7SJ6X
7SJ6X
7SJ6X
Overcurrent Protection
7SJ61/62/64
Protection
4-lines Display
7SJ61/2/4
7SJ63/64
Protection + Local Control
Integrated Grafic Display
7SJ63/64 7SJ63/64
7SJ63/64
Protection + Local Control
Flexible Mounting of
Grafik-Display
7SJ63/64 7SJ63/64
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 2
Protection & Control Relays SIPROTEC 4
System features
Multifunctional protection/control/automation/metering
Ergonomically improved HMI (e.g. functions keys)
New Operation Program (DIGSI4)
Wide range of Communication Features
Fault Records and Event Records
Improved Self Monitoring (battery voltage supervision)
Plausibility Checks
Operational measured Values incl. further processing
Full recovery of device status after power supply failure (no loss of
data)
Increased EMC withstand level (fast transient class 4)
Illuminated LCD
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 3
Protection & Control Relays SIPROTEC 4
System features
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 4
Protection & Control Relays SIPROTEC 4
Human Machine Interface
Control Keys
Key Switches
Local operating Interface
Function Keys
Numerical Keypad
Function Key can be used for Control purpose
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 5
7SJ61 Scope of Functions
busbar
52 RTD box
Local-Remote-Control Interface
Command / Feedback
Trip circuit Lock out PLC-Logic
supervision
&
74TC 86
Communication-
Meter
HMI modules
Fault Recording
RS232/485
Fiber
I, Set points
IEC60870-5-103 Energy meter
Profibus FMS impulse
Profibus DP
Motor protection
I>> I>, Ip IE>> IE>, IEp I2> I< Start up monitor
Inrush-
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86
failure protection
IE>> IE>, IEp 14 locked Lock out
Breaker-- Rotor
Auto
50N 51N reclosing
79M
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 6
7SJ62 Scope of Functions
busbar
Meter
HMI Communication- Fault Recording U, P, Q,
modules f, cos
RS232/485 I, Set points
Fiber
Energy meter
failure protection
IEC60870-5-103 calculated
Profibus FMS impulse
Breaker--
Inrush-
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86 67 67N
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 7
7SJ63 Scope of Functions
busbar
Meter
HMI Communication- Fault Recording U, P, Q,
modules f, cos
RS232/485 I, Set points
Fiber
Energy meter calculated
failure protection
IEC60870-5-103
Profibus FMS impulse
Breaker--
Inrush-
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86 67 67N
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 8
7SJ64 Scope of Functions
busbar
failure protection
Profibus FMS impulse
Breaker--
I>> I>, Ip IE>> IE>, IEp I2> I< Protection
Motor Start up monitor
Inrush- 67N
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86 67
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 9
SIPROTEC 7SJ61 / 7SJ62 / 7SJ63 / 7SJ64
Scope of functions (1)
* not in 7SJ61
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 10
SIPROTEC 7SJ61 / 7SJ62 / 7SJ63 / 7SJ64
Scope of functions (2)
Service Port/ C
Thermo Box
System/Scada B
Time Syn A
Front port
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 13
7SJ61/62/63/64 with RTD box(es) 7XV5662
for Overload/Temperature Supervision
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 15
SIPROTEC 4
7SJ61/62/63/64 V4.4
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 16
SIPROTEC 4
7SJ64
Hardware
Additional serial interface (port D) is available (e.g. for RTD device)
One type (7SJ641) provides the possibility for a NC contact
Significant more CFC capacity compared to 7SJ61/62/63
(PLC ~ factor 2; PLC1 ~ factor 6; MV and Interlocking ~ factor 5)
Basic functionality
like 7SJ62/63 V4.4 plus synchronizing function
Synchronizing function
Synchronous and Asynchronous Switching
Synchrocheck
Four different synchronising parameter sets are available
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 17
7SJ61, 7SJ62 , 7SJ63 and 7SJ64
Overcurrent Protection Highlights
Enhanced performance
Modern tools (CFC) and diverse protection and
supplementary functions allow the implementation of
customised and adaptive protection schemes for difficult
applications
Parameter set change-over, cold load pick-up and user
defined characteristics are but a few of the specialised
features
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 18
7SJ61, 7SJ62 , 7SJ63 and 7SJ64 Overcurrent Prot.
Highlights
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 19