INSTRUCTION MANUAL
SIL 2 Load Cell/Strain Gauge Bridge
Isolating Converter
Din-Rail Model D1064S
D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter ISM0088-11
Characteristics
General Description: The single channel DIN Rail Load Cell/Strain Gauge Bridge Isolating Converter D1064S acts as a galvanically isolated interface installed between a PLC/DCS in
Safe Area and a load cell (or group of load cells) in Hazardous Area. Up to four 350 Ω load cells, or five 450 Ω load cells, or ten 1000 Ω load cells can be connected in parallel.
It provides a fully floating power supply voltage with remote sensing capabilities to load cells located in Hazardous Area and converts the mV signal from the load cell into a 0/4-20 mA
or 0/1-5 V or 0/2-10 V signal according to user desired range. Output circuit provides both current source and sink capabilities.
Modbus output is also provided to interface PLC/DCS using digital communication.
Automatic Calibration: Automatic calibration can be accomplished in the field without disconnecting the unit.
Function: 1 channel I.S. input from strain gauge signals, provides 3 port isolation (input/output/supply) and current (source or sink mode) or voltage output signal. Modbus output is also
provided to interface digital device.
Signalling LED: Power supply indication (green).
Configurability: Totally software configurable, no jumpers or switches, input calibration, mA or V output signal by GM Pocket Portable Configurator PPC1090, powered by the unit or
configured by PC via RS-232 serial line with PPC1092 Adapter and SWC1090 Configurator software. A 16 characters tag can be inserted using the configuration software.
EMC: Fully compliant with CE marking applicable requirements.
Technical Data
Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current consumption @ 24 V: 70 mA with four 350 Ω load cells connected and with 20 mA output typical.
Power dissipation: 1.4 W with 24 V supply voltage, four 350 Ω load cells connected and 20 mA output typical.
Max. power consumption: at 30 V supply voltage, short circuit input, overload condition and PPC1090 connected, 2.2 W.
Isolation (Test Voltage): I.S. In/Out 1.5 KV; I.S. In/Modbus Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 500 V; Modbus Out/Supply 500 V; Out/Modbus Out 500 V.
Input: up to four 350 Ω load cells (parallel connection).
up to five 450 Ω load cells (parallel connection).
up to ten 1000 Ω load cells (parallel connection).
A/D Conversion time: 100 ms.
Bridge supply voltage: 4.2 V nominal.
Bridge output signal: 1 to 4 mV/V.
Line resistance compensation: ≤ 10 Ω.
Output: 0/4 to 20 mA, on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load V max. 30 V in sink mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Resolution: 1 µA current output or 1 mV voltage output.
Response time: ≤ 50 ms (10 to 90 % step change).
Output ripple: ≤ 20 mVrms on 250 Ω load.
Modbus Output: Modbus RTU protocol up to 115.200 baud.
Performance: Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Input:
Accuracy after autocalibration: ≤ ± 0.05 % of full scale.
Linearity accuracy: ≤ ± 0.02 % of full scale of input range.
Temperature influence: ≤ ± 0.002 % of full scale of input range for a 1 °C change.
Supply voltage influence: ≤ ± 0.002 % of full scale of input range for a min to max supply voltage change.
Analog Output:
Calibration accuracy: ≤ ± 0.05 % of full scale.
Linearity error: ≤ ± 0.05 % of full scale.
Supply voltage influence: ≤ ± 0.02 % of full scale for a min to max supply change.
Load influence: ≤ ± 0.02 % of full scale for a 0 to 100 % load resistance change.
Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
Compatibility:
CE mark compliant, conforms to Directive:
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating: temperature limits –20 to + 60 °C,
relative humidity max 90 % non condensing, up to 35 °C.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
ATEX: II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I; II 3G Ex ec IIC T4 Gc
IECEx: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I; Ex ec IIC T4 Gc
INMETRO: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
FM: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx [ia] IIC
FM-C: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex [ia] IIC
EAC-EX: 2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC X, [Ex ia Ma] I X
UKR TR n. 898: 2ExnAiaIICT4 X, ExiaI X
associated apparatus and non-sparking electrical equipment.
Uo/Voc = 5.9 V, Io/Isc = 196 mA, Po/Po = 576 mW at terminals 9-10-11-12-13-14.
Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
Approvals:
DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11.
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11.
IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-7.
IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-7.
INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11.
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and
C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15.
ЕАЭС RU С-IT.HA67.B.00113/20 conforms to GOST 31610.0, GOST 31610.11, GOST 31610.15.
CЦ 16.0034 X conforms to ДСТУ 7113, ГОСТ 22782.5-78, ДСТУ IЕС 60079-15.
TÜV Declaration of Compliance No. C-IS-722238330, SIL 2 according to IEC 61508:2010 Ed.2.
SIL 3 Functional Safety TÜV Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
DNV No. TAA00002BM and KR No.MIL20769-EL001 Cert. for maritime applications.
Mounting: EN/IEC60715 TH 35 DIN-Rail.
Weight: about 155 g.
Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class: IP 20.
Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
2 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter G.M. International ISM0088-11
Ordering information
Model: D1064S Power Bus and DIN-Rail accessories:
Cover and fix MORT016 Anchor for side MCHP065
Power Bus enclosure /B Terminal block male MORT017 Terminal block female MORT022
Operating parameters are programmable by the GM Pocket Portable Configurator PPC1090 or via RS-232 serial line with PPC1092 Adapter and SWC1090 Configurator software.
If the parameters are provided with the purchasing order the unit will be configured accordingly, otherwise the unit will be supplied with default parameters.
G.M. International ISM0088-11 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter 3
Parameters Table
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1064 Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that
added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas
group. See parameters on enclosure side and the ones indicated in the table below:
Hazardous Area/
D1064 Associated Must
D1064 Terminals Hazardous Locations
Apparatus Parameters be
Device Parameters
Ch1 9 - 10 - 11 - 12 - 13 - 14 Po / Po = 576 mW ≤ Pi / Pi
Hazardous Area/
D1064 Associated Must
D1064 Terminals Hazardous Locations
Apparatus Parameters be
Device + Cable Parameters
Co / Ca = 39 µF IIC (A, B)
Co / Ca = 996 µF IIB (C)
Ch1 9 - 10 - 11 - 12 - 13 - 14 Co / Ca = 996 µF IIA (D) ≥ Ci / Ci device + C cable
Co / Ca = 996 µF I
Co / Ca = 996 µF IIIC
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50% of Co and Lo parameters are applicable and shall not be exceeded (50% of the Co and Lo become the limits which must include the cable such that Ci device + C cable ≤
50 % of Co and Li device + L cable ≤ 50 % of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 μF for Groups I, IIA, IIB and 600 nF for
Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200 pF per meter (60 pF per foot), Inductance 1 µH per meter (0.20 µH per foot).
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system
when the above conditions are respected.
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved);
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved).
4 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter G.M. International ISM0088-11
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
SAFE AREA, ZONE 2 GROUP IIC T4,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
CLASS I, ZONE 0, GROUP IIC
MODEL D1064S
3+
=
=
4 - Supply 24 Vdc
In 1 =
Source I Out 1
Load cell +EXC 9 5 +
Sink I
+Sense 10 = 6 mA RL
+
-
RL
Source V
-Sense 11 7 mA
+ +
-EXC 12 8 V
- -
+IN 13
1
-IN 14 = = A- MODBUS
2 IN/OUT RS485
= B+
G.M. International ISM0088-11 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter 5
Warning
D1064 is an isolated Intrinsically Safe Associated Apparatus installed into standard EN/IEC60715 TH 35 DIN-Rail. located in Safe Area / Non Hazardous Locations or Zone 2, Group IIC,
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous
Locations (according to FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, and connected to
equipment with a maximum limit for AC power supply Um of 250 Vrms.
3 +
Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only.
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1064 associated apparatus shall be accomplished
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC.
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D1064 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or
unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Operation
The Load Cell/Strain Gauge Bridge Isolating Converter D1064S acts as a galvanic isolated interface installed between a PLC/DCS in Safe Area/Non Hazardous Locations and a load cell
(or group of load cells) in Hazardous Area/Hazardous Locations. Up to four 350 Ω load cells, or five 450 Ω load cells, or ten 1000 Ω load cells can be connected in parallel.
It provides a fully floating power supply voltage with remote sensing capabilities to load cell located in Hazardous Area/Hazardous Locations and converts the mV signal from load cell
into a 0/4-20 mA or 0/1-5 V or 0/2-10 V signal according to user desired range.
Remote sensing wires (terminals “10” +Sense and “11” –Sense) must be always connected to force lines (terminals “9” +Exc and “12” –Exc) for proper operation of the unit,
in case of 4 wires cell connect the sensing lines near to the cell connections to minimize the power supply voltage compensation error.
Output circuit provides both current source and sink capabilities. Modbus output is also provided to interface PLC/DCS using digital communication.
Presence of supply power is displayed by a green signaling LED.
The isolator provides an automatic calibration function that greatly simplifies the range setup; the automatic calibration requires only a calibration weight and can be executed in field
using the hand-held configurator, without disconnecting the unit (check that area is known to be nonhazardous before proceeding).
The hand-held configurator allows also online monitoring of the isolator operation and measures.
Note that complete system calibration is necessary to obtain the correct value reading. Please follow the instructions manual to setup the system.
The unit is not certified for trading applications, is responsibility of the user to obtain specific approvals if the system is subject to specific regulatory requirements regarding trading
(e.g. EN45501 requirements in Europe).
6 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter G.M. International ISM0088-11
Installation
D1064 is a load cell/strain gauge bridge converter housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail.
D1064 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet"
Instruction Manual D1000 series for detailed instructions. D1064 signal converter operates at low level measuring signals, for best performance, install it far from heat sources
(heat dissipating equipment) and wide temperature excursions, in example at the bottom of a cabinet with heat dissipating equipment, if any, at the top.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit
without suffering or causing any damage (for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections.
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example:
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”.
Connect current source mode positive output at terminal “5” and negative output at “6” or current sink mode positive output at terminal “6” and negative output at terminal “8”
(output can be used only one type at a time, not contemporary).
Connect voltage output positive at terminal “7” and negative output at terminal “8”
(voltage output can be used simultaneously with current output, providing that the two systems connected to are isolated).
Connect serial line Modbus output at terminal “1” and at terminal “2”.
Connect strain gauge bridge voltage supply at terminal “9” positive and terminal “12” negative.
Connect strain gauge bridge voltage sensing supply at terminal “10” positive and terminal “11” negative.
If strain gauge bridge has no internal voltage sensing capability always connect terminal "10" to terminal "9" and terminal "11" to terminal "12";
for better performance connect the wire at the end of the line near the load cells.
Connect strain gauge bridge output signal at terminal “13” positive and terminal “14” negative.
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
The enclosure provides, according to EN/IEC 60529, an IP20 minimum degree of protection. The equipment shall only be used in an area of at least pollution degree 2, as defined in EN/
IEC 60664-1. For hazardous location, the unit shall be installed in an enclosure that provides a minimum ingress protection of IP54 in accordance with EN/IEC 60079-0, that must have a
door or cover accessible only by the use of a tool. Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual
contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1064 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
According to EN61010, D1064 must be connected to SELV or SELV-E supplies.
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking.
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, output must be in accordance
with the corresponding input signal value. If possible change the load cell condition and check the corresponding Safe Area output.
1) Set the ACAL – C RNG value: this value is the full scale weighing range of the system (will define the analog outputs full scale)
This value is defined in “Division” numeric value and is the maximum resolution that can be measured (30.000 division, for better measuring resolution this should be settled at least with
10.000 division).
2) Set the ACAL – C REF value: this value corresponds to the weight value that will be used for calibration (must be equal to or lower than ACAL – C RNG).
This value is defined in “Division” numeric value that is equal to the following formula:
Range [div] x Reference [u.m.]
Reference [div]
Range [u.m.]
To set these values correctly, both the reference weight used to perform the calibration and the full range weight that the system supports must be known.
Example: to calibrate a system which will measure a maximum of 400 Kg, with 20.000 division using a reference weight of 75 Kg user should set:
C RNG value = 20.000 div. (maximum division) that corresponds to 400 Kg
C REF value = (20.000 div. x 75 Kg) / 400 Kg = 3750 div.
3) Remove any weight on the platform (gross weight equal to zero), wait until the system is stable then acquire the weight ZERO pressing the Enter key
4) Place the reference weight on the platform (the same value entered as ACAL – C REF), wait until the system is stable then acquire the weight REF pressing the Enter key
In the example used before, the user should load the 75 Kg reference weight to the measuring system and the acquire the value.
5) Remove the reference weight: the system is calibrated.
The two analog outputs are scaled for downscale = ZERO weight, upscale = RANGE weight without any further action.
The Modbus reading is scaled with the same divisions as entered for the value ACAL – C REF.
For example using the 4-20 mA analog output, module sets output to 4 mA when no load is placed on the weighting system (input read 0 div),
module sets output to 20 mA when a 400 Kg load is placed on the weighting system (input read 20.000 div) and
module sets output to 12 mA when a 200 Kg load is measured (10.000 div).
For details on use or configuration of the module via PPC1090, see next pages.
PPC1090 Operation
The Pocket Portable Configurator type PPC1090 is suitable to configure the “smart” barrier of D1000 series. The PPC1090 unit is not ATEX, UL or FM approved and is only to be used in
Safe Area/Non Hazardous Locations and prior to installation of the isolator and prior to connection of any I.S. wiring. Do not use PPC1090 configurator in Hazardous Area/Hazardous
Locations. The PPC1090 configurator is powered by the unit (no battery power) when the telephone jack is plugged into the barrier (RJ12 6 poles connector type with 1:1 connection).
It has a 5 digit display, 4 leds and four push buttons with a menu driven configuration software and can be used in Safe Area/Non Hazardous Locations without any certification because
it plugs into the non intrinsically safe portion of circuit.
G.M. International ISM0088-11 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter 7
Modbus Communication Line
The D1064 provides a Modbus RTU communication over a RS-485 pair. The RS-485 communication line must be connected according to the RS-485 specifications: the cable must have
a 100 Ω nominal impedance and must be terminated at both ends with a 100 Ω resistor; care must be exercised for the proper polarity of all units connected to the bus, additionally all
equipments must operate at the same baud rate and with the same parity (if used). The line termination resistors must be installed externally.
8 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter G.M. International ISM0088-11
Command 16 – Preset Multiple Registers
This function code is used to write the contents of a contiguous block of registers into the D1064. The starting address and the number of registers are addressed starting from zero.
Register data are packed as two bytes for each register, the first byte contains the high order bits and the secondcontains the low order bits. The format of the request is:
Name Size Value
Function Code 1 byte 0x06
Starting Address 2 bytes see word address section
Number of Registers 2 bytes see word address section
Data to be written 2 x N bytes 2 bytes for every register
Register Addresses
Register addresses used by Modbus are unsigned integer indices starting at zero, from 0 to 65535. The value is an HEX word that can be interpreted as a unsigned or signed integer
(unsigned from 0 to 65535, signed in offset binary form -32768 to +32767). Addresses used by the D1064 are defined in the following tables.
Data Registers
Data registers contain information on input measuring circuits, they are allocated as words at the following addresses:
Address To Description Type Note
0000 0000 Weight Reading Signed Integer Read only, resolution depending upon ACAL - C RNG
0001 01FF Reserved Unsigned Integer Read only, return 0000
Configuration Registers
Configuration registers contain information on isolator configuration, they are allocated at the following addresses:
Address To Description Type Note
0200 02FF Reserved Unsigned Integer Read only, return 0000
System Registers
System registers contain information on isolator system registers, they are allocated at the following addresses:
Address To Description Type Note
0400 041F Reserved Unsigned Integer Read only, return 0000
G.M. International ISM0088-11 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter 9
PPC1090 Configuration
The configuration procedure follows a unit specific menu. The display shows the actual menu item, the led shows the channel configured and the push button actuates as “Enter”,
“Select”, “Down” and “Up” key. The “Enter” key is pressed to confirm the menu item, the “Select” key is pressed to scroll the menu item, the “Down” and “Up” keys are pressed to
decrement or increment the numeric value of menu item. The “Up” key is also pressed to decrement the menu level. When the PPC1090 is plugged into the unit, the display shows the
barrier model (first level menu). Then press the “Enter” key to the second level menu and the “Select” key to scroll the menu voice. When the selected menu item is displayed press the
“Enter” key to confirm the choice. Follow this procedure for every voice of the menu. When a numeric menu item is to be changed, press the “Select” key to highlight the character and
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key.To return to a higher level menu press the “Up” key.
D1064S Menu Menu item description
1) D1064S [1 Level Menu]
Displays Model D1064S. Press “Enter” key to second level menu.
2) CF [2 Level Menu]
Displays the parameters configuration menu. Press “Enter” key to configure the functional parameters, press the
“Select” key to the next menu level item or “Up” key to return to first level.
3) In [2 Level Menu]
Displays the input variable monitoring. Press “Enter” to display the current input value reading, press the “Select” key to
the next menu level item or “Up” key to return to first level.
4) Out I [2 Level Menu]
Displays the current analog output variable monitoring. Press “Enter” to display the actual output value reading, press
the “Select” key to the next menu level item or “Up” key to return to first level.
5) Out U [2 Level Menu]
Displays the voltage analog output variable monitoring. Press “Enter” to display the actual output value reading, press
the “Select” key to the next menu level item or “Up” key to return to first level.
6) ACAL [3 Level Menu]
Displays the input calibration parameters. Press “Enter” immediately, before “ACAL” stops blinking, to configure the
calibration parameters, press the “Select” key to the next menu level item or “Up” key to return to second level.
7) C ref [4 Level Menu]
Displays the reference weight at which the calibration is performed. Press “Enter” to set the value, press the “Select”
key to the next menu level item or “Up” key to return to third level. If you pressed “Enter” key, you can set the reference
weight value; press the “Select” key to highlight the character you want to change and then the “Up” and “Down” keys to
select the number; confirm the modification with the “Enter” key. The value is settable from 0 to 30500 digit.
8) C rng [4 Level Menu]
Displays the upscale weight measured by the module. Press “Enter” to set the value, press the “Select” key to the next
menu level item or “Up” key to return to third level. If you pressed “Enter” key, you can set the upscale weight value;
press the “Select” key to highlight the character you want to change and then the “Up” and “Down” keys to select the
number; confirm the modification with the “Enter” key. The value is settable from 0 to 30500 digit.
9) Zero [4 Level Menu]
Displays the zero reference calibration procedure. Press “Enter” to perform the zero calibration, press the “Select” key
to the next menu level item or “Up” key to return to third level. If you pressed “Enter” key, the display is blinking waiting
or confirmation of calibration procedure; confirm the procedure with the “Enter” key.
10) Ref [4 Level Menu]
Displays the reference calibration procedure. Press “Enter” to perform the reference weight calibration, press the
“Select” key to the next menu level item or “Up” key to return to third level. If you pressed “Enter” key, the display is
blinking waiting for confirmation of calibration procedure; confirm the procedure with the “Enter” key.
11) I Out [3 Level Menu]
Displays the current analog output type configuration. Press “Enter” to set the analog output range, press the “Select”
key to the next menu level item or “Up” key to return to second level. If you pressed “Enter” key, you can choose
between 2 different output ranges; press “Select” key to change the output range and then the “Enter” key to confirm the
choice. The output types are:
4-20 4 to 20 mA current output (for SIL application) 0-20 0 to 20 mA current output
12) U Out [3 Level Menu]
Displays the voltage analog output type configuration. Press “Enter” to set the analog output range, press the “Select” key to the next menu level item or “Up” key to return to
second level. If you pressed “Enter” key, you can choose between 4 different output ranges; press “Select” key to change the output range and then the “Enter” key to confirm
the choice. The output types are:
1-5 1 to 5 V voltage output 2-10 2 to 10 V voltage output
0-5 0 to 5 V voltage output 0-10 0 to 10 V voltage output
13) S bus [3 Level Menu]
Displays the Modbus communication parameters. Press “Enter” to configure the communication parameters, press the “Select” key to the next menu level item or “Up” key to
return to second level.
14) Addr [4 Level Menu]
Displays the Modbus communication address. Press “Enter” to set the value, press the “Select” key to the next menu level item or “Up” key to return to third level.
If you pressed “Enter” key, you can set the address value; press the “Select” key to highlight the character you want to change and then the “Up” and “Down” keys to select the
number; confirm the modification with the “Enter” key. The value is settable from 1 to 255.
15) Baud [4 Level Menu]
Displays the Modbus communication baud rate configuration. Press “Enter” to set the baud rate value, press the “Select” key to the next menu level item or “Up” key to return to
third level. If you pressed “Enter” key, you can choose between 5 different baud rate; press “Select” key to change the baud rate and then the “Enter” key to confirm the choice.
The baud rate values are:
9600 9600 b/s rate 19200 19200 b/s rate
38400 38400 b/s rate 57600 57600 b/s rate
115k2 115200 b/s rate
16) Fort [4 Level Menu]
Displays the Modbus communication format configuration. Press “Enter” to set the communication format, press the “Select” key to the next menu level item or “Up” key to
return to third level. If you pressed “Enter” key, you can choose between 3 different communication format; press “Select” key to change the format and then the “Enter” key to
confirm the choice. The formats are:
8N1 8 bit data, no parity, 1 stop bit
8E1 8 bit data, even parity, 1 stop bit
8O1 8 bit data, odd parity, 1 stop bit
10 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter G.M. International ISM0088-11
SWC1090 Configuration
Software configuration procedure of the D1064S. SWC1090 Configurator is available for download at www.gmintsrl.com.
2.
“Output mA:”
current analog output type configuration:
4-20 mA 4 to 20 mA current output
(for SIL application)
“Output Limits”
3. range limitations for current
and voltage analog outputs:
“Output V:” “mA working”: current analog output
voltage analog output type configuration. range in normal working condition.
1-5 V 1 to 5 V voltage output “V working”: voltage analog output
0-5 V 0 to 20 V voltage output range in normal working condition.
2-10 V 2 to 10 V voltage output
0-10 V 0 to 10 V voltage output
Calibration procedure
4.
Each module must be calibrated to work with the specific load cell and application.
D1064S firmware accepts values expressed in “divisions”, and the maximum value is 30000.
“Reference” and “Range” values must also be expressed in divisions, starting from the original unit of measure.
Calibration example:
The application requires to measure weights up to 1000 Kg (u.m. = Kg)
The user decides to apply a reference weight of 200 Kg. b)
Solution 1) Using 10000 div as range, the reference must be set to 2000 div.
Output resolution is 0.1 Kg/div (1000/10000).
Solution 2) Using 30000 div as range, the reference must be set to 6000 div.
Output resolution is 0.033 Kg/div (1000/30000).
6.
B Save to COM port: writes current
configuration to the D1064S module;
Select button B and wait while
parameters are loaded into the D1064S.
Press button “OK” when done.
G.M. International ISM0088-11 D1064 - SIL 2 Load Cell / Strain Gauge Bridge Isolating Converter 11