FIRE RESERVE TANK RECIRCULATION PUMP SIZING

Project No. 3481 Date 08/05/2023


Project Name SERENIA LIVING Prepared By RR
Checked By DW
Issue IFC

Sl No Description Value Unit Remark


Flow rate Volume of water to be Transferred 227 m3
Preferred working hours of pumps 8 hours
Pumps flow rate 28.4 m3/ hr
0.0079 m3/ sec
124.94 GPM
7.88 l/S

Suction side Flow velocity, V1 1 m/ sec


Diameter of pipe 100 mm
100 say
Hydraulic radius in m = D/4 0.03
Longest run of pipe 20 m
Head loss 0.396 m

Discharge side Flow velocity, V2 1.2 m/ sec


Diameter of pipe 91 mm
100 say
Hydraulic radius in m = D/4 0.03
Longest run of pipe 20 m
Head loss 0.555 m

Head cal. Major head loss 0.952 m


Minor head loss due to bend & valves (40% of Major loss) 0.3807 m
Total loss 1.33 m
Depth of water tank 3 m
Suction head 3 m
Static head (Elevation) 4 m
Required residual pressure 15 m
Safety factor 15% 3.50 m
Total Head of pump 26.83 m

Number of pumps working 1 qty


Number of standby pump 1 qty
Total number of pumps 1 qty
Summary Pump capacity each pump 7.88 lps
Pump head 2.7 Bar
Suction pipe size 100 mm
Delivery pipe size 100 mm
FIRE RESERVE TANK WATER RECIRCULATION PUMP FLOW RATE CONSIDERED 7.88 l/s at 2.7 bar head - 1 Duty + 1 Stand by