Indracontrol S20 Analog Input Module 8 Inputs: Features
Indracontrol S20 Analog Input Module 8 Inputs: Features
Indracontrol S20 Analog Input Module 8 Inputs: Features
Edition 03
S20 analog input module
8 inputs
1 Description
The module is designed for use within an
IndraControl S20 station. This data sheet is only valid in associa-
It is used to acquire analog voltage and current sig- tion with the application description for
nals. the IndraControl S20 system, material
number R911335988.
Features
• 8 analog, bipolar input channels for the connec- Make sure you always use the latest doc-
tion of either voltage or current signals umentation.
• Connection of sensors in 2-wire technology It can be downloaded under
• Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, www.boschrexroth.com/electrics.
±5 V
• Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA,
±20 mA
• Device rating plate stored
Data sheet | S20-AI-8 Bosch Rexroth AG 2/20
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Tolerance data......................................................................................................................... 7
6 Internal circuit diagram ............................................................................................................ 8
7 Terminal point assignment....................................................................................................... 8
8 Connection examples.............................................................................................................. 9
9 Connection notes .................................................................................................................. 10
10 Local diagnostic and status indicators ................................................................................... 11
11 Process data.......................................................................................................................... 12
12 Significant values................................................................................................................... 13
12.1 Calculation of the measured value from the process data input value .............................................. 13
3 Ordering data
4 Technical data
53,6 54
122,4
126,1
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according
to EN 60715).
Data sheet | S20-AI-8 Bosch Rexroth AG 4/20
General data
Color light grey RAL 7035
Weight 204 g (with connectors and bus base module)
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Mounting position any (no temperature derating)
Power consumption
Power consumption typ. 1.365 W (at UBus and UA)
max. 1.605 W (at UBus and UA)
Data sheet | S20-AI-8 Bosch Rexroth AG 5/20
Analog inputs
Number of inputs 8
Description of the input Differential inputs, voltage or current can be chosen separately
Connection method Push-in connection
Connection technology 2-wire, shielded, twisted pair
Current input signal 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
Voltage input signal 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V
Resolution A/D 16 bit
A/D conversion time 2 µs
Measured value representation 16 bits (15 bits + sign bit)
Data formats IB IL
Process data update 300 µs
Filtering RFI filtering / passive TP 1st order
Input filter 30 Hz, 12 kHz and mean-value generation (can be parameter-
ized)
Precision 0.1 % (of measuring range final value for active mean-value
generation and 30 Hz filter)
Input resistance of voltage input 268 kΩ (typical)
Input resistance current input 104 Ω (typical)
Limit frequency (3 dB) 30 Hz
12 kHz (in fast mode)
Open circuit response goes to 0 V, 0 mA; open-circuit detection for 4 mA ... 20 mA
Common mode voltage range -50 V DC ... 50 V DC
Transient protection of inputs Suppressor diode
Overload protection of the current inputs No; ±5.2 V DC, maximum, Imax = 50 mA
Overload protection of the voltage inputs ±30 V DC, maximum
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/ 5g
IEC 60068-2-6
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/ 10g
IEC 60068-2-27
Data sheet | S20-AI-8 Bosch Rexroth AG 6/20
Approvals
For the latest approvals, please visit www.boschrexroth.com/electrics.
Data sheet | S20-AI-8 Bosch Rexroth AG 7/20
5 Tolerance data
The following applies for tolerance values: The drift values refer to the relevant measuring range
final value.
The data is valid for nominal operation (UA= 24 V in
the default configuration (unless documented other-
Tolerances influenced by electromagnetic interfer-
wise).
ence
Default configuration: Filter with 30 Hz, 16-sample Current Voltage
mean-value, IB IL format.
Electromag- EN 61000-4-3/ < ±1.0 % < ±2.0 %
netic fields IEC 61000-4-3
300 μs update time, fast mode (12 kHz filter, 32-sam- Fast tran- EN 61000-4-4/ < ±1.0 % < ±1.0 %
ple mean value) sients (burst) IEC 61000-4-4
Conducted in- EN 61000-4-6/ < ±0.5% < ±0.5%
Tolerances at TA = +25°C terference IEC 61000-4-6
Measuring Absolute Relative
range Typ. Max. Typ. Max. Additional tolerances may occur due to the influence
of high-frequency electromagnetic interference
0 V ... 5 V, ±5 V, ±50 mV ±80 mV ±0.5% ±0.8%
caused by wireless transmission systems in the near
0 V ... 10 V,
±10 V vicinity. The values specified refer to nominal opera-
tion in the event of direct interference to components
0 mA ... 20 mA, ±100 μA ±160 μA ±0.5% ±0.8%
without additional shielding such as a steel cabinet,
4 mA ... 20 mA,
±20 mA etc.
The above mentioned tolerances can be reduced by
300 μs update time, default (30 Hz filter, 16-sample providing further shielding measures for the I/O mod-
average value) ule (e.g., use of a shielded control box/control cabinet,
etc.).
Tolerances at TA = +25°C
Measuring Absolute Relative
range Typ. Max. Typ. Max.
0 V ... 5 V, ±5 V, ±10 mV ±30 mV ±0.10% ±0.30%
0 V ... 10 V,
±10 V
0 mA ... 20 mA, ±20 μA ±60 μA ±0.10% ±0.30%
4 mA ... 20 mA,
±20 mA
a1 00 07
a1 00 01 02 03 04 05 06 07
Supervisor
UBus
a2 10 17
a2 10 11 12 13 14 15 16 17
C 8x
b1 20 27
b1 20 21 22 23 24 25 26 27
Local bus
b2 30 37
b2 30 31 32 33 34 35 36 37
FE
D
UA
E1
E2 # M Fig. 2 Terminal point assignment
U
U
X
REF 8:1 U/I Termi- Color Assignment
nal
point
Supply voltage input
a1, a2 Red 24 V DC Analog module feed-in
(UA) (bridged internally)
UA b1, b2 Blue GND Reference potential of the
24 V AI 1...8 supply voltage (bridged in-
ternally)
Fig. 1 Internal wiring of the terminal points Analog inputs
00 ... 07 Orange U01+ ... Positive voltage connection
Key: U08+ for channels 1 ... 8
Microcontroller 10 ... 17 Orange U01- ... Negative voltage connection
µC U08- for channels 1 ... 8
20 ... 27 Orange I01+ ... Positive current connection
Optocoupler I08+ for channels 1 ... 8
30 ... 37 Orange I01- ... Negative current connection
I08- for channels 1 ... 8
Power supply unit with electrical isola-
tion
Analog/digital converter
M
U
Multiplexer
X
8:1
8 Connection examples
U1+ U2+
+24 V
00 01 02 03 04 05 06 07
U1– U2–
U U 10 11 12 13 14 15 16 17
U
P
20 21 22 23 24 25 26 27 I I1+ I2+
GND
30 31 32 33 34 35 36 37
I I1– I2–
Fig. 3 Connection for voltage and current measure- Fig. 6 Differential voltage input with active 3-wire
ment transmitter
Fig. 4 Connection of potentiometric position sensors Fig. 7 Differential current input with passive 2-wire
transmitter
The values of potentiometric position sensors can be
acquired with voltage measurement. Supply the po-
tentiometer via an external power supply unit (Uext =
10 V).
U1+ U2+
U1– U2–
+24 V
I1+ I2+
I1– I2– I
P
GND
9 Connection notes
12 Significant values
The table is valid from index -AE1.
Input data 0 V ... 10 V ± 10 V 0 V ... 5 V ±5V 0 mA ... 20 mA ± 20 mA 4 mA ... 20 mA
hex dec V V V V mA mA mA
8001 Overrange > +10.837 > +10.837 > +5.419 > +5.419 > +21.6747 > +21.6747 > +21.3397
7F00 32512 +10.837 +10.837 +5.419 +5.419 +21.6747 +21.6747 +21.3397
7530 30000 +10.0 +10.0 +5.0 +5.0 +20.0 +20.0 +20.0
0001 1 +333.33 μV +333.33 μV +166.67 μV +166.67 μV +0.6667 μA +0.6667 μA +4.0005333
0000 0 0 0 0 0 0 0 +4.0 ... +3.2
FFFF -1 -333.33 μV -166.67 μV -0.6667 μA
FDA7 -601 -200 mV
FC7B -901 -150 mV
8AD0 -30000 -10.0 -5.0 -20.0
8100 -32512 -10.837 -5.419 -21.6747
8080 Underrange < -200 mV < -10.837 < -150 mV < -5.419 < -0.4 < -21.6747
8002 Open circuit < +3.2
IB IL format
Resolution = (20 mA - 4 mA) / 30000 = 0.0005333
Measured value = PD-EW x 0.0005333 mA +4 mA
Example 1
PD IW 493Fhex = 18751dec
Value x resolution 18751 x 0.000533 mA = 10 mA
+ 4 mA 10 mA + 4 mA = 14 mA
Measured value 14 mA
Data sheet | S20-AI-8 Bosch Rexroth AG 14/20
14 Standard objects
14.1 Objects for identification (device rating plate)
The objects marked in the last column with an * are described in more detail in the next sections.
The description of the other objects is to be found in the application description for the IndraControl S20 system,
material number R911335988.
Data sheet | S20-AI-8 Bosch Rexroth AG 17/20
Off Green on
On Green/yellow flashing
Data sheet | S20-AI-8 Bosch Rexroth AG 18/20
15 Application objects
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 Fil- 0 0 Mean- 0 0 0 0 Measur- 0 0 0 0 0 0 Data 0 0 0 0 0 0 0 0
ter value ing range format
Filter Code (bin) Code (hex) Data format Code (bin) Code (hex)
30 Hz (default) 0 0 IB IL (default) 00 0
12 kHz 1 1 Reserved Other
Measuring range Code (bin) Code (hex) Set all reserved bits to 0.
0 V ... 10 V (default) 0000 0
-10 V ... +10 V 0001 1
0 V ... 5 V 0010 2
-5 V ... +5 V 0011 3
0 mA ... 20 mA 0100 4
-20 mA ... +20 mA 0101 5
4 mA ... 20 mA 0110 6
Reserved 0111 ... 1110 7 ... E
Channel inactive 1111 F
15.2 Measured value in extended float format Some example values for conversion from floating
(0082hex: Measured Value Float) point to hexadecimal representation:
You can read the IN process data with the 0025hex ob- Floating point Hexadecimal representation
ject. 1.0 3F 80 00 00
The 0082hex object is also available. 10.0 41 20 00 00
This object provides the measured value in the high- 1.03965528 3F 85 13 6D
est internal accuracy of the terminal in the float format. - 1.0 BF 80 00 00
DOK-CONTRL- Bosch Rexroth AG All rights reserved. No part of this document may be reproduced or stored,
S20*AI*8***-DA03-EN-P Electric Drives and Controls processed, duplicated, or circulated using electronic systems, in any form or
Postfach 13 57 by any means, without the prior written authorization of Bosch Rexroth AG,
Electric Drives and Controls. Violations shall give rise to claims for damages.
97803 Lohr, Deutschland
The data specified above only serve to describe the product. They do not in-
Bgm.-Dr.-Nebel-Str. 2
dicate any specific condition or suitability for a certain application. It must be
97816 Lohr, Deutschland remembered that our products are subject to natural wear and ageing.
Tel. +49 9352 18 0
8258_en_02