Generator Protection
Generator Protection
Generator Protection
CONTENT
Generator Step-up
Transformer
Generator
Field CT VT
Gen.
Excitation
AVR
Transformer
Static
Exciter
3
INTRODUCTION TO GENERATOR PROTECTION
.
4
INTRODUCTION TO GENERATOR PROTECTION
. .
5
INTRODUCTION TO GENERATOR PROTECTION
.
System
Ground
Stator
Ground
Exciter
The
"Wild"
G Power
System
Stator
Phase
System 8
Phase
INTRODUCTION TO GENERATOR PROTECTION
Overexcitation
Over Open
Power Loss of Field
Loss of Field Circuits
Overexcitation
Overexcitation
Exciter
The
"Wild"
G Power
System
Abnormal
Inadvertent Frequency
Abnormal Energizing,
Frequency Pole Flashover
Loss of
Reverse Breaker Synchronism
9
Power Failure
INTRODUCTION TO GENERATOR PROTECTION
10
INTRODUCTION TO GENERATOR PROTECTION
■ Type of prime mover
Steam turbines
Gas turbines
Hydro
Diesel
■ Generator construction
Cylindrical rotor
Salient pole
■ Mode of operation
Base load
Peak lopping
Stand by
■ Ratings
Power – from 200kVA to 1000MVA
11
Voltage-from 440V to 24 kV
INTRODUCTION TO GENERATOR PROTECTION
Connection to The Power System:
Direct : ■
Via Transformer : ■
12
INTRODUCTION TO GENERATOR PROTECTION
Y Generator Y Generator
Transformer Station Transformer
Transformer
Earthing
Transformer
Unit/Station Unit
~ Transformer ~ Transformer
Y Y
R
R
13
GENERATOR PROTECTION REQUIREMENTS
21 Distance relay
24 Overexcitation / Volts per Hertz
25 Synchronism-check relay
27 Undervoltage relay
27TN Third-Harmonic Undervoltage relay
30 Annunciator device
32 Reverse power relay
37 Undercurrent or underpower relay
40 Field excitation relay
46 Negative sequence overcurrent relay
47 Negative sequence overvoltage relay
49 Thermal relay
50 Instantaneous AC overcurrent relay
50DT Split Phase Differential
50/27 Inadvertent Energizing
50BF Breaker Failure
51 AC Inverse Time Overcurrent relay
52 Circuit breaker
15
59 Overvoltage relay
59D Third-Harmonic Voltage Differential Ratio
ANSI/IEEE DEVICE IDENTIFICATION
No. DESCRIPTION
. 60 Voltage balance or loss of potential relay
63 Pressure device
64F Field Ground relay
64B Brush Lift-Off Detection
100% Stator Ground Protection by Low
64S Frequency Injection
67 AC directional overcurrent relay
68 Power Swing Blocking
69 Permissive relay
74 Alarm relay
76 DC overcurrent relay
78 Out-of-step relay
79 AC reclosing relay
81 Frequency relay
81R Rate of Change Frequency relay
83 Transfer device
85 Carrier or pilot-wire relay
86 Lock out relay
87 Differential relay
94 Auxiliary tripping relay 16
Allocated Protection Functions For Generators:
87 Differential
32 Reverse power
59 Over-voltage
81O/U Frequency
V/f Over-excitation24
Turbine
49S Stator Over-load
51V Voltage/over-current
Rotor Stator 17
GENERATOR GROUNDING
OBJECTIVES OF GENERATOR GROUNDING:
19
GENERATOR GROUNDING
Solidly Ground Neutral( effecively ground):
This method is not recommend for following reasons:
Disadvantage:
Great damages to generators, Leakage zero-
sequence currents.
21
GENERATOR GROUNDING
High Resistance Grounding:
Two Methods of Neutral High-Resistance Grounding:
Rn Xcg or
Xcg
1.0
Rn
23
Rn is the effective neutral resistance
Xcg is the capacitive reactance of the three phases
GENERATOR GROUNDING
High- Resistance Grounding:
Disadvantage :
-High Transient Overvoltage
- for intermittent ground faults (2.5- 3 ) Voltage Phase-
ground.
Standard Application
24
GENERATOR GROUNDING
High- Resistance Grounding :
Distribution transformer and resistor combination:
Advantage:
▪ Low- Ohmic value Load Resistor.
▪ Primary current 3 – 15 A.
▪ Rugged construction.
Load
Resistor < 200 - 400 A
26
GENERATOR GROUNDING
Low-Resistance Grounding:
27
STATOR EARTH FAULT PROTECTION
Directly Connected Generators :
51N
Unearthed Generators :
Other generators connected in parallel
will generally be unearthed.
50N 51N
11.5kV; 75,000KVA
xV
For operation
xV
ΙF Ι S(PRIMARY) ΙF
250/1A IS R
xV
R
x.6600
R 33 x.200
33
1
Ι S(SECONDARY) x.200 x 0.8x
250
51N 50N
System earth faults are not seen by generator earth fault protection
instantaneous relay may be used.
Advantage : Sensitive
RSTAB
64
Effective
Distribution High
Transformer
R 59 Neutral overvoltage relay
33
STATOR EARTH FAULT PROTECTION
100% Stator Earth Fault Protection :
Two methods :
35
100% STATOR EARTH FAULT - 3RD HARMONIC VOLTAGE
Earthin
g 59
Trans-
former U/V
37
51
STATOR PHASE FAULT PROTECTION
Over current Protection :
For parallel generators, CTs can be located on line side.
51
38
STATOR PHASE FAULT PROTECTION
Differential Protection(87G):
87G used to protect for:
•3 phase line to line
•1 phase line to line
•multi-phase line to ground
•May not be able to detect a 1 phase to ground fault on
high impedance grounded generators
•Restraint or Percentage Differential Trip Characteristic
•Used to improve sensitivity for detecting small levels of
fault current
•Also maintains security against inadvertent tripping due
to through faults
39
PERCENTAGE DIFFERENTIAL PROTECTION - BIASED
BIAS BIAS
OPERATE
40
Slope characteristics
41
ROTOR EARTH FAULT PROTECTION
Rotor Earth Fault Protection( 64R):
Field circuit is and isolated DC system
o Insulation failure at a single point
No fault current, therefore no danger
Field
Winding
AC Injection Method:
Field
Exciter
Winding
~ AC. auxiliary
supply
R
Brushless Machines
No access to rotor circuit
Require special slip ring for measurement
44
If slip rings not present, must use tele-metering technique
ABNORMAL OPERATING CONDITION PROTECTION
Reverse Power Protection (32):
➢ Prevents generator from motoring on loss of prime mover
➢ From a system standpoint, motoring is defined as the flow of real power
into the generator acting as a motor.
➢ With current in the field winding, the generator will remain in synchronism
with the system and act as a synchronous motor.
➢ If the field breaker is opened, the generator will act as an induction motor.
➢ A power relay set to look into the machine is therefore used on most units.
➢ The sensitivity and setting of the relay is dependent upon the type of prime
mover involved.
Prime mover failure can
- cause overheating of low pressure blades in steam turbine
46
ABNORMAL OPERATING CONDITION PROTECTION
Negative Sequence Over current Protection(46):
CAUSE:
Negative sequence currents could result from :
Unbalanced load
Asymmetrical faults
Salient Pole
With connected amortisseur windings 10
With non-connected amortisseur windings 5
Cylindrical Rotor
Indirectly cooled 10
Directly cooled to 960 MVA 8
961 to 1200 MVA 6
1200 to 1500 MVA 5
(VALUES TAKEN
FROM ANSI C50.13-1989)
49
ABNORMAL OPERATING CONDITION PROTECTION
52
ABNORMAL OPERATING CONDITION PROTECTION
. .
53
ABNORMAL OPERATING CONDITION PROTECTION
55
ABNORMAL OPERATING CONDITION PROTECTION
Over Under & Frequency Conditions(81/O/U):
■ Over Frequency(81O):
Result from generator over speed caused by sudden loss of
load
In isolated generators may be due to failure of speed
governing system
Over speed protection may be provide by mechanical
means.
Desirable to have over frequency relay with more sensitive
setting
Over Frequency Setting (typical setting ):
Alarm : 51 Hz 30 Sec
Trip : 53 Hz 10 Sec
56
ABNORMAL OPERATING CONDITION PROTECTION
59
ABNORMAL OPERATING CONDITION PROTECTION
Inadvertent Energizing (dead machine)Protection(50/27):
Inadvertent energizing is closing of the generator breaker while machine is not
running
WHY INADVERTENT ENERGIZING OCCURS
Operating errors
Breaker head flashover
Control circuit malfunctions
Combination of above
Effects of inadvertent energizing:
❖ Generator behaves as an induction motor
❖ Resulting rotor current is forced into negative sequence path in rotor body
❖ Machine impedance during initial energizing is equivalent to its negative sequence impedance
60
ABNORMAL OPERATING CONDITION PROTECTION
DEDICATED PROTECTION SCHEMES TO DETECT INADVERTENT ENERGIZING
❖ Frequency supervised over current scheme
61
GENERATOR BACKUP PROTECTION
62
GENERATOR BACKUP PROTECTION
on measured voltage
Preferred option when generator is connected via step up
transformer
Voltage controlled
Relay switches between fault characteristic and load
63
GENERATOR BACKUP PROTECTION
64
GENERATOR BACKUP PROTECTION
100% Enable
Percent Set Value for Pickup
Pickup Inhibit/Enable
25% Inhibit
25% Percent Nominal Volts 100% Percent Nominal Volts 80% 100%
a.) Voltage-Restrained Overcurrent b.) Voltage-Contolled Overcurrent 65
GENERATOR BACKUP PROTECTION
iX
67
TYPICAL GENERATOR PROTECTION SCHEME
small up to 1MW
. 68
TYPICAL GENERATOR PROTECTION SCHEME
Medium up to 12.5MW
69
TYPICAL GENERATOR PROTECTION SCHEME
70
Large up to 50 MW
TYPICAL GENERATOR PROTECTION SCHEME
Lager than 50 MW
71
TYPICAL GENERATOR PROTECTION SCHEME
Large machine
72