PowerSeries Pro V1.1 Reference Manual 29010134R005 en
PowerSeries Pro V1.1 Reference Manual 29010134R005 en
PowerSeries Pro V1.1 Reference Manual 29010134R005 en
Models:
HS3032, HS3128,
and HS3248
WARNING: This manual contains information on limitations regarding product use and function and information on the lim-
itations as to liability of the manufacturer. Carefully read the entire manual.
Safety instructions for service personnel
Warning: When using equipment connected to the telephone network, always follow the basic safety instructions provided
with this product. Save these instructions for future reference. Inform the end-user of the safety precautions that must be
observed when operating this equipment.
Before installing the equipment
Ensure your package includes the following items:
l Installation and User manuals, including the safety instructions.
l Read and save these instructions.
l Follow all warnings and instructions specified within this document and/or on the equipment.
l HS3032/HS3128/HS3248 alarm controller
l Power Supply, direct plug-in
Selecting a suitable location for the alarm controller
Use the following list as a guide to find a suitable location to install this equipment:
l Locate near a telephone socket and power outlet.
l Select a location free from vibration and shock.
l Place alarm controller on a flat, stable surface and follow the installation instructions.
l Do not locate this product where people may walk on the secondary circuit cable(s).
l Do not connect alarm controller to electrical the same circuit as large appliances.
l Do not select a location that exposes your alarm controller to direct sunlight, excessive heat, moisture, vapors, chem-
icals or dust.
l Do not install this equipment near water. (e.g., bath tub, kitchen/laundry sink, wet basement, near a swimming pool).
l Do not install this equipment and accessories in areas where risk of explosion exists.
l Do not connect this equipment to electrical outlets controlled by wall switches or automatic timers.
l Avoid interference sources.
l Avoid installing equipment near heaters, air conditioners, ventilators, and refrigerators.
l Avoid locating equipment close to or on top of large metal objects (e.g., wall studs).
l See "Locating detectors and escape plan" on page 285 for information on locating smoke and CO detectors.
Safety precautions required during installation
l Never install this equipment and/or telephone wiring during a lightning storm.
l Never touch uninsulated telephone wires or terminals unless the telephone line has been disconnected at the net-
work interface.
l Position cables so that accidents can not occur. Connected cables must not be subject to excessive mechanical
strain.
l Use only the power supply provided with this equipment. Use of unauthorized power supplies may cause damage.
l For direct plug-in versions, use the power supply module supplied with the device.
Warning: This equipment has no mains on/off switch. The plug of the direct plug in versions of this equipment is intended to
serve as the disconnecting device. It is imperative that access to the mains plug and associated mains socket/outlet is never
obstructed. For permanently connected versions of this equipment the fuse in the connector block is the disconnect device. If
the neutral wire cannot be identified, then this equipment must be connected to a mains source that comes from a dis-
connect device that simultaneously disconnects both poles (Line and Neutral).
Important note for international market (EU, Australia, New Zealand)
This equipment is stationary-fixed and must be installed by Skilled Persons only. Skilled Person is defined as a person with
relevant education or experience to enable him or her to identify hazards and to take appropriate actions to reduce the risks
of injury to themselves and others.
l It must be installed and used within an environment that provides the pollution degree max 2, over voltages category
II, in non-hazardous, indoor locations only.
l Use authorized accessories only with this equipment. Do not place any object on the top of the cabinet of this equip-
ment! Do not spill any liquids on the cabinet.
l Do not touch the equipment and its connected cables during an electrical storm; there may be a risk of electric shock.
l Ensure that cables are positioned so that accidents cannot occur. Connected cables must not be subject to excessive
mechanical strain. Do not use the Alarm system to report a gas leak if the system is near a leak.
l These safety instructions should not prevent you from contacting the distributor and/or the manufacturer to obtain any
further clarification and/or answers to your concerns.
-2-
Contents
Section 1: Introduction 5
1.1 About the system 5
Section 2: Installation 11
2.1 Overview of installation process 11
2.2 Alarm controller installation 11
2.3 General wiring instructions 17
2.4 Installing modules 30
Section 3: Configuration 44
3.1 Basic configuration steps 44
3.2 Using the keypad 44
3.3 Enrollment 45
3.4 Working with partitions 47
3.5 Trouble indicators 48
3.6 Keypad partition setup 48
3.7 Alternate communicator setup 50
3.8 Local firmware upgrade 51
3.9 Testing the system 51
Section 4: System operation 52
4.1 Arming and disarming 52
4.2 Partition vs. global keypad 52
4.3 Labels 53
4.4 Annunciation 54
4.5 Keypad function keys 55
4.6 Language selection 57
4.7 [*] Commands 58
4.8 Visual verification 71
Section 5: Programming 72
5.1 How to program 72
5.2 Programming methods 72
5.3 Programming descriptions 75
Section 6: Programming Worksheets 154
6.1 Label Programming 154
6.2 Zone Setup 160
6.3 End Of Line Resistance 162
6.4 System Times 162
6.5 Access Codes 164
6.6 PGM Programming 164
6.7 System Lockout 187
6.8 System Options 188
6.9 Auto-Arm_Disarm 192
6.10 Partition and Zone Assignment 196
6.11 Communications 199
6.12 Call Directions 207
-3-
6.13 DLS Programming 210
6.14 Virtual Inputs 211
6.15 Schedule Programming 212
6.16 Audio Module Programming 216
6.17 Wireless Programming 224
6.18 Alternate Communicator 225
6.19 Keypad Programming 232
6.20 Template Programming 234
6.21 System Information 234
6.22 Module Programming 235
6.23 Wireless Placement Testing 236
6.24 Battery Settings 237
6.25 Restoring Factory Defaults 238
Section 7: Troubleshooting 239
7.1 Testing 239
7.2 Troubleshooting 239
Appendix 1: Reporting codes 250
Appendix 2: Word library 257
Appendix 3: Template programming tables 258
Appendix 4: ASCII characters 264
Appendix 5: Regulatory approvals 265
5.1 FCC COMPLIANCE STATEMENT 265
5.2 Innovation, Scientific and Economic Development Canada (ISED) Statement 266
5.3 UL/ULC Installations 266
5.4 Aux loading and battery selection 270
5.5 SIA False Alarm Reduction Installations: Quick Reference 270
5.6 EUROPEAN EN50131 COMPLIANCE STATEMENT 272
5.7 UK Compliance Statement 274
Appendix 6: Wiring diagrams 276
6.1 HS3032, HS3128, and HS3248 UL/ULC wiring diagram (North America only) 276
6.2 HS3032 and HS3248 wiring diagram (EN50131 only) HSC3020C enclosure 277
6.3 HS3032 and HS3248 wiring diagram (EN50131 only) HSC3020CP enclosure 278
6.4 Zone wiring 278
6.5 Bell wiring 279
6.6 Aux power wiring 280
6.7 Corbus wiring 280
6.8 PGM wiring 281
6.9 Telephone line wiring 282
6.10 Earth ground wiring 282
Appendix 7: Specifications 283
7.1 Locating detectors and escape plan 285
8.0 Limited warranty 288
8.0 SOFTWARE PRODUCT LICENSE 291
-4-
Section 1: Introduction
Section 1: Introduction
1.1 About the system
The PowerSeries Pro alarm panel is a feature-rich, scalable alarm system designed for commercial use. The alarm panel
supports both hardwired and wireless devices. This section lists the features of the alarm panel, available models, and com-
patible devices.
The following symbols are used to indicate features or methods of operation that are only available in a particular market. No
symbol indicates the feature or operation is available for all markets unless noted specifically otherwise.
CP-01
- North America
EN
- Europe
NFA2P
- France
UK
- United Kingdom
Features
The following features are available on the PowerSeries Pro alarm controller.
Zones, wireless keypads, wireless keys, panic pendants, and proximity tags
The system supports the following devices:
l 32 or 128 wireless zones or 32, 128, or 248 wired zones. This includes the 8 wired zones available on the con-
trollers.
l 41 zone types and 15 programmable zone attributes.
l 8 or 16 separate keypads supported.
l 32 separate wireless keys supported.
l 72 or 1000 separate proximity tags supported.
Access codes
l Up to 1002 access codes: 1000 (level 2-EN) including one system master code (level 2-EN). In addition, one installer
code (level 3-EN), and one maintenance code are available.
Note: EN50131-1 compliant systems using more than 100 access codes shall set the access code to 8 digits (section
[041], option 02).
l Programmable attributes for each user code (see "Access code attributes" on page 65)
Programmable outputs (PGMs)
l Up to 4 programmable outputs (PGM) on the alarm controller with 50 available options
l 44, 166, or 180 maximum programmable outputs for HS3032, HS3128, HS3248.
System supervision features
The PowerSeries Pro continuously monitors a number of possible trouble conditions and provides audible and visual indic-
ation at the keypad. Trouble conditions include:
l AC power failure
l Zone trouble
l Fire trouble
l Telephone line trouble
l Communicator trouble
l Low battery condition
l RF jam
l AUX power supply fault
l Failure to communicate
l Module fault (supervisory or tamper)
-5-
Section 1: Introduction
l Bell trouble
l Corbus troubles
l Power unit trouble
Available models
The following alarm controller models are available:
l HS3032
l HS3128
l HS3248
Model comparison
The table below lists the features of each alarm system model.
Table 1-1 Model comparison
Features HS3032 HS3128 HS3248
On board
Zones 8 8 8
PGMs 4 4 4
2-way audio interface 1 1 1
Cellular plug-in interface 1 1 1
On-board ethernet connection 1 1 1
PC-link interface 1 1 1
USB connectors 2 2 2
PC- Link 1 1 1
Expansion
Zones 32 128 248
Low current PGMs 32 128 128
High current PGMs 4 16 16
Relay output PGMs 4 32 32
Partitions 4 8 8
Keypads 8 16 16
Users 72 1000 1000
Standard event buffer 500 1000 1000
Priority event buffer 2000 2000 2000
Alarm buffer 100 100 100
Arming buffer 100 100 100
Wireless device expansion
Wireless zones 32 128 128
Panic pendant zones 32 32 32
Wireless keys 32 32 32
Sirens 8 16 16
Repeaters * 8 8 8
Module expansion
PowerG Transceiver - HSM2HOST 1 1 1
8 Zone Expander - HSM2108 ** 3 15 30
-6-
Section 1: Introduction
-7-
Section 1: Introduction
Compatible devices
The following wireless devices and modules are compatible with this alarm controller.
Note: In the table below and throughout this document, x in the model number represents the operating frequency of the
device as follows: 9 (912-919 MHz), 8 (868MHz), 4 (433MHz).
Note: Only models operating in the band 912-919 MHz are UL/ULC listed where indicated. Only UL approved devices are to
be used with UL/ULC listed systems.
-8-
Section 1: Introduction
Hardwired devices
2-wire smoke detector FSA-210xUL
FSA-210xT UL
x = A, B, or C FSA-210xSUL
A = ULC listed models FSA-210xST UL
B = UL listed models FSA-210xLST UL
C = European and Australian models FSA-210xRUL
FSA-210xRT UL
L = Remote LED output FSA-210xRSUL
R = Auxiliary form C relay FSA-210xRST UL
S = Sounder FSA-210xLRST UL
T = Temperature sensor
4-wire smoke detector FSA-410xUL
FSA-410xT UL
x = A, B, or C FSA-410xSUL
A = ULC listed models FSA-410xST UL
B = UL listed models FSA-410xLST UL
C = European and Australian models FSA-410xRUL
FSA-410xRT UL
L = Remote LED output FSA-410xRSUL
R = Auxiliary form C relay FSA-410xRST UL
S = Sounder FSA-410xLRST UL
T = Temperature sensor
CO detector CO-12/24UL
12-24SIRUL
FW-CO12UL
FW-CO1224UL
CO1224UL
PowerG wireless devices
PowerG wireless short range ceiling mount detector with temperature monitoring PGx862 UL
PowerG wireless long range ceiling mount detector with temperature monitoring PGx872 UL
PowerG wireless outdoor curtain PIR PGx902 UL
PowerG wireless PIR motion detector with optional animal resistance PGx904(P) UL
PowerG wireless PIR motion detector with temperature monitoring PGx914(P) UL
PowerG wireless curtain PIR motion detector PGx924 UL
PowerG wireless PIR motion detector with camera PGx934(P) UL
PowerG wireless outdoor PIR motion detector with camera and with anti-masking PGx944
PowerG wireless mirror optic PIR motion detector PGx974(P) UL
PowerG wireless dual technology (PIR and MW) with anti-masking PGx984(P) UL
PowerG wireless outdoor PIR motion detector with anti-masking PGx994 UL
PowerG wireless recessed door/window contact PGx307
PowerG wireless outdoor contact with axillary input, temperature monitoring, and anti-masking PGx312 UL
PowerG wireless door/window contact with auxiliary input PGx945 UL
PowerG wireless vanishing door/window contact PGx975 UL / PGx303 UL
-9-
Section 1: Introduction
- 10 -
Section 2: Installation
Section 2: Installation
2.1 Overview of installation process
The steps below are provided to assist with the installation of the alarm system. Read over this section to get an overall
understanding of the order of installation. Working from this plan can help reduce problems and reduce the overall time
required for installation.
Step 1 – create a layout
Draw a rough sketch of the site and include all alarm detection devices, zone expanders, keypads and other required mod-
ules.
Step 2 – mount the panel
Decide on a location for the alarm panel and secure it to the wall using suitable mounting hardware. see "Mounting the
enclosure" on page 12
Step 3 – wire the alarm controller
Wire each of the modules to the alarm controller following the guidelines provided in "Corbus wiring" on page 280
Step 4 – wire zones
Complete all zone wiring. Follow the guidelines provided in "Zone wiring" on page 35 to connect zones using normally
closed loops, single EOL resistor, double EOL resistors, triple EOL resistors, fire zones, and keyswitch arming zones.
Step 5 – complete wiring
Complete all other wiring including bells or sirens, telephone line connections, ground connections, Ethernet connection or
any other wiring necessary. Follow the guidelines provided in "Terminal descriptions" on page 27
Step 6 – power up the control panel
Once all zone and alarm controller wiring is complete, connect the battery before applying AC, and power up the system.
The alarm controller will not power up if only the battery is connected.
Step 7 – enroll keypads and modules
All keypads must be enrolled in order to operate on the system. To enroll the first keypad, see "Enrolling the first keypad " on
page 46. To enroll optional keypads, enter installer's programming section [902][000]. For more information, see "Module
Programming" on page 149.
Step 8 – confirm module supervision
By default, all modules are supervised upon installation. Supervision is enabled at all times. To confirm that each module is
properly supervised, see "[903] Confirm Module" on page 150.
Step 9 – enroll wireless devices
Wireless devices are enrolled via the wireless transceiver module (HSM2HOSTx) or RF keypad and Installer programming
section [804]. See "Wireless Programming" on page 132 to enroll wireless devices.
Step 10 – program the system
Section 5 "Programming" on page 72 provides a complete description of how to program the alarm controller. It contains
complete descriptions of the various programmable features and options. Fill out the programming worksheets starting at
"Programming Worksheets" on page 154 completely before attempting to program the system.
Step 11 – test the system
Test the panel completely to ensure that all features and functions operate as programmed.
- 11 -
Section 2: Installation
The following diagram indicates the mounting location of the alarm controller PCB, power supply module and tamper
bracket inside the enclosure.
Wall mounting HSC3010C/ HSC3010CR/ HSC3030CAR enclosures
The following diagram indicates the mounting location of the alarm controller PCB, power supply module and tamper
bracket inside HSC3010C/ HSC3010CR/ HSC3030CAR enclosures.
- 12 -
Section 2: Installation
2.57cm
[1.01in]
2.97cm 30.93cm
[1.17in] [12.28in]
16.69cm
[6.57in]
35.50cm
[13.98in]
31.27cm
[12.31in]
A Use metal standoff and screw in the position indicated. IMPORTANT! Ensure screw
and standoff are tightly secured to establish Earth ground connection for the PCB.
B Tamper mounting location
18.44cm
[7.26in]
0.97cm
[0.38in]
35.38cm
[13.93in]
- 13 -
Section 2: Installation
A Tamper screws
Note: The HSC3020CP is used only for EN50131 and NFA2P certified installations.
HSM3204CX/HSM3350 mounting location in HSC3010C
The following diagram indicates the mounting location of the HSM3204CX/HSM3350, power supply module and tamper
bracket inside HSC3010C/ HSC3010CR/ HSC3030CAR and HSC3020 enclosures.
Figure 2-5 HSM3304CX/HSM3350 mounted in HSC3010C, HSC3010CR, HSC3030CAR enclosures
- 14 -
Section 2: Installation
HSM3350
HSM3408
HSM3408
HSM3408
- 15 -
Section 2: Installation
- 16 -
Section 2: Installation
- 17 -
Section 2: Installation
POWER LIMITED
Cable ties (not supplied) recommended
Use metal standoff and screw in the position
indicated.
Tamper switch and
IMPORTANT! Ensure screw and standoff are tightly
mounting bracket
secured to establish Earth ground connection.
PC LINK MICRO-B
USB TYPE A
STAND OFF
PC BOARD
CABINET HS3032/HS3128/HS3248
Warning: Disconnect AC power and
telephone lines before servicing.
1. Insert standoff into cabinet
mounting hole in the desired
location. Snap in place.
2. Position circuit board mounting
holes over standoffs. Press firmly
on board to snap in place.
This diagram shows routing of power limited and non-power Primary: 120V AC, 60Hz, Class VI
limited wiring inside the enclosure. Battery leads and AC cord Secondary: 18V DC, 3.6A Grommet strip (Not supplied)
are non-power limited. All other wiring is Power limited. Power adaptor module: HS65WPSNA Part# 57000933
Note: Do not connect power adaptor
module to a receptacle controlled by a
switch
Note: Power adaptor module may be mounted
outside the cabinet. Use the following guide to
determine sutiable distance and guage:
DISTANCE GAUGE
2 meters/6.5ft 22AWG
3 meters/10ft 20AWG
4 meters/13ft 18AWG
- 18 -
Section 2: Installation
PC BOARD
STAND OFF
HSM3204CX
Warning: Disconnect AC power
before servicing.
CABINET
- 19 -
Section 2: Installation
STAND OFF
HSM3204CX
PC BOARD Warning: Disconnect AC power
before servicing.
CABINET
4Ah
7Ah
2 x 7Ah
17Ah
This diagram shows routing of power limited and non-power Primary: 120V AC, 60Hz, Class VI
limited wiring inside the enclosure. Battery leads and AC cord Secondary: 18V DC, 3.6A
are non-power limited. All other wiring is Power limited. Power adaptor module: HS65WPSNA Grommet strip (Not supplied)
Note: Do not connect power adaptor Part# 57000933
module to a receptacle controlled by a
switch
Note: Power adaptor module may be mounted
outside the cabinet. Use the following guide to
determine sutiable distance and guage:
DISTANCE GAUGE
2 meters/6.5ft 22AWG
3 meters/10ft 20AWG
4 meters/13ft 18AWG
- 20 -
Section 2: Installation
STAND OFF
PC BOARD
HSM3350
Warning: Disconnect AC power
CABINET before servicing.
- 21 -
Section 2: Installation
PC BOARD
HSM3350
Warning: Disconnect AC power CABINET
before servicing.
Power supply
mounting screws
4Ah
7Ah
2 x 7Ah
17Ah
This diagram shows routing of power limited and non-power Primary: 120V AC, 60Hz, Class VI
limited wiring inside the enclosure. Battery leads and AC cord Secondary: 18V DC, 3.6A Grommet strip (Not supplied)
are non-power limited. All other wiring is Power limited. Power adaptor module: HS65WPSNA Part# 57000933
Note: Do not connect power adaptor
module to a receptacle controlled by a
switch
Note: Power adaptor module may be mounted
outside the cabinet. Use the following guide to
determine sutiable distance and guage:
DISTANCE GAUGE
2 meters/6.5ft 22AWG
3 meters/10ft 20AWG
4 meters/13ft 18AWG
- 22 -
Section 2: Installation
PC BOARD
Tamper switch
and mounting
bracket
PC LINK
USB TYPE A
MICRO-B CABINET
Cable tie
required
Cable tie
1x17 Ah/12V or for NFA2P required
- 23 -
Section 2: Installation
HSC3020CP wiring
Figure 2-16 Panel wiring for HSC3020CP enclosure
The HSC3020CP enclosure ships with the alarm panel, HS65WPS module, power supply and tamper switch already
installed. The communicator, case tamper switch, battery, and AC must be wired during installation.
For HSC3020CP plastic enclosure installations, complete the following steps:
1. Route the AC line in through the opening on the bottom of the cabinet and secure using cable tie as shown in figure 2-
15.
2. Connect AC wires to the fuse block as shown.
Note: Position cable ties over cable insulation, not directly on the exposed AC wires.
- 24 -
Section 2: Installation
- 25 -
Section 2: Installation
- 26 -
Section 2: Installation
Terminal descriptions
The following terminals are available on the PowerSeries Pro alarm controller.
Table 2-1 Terminal descriptions
Terminal Description
BAT+, BAT- Battery terminals. Use to provide backup power during a power outage and additional current when system demands exceed the
power output of power adapter, short term such as when the system is in alarm.
Do not connect the battery until all other wiring is complete.
DC +, DC - The HS65WPS power adapter supplies 18 VDC power input to the alarm controller.
Note: For CE/EN certified applications, the name of the power , the name of the power adapter is HS65WPS. For UL/ULC listed
applications, the name of the power adapter is HS65WPSNA. For ULC Commercial Fire Listed applications and ULC Commercial
Burg Security Level 4 applications, the name of the power adapter is HS65WPSNAS.
Connect the battery before connecting the AC. Do not connect the battery or power adapter until all other wiring is complete.
AUX+, AUX- Auxiliary terminals. Use to power detectors, relays, LEDs, etc. (2 A max). Connect the positive side of device to one of the three
AUX+ terminals and the negative side to AUX- or COM.
BELL+, Bell/Siren power (700 mA continous, 2A max short term). Connect the positive side of any alarm warning device to BELL+, the
BELL- negative side to BELL-.
Note: For EN50131 and UL/ULC listed applications, use maximum 700 mA load on the BELL output.
RED, BLK, Corbus terminals. Use to provide power and communication between the alarm controller and connected modules. Each module
YEL, GRN has four Corbus terminals that must be connected to the Corbus.
PGM1 to Programmable output terminals. Use to activate devices such as LEDs, relays, buzzers, etc.
PGM4 (PGM1, PGM4: 100 mA; PGM2: 300 mA or can be configured for use as a 2-wire smoke detector interface, max loop current 100
mA;
PGM3: 300 mA (negative trigger) or 1 A (positive trigger)
Z1 to Z8 Zone input terminals. Ideally, each zone should have one detection device; however, multiple detection devices can be wired to the
COM same zone.
Corbus wiring
The RED and BLK Corbus terminals are used to provide power while YEL and GRN are used for data communications. The
4 Corbus terminals of the alarm controller must be connected to the 4 Corbus terminals or wires of each module.
The following conditions apply:
l Corbus should be run with 18 to 22 AWG quad, two pair twisted preferred.
l The modules can be home run to the panel, connected in series or can be T-tapped.
l Do not use shielded wire for Corbus wiring.
Note: Any module can be connected anywhere along the Corbus. Separate wire runs for keypads, zone expanders etc. are
not necessary.
- 27 -
Section 2: Installation
Note: No module can be more than 1000 ft / 305 m (in wire length) from the panel. Do not use shielded wire for
Corbus wiring.
Figure 2-19 Corbus wiring
Module (A) is wired correctly as it is within 1000 ft / 305 m of the panel, in wire distance. Module (B) is wired correctly as it is
within 1000 ft / 305 m of the panel, in wire distance. Module (C) is NOT wired correctly as it is farther than 1000 ft / 305 m
from the panel. For models that require more than 1000 ft / 305 m from the main panel, a HSM3204CX power supply/Corbus
extender can be used.
Current ratings
In order for the system to operate properly, the power output of the alarm controller and power supply modules cannot be
exceeded. Use the following data to ensure that the available current is not exceeded.
Table 2-2 System output ratings
Device Output Rating (12 V DC)
HS3032 AUX/ 2 A. Subtract the listed rating for each keypad, expansion module and accessory connected to AUX or Corbus. At least
HS3128 Corbus: 100 mA must be reserved for the Corbus.
HS3248 BELL: 700 mA continuous rating. 2 A. short term. Available only with standby battery connected. DO NOT exceed the 700 mA
load for UL/ULC or EN certified applications.
HSM3350 AUX1: 3 A. Subtract the listed rating for each keypad, expansion module and accessory connected to AUX.
AUX2:
HSM3408 AUX: 500 mA. Continuous rating. Subtract for each device connected. Subtract the total load on this terminal from the alarm
panel AUX/Corbus output.
HSM3204CX AUX/ 2 A. Continuous rating. Subtract for each device connected.
Corbus:
HSM2208 AUX: 250 mA. Continuous rating. Subtract for each device connected. Subtract the total load on this terminal from the alarm
panel AUX/Corbus output.
HSM2108 AUX: 100 mA. Subtract for each device connected. Subtract the total load on this terminal from the panel AUX/Corbus output.
- 28 -
Section 2: Installation
Corbus (2 A max.)***
For UL, ULC and Commercial Listed applications, the total standby and alarm current cannot exceed 2 A.
Note: For EN50131, UL, ULC and Commercial Listed applications, the total standby and alarm current cannot exceed the
values in Aux Loading and Battery Selection for the applicable type of installation.
Overcurrent trouble
If the total current of the panel internal components and all outputs exceeds a threshold of 2.1 A for a period longer than 5
minutes, an overcurrent trouble is generated. When the current goes below a 2.0 A threshold, the trouble restores. Do not
exceed 2.0 A combined between AUX and Corbus.
Note: Total current does not include bell current or battery charging.
Line loss
Voltage loss through wire resistance must be considered for all installations. To ensure proper operation, at least 12.5 VDC
must be applied to all modules on the system (when AC is connected and the battery is fully charged). If less than 12.5 VDC
is applied, system operation is adversely affected.
To correct the problem, try any or all of the following:
1. Connect a HSM2300/2204/3350/3204CX power supply between the alarm controller and the module to provide addi-
tional power to the Corbus.
2. Reduce the length of the Corbus run to the module.
3. Increase the gauge of wire.
- 29 -
Section 2: Installation
Capacitance limits
An increase in capacitance on the Corbus affects data transmission and causes the system to slow down. Capacitance
increases for every foot of wire added to the Corbus. The capacitance rating of the wire used will determine the maximum
length of the Corbus.
For example, 22-gauge, non-shielded, 4-conductor wire has a typical capacitance rating of 20 picofarads per foot (which is
20 nF/1000 ft). For every 1000 feet of wire added – regardless of where it is run – the capacitance of the Corbus increases
by 20 nF.
The following table indicates the total wire distance allowed for the capacitance rating of the wire used:
Table 2-3 Wire capacitance
Wire Capacitance per 1000 ft (300 m) Total Corbus Wire Length
15 nF 5300 ft/1616 m
20 nF 4000 ft/1220 m
25 nF 3200 ft/976 m
30 nF 2666 ft/810 m
35 nF 2280 ft/693 m
40 nF 2000 ft/608 m
Zone expanders
The main alarm controller has connection terminals for zones 1 to 8. Additional HSM2108 and HSM3408 zone expanders
may be added to increase the number of zones on the system. Each zone expander consists of one group of 8 zones. At
enrollment, the zone expander is automatically assigned to the next available 8-zone expander slot/Corbus expander slot.
Connect the RED, BLK, YEL and GRN terminals to the Corbus terminals on the alarm panel. Board current draw: 30 mA.
Figure 2-20 HSM2108 zone expander
- 30 -
Section 2: Installation
Refer to the HSM2108 and HSM3408 installation sheets for more information.
Output expander
The HSM2208 module is used to add up to 8 low-current programmable outputs to the alarm system.
The 4-wire Corbus connection is used by the panel to communicate with the module. Connect the RED, BLK, YEL and GRN
terminals to the Corbus terminals on the alarm panel. Board current draw: 40 mA.
Figure 2-23 HSM2208 output expander
- 31 -
Section 2: Installation
After you have completed the wiring, reconnect power to the security system. Board current draw: 35 mA
UL/ULC residential
fire applications Residential
Burglary
CON1
BAT+ BAT-
RED*
BLK*
GRN
YEL
- 32 -
Section 2: Installation
HSM3350
The HSM3350 is a supervised 3 A, 12 VDC power supply module with dual AUX outputs and dual battery backups.
The 4-wire Corbus connection provides communication between the module and alarm panel. Connect the RED, BLK, YEL
and GRN terminals to the Corbus terminals on the alarm controller.
Figure 2-26 HSM3350 power supply wiring
NOTE: Fire and Security
WARNING! devices that require power
High Voltage from the HSM3350 shall be
UA720
Rev03 UL/ULC Listed for the
Disconnect AC power
intended application and
lines prior to servicing operate over the range 10.8
All circuits are classified for UL installations as power limited/Class II power limited, Status VDC - 12.5VDC.
except for the battery leads which are not power limited. Do not route any wiring LED
over circuit boards. Maintain at least 1” (25.4 mm) separation. A minimum of 1/4”
(6.4 mm) separation must be maintained at all points between power limited wiring
and all other non-power limited wiring. Inspect wiring and ensure connections are
correct before applying power.
+ AUX1 - + AUX2 -
- 33 -
Section 2: Installation
Corbus repeater
The HSM3204CX is a Corbus repeater and isolator module with four high current relay outputs. The module has an on-
board power supply to power Corbus.
Figure 2-27 HSM3204CX Corbus repeater
+BAT-
DC CORBUS IN CORBUS OUT TAM AUX RLY1 RLY2 RLY3 RLY4
_ _
+_ RED BLK YEL GRN RED BLK YEL GRN + + NO COM NC NO COM NC NO COM NC NO COM NC
Keypad Wiring
To wire a keypad to the alarm controller, remove the keypad backplate (refer to the keypad installation sheet) and connect
the RED, BLK, YEL and GRN terminals to the corresponding terminals on the alarm controller.
Keypad zone/PGM wiring
Hardwired devices can be connected to hardwired keypads with inputs (zone) or outputs (PGM). This saves from running
wires back to the control panel for every device.
To connect a zone device to HS2LCDPRO and HS2TCHPRO(BLK) keypads, run one wire to the P/Z terminal and the other
to B. For powered devices, use red and black to supply power to the device. Run the red wire to the R (positive) terminal and
the black wire to the B (negative) terminal.
Keypad zones support Normally Closed Loops, Single End of Line, Double End of Line, and Triple End of Line resistors.
To connect the PGM output, run one wire to the P/Z terminal and the other to R.
- 34 -
Section 2: Installation
Note: When using end of line supervision, connect the zone according to one of the configurations outlined in "Zone wiring"
on page 35. End of line resistors must be placed on the device end of the loop, not at the keypad.
Assigning keypad zones
When using keypad zone inputs, each input used must be assigned a zone number in Installer Programming.
First, ensure that you have enrolled all installed keypads into the desired slots (See "[902] Add/Remove Modules" on page
149). Next, assign keypad zones by entering programming section [861]-[876], subsection 011 for keypads 1-16. Enter a 3-
digit zone number for each of the keypad zones. This number must be programmed into the slot location that the keypad is
assigned to.
Note: A keypad zone overrides the corresponding hardwired or wireless zone.
Once the keypad zones are assigned, you must also program zone definitions and zone attributes. See "[001] Zone types"
on page 78 and See "Zone setup" on page 78.
HSM2955 wiring
For wiring information refer to HSM2955 Installation manual #29010198xxx.
Zone wiring
Power down the alarm controller and complete all zone wiring.
Zones can be wired to supervise normally open devices (e.g., smoke detectors) or normally closed devices (e.g., door con-
tacts). The alarm panel can also be programmed for single end-of-line, double end-of-line, and triple-end of line resistors.
Zone programming is done using the following programming sections:
l [001] selects zone definition
l [013] Opt [1] for normally closed or EOL; Opt [2] for SEOL or DEOL
l [201 - 208] partition assignment.
Alternately, zones may be individually configured as NC, SEOL, DEOL or TEOL through section [002] Zone Attributes,
toggles 9,10, 11 and 15, which will override the option in [013].
Observe the following guidelines when wiring zones:
l For UL listed installations use SEOL or DEOL only
l Minimum 22 AWG wire, maximum 18 AWG
l Do not use shielded wire
l Do not exceed 100 Ω wire resistance. Refer to the following table:
Table 2-4 Burglary zone wiring chart
Wire gauge Maximum length to EOL resistor (ft/meters)
22 3000 / 914
20 4900 / 1493
19 6200 / 1889
18 7800 / 2377
Figures are based on maximum wiring resistance of 100Ω.
- 35 -
Section 2: Installation
Normally closed
Connect hardwired devices to any Z terminal and any COM terminal. Wire normally closed devices in series.
Note: For UL Installations, do not use normally closed loops.
Figure 2-29 Normally closed
The following table shows zone status under certain conditions for NC Loops:
Table 2-5 NC loop status
Loop resistance Loop status
0Ω (shorted wire, loop shorted) Secure
Infinite (broken wire, loop open) Violated
The following table shows zone status under certain conditions for SEOL:
- 36 -
Section 2: Installation
Note: If the DEOL supervision option is enabled, all hardwired zones must be wired for DEOL resistors, except for Fire and
24 Hour Supervisory zones. Do not use DEOL resistors for Fire zones or 24 Hour Supervisory zones.
Note: Do not wire Fire zones to keypad zone terminals if the DEOL supervision option is selected.
Note: This option can only be selected if N/C detection devices or contacts are used. Only one N/C contact can be con-
nected to each zone.
The following table shows zone status under certain conditions for DEOL:
Table 2-7 DEOL loop status
Loop resistance Loop status
0 Ω (shorted wire, loop shorted) Fault
5600 Ω (contact closed) Secure
Infinite (broken wire, loop open) Tamper
11200 Ω (contact open) Violated
- 37 -
Section 2: Installation
The following table shows zone status under certain conditions for TEOL:
Table 2-8 TEOL loop status
Loop resistance Loop status
0 Ω (short) Fault
Infinite Ω (open) Tamper
5600 Ω Restored
11200 Ω Alarm
21200 Ω (alarm and fault/mask) Mask
15600 Ω (fault/mask) Fault
PGM wiring
Min/max operating voltages for devices, sensors and modules is
9.8 V DC - 14 V DC.
PGMs switch to ground when activated from the alarm controller. Connect the positive side of the device to the AUX+ ter-
minal and the negative side to a PGM terminal.
PGM 1, and 4 supply up to 100 mA; PGM 2 and 3 supply up to 300 mA.
A relay is required for current levels that exceed the maximum limits.
PGM2 can also be used for two-wire smoke detectors or 24-hour burglary input alarm.
Note: Use only SEOL resistors on Fire zones.
- 38 -
Section 2: Installation
Figure 2-33 LED output with current limiting resistor and optional relay driver output.
Bell wiring
These terminals supply 700 mA of current at 10.8 - 12.5 VDC for commercial/ residential installations. To comply with NFPA
72 Temporal Three Pattern requirements, section [013] Opt [8] must be ON. Note that steady, pulsed alarms are also sup-
ported. Temporal 4 cadence for CO alarm notification is also supported.
Figure 2-34 Bell wiring
The Bell output is supervised and power limited by 2 A hardware protection. If unused, connect a 1000 Ω resistor across
Bell+ and Bell- to prevent the panel from displaying a trouble. See "Troubleshooting" on page 59.
Note: Ensure that all plugs and jacks meet the dimension, tolerance and metallic plating requirements of 47 C.F.R. Part 68,
Sub-Part F. For proper operation, no other telephone equipment must be connected between the control panel and the tele-
phone company facilities.
- 39 -
Section 2: Installation
Note: Additional 2-wire smoke detectors must be connected in parallel as shown above. The maximum number of smoke
detectors on a 2-wire loop is 18.
Note: Do not combine smoke detector models from different manufacturers on the same circuit. Operation may be impaired.
Refer to the smoke detector installation sheet when positioning detectors.
- 40 -
Section 2: Installation
CO detector
The following hardwired CO detector models can be used with PowerSeries Pro alarm controllers:
l Potter Model CO-12/24, UL File E321434
l Quantum Model 12-24SIR, UL File E186246
l NAPCO Model FW-CO12 or FW-CO1224, UL File E306780
l System Sensor Model CO1224, UL File E307195
Note: For multiple unit connections, the leads between CO detectors must be broken. The power supervision relay must be
powered from the last detector in the loop.
Wireless CO detectors are also available. When installing wireless CO detectors, use only model PG9913UL, PG8913,
PG4913, or PGx933. An HSM2HOSTx (x=9UL/8/4) wireless receiver or HS2LCDRFPRO wireless keypad are required when
installing wireless CO detectors. For more details on these wireless devices, refer to their respective installation manuals.
Note: Use only UL approved devices with UL/ULC listed systems.
- 41 -
Section 2: Installation
HS3032/HS3128/HS3248
AUX
+-
SEOL
ANY ANY
RESISTOR
COM Z
ZONE (5600Ω)
INPUT -
+
ALARM
(SEOL ZONE TYPE 41)
INITIATING
LOOP
RM-1/RM-2 RESISTANCE
POWER LOOP 100Ω
SUPERVISORY
RELAY
(12VDC, 35mA)
Item Description
1
1 Nut
2
2 Earth ground connection from building electrical installation.
3
Note: This ground connection goes to HS65WPSNA power
adapter EGND connections when this power adapter is mounted
4
in the cabinet.
5 3 Cabinet
4 Star washer
6 5 Bolt
6 Earth ground symbol
- 42 -
Section 2: Installation
Connecting power
Batteries
Do not connect the battery until all other wiring is complete.
Note: A sealed, rechargeable, lead acid battery or gel type battery is required to meet UL requirements for power standby
times.
Connect the RED battery lead to the positive battery terminal and the BLACK battery lead to the negative battery terminal.
The panel can be programmed to charge the battery at 400 mA or 700 mA. (See "[982] Battery Settings" on page 152).
Note: Refer to "Aux loading and battery selection" on page 270.
Battery selection chart
After calculating the battery capacity (B) for each specific installation use the following table to determine the battery
required to support the main panel in standby mode for:
l 4 hours (UL/ULC residential burglary, ULC commercial burglary)
l 12 hours (EN50131 Grade 2/Class II)
l 24 hours (UL/ULC residential fire, UL home health care, ULC commercial burglary, ULC residential fire with wired
CO detectors UL985 6th Ed, ULC, fire commercial monitoring- no bell load allowed; INCERT [Belgium])
l 30 Hours (AC fail transmission required) or 60 hours (EN50131 Grade 3)
l 36 Hours (NFA2P 2 shield) or 60 hours (NFA2P 3 shield)
The battery size is measured in amp hours (Ah). The current values in the table denote the maximum current draw permitted
to achieve the desired standby time with the listed battery types.
Table 2-13 Standby battery guide
Battery size Desired standby time
4h 12 h 24 h 30 h 36 h 60 h
4 Ah 700 mA ------ ------ ------ ------ ------
Connecting AC power
The alarm controller requires an 18 VDC switched mode power supply. For information on connecting AC power, refer to Wir-
ing diagrams
- 43 -
Section 3: Configuration
Section 3: Configuration
3.1 Basic configuration steps
Once basic installation of the alarm panel is complete, the following general configuration options should be set:
l create partitions, See "Working with partitions " on page 47.
l assign keypads to partitions, see "Keypad partition setup " on page 48
l assign sirens to partitions, see "Bell/siren operation " on page 47
l set up partition account codes, see "Communications" on page 49
l set up partition timers, see "System times" on page 84
l enroll wireless modules and devices, see "Enrolling modules" on page 46
l assign zone types, see "[001] Zone types" on page 78, and attributes, see "[002] Zone attributes" on page 82
l create zone labels, see "Adding labels" on page 75
l add users, see "Assign access codes" on page 64
l set up the alternate communicator if equipped, see "Alternate communicator setup" on page 50
l program phone numbers, see "System Communications" on page 122
l set up call directions for the central monitoring station, see "System Communications" on page 122
l set up system timers, see "System times" on page 84
l configure reporting codes, see "Reporting" on page 116
l test the system, see "Testing the system" on page 51
Special keys
Scroll symbols < > on keypads with LCD displays indicate that options can be viewed by pressing the scroll keys. These
keys can also be used to position the cursor.
The [*] key is similar in function to the “Enter” key on a personal computer. It is generally used to accept the existing pro-
gramming option. It is also the first key entry for [*] commands and can be used to enter the letters A-F when in Installer Pro-
gramming mode.
The [#] key is similar in function to the “ESC” (escape) key on a personal computer. It is generally used to exit the current pro-
gramming section or to return to the previous one.
LED indicators
Keypads have the following status lights that provide visual indication of basic system status:
Ready: Panel is ready to be armed.
- 44 -
Section 3: Configuration
l Trouble indication – Flashes when troubles are present. During normal operation the Status LED shall indicate
troubles using the following flashing pattern. No Trouble will be indicated by 120ms on / 10 sec off. Troubles will be
indicated by a number of flashes 400ms on / 400ms off (1.7 sec between flashes). Troubles with a lower number of
flashes shall be considered higher priority and will override the indication of lower priority troubles.
Troubles are indicated according to the following priority:
1 flash - no keypads enrolled
2 flashes - module supervision trouble
3 flashes - bus low voltage
4 flashes - low battery trouble
5 flashes - AC trouble
6 flashes - AUX trouble
7 flashes - bell trouble
8 flashes - TLM trouble
How to enter data
Conventions used in this manual
Brackets [ ] indicate numbers or symbols that must be entered on the keypad.
e.g., [*][8][Installer Code][804] requires the following key entries:
[*][8][5555][804]
[*] initiates a special command.
Note: [5555] is the default installer code. The default installer code should be changed during initial programming of the sys-
tem.
[804] indicates the particular programming section being accessed.
Entering letters manually (system labels)
1. In Installer Programming, enter the section requiring text input.
2. Use the arrow keys [<][>] to move the cursor to a blank space or existing character.
3. Press the number key corresponding to the appropriate letter. Each number button accesses three letters and a number.
The first press of the number key displays the first letter. The second press displays the second letter, etc.
1 2 3
A, B, C, 1 D, E, F, 2 G, H, I, 3
4 5 6
J, K, L, 4 M, N, O, 5 P, Q, R, 6
7 8 9
S, T, U, 7 V, W, X, 8 Y, Z, 9,0
0
Space
4. To select lower case letters press [*]. The Select Options list opens. Scroll to “lower case” and press [*] again to select.
5. When the required letter or number is displayed use the arrow keys [<][>] to scroll to the next letter.
6. When finished, press the [#] key to save the label and exit.
7. Continue from step 2 until all labels are programmed.
For information on entering hexadecimal data, see "Programming hex and decimal data" on page 74.
3.3 Enrollment
All optional modules and devices must be enrolled on the system. During enrollment, the electronic serial number (ESN) of
each device is identified to the control panel and zones are assigned. A wireless transceiver HSM2HOST or an RF keypad
must be enrolled first before wireless devices can be enrolled.
- 45 -
Section 3: Configuration
Enrolling modules
During automatic and manual enrollment, if an attempt is made to enroll more than the maximum number of modules, an
error tone sounds and a message is displayed on LCD keypads.
Modules can be enrolled automatically or manually using section [902] of Installer programming. For instructions on
enrolling modules, see "Module Programming" on page 149
To confirm that a module has been successfully enrolled, use Installer programming section [903]. See "[903] Confirm Mod-
ule" on page 150.
Enrolling the first keypad
To enroll a hardwired keypad, connect the keypad to the alarm controller, power up the alarm panel then press any button
on the keypad.
To enroll a wireless keypad, first connect the HSM2HOSTx wireless integration module to the alarm controller. Next, power
up the alarm panel and a wireless keypad. Press any button on the keypad to enroll it on the HSM2HOSTx. The
HSM2HOSTx is then enrolled on the alarm panel. To enroll other keypads, see "Module Programming" on page 149.
Module supervision
By default, all modules are supervised upon installation. Supervision is enabled at all times so that the panel can indicate a
trouble if a module is removed from the system.
To check which modules are currently connected and supervised, see "[903] Confirm Module" on page 150.
If a module is connected but is not recognized by the system, it may be due to any of the following reasons:
l the module is incorrectly wired to the alarm controller
l the module has exceeded its maximum wire run length
l the module does not have enough power
Removing modules
Enrolled modules can be deleted from the system via programming section [902]. For instructions, see "[902] Add/Remove
Modules" on page 149.
- 46 -
Section 3: Configuration
Setting up a partition
Partitions are added or removed from the system by applying or removing a partition mask via Installer programming section
[200]. The number of available partitions depends on the alarm panel model. See "[200] Partition Mask" on page 114 for
more information.
Bell/siren operation
Each partition must have a siren. The system siren connected to the bell output of the alarm controller can be mounted in a
central location within hearing range of all partitions. Each partition can also have wireless sirens activated only on the
assigned partition. See "Wireless Programming" on page 132 for details.
Single siren output operation
With a siren shared across all partitions, control over activation/deactivation of the output depends on the partition that ini-
tiated the alarm sequence. Only the partition that originated the alarm can deactivate the bell output.
Global zones, such as smoke detectors shared by multiple partitions, can deactivate the siren on all partitions the zone is
assigned to.
Multiple siren output operation
When multiple sirens are used in the installation, they can be programmed to sound alarm conditions for all partitions, or for
individual partitions by using a partition enable mask.
If hardwired sirens are used, this is accomplished via bus power supplies with a supervised high-current output. The output
is then programmed as a Fire and Burglary PGM output type.
Note: Only the first output of the HSM2204 output module has bell supervision. Some conditions, such as an installer system
test, may override the partition assignment and cause all sirens to activate. User system tests only activate the sirens/outputs
assigned to that partition.
- 47 -
Section 3: Configuration
Global zones
If a zone is added to more than one partition, it becomes a global zone. A global zone is only armed when all assigned par-
titions are armed and is disarmed when any assigned partition is disarmed.
Global zones behave as follows:
l A global Stay/Away type zone is not activated until all partitions the zone is assigned to are armed in the Away mode.
Interiors must be activated on all partitions for the global Stay/Away zone to be active.
l A shared zone bypassed on one partition is bypassed on all partitions the zone is assigned to.
l An entry delay started on a global zone sounds an entry delay on all keypads assigned to partitions the global zone
is assigned to.
l A global Delay type zone follows the longest programmed delay time of the partitions it is assigned to.
- 48 -
Section 3: Configuration
Bell/PGM support
PGMs must be assigned to one or more partitions. See section [007] for partition assignment.
Note: Bell PGM type requires supervision and follows arming squawks by partition.
Communications
Account codes are assigned to all system and partition events.
For SIA communications, a single account code (programmed in section [310][000]) is used for all events. The partition is
identified via Nri1-8. System events use Nri0.
When using CID communication, individual account codes must be programmed for each partition. See "[310] Account
Codes" on page 122.
Assign zones
Partition zone assignments are completed using sections [201] - [208] for partitions 1 - 8. Subsections [001 - 016] are then
used to enable or disable banks of 8 zones on the partition.
Assign users
Access [*][5] using the master code, select the desired user code and enter digit 4 to modify the partitions that can accept the
user code.
Factory defaults
Individual modules, as well as the alarm panel itself, can have their programming returned to factory default settings. Hard-
ware is defaulted via the following Installer Programming sections:
l [991] Default Keypads
l 000 – Default all keypad programming
l 001-016 – Default keypads 1-8
l [996] Default wireless receiver
l [998] Default HSM2955
l [999] Default system
See "Defaults" on page 152 for more information.
Default all labels
Use programming section [000][999]. The following labels are returned to factory default settings:
l Zone Label
l Partition Labels
l Module Labels
l Partition 1-8 Command Output 1 to 4 Labels
l Schedule 1 to 4 Labels
l Event Labels
l User Labels
System and module programming is not affected.
Hardware reset main control panel
Perform the following to restore the main control panel to default settings:
1. Power down the system.
2. Remove all wires between Zone 1 and PGM 1 on the alarm controller.
3. Connect a short between Zone 1 and PGM 1.
4. Power up the system for 60 seconds.
5. Power down the system and remove the short.
6. Power up the system again. Factory defaults are restored and hardware default is logged to the event buffer.
Note: Hardware default is not available when installers lockout is enabled.
- 49 -
Section 3: Configuration
Communication paths
The path of communication between the alarm panel and the central station must be established through either the alarm
panel’s on-board Public Switched Telephone Network (PSTN) connection (Ethernet) or through the alternate communicator
if equipped.
Communications options
The following alarm panel options must be programmed when configuring the alternate communicator:
[300] option 02: communication path (see "[300] Panel/Receiver Communication Paths " on page 115)
[380] option 01: communications enabled/disabled (see "[380] Communicator Option 1" on page 125)
[383] option 03: ethernet communications enabled/disabled, [383] option 04: cellular communications enabled/disabled
[308][351]-[356] reporting codes (see "[351] Alternate Communicator 1")
[401] option 7: DLS access (see "[401] System Test Events")
Supervision restore
If the alarm system experiences a failure to communicate (FTC) with the central monitoring station, it automatically attempts
to transmit the failed event when communications are restored when [383], option 5 is enabled.
- 50 -
Section 3: Configuration
- 51 -
Section 4: System operation
- 52 -
Section 4: System operation
In the following example, partition 1 is armed, partition 2 is disarmed and ready, partition 3 is disarmed and not ready, par-
tition 4 is in alarm, partition 5 is indicating exit delay, partition 6 is in entry delay, partition 7 is in auto-arm pre-alert and par-
tition 8 is not enabled.
1 2 3 4 5 6 7 8
A R N ! X E P -
Global keypads behave as follows:
l Troubles are displayed and sounded on the global keypad. Troubles can be viewed from the global keypad display
by pressing the right scroll key then (*). The Troubles menu is displayed. An access code may be required to enter
the [*][2] menu depending on system programming.
l Keypad function keys can be programmed for Global Stay Arm, Global Away Arm and Global Disarm.
l Multiple partition arming/disarming may be done from a global keypad, assigned to the same partitions as the user,
by scrolling right and selecting "[*] to Arm All Partitions.
4.3 Labels
Various custom labels can be created to make identification of the alarm system, partitions, zones and modules simpler.
Labels are created by inputting text manually, by selecting words from the Word Library or by downloading/uploading using
DLS. See "[000] Label Programming" on page 75
System label
This feature is used to program a custom label for the security system. This label is used in the event buffer when system
events occur. The maximum label size is 14 ASCII characters.
See "[100] System label" on page 77for programming details.
Zone labels
Customized labels can be created for each zone on the alarm system. These labels are used on various displays and events
to identify the zone. The maximum label size is 14 x 2 ASCII characters.
See "[001]-[248] Zone Labels" on page 75 for more details.
Partition labels
Each partition on the alarm system can have a unique label to identify it. This label is displayed on partition keypads and
event messages. The maximum label size is 14 x 2 ASCII characters.
See "[101]-[108] Partition 1-8 labels" on page 77 for more details.
Module labels
Labels can be created for the following optional system modules:
l keypads
l 8 zone expander modules
l 8 output expander modules
l wireless transceiver
l power supply
l 4 high-current output module
l alternate communicator module
l audio module
l siren
l repeater
The maximum label size is 14 ASCII characters.
See "[801] Keypad labels" on page 77 for more details.
Event labels
Customizable labels can be created for the following events:
- 53 -
Section 4: System operation
l Fire alarm
l Fail to arm
l Alarm when armed
l CO alarm
The maximum label size is 14 ASCII characters.
4.4 Annunciation
Door chime
The keypad can be programmed to use one of four different door chime tones for each zone on the system. Chime is active
only during the disarm state. Only one door chime option can be enabled for each zone.
l Beeps
l Bing-Bong
l Ding-Dong
l Alarm Tone
l Zone Name - Voice Annunciation (HS2LCDWFVPROx keypads only)
The above door chime sounds are programmable in section [861]-[876], subsections [101]-[228].
Chime is enabled/disabled on a partition using the [*][4] command.
Temperature display
Indoor and outdoor temperature can be displayed on system keypads if configured in keypad programming section [861]-
[876]>[023] option 7, and sections [041]-[042]. Temperature is detected using wireless temperature sensors installed on the
system. Refer to "Compatible devices" on page 8.
Global keypads only display outdoor temperature.
- 54 -
Section 4: System operation
- 55 -
Section 4: System operation
- 56 -
Section 4: System operation
- 57 -
Section 4: System operation
- 58 -
Section 4: System operation
“B” appears on the display to indicate the zone is bypassed. If a zone is open, “O” appears on the display. When an open
zone is bypassed, the “O” is replaced by “B.”
5. To clear a bypassed zone, repeat the above procedure. The “B” disappears from the display indicating that the zone is
no longer bypassed.
6. To exit bypass mode and return to the ready state, press [#].
Other bypass features:
The following features are also available on the [*][1] zone bypass menu:
Bypass Open Zones
Displays all currently open or bypassed zones. Use the scroll keys to view zones. Open zones are indicated by an (O). To
bypass a zone, press [*]. A bypassed zone is indicated by a (B).
Note: Zones with tampers or faults must be manually bypassed.
Note: This feature shall not be used for UL/ULC listed systems.
Bypass Group
Note: This feature shall not be used for UL/ULC listed systems.
Displays a programmed group of zones (bypass group) commonly bypassed. Press [*] to bypass all zones in the group.
Program Bypass Group
To program a bypass group, bypass all desired zones then select Bypass Options > Program Bypass Group. The selected
zones are saved to the bypass group. When finished, press [#] to exit.
In order to program a bypass group, a master or supervisor code with access to the appropriate partition must be used.
Bypass Recall
Press [*] while in this menu to bypass the same group of zones that were bypassed the last time the partition was armed.
Clear Bypasses
Press [*] to clear all bypasses.
Shortcuts from the [*][1] base menu:
991 = bypass group
995 = program group 1
998 = bypass open zones
999 = bypass recall
000 = clear group
When the alarm system is armed
When the system is armed, pressing [*][1] toggles between stay, away or night arming. If a night zone is on the system, press-
ing [*][1] either prompts the user for an access code if required, or sounds an acknowledgment tone and changes the arming
mode.
Note: If section [022], Option 5 [Stay/Away Toggle] is on, the system does not change from Away to Stay mode.
Troubleshooting
LCD programmable-message keypad:
l Press [*][2] followed by access code if required to view a trouble condition
l The trouble light flashes and the LCD displays the first trouble condition
l Use the arrow keys to scroll through all trouble conditions present on the system
Note: When additional information is available for a specific trouble condition, a [*] is displayed. Press the [*] key to view the
additional information.
- 59 -
Section 4: System operation
Troubles may be viewed while the system is armed or disarmed. The system may be programmed to show all troubles while
armed or only fire troubles. See section [13] option 3 for details.
The system can be configured to require a user code to view [*][2] system troubles. See section [023] option 5.
To view trouble conditions:
l Press [*][2] to enter the Trouble menu.
l On an LCD keypad, scroll to a trouble type then press [*] to view the specific trouble. The zone name and trouble con-
dition for each trouble are displayed on the screen.
Note: The trouble beeps generated by fire trouble are only silenced after [*][2]trouble menu is exited. A keypress in the
keypad will not silence the fire trouble beeps. For UL installations, set the value in section [023] bit 5 access code required
for [*][2] to enabled.
Table 4-4 : Trouble Indications
Trouble 01 – Service Required:
[01] Bell Circuit Trouble: The bell circuit is open
[02] RF Jam: The HSM2HOSTx has detected an RF Jam condition
[03] Loss of Clock: System time and date require programming.
[04] Output 1 Fault: An HSM2204 module has detected an open condition on output #1.
[05] Warm Start: Warm restart has occured.
[06] USB Wi-Fi Connected: USB Wi-Fi adapter is detected
[07] Power Unit Failure (System): Failure detected with internal power unit.
[08] Failure detected with internal power unit (HSM3204CX Corbus Repeater)
[09] Failure detected with internal power unit (HSM3350 3 A Power Supply)
[10] Overcurrent Trouble: If the total current of the panel internal components and all outputs exceeds a threshold of 2.1 A for a period longer
than 5 minutes, an overcurrent trouble is generated. When the current goes below a 2.0 A threshold, the trouble restores. Do not exceed 2A
combined between AUX and Corbus.
Note: Total current does not include bell current or battery charging.
Trouble 02 – Battery Trouble:
[01] Panel Low Battery Trouble: The battery voltage is low.
[02] Panel No Battery: No battery connected to alarm controller.
[04] HSM2204 01 - 04 Low Battery: An HSM2204 has a low battery voltage.
[05] HSM2204 01 - 04 No Battery: No battery connected to HSM2204.
[07] HSM2300 01 - 04 Low Battery: An HSM2300 has a low low battery voltage.
[08] HSM2300 01 - 04 No Battery: No battery connected to HSM2300.
[10] HSM3204CX Low Battery: A Corbus repeater has a low battery voltage.
[11] HSM3204CX No Battery: No battery connected to corbus repeater.
[13] HSM3350 Low Battery 1: A 3 A power supply module has a low battery voltage.
[14] HSM3350 Low Battery 2: A 3 A power supply module has a low battery voltage.
[15] HSM3350 No Battery 1: No battery connected to 3A power supply module.
[16] HSM3350 No Battery 2: No battery connected to 3A power supply module.
- 60 -
Section 4: System operation
- 61 -
Section 4: System operation
- 62 -
Section 4: System operation
IMPORTANT!
Ensure you have the following information available before contacting Customer Support :
l Alarm controller type and version, (e.g., HS3032, 1.0):
Note: Version number can be accessed by entering [*][Installer Code][900] on any keypad. This information is also located
on a sticker on the printed circuit board.
l List of modules connected to control panel, (e.g., HSM2108, HSM2HOSTx etc.).
- 63 -
Section 4: System operation
l Alarm tone
l Zone Name -Voice Annunciation (HS2LCDWFVPROx keypads only)
The above door chime sounds are programmable in section [861]-[876], subsections [101]-[228].
+ If section [020] option 7 is on, a user must enter [*][6][Master Code][05] to give the installer permission to access pro-
gramming.
* Can only change master code if section [015] option 6 is off.
** Yes if [023] option 8 is on.
The Installer and Master codes are system codes. They can be changed but not deleted. The other codes are user-defined
and can be added or deleted as necessary. By default, access codes have the same partition and attribute programming as
the code used to program them.
Access codes are either 4, 6 or 8 digits in length, depending on the setting of programming section [041]. Duplicate codes
are not valid.
Note: EN50131-1 compliant systems using more than 100 access codes shall set the access code to 8 digits (section [041],
option 02).
Installer Code
This code provides access to Installer Programming [*][8]. The installer code is only used to gain access to configure the sys-
tem though [*][8] Installer Programming and does not have access to any other function. This code can be programed by the
installer in section [006][001]. The default is 5555 (4-digit), 555555 (6-digit) or 55555555 (8-digit).
EN Note: For EN50131-1 approved installations the installer code cannot change the master code or any other level 3 codes.
Attempting to access the master code from the installers code generates an error tone from the system.
Master Code - Access Code [0001]
By default the master code can access all partitions and can perform any keypad function. This code can be used to program
all access codes, including the supervisor and duress codes.
If section [015] option 6 is on, the master code can only be changed by the installer via Installer Programming.
The default is 1234 (4-digit), 123456 (6-digit) or 12345678 (8-digit).
- 64 -
Section 4: System operation
EN The master code can be returned to factory default settings using Installer Programming section [989].
Maintenance Code
The maintenance code can only be used to arm and disarm the system. It cannot bypass zones. Use [*][9] to arm the system,
cancel auto-arming, or perform [*][7] command functions. No arm/disarm bell squawks are sounded when the maintenance
code is used. The Maintenance code can be programed by the installer in programming section [006][003]. The default is
AAAA (4-digit), AAAAAA (6-digit) or AAAAAAAA (8-digit).
User Codes - Access Codes [0002] to [1000]
This type of access code is used to arm and disarm assigned partitions and perform other functions as programmed. It can
access the [*][6] menu if programming option [023] option 8 is on. This code cannot access the [*][5] and [*][8] menus.
User access codes are created by the master user or supervisor users. The default is AAAA (4-digit), AAAAAA (6-digit) or
AAAAAAAA (8-digit).
Supervisor Codes - Access Codes [0002] to [1000]
A supervisor code is a user code with the Supervisor attribute enabled. Users with this attribute can access the [*][5] and [*]
[6] user code programming section for the partition they are assigned to. However, these codes can only program codes
which have equal or lesser attributes. These attributes are changeable via the [*][5] menu. A supervisor code is created by
the master user or other supervisor users.
Duress Codes - Access Codes [0002] to [1000]
Duress codes function the same as user access codes, except they transmit a duress reporting code when used to perform
any function on the system.
Duress codes cannot be used to access [*][5], [*][6] or [*][8] menus.
Duress codes are created by the master user or supervisor users.
Note: Section [019] option 6 must be on to select the Duress Codes attribute.
One Time Use Code
A one time use code is a user code with the One Time User attribute enabled. This access code enables the user to arm the
alarm system an unlimited number of times. However, a user with this code can only disarm the system once per day. The
ability to disarm is reset at midnight or when the one time user code is keyed in by the master code user.
Note: One time use code cannot be applied to wireless keys.
One time use codes are created by the master user or supervisor users.
To add an access code using an LCD keypad:
1. Press [*][5][master/supervisor code] to edit access codes 0002-1000.
2. Use the scroll keys to select a user then press [*] to edit.
3. On the “Press (*) for Access Code” menu, press [*]. The current access code is displayed.
4. Key in the new access code. The code is saved when the last number is keyed in.
To erase an access code, select the user number and enter [*] as the first digit. All digits of the access code must be
entered.
A “-” beside a user code indicates it is not programmed. A “P” indicates the code is programmed. A “T” indicates the code is
programmed and a proximity tag is enrolled.
Access code attributes
Each user code has 6 attributes that can be toggled on or off.
The default attributes of an access code are the same as the code used to enter [*][5], whether a new code is programmed or
an existing one is edited. The available attributes are as follows:
l Supervisor
l Duress code
l Zone bypassing
l Remote access
l Bell squawk
l One time use code
- 65 -
Section 4: System operation
1 – Supervisor
Converts standard user into supervisor user. See "Access code types" on page 64 on page 58 for details.
2 – Duress Code
Converts standard user code into duress code. See "Access code types" on page 64 for details.
3 – Zone Bypassing
Users with this attribute can bypass zones. Section [023] option 4, Access code required for [*][1], must be on to use this
attribute.
7 – Bell Squawk
When this option is assigned, the main bell squawks when the alarm system is away armed. For example, use the arm/dis-
arm bell squawk attribute to have wireless key access codes squawk the bell, while other codes are silent. To do this, enable
this attribute on all access codes associated with wireless keys. This option is off by default for all access codes.
Note: One squawk indicates arming completed; two squawks indicates disarming completed.
Note: This feature is independent of the system option “Bell Squawk on Away Arming.” See "[017] System Option 5" on page
105
The master code's attributes cannot be changed from default. The bell squawk is off at default.
8 – One Time Use Code
Converts standard user code into one time use code. See "Access code types" on page 64 for details. Do not apply this code
to users with wireless keys assigned.
Using an LCD keypad:
1. Press [*][5][Master Code].
2. Use the scroll keys to choose a user (02-1000) then press [*] to select.
3. Scroll to “Press [*] for User Options” then press [*] to select.
4. Scroll to a user attribute and press [*] to toggle it on or off.
Add user labels
Custom labels can be programmed for each user to more easily identify them on the alarm system. Labels can be a max-
imum of 16 characters.
Using an LCD keypad:
1. Press [*][5] then select a user (02-1000).
2. On the “Press [*] for User Labels” screen, press [*].
3. Key in the custom user label. For instructions on how to input labels, See "[000] Label Programming" on page 75
Assigning proximity tags
This section is used to assign proximity tags to users.
Using an LCD keypad:
1. In the [*][5] menu, select a user or enter a user number.
2. Select “Press [*] for Prox Tag”, then pass the enrolled tag near the tag reader on the keypad. A proximity tag can only be
assigned to one user at a time.
To delete a proximity tag:
1. Select a user and then select Press [*] for Prox Tag.
2. Press the [*] key when prompted to delete the proximity tag.
To increase authentication flexibility, user access can be achieved by entering a valid user code or by swiping a proximity
tag. Alternatively, users can be required to enter a valid access code and present a proximity tag. See "[040] User Authentic-
ation" on page 112.
- 66 -
Section 4: System operation
- 67 -
Section 4: System operation
With this feature enabled, the alarm system automatically arms in away mode (stay/away zones active) or disarms at a pro-
grammed time each day (see Auto-Arm Time below). The keypad emits three beeps to indicate the auto arming is enabled
and one long beep to indicate auto arming is disabled.
All arming inhibit features such as latching tampers, AC inhibit, etc. also inhibit Auto Arming and send the Auto Arm Can-
cellation code.
Auto-Arm Time
Menu: [*][6][Master Code] > Auto Arm Time
Keypad: [*][6][Master Code] + 03
This function is used to program the time of day each alarm system partition automatically arms. To program an auto-arm
time, select a day of the week and then key in the time. Valid time entries are 00-23 hours: 00-59 minutes.
At the programmed time, the keypad buzzers beep for a programmed duration (for ULC commercial burglary installations
minimum duration is 10 minutes) to warn that automatic arming is in progress. The siren also squawks once every 10
seconds during this warning period if programmed to do so. When the warning period is complete, the system arms in away
mode.
Auto-arming can be canceled or postponed only by entering a valid access code during the programmed warning period.
When a code is entered, the warning is silenced and auto-arming is canceled or postponed, depending on the auto-arm
postpone timer. The Auto Arm Cancellation reporting code is transmitted (if programmed).
Note: Auto-arming will not silence an active bell.
Note: The Auto Arm Cancellation reporting code is also transmitted if arming is inhibited by one of the following:
l AC / DC Inhibit Arm
l Latching System Tampers
l Zone Expander Supervisory Fault
Other programming options that may affect this function:
See "[151]-[158] Partition Auto-Arm/Disarm" on page 113
See "[014] System Option 2" on page 102
Enable DLS/Allow System Service
Menu: [*][6][Master Code] > System Serv/DLS
Keypad: [*][6][Master Code] + 05
This function enables and disables the DLS window for either 30 minutes or 6 hours depending on the programming of sec-
tion [025] option [7].
This function also enables the end user to provide or deny access to [*][8] Installer Programming. When enabled, the
installer can access Installer Programming either by DLS or via [*8] if a pre-programmed window has been set. After the win-
dow has expired, Installer Programming is unavailable again until the window is re-opened.
Note: DLS programming is not UL tested.
Other programming options that may affect this function:
See "[020] System Option 8" on page 107 and see "[021] System Option 9" on page 109
See "[025] System Option 13" on page 112, bit "7 – DLS Window"
User Call-up
Menu: [*][6][Master Code] > User Call-up
Keypad: [*][6][Master Code] + 06
When selected, this function makes a single attempt to call the downloading computer. The downloading computer must be
waiting for the call before downloading can be performed. Only one call-up is attempted. If a DLS phone number is not pro-
grammed, the alarm panel attempts to reach the DLS computer via IP connection. If the communicator is not properly con-
figured for IP, an error tone is sounded.
User Walk Test
Menu: [*][6][access code] > Walk Test
Keypad: [*][6][access code] + 08
- 68 -
Section 4: System operation
Selecting this function places the alarm panel into user walk test mode. The Ready, Armed and Trouble LEDs on the keypad
flash to indicate that the test is active. If zones are tripped during a walk test, the system sounds a steady 2-second tone on
all keypads and the main bell to indicate that the zone is working correctly.
The walk test can be stopped at any time by re-entering [*][6][Master Code][08] on the keypad. The test automatically ter-
minates after 15 minutes of inactivity. An audible warning begins 5 minutes prior to automatic termination.
Note: Fire and CO alarms are not tested in user's walk test. If a fire or CO alarm is detected, walk test ends automatically and the
appropriate reporting codes are sent immediately to the monitoring station. Refer to the manufacturers instructions provided with
CO and Fire detectors for testing. This feature is not available in CP-01 systems.
Late to Open
Menu: [*][6][Master Code] > Late To Open
Keypad: [*][6][Master Code] + 09
This function enables or disables the Late to Open option. This option sends a reporting code to the central monitoring sta-
tion if the partition has not been disarmed by a programmed time.
Other programming options that may affect this function:
See "[201] Open/Close Events 1", option "[211] Miscellaneous Open/Close Events" on page 118.
Late to Open Time
Menu: [*][6][Master Code] > Late To Open Time
Keypad: [*][6][Master Code] + 10
This function is used to program the time of day the partition must be disarmed by when the Late to Open option is enabled.
A separate time can be programmed for each day of the week. Valid data entries are 00:00 - 23:59. 99:99 disables the late to
open feature for the selected day.
Select a day of the week by scrolling while in the Late to Open menu, or by using keys 1-7 to select Sunday to Saturday
respectively.
Brightness Control
Menu: [*][6][Master Code] > Brightness Control
Keypad: [*][6][Master Code] + 12
This function is used to change the brightness level of keypad display backlighting. Use the scroll keys to increase and
decrease brightness or enter a value from 00 to 15. Selecting 00 turns off keypad backlighting.
Contrast Control
Menu: [*][6][Master Code] > Contrast
Keypad: [*][6][Master Code] + 13
This function is used to change the contrast level of keypad displays. Use the scroll keys to increase and decrease contrast
or enter a value from 00 to 15. Selecting 00 turns off keypad contrast.
Buzzer Control
Menu: [*][6][Master Code] > Buzzer Control
Keypad: [*][6][Master Code] + 14
This function is used to change the volume level of keypad buzzers.
Use the scroll keys (LCD keypads) or the [*] key (LED/ICON keypads) to increase and decrease volume or key in a value
from 00 to 15. Selecting 00 turns off the keypad buzzer.
Note: For UL/ULC listed installations, do not turn off the keypad sounder.
Authorize Firmware Update
Menu: [*][6][Master Code] > Authorize Update
Keypad: [*][6][Master Code] + 17
This function is used to give authorization to the system to start the firmware upgrade process after all firmware upgrade files
for the keypads, HSM2HOST and control panel have been fully downloaded.
Once this option is activated, the keypads and system automatically exit [*][6] and indicate that the firmware update is in pro-
gress.
Interactive Services
Menu: [*][6][Master Code] > Interactive Serv
- 69 -
Section 4: System operation
- 70 -
Section 4: System operation
- 71 -
Section 5: Programming
Section 5: Programming
5.1 How to program
This section describes how to view alarm system programming options using the supported keypad types.
Template programming
Template programming allows the installer to quickly program the minimum functions required for basic operation. The
installer is prompted to enter a 5-digit code that selects predefined programming configurations:
Digit 1 – zone 1-8 definition options
Digit 2 – system EOL options
Digit 3 – alarm controller communications options
Digit 4 – alarm controller call directions
Digit 5 – DLS connection options
(See "Template programming tables" on page 258 for programming information).
Perform template programming after completing the hardware installation. Ensure you have the information listed below
available. Record this information in the programming worksheets for future reference:
l Monitoring station telephone number - provided by the alarm monitoring service.
l Monitoring station account code - provided by the alarm monitoring service.
l Downloading access code.
l Entry delay - installer defined.
l Exit delay - installer defined.
l Installer code - programmable, unique 4-digit code. The default value is [5555].
To perform template programming:
1. Enter [*][8][installer code][899]. If this section has been entered accidentally, press # to exit and the system programming
will not be changed.
2. At the “Enter Data” screen, enter a 5-digit value representing the desired programming options. Reference the template
programming tables to determine what values are required for the installation.
Once the 5-digit number has been entered, the installer cannot exit until all sections are completed. Enter new data
and/or press the [#] key to accept the displayed data and proceed to the next section. Changing a single digit, then
pressing the [#] key advances to the next section but does not save the changed data.
3. After entering a 5-digit template programming value, the first telephone number is displayed. Enter the monitoring station
telephone number after the “D.” Press [#] to complete the entry.
- 72 -
Section 5: Programming
4. After programming the first telephone number, enter a system account code.
l The system account code can be any 4 or 6-digit combination of numbers (0-9) and letters (A-F).
l To enter letters A through F, press [*] then the numbers 1 through 6 for the letter A through F respectively. Press [*]
again to revert back to decimal entry. E.g., to enter “1234FF” press [1234*66].
See "[310] Account Codes" on page 122 for additional details. When the system account code programming is com-
pleted, enter a partition 1 account code using the same method as the system account code.
5. After programming the partition 1 account code, the downloading access code is displayed. Enter the new downloading
access code or press [#] to proceed to the next step. The downloading access code must changed from its default value.
6. The next value is a 3 digit partition 1 entry delay time. Press [>][>][>] to accept the default time of 30 seconds (030) or
enter an entry delay between 001 and 255. E.g., Press 020 for a delay of 20 seconds. See "System times" on page 84 for
additional details. The CP-01 models of the panel will not accept a value less than 30 seconds.
7. The next value is a 3 digit partition 1 exit delay time. Press [>][>][>] to accept the default time of 120 seconds or enter an
exit delay between 001 and 255. E.g., press 030 for a delay of 30 seconds. See "System times" on page 84 for additional
details. The CP-01 models of the panel will not accept a value less than 45 seconds.
8. After programming the exit delay, enter a 4, 6 or 8-digit installer code, depending on the value in "[041] Access Code
Digits" on page 113. See "[006] Installer Defined Access Codes" on page 86 for installer code details.
9. Template Programming will automatically exit after the installer's code has been programmed.
Note: EN50131-1 compliant systems using 1000 access codes shall set the access code to 8 digits (section [041], option
02).
DLS programming
DLS programming involves downloading custom programming using DLS software and a computer. This can be done loc-
ally or by remote.
Note: For UL listed systems an installer must be on the premises.
Local programming with micro USB or Wi-Fi adapter
Follow the steps below in the sequence indicated to set up local programming using DLS:
1. Connect AC Wiring.
In a new installation, the backup battery requires 24 Hrs. charging. AC Power is required for USB Programming until
the battery is charged.
2. Plug the USB header into the alarm controller. A DLS session is initiated on the DLS computer.
3. When the session is complete, remove the USB cable from the alarm controller.
4. Complete the installation.
Remote programming
DLS programming can be performed remotely by connecting to the alarm system via telephone line, cellular network or Eth-
ernet.
Refer to "[401] DLS/SA Options" on page 129. for details.
Note: AC Power must be present for the alarm system to answer incoming calls from DLS.
Installer programming
Installer Programming is used to manually program alarm system options. Access this mode by keying in [*][8][Installer
Code]. Use the scroll keys to navigate through the menus or jump directly to a specific section by keying in a section number.
Programming consists of toggling on and off options in each section or by populating data fields. For descriptions of all pro-
gramming options, see "Programming descriptions" on page 75
Viewing programming
Programming sections can be viewed from any system keypad.
Generally, programming options are accessed in the following way:
1. Enter Installer Programming mode ([*][8]).
- 73 -
Section 5: Programming
The Ready light continues to flash after the HEX digit is entered. If another HEX digit is required press the corresponding
number. If a decimal digit is required, press the [*] key again. The Ready light illuminates and the panel returns to regular
decimal programming.
Example: To enter ‘C1’ for a closing by user 1, enter [*] [3] [*], [1]
[*] to enter hexadecimal mode (Ready light flashes)
[3] to enter C
[*] to return to decimal mode (Ready light is on)
[1] to enter digit 1
- 74 -
Section 5: Programming
If an error is made while inputting data, press the [#] key to exit the section. Select that section again and re-enter the inform-
ation correctly.
When using a Contact ID format, a decimal zero [0] does not transmit for account and reporting codes. Programming a zero
[0] tells the alarm system not to send any pulses for that digit. Decimal zero [0] is a filler digit. To make a zero [0] transmit, it
must be programmed as a Hexadecimal ‘A.’
Example: For the 4-digit account number ‘4032’, enter [4] [*] [1] [*] [3], [2].
[4] to enter the digit 4
[*] to enter Hexadecimal mode (Ready light flashes)
[1] to enter A
[*] to return to decimal mode (Ready light is solid)
[3] to enter the digit 3
[2] to enter the digit 2
Adding labels
[000] Label Programming
Zone and other labels on the alarm system can be customized.
Program labels locally or download/upload using DLS. Local label programming is done via a system keypad, as described
below.
[000] Language selection
To select a language:
1. Enter Installer Programming: [*][8][Installer Code].
2. Enter programming section [000]>[000].
3. Key in the 2-digit number corresponding to the language required. See the following table.
Table 5-3 Language codes
01 = English 11 = Swedish 22 = Bulgarian
02 = Spanish 12 = Norwegian 23 = Latvian
03 = Portuguese 13 = Danish 24 = Lithuanian
04 = French 14 = Hebrew 25 = Ukrainian
05 = Italian 15 = Greek 26 = Slovakian
06 = Dutch 16 = Turkish 27 = Serbian
07 = Polish 18 = Croatian 28 = Estonian
08 = Czech 19 = Hungarian 29 = Slovenian
09 = Finnish 20 = Romanian
10 = German 21 = Russian
- 75 -
Section 5: Programming
3. Scroll to the zone label to be programmed or key in the zone number. (e.g., 001 for zone label 1).
4. Scroll to the desired character’s location using the[<] [>] keys.
5. Enter the number of the corresponding character group until the desired character is displayed (see the following table).
Example: Press the “2” key 3 times to enter the letter “F.”
Press the “2” key 4 times to enter the number “2.”
To delete a character, use the [<] [>] keys to move the cursor under the character, then press [0].
If any key other than [<] or [>] is pressed before [0], the cursor moves one space to the right and deletes that char-
acter.
6. Press [#] to save the changes and exit.
Press To Select/Display
[*] [SELECT]
[#] [ESCAPE]
[0] [SPACE]
[1] [A], [B], [C], [1]
[2] [D], [E], [F], [2]
[3] [G], [H], [I], [3]
[4] [J], [K], [L], [4]
[5] [M], [N], [O], [5]
[6] [P], [Q], [R], [6]
[7] [S], [T], [U], [7]
[8] [V], [W], [X], [8]
[9] [Y], [Z], [9], [0]
Word library
The Word Library is a database of words commonly used when programming labels. Individual words can be combined as
needed (e.g., Front + Door). Words that do not fit on the first line are automatically moved to the bottom line.
To program a custom label using the Word Library:
1. Enter Installer Programming: [*][8][Installer Code].
2. Press [*], scroll to Zone Labels and press [*] again.The first zone is displayed. Alternately, press [000][001].
3. Scroll to the zone label to be programmed or key in the zone number (e.g., 001 for zone label 1).
4. Press [*] to open the Select Option menu.
5. Press [*] again to select the Word Entry option.
- 76 -
Section 5: Programming
6. Enter the 3-digit number corresponding to a word (see "Word library" on page 257) or use the scroll keys [<][>] to view
words in the library.
7. Press [*] to select the word.
8. To add another word, repeat the above procedure from step 4.
9. To add a space, press the right scroll key [>].
10. To clear characters, select Clear to End or Clear Display from the Select Options menu.
11. To save the current label, press [#] to exit label programming.
[064] CO alarm message
Use this section to program a custom label that is displayed on keypads during a carbon monoxide alarm. The maximum
label size is 14 x 2 characters.
[065] Fire alarm message
Use this section to program a custom label that is displayed on keypads during a fire alarm. The maximum label size is 14 x
2 characters.
[066] Fail to arm event message
This message is displayed on all partition keypads if a user attempts to arm the system when it is not ready to arm. The mes-
sage clears after five seconds. The maximum label size is 16 x 2 characters.
[067] Alarm when armed event message
This message is displayed if an alarm occurred while the system was armed. The message is displayed when the system is
disarmed and remains on the screen for 5 seconds. Following this, the zones that went into alarm are displayed. The max-
imum label size is 16 x 2 characters.
[100] System label
Use this section to program a custom label for the security system. This label is used in the event buffer when system events
occur. The maximum label size is 14 x 1 characters.
[101]-[108] Partition 1-8 labels
Use this section to program a name for each partition for display on partition keypads and event messages. The maximum
label size is 14 x 2 characters. See "Programming" on page 72 for specific instructions on how to program labels.
[201]-[208][001]-[004] Partition command output labels
Use this section to program custom labels for command outputs. These labels are used with output activation events in the
event buffer. Enter subsection [201] to [208] to select partition 1 to 8, then enter subsection [001] to [004] to select command
output 1 to 4 label.
The maximum label size is 14 x 2 characters. See "Programming" on page 72 for specific instructions on how to program
labels.
[601]-[604] Schedule labels
Use this section to program custom labels for command output schedules. These labels are used to identify schedules for
PGM command outputs 1-4. The maximum label size is 16 characters. See "Programming" on page 72 for specific instruc-
tions on how to program labels.
[801] Keypad labels
Use this section to create custom labels for keypads on the system. Select 001-016 for keypads 1-16.
[802][001]-[030] HSM2108 Zone expander labels
Use this section to create custom labels for Zone expanders on the system. Select 001-030 for zone expanders 1-15.
[803][001]-[016] HSM2208 Output expander label
Use this section to create a custom label for the output expander. Select 001 for HSM2208. Select 001-016 for output
expanders 1-16.
- 77 -
Section 5: Programming
Zone setup
The following section describes zone programming options. To program a zone type, first enter section [001] and then enter
a 3 digit zone number from 001 - 248. After entering a new zone type for the desired zone number, the keypad will auto-
matically advance to the next zone.
[001] Zone types
A zone type defines how a zone operates within the system and how it responds when triggered.
[001]-[248] Select Zone
Every zone on the system must be assigned a zone type. The available zone types are listed below.
000 – Null Zone
Assign to all unused zones.
001 – Delay 1
Commonly assigned to primary points of entry. Follows entry delay 1 and exit delay timers (section [005]). Arming the alarm
system starts the exit delay timer. After the exit delay has expired, opening the door starts the entry delay timer. During entry
delay, the keypad buzzer prompts the user to disarm the system.
002 – Delay 2
Commonly assigned to secondary points of entry (further from the keypad). Follows entry delay 2 timer (section [005]).
003 – Instant
Commonly used for perimeter doors and windows, this zone type follows the exit delay. The alarm is triggered instantly if the
zone is tripped after the exit delay expires.
- 78 -
Section 5: Programming
004 – Interior
Commonly assigned to interior motion sensors near a point of entry, such as a foyer or hallway, that must be accessed to
reach the keypad. The alarm is activated if the system is armed and a delay type zone (e.g., front door) is not tripped first, or if
the entry/exit timer expires before the alarm is disarmed. Otherwise, the zone is instant if tripped.
005 – Interior Stay/Away
Similar to Interior zone type except that the system bypasses the zone when armed in Stay mode. Commonly used to activ-
ate perimeter zones while permitting free movement throughout the interior.
006 – Delay Stay/Away
Similar to delay 1 except that the zone is bypassed when armed in Stay mode. Commonly used with motion detectors that
cover an entry point.
007 – Delayed 24-Hour Fire
This zone is used with smoke detectors and functions similar to the standard fire zone, except the communicator delays the
alarm memory and transmission by 30 seconds. If the alarm is acknowledged by pressing any key, the siren is silenced and
the transmission aborted. If the smoke detector is not restored after the alarm has been acknowledged, the siren output activ-
ates after 90 seconds and another 30-second delay starts. A code is required to silence the alarm. A tamper or fault causes a
fire trouble to log and transmit.
Note: The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5k6, the alarm state is short and the trouble state is open.
008 – Standard 24-Hour Fire
This zone is used with smoke detectors. The siren sounds instantly when the smoke detector is activated. If enabled, the com-
municator immediately transmits the alarm to the monitoring station. A tamper or fault of this zone type causes a fire trouble
to log and transmit.
Note: The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5.6k, the alarm state is short and the trouble state is open.
009 – Instant Stay/Away
Commonly assigned to interior motion sensors. This zone type is bypassed when armed in Stay mode, but functions like an
Instant zone [003] when armed in Away mode.
010 – Interior Delay
Commonly assigned to interior motion sensors. When Away armed, this zone type functions like the Interior zone type. When
Stay or night armed, tripping the zone activates entry delay 1. Tripping this zone during exit delay does not cause the system
to arm in Away mode, as tripping a regular Delay type zone does.
011 – Day Zone
Commonly used in areas where immediate notification of entry is desired. When disarmed, tripping this zone activates the
keypad buzzer but does not log or report the event. When armed, tripping this zone activates the siren then logs and reports
the event.
Note: An alarm during exit delay causes the siren to activate and remain on when exit delay expires.
012 – Night Zone
Commonly assigned to interior motion detectors in areas accessed during the night. This zone functions like an Interior
Stay/Away zone [005] when armed using any method except the following: If Stay armed, this zone is bypassed; if armed
using [*][1], this zone is bypassed.
016 – Final Door Set (Non CP-01 panels only)
UK This zone type does not use an exit timer (infinite exit delay). The door must be opened then closed to complete the arming
sequence. The arming method determines if infinite exit delay is applied. See the table below.
Note: Disable Exit Delay Termination with this zone type.
If this zone type is bypassed, the alarm system cannot be Away armed.
Arming method Infinite exit delay Arming mode
User code Y Away
Keyswitch Y Away
Away key Y Away
Wireless key away Y Away
- 79 -
Section 5: Programming
*0 arm Y Away
*9 arm N Stay
Stay key N Stay
Wireless key stay N Stay
Remote Access/SMS - Do not use
DLS arm N Away
No activity arming N Away
Note: When Troubles/Open Zones Cancel Arming is enabled with this zone, any troubles or open zones on the system can-
cel arming when the zone is tripped and restored.
Due to the potential energy requirements of infinite exit delay, wireless keypads MUST be powered by a transformer.
If a wireless key is used to away arm the system, the door must still be opened then closed to complete the arming
sequence. The indoor siren will activate until the exit delay has expired.
017 – 24-Hour Burglary
This zone type is active at all times. It reports an alarm if the alarm system is armed or disarmed. This zone type sounds the
siren for the length of Bell time-out if the audible attribute is enabled.
018 – 24-Hour Bell/Buzzer
When the alarm system is armed and this type of zone is tripped, the siren activates for the duration of the bell time-out. If the
alarm system is disarmed when this type of zone is tripped, the keypad buzzer activates until an access code is entered.
023 – 24-Hour Supervisory
This zone is active and reports alarms at all times when tripped. The siren and keypad buzzer do not activate.
Note: The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5.6k, the alarm state is short and the trouble state is open. For use with normally open contacts.
024 – 24-Hour Supervisory Buzzer
When tripped, the keypad buzzer emits a steady tone until a valid access code is entered.
025 – Auto Verify Fire
(Hardwired smoke detectors)
When the zone is activated, a 30-second delay begins but no fire alarm sounds. If the same zone is activated again up to 60
seconds after the delay expires, the alarm is triggered immediately. If the same zone is activated after 60 seconds, the entire
sequence begins again.
If a second fire zone is violated during the auto-verify sequence, both zones a fire alarm is immediately triggered.
(Wireless smoke detectors)
When the zone is activated, a 40-second delay begins. The alarm is triggered if the zone is still faulted after 30 seconds. If
the zone is no longer in alarm, an 80-second verification timer begins. If any fire zone is activated during this period, the
alarm is triggered.
If another fire zone is activated during the auto verify sequence, both zones go into alarm immediately.
Note: Wireless smoke detectors used with this zone type must have a built in siren to act as a pre-alert to the system alarm.
Note: The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5.6kΩ, the alarm state is short and the trouble state is open.
027 – Fire Supervisory
When this zone is tripped, the keypad buzzer activates and a supervisory alarm is sent to the monitoring station. A valid
access code must be entered to silence the buzzer.
Note: The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5.6k, the alarm state is short and the trouble state is open.
040 – 24-Hour Gas
Instant alarm when activated, audible alarm at default.This zone type may be assigned to any device type.
041 – 24-Hour CO
This zone type is used with CO detectors. In the event of an alarm, a distinctive siren cadence is sounded. This is followed by
a 5-second pause and then repeated. After 4 minutes, the 5-second pause is extended to 60 seconds; however, BTO must
be programmed with a value of 5 minutes or higher. The siren is silenced when an access code is entered or the siren times
out.
- 80 -
Section 5: Programming
Note: The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this
zone type is 5k6, the alarm state is short and the trouble state is open. For use with normally open contacts.
042 – 24-Hour Holdup
Instant alarm when activated, silent alarm at default.
Note: Not for use in UL listed installations.
043 – 24-Hour Panic
Instant alarm when activated, audible alarm at default.
045 – 24-Hour Heat
Instant alarm when activated, audible alarm at default.
046 – 24-Hour Medical
Instant alarm when activated, audible alarm at default.
047 – 24-Hour Emergency
Instant alarm when activated, audible alarm at default.
048 – 24-Hour Sprinkler
Instant alarm when activated, audible alarm at default.
049 – 24-Hour Flood
Instant alarm when activated, audible alarm at default.
051 – 24-Hour Latching Tamper
Instant alarm when activated, audible alarm at default. The alarm system cannot be armed until Installer Programming is
entered after the zone is restored.
052 – 24-Hour Non-Alarm
This zone is active at all times but does not cause an alarm. Zone attributes such as Zone Bypassing and Door Chime affect
the functionality of this zone. This zone type can also be assigned to a temperature sensor if indoor/outdoor temperature dis-
play is required without temperature warnings or alarm conditions.
056 –24 Hour High Temperature
This zone type is used with wireless temperature sensors and is activated when the temperature rises above a programmed
threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible alarm at default. This zone type gen-
erates an alarm when the system is armed or disarmed.
Note: This zone type cannot be used on hardwired zones. The temperature threshold includes a 3 °C (5-6 °F) difference
between a given state and its restored condition. For example, an alarm at 6 °C is restored at 3°C (High temperature) or 9°C
(Low temperature), depending upon the zone type selected.
The zone type for wireless temperature sensors must be 24 Hour High/Low Temperature in order for the sensor to operate
properly.
057 – 24-Hour Low Temperature
This zone type is used with wireless temperature sensors and is activated when the temperature drops below a programmed
threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible alarm at default. This zone type gen-
erates an alarm when the system is armed or disarmed.
Note: This zone type cannot be used on hardwired zones.
060 – 24-Hour Non-Latching Tamper
This zone is always active and reports a tamper condition with no audible alarm when opened or tamper/faulted.
061 - 24-Hour Masking
This zone is active 24 hours in either the armed or the disarmed state. This zone type does not generate an alarm, and does
not log in the Alarm Memory. This zone type generates a Masking Trouble on the system.
Note: This zone operates in SEOL only.
066 – Momentary Keyswitch Arm
Often used with a keyswitch module*, turning the key alternately arms and disarms the system and silences the alarms.
Tampers and faults only initiate their respective trouble sequence. The keypad gives no indication when this zone type is
activated.
- 81 -
Section 5: Programming
Note: With audible alarm active, using the keyswitch when disarmed is the same as entering an access code at the keypad.
Using the keyswitch during the first 30 seconds of a delayed fire alarm is the same as pressing a key at the keypad (the 90
second delay starts). Activation of a keyswitch zone arms or disarms the system. Activation of this zone type is NOT logged
nor is the Police code transmitted. Bypassed zones of this type are not un-bypassed when the system is disarmed. When the
zone is bypassed, a zone bypass event buffer log and communication occurs immediately, NOT when the system is armed.
*Keyswitch module not for use in UL/ULC listed installations.
067 – Maintained Keyswitch Arm
Often used with a keyswitch module, turning the key (open state) arms the system. Turning the key back (restored state) dis-
arms the system. Tampers and faults only initiate their respective trouble sequence.
Note: DO NOT use for wireless zones. Activation of the zone does not log or transmit the Police code. Bypassed zones of
this type are not un-bypassed when the system is disarmed. When the zone is bypassed, a zone bypass event buffer log and
communication occurs immediately, NOT when the system is armed.
With an audible alarm active, using the keyswitch when disarmed is the same as entering an access code at the keypad.
Activating this zone type during the first 30 seconds of a delayed fire alarm is the same as pressing a key at the keypad (the
90 second delay starts). If left in the open state, the system does not arm until the zone is restored and tripped again.
068 – Momentary Keyswitch Disarm
Use with a keyswitch module. Activating and restoring this zone disarms the partition and silences alarms. Tampers or faults
do not disarm the zone.
Note: Do not use as a global zone.
069 – Maintained Keyswitch Disarm
Used with a maintained keyswitch. Activating this zone disarms the partition.
Tampers or faults on this zone do not disarm the partition.
071 – Doorbell Zone
This zone type sounds a chime through keypads on the partition when activated. No alarms are generated. Various chime
tones can be programmed. Disabling door chime on the partition also disables the chime on this zone.
Note: Do not use as a global zone.
072 – Push to Set (Non CP-01 panels only)
Activating this zone starts an infinite exit delay when armed according to the methods described in the table below. To com-
plete the arming sequence, this zone must be activated and restored. Once done, the exit delay timer starts.
Arming method Infinite exit delay Arming mode
User code Y Away
Keyswitch Y Away
Away key Y Away
*0 arm Y Away
*9 arm N Stay
Stay key N Stay
Night key N Night
Remote access/SMS - Do not use
DLS arm N Away
No activity arming N Away
Note: Do not use exit delay termination with this zone type. Away arming with this zone bypassed prevents arming.
If you silence a fire alarm by entering a user code, and the zones that imitated the fire alarm remain open, a Bells Silenced
message displays. The system automatically clears the message when all the fire zones are restored on the system. When
the Bells Silenced message displays, a user can still view all standard base menu messages.
Note: The Bells Silenced message also overrides the automatic display of the Alarm Memory feature for fire alarms.
[002] Zone attributes
Zone attributes are used to customize the operation of zones. When a zone type (section [001]) is programmed, the default
zone attribute is automatically assigned.
Note: These attributes override default settings. Do NOT change fire zone attributes from their default settings.
- 82 -
Section 5: Programming
- 83 -
Section 5: Programming
EOL resistance
This section describes how to program EOL resistances to custom values.
[004] End of line resistance
Use this menu to program custom resistance values for SEOL, DEOL, and TEOL options in 3-digit format. For example, to
program the value of 0.5 kΩ, enter 005.
[001] – Single EOL
Alarm
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 28 kΩ (005 to 280)
[002] – Double EOL
Alarm
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 15 kΩ (005 -150)
Tamper
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 15 kΩ (005 -150)
[003] – Triple EOL
Alarm
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 7.5 kΩ (005 -075)
Tamper
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 7.5 kΩ (005 -075)
Fault/Mask
Default value: 10 kΩ
Programmable range: 0.5 kΩ to 15 kΩ (005 -150)
System times
This section describes how to program various timers applicable to the entire alarm system.
[005] System times
This is the base menu used by installers to program timers, including system area [000], partition timers [001]-[008], and day-
light saving time [901]/[902].
[000] – System Area
Bell Cutoff Time
System sirens follow this timer. Fire alarms follow this timer if section [014] option 8 (Fire Bell Continues Option) is off. System tampers follow this
timer. The bell cutoff time is programmed in minutes. Valid entries are 001 to 255 minutes.
- 84 -
Section 5: Programming
EN Note: European products will only activate the armed LED at the end of exit delay.
Settle Delay:
This timer enables a programmable, short duration bypass of all zones on the partition at the time of arming. It allows motion detectors to restore
when the system is armed to help prevent false alarms.
The typical value for this timer is 5 seconds, but can be increased if false alarms persist. Program 000 for no settle delay.
The settle delay duration is programmed in seconds. Valid entries are 000 to 010 seconds.
[900] – Bell Delay Partition Mask
This option enables or disables the Bell Delay feature for individual partitions. When the option is enabled, Bell Delay is
applied to the selected partition during alarm conditions. When the option is disabled, Bell Delay is not applied. The default
setting is (Y): enabled.
[901]/[902] – Daylight savings begin/end
Daylight Begin [001] and Daylight End [002]:
Set the date and time daylight savings starts and ends.
- 85 -
Section 5: Programming
Month
Valid entries are 001-012 (January to December).
Week
Valid entries are 000-005.
Enter “000” to program a specific date (1-31) in the Day field. Enter 001-005 to program the specific week of the month. 005
is the last week of the month.
Day
1-31 (if 000 is programmed in the Week field). 0-6 (Saturday-Sunday) if 001-005 is programmed in the Week field.
Hour
Valid entries are 00-23 hours. This is the time of day to advance or turn the clock back.
Increment
Valid entries are 1 or 2 hours. This is the number of hours to advance or turn the clock back.
Access Codes
This section is used by installers to program the installer code, the master code and the maintenance code. For information
on programming other access codes, see "[*][5] Program access codes" on page 64.
[006] Installer Defined Access Codes
This is the base menu used by installers to program the installer code [001], the master code [002] and the maintenance
code [003]. See below for details.
[001] – Installer Code
This code is used by the installer to gain access to Installer Programming [*][8]. Users with this access code have access to
all levels of system programming.
EN Note: For EN50131-1 approved installations the installer code cannot change the master code or any other level 2 codes.
[002] – Master Code
This code is used by the master user, a person designated to perform operational tasks beyond those of the standard user.
The master code provides access to functionality in the [*][5] and [*][6] menus.
[003] – Maintenance Code
This code is usually assigned temporarily to maintenance personnel who must deactivate the alarm to enter the premises.
The maintenance code can arm and disarm the system, but does not grant access to any other functionality.
UK [005] – Code Version
A programmable 3-digit pin is required to calculate the 5-digit remote reset code. The range of the pin is 000-255 in
decimal. The default value of the pin code is 000.
- 86 -
Section 5: Programming
- 87 -
Section 5: Programming
This output activates for audible exit fault and does not interfere with the operation of any other programmable output.
103 – Sensor Reset [*][7][2]
This output is normally active and deactivates for 5 seconds when a [*][7][2] fire reset command is entered or when an auto
verified fire alarm is detected. This option is used to reset power for latching smoke detectors. The keypad buzzer does not
sound for the 5-second period. See "Smoke detector wiring" on page 40 for instructions on wiring smoke detectors.
104 – 2-Wire Smoke
When this PGM is programmed, the onboard PGM functions as an input instead of an output. 2-wire smoke detectors can be
connected to this input, which means that a zone input does not need to be used.
The PGM is also supervised, and a trouble condition is generated if a 2.2KΩ resistor is not present between the PGM ter-
minal and Aux+.
The 2-wire smoke detector input creates an instant and latching alarm.
107 - External Siren
This output is normally active and provides up to 1A to charge the external sirens battery. When an alarm occurs on the sys-
tem, this PGM triggers and deactivates the voltage to the siren, which causes the siren to sound alarm using power from the
backup battery. Use this output with Grade 3 external battery-operated sirens.
Note: This PGM type works on PGM 3 only.
109 – Courtesy Pulse
Courtesy pulse causes an output to activate for the entry and exit times, plus 2 minutes. This option is typically used to activ-
ate a courtesy light near the exit door for the duration of the entry/exit times.
111 – Keypad Buzzer Follow
PGM output activates with the keypad buzzer when triggered by the events below. The PGM output remains active for the
duration of the keypad buzzer.
l 24-hour supervisory buzzer zone alarm
l Auto-arm and no activity arming pre-alert.
l No activity arm pre-alert
l Entry delay
l Audible exit fault
l Audible exit delay
l Door chime
This PGM type does not activate for local key presses or trouble beeps.
114 – Ready to Arm
This PGM activates when the system is ready to arm (all non-force armed zones on the system are restored). The PGM out-
put de-activates when an access code is entered to arm the system and the exit delay begins. This PGM operates as
described during walk test mode (if all zones are restored).
115 – System Armed Status
This output activates when all selected partitions are armed (end of the exit delay) in either Stay or Away modes. The output
de-activates when the system is disarmed.
116 – Away Armed Status
This PGM switches on when the system is armed with stay/away zones activated. If the system is armed with the stay/away
zones always active, then the away output is active.
117 – Stay Armed Status
This PGM output activates if the system is armed with the stay/away zones bypassed.
120 – Away Armed with No Zone Bypasses Status
When assigned to a single partition, this PGM output activates when the system is armed with stay/away and night zones act-
ive, and no zones are bypassed.
- 88 -
Section 5: Programming
If assigned to multiple partitions, all partitions must be armed in away mode with no bypassed zones before the PGM activ-
ates. If a force armable zone is violated at the time of arming, the PGM does not activate. When the zone is restored, the
PGM activates.
121-124 – Command Outputs 1-4
Command Outputs 1-4 are user-activated by entering [*] [7] [1-4] at any keypad. When an output is activated, three acknow-
ledgment beeps are sounded.
PGM outputs of this type can be programmed to follow a pre-defined schedule (programmed in section "[601]-[604] Sched-
ule labels" on page 77). Even if the output follows a schedule it can be manually turned ON, OFF or follow the schedule
through [*][7].
To select a schedule for these PGM outputs to follow, see "[009] PGM Types " on page 87.
129 – Partition Status Alarm Memory
This feature is intended to be used on a keyswitch plate, with a light controlled by this PGM to indicate system status. When
the partition is armed, the output activates (steady) at the:
NA beginning of exit delay
EN end of exit delay.
If an alarm occurs on the armed partition, the output flashes for the remainder of the armed period. If an alarm occurs on a
disarmed partition (24 Hr Zone), the output flashes until the alarm is acknowledged.
This output will not activate during a walk test or for FMP key, holdup or audible/silent PGM2 input alarms.
132 – Holdup Output
When a Holdup zone (Type [042]) goes into alarm, this output activates until the partition is either armed (access code, key-
switch, [*][0], etc.) or disarmed. A tamper or fault on a holdup zone type does not activate this output. This output does not
activate in Walk Test mode. If a global holdup alarm occurs, each partition with holdup zones assigned must be armed or dis-
armed before the holdup output deactivates. If holdup alarms occur on multiple partitions, an access code must be entered
at each partition before the output deactivates.
Note: Not for use with UL/ULC listed installations.
- 89 -
Section 5: Programming
- 90 -
Section 5: Programming
- 91 -
Section 5: Programming
If multiple zones are enabled, any active zone in that group triggers the output. The PGM will not activate again until all
zones are restored.
- 92 -
Section 5: Programming
- 93 -
Section 5: Programming
11 – Door Chime
ON: activates when chime is enabled.
OFF: does not activate when chime is enabled.
12 – Keypad Buzzer Zone
ON: activates when keypad buzzer goes into alarm.
OFF: does not activate when keypad buzzer goes into alarm.
13 – Audible Exit Fault
ON: activates when audible exit fault pre-alert begins.
OFF: does not activate when audible exit fault pre-alert begins.
14 – Auto-Arm Pre-Alert
ON: activates when auto-arming pre-alert begins.
OFF: does not activate when auto-arming pre-alert begins.
114 – Ready To Arm
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
115 – Armed Status
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
116 – Armed Away Mode
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
117 – Armed Stay Mode
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
120 – Away Armed with No Zone Bypasses Status
01 – True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
121-124 – Command Output 1-4
01 – True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
02 – Timed Output / Latched Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
03 - Access Code Required / No Code Required
ON: access code required for activation.
OFF: no access code required for activation.
129 – Partition Status Alarm Memory
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
- 94 -
Section 5: Programming
- 95 -
Section 5: Programming
OFF: does not activate when the system is disarmed with an alarm in memory.
12 – Emergency Alarm
ON: activates with zone emergency alarm.
OFF: does not activate with zone emergency alarm.
13 – Duress Alarm
ON: activates with duress alarm.
OFF: does not activate with duress alarm.
14 – Hold Up verified
ON: activates when a verified holdup event is detected.
OFF: does not activate when a verified holdup event is detected.
155 – System Trouble
01 – True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
02 – Timed Output / Latched Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
04 – Service Required
ON: activates on service required trouble condition.
OFF: does not activate on service required trouble condition.
05 – Loss of Clock
ON: activates on loss of clock trouble condition.
OFF: does not activate on loss of clock trouble condition.
06 – DC Trouble
ON: activates if a panel low or no battery trouble is detected, or if an HSM2204/2300 1-4 low or no battery trouble is
detected.
OFF: does not activate on DC Trouble condition.
07 – Bus Voltage
ON: activates when a system module has measured a low Aux voltage.
OFF: does not activate for a module low voltage trouble.
08 – AC Trouble
ON: activates when any system device detects an AC Failure condition.
OFF: does not activate for AC Failure conditions.
09 – Device Fault
ON: activates if one of the following device fault conditions is present:
l zone 001 – 248 fault
l keypad 01 – 16 fault
l siren 01 – 16 fault
l repeater 01 – 08 fault
l fire trouble
l CO trouble
l gas trouble
l heat trouble
l freeze trouble
l probe disconnected trouble
l self test trouble
OFF: does not activate if a device fault condition is present.
10 – Device Low Battery
ON: activates if any of the following device low battery conditions is present:
- 96 -
Section 5: Programming
- 97 -
Section 5: Programming
- 98 -
Section 5: Programming
- 99 -
Section 5: Programming
- 100 -
Section 5: Programming
System Options
[013] System Option 1
1 – NC Loop/EOL
ON: All zones are wired as normally closed circuits with returns connected to a COM terminal. The end-of-line resistor is not
required. An alarm is generated when the circuit is opened.
OFF: All zones must be wired with an end-of-line resistor configuration, determined by option 2 below.
Note: The valid EOL value is 5600 Ohms (5.6KΩ).
2 – DEOL/SEOL
ON: All zones use Double-End-of-Line resistors, except Standard Fire, Delayed Fire, Auto-Verified Fire, Co and Supervisory
zone types. DEOL resistors enable detection of zone faults and tampers. The tamper resistor (5.6KΩ) is placed in parallel
across the alarm activating device, and the single EOL resistor (5.6KΩ) is placed between the alarm and tamper contacts.
This allows detection of zone faults (shorted zone), tampers (open zone), alarms (11.2KΩ), and restored zones (5.6KΩ).
- 101 -
Section 5: Programming
If the zone is disarmed and placed in the tamper or fault state, trouble beeps sound on all system keypads until a key is
pressed on each partition. A zone tamper is sent to the monitoring station if programmed. If the zone is armed and a tamper
is activated, the tamper alarm and zone alarm are logged and transmitted.
OFF: All zones must have a 5.6KΩ resistor. If the zone is shorted or open, it is in the tripped state. If the zone is open and pro-
grammed as a fire zone, it is in the trouble state. The EOL and DEOL zone attributes override this system option.
Note: Zone Faults (Supervisories) on wireless zones do not cause an audible alarm while armed.
3 – Show All Troubles When Armed
ON: The Trouble LED illuminates when troubles are present on the system in both the armed and disarmed state.
OFF: The Trouble LED illuminates for all troubles while disarmed, but only for Fire Troubles while armed.
4 – Tamper/Faults Do Not Show As Open
ON: The zone does not show open if the zone is in the tamper or fault states. Only the Trouble LED illuminates.
OFF: The respective zone LED shows open if the zone is in the tamper or fault states. The Trouble LED also illuminates.
5 – Auto-Arm Schedule in [*][6]
ON: The auto-arm schedules ([151] - [158]) are accessible via [*][6] as well as Installer Programming.
OFF: The auto-arm schedules ([151] - [158]) are only accessible to installers via Installer Programming.
Note: This toggle controls access for all eight partitions.
6 – Audible Exit Fault
ON: If a delay type zone is violated after the exit delay has expired, an entry delay warning is sounded through the keypad
and siren indicating that an improper exit was made. If the alarm system is disarmed within the entry delay period no signal
is sent.
OFF: The entry delay warning is sounded only through the keypad.
7 – Event Buffer Follows Swinger
ON: Once an event reaches its swinger shutdown limit programmed in "[377] Communication Variables" on page 123, it will
no longer log events to the event buffer until the swinger shutdown is reset. This avoids filling the event buffer with false
events.
OFF: The event buffer continues to log events to the buffer even after the event has gone into swinger shutdown.
8 – Temporal Three Fire Signaling
ON: All fire bells sound in the temporal three pattern. Cadence is as follows: (500ms ON, 500ms OFF, 500ms ON, 500ms
OFF, 500ms ON, 1.5 sec. OFF).
OFF: All fire bells will sound with the standard 1 second on/1 second off fire bell cadence.
Note: Must be on for UL/ULC installations.
[014] System Option 2
1 – Bell Squawk
ON: The siren emits a single squawk when armed in any manner, including Auto-arm, and a double squawk when disarmed.
When the system is disarmed, the siren emits a series of three squawk pairs to indicate alarms in memory.
OFF: The siren does not squawk when arming or disarming.
NA Note: For UL/ULC, must be enabled if wireless keys are used with the alarm system.
2 – Bell Squawk on Auto-Arm
ON: The siren squawks once every 10 seconds during the auto-arm pre-alert time.
OFF: The siren does not squawk during auto-arm pre-alert.
3 – Bell Squawk On Exit
ON: The siren squawks once per second during exit delay, changing to 3 squawks per second for the final 10 seconds.
OFF: The siren does not squawk for exit delay conditions.
4 – Bell Squawk On Entry
ON: The siren pulses with the same timing as the keypad buzzer during entry delay, changing to 3 squawks per second for
the final 10 seconds.
OFF: The siren does not activate during entry delay.
- 102 -
Section 5: Programming
- 103 -
Section 5: Programming
- 104 -
Section 5: Programming
OFF: The tamper switches on all keypads do not generate tamper alarms.
Note: If this option is used, all keypads should be properly installed and secured (tamper restored) before enabling the
option.
NA Note: Must be ON for UL/ULC commercial burglary listed installations.
[017] System Option 5
1 – Chime on Opening
ON: When a zone with the door chime attribute ON is opened, the system keypads and sirens (if enabled) beep.
OFF: When a zone with the door chime attribute ON is opened, the system keypads and sirens (if enabled) do not beep.
2 – Chime on Closing
ON: When a zone with the door chime attribute ON is closed, the system keypads and sirens (if enabled) beep.
OFF: When a zone with the door chime attribute ON is closed, the system keypads and sirens (if enabled) do not beep.
3 – RF Jam Trouble Beeps
ON: Trouble beeps sound when an RF Jam Trouble is detected
OFF: Trouble beeps do not sound when an RF Jam Trouble is detected
4 – Multi Hit
ON: Alarms from the same zone within the Burglary Verification Timer duration cause the police code or burglary verified to
be logged and transmitted. The number of zone trips required to create a confirmed alarm depends on the value of the pro-
grammable burglary verification counter.
OFF: Alarms from the same zone within the Burglary Verification Timer duration do not cause the police code or burglary veri-
fied to be logged and transmitted.
Note: This feature only applies to zones defined as Interior, Interior Delay, Interior Stay/Away, Instant Stay/Away, Delay
Stay/Away, or Night Zones (PIR Zones). Do enable this option if section [380], option 2 - Restore on Bell Time Out is
enabled.
5 – Late to Close
ON: Provides an audible warning if the alarm system has not been armed by a programmed time of day but does not arm the
alarm system. The alarm system communicates and logs a Late to Close event at the end of the Auto-arm/Postpone pre-alert
for each partition.
OFF: The alarm system will neither communicate nor log a Late to Close event at the time programmed for Auto-arm for each
partition.
Note: If the Auto-arm toggle option is disabled, the Auto-arm Pre-alert still occurs when a time is programmed for that day (if
enabled) and the event is logged and communicated. This option does not directly affect the functionality of Auto-arm. If Late
to Close is enabled and Auto-arming is not, LCD keypads display “System Arming in Progress” during the Late to Close Pre-
alert.
6 – Daylight Savings Time
ON: The alarm system adjusts between Daylight and Standard times according to the times programmed in System Timers
([005] options 901-902).
Note: Auto-arm and Test Transmissions should not be attempted between 0200 and 0300 hours, as they will be missed dur-
ing a daylight savings clock adjust. Events programmed to occur between 0100 and 0200 will occur twice during a daylight
savings clock adjust. Daylight Savings Time programming should not conflict with the Auto-arm and Test Transmissions pro-
gramming.
OFF: The alarm system makes no automatic time adjustments for Daylight Saving time.
7 – Silence Chime During Quick Exit Delay
ON: Door chime does not sound during quick exit.
OFF: Door chime sounds during quick exit, according to zone settings.
8 – Bell Squawk on Away Arm/ Disarm Only
ON: Bell Squawks are only heard when away arming, as well as when disarming from Away mode. This feature prevents the
siren from activating when arming in stay and night modes.
OFF: Bell Squawks are heard during all types of arming and disarming.
- 105 -
Section 5: Programming
Note: This option follows the “Bell Squawk Attribute” features if they are enabled.
[018] System Option 6
1 – Test Transmission Exception
ON: The alarm system does not send a test transmission if a transmission was sent to the receiver within the programmed
interval as set in section [377]>See "[003] – Periodic Test Transmission Cycle" on page 125.
OFF: Test transmissions are always sent at the programmed interval.
2 – Real-Time Bypass Reporting
ON: When a non-24-hour zone is bypassed in [*][1], the system immediately logs and communicates the bypass status of the
zone.
Global Zones: 24-hour and non-24 hour zone bypasses are logged and communicated in real time. Non-24 hour zone unby-
pass events are generated when the last assigned partition is disarmed.
OFF: When a non 24-hour zone is bypassed in [*][1], the system logs and communicates the bypass status of the zone only
after the partition is armed. This option is applied regardless of how zones are bypassed in [*][1], recall bypass group, clear
all bypasses, bypass open zones, bypass recall as well as other methods such as bypassing via ITv2 or DLS.
Global Zones: 24-hour zone bypasses are logged and communicated in real time. Non 24-hour zone bypass events are
logged and communicated when armed. Non 24-hour zone unbypass events are logged and communicated when the par-
tition is disarmed.
3 – Armed Status PGM ON at End of Exit Delay
ON: PGMs are activated at the end of exit delay. This applies to PGMs with one of the following armed status attributes:
l 115 System Armed Status PGM
l 116 Away Armed Status PGM
l 117 Stay Armed Status PGM
l 120 Away Armed with No Zone Bypass Status
l 129 Partition Status Alarm Memory
OFF: PGMs are activated at the beginning of exit delay. This applies to PGMs with one of the armed status attributes listed
above.
4 – Auto Bypass Report
ON: All Night or Stay/Away type zones that are auto-bypassed when arming in Night or Stay mode log and report Zone
Bypass. When disarming, all auto-bypassed Night or Stay/Away zones log and report Zone Un-Bypassed. All manually
bypassed zones continue to log and report.
OFF: All Night or Stay/Away type zones that are auto-bypassed when arming in Night or Stay mode do not log or report Zone
Bypass. When disarming, all auto-bypassed Night or Stay/Away zones do not log and report Zone Un-Bypassed. All manu-
ally bypassed zones continue to log and report.
5 – Keypad Buzzer Follows Bell
ON: The keypad buzzer activates with all bell activity for the selected partition.
OFF: The keypad buzzer only activates with alarms programmed to do so.
7 – Exit Delay Restart
ON: Opening a delay zone door after it has already been opened and closed during an exit delay restarts the exit delay
timer. Further openings and closings do not restart the timer.
OFF: Delay zone openings and closings do not restart the exit delay.
8 – AC Fail Trouble Beeps
ON: System keypads beep when an AC trouble event occurs.
OFF: System keypads are silent during AC troubles.
6 – Reserved
[019] System Option 7
1 – Audible Wireless Device Fault
ON: If a wireless zone fault occurs while armed, the siren sounds for the duration of Bell Time Out. This option only affects
zone definitions that are considered armed. The following zone types do not generate an alarm when faulted while stay
armed: interior stay away zone, delay stay away zone, instant stay away zone, night zone. The following zone types do not
- 106 -
Section 5: Programming
generate an audible alarm in any armed state (stay, away, or night): 24-hour supervisory, 24-hour non-alarm, 24-hour CO,
delayed 24-hour Fire, standard 24-hour fire, Auto-verified fire.
When the partition is armed, wireless supervisory troubles from sirens, keypads and repeaters generate audible alarm con-
ditions.
If Tamper/Fault Detection is enabled, these events can start the burglary verified timer and affect the burglary verified
counter.
OFF: Wireless device faults do not sound the siren.
2 – Latching Troubles
ON: Troubles remain on the system until viewed via [*][2], even if they are restored. The trouble condition is cleared when
the"Press (*) to Acknowledge" option is selected within the [*][2] menu after the trouble has restored. The Trouble LED turns
off unless other troubles are present. The trouble is not cleared if the [*][2] menu times out before the [#] key is pressed.
OFF: Troubles are cleared once restored.
3 – Reserved
4 – Reserved
5 – Audible Bus Fault
ON: All module supervisory trouble conditions activate the siren.
OFF: Only zone expander supervisory trouble conditions while armed activate the siren.
6 – Duress Codes
UK
ON: The duress code attribute can be enabled/disabled from the [*][5] menu. For BS8243 installations the default is off.
OFF: The duress code attribute is not programmable from the [*][5] menu.
7 – Temperature in Celsius
ON: Temperature is displayed in Celsius on LCD keypads.
OFF: Temperature is displayed in Fahrenheit on LCD keypads.
8 – Reset After Zone Activation
ON: Only a police code\sequential detection alarm requires a remote reset once the partition has been disarmed.
OFF: Any burglary alarm requires a remote reset once the partition has been disarmed.
[020] System Option 8
1 – Access Code Entry During Entry Delay
ON: During entry delay the alarm system can only be disarmed using a keyswitch or proximity tag. When the siren is active
an access code can still be used to disarm the system.
OFF: An access code can be used to disarm the system during entry delay.
EN 2 – EU Entry Procedure
ON: If an alarm occurs on a zone when entry delay is not active, the siren activates and the alarm is communicated imme-
diately, depending on the zone type tripped.
When entry delay is active, all burglary type alarms activate the siren, but communication of the alarm is delayed by 30
seconds. When entry delay expires, the alarm is not communicated unless the siren has been active for at least 30 seconds.
Police code is not generated as a result of alarms triggered during entry delay, although the Burglary Verification Timer
starts after entry delay and the 30-second communication delay expire.
This feature is only active when the partition is armed.
OFF: Burglary alarms that occur during entry delay activate the siren and are communicated immediately. Two exceptions
are if the bell delay timer is programmed and if transmission delay is enabled for the zone in alarm. In both cases, the alarm
follows the timer.
3 – [*][8] Access While Armed
ON: This option ensures [*][8] installer programming is accessible from a keypad on a disarmed partition while other par-
titions on the system are still armed.
Note: For UL listed installations, this option must be disabled.
- 107 -
Section 5: Programming
OFF: [*][8] installer programming is not available when any partition on the system is armed. All partitions must be disarmed
and the siren must be off before [*][8] is accessible.
UK 4 – Remote Reset
ON: If an alarm occurs on a burglary zone, the system is locked out after disarming. It remains locked until a 5-digit reset
code, provided by the installer/central station, is keyed in. If a duress code is used to disarm the partition, the system is not
locked out.
In the disarmed state, only Audible 24 Hour Burglary zones, Audible 24 Hour Latching Tamper zones, and Audible 24 Hour
zone on PGM 2 cause lockout.
To obtain the reset code, the user must provide a corresponding system lock code, displayed on the keypad when one of the
following conditions occurs:
l the system has been disarmed (Duress Code excluded)
l the bell has timed out (24Hr zones)
l an access code has been entered (24Hr zones)
On an LCD keypad, the message “REMOTE RESET RQD” is displayed on the top line and “CODE” along with the actual
code is displayed across the bottom line..
While the system is locked out, the only options available are [*][3], [*][6], [*][7], and [*][8]. Accessing [*][8] Installer Pro-
gramming unlocks the alarm system. The system continues to function (alarms, tampers, etc) while the system is locked out.
Lock out follows both transmission and bell delays.
OFF: The system is not locked out after an alarm occurs.
EN 5 – Engineer’s Reset (EU)
ON: If the alarm system has gone into alarm during the previous armed period, or if a 24-hour alarm has occurred (armed or
disarmed), the system cannot be armed (Ready light OFF) until Installer Programming is entered or Engineer’s Reset is per-
formed via DLS. “Reset Required” is displayed on the keypad. This feature applies to tampers and faults in both armed and
disarmed states and does not apply to module tampers, system supervisories, zone expander alarms or PGM 2 input alarms.
Note: If Engineer’s Reset is triggered during exit delay, the system still arms. Troubles cannot be overridden while Engin-
eer’s Reset is enabled.
OFF: The system does not require Engineer’s Reset or to be placed into Installer Programming in order to arm the alarm sys-
tem after an alarm.
6 – Keyswitch Disarming During Entry Delay
ON: Keyswitches, proximity tags and wireless keys disarm the alarm system only if an entry delay is active.
OFF: Keyswitches, proximity tags and wireless keys disarm the alarm system regardless of entry delay.
Note:Do not enable with option in conjunction with [040] Prox and Code.
EN 7 – Installer Access and DLS
ON: The user must enter [*][6][access code][05] before the installer can access Installer Programming by DLS or via the
keypad ([*][8]).
Installer Programming remains accessible for 6 hours, during which time the installer can enter/exit or connect with DLS an
unlimited number of times.
OFF: The installer can access Installer Programming without the user entering [*][6].
EN 8 – Troubles Inhibit Arming
ON: The following troubles prevent arming until restored:
l Tampers on the alarm system, modules and zones
l Corbus troubles
l AC troubles on the alarm system and modules
l Battery troubles on the alarm system, modules and zones
l Transmission troubles (FTC, TLM, GPRS, Ethernet)
l Bell troubles
The alarm system can still be armed if troubles are overridden. To perform a trouble override, while in the Trouble Menu ([*]
[2]), scroll right or left and press [*] when Trouble Acknowledgment is displayed on the keypad. Alternatively, press the [9][9]
key to acknowledge and override the existing troubles.
To override open zones, faulted zones or tampered zones use the Zone Bypass feature.
- 108 -
Section 5: Programming
OFF: The system can be armed even when troubles are present.
Note: When Engineer’s Reset is on, trouble conditions cannot be overridden. Zone Expander supervisory troubles cannot
be acknowledged and overridden. These conditions must be restored before the panel can be armed.
Note: When [024][3] is enabled, AC/DC Inhibit Arming, the AC or DC trouble must be restored before the system can be
armed.
[021] System Option 9
EN 1 – Trouble Display
ON: If the panel is both armed and keypad blanking is active, when a trouble is present the keypad trouble LED will remain
off . When the system is disarmed, or if blanking is removed, the trouble LED will be active if a trouble is present.
OFF: The trouble LED will turn off when keypad blanking is active in armed or disarmed state.
EN 2 – Keypad Blanking while Armed
ON: If [016][3] is disabled within 30 seconds after the exit delay terminates, the keypad blanks (no indicator lights).
OFF:The keypad blanks when the system is armed or disarmed.
Note: For systems compliant with EN50131-1 and EN50131-3, option [021] bit 2 “Keypad blanking while armed” must be
ON.
3 – Reserved
4 – Ready Display
ON: The keypad ready LED will continue to show system ready status while keypad blanking is active.
OFF: The keypad ready LED will turn off when keypad blanking is active.
5 – PGM Blanking
This feature is meant to be used in conjunction with the keypad blanking while armed feature.
EN ON:This feature is necessary to comply with EN50131-1:2006.
When the system enters blanking mode, any PGMs programmed as Armed Status, Ready Status, Away Armed Status, or
Stay Armed Status will de-activate. If blanking is cleared by pressing a key, or entering an access code depending on how
the panel is configured, these PGMs must re-activate if they would have normally been ON if blanking was disabled.
OFF: When the system enters blanking mode, any PGMs programmed as Armed Status, Ready Status, Away Armed Status,
Stay Armed Status) operate normally.
6 – Armed Display
ON: The keypad armed LED will continue to show Armed status while keypad blanking is active.
OFF: The keypad armed LED will turn off when keypad blanking is active.
7 – Open Zones Cancels Arming
ON: The system cannot be armed while zones are open unless the zones are bypassed using [*][1]. In order to bypass open
zones, the bypass attribute needs to be enabled for the zone.
OFF: Open zones do not prevent arming.
8 – Audible Exit Delay for Stay Arming
ON: When the system is armed in Stay mode the exit delay is sounded by 1 beep every 3 seconds.
OFF: When the system is armed in Stay mode the exit delay is silent.
[022] System Option 10
1 – [F] Key Option
ON: When the [F] key is pressed, acknowledge beeps are only emitted from the keypad. The siren does not sound fire alarm.
OFF: [F] key acknowledgment beeps are emitted from the keypad and sounds for fire alarm.
2 – Reserved
3 – Reserved
EN 4 – Transmission Counter in Hours
ON: The alarm system sends a test transmission after the programmed number of hours in the test transmission cycle (Sec-
tion [377], Option 003).
OFF: The alarm system sends a test transmission after the programmed number of days.
- 109 -
Section 5: Programming
- 110 -
Section 5: Programming
Note: For UL Residential installations, ensure the access code requirement is set to ON.
EN 6 – Access Code Required for [*][3]
ON: When using the [*][3] View Alarms in Memory command, an access code must be input before the alarm memory can be
viewed.
OFF: An access code is not required to view alarms in memory using [*][3].
7 – Access Code Required for [*][4]
ON: When using the [*][4] Chimes command, an access code must be input before chimes can be toggled on and off.
OFF: An access code is not required to toggle chimes using [*][4].
8 – [*][6] Accessibility
ON: All user codes provide access to the [*][6] menu.
OFF: Only the master code provides access to the [*][6] menu.
[024] System Option 12
1 – Reserved
2 – Reserved
EN 3 – AC/DC Inhibits Arming
ON: The system cannot be armed when an AC or battery trouble is present. This includes keypad, keyswitch, automatic, and
DLS arming. An error tone is generated if the user attempts to arm the system during an AC/DC trouble.
Note: Displaying AC troubles ([016] option 2) is strongly recommended if this option is enabled.
OFF: The system can be armed, regardless of the presence of an AC or DC trouble and does not check the system battery
upon arming.
EN 4 – Tampers Inhibit Arming
ON: The following conditions trigger Tampers Inhibit Arming:
l Faults on the zones, modules
l Tampers on the zones, modules
l Bell circuit trouble
l Communications fault troubles (TLM, FTC, Radio/Sim card failure, ethernet trouble, communicator fault)
l Warm start troubles
Tampers must be restored through Installer Programming before the system can be armed (including no-activity and key-
switch arming). Reset Required displays on the keypad.
When this option is enabled, manual zone bypassing does not bypass the tamper or fault states (DEOL). This feature also
applies to zone faults.
OFF: Tamper troubles do not latch and do not prevent arming.
5 – Real time Clock
ON: If enabled, the panel will set the time and date automatically provided by either the on board Ethernet or the cellular com-
municator at 4:05pm.
OFF: If disabled, the system time and date needs to be manually programmed
Note: The time zone of the panel must be set in [851][020] and the Ethernet or Cellular communication must be com-
municating to a System 5 Surgard receiver.
6 – Reserved
7 – Reserved
8 – DLS Disconnect
ON: All events except Periodic Test Transmission, Periodic Test with Trouble, and System Test are considered priority
events. If DLS is active when an event occurs, the alarm system immediately terminates the connection in order to com-
municate the new events.
OFF: Only the following alarm type events terminate a DLS session:
l Zone alarms
l FMP key alarms
l Duress alarms
- 111 -
Section 5: Programming
- 112 -
Section 5: Programming
Mode Description
001 Police Code The burglary verification timer operates in minutes.
002 Cross Zoning The burglary verification timer operates in seconds. The first alarm in the sequence does not log or communicate the
alarm or activate the bell.
003 Sequential The burglary verification timer operates in minutes. The first alarm in the sequence causes an audible bell.
Detection
Partition Setup
[151]-[158] Partition Auto-Arm/Disarm
Enter section 151 to 158 for partition 1 to 8 auto-arm/disarm configuration.
[001] – Partition Auto-Arming Times
Use this section to program the time of day a partition is automatically armed. A different auto-arming time can be pro-
grammed for each day of the week from Sunday to Saturday. Time is in 24-hour format (HH:MM) and valid entries are from
00:00 to 23:59.
Conditions that cancel auto-arming if enabled:
l Open zones (depending on the settings of the zone)
l AC/DC troubles
l System troubles
l Any valid disarming procedure - proximity tag, access code, disarm key, etc.
[002] – Partition Auto-Disarm Times
Use this section to program the time of day a partition is disarmed. A different auto-disarming time can be programmed for
each day of the week from Sunday to Saturday. Time is in 24-hour format (HH:MM) and valid entries are from 00:00 to 23:59.
- 113 -
Section 5: Programming
Note: If entry delay is active at auto-disarm time, the system does not disarm. A valid disarming procedure is required by the
user who initiated the entry delay.
[003] – Partition Auto-Disarming Holiday Schedules
Use this section to select a holiday schedule group.
See "[711]-[714] Holiday Schedules" on page 132for more information.
[004] – Partition Auto-Arming Pre-Alert Timer
Use this section to program the duration of the auto-arm pre-alert. The system arms when the pre-alert timer expires. Valid
entries are from 001 - 255 minutes.
If a valid access code is keyed in, this timer is postponed for the length of time programmed in Partition Auto-Arm Postpone
timer (see below). The pre-alert timer can be postponed multiple times. Keyswitches and proximity tags can be used to can-
cel auto-arming.
[005] – Partition Auto-Arm Postpone Timer
Use this section to program the length of time the auto-arm pre-alert timer is postponed for. Valid entries are between 001
and 255 minutes. 000 cancels the postpone timer.
When the postpone timer expires, the Auto-arm pre-alert timer restarts (unless the partition is armed). If left uninterrupted the
partition arms at the end of the pre-alert.
If a code is entered during the pre-alert, auto-arm cancel/postpone is logged and communicated and the postpone timer
starts. When the postpone timer expires, pre-alert is sounded again and the cycle repeats. The Auto-arm may be postponed
multiple times.
[006] – Partition No Activity Arming Timer
Use this section to program the duration of the No Activity timer. If this timer expires and no zones have been activated, the
partition arms in Away mode (exit delay will not sound). When the timer expires, keypad buzzers activate for the time pro-
grammed in No Activity Arming Pre-Alert (see below).
The timer restarts when a delay type zone is restored. The timer does not restart when the system is disarmed. The timer
stops if an un-bypassed zone is tripped, tampered or restored or with any keypad activity.
Separate No Activity Arming timers are provided for each partition.
Valid entries are from 000 – 255 minutes. 000 disables this feature.
[007] – Partition No Activity Arming Pre-Alert Timer
Use this section to program the duration of the No Activity Arming pre-alert that sounds when the No-Activity timer for the par-
tition expires. If any key is pressed or zone is activated or restored, the No Activity Arming pre-alert is aborted.
Valid entries are 000 - 255 minutes. 000 disables this feature.
Note : Wireless key arm keys cannot be used to cancel no activity pre-alert.
[200] Partition Mask
A partition is a limited area of the premises which operates independently from the other areas. Partitions are added or
removed from the system by applying or removing a partition mask.
[001] – Partition 1 to 8 Enable Mask
Select options 01-08 to enable or disable partitions.
Partition 1 is always enabled. Partitions 2 to 8 are selectable.
The number of available partitions depends on the model, as shown below:
- 114 -
Section 5: Programming
All zones assigned to a partition are supervised and operate according to the zone type programmed. If a zone is not
assigned to a partition, it is not supervised and all activity on the zone is ignored by the system.
[300] Panel/Receiver Communication Paths
This section is used to select the path of communications between the alarm system and the central station.
Paths can be established through either the alarm system’s on-board Public Switched Telephone Network (PSTN) con-
nection through the on board Ethernet or through the optional cellular communicator.
Paths to four receivers can be programmed using sections 001 - 004. The communications path for each receiver is defined
by selecting one of the following six options:
[01] Phone Line
Events are communicated through the alarm system phone line programmed in section [301]. If Phone Line is selected for
receiver 1, the phone number programmed in section [301] option [001] is used. If Phone Line is selected for receiver 2, the
phone number programmed in section [301] option [002] is used, etc.
[02] Alternate Communicator Auto Routing
Selecting this option enables the alternate communicator to determine which communications path to use (Ethernet
primary/secondary, and/or cellular primary/secondary). See section [851] Alternate Communicator Programming for details.
[03] Alternate Communicator Receiver 1
Events are communicated through Ethernet receiver 1.
[04] Alternate Communicator Receiver 2
Events are communicated through Ethernet receiver 2.
[05] Alternate Communicator Receiver 3
Events are communicated through cellular receiver 3.
[06] Alternate Communicator Receiver 4
Events are communicated through cellular receiver 4.
- 115 -
Section 5: Programming
Reporting
[307] Zone Reporting
Zone alarms, tampers and faults are transmitted to the central station using automatic contact ID or SIA formats. Reporting
can be toggled on or off by zone using toggle options 1-6 in subsections 001-248.
See "Reporting Codes" on page 223 for zone reporting code descriptions.
1 - Alarm
2 - Alarm Restore
3 - Tamper
4 - Tamper Restore
5 - Fault
6 - Fault Restore
[308] Event Reporting
System events are transmitted to the central station using automatic contact ID or SIA formats. Reporting can be disabled by
toggle options, programmable in the following sub-sections.
See "Reporting codes" on page 250 for event code descriptions.
[001] Miscellaneous Alarm 1
The reporting codes in this section are sent to the Alarm & Restore call direction group.
1 – Duress Alarm
Sent when a duress code is used to perform any function on the system.
2 – Opening After Alarm
Sent during disarming if an alarm occurred during the previous armed period.
- 116 -
Section 5: Programming
- 117 -
Section 5: Programming
7 – Remote Lockout
Sent when a number of invalid access codes have been entered through DLS or Integration. This reporting code is sent to
the system Tamper Alarm & Tamper Restore call direction group.
[201] Open/Close Events 1
1/2 – User Closing/Opening
This reporting code is transmitted when a user arms/disarms a partition and uses the Opening and Closing call direction.
5/6 – Special Closing/Opening
This reporting code is transmitted when a partition is closed/opened using quick arm ([*][0]), downloading, or Stay or Away
function keys without an access code. The Opening and Closing call direction group is used for this reporting code.
7/8 – Keyswitch Opening/Closing
This reporting code is transmitted when a keyswitch zone is used to arm or disarm the system.
[202] Open/Close Events 2
1 – Automatic Closing
This reporting code is transmitted when a partition is automatically armed or schedule armed and uses the Opening call dir-
ection group.
2 – Automatic Disarm
This reporting code is transmitted when a partition is automatically disarmed when a scheduled time of day is reached.
3 – Auto Arm Cancellation/Postpone
This reporting code is transmitted when the automatic arm sequence is canceled during a pre-alert and uses the Opening
and Closing call direction group.
[211] Miscellaneous Open/Close Events
1/2 – Late to Close/Open
This reporting code is transmitted when a partition is not disarmed before the automatic disarm time, when the late to open
option, ([*][6], option 9) is enabled. The Opening and Closing call direction group is used for this reporting code.
5 – Exit Fault
This reporting code is transmitted when an exit error occurs and entry delay expires before the system is disarmed. The
Alarms and Restores call direction group is used for this reporting code.
If the delay zone that caused the exit error has cross zoning enabled, the exit fault and zone alarm transmits if a second zone
is not tripped. The local alarm sequence follows cross zoning rules. The exit error is transmitted with the zone alarm that
caused the fault, even if that zone has transmission delay enabled.
[221] Bypass Events
1/2 – Automatic Zone Bypass/Unbypass
This reporting code is transmitted when a zone is automatically bypassed/unbypassed and uses the Opening and Closing
call direction group.
UK Note: Must be enabled in UK.
03 – Partial Closing
This reporting code is transmitted if zones are manually bypassed at the time of arming or force armed by automatic arming.
The Opening and Closing call direction group is used for this reporting code.
Automatic bypasses caused by stay arming do not cause transmission of this code.
[301] Panel Events 1
1/2 – Panel AC Fail Trouble/Restore
This reporting code is transmitted when the alarm system AC supply fails or has been restored. A programmable delay
applies to both the trouble and the restore. This reporting code is sent to the System Maintenance call direction group.
3/4 – Panel Low Battery Trouble/Restore
These reporting codes are transmitted when the panel battery voltage falls below 11.5VD or is restored. These reporting
codes are sent to the System Maintenance call direction group.
5/6 – Panel Battery Absent Trouble/Restore
These reporting codes are transmitted when the panel battery is not connected or is restored. These reporting codes are
sent to the System Maintenance call direction group and are transmitted when the panel battery is detected as absent.
- 118 -
Section 5: Programming
- 119 -
Section 5: Programming
Note: If DLS is terminated by an alarm, the DLS Lead Out reporting code is not transmitted.
5/6 – SA Lead In/Lead Out
The SA Lead In reporting code is sent:
l after SA communication has been successfully established, but before the alarm system calls back the downloading
computer. This code is only transmitted when call back is enabled.
l on user-initiated call-up.
The SA Lead Out reporting code is sent when an SA session is successfully ended. The SA Lead Out reporting code is still
sent if the session is terminated by an alarm.
7 – Event Buffer 75% Full
Sent when the event buffer reaches a threshold of 75% without being uploaded.
[313] Maintenance Events 3
1/2 – Firmware Update Begin/was Successful
Sent when a remote firmware update is initiated/ is successfully completed.
3 – Firmware Update Fail
Sent after an unsuccessful remote firmware update.
[314] Maintenance Events 4
1/2 – Gas Trouble/Restore
Sent when a trouble occurs or is restored on a wireless gas detector.
3/4 – Heat Trouble/Restore
Sent when a heat trouble occurs or is restored on a wireless temperature detector.
5/6 – Freeze Trouble/Restore
Sent when a freeze trouble occurs or is restored on a wireless temperature detector.
7/8 – Probe Disconnected Trouble/Restore
Sent when a probe disconnected trouble occurs or is restored on a wireless temperature detector.
[321] Receiver Events
2/4/6/8 – Receiver 1 - 4 FTC Restore
Sent when the panel detects an FTC trouble.
[331] Module Events 1
1/2 – Module AC Trouble/Restore
This reporting code is transmitted when a module’s AC supply fails or has been restored. A programmable delay applies to
both the trouble and the restore. This reporting code is sent to the System Maintenance call direction group.
3/4 – Module Battery Trouble/Restore
These reporting codes are transmitted when a module’s battery voltage falls below 11.5VDC or is restored. These reporting
codes are sent to the System Maintenance call direction group.
5/6 – Module Battery Absent/Restore
These reporting codes are transmitted when a module’s battery is absent or is restored. These reporting codes are sent to
the System Maintenance call direction group.
7/8 – Module Power Unit Failure/Restore
These reporting codes are transmitted when a module’s battery is detected as absent or restored. These reporting codes are
sent to the System Maintenance call direction group.
[332] Module Events 2
1/2 – Module Low Voltage Trouble/Restore
Sent when module voltage drops below acceptable levels or is restored.
3/4 – Module Supervisory Trouble/Restore
Sent when communication with a module is lost or restored.
5/6 – Module Aux Trouble/Restore
Sent when a high current output module or power supply module experiences an auxiliary voltage supply trouble.
- 120 -
Section 5: Programming
- 121 -
Section 5: Programming
System Communications
The programming options in this section are used to configure communications between the alarm system and the central
station.
[309] System Call Direction
Use this programming option to select the central station receivers that system events are communicated to. A system event
can be sent to multiple receivers.
[001] Maintenance Events/Restores (all troubles except tampers)
These options control which receiver paths are enabled for maintenance events. To assign a maintenance event to a
receiver, select from the following list:
[01] Receiver 1
[02] Receiver 2
[03] Receiver 3
[04] Receiver 4
[002] Test Transmissions
These options control which receiver paths are enabled for test transmission events. To assign a test transmission event to a
receiver, select from the following list:
[01] Receiver 1
[02] Receiver 2
[03] Receiver 3
[04] Receiver 4
[310] Account Codes
These programming sections are used to set the system and partition account codes.
[000] System Account Code
The system account code is used to identify the alarm system when communicating system events to the central station. The
system account code can be either 4 or 6 digits long. 4 or 6 digit account codes are selected with [383] option 2. Program a
6-digit code only when using the SIA reporting format. SIA uses this account code for all partitions and system events. All
other reporting formats use a 4-digit system account code to report system maintenance (e.g., low battery, zone fault) and
test transmission events. To program a 4-digit code, add FF to the last two digits.
- 122 -
Section 5: Programming
To assign a communications format, select a receiver (option [001]-[004]) then enter the 2-digit code corresponding to the
chosen format. For detailed descriptions of each format, see "Reporting codes" on page 250.
[377] Communication Variables
[001] – Swinger Shutdown
Alarms/Restores
This value defines the number of communication attempts made for alarm/restore events, per zone, before the zone goes
into swinger shutdown. Valid entries are 000 to 014. For CP-01, entries are from 001-006.
Once the programmed number of alarm/restore events have been communicated, no further alarm/restore events for the
zone are communicated until swinger shutdown is reset. The last restore event is not communicated until swinger is cleared.
- 123 -
Section 5: Programming
For example, if the swinger shutdown limit for zone alarms is set to [003], the cycle is as follows: alarm/restore, alarm/restore,
alarm...8 hours or arm/disarm...restore.
The bell output is not activated for alarms on zones that have exceeded the swinger shutdown counter limit. Swinger shut-
down on global zones log once to the system area.
CP-01 Note: Swinger shutdown resets on all partitions when any partition on the system is armed or disarmed, or every day at mid-
night. For CP-01, swinger shutdown is restored after 8 hours of inactivity.
Once reset, the alarm system communicates normally.
Note: The event buffer can follow swinger shutdown if enabled.
Tampers/Restores
This value defines the number of times the same system tamper event occurs before going into swinger shutdown. Valid
entries are 000 to 014.
Maintenance Troubles/Restores
This value defines the number of times the same system Maintenance (trouble) type event occurs before going into swinger
shutdown. Fire troubles follow the Maintenance Swinger Shutdown variable.
[002] – Communication Delays
Transmission Delay (seconds)
This value defines the delay before an alarm is transmitted.
The delay is for zones which have the Transmission Delay attribute enabled. Valid entries are from 000 to 255 seconds (0-
45 seconds for CP-01). Each partition shares the same active timer. If the delay is already active due to an alarm on a dif-
ferent partition, any new activity on another partition does not restart the communications delay timer.
Burglary verified events are postponed until after the transmission delay expires. When a valid disarming procedure is used
while the transmission delay is active, a communications canceled message is briefly displayed on the keypad when the
delay is canceled.
NA Note: For UL/ULC listed installations, the entry delay plus communication delay cannot exceed 45 seconds.
AC Failure Communication Delay (minutes or hours)
This value determines the delay before an AC failure or AC restore is reported. The AC failure or restore is still displayed
immediately. Valid entries are from 000 to 255 minutes/hours (max. 180 minutes for UL commercial installations). Selection
of minutes or hours for the delay is set in section "[382] Communicator Option 3" on page 127.
Note: If AC Failure Communications Delay is programmed as 000, the AC Failure Trouble reporting code is sent imme-
diately.
ULC Note: For ULC commercial fire monitoring, the setting shall be 180 minutes.
TLM Trouble Delay
Use this section to program the number of valid checks (3 second intervals) required before a telephone line trouble is gen-
erated. Valid entries are 000-255 for trouble annunciation and transmission delays of 3 to 765 Seconds (12.75 Minutes).
Wireless Zone Low Battery Transmission Delay (in days)
When a zone reports a low battery condition, the trouble is indicated immediately on the keypad, but the transmission to the
monitoring station is delayed by the number of days programmed in this section. If the low battery condition is not corrected
before the delay expires, the low battery condition is transmitted. The Low Battery Restore transmission is not delayed.
Delinquency Transmission Delay
The value in this section determines the period of time before a delinquency event is generated.
Delinquency delay is measured in days if using closing delinquency or hours if using activity delinquency as programmed in
section [311] option 6. Valid entries are [001]-[255] or [000] to disable.
Communications Cancel Window
After the transmission Delay expires and a zone alarm is transmitted, the communications cancel window begins.
If an access code is entered during this window, a reporting code is communicated and logged. If the window expires
without an access code entry or a code is entered after the window, the communications canceled event is not logged or
communicated.
Note: The cancel window does not start after an [F][M][P] key alarm.
- 124 -
Section 5: Programming
- 125 -
Section 5: Programming
3 – Pulse Dialing
ON: The alarm system dials telephone numbers using pulse (rotary) dialing.
OFF: The alarm system dials telephone numbers using DTMF (dual tone multi-frequency) touch-tone dialing.
4 – Pulse Dial after 5th Attempt
ON: If DTMF dialing is enabled, the alarm system dials telephone numbers using DTMF dialing for the first 4 attempts. If
unsuccessful, the alarm system switches to pulse (rotary) dialing for the remaining attempts.
OFF: If DTMF dialing is enabled, the alarm system dials telephone numbers using DTMF dialing for all dialing attempts.
5 – Parallel Communications
ON: Parallel communications is enabled. The alarm system attempts to communicate through all available receiver paths
(PSTN and IP (IP=Ethernet or Cellular) at the same time. Once acknowledgment is provided by any of the receivers, the
alarm system communicates the next event. If more than one receiver is configured for PSTN, the backup procedure
described below is followed.
OFF: Parallel communications is disabled. If receiver 1 fails, the alarm system attempts to communicate with the next avail-
able receiver (2-4) in sequence.
Note: When Parallel Communications is enabled it will override Communicator Backup Options, see "[384] Communicator
Backup Options" on page 128 for communicator backup programming.
6 – Alternate Dial
ON: After each failed dialing attempt, the communicator switches to the next backup receiver in the sequence:
l Receiver 2 backs up Receiver 1
l Receiver 3 backs up Receiver 2
l Receiver 4 backs up Receiver 3
This continues until communication is successful or the sequence has been repeated 5 times (depending on the number of
maximum dialing attempts). If all 5 attempts fail, an FTC trouble for the primary phone number is logged. All backup receivers
automatically use the same call directions and format as the primary receiver.
OFF: After 5 failed attempts to communicate with the primary receiver, the communicator switches to the next backup
receiver in the sequence and makes up to 5 more attempts. This continues until communication is successful or until all
backup receivers fail, at which point an FTC trouble for the primary number is logged.
7 – Reduced Dialing Attempts
ON: If a TLM trouble is present, The alarm system immediately attempts to call the backup receiver. This option only applies
to PSTN. Backup communications must be enabled. See option 5, Parallel Communications.
A minimum of two receivers should be enabled for this feature to operate as intended. This feature should not be enabled
unless the panel is programmed to use backup communication paths.
OFF: If a TLM trouble is present, the number of dialing attempts programmed shall be attempted before moving on to the
backup receiver.
8 – Activity Delinquency
ON: Inactivity on a partition for a programmed duration (section [377] option 002, Delinquency Transmission Delay) transmits
a Delinquency code to the central station. This option is designed to help monitor the elderly or disabled. The counter is
reset if zone activity is detected or if the system is armed. The Delinquency Transmission Delay is in hours.
Note: Delinquency code is not transmitted while Away armed. Activity on bypassed zones does not affect this timer.
OFF: The Delinquency reporting code is sent when the programmed number of days for delinquency (section [377]) expires
without the partition being Armed. Once the code is sent, the timer is not started again until the partition has been armed.
Each day programmed in the counter represents one day plus the time it takes for the partition to reach midnight. To disable
this feature, program 000 in section [377]>[002] option 5.
[381] Communicator Option 2
1 – Keypad Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the
keypad emits a series of 8 beeps to confirm to the occupant that the code was sent and received. Ringback occurs for each
successfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the
keypad does not sound ringback.
- 126 -
Section 5: Programming
2 – Bell Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the siren
emits a series of 6 squawks to confirm to the occupant that the code was sent and received. Ringback occurs for each suc-
cessfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the siren
does not sound ringback.
4 – Closing Confirmation Enabled/Disabled
ON: When a Closing reporting code is successfully transmitted to a programmed telephone number, the keypad emits a
series of 8 beeps to confirm to the occupant that the Closing Code was sent and received.
OFF: No keypad ringback is generated when a Closing reporting code is successfully transmitted.
8 – Communications Priority Enabled/Disabled
ON: Events follow the priority level indicated in ULC-S559 standard.
Concurrent event communications are prioritized in the following order (highest to lowest priority):
1. Fire Alarms
2. CO Alarm
3. Fire Supervisories
4. Fire Trouble
5. Monitoring (Medical, Panic or Security)
6. All others such as restorals for fire alarms, supervisories, troubles and monitoring.
OFF: Events are communicated in the order they occur.
ULC Note: Must be ON for ULC commercial fire monitoring listed installations.
[382] Communicator Option 3
1 – Reserved
2 – Walk Test Communications
ON: Zone alarms that occur during Walk Test are communicated if programmed to do so.
OFF: Zone alarms during Walk Test are not communicated. FMP key alarms are still communicated.
4 – Call Waiting Cancel
ON: The call waiting cancel string (See "[304] Call Waiting Cancel String" on page 116) is used on the first attempt to dial
each phone number. It is not used on any further dialing attempts.
OFF: The call waiting cancel string is not dialed.
5 – Interactive Communicator Enable/Disable
ON: The system communicates using the Alarm.com communicator. All related programming options, reporting, and super-
vision are enabled when programmed via PC-Link2.
OFF: The Alarm.com communicator and all associated programming functionality are disabled.
6 – AC Failure Communication Delay in Hours/Minutes
ON: The AC failure communication delay (section [377]>[002] option 2) is programmed in hours.
OFF: The AC failure communication delay is programmed in minutes.
8 – Tamper Limit
ON: When disarmed, the system only communicates module tampers. Zone tampers are not communicated.
OFF: When disarmed, the system communicates all tampers.
[383] Communicator Option 4
1 – Phone Number Account Code
ON: The account code communicated to the central station follows the phone number the event is programmed to com-
municate on (programmed in section "[310] Account Codes" on page 122):
l Receiver 1 all events will follow partition 1 account code
l Receiver 2 all events will follow partition 2 account code
- 127 -
Section 5: Programming
- 128 -
Section 5: Programming
DLS Programming
Downloading allows programming of the entire alarm system via a computer. All functions and features, changes and status,
such as trouble conditions and open zones, can be viewed or programmed by downloading.
The following downloading options are available:
l 6-hour window on start up: When the alarm system is powered up, downloading access is available for 6 hours. This
provides the option of downloading without having to complete any keypad programming.
l Double call method: The installer initiates a downloading window by calling the alarm system, hanging up, then call-
ing back again.
l User enabled DLS window: The user initiates a downloading window using [*][6][Master code][05]. This can be a 6-
hour window where the installer initiates and terminates downloading as many times as necessary, or it can be a 1-
hour, 1 use window.
l User initiated call-up: the user can initiate a downloading session using [*][6][Master Code][06].
l On-site downloading using USB: The installer connects a computer directly to the alarm system to perform on-site
downloading.
l Auto event buffer upload: The Event buffer is automatically uploaded to the DLS/SA computer when it reaches 75%
full.
Refer to the DLS/SA programming sections described below for configuration options.
[401] DLS/SA Options
1 – Double Call
ON: Calls for downloading or SA are answered if a successful double call routine is detected. Have the downloading com-
puter call the system and let the telephone line ring once or twice. After 1 or 2 rings, hang up. If called back within the dur-
ation of the double call timer (section [405]), the alarm system answers on the first ring.
OFF : Incoming calls are not answered using the double call routine unless the user enables the DLS window.
Note: This feature controls the DLS window for PSTN connections only.
2 – User Enables/Disables DLS
ON : The [*][6][Master Code][05] command enables a 6-hour window where, on power-up, downloading calls are answered
if a successful double call routine is detected.
OFF: The user cannot enable a downloading window.
3 – DLS CallBack
ON : When a downloading call is answered, both the computer and the alarm system hang up. The alarm system then calls
the downloading computer back using the [402] downloading telephone number and begins the DLS session.
Note: Disable this option if using more than one downloading computer.
OFF : After successful validation, the downloading computer gains immediate access to the alarm system.
4 – User Call-Up
ON : A single call attempt can be made to the downloading computer using [*][6][Master Code][06].
OFF: [*][6][Master Code][06] does not allow initiation of a downloading session.
6 – Panel Call-Up and Baud Rate
ON : When a DLS/SA session is initiated by the user, the initial header is sent at 300 baud.
OFF: When a DLS/SA session is initiated by the user, the initial header is sent at 110 baud. The alarm system will then
switch to 300 baud in order to receive the response from the DLS computer.
7 – Alternate Communicator DLS
ON: When this feature is enabled, the alarm system responds to DLS requests through the alternate communicator IP or cel-
lular paths at any time, regardless of whether the DLS window is active or not.
However, if a pre-defined number of consecutive incorrect DLS access codes is detected (See "Remote Lockout DLS" on
page 101) while trying to establish a connection, alternate communicator DLS access is locked out until the next hour roll-
over.
OFF: When this feature is disabled, the alarm system only responds to DLS requests through the alternate communicator IP
or cellular paths when the DLS window is active.
The DLS/SA window is active following a power up or if enabled using [*][6][maser code][05] (System Service/DLS).
- 129 -
Section 5: Programming
- 130 -
Section 5: Programming
The panel first communicates the Event Buffer 75% full event (if enabled) using either PSTN or IP and then performs the auto-
matic download.
OFF: The alarm system does not automatically call the downloading computer when the Event Buffer 75% full event occurs.
8 – DLS on Programming Change
ON: When the panel returns to the "Ready to Arm" screen after a programming change, 15 minutes later the alarm system
automatically connects to the downloading computer.
OFF: The alarm system does not automatically call the downloading computer when the system programming changes.
[002] Periodic DLS Days
This section is used to program the number of days between periodic DLS downloads. Valid entries are from 001 to 255
days.
[003] Periodic DLS Time
This section is used to program the time of day periodic DLS download takes place. Time is in 24-hour format and the default
is 00:00 (midnight).
[007] Delay Call Window
The delay call window is the upper and lower limits of a random time the panel may initiate a call up to a remote computer.
This feature shall be applied to Periodic DLS Days. When a value is entered in this section, the setting in Periodic DLS Time
(see the option above) is overridden. When 00:00 is entered in this field, the alarm system initiates a DLS call at the time pro-
grammed in Periodic DLS Time. Start and end times must be defined using 24-hour format (e.g., 13:30) and cannot span a
day (e.g., start time of 23:00 and an end time of 01:00).
Virtual Inputs
When using a third party integration, virtual zones can be mapped to configured system zones.
[560][001]-[032]
Assign corresponding 3 digit zone number to virtual input and then the virtual input can be controlled by a third party integ-
ration.
Schedule Programming
The sections described below are used for programming scheduled operating times for PGM command outputs 1-4.
[601]-[604] Programming Schedule 1-4
These sections are used to define schedules for PGM command outputs 1-4 operation. When a PGM is configured for timed
output operation, it activates at the programmed start time and will turn off after the programmed duration. For example, 5
seconds.
Each schedule contains 4 intervals, for Command Outputs 1-4. Within each interval, a start time and end time can be pro-
grammed for each day of the week. Holiday schedules 1-4 can also be selected. To enable the command output to follow a
schedule, program the command output in section [009] and then enter schedule 001 - 004 in section [011].
[101]-[102] Set Start Time/ End Time
Used to program the time of day the schedule interval begins and ends. (HH:MM). Valid entries are 0000-2359 and 9999.
The end time must be equal to or greater than the start time. 9999 is used when an interval needs to extend past 24 hours.
To do this, program the start time of the first interval then the end time with 9999. Program the start time of the second interval
as 9999 and the end time with the desired time when the output should deactivate. Select the day of the week the schedule
will end.
Note: If two intervals in a schedule are programmed with the same start time, the schedule follows the interval with the
longest end time.
[103] Days Assignment
Used to program the day of the week that the schedule interval starts and ends. Use the scroll keys to select a day then
toggle the option on. Multiple days of the week can be enabled.
[104] Holiday Assignment
Program PGMs to follow holiday schedule group 1-4. Select (Y) to enable. If all days of the week for an interval are disabled
(N), the schedule activates on the enabled holidays.
- 131 -
Section 5: Programming
Wireless Programming
[804] Wireless Programming
This programming section is used to enroll, program and delete wireless devices. Note that the HSM2HOSTx wireless trans-
ceiver or RF model keypad must be installed in order to enroll wireless devices.
Note: Refer to the HSM2HOST installation manual for information.
Communicator Programming
[850] Cellular Signal Strength
This section is used to view both the cellular signal strength and the radio technology in use.
Table 5-4 : Cellular Technology
Display Technology
GP GPRS
ED EDGE
HS HSPA
H+ HSPA
CD CDMA
EV EVDO
LT LTE
5 bars indicate maximum signal strength. 0 bars indicate the communicator is not connected to the network.
[851] Alternate Communicator Programming
The programming sections described in this document can be viewed at the keypad. To start programming, enter: [*] [8]
[installer code] [851] [section number], where section number is the 3-digit section number referenced in this section. The pro-
gramming worksheets at the end of this document can be used to record the new values when programming changes have
been made from the default values. Installers may review/record programming options at the panel keypad.
System Options
[001] Ethernet IP Address
Default (000.000.000.000)
Enter the IP address of the communicator. Ensure that the IP address is unique to the communicator on the local network.
- 132 -
Section 5: Programming
Format is 4 fields, each field is a 3 digit decimal number. Valid range: 000-255. If an IP address is programmed in this sec-
tion, the unit will operate with static IP (DHCP disabled). Sections [002] and [003] must also be programmed when using
static IP addresses.
Note: Default for this section is Dynamic Host Configuration Protocol (DHCP) enabled. When enabled, the DHCP server will
set values for: IP address [001], subnet mask [002], and gateway [003]. Programming an IP address in this section will dis-
able DHCP (Static IP).
[002] Ethernet IP Subnet Mask
Default (255.255.255.000)
Enter the Ethernet IP subnet mask of the communicator. Format is 4 fields, each field is 3 digits. Valid range: 000-255.
Note: If DHCP is enabled, the DHCP server will assign the subnet mask for this section and the programmed value will be
ignored.
[003] Ethernet Gateway IP Address
Default (000.000.000.000)
Enter the Ethernet gateway IP address of the communicator. The gateway IP address is required when a router is used on
the local network to reach the destination IP address specified in section [001]. Format is 4 fields, each field is a 3-digit
decimal number.
Valid range: 000-255.
Note: If DHCP is enabled, the DHCP server will assign the gateway IP address for this section and the programmed value
will be ignored.
[004] Receiver Supervision Interval
Default (135)
When receiver supervision is enabled (ON) in section [005] toggle option [3], the unit sends heartbeats to Ethernet receiver 1
or cellular receiver 1 to test the communications path. Use this section to set the interval time (in seconds) when heartbeats
will be sent to the receivers. Valid range 00000-65535 seconds. If the programmed value is less than 10 seconds, super-
vision is disabled.
[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised Default (OFF)
ON: Ethernet receiver 1 will be supervised and heartbeats will be sent to Ethernet receiver 1 based on the super-
vision interval programmed in section [004].
OFF: Ethernet receiver 1 will not be supervised. When disabled, heartbeat 1 is sent to the Ethernet receiver once
every hour, regardless of supervision type (heartbeat 1 or 2). The heartbeat is resent every 5 seconds until ACK is
received. If no event or heartbeat ACK is received after (receiver supervision interval + 75 seconds), supervisory
trouble is indicated.
Note: Ethernet receiver 2 can not be supervised.
[2] Cellular Receiver 3 Supervised Default (OFF)
ON: Cellular receiver 3 will be supervised and heartbeats will be sent to cellular receiver 1 based on the supervision
interval programmed in section [004]. If ACK to heartbeat is not received, it is retransmitted every 5 seconds. Failure
to ACK two consecutive heartbeats will reset the radio.
OFF: Cellular receiver 3 will not be supervised. When disabled, heartbeat is not sent to the receiver. Supervisory
trouble is indicated.
Note: Cellular receiver 2 can not be supervised.
[3] Supervision Type Default (OFF)
ON: Heartbeat 1 (commercial supervision). This supervision type is suitable for applications where swap detection is
required on the supervisory packet.
OFF: Heartbeat 2 (residential supervision). This supervision type is suitable for applications where supervision of the
communication path to the receiver is required (no swap detection).
Note: Commercial supervision is more data intensive than residential supervision and should only be used when required
to meet the approval for the installation.
[4] Primary Path Default (OFF)
ON: Cellular channel is the primary path. Ethernet channel is the secondary path.
- 133 -
Section 5: Programming
OFF: Ethernet channel is the primary path in a dual communicator. Cellular channel is the secondary path.
[6] Remote Firmware Upgrade Default (ON)
ON: The control panel firmware can be remotely upgraded using the Ethernet/cellular paths.
OFF: The control panel firmware can not be remotely upgraded. Local firmware upgrade is still possible.
[7] Alternate Test Transmissions Default (OFF).
ON: When the periodic test transmission interval occurs, the test transmission will alternate between being sent to the
primary and secondary receivers with each test transmission interval.
OFF: When the periodic test transmission interval occurs, the test transmission will be sent to the programmed receiv-
ers, based on the settings of the periodic test transmission reporting codes.
[8] Cellular Low Signal Trouble. Default (OFF)
This option masks the low signal trouble from generating cellular trouble.
ON: A cellular trouble event is generated when the radio signal level falls below threshold level (average CSQ level
is 4 or less).
OFF: A cellular trouble event is not generated when the radio signal level falls below threshold level (average CSQ
level is 4 or less).
[006] System Toggle Options 2
[1] Ethernet 1 receiver enabled. Default (ON)
ON: Ethernet receiver 1 is enabled.
OFF: Ethernet receiver 1 is disabled.
[2] Ethernet receiver 2 is enabled. Default (ON)
ON: Ethernet receiver 2 is enabled.
OFF: Ethernet receiver 2 is disabled.
[3] Reserved
[4] Cellular receiver 3 is enabled. Default (ON)
ON: Cellular receiver 3 is enabled.
OFF: Cellular receiver 3 is disabled.
[5] Cellular receiver 4 is enabled. Default (ON)
ON: Cellular receiver 4 is enabled.
OFF: Cellular receiver 4 is disabled.
[6] Reserved
[7] DLS Over Cellular. Default (ON).
ON: DLS is enabled on the cellular path.
OFF: DLS is disabled on the cellular path.
Note: Program this toggle as OFF to prevent DLS from using the cellular path.
Note: If this toggle is OFF, DLS sessions will occur on the Ethernet path only, regardless of the primary path set in section
[005] toggle option [4]. If it is ON, the communicator will connect to the primary path first for DLS and if the session fails, the
secondary path will be used.
[8] Network Trouble Suppression. Default (OFF).
ON: Cellular/Ethernet Supervisory troubles and restore signals follow delay timer as programmed in section [226].
OFF:Cellular/Ethernet Supervisory troubles and restore signals are sent immediately.
[007] DNS Server IP 1
Default (000.000.000.000)
Enter the IP address for DNS server 1. Format is 4 fields, each field is a 3-digit decimal. Valid range: 000-255.
Note: If no value is programmed and DHCP is used, the DHCP server will configure the address. If an address is pro-
grammed and DHCP is used, the programmed address will be used instead of the DHCP address.
[008] DNS Server IP 2
Default (000.000.000.000)
- 134 -
Section 5: Programming
Enter the IP address for DNS server 2. Format is 4 fields, each field is a 3-digit decimal. Valid range: 000-255.
Note: If no value is programmed and DHCP is used, the DHCP server will assign this value. If an address is programmed
and DHCP is used, the programmed address will be used instead of the DHCP address.
Programming Options
[010] System Toggle Options 3
[1] 2-Way Audio Over Cellular. Default (OFF)
ON: 2-Way Audio Over Cellular is enabled.
OFF: 2-Way Audio Over Cellular is disabled.
[2] Visual verification. Default (OFF)
ON: Visual verification is enabled.
OFF: Visual verification is disabled.
[3] Video On Demand. Default (OFF)
ON: Video On Demand is enabled.
OFF: Video On Demand is disabled.
[4] Receiver Group. Default (OFF)
ON: Receiver Group is enabled.
OFF: Receiver Group is disabled.
[5] Reserved.
[6] Reserved.
[7] Reserved.
[8] Reserved.
[012] DLS Incoming Port
Default (03062)
The DLS incoming local port (listening port) is the port DLS IV will use when connecting to the communicator. If a router or
gateway is used, it must be programmed with a transmission control protocol (TCP) port forward for this port to the com-
municator module IP address. Valid range: 00000 - 65535.
[013] DLS Outgoing Port
Default (03066)
The DLS outgoing port is used for outgoing sessions to DLS IV after an SMS request has been sent to the communicator.
Use this section to set the value of the local outgoing port. The value must be changed if the communicator is located behind
a firewall and must be assigned a particular port number, as determined by the network administrator. In most cases, chan-
ging the default value or configuring the firewall with this port is not required.
Valid range: 00000-65535.
Note: If section [006] toggle option [7] is ON, DLS will use the primary path for session. If section [006] toggle option [7] is
OFF, DLS will use the Ethernet path, if available.
[015] DLS Call-Up IP
Default (000.000.000.000)
[016] DLS Call-Up Port
Default (00000)
Valid range: 00000-65535.
[018] Receiver Group Pair
Default (0000)
Use the Receiver Group Pair to add two receivers to the receiver group in order to select which two receivers get the sim-
ulations event and visual verification communications. Use this option with the receiver group enable option [851][010] bit 4.
You can use any two available receiver paths. Valid range: 0000-FFFF.
[020] Time Zone
Default (00)
- 135 -
Section 5: Programming
Refer tosection [024] 5 Real-Time Clock for more details. Use Column 2 (Offset Hours) to find the local Time Zone. Record
the two digit HEX value from Column 1 (HEX Value) on the same row. Program this HEX value for the Time Zone. Valid
range is 00 - FF.
Table 5-5 World Wide Time Zone
- 136 -
Section 5: Programming
- 137 -
Section 5: Programming
Program 00 to disable this event transmission or FF to enable. See system test options (previous page) for details on set-
tings.
[028] Cellular Receiver 3 Test Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See system test options (previous page) for details on set-
tings.
[029] Cellular Receiver 4 Test Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See system test options (previous page) for details on set-
tings.
Note: The time interval (in minutes) between periodic tests is programmed in section [125] (Ethernet) and section [225] (cel-
lular).
[030] FTC Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when an FTC Trouble on the system
restores.
[095] SA Incoming Local Port
Default (03092)
Valid range: 00000 - 65535
[096] SA Outgoing Local Port
Default (03093)
Valid range: 00000 - 65535
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used when trans-
mitting heartbeat signals to the central station receiver. Signals received from the panel will use the control panel account
number. Valid range: 0000000001-FFFFFFFFFE.
Note: If Ethernet receiver 1 and cellular receiver 1 are programmed as the same receiver (IP and port number are identical),
Ethernet receiver 1 account code will be used.
[102] Ethernet Receiver 1 DNIS
Default (000000)
The Dialed Number Information Service (DNIS) is used in addition to the account code to identify the communicator module
at the central station. Valid range: 000000 - 099999. Value is entered as a leading 0 followed by the 5 digit DNIS. Format is
Binary Coded Decimal (BCD).
Note: Each Ethernet/cellular receiver must be programmed with a unique DNIS.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
The default address enables the communicator to operate in Unattended Mode.
Unattended mode is used when a receiver is not available and the unit is required to perform DLS sessions. Typically used
where the customer programs the control panel daily due to access control and still wants to receive alarms without buying
extra hardware (receiver) or software.
Note: When a valid IP address has been programmed, Ethernet receiver 1 is enabled and will communicate events over the
Ethernet channel.
Ethernet receiver 1 and cellular receiver 1 may be configured to communicate to the same central station receiver. To con-
figure the device to operate using this common receiver mode functionality, program Ethernet receiver 1 and cellular
receiver 1, IP address and port number with identical values.
Note: When operating in common receiver mode, Ethernet receiver 1 account code will be used for Ethernet and cellular.
- 138 -
Section 5: Programming
- 139 -
Section 5: Programming
- 140 -
Section 5: Programming
- 141 -
Section 5: Programming
Some network carriers require login credentials when connecting to an APN. Program the login Password in this Section.
Enter the Cellular Login Password with up to 32 ASCII characters.
[224] Cellular Test Transmission Time of Day
Default (9999)
Enter a 4 digit value using the 24-hour clock format (HHMM) to set the test transmission time of day. Valid range: 00-23 for
the hours (HH) and 00-59 for the minutes (MM).
Note: To disable the test transmission time of day enter 9999 or FFFF in this section.
The internal date and time will be automatically programmed by the primary receiver only.
[225] Cellular Test Transmission Cycle
Default (000000)
This value represents the interval in between test transmissions in minutes. Valid range: 000000 - 999999 minutes. Once the
unit has sent the initial periodic test transmission, all future test transmissions will be offset by the programmed number of
minutes. See sections [026] - [029].
Table 5-7 Cellular Test Transmission Interval
Test Transmission Interval Daily Weekly Monthly
Programmed Minutes 001440 010080 043200
Note: Minimum value is 000005 minutes. Programming an interval that is less than 5 minutes will disable test transmission.
[226] Network Trouble Delay Timer
Default (015)
This option is used to program the delay, in minutes, for reporting a cellular trouble delay. Valid entries are 000 - 255. When
this section is programmed as 00, Cellular, Ethernet and Supervision troubles are not communicated.
[227] Voice Call Timeout
Default (000) Valid entries are 000 - 255.
[228] Voice Call Back Time
Default (010) Valid entries are 000 - 255.
[229] Voice Call Back Number
Default ( ) 32 digit phone number.
Valide entries:: 0000000000000001 to FFFFFFFFFFFFFFFE
[422] Integration Identification Number
This section will display the unique 12-digit number assigned to this control panel for the identification when integrated with
third party applications.
[423]Session 1 Integration Access Code
Default (12345678123456781234567812345678) Valid Range is 0000000000000000 - FFFFFFFFFFFFFFFF.
This section is a programmable 32-digit number used for initialization with third party applications.
Note: If integrating with a third party application, this Access Code field must be programmed to a unique number in oder to
secure the connection with 128 bit encryption.
[424] Session 1 SMS Label
Default (11111111)
This section is used to identify the integration session with a third party integrator.
[425] Session 1 Integration Toggle Options 2
The toggle options in this section are used to enable and configure the path used for integration with third party applications.
[1] Integration over USB Default (OFF)
[2] Integration over Cellular Default (OFF)
[3] Integration over Ethernet Default (OFF)
[4]ITv2 Integration Protocol Default (ON)
- 142 -
Section 5: Programming
- 143 -
Section 5: Programming
Description of Response
Response Code Code Corresponding Action
Bad File
00 Version check failed Contact DSC Tech Support, described the
01 Image type mismatch action attempted with the system and supply
them with the Response Code in Section
02 Device type mismatch [983].
03 Hardware type mismatch
04 General variant mismatch
05 Firmware header wrong length
Panel is Busy
20 System update pending - Disarm the panel to continue with system
panel is armed firmware update process.
21 System update pending -AC Resolve the AC trouble to continue with sys-
trouble (Any AC trouble; tem firmware update process.
device/module)
22 System update pending -low Resolve the low battery trouble to continue
battery (Any low battery with system firmware update process.
trouble; device/module)
25 System update pending - com- Retry in a few minutes; if issue persists, con-
munication in progress tact DSC Tech Support.
Firmware Update Sequence Change
A0 System firmware update suc- None
cessful
A1 System firmware update fail- At least one module was not updated. Use
ure DLS to reapply the firmware to the module
not updated.
A2 System firmware update fail- At least one module was not responding dur-
ure - module not found ing firmware update. Ensure all modules
enrolled are physically connected and
powered up.
AA Device firmware transfer begin None
- 144 -
Section 5: Programming
Description of Response
Response Code Code Corresponding Action
AB Device firmware module None
update begin
AC General device firmware trans- Contact DSC Tech Support, describe the
fer failure action attempted with the system and supply
them with the Response Code in Section
[983].
Firmware Update Status
C0 System ready to update None
C1 System update cancel request The system has received an update cancel
received request from DLS.
C2 System update begin None
Firmware Download Request Reject
E0 Reserved
E1
E2
E3
E4
E5 Remote firmware update dis- Enable remote firmware update in the com-
abled municator in order to perform remote system
firmware update.
Local Status Update States
FE Firmware file empty No action required. Communicator currently
does not have any firmware files.
FD Firmware download in pro- No action required. Communicator is cur-
gress rently downloading firmware.
The table displays firmware update indicator codes and meaning of each code. The updates can be made from com-
municator. The communicator can update firmware of the panel and also of the communicator itself. This section does not
provide specific details such as if the image is still stored or erased due to the cancellation code.
[984] - Communicator Status
The communicator status sections provide the installer with the status of the communicator’s functionality, operational read-
iness, and failures.
The communicator status is displayed as a 6-digit hexadecimal code. The code ranges between 00000F and 2220CF,
though not all numbers in this range are assigned. Each of the 6 digits represents a status or trouble indicator as below:
1. Digits 1 and 2: Signal strength indicators display the presence/strength of cellular radio.
2. Digit 3: Network Indicator, indicates the operational status of the network.
3. Digits 4 and 5: Trouble Indicator displays the type of issue on the communicator or modules associated with and con-
nected to the communicator. See Table 8 on page 17 for a listing of possible values.
4. Digit 6: Reserved, displays as ‘F’ or ‘-’.
For example, a value of 11002F means:
11- Signal strength is excellent
0 - No network issues
02 - Panel supervision trouble with the communicator
The status code for the radio signal strength, its typical troubles, possible causes and troubleshooting instructions is dis-
played in the following table.
- 145 -
Section 5: Programming
- 146 -
Section 5: Programming
- 147 -
Section 5: Programming
Systems Information
[900] System Information
[000] – Control Panel Version
This read-only section contains the model number, software version, hardware revision and serial number of the alarm con-
troller. For example, an entry of 1234 is read as version 12.34.
[001]-[524] – Module Information
This read-only section is used to view the model number, software version, and hardware revision information of the mod-
ules enrolled on the alarm system.
To view information for a specific module, scroll to the corresponding section:
[001]-[016] keypads
[101]-[130] 8-zone expansion module
[201]-[216] 8-output expansion module
[301] -[330] 8 zone expansion module
[460] Alternate Communicator
[461] HSM2Host module
[481] 2 Way Audio Module
[501]-[504] 1A power supply module
[521]-[524] high-current output modules 1-4
[551]-[554] 3A power supply
[601]-[608] Corbus repeater
[901] Installer Walk Test Mode Enable/Disable
This mode tests the operation of each detector in the system. Enter section [901] to initiate a walk test. While in Walk Test
mode, the Ready, Armed, and Trouble LED's on the keypad flash to indicate that the test is active. When a zone is tripped
during the test, a 2-second tone sounds on all system keypads to indicate that the zone is working correctly.
- 148 -
Section 5: Programming
After 10 minutes without zone activity, the alarm system emits 5 beeps every 10 seconds from all keypads. After another 5
minutes of inactivity, Walk Test terminates automatically.
To manually exit walk test mode, enter [901] again.
Module Programming
Use this section to add, remove and confirm the following modules:
l Keypads see "Compatible devices" on page 8
l 8-zone expander module (HSM2108)
l 8-output expander module (HSM2208)
l Power supply (HSM2300)
l 4-output power supply (HSM2204)
l Wireless transceiver (HSM2HOSTx)
l Audio Verification Module (HSM2955)
l 8 zone Expansion Module (HSM3408)
l Power Supply Module (HSM3350)
l Corbus Repeater Module (HSM3204CX)
Once added, modules are supervised by the system.
[902] Add/Remove Modules
Modules can be enrolled automatically our manually. In either case, the serial number of the device is used as an identifier.
Select one of the enrollment options described below.
[000] – Auto Enroll Modules
When this mode is selected, the alarm system automatically enrolls all modules connected to the Corbus. The total number
of modules currently enrolled are displayed on the keypad.
l Enter sub-section [000] to begin auto enrollment of all new modules. The auto enroll screen will show the following:
l KP = Number of keypad type modules
l IO = Number of zone and output type modules
l M = Number of other type modules
Devices are assigned to the next available slot. The slot assignment can be modified using subsections [002] and
[003].
[001] – Enroll Modules
To enroll modules individually:
1. Enter programming section [902][001].
2. When prompted, key in the serial number of the module found on the PCB. An error tone is sounded if an invalid serial
number is used.
3. To cancel enrollment of a module, press [#].
[002] – Module Slot Assignment
This section is used to change the slot number a module is enrolled in. To change the slot number:
1. Enter programming section [902][002].
2. Key in the serial number of the module.
3. When prompted, key in the new two-digit slot number. The previous slot assignment is replaced with the new one. An
error tone sounds if an invalid slot number is keyed in.
[003] – Edit Module Slot Assignment
Like [002], this section is also used to change the slot number of a module. With this option, however, the serial number is
not required. To change the slot number:
1. Enter programming section [902][002].
2. Use the scroll keys to locate the module then press [*] to select.
3. Key in the new two-digit slot number. The previous slot assignment is replaced with the new one. An error tone sounds if
an invalid slot number is keyed in.
- 149 -
Section 5: Programming
Deleting Modules
The following sections are used to remove modules from the system:
[101] – Keypads
[102] – 8-zone Expander Modules
[103] – 8-output Expander Modules
[104] – 8 zone HSM3408 Expander Module
[106] – HSM2Host
[108] – HSM2955
[109] – Power Supply
[110] – 4 High Current Output
[111] – 3A Power Supply Module
[112] – Corbus Repeater Module
1. After entering section [902], scroll to the module type you want to delete (101-112).
2. Press [*] to select the module type then scroll to the specific module you want to delete.
3. Press [*] to select the module then, when prompted, press [*] again to delete.
[903] Confirm Module
The following sections are used to confirm enrollment of individual modules, their serial and slot numbers, and to locate
them physically:
[000] – View All Modules
[101] – Keypads
[102] – 8-zone Expander Modules
[103] – 8-output Expander Modules
[104] – 8 I/O Expander Module
[106] – HSM2Host
[108] – HSM2955
[109] – Power Supply
[110] – 4 High Current Output
[111] – 3A Power Supply Module
[113] – Corbus Repeater Module
To confirm a module:
1. Enter section [903]>[000] to view all enrolled modules or scroll to the module type you want to confirm (101-113).
2. Press [*] to select the module type then scroll to the specific module you want to confirm. Press [*] to enter Confirmation
mode. The module’s serial number and slot number are displayed on the keypad and the status LEDs on the device flash.
This continues until confirmation mode for the device is exited via the [#] key.
Note: Keypad Blanking (section [016], option 3) must be disabled to confirm keypads.
Testing
[904] Wireless Placement Test
This test is used to determine RF signal status for wireless devices and can be performed at a system keypad or at the indi-
vidual device. These instructions pertain to testing at the keypad. For instructions on placement testing at the device, refer to
the installation sheet included with the wireless equipment.
The following test modes are available:
[001]-[248] Placement Test Zones 1-248
Test wireless devices individually by zone.
[521]-[528] Placement Test Repeaters 1-8
Test each enrolled wireless repeater.
- 150 -
Section 5: Programming
[911] Diagnostics
This Diagnostics feature provides a live measurement of voltage, current, and battery condition for the alarm panel and
devices through the system keypad. This information can be used in place of a multimeter to troubleshoot panel and module
troubles. To view specific measurements, scroll to the corresponding section:
[000] Panel
[001] DC input voltage/current
[002] Battery voltage, battery charge voltage/current, battery discharge voltage
[003] Aux supply voltage/current
[004] Bus supply voltage/current
[005] Main bell voltage/current
[006] Zone resistance-Zone 1-8
[001]-[130] Keypad 1-16
[001] Bus supply voltage
[002] I/O 1-Zone XXX resistance, where XXX is the zone number
[101]-[115] HSM2108 Zone expander
[001] Bus supply voltage
[002] Aux supply voltage/current
[003] I/O 1-8 resistance - Zones 1-8
[301]-[330] 8 I/O expander
[001] Zone resistance - Zones 1-8
[501]-[504] 1 A Power supply
[001] Battery voltage/current
[521]-[524] 4 Output 1 A power supply
[001] Battery voltage/current
[551]-[554] 3 A power supply
[001] DC input
[002] Battery voltage, battery charge voltage/current, battery discharge current
- 151 -
Section 5: Programming
Defaults
[989] Default Master Code
This section is used to default the master code to the factory default. After entering this section, key in the installer code then
989.
[989][installer code][989] or [*].
- 152 -
Section 5: Programming
EN
Note: Feature is only available for models.
[990] Installer Lockout Enable/Disable
When this option is enabled, an installer can not perform a hardware default; attempts to do so are logged to the event buf-
fer.
An audible indication of installer lockout is provided when powering up the alarm system (the phone line relay clicks rap-
idly). Software default changes can still be made while installer lockout is enabled.
[990][installer code][990] or [*].
[991] Default Keypads
This programming option is used to return system keypads to factory default settings.
[901]- [916] – Default Keypads 1-16
This section resets individual keypads to factory defaults. After entering this section, select the keypad to default, key in the
installer code then 991 (or press [*]).
[999] – Default All Keypads
This section resets all system keypads to factory defaults. After entering this section, key in the installer code then (*) or 991.
[996] Default Wireless Receiver
This section resets the wireless receiver (HSM2HOSTx) to factory defaults. Enter [996][installer code][996 or *].
[998] Default HSM2955
This section resets the audio module (HSM2955) to factory defaults. Enter [998][installer code][998 or *].
[999] Default System
This section resets the alarm controller to factory defaults. Enter [999][installer code][999 or *].
- 153 -
Section 6: Programming Worksheets
- 154 -
Section 6: Programming Worksheets
- 155 -
Section 6: Programming Worksheets
- 156 -
Section 6: Programming Worksheets
- 157 -
Section 6: Programming Worksheets
- 158 -
Section 6: Programming Worksheets
810 – HSM2204 High-Current Output Supply Label 001 – High-Current Output Supply 1 Label:
(1 X 14 Characters) 002 – High-Current Output Supply 2 Label:
Description on page 78 003 – High-Current Output Supply 3 Label:
004 – High-Current Output Supply 4 Label:
811 – HSM3350 3A Power Supply Label 001 – 3A Power Supply 1 Label:
(1 X 14 Characters) 002 – 3A Power Supply 2 Label:
003 – 3A Power Supply 3 Label:
004 – 3A Power Supply 4 Label:
- 159 -
Section 6: Programming Worksheets
Zone Attributes
1 – Bell Audible 5 –Force Arm 9 – Normally Closed EOL
13 - Zone 2-way Audio Activation
2 – Bell Steady 6 – Swinger Shutdown 10 – Single EOL
14 - Hold Up Verification
3 – Chime Function 7 – Transmission Delay 11 – Double EOL
15 - Triple EOL
4 – Bypass Enabled 8 - Burglary Verification 12 – Fast/Normal Loop Response
- 160 -
Section 6: Programming Worksheets
Zone Type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
000 Null Zone
- 161 -
Section 6: Programming Worksheets
- 162 -
Section 6: Programming Worksheets
Exit Delay:
Settle Delay:
003 – Partition 3 Timer Entry Delay 1:
See partition 1 for defaults Entry Delay 2:
Exit Delay:
Settle Delay:
004 – Partition 4 Timer Entry Delay 1:
See partition 1 for defaults Entry Delay 2:
Exit Delay:
Settle Delay:
005 – Partition 5 Timer Entry Delay 1:
See partition 1 for defaults Entry Delay 2:
Exit Delay:
Settle Delay:
006 – Partition 6 Timer Entry Delay 1:
See partition 1 for defaults Entry Delay 2:
Exit Delay:
Settle Delay:
007 – Partition 7 Timer Entry Delay 1:
See partition 1 for defaults Entry Delay 2:
Exit Delay:
Settle Delay:
008 – Partition 8 Timer Entry Delay 1:
See partition 1 for defaults Entry Delay 2:
Exit Delay:
Settle Delay
900 - Bell Delay Partition Mask 12345678
Default: All partitions on YYYYYYY
- 163 -
Section 6: Programming Worksheets
- 164 -
Section 6: Programming Worksheets
- 165 -
Section 6: Programming Worksheets
- 166 -
Section 6: Programming Worksheets
- 167 -
Section 6: Programming Worksheets
- 168 -
Section 6: Programming Worksheets
- 169 -
Section 6: Programming Worksheets
- 170 -
Section 6: Programming Worksheets
- 171 -
Section 6: Programming Worksheets
- 172 -
Section 6: Programming Worksheets
- 173 -
Section 6: Programming Worksheets
- 174 -
Section 6: Programming Worksheets
- 175 -
Section 6: Programming Worksheets
- 176 -
Section 6: Programming Worksheets
- 177 -
Section 6: Programming Worksheets
- 178 -
Section 6: Programming Worksheets
- 179 -
Section 6: Programming Worksheets
- 180 -
Section 6: Programming Worksheets
- 181 -
Section 6: Programming Worksheets
- 182 -
Section 6: Programming Worksheets
- 183 -
Section 6: Programming Worksheets
- 184 -
Section 6: Programming Worksheets
- 185 -
Section 6: Programming Worksheets
- 186 -
Section 6: Programming Worksheets
Keypad Lockout: EN
Note: For installations maximum programmed lockout of 10
attempts.
- 187 -
Section 6: Programming Worksheets
EN R 2 – DEOL/SEOL
- 188 -
Section 6: Programming Worksheets
o 3 – Keypad Blanking
EN R 3 – Keypad Blanking
R 5 – Keypad Backlighting
o6 – Power Save Mode
o 7 – Bypass Display When Armed
o8 – Keypad Tampers Enabled
EN R 2 – Chime on Closing
- 189 -
Section 6: Programming Worksheets
o 2 – Latching Troubles
EN R 2 – Latching Troubles
o3 – Reserved
o 4 – Reserved
o 5 – Audible Bus Fault
o 6 – Duress Code
R7 – Temperature in Celsius
o 8 – Reset After Zone Activation
EN R 2 – EU Entry Procedure
EN o 1 – Trouble Display
o 3 – Reserved
o 4 – Ready Display
o 5 – PGM Keypad Blanking
o 6 – Armed Display
o 7 – Open Cancels Arming
- 190 -
Section 6: Programming Worksheets
o 3 – Reserved
UL R 2 – Force Dial
- 191 -
Section 6: Programming Worksheets
o5 – ID Tone
o 6 – Tone Generated-2100Hz
o 7 – DLS Window
o 8 – FTC Audible Bell
6.9 Auto-Arm_Disarm
- 192 -
Section 6: Programming Worksheets
- 193 -
Section 6: Programming Worksheets
- 194 -
Section 6: Programming Worksheets
- 195 -
Section 6: Programming Worksheets
- 196 -
Section 6: Programming Worksheets
- 197 -
Section 6: Programming Worksheets
- 198 -
Section 6: Programming Worksheets
6.11 Communications
- 199 -
Section 6: Programming Worksheets
- 200 -
Section 6: Programming Worksheets
- 201 -
Section 6: Programming Worksheets
- 202 -
Section 6: Programming Worksheets
- 203 -
Section 6: Programming Worksheets
- 204 -
Section 6: Programming Worksheets
NA
o 1 – Installer Lead IN
o 2 – Installer Lead OUT
o 3 – DLS Lead IN
o 4 – DLS Lead OUT
o 5 – SA Lead IN
o 6 – SA Lead OUT
o 7 – Event Buffer 75% Full
312 – Maintenance Events 2
EN
o 1 – Installer Lead IN
o 2 – Installer Lead OUT
o 3 – DLS Lead IN
o 4 – DLS Lead OUT
o 5 – SA Lead IN
R 6 – SA Lead OUT
R 7 – Event Buffer 75% Full
R 1 – Firmware Update Begin
313 – Maintenance Events 3 R 2 – Firmware Update Successful
R 3 – Firmware Update Fail
R 1 – Gas Trouble
R 2 – Gas Trouble Restore
R 3 – Heat Trouble
314 – Maintenance Events 4 R 4 – Heat Trouble Restore
R 5 – Freeze Trouble
R 6 – Freeze Trouble Restore
R 7 – Probe Disconnected Trouble
R 8 – Probe Disconnected Restore
R2 – Receiver 1 FTC Restore
R4 – Receiver 2 FTC Restore
321 – Receiver Events
R6 – Receiver 3 FTC Restore
R8 – Receiver 4 FTC Restore
R1 – Module AC Trouble
R2 – Module AC Trouble Restore
R 3 – Module Battery Trouble
R 4 – Module Battery Trouble Restore
331 – Module Events 1
R 5 – Module Battery Absent
R 6 – Module Battery Absent Restore
R 7 – Module Power Unit Fail
R 8 – Module Power Unit Fail Restore
- 205 -
Section 6: Programming Worksheets
- 206 -
Section 6: Programming Worksheets
- 207 -
Section 6: Programming Worksheets
- 208 -
Section 6: Programming Worksheets
EN
Default:002 checks
Wireless Zone Low Bat. Transmission Delay
Default: 0000 days/hours
Delinquency Transmission Cycle Delay
Default: 030 days/hours
Communications Cancel Window
Default: 000 minutes
CP-01 Default: 005 minutes
NA 6 – o Alternate Dial
EN 6 – R Alternate Dial
- 209 -
Section 6: Programming Worksheets
8 – o Activity Delinquency
- 210 -
Section 6: Programming Worksheets
- 211 -
Section 6: Programming Worksheets
- 212 -
Section 6: Programming Worksheets
06 – o Friday
07 – o Saturday
- 213 -
Section 6: Programming Worksheets
- 214 -
Section 6: Programming Worksheets
06 – o Friday
07 – o Saturday
Interval 2 201 – Start Time: 202 – End Time:
203 – Days Assignment: 204 – Holiday Assignment:
(4- digit decimal) 01 – o Sunday o Holiday 1
HH:MM to HH:MM 02 – o Monday o Holiday 2
Default: 0000 03 – o Tuesday o Holiday 3
04 – o Wednesday o Holiday 4
05 – o Thursday
06 – o Friday
07 – o Saturday
Interval 3 301 – Start Time: 302 – End Time:
303 – Days Assignment: 304 – Holiday Assignment:
(4- digit decimal) 01 – o Sunday o Holiday 1
HH:MM to HH:MM 02 – o Monday o Holiday 2
Default: 0000 03 – o Tuesday o Holiday 3
04 – o Wednesday o Holiday 4
05 – o Thursday
06 – o Friday
07 – o Saturday
Interval 4 401 – Start Time: 402 – End Time:
403 – Days Assignment: 404 – Holiday Assignment:
(4- digit decimal) 01 – o Sunday o Holiday 1
HH:MM to HH:MM 02 – o Monday o Holiday 2
Default: 0000 03 – o Tuesday o Holiday 3
04 – o Wednesday o Holiday 4
05 – o Thursday
06 – o Friday
07 – o Saturday
- 215 -
Section 6: Programming Worksheets
- 216 -
Section 6: Programming Worksheets
- 217 -
Section 6: Programming Worksheets
- 218 -
Section 6: Programming Worksheets
- 219 -
Section 6: Programming Worksheets
- 220 -
Section 6: Programming Worksheets
- 221 -
Section 6: Programming Worksheets
- 222 -
Section 6: Programming Worksheets
[802]
1 - o Tampers
2 - o Future Use
3 - R [A] Key Alarm
4 - R [P] Key Alarm
600 2-Way Audio Trigger Option 1
5 - R Duress Alarm
6 - R Opening After Alarm
7 - o Future Use
8 - o Zone Supervision Alarm
1 - o Future Use
2 - R Listen to all zones / Listen to zones in alarm
3 - o Future Use
4 - o Siren Active During 2-Way Audio
603 2-Way Audio Control Option 1
5 - o Hang-Up Auto Detection
6 - o User Call-In
7 - o For Future Use
8 - R 2-Way Audio Initiated by CS
1 - R Audio Capture Enable
2 - o Erase on FTC
3 - o Future Use
4 - o Future Use
605 Record Options
5 - o Future Use
6 - o Future Use
7 - o Future Use
8 - o Future Use
1 - o Audio Station 1 Record
2 - o Audio Station 2 Record
3 - o Audio Station 3 Record
4 - o Audio Station 4 Record
606 Audio Station Record Control Option 1
5 - o Future Use
6 - o Future Use
7 - o Future Use
8 - o Future Use
Call Back / Recovery Window Duration:
610 2 digit entry
Default: 05 minutes
Call Back Acknowledge code:
611 6-digit entry
Default: 999999
Answering Machine Bypass:
612 2-digit entry
Default: 00
Double Call Timer:
613 2-digit entry
Default: 30
- 223 -
Section 6: Programming Worksheets
- 224 -
Section 6: Programming Worksheets
- 225 -
Section 6: Programming Worksheets
- 226 -
Section 6: Programming Worksheets
- 227 -
Section 6: Programming Worksheets
- 228 -
Section 6: Programming Worksheets
- 229 -
Section 6: Programming Worksheets
o6 - Reserved
o7 - Reserved
o8 - Reserved
[427] Session 1 Interactive Polling Interval
Default (00010)
Valid range: 00000- 65535 seconds
[428] Session 1 Integration Server IP
Default (000.000.000.000)
[429] Session 1 Integration Notification Port
Default (00372)
Valid range: 00000- 65535
[430] Session 1 Integration Polling Port
Default (03073)
Valid range: 00000- 65535
[431] Session 1 Integration Server DNS
32 ASCII characters
[432] Session 1 Integration Outgoing Port
Default (03070)
Valid range: 00000- 65535
[433] Session 1 Integration Incoming Port
Default (03071)
Valid range: 00000- 65535
Integration sessions 2-4
[450] - [460] Repeats [423] - [433] for Session 2
[477] - [487] Repeats [423] - [433] for Session 3
[504] - [514] Repeats [423] - [433] for Session 4
Notification controls
R1 – Alarm and Alarm Restore
[691] Session 1 Notification Control
Notifications
R2 –Tamper and Tamper Restore
Notifications
R3 – Arming and Disarming Notifications
R4 – Trouble and Trouble Restore
Notifications
R5 – Test Transmission Notifications
R6 – Reserved
R7 – Reserved
R8 –Reserved
R1 – Alarm and Alarm Restore
[692] Session 2 Notification Control
Notifications
R2 –Tamper and Tamper Restore
Notifications
R3 – Arming and Disarming Notifications
R4 – Trouble and Trouble Restore
Notifications
- 230 -
Section 6: Programming Worksheets
- 231 -
Section 6: Programming Worksheets
- 232 -
Section 6: Programming Worksheets
00 - Null Key
02 - Instant Stay Arm 17 - Arm Interior 37 - Time/Date Programming
03 - Stay Arm 21 - Command Output 1 39 - Trouble Display
04 - Away Arm 22 - Command Output 2 40 - Alarm Memory
05 - [*][9]No Entry Arm 23 - Command Output 3 61 - Partition Select 1
06 - Chime On/Off 24 - Command Output 4 62 - Partition Select 2
07 - System Test 29 - Bypass Group Recall 63 - Partition Select 3
09 - Night Arm 31 - Local PGM Active 64 - Partition Select 4
12 - Global Stay Arm 32 - Bypass Mode 65 - Partition Select 5
13 - Global Away Arm 33 - Bypass Recall 66 - Partition Select 6
14 - Global Disarming 34 - User Programming 67 - Partition Select 7
15 - Temperature 35 - User Functions 68 - Partition Select 8
16 - Quick Exit
011 – Keypad I/O (Zone number or output number; 3-digit decimal; Default: 000):
012 – Local PGM Output Timer Pulse Time Minutes (Default: 00 minutes)
Pulse Time Seconds (Default: 05 seconds)
021 – Keypad Option 1 1 – R[F] Key Enabled
For systems compliant with EN50131-1 and
EN
EN50131-3 Section [021]: options 1 and 2
must be OFF.
2 – R R[M] Key Enabled
2-digit decimal
3 – R R[P] Key Enabled
4 – R Display Code or X’s
022 – Keypad Option 2 1 – R Local Clock Display
2 – o Local Clock 24-Hour
3 – R Auto Alarm Scroll
5 – R Power LED
6 – R Power LED AC Present
7 – R Alarms Displayed While Armed
8 – R Auto Scroll Open Zones
023 – Keypad Option 3 1 – o Armed LED Power Save
2 – R Keypad Status Shows Arm Mode
3 – o 5th Terminal is PGM Output/Zone Input
4 – o Prox Tag Arm/Disarm
7 – o Local Display of Temperature
8 – o Low Temperature Warning
030 – LCD Message:
031 – Downloaded LCD Message Duration (3-digit decimal; 000-255; Default: 000):
041 – Indoor Temperature Zone Entry (3-digit decimal; 000-248; Default: 000):
042 – Outdoor Temperature Zone Entry (3-digit decimal; 000-248; Default: 000):
101-228 – Door Chime Sound: 00 – o Disabled
01 – R 6 Beeps
02 – o Bing Bong
- 233 -
Section 6: Programming Worksheets
03 – o Ding Dong
04 – o Alarm Tone
05 – o Zone Name
Door Chime Zone Assignment:
1 _____ 19 ____ 37 ____ 55 ____ 73 ____ 91 ____ 109____ 127____ 145____ 163____ 181 ____199 ____ 217 ____235 ____
2 _____ 20 ____ 38 ____ 56 ____ 74 ____ 92 ____ 110____ 128____ 146____ 164____ 182 ____200 ____ 218 ____236 ____
3 _____ 21 ____ 39 ____ 57 ____ 75 ____ 93 ____ 111____ 129____ 147____ 165____ 183 ____201 ____ 219 ____237 ____
4 _____ 22 ____ 40 ____ 58 ____ 76 ____ 94 ____ 112____ 130____ 148____ 166____ 184 ____202 ____ 220 ____238 ____
5 _____ 23 ____ 41 ____ 59 ____ 77 ____ 95 ____ 113____ 131____ 149____ 167 ____ 185 ____203 ____221 ____239 ____
6 _____ 24 ____ 42 ____ 60 ____ 78 ____ 96 ____ 114____ 132____ 150____ 168 ____ 186 ____204 ____222 ____240 ____
7 _____ 25 ____ 43 ____ 61 ____ 79 ____ 97 ____ 115____ 133____ 151____ 169 ____ 187 ____205 ____223 ____241 ____
8 _____ 26 ____ 44 ____ 62 ____ 80 ____ 98 ____ 116____ 134____ 152____ 170 ____ 188 ____206 ____224 ____242 ____
9 _____ 27 ____ 45 ____ 63 ____ 81 ____ 99 ____ 117____ 135____ 153____ 171 ____189 ____207 ____ 225 ____243 ____
10 ____ 28 ____ 46 ____ 64 ____ 82 ____ 100 ___ 118____ 136____ 154____ 172 ____190 ____208 ____ 226____ 244 ____
11 ____ 29 ____ 47 ____ 65 ____ 83 ____ 101 ___ 119____ 137____ 155____ 173 ____191 ____209 ____ 227____ 245 ____
12 ____ 30 ____ 48 ____ 66 ____ 84 ____ 102____ 120____138____ 156____ 174 ____192 ____210 ____ 228 ____246 ____
13 ____ 31 ____ 49____ 67_____ 85 ____ 103____ 121____139____ 157____ 175_____193 ____211 ____ 229 ____247 ____
14 ____ 32 ____ 50 ____ 68_____86 ____ 104____ 122____140____ 158____ 176_____194 ____212 ____ 230 ____248 ____
15 ____ 33 ____ 51 ____ 69_____87 ____ 105____ 123____141____ 159____ 177_____195 ____213 ____ 231 ____
16 ____ 34 ____ 52 ____ 70_____88 ____ 106____ 124____142____ 160____ 178_____196 ____214 ____ 232 ____
17 ____ 35 ____ 53 ____ 71_____89 ____ 107____ 125____143____ 161____ 179_____197 ____215 ____ 233 ____
18 ____ 36 ____ 54 ____ 72_____90 ____ 108____ 126____144____ 162____ 180_____198 ____216 ____ 234 ____
- 234 -
Section 6: Programming Worksheets
- 235 -
Section 6: Programming Worksheets
[911] Diagnostics
Description on page 150
000 - Panel Diagnostics
001-016 - Keypad 001 to 016
101-115 - Zone Expander 001 to 015
301-315 - 8 I/O Expander 001 to 015
501-504 - Power Supply 001 to 004
521-524 - High Current Output Battery 001 to 004
551-554 - 3 A Power Supply 001 to 004
601-608 - Corbus repeater 001 to 008
- 236 -
Section 6: Programming Worksheets
- 237 -
Section 6: Programming Worksheets
040 – HSM3350 Module 1 Battery Settings 001 01 – o HSM3350 Battery 1 High Charge
02 – o HSM3350 Battery 2 High Charge
03 – R HSM3350 Battery 2 Enable
040 – HSM3350 Module 2 Battery Settings 002 01 – o HSM3350 2 High Charge Current
02 – o HSM3350 Battery 2 High Charge
03 – R HSM3350 Battery 2 Enable
040 – HSM3350 Module 3 Battery Settings 003 01 – o HSM3350 Battery 1 High Charge
02 – o HSM3350 Battery 2 High Charge
03 – R HSM3350 Battery 2 Enable
040 – HSM3350 Module 4 Battery Settings 004 01 – o HSM3350 Battery 1 High Charge
02 – o HSM3350 Battery 2 High Charge
03 – R HSM3350 Battery 2 Enable
- 238 -
Section 7: Troubleshooting
Section 7: Troubleshooting
7.1 Testing
l Power up system
l Program options as required (See "Programming descriptions" on page 75)
l Trip, then restore zones
l Verify correct reporting codes are sent to the central station
7.2 Troubleshooting
LCD programmable-message keypad:
l Press [*][2] followed by access code if required to view a trouble condition
l The trouble light flashes and the LCD displays the first trouble condition
l Use the arrow keys to scroll through all trouble conditions present on the system
Note: When additional information is available for a specific trouble condition, a [*] is displayed. Press the [*] key to view the
additional information.
- 239 -
Section 7: Troubleshooting
01 – Interactive Zone
14 – Limit Exceeded Trouble
02 – Interactive Partition
Trouble Troubleshooting
Disconnect Bell-/+ leads and measure resistance:
[01] Bell Circuit
Open circuit indicates break in wiring or defective siren/bell.
Bell+, Bell-.open circuit.
Jumper Bell+/- with 1K resistor (Brown, Black, Red):
Check event buffer to determine specific trouble.
[02] RF Jam Detected
If buffer logs RF jam, check for RF interference.
Wireless receiver - excessive noise detected.
Disable RF Jam: section [804] sub-section [801].
- 240 -
Section 7: Troubleshooting
[06] USB Wi-Fi Connected The trouble automatically clears once the HSM3WIFI adapter is unplugged from the
HSM3WIFI USB to Wi-Fi Adapter is plugged into the panel. This trouble serves as a warning as to not to forget to unplug the adapter when
panel configuration via Wi-Fi is completed.
[09] Power Unit Failure (HSM3350) Ensure the combined output power of the 3A power supply module is not exceeding
A fault with the internal power supply has been detected 3A. Power cycle the module and if the trouble persists it may indicate a permanent
on the 3A power supply. hardware failure.
[10] Overcurrent
Reduce the load on the panel by re-powering modules or detectors with a separate
The combined output power on the panel has exceeded power supply module.
2A for a period of more than 5 minutes.
Trouble [2] Module Battery Trouble Press [02] to determine specific trouble
Trouble Troubleshooting
[01] Panel Low Battery Verify voltage measured across DC input terminals is 16-18 VAC. Replace
The panel detects that the battery is below the low battery HSM65W power supply adapter if required.
threshold (less than 11.5VDC). Connect battery, remove AC power.
NOTE: This trouble condition will not clear until the battery Verify measured voltage across Aux terminals is 12.5VDC min.
voltage is 12.5VDC min., under load. NOTE: If battery is
new allow 1 hour to charge. Replace battery if it is no longer able to hold a charge due to age.
[04] 4 High Current output 1-4 Low Battery (HSM2204) Verify voltage measured across DC input terminals is 16-18 VDC. Replace
HSM65W power supply adapter if required.
HSM2204 battery less than 11.5VDC.
Connect battery, remove AC power.
NOTE: This trouble condition will not clear until the battery
voltage is 12.5VDC min., under load. Charge battery. It may Verify measured voltage across Aux terminals is 12.5VDC min.
be low due to a long period without AC. Replace battery if it is no longer able to hold a charge due to age.
- 241 -
Section 7: Troubleshooting
Trouble [2] Module Battery Trouble Press [02] to determine specific trouble
Verify battery is connected.
[05] 4 High Current output 1-4 No Battery (HSM2204)
Ensure battery leads are connected with the right polarity.
Enter 05 to view which HSM2204 does not have a battery
Connect battery, remove AC power.
connected.
Verify measured voltage across Aux terminals is 12.5VDC min
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
[07] Power Supply 1-4 Low Battery (HSM2300) HSM65W power supply adapter if required.
Enter 07 to view which HSM2300 has a battery voltage less Connect battery, remove AC power.
than 11.5V. Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
Verify battery is connected.
[08] Power Supply 1-4 No Battery (HSM2300)
Ensure battery leads are connected with the right polarity.
Enter 08 to view which HSM2300 does not have a battery
Connect battery, remove AC power.
connected.
Verify measured voltage across Aux terminals is 12.5VDC min
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
[10] HSM3204CX low battery HSM65W power supply adapter if required.
Enter 10 to view which HSM3204X has a battery voltage Connect battery, remove AC power.
less than 11.5V
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
[11] HSM3204CX no battery HSM65W power supply adapter if required.
Enter 11 to view which HSM3204CX does not have a Connect battery, remove AC power.
battery connected.
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
[13] HSM3350 low battery 1 HSM65W power supply adapter if required.
Enter 13 to view which HSM3350 has a battery voltage less Connect battery, remove AC power.
than 11.5V.
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
[14] HSM3350 low battery 2 HSM65W power supply adapter if required.
Enter 14 to view which HSM3350 has a battery voltage less Connect battery, remove AC power.
than 11.5V. Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
Verify battery is connected.
[15 ] HSM3350 no battery 1
Ensure battery leads are connected with the right polarity.
Enter 15 to view which HSM3350 does not have a battery
Connect battery, remove AC power.
connected.
Verify measured voltage across Aux terminals is 12.5VDC min
Verify battery is connected.
[16] HSM3350 no battery 2
Ensure battery leads are connected with the right polarity.
Enter 16 to view which HSM3350 does not have a battery
Connect battery, remove AC power.
connected
Verify measured voltage across Aux terminals is 12.5VDC min
- 242 -
Section 7: Troubleshooting
Trouble [3] Bus Voltage Trouble Press [03] to determine specific trouble
Trouble Troubleshooting
[01] HSM2HOST Bus Low Voltage
The 2-way wireless integration module has detected a
voltage less than 6.3V on its aux input.
[02] Keypad 1-16 Bus Low Voltage
Enter 02 to view hardwired keypads with a bus voltage of
less than 6.9V for models that include a wireless
transceiver, 7.7V for the models that do not.
[04] HSM2108 Bus Low Voltage
Enter 04 to view zone expanders with a bus voltage of
less than 5.9V.
[05] HSM2300 Bus Low Voltage
Enter 05 to view power supplies with a bus voltage of less
than 6.9V.
[06] HSM2204 Bus Low Voltage
Enter 06 to view high current output modules that have
Ensure voltage at module is higher than the documented limits.
detected a bus voltage of less than 6.9V.
Ensure wire run is not too long.
[07] Panel Corbus Fault The panel has detected that its
corbus output voltage is less than 9.0V or higher than Check voltage of panel battery.
15V Trouble should clear when AC is re-applied and the battery has had time to charge.
[08] HSM2208 Bus Low Voltage Disconnect AC and allow the panel to run on battery power. Ensure voltage at module
is higher than the documented limits.
The low current output module has detected a voltage
less than 5.9V on its aux input. Ensure that the corbus is not being overloaded or that there is no short anywhere on
the wire run.
[09] HSM2955 Bus Low Voltage
The audio module has detected a voltage less than
9.65V on its aux input.
[10] HSM3408 voltage
The audio module has detected a voltage less than 6.4V
on its aux input.
[11] HSM3204CX bus low voltage
The audio module has detected a voltage less than 6.0V
on its aux input.
[12] HSM3204CX bus fault
Enter 12 to view corbus repeaters which have detected
the voltage on the corbus output is less than 9.0V
[13] HSM3350 bus low voltage
Enter 12 to view corbus repeaters which have detected
the voltage on the corbus output is less than 6.0V
- 243 -
Section 7: Troubleshooting
Trouble Troubleshooting
[01] Zone 1-248 AC
[03] Siren 1-16 AC
[04] Repeater 1-8 AC
[05] HSM2300 1-4 AC Verify voltage measured across DC input terminals is 16-20VDC. Replace HSM65W
power adapter if required.
[06] HSM2204 1-4 AC
For the HSM2204 or HSM2300 modules, ensure a 40VA 16.5VAC transformer is
[07] Alarm Controller being used. Terminal voltage should be 16-17VAC. Replace transformer if required.
[08] HSM3204CX AC
[09] HSM3350 AC
An AC trouble has been detected on a device or module.
- 244 -
Section 7: Troubleshooting
Trouble Troubleshooting
Fire Trouble:
Ensure that, if the PGM-2 is configured as 2-Wire Smoke detector and not used, 5.6K EOL resistor
When a Fire Trouble is generated at the [05] Device faults ie is used.
Device Faults > Fire Trouble
Ensure fire zones have a 5.6K resistor (green, blue, red) connected.
Remove wire leads from Z and COM terminals and measure resistance of the wire
[01] Zone 1-248 faults
leads:
Wireless zones:
Check for a short on DEOL zones or an open condition on SEOL fire zones.
Enter [01] to view zones in fault. This trouble is
Connect a 5.6K resistor across the Z and COM terminals. Verify the trouble condition
generated by a zone wireless supervisory trouble.
clears.
Placement test a wireless device and re-locate it if bad results are received.
Hardwired zones:
This trouble is generated by a short on hardwired zones .
when DEOL or TEOL is used.
[03] Siren 1-16 faults
This trouble is caused by a wireless supervisory fault on a Placement test the wireless siren and re-locate if needed.
wireless siren.
[04] Repeater 1-8 faults
This trouble is caused by a wireless supervisory fault on a Placement test the wireless repeater and re-locate if needed.
wireless repeater, or by the repeater shutting down due
to a loss of AC/DC power.
[06] Device mask
Enter [06] to view the zone label in masking condition. A
Refer to the device manual to troubleshoot conditions that may cause masking detection for that
zone programmed as 24H Anti- Masking or a wireless devices sensors.
device has detected a masking condition with one of its
sensors.
[08] Heat trouble
Move the device to a location with room temperature and ensure the trouble clears. If not check the
Enter 10 to view the wireless zone which is detecting low programming threshold for high temperature for the zone.
temperature.
[09] CO trouble
Enter 09 to view the zone of a CO wireless device that is Refer to the CO devices manual for troubleshooting steps for low sensitivity trouble.
in low sensitivity trouble.
[10] Freeze trouble
Move the device to a location with room temperature and ensure the trouble clears. If not check the
Enter 08 to view the wireless zone which is detecting high programming threshold for low temperature for the zone.
temperature.
[11] Probe disconn.
Enter [11] to view the wireless zone which has detected a Refer to the temperature or flood detectors manual for troubleshooting steps for probe disconnected.
disconnect probe.
[12] Fire trouble If fire zone is a wireless smoke, ensure it is not tampered, or in supervisory trouble. Ensure the
smoke chamber is cleared of dust. If a 2wire smoke is used ensure a 2.2K EOL resistor is used. If
Enter [012] to view which zones are in Fire trouble. zone is a 4 wire smoke, ensure a 5.6K EOL resistor is used.
- 245 -
Section 7: Troubleshooting
Trouble [6] Device Low Battery Press [06] to toggle through specific devices with low battery trouble
Trouble Troubleshooting
[01] Zones 1-248
[02] Keypad 1-16
[03] Siren 1-16
View which device is in low battery through the [*][2] menu.
[04] Repeater 1-8
Replace the batteries in the device with same battery type.
[05] User 1-32
Verify that tamper and low battery condition is cleared and reported.
One or more wireless devices has a low battery.
Verify zone operation.
NOTE: The event is not logged to the event buffer until
the wireless device low battery delay time expires.
Programming section [377], Opt 002.
Trouble Troubleshooting
[01] Zone 1-248 tampers
[02] Keypad 1-16 tampers Check that the tamper switch is securely attached to the wall.
[03] Siren 1-16 tampers Remove the wire leads from I/O and COM and measure the resistance of the wire
[04] Repeater 1-8 tampers leads.
[05] Audio Station 1-4 tampers Connect a 5.6K resistor (Green, Blue, Red) across the I/O and COM terminals.
An open circuit is present on one or more zones with Verify the trouble condition clears.
DEOL or TEOL resistors enabled.
Ensure device cover is secure.
A tamper condition is present on one or more wireless
Ensure device is correctly mounted for wall tamper operation.
devices.
Trip, then restore the tamper. If tamper condition persists, replace wireless device.
Trouble Troubleshooting
[01] Zone 1-248 faults Open/close the device, press a key on the keypad or tamper/restore.
[02] Keypad 1-16 faults Ensure the device is physically present.
[03] Siren 1-16 faults Check for device faults (e.g., low battery).
[04] Repeater 1-8 faults Check the current signal strength and during the last 24 hours.
HSM2HOST has not received a supervisory signal from Replace the battery.
a wireless device for 20 minutes. Replace the device.
- 246 -
Section 7: Troubleshooting
Trouble [9] Module Supervisory Press [09] to determine specific zones with a tamper trouble
Trouble Troubleshooting
[01] HSM2HOST
[02] Keypad 1-30
[04] HSM2108 1-15
Ensure the module is physically connected to the corbus.
[05] HSM2300 1-4
Measure power across corbus Red and Blk directly on the module and ensure its at
[06] HSM2204 1-4 least 10.5V.
[08] HSM2208 1-4 Remove the module from the bus and wire it directly at the panel. If trouble clear it
[09] HSM2955 indicates a wiring issue with were it was previously mounted. If the trouble doesn't
clear, replace the module.
[10 ]HSM3408 1-30
Its its an old removed, or replaced module, ensure it gets deleted via section [902].
[11] HSM3204CX 1-8
[12] HSM3350 1-4
No supervisory response from enrolled module.
Trouble Troubleshooting
[01] HSM2HOST
[02] Keypad 1-16
Ensure the TAM terminal, if present on the
[04] HSM2108 1-30
modules is shorted to ground if tamper support is not used.
[05] HSM2300 1-4
Ensure module cabinet cover is securely closed and properly activating the tamper
[06] HSM2204 1-4 switch, if present.
[08] HSM2208 1-4 Ensure for the Keypads that the rubber tamper plunger is installed on the back plastics
[09] HSM2955 and that the keypad is securely closed and fastened to the wall.
[10] Alt. comm. For the HSM2HOST ensure module is securely closed and correctly mounted for wall
[11] HSM3408 1-30 tamper operation.
[12] HSM3204CX 1-8 Manually trip, then restore the tamper. If tamper condition persists, replace the
module.
[13] HSM3350 1-4
A tamper condition is present on one or more modules.
Trouble Troubleshooting
Measure the voltage across TIP and RING on the panel:
No phone off-hook – 50VDC (approx).
[01] Phone Line Trouble
Any phone off-hook – 5VDC (approx).
Phone line voltage at TIP, RING on main panel less than
Wire incoming line directly to TIP and RING.
3VDC.
If trouble clears, check wiring or the RJ-31 phone jack.
If not using a phone line on the panel, disable it in section [015] option 7.
[02] FTC Receiver 1-4
If using PSTN communications, ensure the central station phone number is
The system failed to communicate with a receiver using programmed correctly. If using IP or cellular, ensure alternate communicator has the
one of the enabled phone numbers. Enter [02] to view correct central station IP and port numbers, as well as APN for cellular.
phone numbers with failure to communicate troubles.
[03] Alternate Comm SIM Lock
SIM lock is enabled and the unit does not have the Replace SIM card with one that does not have a SIM lock pin code programed.
correct SIM PIN.
- 247 -
Section 7: Troubleshooting
[06] Receiver 1-4 Trouble If the network has a firewall, ensure the network has the programmed outgoing ports
open (default UDP port 3060 and port 3065).
Alternate communicator is failing to initialize to the
receiver. Ensure that all cellular receiver APNs have been programmed with the access point
name provided by the cellular provider.
If Common Mode is used, and only one path is initiliazed while the other path is not
successful, generate a manual test transmission over both paths or power cycle the
communicator to recover the "Receiver Not Available" trouble.
[07] Receiver 1-4 Supervision This trouble is indicated when supervision is enabled and the unit is not able to
The alarm system loses communication with an Ethernet successfully communicate with the receiver.
or cellular receiver on the system. If this trouble persists, contact the central station.
[09] Alternate Comm Fault Check section [382] toggle option[5] is ON if using an Alarm.com alternate
The alternate communicator has not responded to any communicator. If not, it should be OFF.
poll commands. Alt Comm Fault is displayed in [*][2] and Ensure the PC-LINK cable between the panel and Alarm.com communicator is
the event buffer. connected properly (not reversed) and is securely in place.
The unit has exhausted all communications attempts to all programmed receivers for
[10] Alternate Comm FTC Fault events generated by the communicator.
Restart the system and if trouble persists, contact the dealer.
Trouble Troubleshooting
[01] Zones 1-248
Ensure the device is physically present.
[02] keypad 1-16
Check the current signal strength and during the last 24 hours.
[03] Siren 1-16
Replace the battery or press the tamper switch.
[04] Repeater 1-8
Enroll the device again.
[05] User 1-32
If wireless devices were recently enrolled, or the HSM2HOST was power cycled, wait
A device is out of sync with the wireless network or was up to 16 minutes for the device to synchronize to the network.
not synchronized with the network after enrollment.
- 248 -
Section 7: Troubleshooting
Trouble Troubleshooting
[05] HSM2300
[06] HSM2204
[07] System area
Check for a short between Aux+ and Aux- or other system ground.
[10] HSM3408
Ensure the aux current draw has not exceeded the documented limits.
[11] HSM3204CX
Ensure voltage between AUX+ and AUx - is between 9VDC to 14VDC.
[12] HSM3350 AUX 1 trouble
[13] HSM3350 AUX 2 trouble
An auxiliary power supply trouble is present.
Trouble [14] Module Tamper Press [14] to determine specific trouble
Trouble Troubleshooting
Check the Alarm.com communicator firmware is compatible with PSP firmware to
support extended number of Zones and Partitions.
Interactive Zone trouble is generated when the Alarm.com firmware does not support
[01] Interactive Zone the configured number of zones in panel (>220 Zones) and Interactive Partition
[02] Interactive Partition Trouble is generated when the Alarm.com firmware does not support configured
number of Partitions.
Ensure to configure compatible number of zones and partitions while using with
Alarm.com.
IMPORTANT!
Ensure you have the following information available before contacting Customer Support :
Alarm controller type and version, (e.g., HSM3032 V1.1):
Note: Version number can be accessed by entering [*][Installer Code][900] on any LCD keypad. This information is also loc-
ated on a sticker on the printed circuit board.
List of modules connected to control panel, (e.g., HSM2108, HSM2HOSTx etc.) .
- 249 -
Appendix 1: Reporting codes
Zone Events
[307] Zone Alarms A/R see "Contact ID & SIA Zone Alarm/Restore Event Codes" on
[307] Zone Restores A/R page 255" for details.
Tamper Events
E(3)83-(601 -616) TA-(0601-0616)
[308]-[101] Keypad 1-16 tamper/restore alarm T/R
R(3)83-(601 -616) TR-(0601-0616)
E (3)83-(801-816) TA-(0801-0816)
[308]-[101] Siren 1-16 tamper/restore alarm T/R
R (3)83-(801-816) TR-(0801-0816)
E(3)83-(901-908) TA-(0901-0908)
[308]-[101] Repeater 1-8 tamper/restore alarm T/R
R (3)83-(901-908) TR-(0901-0908)
E(3)41-(101-130) ES-(0101-0130)
[308]-[101] HSM2108: 8-Zone Expander module #1-30 tamper/restored T/R
R(3)41-(101-130) EJ-(0101-0130)
E(3)41-(201-216) ES-(0201-0216)
[308]-[101] HSM2208: 8-Output Expander module #1-16 tamper/restored T/R
R(3)41-(201-216) EJ-(0201-0216)
- 250 -
Appendix 1: Reporting codes
Opening Events
[308]-[201] User Openings - Disarmed by user O/C E(4)A1-UUU OP-UUUU
[308]-[202] Automatic Arming Canceled O/C E(4)64-UUU CI-0000
Special Opening - System disarmed using: keyswitch,
[308]-[201] O/C E(4)AA-000 OP-0000
maintenance code, DLS software, wireless key
Late to Open - System not disarmed before late to open time
[308]-[211] O/C E(4)53-000 CT-0000
expired
[308]-[202] Automatic (Schedule) Opening O/C E(4)A3-000 OA-0000
[308]-[201] Keyswitch Open O/C E(4)A9-ZZZ OS-ZZZZ
Closing Events
[308]-[201] User Closings - System armed by user, wireless key O/C R(4)A1-UUU CL-UUUU
[308]-[221] Partial Closing - 1 or more zones bypassed when armed O/C E(4)56-000 CG-0000
Special Closing - System armed via: quick arm, keyswitch,
[308]-[201] O/C R(4)AA-000 CL-0000
function key, maintenance code, DLS software
[308]-[211] Late to Close - Auto-arm prealert sounded O/C E(4)54-000 CI-0000
[308]-[211] Exit Fault O/C E(3)74-ZZZ EA-ZZZZ
[308]-[202] Automatic (Schedule) Closing O/C R (4)A3-000 CA-0000
[308]-[201] Keyswitch Close O/C R(4)A9-ZZZ CS-ZZZZ
Module Troubles
E(3)AA-001-016 EM-0001-0016
[308]-[332] Hardwired Module Low Voltage trouble/restore - Keypads MA/R
R(3)AA-001-016 EN-0001-0016
E (3)AA-101-130 EM-0101-0130
[308]-[332] Hardwired Module Low Voltage trouble/restore - HSM2108 MA/R
R (3)AA-101-130 EN-0101-0130
E(3)AA-201-216 EM-0201-0216
[308]-[332] Hardwired Module Low Voltage trouble/restore - HSM2208 MA/R
R(3)AA-201-216 EN-0201-0216
E (3)AA-551 EM-0551
[308]-[332] Hardwired Module Low Voltage trouble/restore - HSM2HOST MA/R
R (3)AA-551 EN-0551
E(3)AA-601-604 EM-0601-0601
[308]-[332] Hardwired Module Low Voltage trouble/restore - HSM2204 MA/R
R(3)AA-601-604 EN-0601-0604
E (3)AA-621-624 EM-0621-0624
[308]-[332] Hardwired Module Low Voltage trouble/restore - HSM2300 MA/R
R (3)AA-621-624 EN-0621-0624
- 251 -
Appendix 1: Reporting codes
- 252 -
Appendix 1: Reporting codes
Alternate Communicator
E(3)3A-000
[308]-[351] Alternate Communicator fault/restore MA/R ET-0000 / ER-0000
R(3)3A-000
E(3)AA-001
[308]-[351] Alternate Communicator Radio/SIM failure/restore MA/R YX-0001 / YZ-0001
R(3)AA-001
E(3)AA-001
[308]-[351] Alternate Communicator cellular trouble/restore MA/R YX-0001 / YZ-0001
R(3)AA-001
E(3)AA-001
[308]-[352] Alternate Communicator Ethernet trouble/restore MA/R YX-0001 / YZ-0001
R(3)AA-001
E(3)5A-001-004 YS-0001-0004
[308]-[354] Alternate Communicator Receiver 1-4 absent/restore MA/R
R(3)5A-001-004 YK-0001-0004
On-Board Communicator
[851][025] Radio activation restore N/A R(5)52-001 RS-0001
[851][226] Ethernet Receiver 1 Test Transmission N/A E(6)A3-951 RP-0001
[851][227] Ethernet Receiver 2 Test Transmission N/A E(6)A3-952 RP-0002
[851][228] Cellular Receiver 3 Test Transmission N/A E(6)A3-955 RP-0003
[851][229] Cellular Receiver 4 Test Transmission N/A E(6)A3-956 RP-0004
Wireless Events
Wireless Zone Low Battery trouble/restore E(3)84-ZZZ XT-ZZZZ
[308]-[361] MA/R
ZZZ= Wireless zones 001-248. R(3)84-ZZZ XR-ZZZZ
Wireless Device Low Battery trouble/restore.
ZZZ= 601-616: wireless keypads E(3)84-ZZZ XT-ZZZZ
[308]-[361] 701-732: wireless keys MA/R
801-816: wireless Sirens R(3)84-ZZZ XR-ZZZZ
901-908: wireless repeaters
E(3)A1-ZZZ AT-ZZZZ
[308]-[361] Wireless Zone AC trouble/restore MA/R
R(3)A1-ZZZ AR-ZZZZ
E(3)8A-ZZZ UT-ZZZZ
[308]-[361] Wireless Device Fault/restore MA/R
R(3)8A-ZZZ UJ-ZZZZ
E(3)8A-ZZZ KT-ZZZZ
[308]-[361] Wireless Temperature and Flood Probe trouble/restore MA/R
R(3)8A-ZZZ KJ-ZZZZ
E(3)8A-ZZZ
[308]-[361] Freeze trouble/restore MA/R ZT/ZJ-ZZZZ
R(3)8A-ZZZ
Self Test Trouble/Restore*
E (3)89-ZZZ
[308]-[361] Note: To prevent a reporting code conflict do not program MA/R YX/YZ-ZZZZ
R (3)89-ZZZ
PG9984 as zone 1.
- 253 -
Appendix 1: Reporting codes
Miscellaneous Alarms
[308]-[001] Duress Alarm - Code entered at keypad A/R E(1)21-000 HA-0000
[308]-[001] Opening After Alarm - Disarmed with alarm in memory A/R E(4)58-000 OR-0000
Recent Closing - Alarm occurs within two minutes of system
[308]-[001] A/R E(4)59-UUU CR-UUUU
arming
[308]-[001] Burglary Verified A/R E(1)39-000 BV-0000
[308]-[001] Burglary Not Verified A/R E(3)78-000 BG-0000
E(1)43-000
[308]-[001] HSM2108 Zone Expander Supervisory Alarm/restore A/R UA-0000 / UH-0000
R(1)43-000
[308]-[002] Holdup Verified A/R E(1)29-000 HV-0000
[308]-[011] Alarm Canceled before expiry of alarm cancellation timer A/R E(4)A6-UUU OC-UUUU
E(1)46-992
[308]-[011] PGM2 (Silent 24 Hour Input) -Aux Input Alarm/restore A/R UA-0992 / UH-0992
R(1)46-992
E(1)4A-992
[308]-[011] PGM2 (Audible 24 Hour Input) -Aux Input Alarm/restore A/R UA-0992 / UH-0992
R(1)4A-992
E(1)11-992
[308]-[305] PGM2 2-Wire Smoke Alarm/Restore A/R FA-0992 / FH-0992
R(1)11-992
Miscellaneous Closing
[308]-[221] Zone Bypass at time of arming O/C E(5)7A-ZZZ UB-ZZZZ
[308]-[221] Zone Unbypass O/C R(5)7A-ZZZ UU-ZZZZ
- 254 -
Appendix 1: Reporting codes
Testing
E(6)A7-UUU
[308]-[401] Walk Test Begin/End T TS-UUUU/TE-UUUU
R(6)A7-UUU
[308]-[401] Periodic Test T E(6)A2-000 RP-0000
[308]-[401] Periodic Test with Trouble T E(6)A8-000 RY-0000
[308]-[401] System Test - [*][6] bell/communications test T E(6)A1-000 RX-0000
Maintenance
E(3)73-ZZZ
[308]-[311] Fire trouble/restore MA/R FT-ZZZZ / FJ-ZZZZ
R(3)73-ZZZ
E(3)8A-ZZZ
[308]-[314] Gas trouble/restore MA/R GT-ZZZZ / GJ-ZZZZ
R(3)8A-ZZZ
E(3)8A-ZZZ
[308]-[314] Heat trouble/restore MA/R KT-ZZZZ / KJ-ZZZZ
R(3)8A-ZZZ
[308]-[311] Cold Start - System has restarted after total power loss MA/R R(3) A5-000 RR-0000
[308]-[312] Event Buffer 75% Full MA/R E(6)22-000 JL-0000
[308]-[312] DLS Lead In - Download session start MA/R E(4)11-000 RB-0000
[308]-[312] DLS Lead Out - Download session stop MA/R E(4)12-000 RS-0000
[308]-[312] SA Lead In - Download session start MA/R E(4)11-000 RB-0000
[308]-[312] SA Lead Out - Download session stop MA/R E(4)12-000 RS-0000
[308]-[312] Installer Lead In - Installer Programming has been entered MA/R E(6)27-000 LB-0000
[308]-[312] Installer Lead out - Installer Programming has been exited MA/R E(6)28-000 LS-0000
E(9)01-900
[308]-[313] Panel firmware update begin/ successful MA/R LB-0900 / LS-0900
R(9)01-900
[308]-[313] Panel firmware update fail MA/R E(9)02-900 LU-0900
E(3)14-000 YP-000
[308]-[321] Panel power unit fail/restore MA/R
R(3)14-000 YQ-000
*
A/R = alarms/restores; T/R = tampers/restorers; O/C = openings/closings; MA/R = maintenance alarms/restores; T = test transmissions
**
UUU = user number (user 001-1000). Note that for CID, enter 999 for user 1000. ZZZ/ZZZZ = zone number (001-248).
***
Zones and panic pendants are identified, wireless keys can be identified for openings and closings.
- 255 -
Appendix 1: Reporting codes
Zone Definition SIA Auto Rep Codes Contact ID Auto Rep Codes
Night Zone BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Burglary BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
Delayed 24-Hr. Fire (Wireless) FA-ZZZZ / FH-ZZZZ E(1) 1A - ZZZ / R(1)1A - ZZZ
Standard 24-Hr. Fire (Wireless) FA-ZZZZ / FH-ZZZZ E(1) 1A - ZZZ / R(1)1A - ZZZ
24-Hr. Sprinkler SA-ZZZZ / SH-ZZZZ E(1) 13 - ZZZ / R(1)13 - ZZZ
24-Hr.Low Temperature ZA-ZZZZ / ZH-ZZZZ E(1) 59 - ZZZ / R(1)59-ZZZ
24-Hr High Temperature KA-ZZZZ / KH-ZZZZ E(1) 58 - ZZZ / R(1)58 - ZZZ
24-Hr. Latching Tamper BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Non Alarm (Walk Test Only) BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Non-latching Tamper TA-ZZZZ / TR-ZZZZ E(3) 83 - ZZZ / R(3)83 - ZZZ
24-Hr. Masking Trouble UT-ZZZZ / UJ-ZZZZ E(3) 8A - ZZZ / R38A-ZZZ
Momentary Keyswitch Arm (Walk Test Only) BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
Maintained Keyswitch Arm (Walk Test Only) BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
Momentary Keyswitch Disarm (Walk Test Only) BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
Maintained Keyswitch Disarm (Walk Test Only) BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Supervisory US-ZZZZ / UR-ZZZZ E(1) 5A - ZZZ / R(1)5A - ZZZ
24-Hr. Supervisory Buzzer UA-ZZZZ / UH-ZZZZ E(1) 5A - ZZZ / R(1)5A - ZZZ
24-Hr. Auto Verified Fire (Wireless) FA-ZZZZ / FH-ZZZZ E(1) 1A - ZZZ / R(1)1A - ZZZ
Fire Supervisory FS-ZZZZ / FV-ZZZZ E(2) AA - ZZZ / R(2)AA - ZZZ
24-Hr. Gas GA-ZZZZ / GH-ZZZZ E(1) 51 - ZZZ / R(1)51 - ZZZ
24-Hr. CO Alarm GA-ZZZZ / GH-ZZZZ E(1) 62 - ZZZ / R(1)62 - ZZZ
24-Hr. Holdup HA-ZZZZ / HH-ZZZZ E(1) 22 - ZZZ / R(1)22 - ZZZ
24-Hr. Panic PA-ZZZZ / PH-ZZZZ E(1) 2A - ZZZ / R(1)2A - ZZZ
24-Hr. Flood WA-ZZZZ / WH-ZZZZ E(1) 54 - ZZZ / R(1)54 - ZZZ
24-Hr Heat KA-ZZZZ / KH-ZZZZ E(1) 58 - ZZZ / R(1)58 - ZZZ
24-Hr. Medical MA-ZZZZ / MH-ZZZZ E(1) AA - ZZZ / R(1)AA - ZZZ
24-Hr. Emergency QA-ZZZZ / QH-ZZZZ E(1) A1 - ZZZ / R(1)A1 - ZZZ
Push to Set (Walk Test Only) BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A - ZZZ
Final Door Set BA-ZZZZ / BH-ZZZZ E(1) 3A - ZZZ / R(1)3A - ZZZ
ZZZ/ZZZZ = zones 001-248
- 256 -
Appendix 2: Word library
- 257 -
Appendix 3: Template programming tables
- 258 -
Appendix 3: Template programming tables
- 259 -
Appendix 3: Template programming tables
- 260 -
Appendix 3: Template programming tables
Common Group
Common Group Common Group Programming
Set all reporting codes to automatic [308] Event Reporting - All Events On
[311][001] Partition 1 Alarm/Restore - Bit 1 Receiver 1 - On
[311][001] Partition 1 Alarm/Restore - Bit 2 Receiver 2 - Off
Alarm/restore call directions enabled
[311][001] Partition 1 Alarm/Restore - Bit 3 Receiver 3 - Off
[311][001] Partition 1 Alarm/Restore - Bit 4 Receiver 4 - Off
[311][002] Partition 1 Tamper/Restore - Bit 1 Receiver 1 - Off
[311][002] Partition 1 Tamper/Restore - Bit 2 Receiver 2 - Off
Tamper/restore call directions disabled
[311][002] Partition 1 Tamper/Restore - Bit 3 Receiver 3 - Off
[311][002] Partition 1 Tamper/Restore - Bit 4 Receiver 4 - Off
[311][003] Partition 1 Open/Close - Bit 1 Receiver 1 - Off
[311][003] Partition 1 Open/Close - Bit 2 Receiver 2 - Off
Opening/closing call directions disabled
[311][003] Partition 1 Open/Close - Bit 3 Receiver 3 - Off
[311][003] Partition 1 Open/Close - Bit 4 Receiver 4 - Off
[309][001] Maintenance - Bit 1 Receiver 1 - On
[309][001] Maintenance - Bit 2 Receiver 2 - Off
Maintenance call directions enabled
[309][001] Maintenance - Bit 3 Receiver 3 - Off
[309][001] Maintenance - Bit 4 Receiver 4 - Off
[309][002] Test Transmission - Bit 1 Receiver 1 - Off
[309][002] Test Transmission - Bit 2 Receiver 2 - Off
Test transmission call directions disabled
[309][002] Test Transmission - Bit 3 Receiver 3 - Off
[309][002] Test Transmission - Bit 4 Receiver 4 - Off
- 261 -
Appendix 3: Template programming tables
l Openings & Closings - Sets Residential Dial Reporting Codes for all openings and closings
Openings/Closings Group Openings/Closings Programming
[308][201] - Bit 1 User Closing - On
[308][201] - Bit 2 User Opening - On
[308][201] - Bit 5 Special Closing - On
Enable All User Open/Close Reports [308][201] - Bit 6 Special Opening - On
[308][202] - Bit 1 Automatic Closing - On
[308][202] - Bit 2 Automatic Opening - On
[308][202] - Bit 3 Automatic Cancel - On
l Zone Alarm Restore Group - Disables all zone alarm restore reporting codes
Zone Alarm Restore Group DLS/Installer Lead In/Out Programming
[307][001] - Bit 2 Alarm Restore - Off
[307][002] - Bit 2 Alarm Restore - Off
[307][003] - Bit 2 Alarm Restore - Off
[307][004] - Bit 2 Alarm Restore - Off
Restore zone alarm reporting codes [307][005] - Bit 2 Alarm Restore - Off
[307][006] - Bit 2 Alarm Restore - Off
[307][007] - Bit 2 Alarm Restore - Off
[307][008] - Bit 2 Alarm Restore - Off
[307][009] - [128] Bit 2 Alarm Restore - Off
- 262 -
Appendix 3: Template programming tables
After entering a valid 5-digit template programming code, the system prompts for the following data in the sequence listed:
1. Central Station Telephone Number
i. Program the required central station phone number. Press [#] to complete your entry.
ii. This phone number is entered into programming section [301][001].
2. Central Station System Account Code (4 or 6-digit code)
i. Program the system account code. All digits must be entered in order to complete your entry.
ii. This account code is entered into programming section [310][000].
3. Partition 1 Account Code (4 digit code)
i. Program the partition 1 account code. All digits must be entered in order to complete your entry.
ii. This account code is entered into programming section [310][001].
4. DLS Access Code (6-digit code)
i. Program the required DLS access code. All 6 digits must be entered in order to complete your entry.
ii. This access code is entered into programming section [403].
5. Entry Delay 1 and Exit Delay
i. Enter the 3-digit entry delay 1 (in seconds) followed by the desired 3-digit exit delay (in seconds). These entries affect
all partitions.
ii. All 3 digits must be entered in order to complete each section entry.
iii. These values are entered in programming sections [005][001]-[008] entry 1 and 3 respectively.
6. Installer's Code
i. Enter the 4, 6 or 8-digit installer access code (dependent on section [041]). All digits must be entered in order to com-
plete the section entry.
ii. This code is entered into programming section [006][001].
iii. After the installer code has been programmed the system returns to the base installer programming menu.
iv. All template programming information defaults after performing a hardware or software panel default. The 5-digit tem-
plate programming code is defaulted to 0000000.
Note: Pressing the pound key (#) advances through template programming, accepting what is displayed in these locations,
potentially overwriting desired programming. Depending on the option programmed, restoring the defaults using template
programming may not be possible.
- 263 -
Appendix 4: ASCII characters
Q R S T U V W X Y Z [ ¥ ] ^ _ ╲ a b c d e f g h
□ 「 」 ֻ ▪ ヲ ア ィ ゥ ェ ォ カ ュ ョ シ ア イ ゥ ェ ォ カ キ ク
161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184
ケ コ サ シ ス セ ソ タ ダ ツ テ ト ナ ニ ヌ ネ ノ ハ ヒ フ ヘ ホ マ ミ
185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208
ム メ モ ヤ ユ ョ ラ リ ル レ ロ ワ ン ゙ ▢ α ä β Ɛ μ σ ρ ϧ ʃ
209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232
⊣ ϳ x ¢ £ ñ Ö p q θ ∞ Ω ϋ Σ π X y 千 Ⴌ Ħ ÷
233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253
- 264 -
Appendix 5: Regulatory approvals
- 265 -
Appendix 5: Regulatory approvals
Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or corporation
commission for information.
Alarm dialling equipment must be able to seize the telephone line and place a call in an emergency situation, even if other equipment (telephone,
answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialling equipment must be connected to a
properly installed RJ-31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. Proper
installation is depicted in the figure below. Consult your telephone company or a qualified installer if you have any questions concerning these
instructions or about installing the RJ-31X jack and alarm dialling equipment for you.
- 266 -
Appendix 5: Regulatory approvals
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified in accordance with SIA-CP-01 Standard) as
proof of compliance with the above mentioned standards. For further information on this product’s listings please also refer to the official listing guides published at the
UL web site (www.ul.com) under Online Directions Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations, refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.
l Control Unit must be enclosed in model HSC3010C or HSC3020C enclosure.
l Power supply model SOY-1800360NA (HS65WPSNA) must be employed.
l 24 h standby power must be provided for fire applications and 4h for burglary only applications (AC trouble must be transmitted to SRC).
l One DSC Model RM-1 or RM2 end-of-line supervision relay module must be used.
l Priority of signals needs to be set Fire, CO/ Medical, Burg, Panic, AUX (Flood).
l All burglary-type zones shall be configured with SEOL or DEOL configuration. Use model EOLR-2
l (refer to section [002], bit 10 or 11 shall be ON)
l Use at least one PG9926/ PG9916/ PG9936 Smoke Detector for Fire Installations (section [001], fire zone shall be programmed as type 025)
l The entry delay shall not exceed 45 seconds (see section [005])
l The exit delay shall not exceed 60 seconds (refer to section [005])
l The minimum Bell Time-out is 4 minutes (refer to section [005])
Note: Connect Bell output to a UL/ULC Listed audible device (e.g., UL File S8534, model TS-443S-6), rated to operate over the range of 10.8 to 12.5 VDC and 85dBA
minimum. Wireless sirens PG9901 and PG9911 may also be used as audible devices.
Note: For ULC Residential Fire installations, minimum bell time-out is 5 min. For UL Home Health Care installations, minimum bell time-out is 5 min. For UL Com-
mercial Burglary installations, minimum bell time-out is 15 min.
l Temporal Three Fire Signal shall be enabled (section [013], opt.8 ON)
l Arm/Disarm Bell Squawk shall be enabled when using wireless key PG4939/PG4929/PG4949 (section [014], option 1 shall be ON)
l A code shall be required for bypassing (section [023], option 4 shall be ON)
l Trouble beeps shall be enabled (section [022], option 7 shall be ON)
l AC trouble indication LED shall be enabled (Keypad Programming, section [022], options 5 and 6 shall be ON)
l DACT Communicator shall be enabled for Supervising Station Monitoring (section [380], option 1 shall be ON)
Note: The DACT communicator for this product has no line security.
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be ON)
This product is programmed to perform 5 attempts for communication of an event to the supervising station. If unsuccessful, a Fail To Communicate (FTC) trouble is
generated.
Test transmission cycle shall be set (refer to section [351]) for monthly transmission for UL residential burglary applications and to 7 days for UL residential fire applic-
ations.
Note: For ULC Residential/Commercial installations set for daily test transmission.
l For UL Residential Fire installations, [*][2] requires code shall be enabled (Section [023] option 5 ON) and latching troubles shall be enabled (Section [019] option
2 ON)
l If a repeater is needed, two repeaters model PG9920 shall be used to ensure proper signal routing.
l Wireless Supervision window shall be set to 4 hours for Fire Installations (Wireless Programming, section [804]>[802] shall be programmed with the value 16).
l Wireless Supervision window shall be set to 24 hours for Burglary Installations only (Wireless Programming, section [804]>[802] shall be programmed with the
value 96).
l RF Jam detection shall be enabled (refer to Wireless Programming (section [804][801], option 00 shall be OFF).
l New Alarms will Disconnect 2-way Audio (section [022], option 6 OFF).
Requirements for UL985 6th edition compliant installations:
For UL residential fire applications (including CO) compliant with UL985 6th edition, the following guidelines shall be respected:
l Two UL listed compatible keypads (for example HS2LCDPRO, HS2TCHPRO(BLK), HS2LCDRFPRO9) shall be used, each having communication bus wir-
ing directly connected to the RED/BLK/YEL/GRN terminals located on the main control panel board assembly.
l Power loop supervision relay model RM-1(C) or RM-2 shall be connected to AUX power output to report wiring faults if it is used for powering fire/CO detec-
tion devices.
l Section [023] option 5 shall be ON. A user code shall be required to view the [*] [2] trouble menu. When enabled, trouble beeps will only be silenced when the
[*] [2] has been entered and exited.
l In section [377] [003] a test transmission must be sent to the monitoring station every 7 days (default: 007).
l In section [377] [004], the default time is programmed for 4.45 a.m (0445). The panel will generate a random test transmission time within a ± 60 minute win-
dow.
l If a repeater is required, two of the PG9920 models shall be used for proper signal routing.
l Latching troubles shall be enabled (section [019] option 2 must be set to ON).
l In a combination fire and burglary application, fire alarm detection devices shall not be powered from the same AUX output (control panel, zone expander,
power supply) as burglary alarm initiating devices.
l Power supply wiring for fire alarm detection devices (smoke detectors, CO Detectors) shall be connected to the control panel AUX output (located
on the main control panel board assembly).
l Power supply wiring for burglary alarm initiating devices (motion detectors, magnetic contacts, glass break detectors, etc.) shall be connected to
the compatible power supply modules AUX outputs (located on the power supply module board assembly, for example HSM3350, HSM3204CX) or
expander module AUX output (located on the expander module board assembly, for example HSM3408).
ULC Commercial Burglary Security Levels I-IV:
The following wireless PowerG devices models are ULC listed under ULC-S304 requirements for use in Commercial Burg applications rated for security level 1.
l PG9914 l PG9924 l PG9939 l PG9974P
l PG9905 l PG9929 l PG9944 l PG9984
l PG9920 l PG9934P l PG9945 l PG9984P
l PG9975 l PG9935 l PG9949 l PG9985
l PG9922 l PG9938 l PG9974 l PG9994
- 267 -
Appendix 5: Regulatory approvals
The wireless supervision window shall be set to 4h for such applications and the tamper detection for removal from mounting location shall be enabled.
UL Central Station and Police Connect with Standard or Encrypted Line Security Service
l The installation must use the integral Ethernet communicator or the plug-in cellular modules Models LE9080, 3G9080 or 3H9080, which communicates over Cel-
lular Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV/5 receiver.
l Polling time shall be 200 seconds and compromise detection time shall be 6 minutes.
l For Encrypted line security applications, the integral Ethernet communicator or the plug-in cellular modules Models LE9080, 3G9080 or 3H9080 shall have the
Encryption Key enabled (AES128 bit encryption algorithm is validated under NIST Certificate No.5371 and 5372.)
l Wireless Supervision window shall be enabled (refer to Wireless Programming, sections [804]>[802].)
l Open/Closing acknowledgment shall be enabled (Not required for Police Station connected systems.)
l Bell test for police station connect.
UL Local, Central Station and Police Connect with No Line Security Service
l All zones shall be programmed as end-of-line supervised.
l All intrusion zones shall be programmed as audible.
l The installation shall use a Bell UL Listed for Mercantile local alarms (e.g., Honeywell Model AB-12M bell housing). Connections from the control unit to the bell
shall be made in conduit. (Optional for central Station).
l The Bell shall be tested daily. Alternate option is to have bell squawk enabled for arming/disarming. The Bell activation cannot be delayed for more than 5 mins.
l The bell timeout shall be programmed for 15 minutes minimum.
l At least one system remote keypad with tamper switch shall be employed
l The integral communciator (DACT/IP) or plug-in cellular module shall be enabled and shall be programmed to provide a low battery transmission.
l The control panel shall be in a separately listed HSC3030CAR attack resistant enclosure.
l The maximum entry delay time shall not exceed 45s (25s for a local) as a result of the attack test. The maximum exit delay time shall not exceed 60 s.
l A tamper switch shall be used to protect the enclosure cover of the control unit. A tamper switch shall also be used on the keypad rear to detect removal from the
wall.
l 24 h check in transmission shall be enabled.
l Open/Closing acknowledgement enabled.(Not Police Station).
l The Installation shall use the internal communicator (DACT or IP) alone or in conjunction with plug-in cellular modules Models LE9080, 3G9080 or 3H9080, which
communicate over Cellular Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV/5 receiver.
UL Home Health Care Signaling Equipment
l There must be at least two keypads, one of the compatible keyapds models HS2LCDPRO, HS2LCDRFPRO9, HS2LCDWFPRO9, HS2LCDWFVPRO9,
HS2TCHPRO(BLK).
l Each system shall be programmed to activate an audible Trouble signal within 90 seconds upon loss of microprocessor memory
ULC Central Station Fire and Burglary Monitoring Installations
l For installation requirements, levels of security, communication modules and configurations (Refer to the ULC Installation Guide for PowerSeries Pro, P/N
#29010346).
l HS2TCHPRO(BLK) touch screen keypad is for supplementary use only with ULC Commercial Fire Monitoring.
l For Commercial Fire monitoring, the primary power failure transmission may be delayed up to 3h and Bell shall be disabled.
Note: As per ULC Bulletin 2017-02A, ULC Fire and Security Systems Group is accepting the use of MFVN digital telephone services for connection of digital dialer
transmitters ULC listed to be connected to the public switched telephone network communication system. Since the MFVN communication channel technologies
available are not provided with 24 hour standby power on the equipment and facilities used between the premises and the signal receiving center, it is required that, for
passive communication channels used in monitored protective signaling system installations, the testing time of the passive communication channels should be
reduced from the current 24 hours to 6 hours to better ensure that the system and communication channels are operating in their intended manner to reduce the life
safety risk. A change in testing frequency for intrusion alarm systems is not required due to the many different levels of line security options available for these system
types, which should be applied based on communication supervision needs for each installation.
For PowerSeries Pro panels, the following programming options shall be adjusted to meet the new 6 hour test transmission when used in ULC-S561 compliant install-
ations:
l Section [022] turn option 4 ON for hours.
l Section [377] option [003] set to 006 (for 6 hours).
l Section [309] option [002] enable test transmission for all applicable receivers.
Programming
The notes in the programming sections of thePowerSeries Pro Reference Manual describing the system configurations for UL/ULC listed installations shall be imple-
mented.
Control of the Protected Premises
In order to have a UL certificated system, the protected area shall be under the responsibility of one ownership and management (i.e., one business under one name).
This may be a group of buildings attached or unattached with different addresses but under the responsibility of someone having mutual interest. The person of mutual
interest is not the alarm-installing company.
Note: This does not apply to strip mall applications where each independent business must have their own separate alarm system.
e.g.,1: A commercial partitioned system that has an office and a warehouse area in a building where each area can be armed or disarmed independently. e.g.,2: A res-
idential system partitioned so that the garage area is armed separately from the house.
Each of the above examples is under the sole responsibility of a single owner. The bell and DACT power supply must be in a protected area including partitioned sys-
tems. The bell and DACT power supply must be located where it can be heard by the person or persons responsible for maintaining the security system during the
daily arming cycle.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the person operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
- 268 -
Appendix 5: Regulatory approvals
The local control unit and the local power supply must be protected in one of the following ways:
l The control unit and audible alarm device must be in a protected area which is armed 24 hours a day.
l Each partition must arm the area protecting the control unit and the audible alarm device power supply. This may require duplicate protection armed by each par-
tition. Access to this protected area, without causing an alarm, will require that all partitions be disarmed.
l In all cases described above, the protected area for the control unit must be programmed as not-bypassable.
Casual Users
The installer should caution the user not to give system information (e.g., codes, bypass methods, etc.) to casual users (e.g., service people) and to only give out
One-Time Use codes.
User Information
The installer should advise the user and note in the User’s Manual:
l Service organization name and telephone number
l The programmed exit and entry time
l Instructions to test system weekly
l Note that the installer code cannot arm or disarm the system
- 269 -
Appendix 5: Regulatory approvals
Note: For NFA2P 2 shield installations, use 18 Ah batteries and 450 mA load for 36-hour standby. For NFA2P 3 shield install-
ations, use 18 Ah batteries and the same loadings as for EN50131 Grade 3 in the table above.
- 270 -
Appendix 5: Regulatory approvals
Notes
l Programming at installation may be subordinate to other UL requirements for the intended application.
l Cross zones have the ability to individually protect the intended area (e.g. motion detectors which overlap).
l Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.
l This control panel has a communication delay of 30 seconds. It can be removed or increased up to 45 seconds by
the end user with installer consultation.
l The system shall be installed with the sounding device activated and the communicator enabled for transmission
using SIA or CID format.
l ULC commercial burglary installations require DEOL resistors.
Table 5-1 SIA quick reference
SIA Feature Programming Section Comments Range/Default Requirement
Range:45-
Exit Time 255 seconds Required
Access to Entry and Exit delays and Bell Time Out for the system.
[005]>[001], option 3 Default: 60 (programmable)
sec.
Exit Delay Restart Opening a Delay zone door after it has already been opened and Default:
Required
[018], option 7 closed during an exit delay restarts the exit delay timer. Enabled
If no exit after
Auto Stay Arm on Un-vacated
Function key: Forces the system to arm in Stay mode if the occupant full arm
Premises Required
does not exit the premises after pressing the Away function key. Default:
[001]>[001]-[248] Zone type 05, 06,09
Enabled
System times and audible exit beeps can be disabled when using the
wireless key to stay arm the system. When away arming, audible exit
beeps can not be disabled.
Exit Time and Progress
For remote arming (using keyfob), it is possible to program the instant
Annunciation/Disable or Remote Default:
stay arm (no exit delay). By default this option is OFF. Allowed
Arming Enabled
When arming/disarming with keyfob the bell squawk option shall be
[861]>[001]-[005], option 4
enabled.
The Bell shall be tested daily. Alternate option is to have bell squawk
enabled for arming/disarming
Range: 30 Required
Access to entry and exit delays and bell time out for the system
Entry delay(s) sec. to 4 min.
Note: Combined entry delay and communications delay (abort (programmable)
[005]>[001]-[008], options 1 and 2 Default: 30
window) shall not exceed 60s.
sec.
Abort Window for Non-Fire zones Access to zone attributes, i.e., swinger shutdown, transmission delay Default: Required
[002]>[001]-[248], option 7 ON and cross zone. May be disabled by zone or zone type. Enabled
Range: 00 - 45
Abort Window Time - for Non-Fire Access to the programmable delay before communicating alarms
sec. Required
zones Note: Combined entry delay and communications delay (abort
Default: 30 (programmable)
[377]>[002], option 1 window) shall not exceed 60 seconds.
sees
An audible tone is generated when an alarm is aborted during the Hard-coded
Abort Annunciation Required
abort window. ON
Duress Feature When this feature is enabled, selected user codes send a duress
reporting code to the central station when used to perform any Default: N Required
[*][5]> master code> user 2-95> 5> 2 function on the system. Section [019], option [6] must be enabled.
Range: 005-
Cancel Window Access to the communications cancel window. Minimum duration 255
[377]>[002], option 6 must be 5 minutes.
Default: 005
A Cancel was
Cancel Annunciation transmitted Required
Access to the reporting code for Alarm Canceled.
[308]>[001], option 8 Default:
Enabled
- 271 -
Appendix 5: Regulatory approvals
Programming
Cross Zoning Enables cross zoning for entire system. Zones can be enabled for required
Required
[042]>Selection 3, option 002 cross zoning via zone attribute option 8 in sections [002][101] - [248]. Default:
Disabled
Range: 000-
Burglary Verification Timer 255 sec.
Access to the programmable Cross Zone timer. Allowed
[005]>[000], option 3 Default: 60
seconds
Swinger Shutdown for Alarms Access to the swinger shutdown limit for zone alarms. Required
Default: 2 trips
[377]>[001], option 1 For all non-fire zones, shut down at 1 to 6 trips. (programmable)
Non-police
Access to swinger shutdown, transmission delay and cross zone response
Swinger Shutdown Enable
attributes. Zone attribute option 6 (Swinger Shutdown enabled) is zones Allowed
[002]>[001] - [248], option 6 ON ON. Default:
Enabled
- 272 -
Appendix 5: Regulatory approvals
- B - use of one self-powered warning device and one ATS SP3 required (internal dialer or ethernet or plug-in cellular mod-
ule)
- C - use of dual path ATS DP2 required (any combination of internal dialer and ethernet and/or cellular module)
- D - use of an ATS SP4 required (internal ethernet or plug-in cellular module with encryption enabled)
- E - use of dual path ATS DP3 required (combination of internal ethernet and plug-in cellular module with encryption
enabled)
For EN50131 compliant installations, with alarm control panels HS3248, HS3128 and HS3032, only the intrusion portion of
the alarm system may be activated.
For EN50131 compliant installations, the following functions must be disabled:
- Fire Alarm
- CO Alarm
- Auxiliary (Medical) Alarm functions
- In Section 861-21, options 1 and 2 must be off.
For EN50131 compliant installations, the following zone types must not be used:
007 – Delayed 24-Hour Fire 041 -– 24-Hour CO 049 – 24-Hour Flood
008 – Standard 24-Hour Fire 045 – 24-Hour Heat 052 – 24-Hour Non-Alarm
025 – Auto Verified Fire 046 – 24-Hour Medical 056 – 24-Hour High Temperature
027 – Fire Supervisory 047 – 24-Hour Emergency 057 – 24 Hour Low Temperature
040 – 24-Hour Gas 048 – 24-Hour Sprinkler* 071 – Door Bell
In this configuration, no non-mandatory events are generated in the Event Buffer and compliance with minimum 500 man-
datory events storage (Grade 3) is ensured as per Section 8.10.1 in EN50131-3. Compliance labeling should be removed or
adjusted if non-compliant configurations are selected.
- 273 -
Appendix 5: Regulatory approvals
Notes for EN50136-1:2012 compliant installations - Applicable to integrated phone line and Ethernet communicator
only.
The communicator operates in pass-through mode and it does acknowledge the alarm to the compatible control panel after
an acknowledgement has been received from the compatible alarm receiver.
1. The integrated communicator is monitored by the control panel and is programmed via the menu available from the
compatible keypad connected to the alarm control panel HS3248, HS3128, HS3023.
2. The communicaton path is immune to conducted and radiated RF fields, with levels up to 10V/m as tested per
EN50130-4 Standard.
3. The control panel with integrated communication module conforms with radiated emissions levels for Class B equip-
ment as per standards EN61000-6-3/EN55032/CISPR32.
4. The control panel has two integrated communication paths: Phone line dialer and Ethernet (IP) communication path.
These can be used in an ATS with the following categories:
l Single Path mode SP3 (Phone line dialer) or SP4 (IP path), or
l Dual Path mode DP2 integrated Ethernet (IP) path in conjunction with the compatible control panel
HS3248/HS3128/HS3032 integrated PSTN communicator, or
l Dual Path DP3 integrated Ethernet (IP) path in conjunction with the plug-in cellular module 3G9080-EU or
GS9080.
5. The integrated Ethernet (IP) communication path uses sequential authentication for substitution security and encryp-
tion AES128 bit for information security. The AES128-bit key is validated by NIST, Certificate No. 5371.
6. The integrated communicators have been tested for compliance in conjunction with the following applicable stand-
ards: EN50136-1:2012, EN50136- 2:2013, EN50131-10:2014, Grade 3, Class II, ATS configuration: SP3, DP2, DP3.
For EN50131-1:2006/A1:2009 /A2:2017 compliant installations, the following programming options must be set as
described: Supervision heartbeat set to 180 seconds for SP4 and DP3 configuration, along with the ARC receiver
supervison window set to 180 seconds. For DP2 configuration, the supervison must be set to 30 minutes.
This product is in conformity with the Electromagnetic Compatibility Directive 2014/30/EU, the Low Voltage Directive
2014/35/EU, and the RoHS3 Directive (EU) 2015/863.
The product is labelled with the CE mark as proof of compliance with the above mentioned European Directives. Also, a CE
declaration of conformity (DoC) for this product can be found at www.dsc.com under the Agency Listings section.
- 274 -
Appendix 5: Regulatory approvals
ated if the initial entry door is opened before the HS3032/HS3128/HS3248 have been unset. During the entry time, it is pos-
sible to unset the alarm system using a digital key only. Complete unsetting before programmed entry delay expires.
IMPORTANT
If using a remote device to remotely set/unset your intruder alarm system, your attention is drawn to the fact that whenever a
premises is unattended but its intruder alarm system(s) is (are) not fully set, any related insurance cover might be inop-
erative. For advice on this matter, it is recommended that you consult your insurer(s).”
The CIE and notification equipment should be located and supervised to minimize the risk of vandalism or sabotage. It is
preferable for the CIE, signaling and network equipment to be located in an area where a confirmed activation will be gen-
erated.
HS3032, HS3128 and HS3248 are compliant with criteria for sequentially confirmed intruder alarm systems as per Standard
BS8243:2010.
For an alarm condition to be regarded as sequentially confirmed:
a) The HS3032, HS3128 and HS3248 should be configured so that at least two separate alarm conditions are reported,
each originating from an independent detector within the confirmation time; Section [042] option 003 (Sequential Detection),
section [005]>[000], Burglary Verification.
Timer set to a value between 30 and 60.
b) The two detectors should either be of:
1) different technologies which are permitted to have overlapping areas of coverage; or
2) the same single technology and not have overlapping areas of coverage.
To be regarded as independent, each detector should be configured to report alarm conditions separately to the HS3032,
HS3128 and HS3248.
The HS3032, HS3128 and HS3248 are capable of supporting the completion of the full setting procedure by one of the fol-
lowing methods:
a) push button switch mounted outside the supervised premises. Instructions to be provided for the zone type to be pro-
grammed for the key
arming; or
b) protective switch (i.e., door contact) fitted to the final exit door of the alarmed premises or area. Use zone type 016 (Final
Door Set) for the final exit door.
In this case the setting procedure is a two-stage process of initiating the setting procedure within the supervised premises
(e.g., using wireless key PG8929,PG8939, PG8938, PG8949 or user code) followed by completion of setting by one of the
two methods described above.
This prohibits the use of a timed exit procedure.
If a protective switch (i.e. door contact) is used as the method of completion of setting, then the keypad should be sited near
to the final exit door so that the IAS can be unset promptly. Where appropriate, additional internal audible indications
(PG8911 indoor sirens) should be provided so that persons within a building are informed that the HS3032, HS3128 and
HS3248 are due to be set. Additional keypads should be provided, where appropriate, so that if the alarm panel is set there
are means available locally within the supervised premises to unset the system.
HS3032, HS3128 and HS3248 are capable of supporting the following unsetting methods in accordance with BS8243:
6.4.2 Prevention of entry to the supervised premises before the HS3032, HS3128 and HS3248 are unset. Unsetting using
PG8929,PG8939, PG8938, PG8949 wireless key before entering the supervised premises causes or permits the initial entry
door to be unlocked. Program PGM1 or PGM2 in Section [009] to activate when system is disarmed and release the mag-
lock on the entry door.
- 275 -
Appendix 6: Wiring diagrams
ETHERNET
IN Alarm
initiating
IN NO loop
OUT resistance
ALM
100
OUT
IMPORTANT: Minimum
EOLR-2
6.4 (1/4”) separation WHT RED GRN
END-OF-LINE-
must be maintained
RESISTOR
between RM-1 circuits
4Ah 5600 0.5W
Black - and all other wiring. NOTE: Refer to Installation Manual & Smoke Detector
7Ah
2 x 7Ah
Instruction Sheet when locating detectors.
Red + 17Ah
TYPICAL ZONE CIRCUITS AC wiring details for ULC-561 using HSC3010CR
NOTE: Maximum line impedance 100 Not required for UL/ULC.
Single End-of-Line Resistor Wiring enclosure
Double End-of-Line Resistor Wiring Triple End-of-Line
Resistor Wiring
Mask
RESISTOR /Fault
IDENTIFICATIONS
2-WIRE SMOKE 3
- 276 -
Appendix 6: Wiring diagrams
6.2 HS3032 and HS3248 wiring diagram (EN50131 only) HSC3020C enclosure
POWER LIMITED
PC BOARD
Tamper switch
and mounting
bracket
PC LINK
USB TYPE A
MICRO-B CABINET
Cable tie
required
Cable tie
1x17 Ah/12V or for NFA2P required
- 277 -
Appendix 6: Wiring diagrams
6.3 HS3032 and HS3248 wiring diagram (EN50131 only) HSC3020CP enclosure
- 278 -
Appendix 6: Wiring diagrams
Mask 3
/Fault
- 279 -
Appendix 6: Wiring diagrams
To comply with NFPA 72 Temporal Three Pattern requirements, program Section [013] Opt [8] ON.
The Bell output is supervised and power limited. Connect a 1000 Ω resistor across Bell+ and Bell- to prevent the panel from
displaying a trouble. See [*][2].
Figure 6-1 Bell wiring
Note: Bell output is current limited by 2 A. Steady, Fire Pulsed, Fire Temporal Three and CO Temporal Four pattern alarms
are supported.
Module (A) is wired correctly as it is within 1000 ft / 305 m of the panel, in wire distance. Module (B) is wired correctly as it is
within 1000 ft / 305 m of the panel, in wire distance. Module (C) is NOT wired correctly as it is farther than 1000 ft / 305 m
from the panel. For models that require more than 1000 ft / 305 m from the main panel, a HSM3204CX power supply/Corbus
extender can be used.
- 280 -
Appendix 6: Wiring diagrams
- 281 -
Appendix 6: Wiring diagrams
Item Description
1
1 Nut
2
2 Earth ground connection from building electrical installation.
3
Note: This ground connection goes to HS65WPSNA power
adapter EGND connections when this power adapter is mounted
4
in the cabinet.
5 3 Cabinet
4 Star washer
6 5 Bolt
6 Earth ground symbol
- 282 -
Appendix 7: Specifications
Appendix 7: Specifications
Zone Configuration
l 32, 128 or 248 wireless zones supported and up to 8 hardwired zones available on the controller
l 41 zone types and 15 programmable zone attributes
l Zone configurations available: normally closed, single EOL resistor, DEOL resistor, and TEOL resistor.
l Hardwired zone expansion (fully supervised) available using the model HSM2108 or HSM3408 (eight zone
expander module)
l Wireless zone expansion (fully supervised) available using the HSM2Host 2-way wireless integration module oper-
ating at 915 MHz (North America), 433 MHz (Europe) and 912-919 MHz (international)
Access Codes
l Up to 1003 access codes: 1000 (level 2-EN), one installer code (level 3-EN), one maintenance code, and one guard
code.
l Programmable attributes for each user code
l Access codes are either 4, 6 or 8 digits in length, depending on the setting of programming section [041]. Duplicate
codes are not valid.
Note: For EN50131-1 Grade 2 compliant systems using 100 access codes or less, 6 digit codes must be used. If using more
than 100 access codes, 8 digit codes must be used. For EN50131-1 Grade 3 compliant systems 8 digit codes must be used.
Warning Device Output
l 2 remote, wireless indoor/outdoor warning devices supported: models PGX901 (indoor), PGX911 (outdoor) (X=4, 8,
or 9)
l Programmable as steady, pulsed or temporal three (as per ISO8201) and temporal four (CO alarm) output
l Warning device sounds alarms in the following priority: fire, CO, burg
Note: For NFA2P certified systems the delay for operating the warning device shall be set to max. 10 min.
Memory
l CMOS EEPROM memory
l Retains programming and system status on AC or battery failure for 20 years min. (not verified by UL)
Power Supply - North America
l Power Supply:HS65WPSNA (cord connected) and HS65WPSNAS (hardwired, use in ULC Commercial Burg Secur-
ity Level IV and ULC Commercial Fire Monitoring applications)
l Primary: 120 VAC, 60 Hz, Energy Efficiency Class VI
l Secondary: 18 V DC, 3.6 A Limited Power Source (LPS)
l Model HS65WPSNA mounted in the same enclosure or outside, cord connected
l Model HS65WPS mounted in the same enclosure, permanently connected
Power Supply - International
l Power Supply: HS65WPS
l Primary: 100-240 V AC, 50 Hz, 1.7 A, Energy Efficiency Class VI
l Secondary: 18 Vdc, 3.6A, LPS
l Mounted in the same enclosure, permanently connected
Note: For installations using the power supply module mounted inside the cabinet, replace fuse only with the same type (20
mm) rated New fuse rating 250 V/3.15 A Slow Blow.
Regulated power supply:
l 3.6 A regulated, supervised
l Type A as per EN50131-6 Standard
l FET protected for Bell, Aux+ and Battery terminals
l Reverse battery detection/protection
l Supervision for input power and low battery
l Normal and high current battery charge options
l Supervised battery charging circuit
Current draw (control panel board assembly):
l 120 mA (nominal)
Bell Output:
- 283 -
Appendix 7: Specifications
l Ratings:
l UL/ULC applications: 10.8 V DC - 12.5 V DC
l EN applications: 10 V DC - 14 V DC
l 700 mA supervised (1 k Ohm) bell output (current limited at 2 amps)
l Steady, Pulsed, Temporal 3 fire, Temporal 4 CO alarm cadences
l Bell open short circuit detection (software + hardware)
Aux+:
l Ratings:
l UL/ULC applications: 10.8 V DC - 12.5 V DC
l EN applications: 10 V DC - 14 V DC
l Current = 2 A (shared with Corbus R(ed) and PGM outputs)
l Output ripple voltage: 600 mVp-p max.
l Onboard programmable outputs:
l PGM 1 - 100 mA switched programmable output
l PGM 2 - 300 mA current-limited switched programmable output. 2-Wire smoke detectors (100 mA current lim-
ited) are supported using this PGM
l PGM 3 - 300 mA switched programmable output
l PGM 4 - 100 mA switched programmable output
l Hardware PGM over current protection
l The voltage at any independent power output below which the power output fault signal or message is generated:
9.8 V DC
l Over-voltage protection trigger voltage: 15 V DC
Battery
l 12 V sealed lead acid, rechargeable
l Battery capacity: Refer to table "Aux loading and battery selection" on page 270
l Maximum standby time: Refer to "Aux loading and battery selection" on page 270 for each type of application.
l Recharging time to 80% 72 hours
l Recharging rate: 400 mA (12 hours max.), 700 mA (24 hour backup)
l Backup time: 24 hours (UL)
l Battery lifespan: 3-5 years
l Low battery trouble indication threshold 11.3 VDC
l Battery restore voltage 12.5 V
l Main board current draw (battery only):
l HS3032/HS3128/HS3248 (no alternate communicator) standby 100 mA DC
l HS3032/HS3128/HS3248, (including plug-in communicator) standby 120 mA DC
l Self-reseting FETs for short/overcurrent protection on the circuit board
l Internal clock locked to the internal Real Time Clock
The standby battery does not automatically recharge on reconnection of the AC mains (external power supply) if the battery
terminal voltage is less than 9.6 VDC.
The minimum energy level of the standby battery in a charged state (as a percentage of the rated capacity for the range of
batteries that can be used with the power supply) is 90% for 17 Ah batteries.
Operating Environmental Conditions
l Temperature range: UL/ULC: 0°C to +49°C (32°F to 120°F), For EN50131 applications: -10˚C to +55˚C
l Relative humidity: 5% to 93% RH non-condensing
Note: The alarm panel is not suitable for use external to the supervised premises.
Alarm Transmitter Equipment (ATE) Specification
l Digital dialer integral to the main control board
l Supports SIA and Contact ID
l Complies with TS203 021-1, -2, -3 Telecom equipment requirements and EN50136-1, EN50136-2, ATS SP3, DP2
(when used in conjunction with Ethernet and/or Cellular paths).
l The integral Ethernet communication port and optional plug-in cellular module (models 3G9080, 3H9080, LE9080
for UL/ULC and 3G9080-EU, GS9080 for EN50131 applications) can be installed in the same enclosure and con-
figured as primary or back-up, with AES 128-bit encryption.
l Compliant with EN50136-1, EN50136-2 ATS configurations SP4, DP3.
- 284 -
Appendix 7: Specifications
- 285 -
Appendix 7: Specifications
l Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may pre-
vent the unit from detecting smoke.
l Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector
may prevent smoke from entering the unit.
l Do not locate detectors in areas of high humidity.
l Do not locate detectors in areas where the temperature rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
l Smoke detectors should always be installed in USA in accordance with Chapter 29 of NFPA 72, the National Fire
Alarm Code.
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved single- and multiple-station smoke alarms shall
be installed as follows:
1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a sleeping room, the distance measured along a path of travel.
3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics.
5. In the living area(s) of a guest suite.
6. In the living area(s) of a residential board and care occupancy (small facility).
Figure 1 Figure 2 Figure 3
Figure 3a Figure 4
- 286 -
Appendix 7: Specifications
l Write the fire escape plan down and rehearse it frequently so that should an emergency arise, everyone will know
what to do. Revise the plan as conditions change, such as the number of people in the home, or if there are changes
to the building’s construction.
l Make sure your fire warning system is operational by conducting weekly tests. If you are unsure about system oper-
ation, contact your installer.
l We recommend that you contact your local fire department and request further information on fire safety and escape
planning. If available, have your local fire prevention officer conduct an in-house fire safety inspection.
Figure 5
- 287 -
8.0 Limited warranty
Digital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the
product shall be free of defects in materials and workmanship under normal use. During the warranty period, Digital Security
Controls shall, at its option, repair or replace any defective product upon return of the product to its factory, at no charge for
labour and materials. Any replacement and/or repaired parts are warranted for the remainder of the original warranty or
ninety (90) days, whichever is longer. The original purchaser must promptly notify Digital Security Controls in writing that
there is defect in material or workmanship, such written notice to be received in all events prior to expiration of the warranty
period. There is absolutely no warranty on software and all software products are sold as a user license under the terms of
the software license agreement included with the product. The Customer assumes all responsibility for the proper selection,
installation, operation and maintenance of any products purchased from DSC. Custom products are only warranted to the
extent that they do not function upon delivery. In such cases, DSC can replace or credit at its option.
International Warranty
The warranty for international customers is the same as for any customer within Canada and the United States, with the
exception that Digital Security Controls shall not be responsible for any customs fees, taxes, or VAT that may be due.
Warranty Procedure
To obtain service under this warranty, please return the item(s) in question to the point of purchase. All authorized dis-
tributors and dealers have a warranty program. Anyone returning goods to Digital Security Controls must first obtain an
authorization number. Digital Security Controls will not accept any shipment whatsoever for which prior authorization has not
been obtained.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover:
l damage incurred in shipping or handling;
l damage caused by disaster such as fire, flood, wind, earthquake or lightning;
l damage due to causes beyond the control of Digital Security Controls such as excessive voltage, mechanical shock
or water damage;
l damage caused by unauthorized attachment, alterations, modifications or foreign objects;
l damage caused by peripherals (unless such peripherals were supplied by Digital Security Controls Ltd.);
l defects caused by failure to provide a suitable installation environment for the products;
l damage caused by use of the products for purposes other than those for which it was designed;
l damage from improper maintenance;
l damage arising out of any other abuse, mishandling or improper application of the products.
Items Not Covered by Warranty
In addition to the items which void the Warranty, the following items shall not be covered by Warranty: (i) freight cost to the
repair centre; (ii) products which are not identified with DSC's product label and lot number or serial number; (iii) products
disassembled or repaired in such a manner as to adversely affect performance or prevent adequate inspection or testing to
verify any warranty claim. Access cards or tags returned for replacement under warranty will be credited or replaced at
DSC's option. Products not covered by this warranty, or otherwise out of warranty due to age, misuse, or damage shall be
evaluated, and a repair estimate shall be provided. No repair work will be performed until a valid purchase order is received
from the Customer and a Return Merchandise Authorization number (RMA) is issued by DSC's Customer Service.
Digital Security Controls Ltd.’s liability for failure to repair the product under this warranty after a reasonable number of
attempts will be limited to a replacement of the product, as the exclusive remedy for breach of warranty. Under no cir-
cumstances shall Digital Security Controls be liable for any special, incidental, or consequential damages based upon
breach of warranty, breach of contract, negligence, strict liability, or any other legal theory. Such damages include, but are
not limited to, loss of profits, loss of the product or any associated equipment, cost of capital, cost of substitute or replacement
equipment, facilities or services, down time, purchaser’s time, the claims of third parties, including customers, and injury to
property. The laws of some jurisdictions limit or do not allow the disclaimer of consequential damages. If the laws of such a
jurisdiction apply to any claim by or against DSC, the limitations and disclaimers contained here shall be to the greatest
extent permitted by law. Some states do not allow the exclusion or limitation of incidental or consequential damages, so that
the above may not apply to you.
- 288 -
Disclaimer of Warranties
This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed or implied
(including all implied warranties of merchantability or fitness for a particular purpose) and of all other obligations or liabilities
on the part of Digital Security Controls. Digital Security Controls neither assumes responsibility for, nor authorizes any other
person purporting to act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or liability
concerning this product. This disclaimer of warranties and limited warranty are governed by the laws of the province of
Ontario, Canada.
WARNING: Digital Security Controls recommends that the entire system be completely tested on a regular basis. However,
despite frequent testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for this product
to fail to perform as expected.
Out of Warranty Repairs
Digital Security Controls will at its option repair or replace out-of-warranty products which are returned to its factory accord-
ing to the following conditions. Anyone returning goods to Digital Security Controls must first obtain an authorization number.
Digital Security Controls will not accept any shipment whatsoever for which prior authorization has not been obtained.
Products which Digital Security Controls determines to be repairable will be repaired and returned. A set fee which Digital
Security Controls has predetermined and which may be revised from time to time, will be charged for each unit repaired.
Products which Digital Security Controls determines not to be repairable will be replaced by the nearest equivalent product
available at that time. The current market price of the replacement product will be charged for each replacement unit.
WARNING - READ CAREFULLY
Note to Installers
This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring
each item in this warning to the attention of the users of this system.
System Failures
This system has been carefully designed to be as effective as possible. There are circumstances, however, involving fire,
burglary, or other types of emergencies where it may not provide protection. Any alarm system of any type may be com-
promised deliberately or may fail to operate as expected for a variety of reasons. Some but not all of these reasons may be:
Inadequate Installation
A security system must be installed properly in order to provide adequate protection. Every installation should be evaluated
by a security professional to ensure that all access points and areas are covered. Locks and latches on windows and doors
must be secure and operate as intended. Windows, doors, walls, ceilings and other building materials must be of sufficient
strength and construction to provide the level of protection expected. A reevaluation must be done during and after any con-
struction activity. An evaluation by the fire and/or police department is highly recommended if this service is available.
Criminal Knowledge
This system contains security features which were known to be effective at the time of manufacture. It is possible for persons
with criminal intent to develop techniques which reduce the effectiveness of these features. It is important that a security sys-
tem be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it
does not provide the protection expected.
Access by Intruders
Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by moving through
an area of insufficient coverage, disconnect a warning device, or interfere with or prevent the proper operation of the system.
Power Failure
Control units, intrusion detectors, smoke detectors and many other security devices require an adequate power supply for
proper operation. If a device operates from batteries, it is possible for the batteries to fail. Even if the batteries have not failed,
they must be charged, in good condition and installed correctly. If a device operates only by AC power, any interruption, how-
ever brief, will render that device inoperative while it does not have power. Power interruptions of any length are often
accompanied by voltage fluctuations which may damage electronic equipment such as a security system. After a power inter-
ruption has occurred, immediately conduct a complete system test to ensure that the system operates as intended.
Failure of Replaceable Batteries
This system’s wireless transmitters have been designed to provide several years of battery life under normal conditions. The
expected battery life is a function of the device environment, usage and type. Ambient conditions such as high humidity, high
or low temperatures, or large temperature fluctuations may reduce the expected battery life. While each transmitting device
- 289 -
has a low battery monitor which identifies when the batteries need to be replaced, this monitor may fail to operate as expec-
ted. Regular testing and maintenance will keep the system in good operating condition.
Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the radio
path or deliberate jamming or other inadvertent radio signal interference.
System Users
A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physical disability,
inability to reach the device in time, or unfamiliarity with the correct operation. It is important that all system users be trained
in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm.
Smoke Detectors
Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of reasons, some of
which follow. The smoke detectors may have been improperly installed or positioned. Smoke may not be able to reach the
smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the other side of closed doors. Smoke detectors
may not detect smoke from fires on another level of the residence or building.
Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot sense all types of
fires equally well. Smoke detectors may not provide timely warning of fires caused by carelessness or safety hazards such
as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits,
children playing with matches or arson.
Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warning to allow all
occupants to escape in time to avoid injury or death.
Motion Detectors
Motion detectors can only detect motion within the designated areas as shown in their respective installation instructions.
They cannot discriminate between intruders and intended occupants. Motion detectors do not provide volumetric area pro-
tection. They have multiple beams of detection and motion can only be detected in unobstructed areas covered by these
beams. They cannot detect motion which occurs behind walls, ceilings, floor, closed doors, glass partitions, glass doors or
windows. Any type of tampering whether intentional or unintentional such as masking, painting, or spraying of any material
on the lenses, mirrors, windows or any other part of the detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness can be reduced
when the ambient temperature rises near or above body temperature or if there are intentional or unintentional sources of
heat in or near the detection area. Some of these heat sources could be heaters, radiators, stoves, barbeques, fireplaces,
sunlight, steam vents, lighting and so on.
Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if there is an inter-
vening wall or door. If warning devices are located on a different level of the residence or premise, then it is less likely that
the occupants will be alerted or awakened. Audible warning devices may be interfered with by other noise sources such as
stereos, radios, televisions, air conditioners or other appliances, or passing traffic. Audible warning devices, however loud,
may not be heard by a hearing-impaired person.
Telephone Lines
If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time. Also an intruder
may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect.
Insufficient Time
There may be circumstances when the system will operate as intended, yet the occupants will not be protected from the
emergency due to their inability to respond to the warnings in a timely manner. If the system is monitored, the response may
not occur in time to protect the occupants or their belongings.
Component Failure
Although every effort has been made to make this system as reliable as possible, the system may fail to function as intended
due to the failure of a component.
Inadequate Testing
Most problems that would prevent an alarm system from operating as intended can be found by regular testing and main-
tenance. The complete system should be tested weekly and immediately after a break-in, an attempted break-in, a fire, a
storm, an earthquake, an accident, or any kind of construction activity inside or outside the premises. The testing should
- 290 -
include all sensing devices, keypads, consoles, alarm indicating devices and any other operational devices that are part of
the system.
Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also is not a
substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an
emergency situation.
IMPORTANT - READ CAREFULLY:
DSC Software purchased with or without Products and Components is copyrighted and is purchased under the following
license terms:
l This End-User License Agreement (“EULA”) is a legal agreement between You (the company, individual or entity
who acquired the Software and any related Hardware) and Digital Security Controls, a division of Tyco Safety
Products Canada Ltd. (“DSC”), the manufacturer of the integrated security systems and the developer of the software
and any related products or components (“HARDWARE”) which You acquired.
l If the DSC software product (“SOFTWARE PRODUCT” or “SOFTWARE”) is intended to be accompanied by
HARDWARE, and is NOT accompanied by new HARDWARE, You may not use, copy or install the SOFTWARE
PRODUCT. The SOFTWARE PRODUCT includes computer software, and may include associated media, printed
materials, and “online” or electronic documentation.
l Any software provided along with the SOFTWARE PRODUCT that is associated with a separate end-user license
agreement is licensed to You under the terms of that license agreement.
l By installing, copying, downloading, storing, accessing or otherwise using the SOFTWARE PRODUCT, You agree
unconditionally to be bound by the terms of this EULA, even if this EULA is deemed to be a modification of any pre-
vious arrangement or contract. If You do not agree to the terms of this EULA, DSC is unwilling to license the
SOFTWARE PRODUCT to You, and You have no right to use it.
The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties, as well as other intellectual
property laws and treaties. The SOFTWARE PRODUCT is licensed, not sold.
1. GRANT OF LICENSE This EULA grants You the following rights:
(a) Software Installation and Use - For each license You acquire, You may have only one copy of the SOFTWARE
PRODUCT installed.
(b) Storage/Network Use - The SOFTWARE PRODUCT may not be installed, accessed, displayed, run, shared or used con-
currently on or from different computers, including a workstation, terminal or other digital electronic device (“Device”). In
other words, if You have several workstations, You will have to acquire a license for each workstation where the SOFTWARE
will be used.
(c) Backup Copy - You may make back-up copies of the SOFTWARE PRODUCT, but You may only have one copy per
license installed at any given time. You may use the back-up copy solely for archival purposes. Except as expressly
provided in this EULA, You may not otherwise make copies of the SOFTWARE PRODUCT, including the printed materials
accompanying the SOFTWARE.
2. DESCRIPTION OF OTHER RIGHTS AND LIMITATIONS
(a) Limitations on Reverse Engineering, Decompilation and Disassembly - You may not reverse engineer, decompile, or dis-
assemble the SOFTWARE PRODUCT, except and only to the extent that such activity is expressly permitted by applicable
law notwithstanding this limitation. You may not make any changes or modifications to the Software, without the written per-
mission of an officer of DSC. You may not remove any proprietary notices, marks or labels from the Software Product. You
shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA.
(b) Separation of Components - The SOFTWARE PRODUCT is licensed as a single product. Its component parts may not be
separated for use on more than one HARDWARE unit.
(c) Single INTEGRATED PRODUCT - If You acquired this SOFTWARE with HARDWARE, then the SOFTWARE PRODUCT
is licensed with the HARDWARE as a single integrated product. In this case, the SOFTWARE PRODUCT may only be used
with the HARDWARE as set forth in this EULA.
(d) Rental - You may not rent, lease or lend the SOFTWARE PRODUCT. You may not make it available to others or post it on
a server or web site.
- 291 -
(e) Software Product Transfer - You may transfer all of Your rights under this EULA only as part of a permanent sale or trans-
fer of the HARDWARE, provided You retain no copies, You transfer all of the SOFTWARE PRODUCT (including all com-
ponent parts, the media and printed materials, any upgrades and this EULA), and provided the recipient agrees to the terms
of this EULA. If the SOFTWARE PRODUCT is an upgrade, any transfer must also include all prior versions of the
SOFTWARE PRODUCT.
(f) Termination - Without prejudice to any other rights, DSC may terminate this EULA if You fail to comply with the terms and
conditions of this EULA. In such event, You must destroy all copies of the SOFTWARE PRODUCT and all of its component
parts.
(g) Trademarks - This EULA does not grant You any rights in connection with any trademarks or service marks of DSC or its
suppliers.
3. COPYRIGHT
All title and intellectual property rights in and to the SOFTWARE PRODUCT (including but not limited to any images, pho-
tographs, and text incorporated into the SOFTWARE PRODUCT), the accompanying printed materials, and any copies of the
SOFTWARE PRODUCT, are owned by DSC or its suppliers. You may not copy the printed materials accompanying the
SOFTWARE PRODUCT. All title and intellectual property rights in and to the content which may be accessed through use of
the SOFTWARE PRODUCT are the property of the respective content owner and may be protected by applicable copyright
or other intellectual property laws and treaties. This EULA grants You no rights to use such content. All rights not expressly
granted under this EULA are reserved by DSC and its suppliers.
4. EXPORT RESTRICTIONS
You agree that You will not export or re-export the SOFTWARE PRODUCT to any country, person, or entity subject to Cana-
dian export restrictions.
5. CHOICE OF LAW
This Software License Agreement is governed by the laws of the Province of Ontario, Canada.
6. ARBITRATION
All disputes arising in connection with this Agreement shall be determined by final and binding arbitration in accordance
with the Arbitration Act, and the parties agree to be bound by the arbitrator’s decision. The place of arbitration shall be
Toronto, Canada, and the installation manual of the arbitration shall be English.
7. LIMITED WARRANTY
(a) NO WARRANTY - DSC PROVIDES THE SOFTWARE “AS IS” WITHOUT WARRANTY. DSC DOES NOT WARRANT THAT
THE SOFTWARE WILL MEET YOUR REQUIREMENTS OR THAT OPERATION OF THE SOFTWARE WILL BE
UNINTERRUPTED OR ERROR-FREE.
(b) CHANGES IN OPERATING ENVIRONMENT - DSC shall not be responsible for problems caused by changes in the oper-
ating characteristics of the HARDWARE, or for problems in the interaction of the SOFTWARE PRODUCT with non-DSC-
SOFTWARE or HARDWARE PRODUCTS.
(c) LIMITATION OF LIABILITY; WARRANTY REFLECTS ALLOCATION OF RISK - IN ANY EVENT, IF ANY STATUTE
IMPLIES WARRANTIES OR CONDITIONS NOT STATED IN THIS LICENSE AGREEMENT, DSC’S ENTIRE LIABILITY
UNDER ANY PROVISION OF THIS LICENSE AGREEMENT SHALL BE LIMITED TO THE GREATER OF THE AMOUNT
ACTUALLY PAID BY YOU TO LICENSE THE SOFTWARE PRODUCT AND FIVE CANADIAN DOLLARS (CAD$5.00).
BECAUSE SOME JURISDICTIONS DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR
CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
(d) DISCLAIMER OF WARRANTIES - THIS WARRANTY CONTAINS THE ENTIRE WARRANTY AND SHALL BE IN LIEU OF
ANY AND ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIED (INCLUDING ALL IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE) AND OF ALL OTHER OBLIGATIONS OR
LIABILITIES ON THE PART OF DSC. DSC MAKES NO OTHER WARRANTIES. DSC NEITHER ASSUMES NOR
AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR TO CHANGE THIS
WARRANTY, NOR TO ASSUME FOR IT ANY OTHER WARRANTY OR LIABILITY CONCERNING THIS SOFTWARE
PRODUCT.
(e) EXCLUSIVE REMEDY AND LIMITATION OF WARRANTY - UNDER NO CIRCUMSTANCES SHALL DSC BE LIABLE
FOR ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL OR INDIRECT DAMAGES BASED UPON BREACH OF WARRANTY,
BREACH OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, OR ANY OTHER LEGAL THEORY. SUCH DAMAGES
INCLUDE, BUT ARE NOT LIMITED TO, LOSS OF PROFITS, LOSS OF THE SOFTWARE PRODUCT OR ANY ASSOCIATED
EQUIPMENT, COST OF CAPITAL, COST OF SUBSTITUTE OR REPLACEMENT EQUIPMENT, FACILITIES OR SERVICES,
DOWN TIME, PURCHASERS TIME, THE CLAIMS OF THIRD PARTIES, INCLUDING CUSTOMERS, AND INJURY TO
- 292 -
PROPERTY.
WARNING: DSC recommends that the entire system be completely tested on a regular basis. However, despite frequent test-
ing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for this SOFTWARE PRODUCT to
fail to perform as expected.
- 293 -
The trademarks, logos, and service marks displayed on this document are registered in the United States [or other countries]. Any mis-
use of the trademarks is strictly prohibited and Tyco will aggressively enforce its intellectual property rights to the fullest extent of the
law, including pursuit of criminal prosecution wherever necessary. All trademarks not owned by Tyco are the property of their respect-
ive owners, and are used with permission or allowed under applicable laws.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products
include all features. Availability varies by region; contact your sales representative.