SW2020 Users LPG E1 16 1 F
SW2020 Users LPG E1 16 1 F
SW2020 Users LPG E1 16 1 F
Salwico SW2020
User Manual, LPG version
çConsilium
The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error or
damage resulting from the usage of this document.
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: [email protected]
Internet: www.consilium.se
Contents
1. GENERAL INFORMATION A
1.1 DESCRIPTION OF THE SYSTEM
1.2 GENERAL BLOCK DIAGRAM
2. INSTALLATION B
2.1 CONTROL UNIT
2.2 ANALYZING UNIT
2.3 PIPE SYSTEM
2.4 FLAME TRAPS
2.5 MANUAL SHUT-OFF VALVES
2.6 SAMPLING PIPE ACCESSORIES
2.7 SAMPLING POINTS
2.8 ELECTRICAL CONNECTION
2.9 COMMISSIONING DOCUMENTS
3. OPERATION C
3.1 GENERAL PRINCIPLES
3.2 DISPLAY MODES
3.3 LISTS: ALARM, FAULT CODES, DISCONNECTION
3.4 SETUP - GENERAL SETTINGS
LEVEL 1 - SET TIME, DATE, TEST OF LEDS & BUZZER, ETC
LEVEL 2 - CALIBRATION, ETC
LEVEL 3 - SYSTEM SETUP AT START UP
3.5 SETUP - SAMPLING POINTS
3.6 GUIDELINES FOR DAILY HANDLING
4. TECHNICAL DATA D
4.1 INTERNAL CONNECTION
4.2 INTERNAL CONNECTION ON RIOK-40 AND RIOK-41
4.3 PNEUMATIC BLOCK DIAGRAM, ANALYSING UNIT
4.4 FLOW EXAMPLES
4.5 CALCULATION OF SAMPLING TIME
4.6 VACUUM PUMP
4.7 GAS DETECTORS
1. GENERAL INFORMATION
A1
Salwico SW2020
General Information
A2
Salwico SW2020
General Information
REPEATER UNIT
CONTROL UNIT
ANALYSING UNIT
MEASURING
POINT INSIDE
ANALYSING UNIT
S-4-005.285/E
A3
Salwico SW2020
Installation
2. INSTALLATION
B1
Salwico SW2020
Installation
DETECTOR
The control unit is the man-machine interface and controls the electronics in the
analysing unit. It consist of a LCD clear text Display, LED Display, LED's, keyboard,
microprocessor and memory for the software, definitions, additional texts etc. The unit
is normally made for wall mounting and should be placed in a well visible position e.g.
cargo control room. Electrical connection terminals to the analysing unit, the repeater
unit and the optional printer are placed in the bottom of the control unit cabinet.
As an alternative both the control unit and the analysing unit can be delivered in one
single cabinet.
The SW2020 control unit is divided into two parts; the gas alarm panel and the
operating panel.
The gas alarm panel is activated when a gas alarm situation is detected in the system.
The sampling point number, alarm level (LO or HI) and the actual gas detector in alarm
are displayed.
There are three keys on the operating panel. The Alarm Mute key is used to
acknowledge the gas alarm and the Alarm Reset key is used to reset the gas alarm.
The third key Alarms in Queue is used to toggle the sampling points in alarm.
The Operating Panel continuously shows, in the clear text display, sampling point and
the last measured value.
The Fault LED is lit and a fault message is shown in the clear text display when a fault
alarm is generated.
The List and Setup keys are used to manage the gas sampling system. The numeric
keypad is among other things used for value settings and clear text setup.
B2
Salwico SW2020
Installation
The analysing unit should be installed not less than 3 metres above the main deck in
order to avoid air locks in the pipes and ensure the correct work of the automatic flow
watching function. The area should be ventilated and temperature-controlled.
The analyzing unit is designed to be off a gas-tight construction and this needs to be
considered during installation of the equipment onboard when cables are entering
into the bottom of the cabinet.
There must not be an opening that could potentially ventilate Explosive or Toxic
gases to a safe area onboard.
For installation and for the future service work, there must be enough space, approx.
0.5m, at the pipe connection side, normally the left side.
There are removable plates intended for the installation of cable inlets on the
underside of the cabinet, for electrical connections.
The electrical connections are made in accordance with the electrical drawing in this
chapter.
Analysing Unit
Calibration gas
Bar
B3
Salwico SW2020
Installation
NB! These nipples should be tightened with a spanner, 1.25 turn only, from the hand-
tightening stop. If dismounted the nipple should be retightened to exactly the same
position during re-mounting.
The pipes between the analysing unit and the normal shut-off valves should be
mounted in such a way that air locks do not occur.
Also note that the pipes should be installed in such a way that service can be
performed on an individual flame trap as well as on On-Line Filters without
unnecessary dismounting of other pipes.
Exhaust Pipe
The exhaust pipe from the analysing cabinet is connected via a nipple at the intended
site and should be mounted with a slope towards the exhaust point. Refer to picture on
previous page.
Instrument air 5 - 16 Bar inlet (only used when APCS function is present)
The inlet pipe for dry instrument air is connected to the analysing unit via a nipple at
intended site. Refer to picture on previous page.
B4
Salwico SW2020
Installation
When the sampling pipes are installed, care should always be taken that the pipes are
installed in such a way that the risk of air locks is avoided.
There are two main ways of installing the piping from the analysing unit to the various
sampling points; either the pipes are installed above deck or through the pipe tunnel,
or a combination of both methods. Note that pipes installed above deck must be
protected against mechanical damage. Refer to drawing Pipe installation example in
this chapter.
All pipe couplings with conical seals forming part of the pipe system should always be
sealed with Loctite 577. (NB! Not thread tape).
The pipes should also be fixed in such a way that vibrations or other similar actions do
not damage them. When installing the pipes, care should be taken not to allow them to
become deformed.
The drawing Suspension and fixing in this chapter shows a proposed method of
suspension and fixing.
When a pipe cut is necessary, make sure that the pipe is not deformed at the cut and
that the airflow resistance is not increased. Also note that capillary connections have to
be carefully soldered to avoid unnecessary airflow resistance.
Refer to separate instructions for installation of other components of the pipe system.
B5
Salwico SW2020
Installation
NB. 2.
A test has to be performed on every sampling pipe to verify that there are no
leakages. Also verify that each sampling point is correctly connected to the
Analysing Unit. It is possible to do a test of the air tightness by disconnecting the
tubes one by one on the inside of the cabinet and perform the test by connecting
a manometer, shut-off valve and compressed air.
B6
Salwico SW2020
Installation
SHUT-OFF VALVES
B7
Salwico SW2020
Installation
DECK BULKHEAD PASSAGE
B8
Salwico SW2020
Installation
1 2
PIPE
PIPE
PIPE
B9
ITEM No. DETECTOR POSITION ITEM No. DETECTOR POSITION ITEM No. DETECTOR POSITION
1 TANK 1 FWD PORT HOLD SPACE TOP 11 TANK 3 AFT PORT HOLD SPACE BOTTOM 21 FRESHWATER GLYCOL TANK BREATHER
2 TANK 1 FWD STBD HOLD SPACE TOP 12 TANK 3 AFT STBD HOLD SPACE BOTTOM 22 MOTOR ROOM TOP
3 TANK 1 AFT PORT HOLD SPACE BOTTOM 13 TANK 4 FWD PORT HOLD SPACE TOP 23 MOTOR ROOM BOTTOM
4 TANK 1 AFT STBD HOLD SPACE BOTTOM 14 TANK 4 FWD STBD HOLD SPACE TOP 24 COMPRESSOR ROOM TOP
FIXED INSTALLED ELECTRICAL TYPE GAS DETECTORS
5 TANK 2 FWD PORT HOLD SPACE TOP 15 TANK 4 AFT PORT HOLD SPACE BOTTOM 25 COMPRESSOR ROOM BOTTOM LOCATION OF DETECTION POINTS FOR GAS DETECTION FOR FL AMMABLE/TOXIC
6 TANK 2 FWD STBD HOLD SPACE TOP 16 TANK 4 AFT STBD HOLD SPACE BOTTOM 26 AIR INTAKE ACCOMODATION SPACE (IN DUCT) PRODUCTS WITH FIXED POINT GAS D ETECTORS.
7 TANK 2 AFT PORT HOLD SPACE BOTTOM 17 VENT MAST AFT 27 AIR INTAKE ENGINE ROOM (FAN ROOM, PORT)
SW2020 GAS SAMPLING SYSTEM DETECTION POINTS
8 TANK 2 AFT STBD HOLD SPACE BOTTOM 18 VENT MAST FWD 28 AIR INTAKE ENGINE ROOM (FAN ROOM, STBD)
LOCATION OF SAMPLE POINTS FOR GAS DETECTION FOR FLAMMABLE/TOXIC
9 TANK 3 FWD PORT HOLD SPACE TOP 19 AIRLOCK TOP 29 ENTRANCE CORRIDOR OF ACCOMODATION 'A' DECK PORT PRODUCTS WITH FIXED GAS SAMPLING SYSTEM.
10 TANK 3 FWD STBD HOLD SPACE TOP 20 AIRLOCK BOTTOM 30 ENTRANCE CORRIDOR OF ACCOMODATION 'A' DECK STBD
27 29 15 13 11 9 7 5 3 1
P RO
VIS
ION
C RA
NE
(P&
S)
SPILL TK(P&S)
UP
DN UP
GARBAGE UP
UP
LKR
CO2 RM FIRE
M.V. M.F.
LKR AIR
& L OCK
M.V.
B.A. WALKWAY
BOTTLE
WALKWAY
ACCOMMODATION
ENGINE DOME UP DN
H DOME UP DOME DOME
C.L. UP C.L.
DN C.P.
A. P. 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260
EXAMPLE OF AN INSTALLATION
H H
PAINT & DECKTORE
S
DECK STORE
R.H.
M.F. M.V.
EMER.
D/GEN.RM.
DN UP
UP
28
26 30 16 14 12 10 8 6 4 2
27
26 29 30
28
14 13
19 22 21 24 25 17 10 9 18 6 5 2 1
20 23
VOID
VOID
BOSUN STR
STEERING GEAR
ROOM F.W.TK(S)
2ND DECK
EMER.
F.P.
SPACE ENGINEROOM COFFERDAM (P&S)
E.
T
NO.3 CARGO TANK NO.2 CARGO TANK
A.T.
3RD DECK
NO.4 CARGO TANK NO.1 CARGO TANK
E.
T
C.W.T.
B10
Installation
Salwico SW2020
16 15 12 11 8 7 4 3
Salwico SW2020
Installation
B11
Salwico SW2020
Installation
Installation of the valves shall be made in the wall between the safe and explosive
zones. Holes are cut for the insertion of welding sleeves with an internal thread, the
shut-off valve then being screwed on from inside a safe zone by means of taper thread
couplings supplied and sealed with ”Loctite 577”.
NB!
All valves should be marked with the number of the corresponding sampling point.
It is important that the mutual distance between the valves is taken into consideration,
and that the sampling pipes from the analysing unit are installed in such a way that any
service on an individual shut-off valve can be carried out without any unnecessary
dismounting of other pipes.
B12
Salwico SW2020
Installation
2.6.1 FILTERS
Each individual sampling pipe should be protected with filters in order to avoid fouling
of both the pipes themselves as well as flame traps, valves, flow meter and detector.
On-Line Filter
This filter is used for such sampling pipes where end-line filters cannot be used for a
variety of reasons, such as areas which may be temporarily water-filled or where
access is for other reasons, so difficult that necessary filter replacement may be
impaired or neglected.
Installation of on-line filters must be done in such a manner that the filter is easily
accessible for replacement, without causing unnecessary strain on pipes and
connections. The online filter should always be placed as close to the sampling point
as is practically feasible, but never in a safe zone. The nipples should be tightened in
accordance with pipe connections, see chapter 2.
We recommend that each individual filter should be marked with its corresponding
sampling point number.
B13
Salwico SW2020
Installation
In certain areas care must be taken to prevent oil or water from being sucked into the
sampling pipes, and in such cases a height above the bottom of 0,5 m or more can be
allowed. Corners, where the air circulation is low, should be avoided. Note that the last
0.2 m of the pipe termination end must point downwards.
Each pipe termination should be marked with the corresponding sampling point
number.
Option
• Cofferdams
• Pipe tunnels
• Hold spaces around cargo tanks
• Other empty areas adjacent to slop tanks
In accordance with these rules it is essential that the planned number of sampling
points and their location including the pipe installation should be evaluated and
commented on by the classification societies prior to installation.
Salwico SW2020 has one sampling point for internal monitoring of the analysing
cabinet, normally the last sampling point.
B14
Salwico SW2020
Installation
SYSTEM FAILURE GAS WARNING ( LOW ALARM) GAS ALARM (HIGH ALARM)
INPUT 230 VAC
NORM. ACT. NORM. ACT. RES ET WHEN RES ET WHEN RES ET WHEN RES ET WHEN
CONVE RTER
20
21
31
41
51
71
61
19
29
49
22
23
25
26
27
28
30
32
42
43
45
46
47
48
50
52
69
70
72
24
44
62
63
65
66
67
68
64
EMERG. POWER
INPUT 230VAC
MODBUS
B15
Salwico SW2020
Installation
B16
Salwico SW2020
Installation
GAS SAMPLING SYSTEM SW2020, COMMISSIONING SET-UP
Ref no: SG- Yard: Hull no:
Start up time: sec Alarm delay time: sec Date:
ALARM LEVELS
Det #1: Low High Det#2: Low High
Det #3: Low High Det#4: Low High
B17
Salwico SW2020
Installation
Fill in
Description / Task / Check Sign./ Date:
data:
When this document has been completed, two copies shall be made: one copy for the shipowner and one
copy to be sent to:
Consilium Marine AB
Attention: After Sales Department
P.O. Box 8763
SE-402 76 GÖTEBORG, SWEDEN
B18
Salwico SW2020
Operation
3. OPERATION
C1
Salwico SW2020
Operation
GAS
SAMPLING ALARM
POINT LEVEL
DETECTOR
F1 F2 F3 F4
7 8 9 FAULT
4 5 6 M
1 2 3 R
0
The Control Unit of the SW2020 Gas Sampling System is divided into two separate
parts.
The left-hand side consists of only three keys: ALARM MUTE, ALARM RESET and
ALARM IN QUEUE. The ALARM IN QUEUE key is used to find a gas alarm in the
gas alarm list and the two other keys to either mute or to reset an alarm (the gas
level is measured again to see if the alarm condition has disappeared).
The right-hand side is used for operation of the system. Just press one of the six
LIST and SETUP keys to start managing the system. All six keys will open a list of
items (sampling points, alarms etc.).
Use the four arrow keys to find the item you want and use the function keys to select
an action to perform.
The function of each individual push-button key on the control unit is described
below.
Button Function
LIST – List all sampling points in the system. Use Ç, È, PgÇ
SAMPLING POINTS and PgÈ to choose a sampling point.
LIST – List all disconnected sampling points, external control
DISCONNECTION’S and detectors.
Use Ç, È, PgÇ and PgÈ to choose an entry.
LIST – List all gas alarms in the system. Use Ç, È, PgÇ and
ALARMS PgÈ to choose an entry.
LIST – List all faults in the system. Use Ç, È, PgÇ and PgÈ to
FAULTS choose a fault.
SETUP – List all sampling points in the system. Use Ç, È, PgÇ
SAMPLING POINTS and PgÈ to choose a sampling point. Access level is
required to change settings.
SETUP – List all general settings in the system. An access level
GENERAL SETTINGS above 1 is required to change most settings.
F1 ,F2 ,F3, F4 Function keys. Push here to perform an action.
0, 1, 2 – 9 Numeric input buttons
↵ (ENTER) Used to accept a numeric input
ESC Go to the previous menu.
C2
Salwico SW2020
Operation
HOME Go to the standby menu.
Ç List the next list entry. The LED is lit when the button is
active.
È List the previous list entry. The LED is lit when the
button is active.
Pg Ç Display the fifth list item to come (the list must have
more then 5entries).
Pg È Display the fifth previous list item.
M – FAULT MUTE Mute all faults in the system.
F – FAULT RESET Reset a fault in the fault list.
ALARM MUTE Mute all gas alarms in the system.
ALARM RESET Reset the displayed sampling point in alarm.
ALARM IN QUEUE Display the next gas alarm in the alarm list.
C3
Salwico SW2020
Operation
** RUNNING ** <12:01:54>
sp5: Tank 2 FWD port hold space bottom
0 %LEL CxHy
The standby menu displays the system status. Another message could be:
** STARTUP ** <12:01:54>
Please wait -
System check in
progress...
The standby mode can be identified by the clock in the upper right corner and can be
reached by pressing the HOME key. The control unit will automatically return to
standby mode after 30 minutes of inactivity.
You could for instance make a manual measurement on sampling point number 5
(SP5) by first pressing LIST – SAMPLING POINTS, then choose SP5 with the arrow
keys and finally press F3 (MEASURE) to start measuring on SP5. The display should
now look like below.
Some menus require a numerical input. Manual measurement is one of them. Enter
a new value with the numerical keyboard. Press ENTER to change the new value
into the current value and press F1 to start measuring.
Just press F1 if you want to start measuring using the default value (5-minutes).
The display will now show the measurement value on the selected sampling point.
The system used in the examples in this manual consists of 60 sampling points and
one detector measuring hydrocarbon gases (CxHy).
C4
Salwico SW2020
Operation
3.2.3 GAS ALARM
With reference to the alarm list:
1. When the “Alarm Mute” button is pressed, the acoustic alarm stops and all alarm
outputs with mute functionality are deactivated. The scanning cycle continues and
will give new alarms for each sampling point exceeding the alarm level. The alarms
are stored in the Alarm List and the SP of the last occurred alarm is shown as well as
the alarm level “LO” or “HI”.
2. Activation of the “Alarm Reset” button starts a revaluation of the SP in alarm. An
“Alarm Reset” request will stop the sampling sequence and make a new
measurement. This revaluation is to be able to accept an alarm reset on the SP if the
level is now below the alarm level. If You push the “Alarm in Queue” button and
make a Reset of all SP’s in alarm, the system will start re-evaluating these SP’s one
by one. It may therefore take a while to complete alarm reset for several SP’s.
1. An Analyse pump, flow failure is caused by the flow switch FS and stops the pump
and scanning sequence if the system does not have the pump redundancy option.
The FS is detecting that the pump pressure is too low. The cause is probably a
membrane leakage of the pump or a fault of the FS itself. Service is needed if the
fault cannot be reset.
3. Analyse Pump or Internal Leakage is indicated when the automatic leakage
control fails. This control is automatically done once per 24 hours by closing all the
sampling valves, running the analysing pump and checking that the vacuum switch
VS1 is activated. If the VS1 is not activated the cause is a leakage at the vacuum
side of the pump from pipes, solenoid valves, pipe couplings or the VS1 itself.
4. Calibration. This fault indicates that zero or span calibration is not completed due to
a value that is out of range, either due to a gas detector fault or a test gas fault. The
bottle might be empty or the test gas mixture is not corresponding to the value that is
set for span calibration.
5-8. Gas Detector 1-4. Indicates a fault depending on which type of detector that is in
use. There might be a loss of power, a dirty mirror in an IR-detector or a sensor
failure etc.
10. Fault compressed instrument air. Indicates that the pressure from the pressure
regulator is below 2.8 Bar.
C5
Salwico SW2020
Operation
12. Flow fault on SP#. Indicates a flow fault on the SP listed. Before indication of a flow
fault the automatic pipe cleaning function first attempt to remove the cause of the
flow fault by flushing the sampling pipe during 15 seconds and then tries to obtain a
new sample. If the flow fault still remains the sampling point is automatically
disconnected and a flow fault alarm is generated and listed in the fault list. The
scanning cycle continues to the next sampling point. As long as the flow fault for a
certain sampling point is listed in the fault list the fault remains. To be able to reset
the flow fault the cause has to be removed. If a mistake was done concerning a SP
in a ballast tank that should normally had been disconnected before ballasting the
SP has to be disconnected via “List Sampling Point” Key.
13. Fuse fault as indicated. Switch off the main power and change the broken fuse.
14. Low 5 volt in control unit. Service or exchange of the unit might be necessary.
17. Analysing unit no answer, indicates that there is no contact with the PCB –RIOK-
40. The reason might be a function fault, power fault, fuse fault or a cable brake.
18. Analysing unit booted, indicates that the fault message according to 17 is reset.
19. No custom set-up, using factory (default) set-up, indicates that custom related
settings are not done. This normally only occurs the first time the system is started at
the workshop.
20. Flash memory error in control unit indicates a faulty flash memory. Exchange of
the same might be necessary. Consult the service department for assistance.
21-24.Negative drift, analyser 1-4 (Abnormal condition). Calibrate the detector.
C6
Salwico SW2020
Operation
3.3 LISTS
All operations required by the average user can be performed from the four lists in
the system.
When you want more detailed information about an alarm press LIST ALARMS on
the right-hand side of the control unit. This list is opened automatically when a new
gas alarm is detected. Use the arrow keys to display the next and previous alarms.
The display below shows the first alarm of three. The alarm occurred on sampling
point 1 and 43 %LEL CxHy (Alarm level ’Hi’) was measured.
Mute faults by pressing the FAULT MUTE key and reset faults by pressing the
FAULT RESET key.
C7
Salwico SW2020
Operation
C8
Salwico SW2020
Operation
Select a sampling point with the arrow keys (sampling point 5 is selected in the
example below) and then use the function keys to perform an action.
Actions such as purge and manual measure can not be performed on disconnected
sampling points. The only allowed action on a disconnected sampling point is
RECONNECT.
C9
Salwico SW2020
Operation
Sampling point 1 to 8 are members of group 1 in the example below. The group
members and the free text on row 2 (STB Water ballast tanks, SP 1-8) are
configurable in SETUP but requires access level 2.
** GROUP 1(3) **
Grp1: FWD port hold spaces, SP1-8
DISCONNECT
And reconnected again, the user will be asked to automatically purge all sampling
points in the group (recommended). Take care when reconnecting a whole group -
make sure that all areas are empty and do not require IG Mode (if that option is
implemented).
** GROUP 1(3) **
Grp1: FWD port hold spaces, SP1-8
RECONNECT
** GROUP 1(3) **
Grp1: FWD port hold spaces, SP1-8
RECONNECT DISCONNECT
Disconnected sampling points are listed here. Reconnect the chosen sampling point
by pressing F1 (RECONNECT).
Disconnected sampling points and activated external control off are listed here.
It is possible to deactivate the external control by pressing F1 (RECONNECT).
C10
Salwico SW2020
Operation
The system changes the access level and enters CONFIGURATION MODE when
the correct access code for level 2, 3 or 4 is entered. The system will not start until
the user chooses to start the system again (the access level is automatically
changed back to 1) or the user timeout expires after 30 minutes.
Choose a menu with the Arrow Keys. The menu numbers in this document are
shown between brackets in each header.
Enter the access level you want to change access code for, push ↵ and then F1 to
continue. The code can only be changed for access levels lower or the same as the
current access level (level 2 in the example below).
Enter the new 4-digit access code, push ↵ and then F1 to continue.
Enter the same access code again and push ↵. The result of the operation is
displayed on row 3.
C11
Salwico SW2020
Operation
Push F1 to print the system configuration. Printing the systems configuration can,
needless to say, only be done when there’s a printer in the system.
TEST
TEST
The External Control Off disables steering of external output of type GAS ALARM.
Start the External Control Off functionality by pressing F1. Default timeout values is
5 minutes but can be changed by the numeric keys.
Deactivate the External Control Off by pressing F2 when it is running.
After the timeout has expires the External Control Off is deactivated automatically.
C12
Salwico SW2020
Operation
Push F1 to check the system (valves and connections) for internal leakage.
START STOP
Push F1 to restart the sampling sequence. The system will change back to access
level 1 and save the current system configuration.
Push F1 to restart the sampling sequence. The system will change back to access
level 1 but will NOT save the current system configuration. All changes to the system
configuration will be lost.
C13
Salwico SW2020
Operation
Gas detectors must be adapted and calibrated to the system on the A/D inputs with
two different gas concentrations: Zero and a Span gas value determined by the user
(the span gas value must be in the area 25-100% off the highest measurement for
the gas detector).
Calibration of span is only accepted when dS, in figure 1, is below a certain value
depending on the brand and type of gas detector.
M e a s u re d
G a s -v a lu e Id e a l g r a p h
S pan
dS R e a l g ra p h
0
d0
0 Span
E x p e c te d
G a s - v a lu e
F i g u r e 1 : T w o -p o in t c a lib ra tio n . “ G a s -v a lu e s ” b e lo w 0 a re in t e r p r e te d
a s “n e g a tiv e d rift ” o r a s a fa u lt c o n d itio n .
C14
Salwico SW2020
Operation
Select one detector (1-4) to calibrate by entering a numeric input and ↵. Push F1 to
continue.
Enter the concentration of the span-gas. Push F1 to continue. Note that the
procedure for calibrating span for Oxygen will differ.
Open the valve(s) connecting the test-gas bottle to the test-gas tube in the analysing
unit. Push F1 to continue.
Start the calibration procedure and change to menu 12d by pushing F1. The
measured gas-value can now be seen on row 2.
Wait until the measured gas-value has stabilised and then calibrate the detector with
F1.
If calibration fails:
• Check that the test gas bottle is not empty.
• Check the tube to the test gas bottle.
• Calibrate the gas detector manually according to the calibration procedure
(The procedure depends on the brand and type of gas detector).
CALIBRATE EXIT
Note: After a successful calibration, finish by saving the current setup (10).
C15
Salwico SW2020
Operation
Adjust zero on a gas detector (13)
Calibration of zero in the system on the A7D inputs for a gas detector is done with air
from the fresh air inlet (except for O2, described separately below).
Select one detector (1-4) to calibrate by entering a numeric input and ↵. Push F1 to
continue.
ADJUST
Note: After a successful calibration, finish by saving the current setup (10).
Select one detector (1-4) to undo calibration by entering a numeric input and ↵. Push
F1 to undo calibration of the chosen detector. The previous value is presented on the
control unit.
C16
Salwico SW2020
Operation
3.4.2.2 Calibration procedure for gas detectors with 4-20 mA output signal.
These types of detectors are factory calibrated. They have a continuous self-test
function and report dirty optics and fault by setting the output signal:
4 mA +/- 0,3 mA: Normal zero level
1 mA for 3 sec at 5 min intervals: Early indication of dirt accumulation on windows.
1 mA continuously: Dirt accumulation on windows
0 mA: Internal Malfunction
Check the output signal by connecting an Ampere meter measuring the current in the
range 0-30 mA DC in serial with the electric cable from terminal 3 on the detector
and the system terminal 353.
The following described calibration procedure is performed during the zero and span
set-up calibration from the control panel.
Remove the cover from the detector. Connect an Ampere meter measuring the
current in the range 0-30 mA DC on terminal M1(+) and M2(-) at the PCB.
Zero adjustment: Apply clean air and adjust on the potentiometer P2 to 4 mA.
Due to the fact that this detector is a catalytic type and the sample is taken from an
inert gas area, the sample needs to be diluted with 50% air. The detecting range for
the detector is 0-100% LEL. If the detector is reading 25% LEL (diluted), the actual
value of the sampled gas is 50% LEL. Consequently, every reading is doubled in the
panel. When the detector is system calibrated, the calibration gas is not diluted. A
calibration gas of 45% LEL will show 90% LEL on the display.
Span calibration: Apply calibration gas. Adjust the output current on potentiometer
P3.
The current can be calculated using the following formula:
Since the gas is diluted with 50% air, every reading is doubled in the panel. When
the detector is system calibrated, the gas is not diluted. A calibration gas of 45% will
correctly indicate 90% on the display.
The following described calibration procedure is performed during the zero and span
set-up calibration from the control panel.
Remove the cover from the detector. Connect an Ampere meter measuring the
current in the range 0-30 mA DC on terminal M1(+) and M2(-) at the PCB.
Zero adjustment: Apply clean air. OBS for zero calibration of oxygen detectors, use
our combined calibration gas with Nitrogen (N2) base or 100 % N2.
Adjust on the potentiometer P3 to 4 mA.
Span calibration: Apply calibration gas. Adjust the output current on potentiometer
P1.
The current can be calculated using the following formula:
C17
Salwico SW2020
Operation
Current I mA = ((16 mA/full scale gas) x (calibration gas concentration x 2)) + 4 mA
Note!
After the calibration and in order to set the new values, always finish in menu 11.
“Restart the system, save the current set-up”.
Change the current number of groups with a numeric input and ↵. A group is a
collection of Sampling Points, the groups defined in this menu are configured
individually in the Sampling Points Setup, see 3.5.
C18
Salwico SW2020
Operation
Change the current start-up time with a numeric input and ↵. The start-up time
determines how long the SW2020 will wait after power-on before starting the
sampling sequence (to allow warm-up of gas detectors).
Change the current alarm delay time with a numeric input and ↵. The alarm delay
time determines how long the SW2020 waits before measuring after gas from the
correct Sampling Point has arrived at the detector(s).
Figure 2: Measurement on a
sampling point.
This time should be equal to the reaction time of the slowest gas detector in the
system
Change the current measurement time for all sampling points with a numeric input
and ↵. The measurement time for a Sampling Point is the time it takes for the gas to
arrive from the SP to the detector(s). See figure 2
Observe that measurement times for individual measurement points will be lost.
C19
Salwico SW2020
Operation
Change the current alarm level for all sampling points. Observe that alarm levels for
individual measurement points will be lost.
Choose a gas detector with a numeric input and ↵. Continue with F1.
Choose the alarm level to change (High or Low) with F2 and ↵. Continue with F1.
Enter the new alarm level with a numeric input and ↵. Exit with F1.
Enter the new sampling sequence length with a numeric input and ↵. Continue with
F1.
Menu 20b is a list where the index in the sampling sequence is chosen with the
arrow keys; the current sequence index can be seen on row 3. The sampling point
corresponding to a sequence index is changed with a numeric input and ↵. Abort
definition of the sampling sequence with F1 and save the current sequence with F2.
Push F1 to change back to access level 1 and restart the sampling sequence with
the configuration that was defined at the factory.
All custom settings (changes in the configuration after delivery) will be lost.
C20
Salwico SW2020
Operation
Push SETUP - Sampling Points and then use the Arrow Keys to choose the
sampling point (or group) to configure. Access level 2 is required to enter the
Sampling Points Setup.
CONTINUE
ABORT SAVE
The new text is entered with the alpha - numeric keyboard and the backspace button
(←).
Push an alpha - numeric button until you see the desired symbol and then wait for
the timer to expire (about one second) to add the symbol to the free text.
The symbols associated with each alpha – numeric button are written on the buttons.
Note that upper and lower case letters as well as the numeric itself is available for
each button.
Save the new free text with F2 or return to previous menu without saving with F1 (or
ESC).
Note:
Leave the setup mode with (10) if the new settings should be saved.
C21
Salwico SW2020
Operation
Push F2 to change the alarm level. Choose a detector with a numeric input and ↵.
Push F1 to continue.
Enter a new alarm level with numeric input and ↵. Push F1 to finish.
Push F3 to change the measurement time. Enter a new measurement time with
numeric input and ↵. Push ESC to finish.
The measurement time for a Sampling Point is the time it takes for the gas to arrive
from the SP to the detector(s). See figure 2.
C22
Salwico SW2020
Operation
3.5.2 CONFIGURING A GROUP
If a number of groups are configured in the system (see 3.4.), they will be present in
the Sampling Point List. Use the Arrow Keys to select a Group.
TEXT DEFINE
CONTINUE
ABORT SAVE
The new text is entered with the alpha - numeric keyboard and the backspace button
(←).
Push an alpha - numeric button until you see the desired symbol and then wait for
the timer to expire (about one second) to add the symbol to the free text.
The symbols associated with each alpha – numeric button are written on the buttons.
Note that upper and lower case letters as well as the numeric itself is available for
each button.
Save the new free text with F2 or return to previous menu without saving with F1 (or
ESC).
Push F1 to ADD a Sampling Point to the Group. Push F2 to remove the last
Sampling Point from the Group and push F3 to exit the menu.
Define group 3
Sp:1,2,3
Push F1 to ADD Sampling Point 4 to the group or enter a new Sampling Point with
numeric input and ↵. The ESC button will return to the previous menu without adding
a new sampling point.
ADD
C23
Salwico SW2020
Operation
Alarm levels:
See this manual chapter 3 Gas alarm.
There are two alarm levels in the SW2020:
- At 99% L.E.L., Low alarm will occur
- At 100% L.E.L., High alarm will occur
Fault Alarms:
See this manual chapter 3 Fault alarm.
C24
Salwico SW2020
Technical Data
4.TECHNICAL DATA
D1
Salwico SW2020
Technical Data
D2
Salwico SW2020
Technical Data
D3
Salwico SW2020
Technical Data
Outputs on RIOK-41´s
Output Terminal Position Description
16 2 V101 Solenoid Valve Sampling Point 1
17 4 V102 Solenoid Valve Sampling Point 2
18 6 V103 Solenoid Valve Sampling Point 3
19 8 V104 Solenoid Valve Sampling Point 4
20 10 V105 Solenoid Valve Sampling Point 5
21 12 V106 Solenoid Valve Sampling Point 6
22 14 V107 Solenoid Valve Sampling Point 7
23 16 V108 Solenoid Valve Sampling Point 8
24 2 V109 Solenoid Valve Sampling Point 9
25 4 V110 Solenoid Valve Sampling Point 10
. .
. .
. .
n Vn Solenoid Valve Sampling Point n
D4
Salwico SW2020
Technical Data
FA FA FA FA FA FA FA
FA FA FA FA FA FA FA
A A A A A A A
V3 A
S
DILUTION FM3
PUMP 15L 150
0
FS FA
P2 FS2
VS
VS1 M
S1 ANALYZING FM3 ST600 VCM ST400 NH3
PUMP 15L 150 0-100%LEL 0-100%±PM
A P 0
FS FA
P1 FS1
P G1 G2
M V4 A
V2 A
P R
V5 FA
S
FRESH AIR
INLET TEST GAS OUTLET
INLET
D5
Salwico SW2020
Technical Data
FA FA FA FA FA FA FA
FA FA FA FA FA FA FA
A A A A A A A
V3 A
S
DILUTION FM3
PUMP 15L 150
0
FS FA
P2 FS2
VS
VS1 M
S1 ANALYZING FM3 ST600 VCM ST400 NH3
PUMP 15L 150 0-100%LEL 0-100%±PM
A P 0
FS FA
P1 FS1
P G1 G2
M V4 A
V2 A
P R
V5 FA
S
FRESH AIR
INLET TEST GAS OUTLET
INLET
D6
Salwico SW2020
Technical Data
D7
Salwico SW2020
Technical Data
FA FA FA FA FA FA FA
FA FA FA FA FA FA FA
A A A A A A A
V3 A
S
DILUTION FM3
PUMP 15L 150
0
FS FA
P2 FS2
VS
VS1 M
S1 ANALYZING FM3 ST600 VCM ST400 NH3
PUMP 15L 150 0-100%LEL 0-100%±PM
A P 0
FS FA
P1 FS1
P G1 G2
M V4 A
V2 A
P R
V5 FA
S
FRESH AIR
INLET TEST GAS OUTLET
INLET
D8
Salwico SW2020
Technical Data
120
100
80
Sampling time, second
60
40
20
0
0m 50m 100m 150m 200m 250m 300m
Pipe length, meter
Sampling pipe length, m 0 25 50 75 100 125 150 175 200 225 250 275 300
Sampling time, sec 10 15 22 28 35 43 52 61 70 80 91 105 120
Diagram for calculation of the optimal sampling time is 6 mm. For a SW2020-system with two pumps the sum
corresponding to the sampling point length. The pump of presuction and analysing time is the total sampling
capacity is 15 L/min and the sampling pipe inner diameter time to insert in the setup for the sampling points.
D9
Salwico SW2020
Technical Data
The vacuum pump 107 CCD20 used in the SW2020 Gas Sampling System is a
membrane pump designed for a high degree of efficiency when it is used for
vacuum.
It is designed for continuous operation with permanently lubricated bearings, a
long life Buna “N” diaphragm, stainless steel valves and aluminum valve plate.
The pump is balanced for low vibration operation and in addition mounted on
shock absorbers.
The diagram for calculation of sampling time previous in this manual is a result
from real tests on vacuum pump 107 CCD20, with sampling pipes of inner
diameter 6 mm.
The flow meter and the flow switch monitor the flow capacity of the pump.
The system vacuum guard or the flow switch supervises the tightness of the
pump membrane.
DATA:
MAINTENANCE:
Below procedures refer to the drawing and part list found on the next page.
Exchange the diaphragm (item 3) by removing the diaphragm hold down plate
(item 5) with the four screws (item 4).
Our Spare part set for the pump Art. No. 7360, contains diaphragm, valve
flappers and valve plate gasket (item 3, 20 and 23).
D10
Salwico SW2020
Technical Data
D11
Salwico SW2020
Technical Data
D12
Salwico SW2020
Spare Parts List
E1
Salwico SW2020
Spare Parts List
ART.NO 1720
ART.NO 1710
E2
Salwico SW2020
Products list
6. PRODUCTS LIST
F1
ANALYZING UNIT
F2
Products list
Salwico SW2020
Pos Description Code Type Data Art. No
F3
Products list
Salwico SW2020
Salwico SW2020
Maintenance
7. MAINTENANCE
G1
Salwico SW2020
Maintenance
General
The SW2020 gas sampling system has no parts that need daily maintenance
and since the central continuously supervises itself it will generate a fault
message if something is malfunctioning.
The daily handling of the system is described in the document “Guidelines for
the daily handling of Salwico SW2020”. It is essential to follow these guidelines
in order to have a reliable and functional system.
Maintenance
Every 3-6 months it is also recommended to visually check that the sampling
pipes from the central cabinet to the deck passage are not broken in any way.
Additional information
There is an online filter on each sampling line and it might get filled with dust or
dirt etc. If such a filter is blocked the remedy is to replace the filter.
The central will generate a sampling point flow fault alarm any filter is blocked.
On-line filter
The online filter has an internal sinter filter, which is replaceable.
The recommendations are to always have some spare filters in the spare part
set.
G2