Cable Tray SOP
Cable Tray SOP
Cable Tray SOP
Bros. General Contractors, Inc.
Standard Operating Procedures for Cable Tray Installation
TABLE OF CONTENTS
2 Section A: Introduction
2 Section B: Receiving and Unloading
3 Section C: Storage
3 Section D: Installation
3 Section D.1: Common Tools for Installation
4 Section D.2: Installation of Support Structure
9 Section D.3: Straight Length Section Installation
16 Section D.4: Fittings Installation
18 Section D.5: Field Modifications
20 Section D.6: Ancillary Products / Accessories
22 Section D.7: Grounding
25 Section E: Installation of Cable
28 Section F: Maintenance
1
INSTALLATION PRACTICES OF LADDER TRAY
SECTION A: INTRODUCTION
To ensure that the complete ladder tray wiring system performs as designed, it is important that
it is properly installed. Personal injury as well as property damage will result if proper installation
and maintenance procedures are not adhered to. Qualified field personnel working to a pre-determined
layout plan will save considerable installation time. Per the National Electrical Code (NEC) a qualified
person is one who is familiar with the construction of the apparatus and the hazards involved.
The system designer (engineer) who has access to the local building codes, the building design,
equipment specification and location, and the clearances required by other subtrades is the person
best suited in designing the layout and supporting structures. It is the designer who has the technical
information critical in designing and routing a satisfactory support structure. Due to the ease in field
altering today’s ladder tray product, there is a tendency to leave the routing up to the electricians
on site. On a project of considerable scope there are large quantities of strut, threaded rod, clips,
connectors, ladder tray, fittings as well as hardware, all intended for specific functions and locations. Field
personnel must be free to do their disciplines of electrical constructions, testing, energizing, grounding
and locking out of circuitry. All this must be done in accordance with the National Electrical Code (NEC)
as well as local and customer building regulations.
.
Immediately after unloading, use the manufacturer’s packing list to note shipping damage or shortages
in order to file a freight claim. Regardless of the freight terms of payment, the manufacturer should
be notified.
2
SECTION C: STORAGE
All tray items whether stored outside or indoors, should be placed on sufficient support, to enable
future mechanical lifting. Trays and fittings should be stacked by their physical dimensions (width) and
type. Cable tray should be stored away from well travelled corridors. Stack loosely on adequate support to prevent
contact with moisture and the ground. For straight lengths; supports should be placed no closer than 1/4 of the tray
from its ends if using 20 foot tray that would be approximately 5 foot from either end. If not covered, the tray should
be stacked slightly higher at one end to allow for the drainage of accumulated moisture.
SECTION D: INSTALLATION
Installation should only be attempted by site personnel well versed in State and Federal electrical
construction practices and the NEC as it relates to electrical equipment and wiring.
LADDER TRAY IS A MECHANICAL SUPPORT SYSTEM FOR CABLES AND IS NOT TO BE USED AS A
WALKWAY, LIFTING APPARATUS OR LADDER.
This SOP is intended only as a practical guide for installers and its intent is not to cover all
the possible contingencies encountered on site.
3
cross member. The length of the cross member should be sufficient to allow for the attachment
of the tray clips plus some horizontal adjustment of the tray.
3. Thread second set of hex nuts onto all-thread moving the top of the cross member up to the
underside of the ladder tray.
4. Ensure cross member is level (with bottom set of hex nuts), then move top set of nuts down until
the cross member is snug and level.
5. Cross check the length of cross member to ensure tray clips and required horizontal adjustment
can be accomplished.
4
D.2.1.2: SINGLE ROD HANGER SUPPORT (REFER TO DIAGRAMS D.2.A AND D.2.B)
Center hung tray supports allow for quicker and easier cable installation by allowing cables to be
deposited into tray systems from each side. There is a maximum load capacity per hanger of 3g
700lbs to 750lbs with the maximum support spacing of 1/8”. Up to 750lbs loading capability
this system reduces the cost of the support system substantially. There is an overall reduction in
hardware, all-thread, and field labor required in the fabrication of supports and installation. Caution
must be exercised in loading the cable. Each side must be symmetrically loaded with equal cable
weight on either side of the center support. This system is limited to tray width of 24”.
To Install:
1. Thread rod onto all-thread up to 8” above bottom elevation of tray.
2. Slide the washer and followed by 1∕2” x 6” tube and then another washer onto all-thread.
3. The tray must be lifted up so that the all-thread passes through its center.
4. Slide horizontal support onto all-thread to the underside of the tray (held at approximate elevation).
5. Place another washer on the all-thread.
6. Thread a second nut up the all-thread until it reaches the cross member. Continue threading
second nut until desired elevation is reached.
vii. Thread first nut down until cross support is held in place.
The tray can be affixed to the cross support in the majority of cases either to the inside or outside
of tray. The placement of the vertical hanger is critical. They must be as close to the center grid line
of the tray run as possible.
5
D.2.2: WALL AND CANTILEVER SUPPORTS (SEE DIAGRAMS D.3.A THROUGH D.3.D)
These supports may be attached to the following structural materials: poured-in-place concrete, precast
concrete, brick or concrete and structural steel. For concrete and concrete related structures use
masonry expansion bolts. A minimum of two (2) bolts must be used. Please consult the manufacturer’s
data for both pullout and shear loads for masonry bolts. For attachment to structural
steel use beam clamps, bolting or welding. Avoid drilling or welding to light structural members as it
may impair the capacity of the member. When welding is the only option; it must be done by a certified
structural welder after receiving explicit approval from the OSR.
Position trays on brackets as close to the attachment point as possible to minimize the bending moment.
The lengths of the bracket shown in diagram D.3.A is limited to 24” and therefore, tray width
should not exceed 18”. In Diagram D.3.B the maximum length of the bracket is 22” and maximum tray
width is 12”. In diagram D.3.C and D.3.D maximum bracket length 36” and maximum tray width is 30”
6
D.2.4: VERTICAL SUPPORT INSTALLATIONS (DIAGRAMS D.4.A THROUGH D.4.C)
The installations of supports for these applications are covered in the preceding documentation.
However, due to the inherent complexity of this install, the issue of safety cannot be overemphasized.
This is not an application left to the inexperienced electrician.
The securing of cable to the tray run must be accomplished through the use of “P” clamps. Plastic tie
wraps are not permissible.
Pre-planning at this stage may address the installation of temporary bracing (if required) during the
installation of the cable. This bracing will prevent unbalanced loading from exceeding design-bending
moments. These temporary braces might also serve as pickup/fastening points for the placement
of cable rollers and pulleys.
7
Once the supports are in place, installation of the ladder tray may begin at any location that is
convenient. To maximize the rigidity of the ladder tray, the section should be laid out so that the
splice locations are between the quarter point of the tray 5’ for a 20’ section and the location of the
support (Diagram D.5.A). This pre-layout is especially important if the support spacing is not
equal. On the other hand, if installing 6 meter tray lengths on support spacing of 6 meters, the
connector plates will be in the same position (Diagram D.5.A) throughout the tray run. If the span
between the tray supports is less than the length of the straight section (Diagram D.5.B), place the tray
across both supports so that the ends are cantilevered. If the support span is the same as the length of
tray, fasten two sections together (Diagram D.5.C). The support span should not exceed the length of one
section of tray! There should not be more than one splice connection between two (2) supports. Do not
locate tray connectors over supports or at the midpoint. Position the next straight length across the next
support and connect it to the previous one. The connecting plates and bolt ends (nuts) must be on the
outside of the tray. (Diagram D.8) Tighten the rib-shanked bolts to draw bolt head flush with the inside
of the siderail (20-27 ft/lbs).
8
D.3.2: EXPANSION CONNECTORS
When installing ladder tray it is important to consider the amount of thermal movement of the system.
This expansion and contraction is quite pronounced when installed outdoors especially in northern
climates. Steel and aluminum have different coefficients of linear expansion. The number of expansion
connectors (EC) is determined by: 1. temperature differential and 2. the length of the straight run
of ladder tray (Diagram D.7).
DIAGRAM D.7
9
DIAGRAM D.8.B
DIAGRAM D.8.C
10
of the bolt head must be flush with the inside of the siderail. Then back off the nut 1/2 turn.
To maintain electrical continuity all expansion connectors require a bonding jumper. The ends of the
jumper must be a minimum distance of 50mm (2”) from the edge of the connector plate. It must have
sufficient length to allow for anticipated maximum expansion. (Diagram D.8.D).
There must be a support located no more than 24” from each side of the expansion connector.
11
As with expansion connections, bonding jumpers must be used to maintain electrical continuity.
D.3.4: HORIZONTAL ADJUSTABLE ELBOW (DIAGRAM D.10)
For horizontal directional changes that are minor and do not require a radius fitting, use a horizontal
adjustable elbow. Supports should be positioned within 24” of each end of the fitting.
i. Connect inside section (with hinge) and position existing tray sections to establish angle.
ii. Position outside connector locating plate at the midpoint.
iii. Trim excess material (if required) from the ends of the outside connecting plate. Install
and tighten all hardware. As with expansion and vertical connectors, bonding jumpers may be
required to maintain electrical continuity.
DIAGRAM D.10 HORIZONTAL ADJUSTABLE ELBOW
12
D.3.7: ADAPTER CONNECTORS (DIAGRAM D.13)
When connecting ladder trays of different siderail heights or brands, use Adapter Connectors.
13
D.4: INSTALLATION OF TRAY FITTINGS
D.4.1: SUPPORT LOCATIONS FOR FITTINGS (DIAGRAM D.16 HORIZONTAL FITTINGS SUPPORT)
Ladder tray comes under its greatest stress at all fitting locations during cable pulling. It is critical that the structural
integrity of the system is not compromised during cable pulling. We recommend that the following support locations
are used for the appropriate fitting types. Supports for horizontal fittings should be located at a distance, no greater
than 24” from each end of the fitting as well as the following locations:
1. At the midpoint (45 degrees) of the arc for a 90 degree elbow.
2. At the midpoint (30 degrees) of the arc for a 60 degree elbow.
3. At the midpoint (22-1/2 degrees) of the arc for a 45 degree elbow, excluded are 12”
radius fittings.
4. At the midpoint (15 degrees) of the arc for a 30 degree elbow, excluded are 12”
radius fittings.
14
D.18: HORIZONTAL CROSS SUPPORT
i. For 12” radius Tees, place supports no greater than 24” from each of the four
(4) ends.
ii. For larger radii, at least one support should be located under each siderail (4) as illustrated.
15
D.22: VERTICAL INSIDE (V/I) AND VERTICAL OUTSIDE (V/O) FITTING SUPPORTS
i. A vertical outside fitting should be supported at a location close to each end, top and bottom.
ii. A vertical inside elbow needs only to be supported at a location close to its top end.
Both inside and outside fittings should be additionally supported at a distance no greater than
24” from each end (2).
16
DIAGRAM D.24 DIAGRAM D.25
DIAGRAM D.26
17
DIAGRAM D.27 DIAGRAM D.28 DIAGRAM D.29
Barrier strips are used in ladder trays containing conductors connected to different power or distribution
transformers or other different sources of voltage. For straight lengths of tray, the barriers are placed
at required locations and then fastened every 36” by either #10 x 1/2” self-drilling and
self-tapping screws or clamps (BC). For barriers used on vertical fittings, there should be a minimum
of three (3) attachment points. For straight length barriers (SB) straight alignment can be achieved by
the use of splice connectors (PSS). The height of the barrier strip must not be greater than the loading
depth of the ladder tray
18
DIAGRAM D.33 BARRIER DIAGRAM D.34 BARRIER STRIP ATTACHMENT,
STRIP APPLICATION SELF DRILLING & SELF TAPPING SCREW
Dropouts are available in 4” radius to provide a means of cable exiting both ladder tray and communication
channel. They provide a smooth surface on the radius face to protect the sheathing of the cable. There are two
types: snap on or drop in (inserted between rungs). Both types are secured in place with #10 x 1∕2”
self-drilling and self-tapping Tec screws.
This adapter (CT) is used when a conduit run terminates at a ladder tray run. This is a mechanical
connection. In order to maintain electrical continuity an equipment grounding connection must be
19
established between the ladder tray and the conduit (Diagram D.43). To fasten this adapter to the top
flange field, drill two (2) 3/8” holes, insert bolts from the top, fasten nuts and tighten in place.
DIAGRAM D.40 CONDUIT TO LADDER DIAGRAM D.41 INSTALLED CONDUIT
TRAY ADAPTER TO LADDER TRAY ADAPTER
20
NEC Reference
392.60 Grounding and Bonding.
(A) Metallic Cable Trays. Metallic cable trays shall be permitted to be used as equipment grounding conductors
where continuous maintenance and supervision ensure that qualified persons service the installed cable tray system
and the cable tray complies with provisions of this section. Metallic cable trays that support electrical conductors
shall be grounded as required for conductor enclosures in accordance with 250.96 and Part IV of Article 250. Metal
cable trays containing only non-power conductors shall be electrically continuous through approved connections or
the use of a bonding jumper.
Informational Note: Examples of non-power conductors
include nonconductive optical fiber cables and Class 2 and
Class 3 Remote Control Signaling and Power Limiting Circuits.
It is not necessary to install bonding jumpers at standard rigid aluminum or galvanized steel splice plate
connections or offset reducing splice plate connections.
For rigid splice plate connections of materials and finishes other than aluminum or galvanized steel, bond
jumpers may be required. For example, stainless steel splice plates require bonding jumpers.
4.7.2 Cable Trays with Separate Equipment Grounding Conductor Installed (See Figure 4.61.)
When a separate EGC cable is installed in or on cable tray, it may be bonded to the cable tray with a
grounding clamp. Ground clamp styles include bolted lug types that require drilling the cable tray side rail
and clamp-on styles that work like a beam clamp. One grounding clamp should be used on each straight
section of cable tray.
At standard rigid connections, bonding jumpers do not have to be installed
21