED indication "Mains Breaker" Indication of
mains circuit breaker status)
3816 LED_6_On
Level: 1 Current display status of LED 6
Range: 0..1 (On-board LED indication "Voltage Adj." Indication of
voltage match)
3817 LED_7_On
Level: 1 Current display status of LED 7
Range: 0..1 (On-board LED indication "Frequ. Adj." Indication of
frequency match)
3818 LED_8_On
Level: 1 Current display status of LED 8
Range: 0..1 (On-board LED indication "Phase Adj." Indication of
phase match)
3821 ArgosLED_Auto
Level: 1 Current status of the ARGOS LED 1 when the default
Range: 0..1 assignment (index 0) is used
1: Automatic mode
0: Manuel mode
3822 ArgosLED_CommonAlarm
Level: 1 Current status of the ARGOS LED 2 when the default
Range: 0..1 assignment (index 1) is used
1: Common alarm active
0: No alarm
3823 ArgosLED_SyncEnable
Level: 1 Current status of the ARGOS LED 3 when the default
Range: 0..1 assignment (index 2) is used
1: Load sharing (island parallel or mains parallel) active
0: Not in load sharing
Flashing: Request for synchronize active
3824 ArgosLED_BUSVoltsOK
Level: 1 Current status of the ARGOS LED 4 when the default
Range: 0..1 assignment (index 3) is used
1: Voltage (+/- 10 %) and frequency (+/- 5 Hz) at BUS
terminals OK
0: Not OK
3825 ArgosLED_CBClosed
Level: 1 Current status of the ARGOS LED 5 when the default
Range: 0..1 assignment (index 4) is used
1: Status of circuit breaker is closed
0: Status of circuit breaker is opened
Flashing: Request for un-synchronize active
3826 ArgosLED_TripFatal
Level: 1 Current status of the ARGOS LED 6 when the default
Range: 0..1 assignment (index 5) is used
1: Emergency shutdown alarm active or circuit breaker
tripped
0: Common alarm indication has to be noted
3827 ArgosLED_SyncCheckOK
Level: 1 Current status of the ARGOS LED 7 when the default
Range: 0..1 assignment (index 6) is used
1: Circuit breaker release
0: No release
3828 ArgosLED_GENVoltsOK
Level: 1 Current status of the ARGOS LED 7 when the default
Range: 0..1 assignment (index 6) is used
1: Voltage (+/- 10 %) and frequency (+/- 5 Hz) at GEN
terminals OK
0: Not OK
Flashing (long): Engine start sequence active
Flashing (short): Engine stop sequence active
3830 Phase_SpeedControl BASIC, MEDIUM, EXTENDED
Level: 1 (only with speed governor option)
Range: 0..9 Current operational phase of speed control
Page(s): 98
3831 Phase_StartStop
Level: 1 Current operational phase of start-stop sequence control
Range: 0..15
Page(s): 117, 120
3832 Phase_GenControl
Level: 1 Current operational phase of generator control
Range: 0..20
Page(s): 117, 120, 143
3840 HardwareVersion
Level: 1 Version number of control unit hardware
Range: 00.00..99.99
Page(s): 241
3841 AddHardwareVersion
Level: 1 Additional version number of control unit hardware
Range: 00.00..99.99
Page(s): 241
3842 SoftwareVersion
Level: 1 Version number of software (firmware)
Range: 0000.00.00...6552.99.99 4 digits customer number, 2 digits variation, 2 digits
Page(s): 22, 241 modification index
3843 BootSoftwareVersion
Level: 1 Version number of boot loader software
Range: 65.0.00...65.5.35
Page(s): 241
3844 SerialDate
Level: 1 Serial date of control unit hardware
Range: 0..65535
Page(s): 241
3845 SerialNumber
Level: 1 Serial number of control unit hardware
Range: 0..65535
Page(s): 241
3847 HardwareType
Level: 1 Type of control unit hardware
Range: 0A..0D Hex 0x0A: all previous versions
0x0B: 320-00-160-03
0x0C: reserved
0x0D: reserved
3848 ConfigCheckSum
Level: 1 Check-sum over the parameters of the configuration
Range: 0000..FFFF Hex
Page(s): 242
3850 Identifier
Level: 1 Identification number of PC programme / handheld
Range: 0..65535 programmer
Page(s): 242
3851 LastIdentifier
Level: 1 Identification number of the parameter alteration saved last
Range: 0..65535
Page(s): 242
3857 CompileTime
Level: 1 Timestamp of the firmware compilation: Time
Range: 00:00..23:59
3858 CompileDate
Level: 1 Timestamp of the firmware compilation: Day, month
Range: 00.00..31.12
3859 CompileYear
Level: 1 Timestamp of the firmware compilation: Year
Range: 2000..3000
3865 CalculationTime
Level: 1 Calculation time required by main processor
Range: 0..15.625 ms
3870 Timer
Level: 1 Internal millisecond timer
Range: 0..65,535 s
3871 OperatingHourMeter BASIC, MEDIUM, EXTENDED
Level: 1 Number of operating hours at running generating set
Range: 0..65535 h
Page(s): 98, 184
3872 OperatingMinuteMeter BASIC, MEDIUM, EXTENDED
Level: 1 Minutes of running generating set to next full operating hour
Range: 0..59 min
Page(s): 98, 184
3873 OperatingSecondMeter BASIC, MEDIUM, EXTENDED
Level: 1 Seconds of running generating set to next full minute
Range: 0..59 s
Page(s): 98, 184
3895 RAMTestAddrHigh
Level: 6 High value of currently tested memory address
Range: 0000..FFFF Hex
Page(s): 259
3896 RAMTestAddrLow
Level: 6 Low value of currently tested memory address
Range: 0000..FFFF Hex
Page(s): 259
3897 StackTestFreeBytes
Level: 6 Indication of free bytes in stack
Range: 0000..0800 Hex
Page(s): 262
12001 FrequencyNet_Lx
ff. Level: 1 Current frequency value of busbar phase Lx
Range: 0..100 Hz x = 1…3
Page(s): 83
12004 FrequencyNetAvg_L1
Level: 4 Strongly filtered frequency value of busbar phase 1
Range: 0..100 Hz
Page(s): 83
12006 FrequencyNetRaw_Lx
ff. Level: 6 Unfiltered frequency value of busbar phase Lx
Range: 0..100 Hz x = 1…3
Page(s): 83
12011 FrequencyGeneratorLx
ff. Level: 1 Current frequency value of generator phase Lx
Range: 0..100 Hz x = 1…3
Page(s): 83, 164
12016 FrequencyGenRaw_Lx
ff. Level: 6 Unfiltered frequency value of generator phase Lx
Range: 0..100 Hz x = 1…3
Page(s): 83
12036 VectorShift_Lx
ff. Level: 1 Current value of voltage vector shift per 360° el of phase Lx
Range: -180..180 °el x = 1…3
Page(s): 167
12046 RoCoF_Lx
ff. Level: 1 Current value of rate of change of frequency (df/dt) of
Range: -100..100 Hz/s phase Lx
Page(s): 166 x = 1…3
12051 PhaseDifference_Lx
ff. Level: 1 Phase difference between busbar and generator phase Lx
Range: -180..180 °el (equals synchronoscope indication)
Page(s): 159, 171, 196, 197 x = 1…3
12101 VoltageBus_Lx
ff. Level: 1 Current line voltage value of busbar phase Lx at DGM-02-
Range: 0..600 V terminals (secondary side in case of external PTs)
Page(s): 84 x = 1…3
12104 VoltageBus_x_y
ff. Level: 1 Current phase-to-phase voltage value of busbar phases Lx/Ly
Range: 0..600 V at DGM-02-terminals (secondary side in case of external
Page(s): 84 PTs)
x = 1, 2, 3 and y = 2, 3, 1
12107 VoltageBusPrim_x_y
ff. Level: 1 Current system phase-to-phase voltage value of busbar
Range: 0..60000 V phases Lx/Ly (primary side in case of external PTs)
Page(s): 85 x = 1, 2, 3 and y = 2, 3, 1
12111 VoltageBusRel_x_y
ff. Level: 1 Current relative value of phase-to-phase voltage of busbar
Range: 0..200 % phases Lx/Ly, rated against 10321 VoltageRated
Page(s): 84, 148, 158 x = 1, 2, 3 and y = 2, 3, 1
12121 VoltageGen_Lx
ff. Level: 1 Current line voltage value of generator phase Lx at DGM-02-
Range: 0..600 V terminals (secondary side in case of external PTs)
Page(s): 84 x = 1…3
12124 VoltageGen_x_y
ff. Level: 1 Current phase-to-phase voltage value of generator phases
Range: 0..600 V Lx/Ly at DGM-02-terminals (secondary side in case of
Page(s): 84 external PTs)
x = 1, 2, 3 and y = 2, 3, 1
12127 VoltageGenPrim_x_y
ff. Level: 1 Current system phase-to-phase voltage value of generator
Range: 0..60000 V phases Lx/Ly (primary side in case of external PTs)
Page(s): 85 x = 1, 2, 3 and y = 2, 3, 1
12131 VoltageGenRel_x_y
ff. Level: 1 Current relative value of phase-to-phase voltage of generator
Range: 0..200 % phases Lx/Ly, rated against 10321 VoltageRated
Page(s): 84, 148, 158, 165, 166, 169 x = 1, 2, 3 und y = 2, 3, 1
12140 Current_DigitalPoti
Level: 6 Gain of generator current inputs
Range: 0..63 (internal digital potentiometer setting)
automatically set to 62 for external 1A CTs and to 53 for 5A
CTs according to 14310 CTs5AOr1A
12141 Current_Lx
ff. Level: 1 Current value of line current of phase Lx through
Range: 0..10 A DGM-02-terminals (secondary side of external CTs)
Page(s): 87 x = 1…3
12147 CurrentPrim_Lx
ff. Level: 1 Current value of system current of phase Lx
Range: 0..10000 A (primary side of external CTs)
Page(s): 87 x = 1…3
12151 CurrentRel_Lx
ff. Level: 1 Current relative value of system current of phase Lx, rated
Range: 0..200 % against 10322 CurrentRated
Page(s): 87, 162, 163, 168, 169 x = 1…3
12198 CosPhiConventnlMeter
Level: 1 Current value of overall system power factor, scaled for
Range: -1..1 conventional cos- -meters
(scale of -1.00…0.00…+1.00 equals
0.00LD…1.00…0.00LG)
12199 CosPhiSignedLeadLag
Level: 1 Current value of overall system power factor, signed to
Range: -1..1 characterize lead and lag conditions
(scale of -1.00…0.00…+1.00 equals
1.00LD…0.00LD/0.00LG…1.00LG)
12200 Power
Level: 1 Current overall real power value (calculation value from
Range: -6..6 kW secondary voltage and current values for reference)
Page(s): 87
12201 PowerReactive
Level: 1 Current overall reactive power value (calculation value from
Range: -6..6 kVAr secondary voltage and current values for reference)
Page(s): 87
12202 PowerApparent
Level: 1 Current overall apparent power value (calculated from
Range: -6..6 kVA secondary voltage and current values)
Page(s): 87
12203 cosPhi
Level: 1 Current value of overall system power factor (physically
Range: -1..1 correct scaling)
Page(s): 87, 148
12204 sinPhi
Level: 4 Current value of overall system sin
Range: -1..1
Page(s): 87
12205 PowerRelative
Level: 1 Current relative value of overall system real load, rated
Range: -200..200 % against 10330 LoadRated
Page(s): 71, 87, 141, 150, 159, 160,
180, 181, 190, 198, 236
12206 PowerReactiveRelativ
Level: 1 Current relative value of overall system reactive load, rated
Range: -200..200 % against 10330 LoadRated
Page(s): 87, 148, 152, 161, 162, 236
12208 PowerPrim
Level: 1 Current value of overall system real load
Range: -30000..30000 kW
Page(s): 87, 199
12209 PowerReactivePrim
Level: 1 Current value of overall system reactive load
Range: -30000..30000 kVAr
Page(s): 87
12210 PowerApparentPrim
Level: 1 Current value of overall system apparent load
Range: -30000..30000 kVA
Page(s): 87
12211 Power_Lx
ff. Level: 1 Current real power value of phase Lx (calculation value from
Range: -6..6 kW secondary voltage and current values for reference)
Page(s): 87 x = 1…3
12221 PowerReactive_Lx
ff. Level: 1 Current reactive power value of phase Lx (calculation value
Range: -6..6 kVAr from secondary voltage and current values for reference)
Page(s): 87 x = 1…3
12231 PowerApparent_Lx
ff. Level: 1 Current apparent power value of phase Lx (calculation value
Range: -6..6 kVA from secondary voltage and current values for reference)
Page(s): 87 x = 1…3
12241 PowerPrim_Lx
ff. Level: 1 Current value of phase Lx real load
Range: -30000..30000 kW x = 1…3
Page(s): 87
12251 PowerReactivePrim_Lx
ff. Level: 1 Current value of phase Lx reactive load
Range: -30000..30000 kVAr x = 1…3
Page(s): 88
12261 PowerApparentPrim_Lx
ff. Level: 1 Current value of phase Lx apparent load
Range: -30000..30000 kVA x = 1…3
Page(s): 88
12271 cosPhi_Lx
ff. Level: 1 Current value of phase Lx power factor
Range: -1..1 x = 1…3
Page(s): 88
12281 sinPhi_Lx
ff. Level: 4 Current value of phase Lx sin
Range: -1..1 x = 1…3
Page(s): 88
12291 Phi_Lx
ff. Level: 4 Current value of phase Lx phase angle
Range: -180..180 °el x = 1…3
Page(s): 88
12331 LoadLimitMin BASIC, MEDIUM, EXTENDED
Level: 4 Minimum possible load setpoint
Range: -200..200 %
Page(s): 141
12332 LoadLimitMax BASIC, MEDIUM, EXTENDED
Level: 4 Maximum possible load setpoint
Range: -200..200 %
Page(s): 142, 145
12333 PowerLimitDeRate BASIC, MEDIUM, EXTENDED
Level: 4 Maximum possible load setpoint allowed after temperature-
Range: 0..200 % dependent de-rating
Page(s): 145 (to be activated by 14070 LoadDeRateTempOn)
12338 LoadLimitActive BASIC, MEDIUM, EXTENDED
Level: 4 Indication load limitation is active
Range: 0..1
Page(s): 145
12380 AVROffset
Level: 1 Current offset for voltage control or power factor control
Range: -100..100 % (output from control loop to AVR)
Page(s): 71, 113, 203
12382 AVROffsetIncPulse BASIC, MEDIUM, EXTENDED
Level: 1 Voltage offset increase output pulse signal derived from
Range: 0..1 voltage control offset
Page(s): 57, 115
12384 AVROffsetDecPulse BASIC, MEDIUM, EXTENDED
Level: 1 Voltage offset decrease output pulse signal derived from
Range: 0..1 voltage control offset
Page(s): 57, 115
12385 AVRGovSetpoint
Level: 4 Current voltage governor setpoint to control the AVR offset
Range: 0..200 %
Page(s): 146, 203, 205
12386 AVRGovCurrentValue
Level: 4 Current voltage governor current value to control the AVR
Range: 0..200 % offset
Page(s): 203
12387 sinPhiGovSetpoint BASIC, MEDIUM, EXTENDED
Level: 4 Current reactive power governor or power factor governor
Range: -1..1 setpoint to control the internal offset value for the voltage
governor
12388 sinPhiGovCurrntValue BASIC, MEDIUM, EXTENDED
Level: 4 Current reactive power governor or power factor governor
Range: -1..1 current value to control the internal offset value for the
voltage governor
12454 Sets2ShareLoad31to16 GROUP-TO-GROUP
Level: 1 Indication of sets (group 2 at CAN-2) taking part in
Range: 0000..FFFF Hex isochronous load sharing
(Bit pattern of sets 16 through 31)
12455 Sets2ShareLoad15to01 GROUP-TO-GROUP
Level: 1 Indication of sets (group 2 at CAN-2) taking part in
Range: 0000..FFFF Hex isochronous load sharing
(Bit pattern of sets 1 through 15)
12456 Sets2ShareVAr31to16 GROUP-TO-GROUP
Level: 1 Indication of sets (group 2 at CAN-2) taking part in
Range: 0000..FFFF Hex VAr-sharing
(Bit pattern of sets 16 through 31)
12457 Sets2ShareVAr15to01 GROUP-TO-GROUP
Level: 1 Indication of sets (group 2 at CAN-2) taking part in
Range: 0000..FFFF Hex VAr-sharing
(Bit pattern of sets 1 through 15)
12461 NoOfSets2LoadSharing GROUP-TO-GROUP
Level: 1 Number of sets (group 2 at CAN-2) taking part in
Range: 0..31 isochronous load sharing
12462 NoOfSets2VArSharing GROUP-TO-GROUP
Level: 1 Number of sets (group 2 at CAN-2) taking part in
Range: 0..31 VAr-sharing
12464 SetsShareLoad31to16
Level: 1 Indication of sets taking part in isochronous load sharing
Range: 0000..FFFF Hex (Bit pattern of sets 16 through 31)
12465 SetsShareLoad15to01
Level: 1 Indication of sets taking part in isochronous load sharing
Range: 0000..FFFF Hex (Bit pattern of sets 1 through 15)
12466 SetsShareVAr31to16
Level: 1 Indication of sets taking part in VAr-sharing
Range: 0000..FFFF Hex (Bit pattern of sets 16 through 31)
12467 SetsShareVAr15to01
Level: 1 Indication of sets taking part in VAr-sharing
Range: 0000..FFFF Hex (Bit pattern of sets 1 through 15)
12471 NoOfSetsLoadSharing
Level: 1 Number of sets taking part in isochronous load sharing
Range: 0..31
12472 NoOfSetsVArSharing
Level: 1 Number of sets taking part in VAr-sharing
Range: 0..31
12473 GroupMasterID BASIC, MEDIUM, EXTENDED
Level: 1 ID of currently active master group control unit (identifying
Range: 0..31 the unit in charge of group sync / load control)
Page(s): 139, 143
12480 RelayAnalogLSLineOn BASIC, MEDIUM, EXTENDED, GROUP-TO-GROUP
Level: 1 Relay status for closing the connection to an analogue load
Range: 0..1 share line
Page(s): 57, 151
12481 RelayAnlogVArSLineOn BASIC, MEDIUM, EXTENDED, GROUP-TO-GROUP
Level: 1 Relay status for closing the connection to an analogue
Range: 0..1 reactive load share line
Page(s): 152
12491 DblSyncInitTimer MEDIUM, EXTENDED
Level: 4 Double synchronization: Timer indication of
Range: 0..100 s 10491 DblSyncInitTime
Page(s): 136
12492 DblSyncDecayTimer MEDIUM, EXTENDED
Level: 4 Double synchronization: Timer indication of
Range: 0..100 s 10492 DblSyncDecayTime
Page(s): 136
12493 DblSyncMaxParalTimr1 MEDIUM, EXTENDED
Level: 4 Double synchronization: Timer indication of
Range: 0..100 s 10493 DblSyncMaxParalTime1
Page(s): 136
12494 DblSyncMaxParalTimr2 MEDIUM, EXTENDED
Level: 4 Double synchronization: Timer indication of
Range: 0..100 s 10494 DblSyncMaxParalTime2
Page(s): 136
12495 DblSyncAlternativeCB MEDIUM, EXTENDED
Level: 1 Double synchronization: Binary control signal to change-over
Range: 0..1 the voltage measuring inputs to the mains busbar
Page(s): 135
12610 *CB_DeadBusClsInhib
Level: 1 Indication of interlock for dead-bus-closing due to sets
Range: 0..1 closing on dead bars with higher priority
Page(s): 155 * = G: Generator (BASIC, MEDIUM, EXTENDED)
* = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
12611 *CB_DeadBusClsInit
Level: 1 Indication of activity to initialize dead bus closing
Range: 0..1 * = G: Generator (BASIC, MEDIUM, EXTENDED)
Page(s): 155 * = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
12612 *CB_DeadBusClsConf
Level: 1 Indication of no other set attempting to close on dead bus
Range: 0..1 * = G: Generator (BASIC, MEDIUM, EXTENDED)
Page(s): 155 * = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
12613 *CB_DeadBusClosing
Level: 1 Indication of activity of dead-bus-closing procedure
Range: 0..1 * = G: Generator (BASIC, MEDIUM, EXTENDED)
Page(s): 155 * = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
12621 MCB_Release MEDIUM, EXTENDED
Level: 1 Double synchronization: Mains circuit breaker release
Range: 0..1 (Summing signal of all protections and conditions checked to
allow mains circuit breaker closure)
12622 MCB_RelayCloseOn MEDIUM, EXTENDED
Level: 1 Double synchronization: Current status of signal to close
Range: 0..1 mains circuit breaker
Page(s): 135
12623 MCB_RelayOpenOn MEDIUM, EXTENDED
Level: 1 Double synchronization: Current status of signal to open
Range: 0..1 mains circuit breaker
Page(s): 135
12624 MCB_StateClosed BASIC, MEDIUM, EXTENDED
Level: 1 Current status of mains circuit breaker
Range: 0..1
Page(s): 127
12625 MCB_Set MEDIUM, EXTENDED
Level: 1 Double synchronization: Current status of mains circuit
Range: 0..1 breaker as required by control unit
12629 MCB_ChangeStateDecay BASIC, MEDIUM, EXTENDED
Level: 4 Timer indication of 10624 MCB_ChangeStateDecay
Range: 0..1000 s
Page(s): 158
12630 MainsRestoreTimer GROUP-TO-MAINS
Level: 4 Timer indication of 10630 AutoResyncLockTime
Range: 0..1000 s
Page(s): 140
12710 ProtTimerOverFreq
Level: 4 Timer indication of 10710 ProtTimeOverFreq
Range: 0..100 s
Page(s): 164
12711 ProtTimerUnderFreq
Level: 4 Timer indication of 10711 ProtTimeUnderFreq
Range: 0..100 s
Page(s): 164
12712 ProtTimerOverVolt
Level: 4 Timer indication of 10712 ProtTimeOverVolt
Range: 0..100 s
Page(s): 165
12713 ProtTimerUnderVolt
Level: 4 Timer indication of 10713 ProtTimeUnderVolt
Range: 0..100 s
Page(s): 166
12714 ProtTimerOverROCOF
Level: 4 Timer indication of 10714 ProtTimeOverROCOF
Range: 0..100 s
Page(s): 166
12715 ProtTimerVectorShift
Level: 4 Timer indication of 10715 ProtTimeVectorShift
Range: 0..100 s
Page(s): 167
12716 ProtTimerCurrentSymm
Level: 4 Timer indication of 10716 ProtTimeCurrentSymm
Range: 0..100 s
Page(s): 168
12717 ProtTimerVoltageSymm
Level: 4 Timer indication of 10717 ProtTimeVoltageSymm
Range: 0..100 s
Page(s): 169
12718 ProtTimerPowerSupply
Level: 4 Timer indication of 10718 ProtTimePowerSupply
Range: 0..100 s
Page(s): 170
12719 ProtTimerUnderCurr
Level: 4 Timer indication of 10719 ProtTimeUnderCurr
Range: 0..100 s
Page(s): 169
12720 ProtTimerPhaseCheck
Level: 4 Timer indication of 10720 ProtTimePhaseCheck
Range: 0..100 s
Page(s): 171
12731 ChckTimerLowLoadSw1
Level: 4 Timer indication of 10731 ChckTimeLowLoadSw1
Range: 0..1000 s
Page(s): 181
12732 ChckTimerLowLoadSw2
Level: 4 Timer indication of 10732 ChckTimeLowLoadSw2
Range: 0..1000 s
Page(s): 181
12733 ChckTimerHighLoadSw1
Level: 4 Timer indication of 10733 ChckTimeHighLoadSw1
Range: 0..1000 s
Page(s): 182
12734 ChckTimerHighLoadSw2
Level: 4 Timer indication of 10734 ChckTimeHighLoadSw2
Range: 0..1000 s
Page(s): 182
12740 ChkTimerLoadCtrlDiff
Level: 4 Timer indication of 10740 ChckTimeLoadCtrlDiff
Range: 0..100 s
Page(s): 180
12800 VoltMatchTriggered
Level: 1 Indication that synchronous condition "voltage matched"
Range: 0..1 triggered and delay time started
Page(s): 159
12801 SyncCheckTriggered
Level: 1 Indication that synchronous condition "phase matched"
Range: 0..1 triggered and delay time started
Page(s): 159
12802 OverLoadTriggered
Level: 1 Indication that overload protection triggered and delay time
Range: 0..1 started
Page(s): 160
12803 RevPower1Triggered
Level: 1 Indication that reverse power protection stage 1 triggered and
Range: 0..1 delay time started
Page(s): 160
12804 RevPower2Triggered
Level: 1 Indication that reverse power protection stage 2 triggered and
Range: 0..1 delay time started
Page(s): 160
12805 OverExcitTriggered
Level: 1 Indication that over-excitation protection triggered and delay
Range: 0..1 time started
Page(s): 161
12806 ExcitLossTriggered
Level: 1 Indication that excitation loss protection triggered and delay
Range: 0..1 time started
Page(s): 162
12807 OverCurr1Triggered
Level: 1 Indication that overcurrent / time protection stage 1 triggered
Range: 0..1 and delay time started
Page(s): 163
12808 OverCurr2Triggered
Level: 1 Indication that overcurrent / time protection stage 2 triggered
Range: 0..1 and delay time started
Page(s): 163
12809 SCCurrentTriggered
Level: 1 Indication that overcurrent / instant (short circuit) protection
Range: 0..1 triggered and delay time started
Page(s): 164
12810 OverFreqTriggered
Level: 1 Indication that over-frequency protection triggered and delay
Range: 0..1 time started
Page(s): 164
12811 UnderFreqTriggered
Level: 1 Indication that under-frequency protection triggered and
Range: 0..1 delay time started
Page(s): 164
12812 OverVoltTriggered
Level: 1 Indication that overvoltage protection triggered and delay
Range: 0..1 time started
Page(s): 165
12813 UnderVoltTriggered
Level: 1 Indication that undervoltage protection triggered and delay
Range: 0..1 time started
Page(s): 166
12814 OverROCOF_Triggered
Level: 1 Indication that loss of mains protection due to RoCoF - rate
Range: 0..1 of change of frequency (df/dt) triggered and delay time
Page(s): 167 started
12815 VectorShiftTriggered
Level: 1 Indication that loss of mains protection vector shift triggered
Range: 0..1 and delay time started
Page(s): 167
12816 CurrentSymmTriggered
Level: 1 Indication that current balance protection triggered and delay
Range: 0..1 time started
Page(s): 168
12817 VoltageSymmTriggered
Level: 1 Indication that voltage balance protection triggered and delay
Range: 0..1 time started
Page(s): 169
12818 PowerSupplyTriggered
Level: 1 Indication that protection due to power supply deviation
Range: 0..1 triggered and delay time started
Page(s): 170
12819 UnderCurrTriggered
Level: 1 Indication that undercurrent protection triggered and delay
Range: 0..1 time started
Page(s): 170
12820 PhaseCheckTriggered
Level: 1 Indication that additional phase difference check triggered
Range: 0..1 and delay time started
Page(s): 171
12831 LowLoadSw1Triggered
Level: 1 Indication that load switching point 1 triggered for low load
Range: 0..1 and delay time started
Page(s): 181
12832 LowLoadSw2Triggered
Level: 1 Indication that load switching point 2 triggered for low load
Range: 0..1 and delay time started
Page(s): 181
12833 HighLoadSw1Triggered
Level: 1 Indication that load switching point 1 triggered for high load
Range: 0..1 and delay time started
Page(s): 182
12834 HighLoadSw2Triggered
Level: 1 Indication that load switching point 2 triggered for high load
Range: 0..1 and delay time started
Page(s): 182
12840 LoadCtrDiffTriggered
Level: 1 Indication that load control deviation triggered and delay
Range: 0..1 time started
Page(s): 180
12850 VoltMatchLocked
Level: 1 Indication that synchronous condition "voltage matched" has
Range: 0..1 been locked to close the circuit breaker automatically
Page(s): 138, 157, 159
12851 SyncCheckLocked
Level: 1 Indication that synchronous condition "phase matched" has
Range: 0..1 been locked to close the circuit breaker automatically
Page(s): 137, 157, 159
12852 OverLoadTripped
Level: 1 Indication that circuit breaker has tripped due to overload
Range: 0..1
Page(s): 160
12853 RevPower1Tripped
Level: 1 Indication that circuit breaker has tripped due to reverse
Range: 0..1 power stage 1
Page(s): 161
12854 RevPower2Tripped
Level: 1 Indication that circuit breaker has tripped due to reverse
Range: 0..1 power stage 2
Page(s): 161
12855 OverExcitTripped
Level: 1 Indication that circuit breaker has tripped due to over-
Range: 0..1 excitation
Page(s): 161
12856 ExcitLossTripped
Level: 1 Indication that circuit breaker has tripped due to excitation
Range: 0..1 loss
Page(s): 162
12857 OverCurr1Tripped
Level: 1 Indication that circuit breaker has tripped due to overcurrent /
Range: 0..1 time stage 1
Page(s): 163
12858 OverCurr2Tripped
Level: 1 Indication that circuit breaker has tripped due to overcurrent /
Range: 0..1 time stage 2
Page(s): 163
12859 SCCurrentTripped
Level: 1 Indication that circuit breaker has tripped due to overcurrent /
Range: 0..1 instant (short circuit)
Page(s): 164
12860 OverFreqTripped
Level: 1 Indication that circuit breaker has tripped due to over-
Range: 0..1 frequency
Page(s): 164
12861 UnderFreqTripped
Level: 1 Indication that circuit breaker has tripped due to under-
Range: 0..1 frequency
Page(s): 164
12862 OverVoltTripped
Level: 1 Indication that circuit breaker has tripped due to overvoltage
Range: 0..1
Page(s): 165
12863 UnderVoltTripped
Level: 1 Indication that circuit breaker has tripped due to undervoltage
Range: 0..1
Page(s): 166
12864 OverROCOF_Tripped
Level: 1 Indication that circuit breaker has tripped due to loss of
Range: 0..1 mains, RoCoF - rate of change of frequency (df/dt)
Page(s): 167
12865 VectorShiftTripped
Level: 1 Indication that circuit breaker has tripped due to loss of
Range: 0..1 mains, vector shift
Page(s): 167
12866 CurrentSymmTripped
Level: 1 Indication that circuit breaker has tripped due to current
Range: 0..1 unbalance
Page(s): 168
12867 VoltageSymmTripped
Level: 1 Indication that circuit breaker has tripped due to voltage
Range: 0..1 unbalance
Page(s): 169
12868 PowerSupplyTripped
Level: 1 Indication that circuit breaker has tripped due to power
Range: 0..1 supply deviation
Page(s): 170
12869 UnderCurrTripped
Level: 1 Indication that circuit breaker has tripped due to undercurrent
Range: 0..1
Page(s): 170
12870 PhaseCheckLocked
Level: 1 Indication that additional phase difference check is locked
Range: 0..1
Page(s): 157, 171
12881 LowLoadSw1Tripped
Level: 1 Indication that load switching point 1 has tripped for low load
Range: 0..1
Page(s): 181
12882 LowLoadSw2Tripped
Level: 1 Indication that load switching point 2 has tripped for low load
Range: 0..1
Page(s): 181
12883 HighLoadSw1Tripped
Level: 1 Indication that load switching point 1 has tripped for high
Range: 0..1 load
Page(s): 182
12884 HighLoadSw2Tripped
Level: 1 Indication that load switching point 2 has tripped for high
Range: 0..1 load
Page(s): 182
12890 LoadCtrlDiffTripped
Level: 1 Indication that checking the load control deviation has
Range: 0..1 tripped a warning
Page(s): 180
13000 ErrAutoNotAvailable
Level: 1 Error indication of automatic mode not possible
Range: 0..1
Page(s): 89, 262
13001 Err*CB_Status
Level: 1 Error indication of circuit breaker state not plausible
Range: 0..1 * = G: Generator (BASIC, MEDIUM, EXTENDED)
Page(s): 127, 131, 263 * = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
13002 ErrMCB_Status BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of mains circuit breaker state not plausible
Range: 0..1
Page(s): 127, 263
13003 Err*CB_Trip
Level: 1 Error indication of circuit breaker tripped by protection or
Range: 0..1 emergency shutdown alarm
Page(s): 263 * = G: Generator (BASIC, MEDIUM, EXTENDED)
* = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
13004 ErrMCB_Trip MEDIUM, EXTENDED
Level: 1 Double synchronization: Error indication of mains circuit
Range: 0..1 breaker tripped by protection or emergency shutdown alarm
Page(s): 263
13005 ErrPhaseRotationGen
Level: 1 Error indication of phase rotation of the voltages at GEN
Range: 0..1 terminals
Page(s): 264
13006 ErrPhaseRotationBus
Level: 1 Error indication of phase rotation of the voltages at BUS
Range: 0..1 terminals
Page(s): 264
13008 Err*CB_TripByInhib
Level: 1 Error indication of circuit breaker tripped by
Range: 0..1 2824 Sw*CB_Inhibit
Page(s): 264 * = G: Generator (BASIC, MEDIUM, EXTENDED)
* = M: Mains (GROUP-TO-MAINS)
* = B: Bus tie (GROUP-TO-GROUP)
13009 ErrMCB_TripByInhib MEDIUM, EXTENDED
Level: 1 Double synchronization: Error indication of mains circuit
Range: 0..1 breaker tripped by 2872 SwMCB_Inhibit
Page(s): 264
13012 ErrOverLoadTrigger
Level: 1 Warning indication that overload protection triggered
Range: 0..1
Page(s): 160, 265
13013 ErrRevPower1Trigger
Level: 1 Warning indication that reverse power protection stage 1
Range: 0..1 triggered
Page(s): 161, 265
13014 ErrRevPower2Trigger
Level: 1 Warning indication that reverse power protection stage 2
Range: 0..1 triggered
Page(s): 161, 265
13015 ErrOverExcitTrigger
Level: 1 Warning indication that over-excitation protection triggered
Range: 0..1
Page(s): 161, 265
13016 ErrExcitLossTrigger
Level: 1 Warning indication that excitation loss protection triggered
Range: 0..1
Page(s): 162, 265
13017 ErrOverCurr1Trigger
Level: 1 Warning indication that overcurrent / time protection stage 1
Range: 0..1 triggered
Page(s): 163, 265
13018 ErrOverCurr2Trigger
Level: 1 Warning indication that overcurrent / time protection stage 2
Range: 0..1 triggered
Page(s): 163, 265
13019 ErrSCCurrentTrigger
Level: 1 Warning indication that overcurrent / instant (short circuit)
Range: 0..1 protection triggered
Page(s): 164, 265
13020 ErrOverFreqTrigger
Level: 1 Warning indication that over-frequency protection triggered
Range: 0..1
Page(s): 165, 265
13021 ErrUnderFreqTrigger
Level: 1 Warning indication that under-frequency protection triggered
Range: 0..1
Page(s): 165, 265
13022 ErrOverVoltTrigger
Level: 1 Warning indication that overvoltage protection triggered
Range: 0..1
Page(s): 165, 265
13023 ErrUnderVoltTrigger
Level: 1 Warning indication that undervoltage protection triggered
Range: 0..1
Page(s): 166, 265
13024 ErrOvrROCOF_Trigger
Level: 1 Warning indication that loss of mains protection due to
Range: 0..1 RoCoF - rate of change of frequency (df/dt) triggered
Page(s): 167, 265
13025 ErrVectrShftTrigger
Level: 1 Warning indication that loss of mains protection due to vector
Range: 0..1 shift triggered
Page(s): 167, 265
13026 ErrCurrSymmTrigger
Level: 1 Warning indication that current balance protection triggered
Range: 0..1
Page(s): 168, 265
13027 ErrVoltSymmTrigger
Level: 1 Warning indication that voltage balance protection triggered
Range: 0..1
Page(s): 169, 265
13028 ErrPwrSupplyTrigger
Level: 1 Warning indication that power supply deviation protection
Range: 0..1 triggered
Page(s): 170, 265
13029 ErrUnderCurrTrigger
Level: 1 Warning indication that undercurrent protection triggered
Range: 0..1
Page(s): 170, 265
13032 ErrOverLoadTrip
Level: 1 Error indication that overload protection has tripped
Range: 0..1
Page(s): 160, 266
13033 ErrRevPower1Trip
Level: 1 Error indication that reverse power protection stage 1 has
Range: 0..1 tripped
Page(s): 161, 266
13034 ErrRevPower2Trip
Level: 1 Error indication that reverse power protection stage 2 has
Range: 0..1 tripped
Page(s): 161, 266
13035 ErrOverExcitTrip
Level: 1 Error indication that over-excitation protection has tripped
Range: 0..1
Page(s): 161, 266
13036 ErrExcitLossTrip
Level: 1 Error indication that excitation loss protection has tripped
Range: 0..1
Page(s): 162, 266
13037 ErrOverCurr1Trip
Level: 1 Error indication that overcurrent / time protection stage 1 has
Range: 0..1 tripped
Page(s): 163, 266
13038 ErrOverCurr2Trip
Level: 1 Error indication that overcurrent / time protection stage 2 has
Range: 0..1 tripped
Page(s): 163, 266
13039 ErrSCCurrentTrip
Level: 1 Error indication that overcurrent / instant (short circuit)
Range: 0..1 protection has tripped
Page(s): 164, 266
13040 ErrOverFreqTrip
Level: 1 Error indication that over-frequency protection has tripped
Range: 0..1
Page(s): 165, 266
13041 ErrUnderFreqTrip
Level: 1 Error indication that under-frequency protection has tripped
Range: 0..1
Page(s): 165, 266
13042 ErrOverVoltTrip
Level: 1 Error indication that overvoltage protection has tripped
Range: 0..1
Page(s): 165, 266
13043 ErrUnderVoltTrip
Level: 1 Error indication that undervoltage protection has tripped
Range: 0..1
Page(s): 166, 266
13044 ErrOverROCOF_Trip
Level: 1 Error indication that loss of mains protection due to
Range: 0..1 RoCoF - rate of change of frequency (df/dt) has tripped
Page(s): 167, 266
13045 ErrVectorShiftTrip
Level: 1 Error indication that loss of mains protection due to vector
Range: 0..1 shift has tripped
Page(s): 167, 266
13046 ErrCurrSymmTrip
Level: 1 Error indication that current balance protection has tripped
Range: 0..1
Page(s): 168, 266
13047 ErrVoltSymmTrip
Level: 1 Error indication that voltage balance protection has tripped
Range: 0..1
Page(s): 169, 266
13048 ErrPowerSupplyTrip
Level: 1 Error indication that power supply deviation protection has
Range: 0..1 tripped
Page(s): 170, 266
13049 ErrUnderCurrTrip
Level: 1 Error indication that undercurrent protection has tripped
Range: 0..1
Page(s): 170, 266
13070 ErrLoadControlDiff
Level: 1 Warning indication of load control deviation
Range: 0..1
Page(s): 180, 266
13095 Err_SW_HW_Mismatch
Level: 1 Error indication of software variant does not fit the hardware
Range: 0..1 variant
Page(s): 267, 272
13100 SErr…
ff. Level: 1 Sentinel for the occurrence of…
Range: 0..255 Related current errors see 13000 ff.
13500 LoadPlant_Total GROUP-TO-MAINS
Level: 4 Currently effective power produced by the entire plant, kW-
Range: 0..30000 kW value of the entire plant
Page(s): 145
13501 LoadRated_Gen_x
ff. Level: 4 Rated power of generating set with the node number x in the
Range: 0..30000 kW CAN network
x = 1…20
13521 LoadRated_Group_x
ff. Level: 4 Rated power of group unit with the node number 20 + x in
Range: 0..30000 kW the CAN network
x = 1…9
13551 LoadRated_2_Gen_x GROUP-TO-GROUP
ff. Level: 4 Rated power of generating set with the node number x in the
Range: 0..30000 kW CAN network at CAN-2
x = 1…20
13571 LoadRated_2_Group_x GROUP-TO-GROUP
ff. Level: 4 Rated power of group unit with the node number 20 + x in
Range: 0..30000 kW the CAN network at CAN-2
x = 1…9
13600 Load_kW_2_Total GROUP-TO-GROUP
Level: 1 Current average value of relative active power of all load
Range: -200..200 % sharing participants at CAN-2
Page(s): 153
13601 Load_kW_2_Gen_x GROUP-TO-GROUP
ff. Level: 1 Current relative active power of generating set with the node
Range: -200..200 % number x in the CAN network at CAN-2
x = 1…20
13621 Load_kW_2_Group_x GROUP-TO-GROUP
ff. Level: 1 Current relative active power of group unit with the node
Range: -200..200 % number 20 + x in the CAN network at CAN-2
x = 1…9
13630 Load_kW_2_AnaLSL GROUP-TO-GROUP
Level: 1 Current relative active power of analogue load sharing line
Range: -200..200 % for group 2
13650 Load_kVAr_2_Total GROUP-TO-GROUP
Level: 1 Current average value of relative reactive power of all VAr-
Range: -200..200 % sharing participants at CAN-2
Page(s): 153
13651 Load_kVAr_2_Gen_x GROUP-TO-GROUP
ff. Level: 1 Current relative reactive power of generating set with the
Range: -200..200 % node number x in the CAN network at CAN-2
x = 1…20
13671 Load_kVAr_2_Group_x GROUP-TO-GROUP
ff. Level: 1 Current relative reactive power of group unit with the node
Range: -200..200 % number 20 + x in the CAN network at CAN-2
x = 1…9
13680 Load_kVAr_2_AnaLSL GROUP-TO-GROUP
Level: 1 Current relative reactive power of analogue reactive load
Range: -200..200 % sharing line for group 2
13700 ProducedPower
Level: 1 Indication of produced power displayed in GWh
Range: 0..65535 GWh
Page(s): 184
13701 ProducedPower
Level: 1 Indication of produced power displayed in MWh up to the
Range: 0..999 MWh transfer on a GWh
Page(s): 184
13702 ProducedPower
Level: 1 Indication of produced power displayed in kWh up to the
Range: 0..999 kWh transfer on a MWh
Page(s): 184
13703 ProducedPowerPulse
Level: 1 Energy impulse (pulse length of 200 ms) as a function of
Range: 0..1 produced power
Page(s): 183
13704 ProducedPowerReac
Level: 1 Indication of produced reactive power displayed in GWh
Range: 0..65535 GWh
Page(s): 184
13705 ProducedPowerReac
Level: 1 Indication of produced reactive power displayed in MWh up
Range: 0..999 MWh to the transfer on a GWh
Page(s): 184
13706 ProducedPowerReac
Level: 1 Indication of produced reactive power displayed in kWh up
Range: 0..999 kWh to the transfer on a MWh
Page(s): 184
13707 ProducPowerReacPulse
Level: 1 Reactive energy impulse (pulse length of 200 ms) as a
Range: 0..1 function of produced reactive power
Page(s): 183
13710 ConsumedPower GROUP
Level: 1 Indication of consumed power displayed in GWh
Range: 0..65535 GWh
Page(s): 184
13711 ConsumedPower GROUP
Level: 1 Indication of consumed power displayed in MWh up to the
Range: 0..999 MWh transfer on a GWh
Page(s): 184
13712 ConsumedPower GROUP
Level: 1 Indication of consumed power displayed in kWh up to the
Range: 0..999 kWh transfer on a MWh
Page(s): 184
13713 ConsumedPowerPulse GROUP
Level: 1 Energy impulse (pulse length of 200 ms) as a function of
Range: 0..1 consumed power
Page(s): 183
13714 ConsumedPowerReac GROUP
Level: 1 Indication of consumed reactive power displayed in MWh up
Range: 0..65535 GWh to the transfer on a GWh
Page(s): 184
13715 ConsumedPowerReac GROUP
Level: 1 Indication of consumed reactive power displayed in MWh up
Range: 0..999 MWh to the transfer on a GWh
Page(s): 184
13751 VoltAdj_GenLx_440_60
ff. Level: 6 Factory calibration value: Calibration offset for voltage
Range: -10..10 % readings at terminal X at a frequency of 60 Hz
x = 1…3
X = 1…3
13754 CurrentAdj_Lx_1A_50
ff. Level: 6 Factory calibration value: Calibration offset for current
Range: -10..10 % readings through terminals X1/X2 using 1A-CTs at a
frequency of 50 Hz
x = 1…3
X1/X2 = 5/6…9/10
13757 CurrentAdj_Lx_1A_60
ff. Level: 6 Factory calibration value: Calibration offset for current
Range: -10..10 % readings through terminals X1/X2 using 1A-CTs at a
frequency of 60 Hz
x = 1…3
X1/X2 = 5/6…9/10
13760 CurrentAdj_Lx_5A_50
ff. Level: 6 Factory calibration value: Calibration offset for current
Range: -10..10 % readings through terminals X1/X2 using 5A-CTs at a
frequency of 50 Hz
x = 1…3
X1/X2 = 5/6…9/10
13763 CurrentAdj_Lx_5A_60
ff. Level: 6 Factory calibration value: Calibration offset for current
Range: -10..10 % readings through terminals X1/X2 using 5A-CTs at a
frequency of 60 Hz
x = 1…3
X1/X2 = 5/6…9/10
13766 CurrentAdjOffset_Lx
ff. Level: 6 Current offset of current readings through terminals X1/X2
Range: -10..10 % x = 1…3
X1/X2 = 5/6…9/10
13769 PhaseAdj_Lx_1A_50Hz
ff. Level: 6 Factory calibration value: Calibration offset for the phase
Range: 0..180 ° angle using 1A-CTs at terminals X1/X2 at a frequency of
50 Hz
x = 1…3
X1/X2 = 5/6…9/10
13772 PhaseAdj_Lx_1A_60Hz
ff. Level: 6 Factory calibration value: Calibration offset for the phase
Range: 0..180 ° angle using 1A-CTs at terminals X1/X2 at a frequency of
60 Hz
x = 1…3
X1/X2 = 5/6…9/10
13775 PhaseAdj_Lx_5A_50Hz
ff. Level: 6 Factory calibration value: Calibration offset for the phase
Range: 0..180 ° angle using 5A-CTs at terminals X1/X2 at a frequency of
50 Hz
x = 1…3
X1/X2 = 5/6…9/10
13778 PhaseAdj_Lx_5A_60Hz
ff. Level: 6 Factory calibration value: Calibration offset for the phase
Range: 0..180 ° angle using 5A-CTs at terminals X1/X2 at a frequency of
Page(s): 60 Hz
x = 1…3
X1/X2 = 5/6…9/10
13840 HardwareVariantCode
Level: 4 Indication of hardware variant code
Range: 0000..FFFF Hex
13841 SoftwareVariantCode
Level: 4 Indication of software (firmware) variant code
Range: 0000..FFFF Hex
13871 RTC_Year
Level: 1 Current year of internal clock
Range: 0..99
Page(s): 183
13872 RTC_Month
Level: 1 Current month of internal clock
Range: 1..12
Page(s): 183
13873 RTC_Date
Level: 1 Current date of internal clock
Range: 1..31
Page(s): 183
13874 RTC_Weekday
Level: 1 Current weekday of internal clock
Range: 1..7
Page(s): 183
13875 RTC_Hour
Level: 1 Current hour of internal clock
Range: 0..23 h
Page(s): 183
13876 RTC_Minute
Level: 1 Current minute of internal clock
Range: 0..59 min
Page(s): 183
13877 RTC_Second
Level: 1 Current second of internal clock
Range: 0..59 s
Page(s): 183
13900 Load_kW_Total
Level: 1 Current average value of relative active power of all load
Range: -200..200 % sharing participants
Page(s): 141, 153
13901 Load_kW_Gen_x
ff. Level: 1 Current relative active power of generating set with the node
Range: -200..200 % number x in the CAN network
Page(s): 236 x = 1…20
13921 Load_kW_Group_x
ff. Level: 1 Current relative active power of group unit with the node
Range: -200..200 % number 20 + x in the CAN network
x = 1…9
13930 Load_kW_AnaLSL BASIC, MEDIUM, EXTENDED, GROUP-TO-GROUP
Level: 1 Current relative active power of analogue load sharing line
Range: -200..200 %
13950 Load_kVAr_Total
Level: 1 Current average value of relative reactive power of all VAr-
Range: -200..200 % sharing participants
Page(s): 148, 153
13951 Load_kVAr_Gen_x
ff. Level: 1 Current relative reactive power of generating set with the
Range: -200..200 % node number x in the CAN network
Page(s): 236 x = 1…20
13971 Load_kVAr_Group_x
ff. Level: 1 Current relative reactive power of group unit with the node
Range: -200..200 % number 20 + x in the CAN network
x = 1…9
13980 Load_kVAr_AnaLSL BASIC, MEDIUM, EXTENDED, GROUP-TO-GROUP
Level: 1 Current relative reactive power of analogue reactive load
Range: -200..200 % sharing line
22001 EngineStartInProgr BASIC, MEDIUM, EXTENDED
Level: 1 Indication of engine starting sequence in progress
Range: 0..1
Page(s): 122
22004 EngineStopInProgress BASIC, MEDIUM, EXTENDED
Level: 1 Indication of engine stopping sequence in progress
Range: 0..1
Page(s): 124
22010 EngineStartTimer BASIC, MEDIUM, EXTENDED
Level: 1 Timer indication of 20000 EngineStartMaxTime
Range: 0..1000 s
Page(s): 122
22011 PreStartTimer BASIC, MEDIUM, EXTENDED
Level: 1 Timer indication of 20001 PreStartTime
Range: 0..1000 s
Page(s): 121, 123
22012 CrankTimer BASIC, MEDIUM, EXTENDED
Level: 1 Timer indication of 20002 CrankTime
Range: 0..1000 s
Page(s): 123
22013 IgnitionTimer BASIC, MEDIUM, EXTENDED
Level: 1 Timer indication of 20003 IgnitionTime
Range: 0..1000 s
Page(s): 123
22014 CrankAttemptTimer BASIC, MEDIUM, EXTENDED
Level: 1 Timer indication of 20004 CrankAttemptTime
Range: 0..1000 s
Page(s): 123
22816 CmdSyncActive
Level: 1 Indication of sync command for the start-stop sequence
Range: 0..1
Page(s): 126, 148
22817 CmdLoadActive
Level: 1 Indication of load command for the start-stop sequence
Range: 0..1
Page(s): 126
22818 CmdUnLoadActive
Level: 1 Indication of unload command for the start-stop sequence
Range: 0..1
Page(s): 126
22819 CmdUnSyncActive
Level: 1 Indication of un-sync command for the start-stop sequence
Range: 0..1
Page(s): 126
22820 CmdStopActive BASIC, MEDIUM, EXTENDED
Level: 1 Indication of engine stop command for the start-stop
Range: 0..1 sequence
Page(s): 124
22821 CmdEcyStopActive BASIC, MEDIUM, EXTENDED
Level: 1 Indication of emergency stop or emergency shutdown
Range: 0..1 command for the start-stop sequence
Page(s): 124
23071 ErrUnexpectedShtDwn BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of unexpected shutdown
Range: 0..1
Page(s): 124, 267
23072 ErrEmergencyStop
Level: 1 Error indication of shutdown due to emergency stop or
Range: 0..1 emergency shutdown
Page(s): 124, 267
23073 ErrPreStartFailed BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of pre-start actions failed
Range: 0..1
Page(s): 123, 267
23074 ErrFailedToStart BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of engine start failed
Range: 0..1
Page(s): 122, 267
23075 ErrFailedToSync
Level: 1 Error indication of synchronization failed
Range: 0..1
Page(s): 126, 268
23076 ErrFailedToLoad
Level: 1 Error indication of load failed
Range: 0..1
Page(s): 126, 268
23077 ErrFailedToUnLoad
Level: 1 Error indication of unload failed
Range: 0..1
Page(s): 126, 269
23078 ErrFailedToUnSync
Level: 1 Error indication of un-sync failed
Range: 0..1
Page(s): 126, 269
23079 ErrFailedToStop BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of engine stop failed
Range: 0..1
Page(s): 124, 269
23080 ErrShtDwnOverCrank BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of shutdown due to digital input function
Range: 0..1 "Over Crank or Starter Overload" ( 2845 SwOverCrank)
Page(s): 125, 269
23081 ErrShtDwnLowOilPress BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of shutdown due to digital input function
Range: 0..1 "Low Engine Oil Pressure" ( 2846 SwLowEngOilPress)
Page(s): 125, 270
23082 ErrShtDwnHighCoolTmp BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of shutdown due to digital input function
Range: 0..1 "High Engine Coolant Temperature"
Page(s): 125, 270 ( 2847 SwHighEngCoolTemp)
23083 ErrShtDwnGenericExt BASIC, MEDIUM, EXTENDED
Level: 1 Error indication of shutdown due to digital input function
Range: 0..1 "Generic External Fault" ( 2848 SwShutDownGeneric)
Page(s): 125, 270
23084 ErrGenericWarning BASIC, MEDIUM, EXTENDED
Level: 1 Warning indication due to digital input function "Generic
Range: 0..1 External Fault" ( 2878 SwGenericWarning)
Page(s): 124, 270
23100 SErr…
ff. Level: 1 Sentinel for the occurrence of…
Range: 0..255 Related current errors see 23000 ff.
23700 ErrorState(x) DeviceNet, Operating Instructions, Manual No. DG 05 003-e
ff. MODBUS, Operating Instructions, Manual No. DG 05 002-e
Level: 1 Overview of error bits from 3001 through 3095, 13000
Range: 0000..FFFF Hex through 13095, 23000 through 23095
x = 0…17
23720 BitCollection(x) DeviceNet, Operating Instructions, Manual No. DG 05 003-e
ff. MODBUS, Operating Instructions, Manual No. DG 05 002-e
CANopen Implementation, Manual No. DG 06 002-e
HEINZMANN-CAN Customer Module, Manual No.
DG 05 007-e
Level: 1 Bit collection according to definition in parameters starting
Range: 0000..FFFF Hex with 29900 BitCollParamSet(x) to send by communication
modules
x = 0…1
5100 NoStoreSErrOn
Level: 6 Enable/Disable of no saving of errors to error memory before
Range: 0..1 next reset
Page(s): 246
5101 CommAlarmWarnFlashOn
Level: 4 Selection of whether the common alarm indicator is to blink
Range: 0..1 when only warnings are active
Page(s): 244
5102 CommonAlarmResetOn
Level: 4 Selection of whether the common alarm indicator is to be
Range: 0..1 reset briefly (edge change) if some new error has occurred
Page(s): 244
5103 CommonAlarmResetBoth
Level: 4 Selection whether an edge change
Range: 0..1 (5102 CommonAlarmResetOn = 1) should be generated also
Page(s): 244 when an error is cleared (always for every error change)
5510 AnalogInx_CurrOrVolt
ff. Level: 6 Selection of input signal mode of analogue input x
Range: 0..1 x = 1…3
Page(s): 64 0: voltage input
1: current input
5512 AnalogInx_TempLin BASIC, MEDIUM, EXTENDED
ff. Level: 6 Selection of the temperature linearization characteristic for
Range: 0..4 analogue input x
Page(s): 67, 70 x = 1…7
0: none
1…4: linearization characteristic 1…4
5645 AnlogOut2_CurrOrVolt
Level: 6 Selection of output signal mode of analogue output 2
Range: 0..1 0: voltage output
1: current output
Only for control units, which were delivered before
May 2005!
5650 AnlogOut3_CurrOrVolt
Level: 6 Selection of output signal mode of analogue output 3
Range: 0..1 0: voltage output
Page(s): 72 1: current output
5655 AnlogOut4_CurrOrVolt
Level: 6 Selection of output signal mode of analogue output 4
Range: 0..1 0: voltage output
Page(s): 72 1: current output
14020 LoadSetpPCOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the load setpoint adjustment via PC
Range: 0..1
Page(s): 143, 202
14030 LoadRampOn
Level: 4 Enable/Disable of the load ramps
Range: 0..1
Page(s): 206
14040 SlipSyncOn
Level: 4 Enable/Disable of the slip synchronization
Range: 0..1
Page(s): 137, 197
14050 AVR_VoltMatchOn
Level: 4 Enable/Disable of the voltage matching during
Range: 0..1 synchronization
Page(s): 146, 204
14051 AVR_PFControlOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the power factor control in mains parallel
Range: 0..1 mode of operation
Page(s): 146, 205
14052 AVR_VARControlOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the VAr-control in island mode of
Range: 0..1 operation
Page(s): 146, 205
14053 AVR_PFSetpFixedOrExt BASIC, MEDIUM, EXTENDED
Level: 4 Selection of source of power factor setpoint
Range: 0..1 0: external analogue setpoint 1)
Page(s): 148 1: internal fixed setting 2)
1)
2901 PFSetpoint
2)
10660 AVR_PFForced
14070 LoadDeRateTempOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the temperature-dependent load limitation
Range: 0..1
Page(s): 145
14075 LoadDeRateByDCOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the load limitation if the speed governor
Range: 0..1 operates at its fuel limitation (only if the CAN connection to
Page(s): the HEINZMANN speed governor is activated)
14300 VoltageIn440VOr220V
Level: 4 Selection of 3 phase voltage measurement range
Range: 0..1 0: 100…200 Vph-ph
Fixed for DGM-02-BASIC and DGM- (connected to terminals 1A, 2A, 3A, 97A, 96A, 95A)
02-MEDIUM: 1 1: 240…480 Vph-ph
Page(s): 83, 242 (connected to terminals 1, 2, 3, 97, 96, 95)
14305 ExternalPhaseDiffOn EXTENDED, GROUP-TO-MAINS
Level: 6 Enable/Disable of the compensation value for the external
Range: 0..1 phase difference between GEN and BUS terminal voltage
Page(s): 138 10305 ExternalPhaseDiff
14310 CTs5AOr1A
Level: 4 Selection of 3 phase current measurement range
Range: 0..1 0: 1 Amp
Page(s): 86 1: 5 Amp
14311 CTsChangePolarity
Level: 4 Selection of the current flow direction of the current
Range: 0..1 transformers
Page(s): 86
14702 ProtOverLoadOn
Level: 6 Enable/Disable of the overload protection
Range: 0..1
Page(s): 160
14703 ProtRevPower1On
Level: 6 Enable/Disable of the reverse power protection stage 1
Range: 0..1
Page(s): 161
14704 ProtRevPower2On
Level: 6 Enable/Disable of the reverse power protection stage 2
Range: 0..1
Page(s): 161
14705 ProtOverExcitOn
Level: 6 Enable/Disable of the over-excitation protection
Range: 0..1
Page(s): 161
14706 ProtExcitLossOn
Level: 6 Enable/Disable of the excitation loss protection
Range: 0..1
Page(s): 162
14707 ProtOverCurr1On
Level: 6 Enable/Disable of the overcurrent / time protection stage 1
Range: 0..1
Page(s): 163
14708 ProtOverCurr2On
Level: 6 Enable/Disable of the overcurrent / time protection stage 2
Range: 0..1
Page(s): 163
14709 ProtSCCurrentOn
Level: 6 Enable/Disable of the overcurrent / instant (short circuit)
Range: 0..1 protection
Page(s): 164
14710 ProtOverFreqOn
Level: 6 Enable/Disable of the over-frequency protection
Range: 0..1
Page(s): 165
14711 ProtUnderFreqOn
Level: 6 Enable/Disable of the under-frequency protection
Range: 0..1
Page(s): 165
14712 ProtOverVoltOn
Level: 6 Enable/Disable of the overvoltage protection
Range: 0..1
Page(s): 165
14713 ProtUnderVoltOn
Level: 6 Enable/Disable of the undervoltage protection
Range: 0..1
Page(s): 166
14714 ProtOverROCOF_On
Level: 6 Enable/Disable of the loss of mains protection due to
Range: 0..1 RoCoF - rate of change of frequency (df/dt)
Page(s): 167
14715 ProtVectorShiftOn
Level: 6 Enable/Disable of the loss of mains protection due to vector
Range: 0..1 shift
Page(s): 168
14716 ProtCurrentSymmOn
Level: 6 Enable/Disable of the current balance protection
Range: 0..1
Page(s): 168
14717 ProtVoltageSymmOn
Level: 6 Enable/Disable of the voltage balance protection
Range: 0..1
Page(s): 169
14718 ProtPowerSupplyOn
Level: 6 Enable/Disable of the protection due to power supply
Range: 0..1 deviation
Page(s): 170
14719 ProtUnderCurrOn
Level: 6 Enable/Disable of the undercurrent protection
Range: 0..1
Page(s): 170
14731 ChckLowLoadSw1On
Level: 6 Enable/Disable of the load switching point 1 for low load
Range: 0..1
Page(s): 182
14732 ChckLowLoadSw2On
Level: 6 Enable/Disable of the load switching point 2 for low load
Range: 0..1
Page(s): 182
14733 ChckHighLoadSw1On
Level: 6 Enable/Disable of the load switching point 1 for high load
Range: 0..1
Page(s): 182
14734 ChckHighLoadSw2On
Level: 6 Enable/Disable of the load switching point 2 for high load
Range: 0..1
Page(s): 182
14740 ChckLoadCtrlDiffOn
Level: 6 Enable/Disable of checking the load control deviation
Range: 0..1
Page(s): 180
14752 OverLoadTripOrWarn
Level: 6 Selection of the reaction at overload
Range: 0..1 0: warning only
Page(s): 160 1: protection trip (opens the circuit breaker)
14753 RevPower1TripOrWarn
Level: 6 Selection of the reaction at reverse power stage 1
Range: 0..1 0: warning only
Page(s): 161 1: protection trip (opens the circuit breaker)
14754 RevPower2TripOrWarn
Level: 6 Selection of the reaction at reverse power stage 2
Range: 0..1 0: warning only
Page(s): 161 1: protection trip (opens the circuit breaker)
14755 OverExcitTripOrWarn
Level: 6 Selection of the reaction at over-excitation
Range: 0..1 0: warning only
Page(s): 162 1: protection trip (opens the circuit breaker)
14756 ExcitLossTripOrWarn
Level: 6 Selection of the reaction at excitation loss
Range: 0..1 0: warning only
Page(s): 162 1: protection trip (opens the circuit breaker)
14757 OverCurr1TripOrWarn
Level: 6 Selection of the reaction at overcurrent / time stage 1
Range: 0..1 0: warning only
Page(s): 163 1: protection trip (opens the circuit breaker)
14758 OverCurr2TripOrWarn
Level: 6 Selection of the reaction at overcurrent / time stage 2
Range: 0..1 0: warning only
Page(s): 163 1: protection trip (opens the circuit breaker)
14759 SCCurrentTripOrWarn
Level: 6 Selection of the reaction at overcurrent / instant (short circuit)
Range: 0..1 0: warning only
Page(s): 164 1: protection trip (opens the circuit breaker)
14760 OverFreqTripOrWarn
Level: 6 Selection of the reaction at over-frequency
Range: 0..1 0: warning only
Page(s): 165 1: protection trip (opens the circuit breaker)
14761 UnderFreqTripOrWarn
Level: 6 Selection of the reaction at under-frequency
Range: 0..1 0: warning only
Page(s): 165 1: protection trip (opens the circuit breaker)
14762 OverVoltTripOrWarn
Level: 6 Selection of the reaction at overvoltage
Range: 0..1 0: warning only
Page(s): 165 1: protection trip (opens the circuit breaker)
14763 UnderVoltTripOrWarn
Level: 6 Selection of the reaction at undervoltage
Range: 0..1 0: warning only
Page(s): 166 1: protection trip (opens the circuit breaker)
14764 OverROCOF_TripOrWarn
Level: 6 Selection of the reaction at excessive RoCoF
Range: 0..1 0: warning only
Page(s): 167 1: protection trip (opens the circuit breaker)
14765 VectorShftTripOrWarn
Level: 6 Selection of the reaction at vector shift
Range: 0..1 0: warning only
Page(s): 168 1: protection trip (opens the circuit breaker)
14766 CurrSymmTripOrWarn
Level: 6 Selection of the reaction at current unbalance
Range: 0..1 0: warning only
Page(s): 168 1: protection trip (opens the circuit breaker)
14767 VoltSymmTripOrWarn
Level: 6 Selection of the reaction at voltage unbalance
Range: 0..1 0: warning only
Page(s): 169 1: protection trip (opens the circuit breaker)
14768 PowrSupplyTripOrWarn
Level: 6 Selection of the reaction at power supply deviation
Range: 0..1 0: warning only
Page(s): 171 1: protection trip (opens the circuit breaker)
14769 UnderCurrTripOrWarn
Level: 6 Selection of the reaction at undercurrent
Range: 0..1 0: warning only
Page(s): 170 1: protection trip (opens the circuit breaker)
15770 RestoreSRamData
Level: 6 Enable of the back storage of SRAM data
Range: 0..1 Use parameter only after exchange of the SRAM
Page(s): 185 component. Parameter is automatically being reset
internally, but indication in DcDesk 2000 not
automatically updated.
24001 EngStartSequenceOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the usage of engine starting sequence
Range: 0..1
Page(s): 122
24004 EngStopSequenceOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the usage of engine stopping sequence
Range: 0..1
Page(s): 124
24017 WarmUpAtIdleOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the starting sequence including warm-up
Range: 0..1 period at low idle speed
Page(s): 123
24018 CoolDownAtIdleOn BASIC, MEDIUM, EXTENDED
Level: 4 Enable/Disable of the starting sequence including cool down
Range: 0..1 at idle speed
Page(s): 124
24810 ChanTyp…
ff. Level: 6 Configuration of module type when one switching function is
Range: 0..8 received by communication modules
Page(s): 223, 227, 228 0: not used
4: CANopen
5: DeviceNet
6: Modbus
7: SAE-J1939
8: HZM-CAN customer module
Switching functions see 2810 ff.
25750 CANopen Functions CANopen Implementation, Manual No. DG 06 002-e
to
25799
25800 Modbus Functions MODBUS, Operating Instructions, Manual No. DG 05 002-e
to
25849
25850 DeviceNet Functions DeviceNet, Operating Instructions, Manual No. DG 05 003-e
to
25899
25950 HZM-CAN customer module HEINZMANN-CAN Customer Module, Manual No.
to Functions DG 05 007-e
25999
16 List of Figures
Figure 1: ARGOS Front View ................................................................................................. 29
Figure 2: Overview of DGM-02 Versions and their Applications ........................................... 36
Figure 3: Island Parallel Mode ................................................................................................. 39
Figure 4: Island Parallel Operation with Group-to-Group ....................................................... 41
Figure 5: Mains Parallel Operation with Group-to-Mains ....................................................... 42
Figure 6: DcDesk 2000 Window: "Information Control Unit" ................................................ 43
Figure 7: Dimensional Drawing DGM-02 ............................................................................... 48
Figure 8: Use of the Retrofit Kit for Marine Applications ....................................................... 50
Figure 9: Connection of Power Supply .................................................................................... 53
Figure 10: Connection of Digital Inputs .................................................................................. 56
Figure 11: Connection of Digital Outputs ................................................................................ 59
Figure 12: Reading out a Parameter via a PWM Output.......................................................... 63
Figure 13: Connection of Voltage and Current Signals to Inputs ............................................ 65
Figure 14: Calibration of Analogue Inputs .............................................................................. 66
Figure 15: Connection of Analogue Outputs ........................................................................... 72
Figure 16: Reading out a Parameter via an Analogue Output .................................................. 74
Figure 17: Speed Probe Connection ......................................................................................... 76
Figure 18: 3-Phase Voltage and 3-Phase Current Sensing for Generator Control ................... 79
Figure 19: 3-Phase Voltage and 3-Phase Current Sensing for Group-to-Mains Application .. 79
Figure 20: 3-Phase Voltage and 3-Phase Current Sensing for Group-to-Group Application .. 80
Figure 21: Connection of 3-Phase Voltage and 3-Phase Current Sensing ............................... 81
Figure 22: Control Structure for DGM-02 w/o integrated Speed Governor Function ............. 90
Figure 23: Control Structure for DGM-02 with integrated Speed Governor Function ............ 90
Figure 24: Options to Connect a Positioner ............................................................................. 91
Figure 25: Fixed Starting Fuel Limitation.............................................................................. 100
Figure 26: Variable Starting Fuel Limitation ......................................................................... 102
Figure 27: Temperature-dependent Starting Fuel .................................................................. 103
Figure 28: Temperature-dependent Starting Fuel Limitation ................................................ 104
Figure 29: Starting Behaviour when Starting Speed Ramp is enabled .................................. 105
Figure 30: Speed-dependent Fuel Limitation ......................................................................... 107
17 List of Tables
Table 1: Map Structure ............................................................................................................. 32
Table 2: Versions meant for Generator-to-Busbar Applications ............................................. 37
Table 3: Version for Group-to-Group and Group-to-Mains Applications ............................... 39
Table 4: Overview of available Versions ................................................................................. 44
Table 5: Power Supply Input .................................................................................................... 53
Table 6: Digital Inputs.............................................................................................................. 54
Table 7: Digital Outputs ........................................................................................................... 57
Table 8: Configurable Digital Outputs ..................................................................................... 58
Table 9: PWM Outputs ............................................................................................................ 61
Table 10: Analogue Inputs ....................................................................................................... 64
Table 11: Configurable Analogue Inputs ................................................................................. 65
Table 12: Parameters for Analogue Inputs ............................................................................... 70
Table 13: Parameters for Temperature Input ........................................................................... 70
Table 14: Analogue Outputs .................................................................................................... 71
Table 15: Configurable Analogue Outputs .............................................................................. 72
Table 16: Speed Probe Input .................................................................................................... 76
Table 17: 3-Phase Voltage and 3-Phase Current Sensing ........................................................ 83
Table 18: Position Setpoint Output to Positioner ..................................................................... 91
Table 19: Speed Governor Parameters ..................................................................................... 94
Table 20: Speed Setpoint Switch Functions ............................................................................. 94
Table 21: Limiting Functions ................................................................................................. 106
Table 22: Offset Signal Output to Speed Governor ............................................................... 111
Table 23: Raise/Lower Signals to Speed Governor ............................................................... 111
Table 24: Offset Signal Output to AVR ................................................................................. 114
Table 25: Raise/Lower Signals to AVR ................................................................................. 115
Table 26: Priority of Commands for the Start-Stop Sequence ............................................... 119
Table 27: Start-Stop Phase and Phase of Generator Control ................................................. 121
Table 28: Output Parameters Start-Stop Sequence ................................................................ 122
Table 29: Engine Starting Sequence Settings ........................................................................ 124
Table 30: Engine Stopping Sequence Settings ....................................................................... 125
Table 63: Parameters of Load Switching Points for low Load .............................................. 182
Table 64: Parameters of Load Switching Points for high Load ............................................. 182
Table 65: Indicated Values of Real-Time Clock .................................................................... 183
Table 66: Indicated Values of Operating Data and Energy Measurement ............................. 184
Table 67: Parameters Synchronizing Governor ..................................................................... 196
Table 68: Parameters Active Load Governor ......................................................................... 198
Table 69: Parameters Voltage and Reactive Load Governor ................................................. 203
Table 70: Sensors ................................................................................................................... 216
Table 71: Sensor Sources ....................................................................................................... 217
Table 72: Sensor Measuring Ranges ...................................................................................... 219
Table 73: Sensor default Values in Case of Error .................................................................. 221
Table 74: Self-Latching Sensor Failure ................................................................................. 222
Table 75: Switching Functions Parameters ............................................................................ 223
Table 76: Switching Functions ............................................................................................... 226
Table 77: Switching Functions Sources ................................................................................. 227
Table 78: Bus Protocols ......................................................................................................... 229
Table 79: CAN Connections .................................................................................................. 229
Table 80: HZM-CAN Device Types ...................................................................................... 231
Table 81: HZM-CAN Baud Rate ........................................................................................... 233
Table 82: Cable Types for CAN Bus and Modbus ................................................................ 239
Table 83: Alarm Signals ......................................................................................................... 244
Table 84: Configuration Errors – Switching Functions Allocation ....................................... 249
Table 85: Configuration Errors – Sensor Allocation ............................................................. 249
Table 86: Configuration Errors – Speed Range ..................................................................... 249
Table 87: Configuration errors – Set Data ............................................................................. 250
Table 88: Configuration Errors – Communication Protocol HZM-CAN PE......................... 250
Table 89: Configuration Errors – Communication Protocol CANopen ................................. 250
Table 90: Configuration Errors – Communication Protocol Modbus .................................... 250
Table 91: Configuration Errors – Communication Protocol DeviceNet ................................ 250
Table 92: Configuration Errors – Communication Protocol SAE-J1939 .............................. 251
Table 93: Configuration Errors – Communication Protocol HZM-CAN CM ....................... 251
Table 94: Parameter Groups ................................................................................................... 275
THESEUS Installation & Commissioning Guide 379
17 List of Tables
18 Download of Manuals
Technical manuals can be downloaded in pdf-format from our homepage:
www.heinzmann.com.
If the desired manual should not be available there, send an e-mail to:
[email protected]
or write to:
HEINZMANN GmbH & Co. KG
Technische Redaktion
Am Haselbach 1
D-79677 Schönau/Germany
We would be pleased to receive your comments about the contents and presentation of our
publications.
Send your comments to the e-mail or address shown above please.
Version Information
Chapter 10 Sensors added and chapter 6.5 Analogue Inputs Dec 07 DiD, DeM,
revised ShD
Chapter 17 List of Tables added Dec 07 DeM
Chapter 11 Switching Functions added and chapter 6.2 Digital Dec 07 DiD, DeM
Inputs revised
Chapter 6.3 Digital Outputs revised Dec 07 DiD, DeM
Chapter 6.9 Communication Interfaces replaced by chapter 12 Bus Jan 08 DiD, DeM
Protocols and chapter 9.4 DeviceNet, Modbus, SAE-J1939
replaced by chapter 12.6 Networks with DeviceNet, Modbus,
SAE-J1939, CANopen
Chapter 13 Data Management added Jan 08 DiD, DeM
Chapter 2.2 General System Description and 2.7 Level added Jan 08 DiD
Chapter 6.8 Analogue Load Share Lines moved to 7.11 Analogue Jan 08 DiD
Load Share Line
Chapter 6.8 Voltage, Current and Load Measurement revised Jan 08 DiD, DeM
Chapter 7.2.8 Start Fuel Adjustment renamed in 7.2.8 Starting Jan 08 DeM
Fuel Limitation and revised
Chapters 7.2.5 Speed Setpoint Determination, 7.2.6 Speed Ramp Jan 08 DeM
and 7.2.7 Droop added
Chapter 7.2 Integrated Speed Governor revised Jan 08 DeM, ShD
Chapter 7.3 Offset Signal to external Speed Governor revised Jan 08 DeM, ShD
Chapter 7.11 Analogue Load Share Line revised Feb 08 DiD, ShD
Chapter 7.13 Protections revised and chapter 7.13.4 List of Feb 08 DiD
Protective Functions added
Chapter 7.14 Warning and Emergency Shutdown Functions added Feb 08 DiD
Chapter 7.16 Real-Time Clock and Operating Data Memory added Feb 08 DiD
Chapter 8.1 Speed Governor revised and sub chapter added Feb 08 DiD
Chapters 5.3.1 Retrofit Kit for Marine Applications and Mar 08 DiD
5.3.2 CAN Repeater CR-01 added
Chapter 7.12 Connection to Dead Busbar added Mar 08 DiD
10-10 Alarm indication 3040 ErrCloseToLimit replaced by status bit Jan 09 DiD, DeM
indication 12338 LoadLimitActive, refer to chapter 7.9 Load
Limitation
Alarm indication 13007 ErrLostSyncRelease deleted without Jan 09 DeM
replacement
Alarm description and response for 13001 ErrGCB_Status and Jan 09 DeM
13002 ErrMCB_Status updated in the chapter 14.7 Error
Parameter List
Chapter 13.4 Check-Sum over Parameter Values of the Jan 09 DeM
Configuration and chapter 15 Parameter Description updated
Chapter 15.1 Synoptic Table renamed in 15.1 General and revised Jan 09 DeM
Chapter 7.14.9 Load Control Deviation and alarm description for Mar 09 DiD, DeM
13070 ErrLoadControlDiff in chapter 14.7 Error Parameter List
added
Table 4: Overview of available Versions updated Apr 09 DeM
Chapter 7.14.3 Exhaust Gas Temperature Warning added and March 2010 DeM
alarm description for 3041 ErrExhaustTempWarn added in chapter
14.7 Error Parameter List
Sensor values for coolant pressure and auxiliary coolant pressure, March 2010 DeM
chapter 7.14.5 Speed-dependent Coolant Pressure Monitoring
added and alarm description for 3044 ErrCoolantPressWarn and
3046 ErrAuxCoolPressWarn added in chapter 14.7 Error
Parameter List
Sensor value for fuel pressure, chapter 7.14.6 Fuel Pressure March 2010 DeM
Monitoring added and alarm description for
3042 ErrFuelPressWarn added in chapter 14.7 Error Parameter
List
Chapter 7.14.8 Generator Temperature Warning added and alarm Aug 2010 DeM
description for 3048 ErrGenTempWarn added in chapter
14.7 Error Parameter List
Chapter 8.1.2 PID Map updated Sep 2010 DeM
Various parameter names changed, which were adapted for the Sep 2010 DeM
DcDesk functionality "Clear text for bit parameters"
Relay output listed in chapter 6.3 Digital Outputs Sep 2010 DiD, DeM
Sub chapters added in chapter 6.8 Voltage, Current and Load Sep 2010 DeM
Measurement
Chapter 6.8.2 Basic Settings for the Voltage and Frequency Sep 2010 DiD, DeM
Measurement updated
Minor modifications in the chapters 2.2.5 RS-485 / Modbus Sep 2010 DiD, DeM
Communication, 6.8.3 Basic Settings for the Current and Load
Measurement, 7.4.2 Connection via Raise/Lower Signals and
7.6 Circuit Breaker I/Os
Chapter 7.5.4 Engine Starting and Stopping Sequence Settings Sep 2010 DiD, DeM
updated
Chapter 7.6.3 Release / Trip Relay updated Sep 2010 DeM
Chapter 7.6.1.2 External Closing and Opening of the Circuit Sep 2010 DiD, DeM
Breaker, 7.7.3 External Phase Difference and 7.7.8 Automatic
Synchronization in Manual Mode added
Chapter 7.12 Connection to Dead Busbar updated Oct 2010 DiD, DeM
Alarm response 23077 ErrFailedToUnLoad corrected in the Oct 2010 DiD, DeM
chapter 14.7 Error Parameter List
Alarm description for 23084 ErrGenericWarning added in chapter Oct 2010 DeM
14.7 Error Parameter List
Chapter 7.2.7 Droop updated Oct 2010 DeM
Alarm response 3070 ErrCanBus1 and 3072 ErrCanBus2 Oct 2010 DeM
corrected for Group-to-Group application in the chapter 14.7 Error
Parameter List
Chapter 6.7 Speed Sensing including subchapters updated Oct 2010 DeM
Chapter 7.3 Offset Signal to external Speed Governor updated Oct 2010 DeM
Chapter 7.8.3 Generators with Group-to-Mains Device revised and Oct 2010 DeM
subchapter 7.8.3.1 Power Plant's Gross Load Setpoint added
Some minor modifications Oct 2010 DeM
05-12 Warning notices and chapter 1 Safety Instructions and related April 2012 HaF, DeM
Symbols updated
Chapter 2.1 Proper and intended Use added April 2012 HaF, DeM
Figure 34: Analogue Signal to AVR updated April 2012 ShD, DeM
Det Norske VeritasType Approval Certificate No. updated April 2012 DeM
Subitem Environmental Tests in Chapter 5 Specifications updated April 2012 ShD, DeM