3500 Installation and Operation Manual
3500 Installation and Operation Manual
3500 Installation and Operation Manual
* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric
Company.
Contact Information
The following contact information is provided for those times when you cannot contact your
local representative:
USA
1.775.782.3611
Telephone
1.800.227.5514
Fax 1.775.215.2873
Internet www.GEmeasurement.com
Additional Information
NOTE
This manual does not contain all the information required to operate and maintain the product. Refer to the
following manuals for other required information.
3500 Monitoring System Installation and Maintenance Manual (part number 129766-01)
3500 Monitoring System Rack Configuration and Utilities Guide (part number 129777-01)
Contents
1. Receiving and Handling Instructions 1
2. Installing a New System 2
2.1 Receiving, inspecting, and handling 2
2.2 Installing the rack 2
2.3 Connecting Power 14
2.4 Connecting devices to the Rack Interface Module 17
2.5 Connecting the field wiring to the I/O modules 18
3. Operating the System 20
3.1 Verifying Configuration 20
3.2 Operating Switches 21
3.3 System Contacts 21
3.4 Reading the LEDs 22
3.5 Collecting Data from Output Terminals 26
4. Common Maintenance Procedures 28
4.1 Changing configuration 28
4.2 Module Configuration Retention and Storage 28
4.3 Replacing Modules 30
4.4 Verifying channels 34
Circuit boards contain devices that are susceptible to damage when exposed to electrostatic
charges. Damage caused by obvious mishandling of the board will void the warranty. To avoid
damage, observe the following precautions in the order given.
l Avoid tools or procedures that would subject the circuit board to static damage. Some
possible causes include ungrounded soldering irons, non-conductive plastics, and similar
materials.
l Use extra caution during dry weather. Relative humidity less than 30% tends to multiply the
accumulation of static charges on any surface.
Note that in order to connect field wiring to the I/O modules, you will need additional information
provided in the 3500 Field Wiring Diagram Package, part number 130432-01.
Verify that your rack is fully assembled. A fully assembled rack has modules or covers labeled
“Future Expansion” in all slots on the front of the rack and has I/O modules or connector covers
on all slots on the back of the rack. If your rack is not fully assembled, contact your local
representative.
Customers and third parties that are in control of product at the end of its life or at the end of its
use are solely responsible for proper disposal of product. No person, firm, corporation,
association or agency that is in control of product shall dispose of it in a manner that is in
violation of United States state laws, United States federal laws, or any applicable international
law. Bently Nevada, Inc., is not responsible for disposal of product at the end of its life or at the
end of its use.
Illustration
See "Installing a panel mount See "Installing a Bulkhead See "Installing a rack-mount
Refer to
rack" on page 3 mount rack" on page 8 rack" on page 10
Caution
Do not use clamps as handles while carrying or installing the rack. The clamps may fall off resulting in injury to
personnel and damage to the rack.
Caution
Do not use clamps as handles while carrying or installing the rack. The clamps may fall off resulting in injury to
personnel and damage to the rack.
(2) Clamp.
1. 3500 Mini-rack
2. Adapter Panel
3. Standard 19-inch EIA rack
I/O Module
2. Verify that the power source matches the values listed under “Power requirements” in the
table above
3. Install a power switch or circuit breaker close to the rack and mark the switch or breaker as
the disconnect device for the rack.
WARNING
HAZARDOUS VOLTAGE
RISK OF ELECTRIC SHOCK OR BURN.
Multiple power sources may be present.
User proper isolation techniques and remove all power prior to servicing.
5. Connect the power cable as shown in the following figure and table:
(1) Power cable. Select a wire gage and type that meets the local code requirements
and meets the power requirements as listed in Table 2-1: Power Supply I/O Modules,
using Table 2 2: Power wire legend to identify the wires.
(3) Lug Connector. A #6 stud size Spade Lug Connector with an insulated ferrule must
be used when wiring the Power Input Module. Ensure that the ferrule completely
covers any exposed wire.
6. Close the hinged terminal protector. The terminal protector must remain in place to guard
against inadvertent contact.
The OK Relay is normally energized and is used to indicate System contacts let you use external contacts to
whether the 3500 Monitoring System is OK. control the operation of the rack.
OK Relay contact rating: 5 A @ 24 Vdc or 5 A @ 120 Vac Wiring recommendations: 18 AWG to 22 AWG
50/60 Hz or 3 A @ 220 Vac 50/60 Hz resistive maximum. stranded 2-wire shielded with insulating sheath.
Note
Shields are spliced into a single wire then grounded at the stud marked “SHIELD”. Shields should be insulated.
Temporarily increases the alarm (Alert and Danger) setpoint values by a specific multiple
Trip (usually two or three). This function is normally applied by manual (operator) action during
TM
multiply startup to allow a machine to pass through high vibration speed ranges without monitor alarm
indications.
Rack
Used to prevent an alarm from being declared on any monitor or relay in the 3500 rack. This is
INHB alarm
typically used when performing maintenance functions.
inhibit
Used to signal when the modules in the 3500 rack are to be reset. This contact has the same
RST Reset
function as the Rack Reset switch on the front panel of the Rack Interface Module.
Connect transducer wires Simplify wiring at the rear of the rack by using cables to connect external
directly to the I/O modules termination I/O modules to external termination blocks.
Refer to the 3500 Field Wiring Diagram Package, part number 130143-01, for information about
how to connect transducer field wiring to the I/O modules in your rack.
• Verifying configuration
• Operating switches
• Reading LEDs
After power is applied to the rack, the configuration LED (CONFIG OK) indicates that the rack
contains a complete and correct configuration.
Reset switch
Clears latched alarms and resets Timed OK Channel Defeat indications. If the Configuration LED is
blinking at 5 Hz, it will be stopped. This switch performs the same function as the Rack Reset
contact on the Rack Interface I/O Module.
Key Switch
Prevents unauthorized changes to the configuration settings. When the switch is in the RUN
position, the 3500 rack cannot be configured. When the switch is in the PROGRAM position, the
3500 rack can be configured and the rack continues to operate normally. By removing the key,
you can lock the Rack Interface Module in the RUN or PROGRAM position.
Trip multiply ( TM )
Temporarily increases the alarm (Alert and Danger) setpoint values by a specific multiple (usually
two or three). This function is normally applied by manual (operator) action during startup to
Reset ( RST )
Same function as pressing in the RESET switch on the front of the rack.
Figure 3 - 4: LEDs
3500/15 Power SUPPLY all of the output voltages from the supply are within
below
Supply OK specification.
Flashes at the rate that messages are sent from the See "OK and TX/RX
Most 3500 modules TX/RX
module. LEDs" on page 24
CHn An alarm condition has occurred with this relay. See "Relay Alarm
3500/32 and 34 Relay
ALARM (Where “n” is the channel number 1 through 4.) LED" on page 25
TEST
3500/53 Overspeed The module is in test mode See "Test mode" on
MODE
Protection system page 26
ALARMS
On All of the output voltages from the supply are within specification No action required
Off An output voltage from the supply is not within specification Refer to the following procedures
Module is not configured or is in Reconfigure the module (see 3500 Rack Configuration
1 Hz 1 Hz
configuration mode Guide, part number 129777-01)
Not
XX Module is not operating correctly Check the System Event list
flashing
Event lists
Contain records of things that happen to the rack. The system maintains two event lists -- the
Alarm Event list and the System Event list. To view these lists, refer to the 3500 Monitoring System
Configuration Guide, part number 129777-01.
TM LED
Trip multiply temporarily increases the alarm (Alert and Danger) setpoint values by a specific
multiple (usually two or three). This function is normally applied by manual (operator) action
during startup to allow a machine to pass through high vibration speed ranges without monitor
alarm indications.
Config OK LED
Configuration is the process of setting system, module, and channel options so that all the
modules in a 3500 rack work together.
Bypass LED
Bypass is an operating condition of a 3500 monitoring module where functions of all 4 channels
in the monitor are suppressed. When the channels in a bypassed 3500 monitor go in alarm, the
alarm events are posted to the Alarm Event List but any relays that use the alarms from the
monitor in the relay alarm logic will not be activated.
Alarm LED
The 3500 Overspeed Detection System (ODS) consists of mulitiple ODS modules that operate as a
group. The alarms generated from this group are the result of a voting process that is set up in
configuration. The alarm LEDs on the modules in overspeed detection systems indicate the result
of this voting. Use the 3500 Configuration program to determine how this voting has been
configured for the modules in the ODS.
l Changing configuration
l Replacing modules
l Verifying channels
Configuration settings are usually protected by security settings. The security setting for a typical
3500 Monitoring System that is operating normally is “Change Setpoints in Program Mode”. This
section shows how to adjust setpoints. To change other configuration settings, refer to the 3500
Monitoring System Rack Configuration and Utilities Guide, part number 129777-01.
It is recommended to store the current rack configuration file for a particular rack onto a PC and
then reconfigure the rack upon making any changes. The OK LED on the device will not go solid
green if the configuration for that device is not valid.
Note that setpoints can be adjusted only for those parameters that are enabled and that
some parameters have both upper and lower setpoint values. Parameters are enabled or
disabled by using the Channel Option screen. Refer to the 3500 Monitoring System Rack
Configuration and Utilities Guide for more information.
6. For phase setpoints, enter the values for the beginning and ending setpoint in the text
boxes below the phase diagrams.
7. Apply the adjusted setpoints to the rack by clicking OK and then download the revised
configuration to the rack.
3500 modules must have valid configuration settings in order to operate properly.
Replacement modules are not configured. By saving the configuration, you can download
the original configuration settings to the replacement module. The 3500 Monitoring System
Configuration and Utilities Guide, part number 129777-01, shows how to save configuration
files.
l Check that the LEDs for the replaced module are indicating correct operation.
3500 modules must have valid configuration settings in order to operate properly.
Replacement modules are not configured. By saving the configuration, you can download
the original configuration settings to the replacement module.
The 3500 Monitoring System Configuration and Utilities Guide, part number 129777-01,
shows how to save configuration files.
If the wires connected to the I/O module are not labeled, label the wires before you remove
them.
The 3500 Monitoring System Configuration and Utilities Guide, part number 129777-01, shows
how to download configuration files.
9. Verify operation.
l Check that the LEDs for the replaced module are indicating correct operation (see Reading
the LEDs in section 2.4.1).
1. Loosen the screws to the main module so that they are free of the rack chassis, but still
attached to the main module.
2. Use the ejectors to pry the main module loose from the backplane connectors.
3. Once freed from the backplane, the main module can be removed completely from the rack
2. Slide the main module into place, ensuring that they are properly in the guides provided on
the floor and roof of the rack chassis.
3. Tighten the screws securely.
Application Advisory: It is important to tightly secure the thumb screws to ensure each module
is Chassis grounded. Loose thumb screws may allow noise to show on the channel readings.
The 3500 Monitoring System is a high precision instrument that requires no calibration. The
functions of the 3500 modules, however, must be verified at regular intervals. All modules in the
3500 Monitoring System should be verified at these maintenance intervals. The procedures in the
Maintenance and Troubleshooting sections of the module reference manuals describe the
verification and troubleshooting process. (Refer to the reference manuals listed in 3500 Field
Wiring Diagram Package (130432-01)