Alarm and Fault Finding

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

LOPX Separation System

Alarms and Fault Finding

Printed Nov 1998


Book No. 1810144-02 V5

Alfa Laval Marine & Power


Alfa Laval reserve the right to make changes at any time without
prior notice.
Any comments regarding possible errors and omissions or
suggestions for improvement of this publication would be
gratefully appreciated.
Copies of this publication can be ordered from your local
Alfa Laval company.
Published by: Alfa Laval Marine & Power AB
S - 147 80 Tumba
Sweden
© Copyright Alfa Laval Marine & Power AB 1998.
Study instruction manuals and observe the
warnings before installation, operation,
service and maintenance.

Not following the instructions can result in


serious accidents with fatal injuries.

P000272A
In order to make the information clear only foreseeable conditions have
been considered. No warnings are given, therefore, for situations
arising from unintended usage of the machine and its tools.

A summary of the safety information is found in the Safety chapter


under divider 1.
Contents

1 Scope 1 4 Alarm Tests 25

2 EPC Signs 3 5 Test Program 27

3 Alarms 5 5.1 How to Start the


Test Program 27
3.1 Alarm Functions 5
5.2 Lamp Test 28
3.2 Alarm Reset 6
5.3 How to Activate Different
3.3 Alarm Survey 7 Parts of the Test Program 28

3.4 LED Alarms and Fault Finding 8 5.4 Functions in the Test Program29
3.4.1 High Oil Pressure 8
3.4.2 Low Oil Pressure (Low Flow) 9
3.4.3 Sludge Discharge Failure 10
3.4.4 Water Transducer Fault 11
3.4.5 Emergency Stop 12
3.4.6 Vibrations (Option) 13
3.4.7 Heater Fault 14

3.5 LED and Display Alarms and


Fault Finding 15
3.5.1 High or Low Oil Temperature
(Option) 15
3.5.2 Temperature Sensor Error
(Option) 16

3.6 Display Alarms and Fault


Finding 17
3.6.1 Communication Error 17
3.6.2 Processor Fault 18
3.6.3 Programming Error 18
3.6.4 Power Failure 19
3.6.5 Temperature Deviation 20
3.6.6 ALCAP Alarms 21
3.6.7 Other Alarms 23
3.6.8 Countdown Timer Alarm 23

1810144-02
1810144-02
1 Scope

The alarms, alarm tests and the test program


are valid for the following separation systems:

LOPX 705
LOPX 707

LOPX 709
LOPX 710

LOPX 713

LOPX 714

Including the EPC-400 control unit with


PROM (memory chips):

PROM (front circuit board):31830-6210-1


PROM (rear circuit board):31830-6132-1

1810144-02 1
1 Scope LOPX Alarms and Fault Finding

2 1810144-02
2 EPC Signs

The control unit signs for the LOPX


separation system are shown in this chapter.

P000661A
Monitoring functions

P000652A

Monitoring functions (options)

1810144-02 3
2 EPC Signs LOPX Alarms and Fault Finding

P000631A
Output signals

P000642A

Operating symbols

4 1810144-02
3 Alarms

3.1 Alarm Functions


The alarm system is designed to ensure that
the separation system always remains in a safe
state. There are two different types of alarm
functions:
• Sensor-related alarm functions are
indicated by light emitting diodes (LEDs)
on the EPC-400.
• Display-related alarm functions are
indicated on the EPC-400 display. When
any of the displayed alarm functions are
activated the left digits start flashing and
the right digits are steadily lit.

If there is more than one alarm at the same


time, the EPC-400 will display the alarms in
the order in which they occurred.

G044204A

An activated alarm condition is identified either by an alarm LED (to the left in the
picture) or an alarm code on the display together with the main alarm LED (to the
right in the picture).

1810144-02 5
3 Alarms LOPX Alarms and Fault Finding

3.2 Alarm Reset


1. Acknowledge the alarm signal by pressing
the alarm push-button.
The flashing light then changes to steady.

G001645A
2. Remedy the cause.
3. Reset the alarm function by pressing the
alarm push-button a second time.
The LED will turn off.

G001647A
It is possible to reset the system without
remedying the cause, but the alarm signal will
be repeated.

NOTE

Never return to the EPC-400 control


unit to acknowledge or reset an alarm
if it by any means can be hazardous.

WARNING

Disintegration
hazard

Never reset an alarm without first


finding and remedying the cause.

6 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.3 Alarm Survey


LED Display Alarm function Page
alarms alarms

High Oil Pressure 8

Low Oil Pressure (Low Flow) 9

Sludge Discharge Failure 10

Water Transducer Fault 11

Emergency Stop 12

Vibrations (Option) 13

Heater Fault 14

High or Low Oil Temperature (Op-


15
tion)

Temperature Sensor Error (Op-


16
tion)

Communication Error 17

Processor Fault 18

Programming Error 18

Power Failure 19

Temperature Deviation 20

ALCAP Alarms 21

Other Alarms 23

Countdown Timer Alarm 23

1810144-02 7
3 Alarms LOPX Alarms and Fault Finding

3.4 LED Alarms and Fault


Finding

3.4.1 High Oil Pressure

S001801A

Cause Corrective action

Regulating valve, RV4, or other valves, downstream Open or regulate RV4, or other valves, to correct back
throttled or closed. pressure, normally about 1.5 bar (150 kPa).

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode (PS41) flashes. Alarm diode off.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.

8 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.4.2 Low Oil Pressure (Low Flow)

S001802A
Causes Corrective actions

Too low oil feed. Check the oil feed pump.


Adjust the oil flow.

Strainer before the oil feed pump is clogged. Clean the strainer.

Oil feed pump has stopped. Check the oil feed pump.

Change over valve (V1) is in recirculation position. 1. Check the air supply to the solenoid valve block air
(MV1).
2. Check MV1.
3. Check V1.

Too low back pressure. Increase the back pressure with regulating valve RV4.
The correct back pressure is normally about 1.5 bar
(150 kPa).

Bowl opened accidentally during operation. Check the opening water valve (MV15) for leakage.
See “Separator Manual”.

Leakage from bowl. See “Separator Manual”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode (PS42) flashes. Alarm diode off.

V1 is set for oil recirculation. V1 is set for oil feed to separator.

1810144-02 9
3 Alarms LOPX Alarms and Fault Finding

3.4.3 Sludge Discharge Failure

I000682A
Causes Corrective actions

No or very low opening water supply. Check the water supply system:
11 litres/min are required for LOPX 705
18 litres/min are required for LOPX 707,709,710, 713 &
714.

Opening water valve (MV15) damaged. Check MV15.

No signal from low oil pressure switch (PS42) at dis- Check PS42.
charge.

Separator operating system not working. 1. Check the separator by manually opening MV15 for
discharge.
2. Dismantle and check the operating system. See
“Separator Manual”.

Dosing ring tightened too much. Tighten the dosing ring screws with a torque of 7 Nm for
LOPX 705
Tighten the dosing ring screws with a torque of 20 Nm for
LOPX 707,709,710, 713 & 714.

N.B. This alarm is activated after two attempts to discharge, within the same discharge cycle, have failed.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode flashes. Alarm diode off.

The stop sequence is initiated. 1. If the power has been off for more than about 10
minutes the separator bowl must be stopped and
manually cleaned before restart.
2. The separator and the EPC program have to be
restarted.

10 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.4.4 Water Transducer Fault

S000261A
Causes Corrective actions

Loose connection between transducer test circuit Check connections.


board and oscillator.

Faulty oscillator unit or faulty EPC control module. Check supply voltage in the MT4 on terminal 3 - 4 (20 V
DC).
About every fifth second the voltage at terminal 4 - 5 (20
V DC) will drop for approx. 0.5 second:
• If voltage drop: replace the oscillator unit.
• If no voltage drop: replace the EPC control module.
For more information about the interconnections, see
“System Reference”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode flashes. Alarm diode off.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.

1810144-02 11
3 Alarms LOPX Alarms and Fault Finding

3.4.5 Emergency Stop

S003911A
Cause Corrective actions

Emergency stop button has been pushed. 1. Remedy the cause for the emergency stop.
2. Reset the alarm by switching the power off and on.
3. Restart the separator.
4. Restart the EPC program.

Automatic actions at alarm Automatic action after alarm reset

Main alarm flashes. N.B. This alarm function can not be reset by pushing
the alarm reset button. See above.
Alarm diode flashes.

The separator is stopped and the heater turned off.

Oil feed through the heater and separator stays on for


max. 3 minutes, or until FS4 signals no flow. Bowl
closing water supplied for 15 seconds.

DANGER

Disintegration
hazard

The separator bowl must be manually


cleaned before starting up again

12 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.4.6 Vibrations (Option)

S000111A
Cause Corrective actions

Vibration switch activated: separator bowl out of bal- 1. Remedy the cause. See “Separator Manual”.
ance. Check the vibration switch setting.
2. Reset the alarm by switching the power off and on.
3. Clean the separator bowl.
4. Restart the separator.
5. Restart the EPC program.

Automatic actions at alarm Automatic action after alarm reset

Main alarm flashes. N.B. This alarm function can not be reset by pushing
the alarm reset button. See above.
Alarm diode flashes.

The separator is stopped and the heater turned off.

Oil feed through the heater and separator stays on for


max. 3 minutes, or until FS4 signals no flow. Bowl
closing water supplied for 15 seconds..

DANGER

Disintegration
hazard

The separator bowl must be manually


cleaned before starting up again

1810144-02 13
3 Alarms LOPX Alarms and Fault Finding

3.4.7 Heater Fault

I000221A
N.B. Heater fault is only activated if the heater is controlled by the EPC-400.

Cause Corrective action

Oil flow stopped or temperature switch tripped in an If oil flow stopped, investigate the cause.
installed Heatpac heater. See corrective actions for PS42.
Check the flow switch on the Heatpac heater.
If temperature switch tripped, investigate the tempera-
ture switch setting. If OK check that the heater is clean.

Clogged heater. Clean heater.

Safety switch for other type of electric heater or steam Remedy the cause.
heater tripped.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode flashes. Alarm diode off.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.

Heater switched off. Heater switched on.

14 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.5 LED and Display


Alarms and Fault
Finding

3.5.1 High or Low Oil Temperature


(Option)
S000141A
S000121A

N.B. Also applicable to TT2 temperature sensor, if fitted.

Causes Corrective actions

Low temperature alarm when: Investigate the reason and remedy it.
- clogged heater
- insufficient steam supply
- faulty steam trap
- faulty steam supply valve
- electrical fault (tripped fuse)

High temperature alarm when: Investigate the reason and remedy it.
- faulty steam supply valve
- electrical control system out of action

Set point (P7) changed or the alarm limits are too 1. Adjust the parameters.
close to the set point. P5 = max. temp
P6 = min. temp
P7 = set point.
See “Parameter List”.
2. Check the temperature control loop.

Steam control valve (SRV1) open or closed too much. 1. Check and adjust the SRV1 function.
2. Check the EPC output functions.

Low temperature alarm when the temperature in- Check the heater and parameter P41, See “Parameter
creases too slowly, during start-up. List”.

Pt 100 temperature signal faulty. Check the Pt 100 temperature sensor.

N.B. The current temperature is indicated when the alarm is acknowledged. To find the appropriate
temperature sensor reading, push the alarm reset button twice 1C (1F) = TT1, 2C (2F) = TT2.
For more information, see “Operating Instructions”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode and displayed value flash. Alarm diode off and display returned to normal.

Oil feed (MV1) off. MV1 on.

Heater switched off at high temperature (if controlled Heater switched on when temperature is below set point
by EPC-400). (if heater is controlled by EPC-400).

1810144-02 15
3 Alarms LOPX Alarms and Fault Finding

3.5.2 Temperature Sensor Error


(Option)
S000121A

S000131A
N.B. Also applicable to TT2 temperature sensor, if fitted.

Causes Corrective actions

Temperature sensor is incorrectly connected. Check the temperature sensor by the test program, see
‘‘Analog inputs’’ on page 32 in the chapter Test Program.

Temperature sensor loop is open or short-circuit. Check the connections.

Temperature sensor cables are too close to power ca- Check the cables between the temperature sensor and
bles. EPC-400.

N.B. Push the alarm reset button to find appropriate process value reading.
1C (1F) = TT1, 2C (2F) = TT2. If both temperature sensors are fitted, alarm A6 is also activated.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode and displayed value flashes. Alarm diode off and display returned to normal.

Oil feed (MV1) off. MV1 on.

Heater switched off at high temperature (if controlled Heater switched on when temperature is below set point
by EPC-400). (if heater is controlled by EPC-400).

16 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.6 Display Alarms and


Fault Finding

3.6.1 Communication Error

S000151A

Alarm code Cause Corrective actions

Communication error with exter- 1. Check external and internal


I001191A

nal computer. connections.


2. If internal communication error,
replace the control module.

Communication error between 1. Check by measurement the fuses


I001105A

front and rear circuit board. A1:F2 (front board), A2:F2 (rear
board).
(See “Component Description,
EPC-400 Control Unit”).
2. Replace the control module.

Automatic action at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

1810144-02 17
3 Alarms LOPX Alarms and Fault Finding

3.6.2 Processor Fault

S000161A
Alarm codes Causes Corrective actions

Internal RAM error. Replace control module.


I001091A

External RAM error. Replace control module.


I001106A

E2 RAM error. Replace control module.


I001092A

Program error. Replace control module.


I001093A

Mode switch error. Check that the mode selector is in the cor-
I001096A

rect position.

A / D (Analog / Digital) conversion Check the fuse A1:F2 (front board)


I001094A

error. If the fuse is correct, replace the control


module.

Calibration error. Ask for service or replace the control mod-


I001095A

ule.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

3.6.3 Programming Error


S000171A

Alarm code Cause Corrective action

In programming mode too long Change the mode selector to the


I001108A

(more than 30 minutes without “L” (Local) position and, when appropriate,
programming during this time). return to the “P” (Programming) position
and continue with programming.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

18 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.6.4 Power Failure

S000181A
Alarm codes Causes Corrective actions
I001103A Power failure. 1. Check the power supply.
2. If the power has been off more than
about 10 minutes the separator bowl
must be stopped and manually
cleaned before restart.
3. Restart the heater, separator and
EPC program.

Power supply frequency too high 1. Check the power supply.


I001104A

(more than + 5%).1


2. If the power has been off more than
about 10 minutes the separator bowl
must be stopped and manually
cleaned before restart.
3. Restart the heater, separator and
EPC program.

Automatic actions at alarm Automatic actions after alarm reset

All outputs are off.

Only valid for alarm A4-1: Only valid for alarm A4-1:
Main alarm diode and display Main alarm off.
start to flash when power returns. Display indicates “OFF”.

Only valid for alarm A4-2: Only valid for alarm A4-2:
Main alarm flashes. Main alarm off.
Display flashes. Display normal.

1. The frequency deviation must be continuous or repeated during the alarm delay time before an alarm is acti-
vated.

1810144-02 19
3 Alarms LOPX Alarms and Fault Finding

3.6.5 Temperature Deviation

Alarm code S000191A Cause Corrective actions

Temperature deviation alarm (dif- At commissioning:


I001109A

ference between TT1 and TT2 is Check if the distance between


more than 30 °C/54 °F). sensors is too great.
System in operation:
Check the temperature sensors.

N.B. Push the alarm reset button to find the appropriate process value reading 1C (1F) = TT1,
2C (2F) = TT2. For more information, see “Operating Instructions”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

20 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.6.6 ALCAP Alarms

S000211A
Alarm codes Causes Corrective actions
High water transducer (MT4) val-
I001111A
ue (above 400):

• High water content in oil. Check the oil system for water leakage.
• Water transducer dirty. Clean the contact surfaces of water trans-
ducer. See “Component Description, Wa-
ter Transducer”.
Low water transducer (MT4) val-
I001112A

ue (below 100):

• Open circuit in the MT4. 1. Check connections in control unit and


transducer.
2. Check cables for damage.
• Bad connection between 1. Check the cable connection.
oscillator unit and electrode.
2. Tighten oscillator electrode connector
ALCAP stand-by for more than 1. The reason for stand-by mode must
I001113A

24 hours. be checked!
2. Try to operate the system normally.
PROM and/or RAM fault. Replace control module.
I001115A

Water transducer trigger value 1. System and component check:


I001116A

less than 30.


• Check that the valve block strainer is
Insufficient displacement water.
free from deposits.
Insufficient conditioning water.
• Check that the displacement water
flow from MV10 is correct.
• Check that the inner water pipe in the
separator inlet pipe is free from
deposits. Clean if necessary.
• Check that the seal ring and sealing
surface on the sliding bowl bottom are
free from any damage.
2. If the alarm still occurs, please check
following parameter settings in EPC
400:
• P12 ≥ 5 (If this value is below 5, then
set it to 5)
• P70 = according to parameter list
setting for your separator type
• P76 = actual value of P12 x actual
value of P70.

1810144-02 21
3 Alarms LOPX Alarms and Fault Finding

S000211A
Alarm codes Causes Corrective actions
Water transducer (MT4) trigger- 1. Check for water leakage into lube oil
I001117A
ing 5 times in a row. system (e.g. from cooler or engine).
2. Change over to stand-by mode
(adjust P10 to 0).

Automatic actions at alarm Automatic actions after alarm reset


Main alarm flashes. Main alarm off.
Display flashes. Display normal.
Oil feed off. Oil feed on.

DANGER

Disintegration hazard

If the A7 - 11 alarm is not remedied


there is a risk for breakdown.

22 1810144-02
LOPX Alarms and Fault Finding 3 Alarms

3.6.7 Other Alarms

S000201A
Alarm codes Causes Corrective actions

Extra alarm. 1. Check the connected external


I001121A
function.
2. Check the jumper at terminal XC-X7:1
(when extra alarm not used).

Low pressure signal (PS42) Check the pressure switch.


I001122A

faulty at start. Circuit should be


open.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

Only valid for alarm A9-1: Oil feed on.


If P43=1 then oil feed off.

Only valid for alarm A9-2:


The start of the timer sequences
is blocked.

3.6.8 Countdown Timer Alarm


I001452A

Alarm codes Causes Corrective actions

The count down timer has Restart the timer after relevant actions are
I001451A

reached zero. completed (Parameter 94).

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

1810144-02 23
3 Alarms LOPX Alarms and Fault Finding

24 1810144-02
4 Alarm Tests

Use the following guide for testing alarm


functions by activating them. Alarms are
provoked by one or more actions (A, B and so
on) as shown in the right column, however,
certain alarm functions can not be tested
without being disconnected.
N.B. If the alarm functions are to be
disconnected in the control unit, be
careful to avoid a short-circuit.

The recommendation is to test the alarms


every 3 months.
LED alarm Display alarm Function Sensor Actions to provoke an alarm

High oil pressure PS41 Increase back pressure.

Low oil pressure (low PS42 A. Stop oil feed pump.


flow)
B. Change MV1 position by reducing
air pressure.
C. Reduce the back pressure.

Sludge discharge failure PS42 1. Disconnect hose for opening water


(MV15).
2. Initiate a sludge discharge.

Water transducer fault MT4 Disconnect cable to XE:4 (the test signal
to MT4).

Emergency stop XS2 Press the emergency stop button.

Vibrations (option) XS1 Tap the vibration switch until the alarm is
released.

Heater fault - 1. Start the heater.


2. Disconnect cable to X9:3.

1810144-02 25
4 Alarm Tests LOPX Alarms and Fault Finding

LED alarm Display alarm Function Sensor Actions to provoke an alarm

High or low oil tempera- TT1 A. Remove sensor from pipe and put
ture (option) into hot/cool liquid.
B. Change alarm limit parameters
(P5 = max. temp., P6 = min. temp.)
For more information see the
“Parameter List”.
N.B. Reset the parameter values
after test.

Communication error - Remove fuse A2:F2 (rear board).

A / D conversion error - Remove fuse A1:F2 (front board).

Programming error - Leave the mode selector switch in


position P for 30 minutes.

Power failure - Switch the power to the EPC off and on.

Power supply frequency - Set parameter P21 to wrong frequency.


too high (more than
+ 5%).

Temperature deviation TT1 - TT2 Remove sensor from pipe to cool or heat
up (temp. diff. more than 30 °C/54 °F).

High water transducer MT4 Touch the central screw in the MT4
value (above 400). connection box.

Low water transducer MT4 Disconnect the central screw in the MT4
value (below 100). connection box and keep the oscillator
unit free.

Water transducer trigger MT4 Close displacement water supply and


value not above 30. wait 4 discharge cycles.
Insufficient amount of The amount of displacement water is
displacement water. checked every fourth discharge.

Extra alarm - A. Activate appropriate sensor.


B. Disconnect cable X7:1.

PS42 faulty at start PS42 With the EPC in off mode put a jumper
(Circuit should be open) between XC- X7:4 and push the start
button.

26 1810144-02
5 Test Program

The EPC-400 control unit has a test program,


for testing of input and output functions,
memory etc.

This test program should be run during


installation and whenever there is a need for it,
for instance, during fault finding.

5.1 How to Start the Test


Program

NOTE

The test program is only to be used


when the separator system is out of
operation.

To run the test program, do as follows:


1. Open the control unit door.
2. Switch the power off and the mode
selector in any position (R, L or P).
3. Press the discharge and the alarm push-
buttons simultaneously, and keep them
pressed.
4. Switch the power on.
5. Release the discharge and alarm push-
buttons when the test program has started.
P000191A

1810144-02 27
5 Test Program LOPX Alarms and Fault Finding

5.2 Lamp Test


The test program starts with a lamp test.
1. The display lit with power on.
TT2

TT1 MT4 FS4

2. There are two ways to check the lamps: FOPX


XS1
XT1

• Each LED and display segment


V1 MV10

individually lit (see the picture). MV15


MV16
V5

EPC-400

• Each group of LED:s and display


FOPX

G001142A
segments lit.
Push the button 2 (see the figures in the
picture below) to switch between the two
modes.

5.3 How to Activate


Different Parts of the
Test Program
Use the push-buttons to activate different parts
of the test program (see the figures 1, 2 and 3
in the picture).
1. Push button 1 to step from function 1 to
function 2 etc. in the test program.
It is not possible to step backwards.
Wait until the function is activated before
pushing the button again.
2. Push button 2 to step forward within each
function in the test program, for instance
from function 1.1 to 1.2.
P000181A

3. Push button 3 to activate or deactivate


output terminal (function 5 and 6).

28 1810144-02
LOPX Alarms and Fault Finding 5 Test Program

5.4 Functions in the Test


Program
1. Memory

Function
I000941A

1.1 PROM

1.2 Internal RAM


Memory correct
1.3 External RAM
I000951A

1.4 EEPROM

Memory fault

2. Digital inputs

Function Terminal Unit Correct


value

2.1 Low flow (Low oil pressure) X7:4-XC PS42 0


I000941A

2.2 High pressure X7:3-XC PS41 1

2.3 Not in use - -


Circuit open
2.4 Extra alarm X7:1-XC - 1
I000961A

2.5 Emergency stop or Vibration X8:4-XC XS2 or 1


switch XS1
Circuit closed 2.6 Not in use - -

2.7 Start or stop EPC X8:2-XC Remote 0


switch

2.8 Start or stop heater X8:1-XC Remote 0


switch

1810144-02 29
5 Test Program LOPX Alarms and Fault Finding

3. Digital inputs

Function Terminal Unit Correct


value

3.1 Alarm acknowledge or Reset X9:4-XC Remote 0


switch
I000941A

3.2 Heater fault X9:3-XC 1


Circuit open
3.3 Sludge discharge X9:2-XC Remote 0
switch
I000961A

Circuit closed

4. Mode selector

Function

4.11 Remote (R) position


I000971A

4.1 Local (L) position

4.1 Program (P) position


Remote position

R
I000981A

Local position L
P
I000991A

Program position

1. 4.1 has three positions: R, L, and P.

30 1810144-02
LOPX Alarms and Fault Finding 5 Test Program

5. Digital outputs

Use push-button 3 to activate or deactivate


each output (see ‘‘How to Activate Different
Parts of the Test Program’’ on page 28).
N.B. Corresponding green LED is not lit.
Function Terminal Unit

5.1 Oil feed X4:4-XD MV1/V1


I000941A

5.2 Displacement or conditioning X5:1-XD MV10A


water drain
Circuit deactive
5.3 Displacement or conditioning X5:2-XD MV10
water supply
I000961A

5.4 Opening water X5:3-XD MV15

Circuit active 5.5 Closing water X5:4-XD MV16

5.6 Steam shut-off valve or Heatpac X6:1-XD -


fixed load

5.7 Steam valve decrease or Heatpac X6:2-XD -


fixed load

5.8 Steam valve increase or Heatpac X6:3-XD


fixed load

6. Digital outputs

Use button 3 to activate or deactivate each


output (see ‘‘How to Activate Different Parts
of the Test Program’’ on page 28).
N.B. Corresponding green LED is not lit.
Function Terminal Unit

6.1 Heatpac variable load X6:4-XD


I000941A

6.2 Heatpac alarm blocking during X4:2-XD K15 in


start power
Circuit deactive unit

6.3 Not in use


I000961A

6.4 Separator stop X1:1-2

Circuit active 6.5 Not in use

6.6 Remote/common alarm X2:1-2

6.7 Blocking vibration switch X2:3-4 XS1

1810144-02 31
5 Test Program LOPX Alarms and Fault Finding

7. Not in use

8. Analog inputs

To simulate the temperature sensor elements


(Pt 100) in 8.1 and 8.2, a resistor can be used.

P000111A
Separate plug connectors with appropriate
resistors are included in the test module kit.
Resistor Reference temp. Display reading
110 Ω 25 °C (77 °F) 60
140 Ω 104 °C (219 °F) 215

The normal value on the display for function


8.1 and 8.2 should be 60 – 215. Outside the
range 42 – 233 indicates a fault. 000 (or a very
low value) or 255 indicates a serious fault.

A normal value for function 8.3, Reference


4 V should be 195 – 215.

This table shows how to find the fault:


“Temperature sensor error”: alarm code “EEE” Possible causes

Function Terminal Unit Fuse A1:F2 A/D conver- Input Input short
blown sion faulty open circuit

8.1 Temperature sensor for control X10: 1 – 3 TT2 000 000 255 000

8.2 Temperature sensor for alarm X11: 1 – 3 TT1 000 000 255 000

8.3 Reference 4 V 000 000 195 – 215 195 – 215

8.4 Not in use

Function Terminal Unit Displayed value

8.5 Calibration X10 TT2 0 = OK E = Error

8.6 Calibration X11 TT1 0 = OK E = Error

For instance, if the display shows “000” for


function 8.1, 8.2 and 8.3, it must be either a
blown fuse or A/D converter fault. Check it in
this order:
1. If the fuse is blown, replace it.
2. If the fuse is correct, replace the control
module.

32 1810144-02
LOPX Alarms and Fault Finding 5 Test Program

9. Serial communication

Function Terminal Unit

I000941A
9.1 Not applicable X13:1-4
(The display will show an E).
Circuit correct
9.2 RS 232 C X14 X14:1-4
Measure -10 to -12V DC
on X14:1-4 (Circuit correct).
I000951A

Circuit fault

N.B. After the test, remove the terminal


jumpers and connect communication
cables.

10. Test of EPROM (rear circuit board)

I000941A
11. Test of internal RAM in CPU
Circuit correct
(rear circuit board

12. Test of external RAM in CPU


(rear circuit board)

13. Test of IC 8255 I/O port I000951A


Circuit fault
(rear circuit board)

14. Low reference analog input


(internal)

A value between 42 and 66 is displayed,


when it is correct.

15. High reference analog input


(internal)

A value between 220 and 310 is displayed,


when it is correct.

1810144-02 33
5 Test Program LOPX Alarms and Fault Finding

16. Transducer signal (internal)

The display shows 100 ± ∼50 with oil


inside the WT 200 and 55 ± 10 with air,
when it is correct.

17. Not in use

18. Not in use

N.B. Stop the test program by switching


power off-on.

34 1810144-02

You might also like