SIPROTEC 4 7SJ61/62/63/64

Overcurrent Protection

7SJ61/62/64
 Protection
 4-lines Display
7SJ61/2/4

7SJ63/64
 Protection + Local Control
 Integrated Grafic Display

7SJ63/64 7SJ63/64

7SJ63/64
 Protection + Local Control
 Flexible Mounting of
Grafik-Display

7SJ63/64 7SJ63/64

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 2
Protection & Control Relays SIPROTEC 4
System features

 Multifunctional protection/control/automation/metering
 Ergonomically improved HMI (e.g. functions keys)
 New Operation Program (DIGSI4)
 Wide range of Communication Features
 Fault Records and Event Records
 Improved Self Monitoring (battery voltage supervision)
 Plausibility Checks
 Operational measured Values incl. further processing
 Full recovery of device status after power supply failure (no loss of
data)
 Increased EMC withstand level (fast transient class 4)
 Illuminated LCD

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 3
Protection & Control Relays SIPROTEC 4
System features

 Enhanced metering & statistical functions


 Remote and local Interrogation with separate interfaces
 Freely programmable I/O´s and LED´s
 Robust Terminal Blocks with CT Shorting Facilities
 Real time clock with synchronisation
(via IEC or binary input or IRIG B interface)
 PLC Logic (Continuous Function Chart CFC)
 Freely programmable Mimic Display (for 7SJ63 & 7SJ64 )
 Freely programmable function keys
 Key switches for local/remote and interlocking (for 7SJ63 &
7SJ64 )
 Full bay RTU functionality (full control & monitoring)

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 4
Protection & Control Relays SIPROTEC 4
Human Machine Interface

Run and Error LED’s


Large illuminated Display
Cursor Keys

LED’s with reset Key

Control Keys

Key Switches
Local operating Interface
Function Keys

Numerical Keypad
Function Key can be used for Control purpose

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 5
7SJ61 Scope of Functions

busbar

52 RTD box
Local-Remote-Control Interface
Command / Feedback
Trip circuit Lock out PLC-Logic
supervision
&
74TC 86

Communication-
Meter
HMI modules
Fault Recording

RS232/485
Fiber
I, Set points
IEC60870-5-103 Energy meter
Profibus FMS impulse
Profibus DP
Motor protection
I>> I>, Ip IE>> IE>, IEp I2>  I< Start up monitor
Inrush-
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86

failure protection
IE>> IE>, IEp 14 locked Lock out
Breaker-- Rotor
Auto
50N 51N reclosing
79M

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 6
7SJ62 Scope of Functions

busbar

52 RTD box Voltage


Local-Remote-Control Interface
f<> V> V<
Command/Feedback Directional
Trip circuit Lock out Phase rotation
PLC-Logic 81O/U 59 27
supervision Fault Locator
&
74TC 86 21FL
47

Meter
HMI Communication- Fault Recording U, P, Q,
modules f, cos 
RS232/485 I, Set points
Fiber
Energy meter

failure protection
IEC60870-5-103 calculated
Profibus FMS impulse
Breaker--

I>> IE>> IE>, IEp I2>  Motor


I<
Protection
Start up monitor
I>, Ip

Inrush-
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86 67 67N

IE>> IE>, IEp 14 locked Lock out


IEE>> UE>
Rotor
IEE>
Auto
50N 51N 79M
reclosing S67N S64
Dirct. sens. Ground fault

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 7
7SJ63 Scope of Functions

busbar

52 Local-Remote-Control RTD box Voltage


Interface
Command/Feedback
Trip circuit Lock out
f<> V> V< Directional
supervision Phase rotation
PLC-Logic Fault Locator 81O/U 59 27

Motor & 21FL


33 74TC 86
control 47

Meter
HMI Communication- Fault Recording U, P, Q,
modules f, cos 
RS232/485 I, Set points
Fiber
Energy meter calculated

failure protection
IEC60870-5-103
Profibus FMS impulse
Breaker--

I>> IE>> IE>, IEp I2>  Motor


I<
Protection
Start up monitor
I>, Ip

Inrush-
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86 67 67N

IE>> IE>, IEp 14 locked Lock out


Rotor IEE>> UE>
Auto IEE>
50N 51N reclosing 79M
S67N S64
Dirct. sens. Ground fault

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 8
7SJ64 Scope of Functions

busbar

52 RTD box Synchronizing


Voltage
Local-Remote-Control Interface
Command/Feedback 25
Trip circuit Lock out f<> V> V<
supervision
PLC-Logic Fault Locator 81O/U 59 27

Motor & 21FL


33 74TC 86 Directional
control 47

Meter Phase rotation


HMI Communication- Fault Recording U, P, Q,
modules f, cos 
RS232/485 I, Set points
Fiber

IEC60870-5-103 Energy meter calculated

failure protection
Profibus FMS impulse

Breaker--
I>> I>, Ip IE>> IE>, IEp I2>  I< Protection
Motor Start up monitor

Inrush- 67N
50 51 50N 51N 46 49 blocking 50BF 37 48 66/86 67

IE>> IE>, IEp locked Lock out


14 IEE>> UE>
Rotor
Auto IEE>
50N 51N reclosing 79M
S67N S64
Dirct. sens. Ground fault

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 9
SIPROTEC 7SJ61 / 7SJ62 / 7SJ63 / 7SJ64
Scope of functions (1)

Overcurrent Protection ANSI No.


 Definite-time overcurrent- and earth fault protection 50,50N
 Inverse-time overcurrent- and earth fault protection 51,51N
 Breaker failure protection 50BF
 Phase unbalance current protection 46
 Thermal overload protection 49
 Starting time supervision 48
 Auto reclosure 79
 Directional overcurrent- and earth fault protection* 67,67N
 Directional*/non-directional sensitive earth fault detection 67Ns/50Ns
 Phase sequence* 47
 Displacement voltage* 64

* not in 7SJ61
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 10
SIPROTEC 7SJ61 / 7SJ62 / 7SJ63 / 7SJ64
Scope of functions (2)

Overcurrent Protection ANSI No


 Locked rotor protection 14
 Restart inhibit 66/68
 Under current monitoring 37
 Temperature monitoring (via ext RTD box) 38
 Undervoltage / overvoltage protection* 27/59
 Overfrequency / underfrequency protection* 81 O/U
 Synchronizing** 25
 Fault Locator* 21 L
 Trip circuit supervision 74C
 Lock Out 86
 Intermitten earth fault

* not in 7SJ61 ** only in 7SJ64


Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 11
SIPROTEC 7SJ61 / 7SJ62 / 7SJ63 / 7SJ64
Scope of functions (3)

 Measured value processing, max demand, metered value


 Serial communication interface
 Connection to RTD (resistance temperature detector) interface
 Several setting groups
 Fault recorder
 Metering pulse processing
 CB control
 Programmable function key
 Feeder control mimic diagram***
 Control key***
 Interlocking using CFC

*** only in 7SJ63 / 64


Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 12
Connection Diagram: Example 7SJ62

Service Port/ C
Thermo Box

System/Scada B

Time Syn A

Therm Box D only 7SJ64

Front port

Version Width No. Of No. Of Power


binary Output Output
inputs relays relays
7SJ61 1/3 3/8/11 4/8/6
7SJ62 1/3 8/11 8/6
7SJ63 1/2 11/24/20 8/11/11 -/4/4
1/1 37/33 14 / 14 8/-
7SJ64 1/3 7 5
1/2 15/20 13/8 4 (2)
1/1 33 11 8 (4)

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 13
7SJ61/62/63/64 with RTD box(es) 7XV5662
for Overload/Temperature Supervision

FO - connection to service interface O


OR RS485
RS485 connection to service interface

 Connection of up to 2 RTD devices to the service interface


(FO or RS485 bus)
 Monitoring of up to 12 measuring points (6 per RTD device) -
Two thresholds are programmable with DIGSI (as inputs to the
logic editor)
Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 14
SIPROTEC 4
7SJ61/62/63/64 V4.4

New Functions (1)


 Intermittent Earth Fault protection

 Temperature detection via external RTD-device


 Up to 2 RTD-devices with a total of 12 measuring points can be
connected to the relay
 via RS485. For every measured value two settable thresholds are
programmable

 Sensitive Ground Fault protection function can operate as a


sensitive function 67Ns (as up to now) and as additional
normal earth fault protection (50N, 51N):
3 Ph + I E(meas) + I E(cal) or 3 PH + I EE(meas) + I E(cal)
 Second stage for Overvoltage protection

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 15
SIPROTEC 4
7SJ61/62/63/64 V4.4

New Function (2)


 Improvement of Automatic Reclosing functionality

 Various extensions of setting ranges (Voltage protection, ...)

 New CFC function blocks (e.g.: +, -, *, /)

 7SJ61/62: two NC contacts possible (adjustable via jumper)

 Upgrade of former parameter sets is possible


This function allows the upgrade of versions V4.2
parameter sets to version V4.4.
Consistent parameters and indications are maintained.
Different and new parameters are logged in a delta list.

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 16
SIPROTEC 4
7SJ64

 Hardware
 Additional serial interface (port D) is available (e.g. for RTD device)
 One type (7SJ641) provides the possibility for a NC contact
 Significant more CFC capacity compared to 7SJ61/62/63
(PLC ~ factor 2; PLC1 ~ factor 6; MV and Interlocking ~ factor 5)

 Basic functionality
 like 7SJ62/63 V4.4 plus synchronizing function

 Synchronizing function
 Synchronous and Asynchronous Switching
 Synchrocheck
 Four different synchronising parameter sets are available

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 17
7SJ61, 7SJ62 , 7SJ63 and 7SJ64
Overcurrent Protection Highlights

 One device contains all the protection functions


required in the bay
 From basic overcurrent to full directional over-current
measurement with supplementary protection functions
ranging from over and under-voltage, over and under-
frequency, breaker failure to trip circuit supervision all in one
device and also serial interface to RTD device.

 Enhanced performance
 Modern tools (CFC) and diverse protection and
supplementary functions allow the implementation of
customised and adaptive protection schemes for difficult
applications
 Parameter set change-over, cold load pick-up and user
defined characteristics are but a few of the specialised
features

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 18
7SJ61, 7SJ62 , 7SJ63 and 7SJ64 Overcurrent Prot.
Highlights

 Stable performance with numerical techniques


 Well proven numerical techniques and filtering are used to
surpress hormonics and reduce the influence of DC
components of the measurement and achieve reproducable
performance
 Frequency adaptation algorithm is implemented to ensure
accurate measurements and protection operating
characteristics in case of moving frequencies.

Module 10A: Bay Management Device 7SJ61/62/63/64 TASK FORCE SIPROTEC 4 Page - 19