GE Fanuc IC695ALG808

http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/IC695ALG808

Rx3i PacSystem

Isolated Analog Output module, 8 channels, that is configurable IC695A


IC695AL IC695ALG

919-535-3180
[email protected]
PACSystems™ RX3i
GFK-2481 Isolated Analog Output Module, IC695ALG808
November 2007

Isolated Analog Voltage/Current Output module IC695ALG808 provides


MODULE OK eight configurable voltage or current output channels. Analog channels can
FIELD STATUS be configured for these output ranges:
TB ▪ Current: 0 to 20mA, 4 to 20mA

▪ Voltage: +/- 10V, 0 to 10V


IC695ALG808
The module must be located in an RX3i Universal Backplane. It requires an
RX3i CPU with firmware version 5.0 or later. Machine Edition Version 5.7
Q1
SP3 Logic Developer-PLC or later must be used for configuration.

These modules can be used with a Box-style (IC694TBB032), Extended


Q2
Box-style (IC694TBB132), Spring-style (IC694TBS032), or Extended
Spring-style (IC694TBS132) Terminal Block. Extended terminal blocks
Q3
provide the extra shroud depth needed for shielded wiring. See the
PACSystems RX3i System Manual, GFK-2314 revision B or later for more
Q4 information about Terminal Blocks. Terminal Blocks are ordered separately.

Isolated +24 VDC Power


Q5
The module must receive 24 VDC field power from an external source. The
external source must be connected directly to the module’s terminal block. It
Q6
cannot be connected via the TB1 connector on the RX3i Universal
Backplane.
Q7
Module Features

Q8 ▪ Completely software-configurable, no module jumpers to set


▪ Individually enable or disable channels
▪ Clamping and Alarm Limits
▪ Latching of Alarms
▪ Configurable output bias
▪ Rapid channel acquisition times based on filter frequency
▪ On-board error-checking
▪ Configurable scaling and offsets per channel
▪ High alarm, low alarm, high-high alarm, low-low alarm detection and
reporting selectable per channel
▪ Module fault reporting
▪ Configurable Hold Last State or Output Defaults
2 RX3i Isolated Analog Output Module

GFK-2481

Specifications
Output Ranges Current: 0 to 20mA, 4 to 20mA
Voltage: +/- 10V, 0 to 10V
Backplane Power Requirements 80mA maximum at 3.3V
Power Dissipation within 7.25 Watts maximum (Vuser=24V)
Module
Thermal Derating See derating curves later in this document
External +Power Supply Voltage Range: 19.2V to 30V (24V nominal)
Current: 600mA maximum
Resolution +/-10V: 15.9 bits, 0 to 10V: 14.9 bits, 0 to 20mA: 15.9 bits,
4 to 20mA : 15.6 bits
Output Data Format Configurable as floating point IEEE 32 bit or 16-bit integer in a 32-bit field
Analog Update Rate 8 milliseconds (approximate, all eight channels)
(Determined by I/O scan time,
application dependent)
Output Overvoltage Protection Current outputs only: -30V for 60 seconds, +30V for one hour
Calibrated Accuracy Accurate to within 0.15% of full scale at 25°C
Accurate to within 0. 25% of full scale at 60°C
In the presence of severe RF interference (IC 801-3, 10V/M), accuracy may
be degraded to +/-1% FS.
Output Load Reactance Current: 10µH maximum, Voltage: 1µF maximum
Maximmum Output Load Current: 1350 Ohms maximum
Voltage: 2 Kohms minimum
Output Gain Drift Voltage output: 20ppm per degree C typical
Current output: 35ppm per degree C typical
Output Settling Time Voltage or current output: 2ms, 0 to 95%
Isolation, Field to Backplane 2550VDC for one second

Output Points vs. Temperature, Current Mode


Thermal deratings for module IC695ALG808 are shown below.
RX3i Isolated Analog Output Module 3
GFK-2481

Release History
Firmware
Version Upgrade Kit
Revision
IC695ALG808-AA 1.00 None: Initial Release

LEDs
The Module OK LED indicates module status. The Field Status LED indicates whether the external +24
VDC power supply is present and is above the minimum level and whether or not faults are present. All
LEDs are powered from the backplane power bus.

LED Indicates
Module OK ON Green: Module OK and configured.
Quick Flashing Green: Module performing powerup sequence.
Slow Flashing Green or Amber: Module OK but not configured.
OFF: Module is defective or no backplane power present
Field Status ON Green No faults on any enabled channel, Terminal Block is present, and field
power is present.
ON Amber and TB Green: Terminal Block is installed, fault on at least one
channel, or field power is not present.
ON Amber and TB Red: Terminal Block not fully removed, field power still
detected.
OFF and TB Red: Terminal block not present and no field power is detected.
TB ON Red: Terminal block not present or not fully seated. See above.
ON Green: Terminal block is present. See above.
OFF: No backplane power to module.
4 RX3i Isolated Analog Output Module

GFK-2481

Field Wiring
The table below lists wiring connections for the Isolated Analog Output Modules. There are no shield
terminals.
Terminal Assignment Assignment Terminal
1 No Connect No Connect 19
2 Channel 1 Voltage/Current Output Channel 5 Voltage/Current Output 20
3 Channel 1 Ground/Return Channel 5 Ground/Return 21
4 No Connect No Connect 22
5 No Connect No Connect 23
6 Channel 2 Voltage/Current Output Channel 6 Voltage/Current Output 24
7 Channel 2 Ground/Return Channel 6 Ground/Return 25
8 No Connect No Connect 26
9 No Connect No Connect 27
10 Channel 3 Voltage/Current Output Channel 7 Voltage/Current Output 28
11 Channel 3 Ground/Return Channel 7 Ground/Return 29
12 No Connect No Connect 30
13 No Connect No Connect 31
14 Channel 4 Voltage/Current Output Channel 8 Voltage/Current Output 32
15 Channel 4 Ground/Return Channel 8 Ground/Return 33
16 No Connect No Connect 34
17 External + Power Supply (+24V In) No Connect 35
18 External - Power Supply (+24V Rtn) No Connect 36
Each channel can be individually configured to operate as a voltage output or a current output - not both
simultaneously.

Current
Voltage
No Connect 1 Output 19 No Connect
Output
Channel 1 Output 2 + + 20 Channel 5 Output
V I
Channel 1 Return 3 _ _ 21 Channel 5 Return
No Connect 4 22 No Connect

5 23
6 24
. .
17
24VDC
+ .
.
18 - 36

There are no shield terminals on these modules. For shielding, tie cable shields to the ground bar along the
bottom of the backplane. M3 tapped holes are provided in the ground bar for this purpose.

For technical assistance, please go to www.gefanuc.com/support

All rights reserved. PACSystems is a Trademark of GE Fanuc Intelligent Platforms, Inc.