'RAUP IOM-Aug06
'RAUP IOM-Aug06
'RAUP IOM-Aug06
Operation
Maintenance
Split System
Condensing Units
20-55 Tons
Models
RAUP 250, RAUP 300,
RAUP 400, RAUP 500, RAUP 600
Foreword
These installation operation and maintenance instructions are for the continued successful operation of this equipment. The
given as a guide to good practice in the installation, putting, into services of a qualified service technician should be employed
service, operation and periodic maintenance by the Trane Product through the medium of a maintenance contract with a reputable
user. They do not contain the full service procedures necessary service company.
Warranty
Warranty is based on the general terms and conditions of The limits are exceeded or if the control system or the electrical wiring
Trane Company. The warranty is void if the equipment is repaired is modified. Damage due to misuse, lack of maintenance or failure
or modified without the written approval of Trane, if the operating to comply with the manufacturer’s instructions or recommendations
is not covered by the warranty obligation.
Receiving/Handling
On arrival, inspect the unit before signing the delivery note. Specify If any concealed damage is discovered, stop unpacking the
any damage on the delivery note, and send a registered letter of shipment . Take photos of the damaged material if possible. Notify
protest to the last carrier of the goods within 72 hours of delivery. the Carrier immediately by phone and registered mail. Notify the
Notify the local Trane Sales Office at the same time. The unit local Trane Sales office. Concealed damage must be reported
should be totally inspected within 15 days of delivery. within 15 days of delivery.
(i)
Contents
Performance Data
Foreword (i)
Warranty (i)
Receiving / Handling (i)
Nomenclature 1
General Data 20-55 Ton Condensing Unit 2
Installation
General Information 3
Unit Nameplate 3
Machine Room Installation Requirements 3
Vibration Isolators (option) 3
Electrical Connections 5
Unit Start-up 5
Operation / Maintenance
Unit Operation 7
Seasonal start-up procedure 7
Maintenance
Maintenance 7
Weekly Maintenance 7
Maintenance Inspections 8
Compressor
Motor Winding Thermostat 9
Compressor Manifold Piping 9
Trouble Analysis 10 to 12
Dimensional Data
Dimensional Data Condensing Unit 13 to 17
Wiring Diagram
Schematic & Termination Diagram 18 to 29
Installation Checklist 30
Commissioning Log Sheet 31
(ii)
MODEL NOMENCLATURE
MODEL NOMENCLATURE
EG:
R A U P 2 5 0 D 1 B 0 A
1 2 3 4 5 6 7 8 9 10 11 12
Digit Description
A Air Cooled
U Unit Airflow-Upflow
P Development Sequence
A Service Indicator
1
Table 1 General Data Outdoor Unit
1
MCA - Minimum Circuit Ampacity is 125% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the motor RLA.
2
At 7 deg C SST and 35 deg C Ambient, 400V, Subcooling 8.3 K, Superheat 11.1 K.
3
Nominal Airflow is rated with standard air-dry coil.
2
Installation
Unit nameplate
The unit nameplate gives the full model reference. The power
supply of the unit is specified and must not vary by more that 5%
of the specified voltage.
Foundation
A special base or foundation is not required when the floor is
level and of sufficient strength to support the unit's weight.
Clearances
Provide sufficient clearance around the unit for performance of
service and maintenance. Caution unit operation is a function of
the air temperature. Any recycling of the air fed out by the fans
will increase the air intake temperature over the condense fins
and result in a high temperature out. Make sure nothing prevents
air flow to run through the unit coils. Refer to dimensional drawing Vibration Isolators (option)
recommended for detailed clearances, under “Dimensional Data”
section. Vibration isolators (rubber pads) are recommended and are to be
placed under the unit feet. The unit is levelled by placing the
3
Installation
Refrigerant circuit Pressure and leak testing
One circuit on sizes 250 and 300, and two circuits on When pressure and leak testing, these safety precautions
sizes 400, 500 and 600. Single circuit units will have must be adhered to:
two compressors manifolded. Both circuits of the four 1. Do not work in a closed area where refrigerant may
compressor units are manifolded. Refrigerant connections be leaking- a sufficient quantity of vapors may be
not connected are sealed and plugged. present to cause personal injury. Provide adequate
ventilation.
Refrigerant pipe connections 2. Do not use oxygen or ecetylene in place of refrigerant
Determination of the size of the pipe connections. and dry nitrogen for leak testing- a violent explosion
may result.
Liquid line 3. Always use a pressure regulator , valves and gauges
Size the liquid line on the basis of: to control drum and line pressures when pressure
1. Full load operating conditions. testing the system. Excessive pressures may cause
2. A pressure drop of 100 kPa maximum. line ruptures, equipment damage or an explosion
3. A liquid velocity not exceeding 3 m/s (to avoid resulting in personal injury.
hammer).
Pressure test the liquid line , and suction line at pressures
Suction line dictated by local codes.
Design the suction line to provide sufficient gas velocity
in both horizontal and ver tical runs to carry the Caution: Do not exceed the high pressure control
compressor oil and ensure a uniform rate of return to setting plus 0.7 bar. Test pressures on liquid line and
the compressor. Size the hot gas line on the basis of: on suction line must comply with local and national
1. Producing gas velocity in horizontal runs at least codes.
2.5 m/s at minimum operating conditions.
2. Producing gas velocity in vertical risers at least 5
m/s at minimum operating conditions. Charge enough refrigerant into the system to raise the
3. Gas velocity should not exceed 20 m/s under pressure to 1 bar. Using oil-pumped dry nitrogen, build
maximum load conditions. the system pressure to 7 bar.
4. Maximum pressure drop in suction line should not Check the piping and the evaporator unit for leaks with
exceed 20 kPa. a leak detector. Be very thorough in this test, checking
every possible point of leakage. If leaks are found
during the testing, release the test pressure, break the
Pitch the horizontal run of suction line toward the connection and make a new joint. Retest to make sure
evaporator. the connection is solid.
1
Note: MCA = Minimum circuit ampacity = 125% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan RLA.
2
Maximum fuse size = 225% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan RLA.
4
Installation
When hooking a vacuum pump to a refrigeration system, Caution :
it is important to connect the pump to both the high and 1. All wiring should comply with local and national
low side of the system. codes. Type and location of disconnect switches
Follow the pump manufacturer’s directions as to the should comply with local and national codes. Install
proper methods of using the vacuum pump . disconnect switch near unit, within sight, for safety.
The lines used to connect the pump to the system should 2. Use copper conductors only for installation wiring.
be copper and of the largest diameter that can pratically Unit terminals are not designed to accept other type
be used. Using larger line sizes with minimum flow of wiring. The use of aluminium wire may cause
resistance can significantly reduce evacuation time. galvanic corrosion and/or overheating at the
Rubber or synthetic hoses are not acceptable for unit connection points with resultant equipment failure.
evacuation because they have moisture absorbing
characteristics which result in excessive rates of Unit Start-Up
outgassing and pressure rise during standing vacuum Preparation for start-up
test. This makes it impossible to determine if the unit has Before starting the unit, use the following procedures
a leak. to ensure that the unit is completely and
An electronic thermopile vacuum gauge should be installed properly installed and ready for start-up.
in the common line ahead of the vacuum pump shutoff The installer must make sure that the following points
valve as shown in Figure 2. Close Valve B and open are checked before the initial start-up.
Valve A. After several minutes, the gauge reading will 1. Inspect all wiring connections. Connections should
indicate the minimum blank-off pressure the pump is be clean and tight. Trace circuits to ensure that wiring
capable of pulling . Rotary pump should produce vacuum agrees with wiring diagrams provided with the unit.
of less than 100 microns. Information in the title block of the wiring diagram
Open Valve B and evacuate the system to a pressure of should match the data that appears on the unit
500 microns or less. Valve A must be closed when taking nameplate.
this reading. Once 500 microns or less is obtained, with 2. Close the unit power fused disconnect switch and
Valve A closed, a time versus pressure rise should be the manual disconnect switch.
performed. The maximum allowable rise over a 15 minute 3. Check the unit supply voltage to ensure that the
period is 200 microns. If pressure rise is greater than voltage is within the utilization range.
200 microns but levels off to a constant value, excessive 4. Check the compressor oil level.
moisture is present. If the pressure steadily continues to 5. Check with a phase-meter the direction of rotation
rise, a leak is indicated. of scroll Trane compressors or check the good
operation of the discharge and suction pressures.
6. As the various motors of the system are started,
Figure 2 check the direction of rotation and make sure that
the driven equipment is operating satisfactorily.
Vacuum pump connection.
7. Ensure sufficient cooling load available at day of
start-up (minimum of 50% of design load).
Preparation
Before putting the system into operation, perform these
service and check-out procedures :
1. Before making any electrical power connections make
sure that the insulation resistance of all power terminal
to earth is in accordance with the international electrical
codes. Measure the insulation of all electrical motors
using a 500 V DC tester and refer to the manufacturer’s
specifications.
Warning :
No motor should be started if the insulation resistance
is less than 2 mega ohms. Under no circumstances
should any voltage be applied to a motor while it is
under vacuum.
2. Check the unit supply voltage to ensure that the voltage
is within the utilization range.
Electrical Connections
Wiring diagrams are furnished with the units, but extra Caution :
copies may be obtained from the local Trane sales office. Phase unbalance must not exceed 2% . Supply for all
The installing contractor is to provide and install fused motors is to be within plus or minus 5% of the voltages
disconnect switches and the wiring up to the unit control specified on the compressor nameplate.
panel. Check all wiring connections and trace the circuits
to make sure that they agree with the wiring diagrams.
3. Place all refrigerant circuit valves in operating position.
5
Installation
4. Reset all controls equipped with a manual reset function. Oil level
Oil should be visible in the compressor, under full load, in
Refrigerant charging the compressor oil level sight glass. The unit was charged
After the refrigeration pipework system has been pressure with the proper amount of oil before shipping. Under normal
tested and evacuated, and meets the vacuum pressure operation, compressor oil is always expected to return to
requirements of paragraph <<Field evacuation>>, the compressor oil sump, and no additional oil should be added.
refrigerant may be charged as follows. Be sure to follow the For oil level indication, refer to compressor oil sight glass, as
start-up procedure at the same as charging the refrigerant. per Figure 3. If oil is within sight glass visibility, oil quantity
1. Loosely connect a cylinder of refrigerant to the 1/4” OD should be sufficient.
Charging Valve Located on the liquid line.
2. Open and close the valve on the refrigerant cylinder to Refrigerant pressures
purge the connection. Tighten the coupling nut. Observe operating pressures. If pressures are above or
3. Invert the refrigerant cylinder so that only liquid will enter below normal see <<Trouble Analysis>> section. Normal
the system operating pressures are in Table 2. A High & Low pressure
4. Allow the compressor to continue running throughout the settings are found in Table 1
remainder of the charging operation. Do not allow the
pressure to fall bellow 0.15 bar. Liquid line sight glass (Optional)
The flow of refrigerant through the sight glass should be
smooth and without bubbles. Bubbles indicate a refrigerant
Caution: shortage and probably a leak, or a restriction in the liquid
Do not attempt to start the compressor by blocking the line.
safety controls. Allow the condensing unit to function
in a normal manner. Superheat
Normal Superheat is 6 to 8 deg C. Overfeeding of the
evaporator results in high suction pressure, low superheat
5. Allow the system to continue functioning for approximately and possible liquid carryover. Inadequate or too high a
30 minutes. If during this period bubbles appear in the superheat is remedied by adjusting stem on the thermostatic
liquid line sight glass, add refrigerant. expansion valve (TEV). If this fails to correct the condition,
6.Leak-test the refrigerant circuit. then the valve cage or power element of the TEV may be
defective and should be replaced.
Start-up procedure
1. Start the unit by switching to <<On>> Caution:
2. After the unit has started, allow it to operate for at least 1. Excessive foaming indicates the presence of
15 minutes to stabilise operating pressures. Then check : refrigerant in the oil and will result insufficient
- compressor oil level. compressor lubrication. Turn off the motor and
- compressor and fan motor power consumption. investigate the cause.
- suction pressure. 2. An excess of the oil in the compressor can cause
- discharge pressure. problems in the same way as a lack of oil. Before
- liquid line sight glass. topping up , contact a qualified service technician.
- superheat. Use only Tranerecommended oils.
- subcooling.
Figure 3 - Compressor oil level
All readings and measurement should be logged.
Procedures are given below.
Maximum
oil level
Minimum
oil level
CAUTION
PHASE ROTATION IS CRITICAL
IF SUCTION PRESSURE DOSE NOT FALL TO EXPECTED
OPERTATING LEVEL WITHIN THIRTY (30) SECONDS
AFTER COMPRESSOR IS STARTED, COMPRESSOR
WARNING
1. Do NOT run the compressor on reverse rotation
ROTATION MAY BE REVERED. 2. Do NOT perform any pump down cycle with Scroll
compressor
TO REVERSE ROTATION, DISCONNECT ALL UNIT POWER 3. Do Not run the compressor below the setting of low
AND REVERSE ANY TWO (2) INCOMING POWER LEAD pressure switch
WIRES AT THE UNIT HIGH VOLTAGE TERMINAL BLOCK. 4. Do NOT by pass any safety devices when operating the
RECONNECT ALL UNIT POWER, RESTART UNIT, AND system.
RE-CHECK SUCTION PRESSURE. Failure to observe any of the above will cause severe
damage to the Scroll compressors.
6
Operation / Maintenance
Figure 3A
PIPING DETAILS OF REFRIGERANT COILS
SOLENOID
LIQUID VALVE
EXPANSION VALVE
CAPILLARY TUBES
STRAINER SIGHT
GLASS
EXPANSION VALVE
THERMAL BULBS
EXPANSION
VALVE
HP
4m/s LP
max. 4m
U-trap
8 to 12m/s
max. 4m
Evaporator Figure 3C
4m/s
Figure 3B Maintenance
Table 2 - Normal operating conditions
Ambient Temperature (C) The following maintenance are given as an essential part of
25 30 40 the required maintenance of this equipment. However the
services of a qualified services technician are required to
Discharge pressure (bar) 14-17 17-19 22-25 perform the periodic maintenance procedures as part of a
Suction pressure (bar) 4-6 4-6 4-6 regular maintenance contact. Perform all maintenance
procedures at the scheduled intervals. This will prolong the
life of the unit and reduce the possibility of costly equipment
Final checkout failure. Use an <<operator’s log>> to record a weekly
Run the unit sequentially through its stages of cooling.
Once proper unit operation is confirmed, perform these final <<operator condition history>> for this machine. The operating
steps: log for this unit can be a valuable diagnostic tool for service
1.Inspect the unit for debris and/or misplaced tools and personnel also, the operator, by noticing trends in the operating
hardware. conditions can often foresee and prevent problem situations
2.If the unit is operated immediately, be sure all valves are before they become serious. It may be required for inspection
in operating position.
3.Secure all panels including control panel in place. in the event of warranty claim.
Table 2A
General interconnecting line sizes.
LENGTH OF INTERCONNECTING LINES(FT)**
0-20 21-40 41-60 61-80 81-100 101-120 121-140 141-160 161- 180 181-200
CONDENSING LINE SIZE - O.D.(IN.)
UNIT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT
5
RAUP 400 /8 1 5/8 7
/8 1 5/8 7
/8 1 5/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8
7 5 7 5 7 1 7 1 7 1 1 1 1 1 1 1 1 1
RAUP 250,500 /8 1 /8 /8 1 /8 /8 2 /8 /8 2 /8 /8 2 /8 1 /8 2 /8 1 /8 2 /8 1 /8 2 /8 1 /8 2 /8
7
RAUP 300,600 /8 1 5/8 7
/8 2 5/8 7
/8 2 1/8 7
/8 2 1/8 1 1/8 2 1/8 1 1/8 2 1/8 1 1/8 2 1/8
** In shaded region, use 2 1/8 for all horizontal runs, and 1 5/8 for all vertical risers.
However, for correct and proper pipe sizing, it is
recommended to size piping based on Trane
recommended piping guide or use computer aided
software where applicable
8
Compressor
Table 2B
Compressor Manifold Piping Compressor Sequencing
The compressor refrigerant piping Unit Control Circuit Circuit
manifold system was purposely designed Size Step Comp.1 Comp.2
to provide proper oil return to both
250 1 1 (50%) -
compressors; therefore, the original
refrigerant manifolding system should 300 2 1,2 (100%) -
not be modified in any way! 400 1 1 (50%) -
500 2 1,2 (100%) -
If a compressor replacement is required,
do not alter the compressor manifold 600 3 1,2 (100%) 3 (50%)
piping; improper oil retur n and 4 1,2 (100%) 3,4 (100%)
compressor failure could result.
If a suction filter is required, install it a
minimum of 18” upstream of the
compressor manifold piping.
See Figure 4 Note: 1, 2, 3 and 4 indicate which compressor in the unit is operat-
Caution : Altering the original ing. (%) indicates the amount of the circuit in the operation during a
manifold piping may cause oil given step. Refer to dimensional data for the location of the compressors
compressor failure. 1, 2, 3 and 4 in the RAUP unit.
Figure 4 :
Location Requirements for Suction
Line Filter Installation after Motor
Burnout
Compressor 2 Compressor 1
Minimum 18 straight,
unobstructed piping
to suction line filter
Suction Line
Note: Anytime one compressor is
replaced, the oil charge for the (Compressor 1)
remaining compressor must be
replaced. Common
Suction Gas
from Evaporator
9
Trouble Analysis
B. Compressor stops
Problems and symptoms Probable Cause Recommended action
10
Trouble Analysis
C. Compressor shortcycles
Problems and symptoms Probable cause Recommended action
Suction pressure too low and Restricted liquid liner driver. Replace driver core.
frosting at driver.
High temperature in conditioned Excessively high cooling load Check infiltration and insulation
space of conditioned space.
Oil level too low (sight glass). Insufficient oil charge. All oil.
Excessively cold suction. Liquid flooding back to compressor Readjust superheat setting
Noisy compressor and verify correct bulb
mounting.
F. Compressor is noisy
11
Trouble Analysis
Too little or too warm condenser air. Excessively warm air leaving Clean coil, check fan and motor
condenser. for proper operation.
Restricted air flow. Cuts out on high pressure control.
Abnormally cold suction line; liquid a) Expansion valve opens too far. a) Adjust superheat and check
flood-back to compressor. bulb attachment.
b) Expansion valve stuck in open b) Repair or replace.
position.
No refrigerant flow through Expansion valve power element has Replace valve power element.
expansion valve. lost charge.
Superheat too high. Too much pressure drop in Check external equaliser of
evaporator. expansion valve.
This is by no means a complete analysis of the scroll provide the background necessary for him to recognize
refrigeration system. Instead, its intention is to familiarize and accurately correct or report any developing problem.
the operator with the operation of the scroll unit and
12
13
14
15
16
17
Schematic &
Termination Diagram RAUP 250
FUSED
EVF-OL
STOP
DISCONNECT
MCB
C1 C2 NOTES:
1 DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
COMPR. 1 COMPR. 2 CF1 CF2 AND/OR DASHED DEVICE OUTLINES INDICATE
STEP 1 STEP 2 COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
3 2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER
T1 MCB IS INSTALLED
32 31
T2 3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF INTERLOCK INTERLOCK
T3
30
J2 INPUT J1
33
WARNING
HAZARDOUS VOLTAGE!
STARTER CONTROLLER
220V DISCONNECT ALL ELECTRIC POWER
POWER MODULE INCLUDING REMOTE DISCONNECTS
33 30
SUPPLY BEFORE SERVICING.
240 0
FAILURE TO DISCONNECT POWER
TX1 J5 J4 OUTPUT J3 BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.
PT
240 V - CONTROL WIRING
L1 L2 L3 N E
30
31
J3 J3
J3
32A
32B
C1 C2
30
34 30 35 30 FOR CCH C5 31
FOR CCH OPTION 36 30
OPTION A1 A2 A1 A2 32 33 30
32 FOR CCH
32
MCB
T1 T2 T3 T4 T5 T6 T7 OPTION
32A
32B C5
A-C1 A-C2
32
CCH1 CCH2
TO STARTER
CONTROLLER TX1
JUMPER J2
18
Schematic &
Termination Diagram RAUP 250
9 3
G RRR
S1
5
200mm 10 140mm
L1 L2 L3 N E
5T2
5T3
5T1
E 8
ADD FOR CCH OPTION
1TB5
800mm
TB
MODULE
CONTROLLER
STARTER
12 14 12 14
J1
2
MCB
A-C1 A-C2 C5
J3
390mm
T1
T2
T3
T4
T5
T6
T7
255mm
226mm
11
J2
8
J4
9
240V/24V
6 7 COMP. # 2
TX1
4
CONTROL LINE
J5
1
385mm
* 6 TERMINAL BLOCK, 3P 1
7 TERMINAL END PLATEL 1
POWER TOTAL
CABLE LENGTH 8 TERMINAL STOPPER 7
SIZE
9 TERMINAL RAIL, Total Length 700
2 _
COMP #1 6mm 10 WIRE DUCT, Total Length 1666
2
11 CONTACTOR FOR FAN MOTOR W/AUXILLARY CONTACT 1
COMP #2 6mm _
12 CONTACTOR FOR COMPRESSSOR 2
13 PANEL, STARTERL 1
** 14 AUXILLARY CONTACTOR 2
19
Schematic &
Termination Diagram RAUP 250
-
LPCO 2
JUMPER COM 0 WARNING : - CONTACT INPUTS ONLY J4 T2 T3
t4 HMWT 4 Error
S1 - S4 THERMOSTAT STATUS
TX1
INPUT: USE BLACK COLOR 0.5 SQMM. OUTPUT: USE BLACK 1 SQMM.
TERMINATION (CONTROL)
N
NOTES:
32 33 30 1 DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
CONTROL BOX
20
Schematic &
Termination Diagram RAUP 300
FUSED
EVF-OL
STOP
EVF-C
J2 INPUT J1
33
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
STARTER CONTROLLER INCLUDING REMOTE DISCONNECTS
220V MODULE
POWER BEFORE SERVICING.
33 30
SUPPLY FAILURE TO DISCONNECT POWER
240 0
BEFORE SERVICING CAN CAUSE
TX1 J5 J4 OUTPUT J3 SEVERE PERSONAL INJURY OR DEATH.
IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.
PT
240 V - CONTROL WIRING
L1 L2 L3 N E
30
31
J3 J3
J3
32A
32B
C1 C2
30
30 30 C5 31
34 35
FOR CCH FOR CCH 36 30
OPTION A1 A2 A1 A2 OPTION 32 33 30
32 32 FOR CCH
MCB
T1 T2 T3 T4 T5 T6 T7 OPTION
32A 32B C5
A-C1 A-C2
95 95 32
OL1 OL2 CCH1 CCH2
96 96
TO STARTER
41 42 43 CONTROLLER TX1
{
J2
JUMPER
TO J1
21
Schematic &
Termination Diagram RAUP 300
9 3
G R RR
S1
5
200mm 10 140mm
L1 L2 L3 N E
5T2
5T3
5T1
E 8
ADD FOR CCH OPTION
1TB5
800mm
TB
MODULE
CONTROLLER
STARTER
13 15 13 15
J1
2
MCB
A-C1 A-C2 C5
J3
390mm
T6
T7
T2
T3
T4
T5
T1
255mm
226mm
11
J2
8
J4
9 OL 1 OL 2
240V/24V
4 6 7 COMP. # 2
TX1
12 12
CONTROL LINE
J5
1
385mm
* 6 TERMINAL BLOCK, 3P 1
7 TERMINAL END PLATE 1
POWER TOTAL
CABLE LENGTH 8 TERMINAL STOPPER 7
SIZE
9 TERMINAL RAIL, Total Length 700
2 _
COMP #1 6mm 10 PVC TRUNKING 1", Total Length T 1666
2
11 CONTACTOR, FAN 1
6mm _
COMP #2
12 OVERLOAD CONTACTOR 2
13 CONTACTOR FOR COMPRESSOR 2
14 PANEL, STARTERLA 1
** 15 AUXILLARY CONTACTOR 2
22
Schematic &
Termination Diagram RAUP 300
-
LPCO 2 WARNING : - CONTACT INPUTS ONLY
- NO AC SIGNAL AT INPUTS
JUMPER COM 0 J4 T2 T3
HPCO 2 ALM/NC
OL 3 COM
JUMPER COM 0 ALM/NO
OL 4 TRIP
HMWT 3 LIGHT
JUMPER COM 0 7 SEGMENT DISPLAY CODE TABLE
HMWT 4 7 Segment Display Error Description
2
-- NORMAL
S1 L1 LPCO 1 Error
TO TEMP. CONTROLLER STEP 1
COM 0 H1 HPCO 1 Error N L (240 V)
O1 OL 1 Error
JUMPER CIRCUIT A
2
S2 O2 OL 2 Error
t1 HMWT 1 Error
TO TEMP. CONTROLLER STEP 2
S3 t2 HMWT 2 Error
COM 0 L2 LPCO 2 Error
JUMPER H2 HPCO 2 Error
240V/21, 8V
S4 O3 OL 3 Error
O4 OL 4 Error
CIRCUIT B
J5
t3 HMWT 3 Error
TX1
t4 HMWT 4 Error
S1 - S4 THERMOSTAT STATUS
INPUT: USE BLACK COLOR 0.5 SQMM. OUTPUT: USE BLACK 1 SQMM.
TERMINATION (CONTROL)
NOTES:
N
CONTROL BOX
BEFORE SERVICING CAN CAUSE 2 SECONDS AND RETURN TO DISPLAY THE EXISTING
SEVERE PERSONAL INJURY OR DEATH. ERROR/STATUS CODES.IF MORE THAN 1 ERROR HAPPENS,
THEY ARE DISPLAYED 2 SECOND EACH.IF THERE IS NOT ANY
IMPORTANT MEMORABLE ERRORS,THE NORMAL CODE WILL BE DISPLAYED.
PRESS AND HOLD SW3 BUTTON FOR 4 SECONDS TO
CLEAR THE MEMORABLE ERROR.
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED 3
TO ACCEPT ANY OTHER WIRING.
23
Schematic &
Termination Diagram RAUP 400-500
NOTES: LEGEND
SEE UNIT NAMEPLATE 1 DASHED LINES INDICATE RECOMMENDED FIELD
FOR LINE VOLTAGE WIRING BY OTHERS. DASHED LINE ENCLOSURES
DEVICE
DESCRIPTION
L1 L2 L3 N FUSED DISCONNECT SWITCH EVF-C / EVF-OL AND/OR DASHED DEVICE OUTLINES INDICATE DESIGNATION
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE LPCO LOW PRESSURE CUT-OUT
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING. HPCO HIGH PRESSURE CUT-OUT
EVF
2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER HMWT HIGH MOTOR WINDING T-STAT
IS INSTALLED
OL 1, 2, 3, 4 INTERNAL OVER LOAD, COMPRESSOR
3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF-OL INTERNAL PROTECTOR, EVAPORATOR FAN
INTERLOCK
EVF-C STARTER, EVAPORATOR FAN
A-C1, A-C2, B-C3, B-C4 STARTER, COMPRESSOR
START
EVF-OL
STOP
MCB
FUSED
S1 SYSTEM SWITCH
DISCONNECT
CF 1, 2, 3, 4 FAN, CONDENSOR
SWITCH
EVF-C(AUX) MCB CIRCUIT BREAKER
L1 L2 L3 N
PT C5 STARTER, CONDENSOR FAN
PT POWER TERMINALS
TB TERMINATION BLOCK
SUPPLIED & INSTALLED BY CUSTOMER
FACTORY INSTALLED
TERMINATION BLOCK, CONTROL
TX1 TRANSFORMER 240V : 21V, 8V
C1, C2, C3, C4 COMPRESSOR
A-C1 A-C2 B-C3 B-C4
C5 CCH CRANKCASE HEATER
C1 C2 C3 C4
3
T1 MCB
32 31
FOR RAUP500 ONLY
T2
EVF INTERLOCK
WARNING
HAZARDOUS VOLTAGE!
T3
30 DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
J2 INPUT J1 FAILURE TO DISCONNECT POWER
33 BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
TX1 J5 J4 OUTPUT J3
L1 L2 L3 N E
30
31
J3 J3 J3 J3
J3
32C
32D
32A
32B
C4 C2 C3 C1 32
30
30
C5 37 30 36 30 35 30 34 30 31
30 FOR CCH 32 FOR CCH
OPTION OPTION FOR CCH
32 33 30 OPTION
32 A1 A2 A1 A2 A1 A2 32
MCB
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11
C5 32D 32C 32B 32A
B-C4 B-C3 FOR CCH A-C2 A-C1
OPTION
32
JUMPER
TO STARTER
CONTROLLER TX1
J2
24
Schematic &
Termination Diagram RAUP 400-500
PT
L1 L2 L3 N E E
5T2
5T3
5T1
7
1TB5
1000mm
2 8 9
B-C4 B-C3 A-C2 A-C1
10
8
MCB
J3 J4 J5 500 mm C5
240V/21, 8V
11 12 14 12 14 12 14 12 14
TX1
9
STARTER
CONTROLLER 4
MODULE 582mm
1
CIRCUIT # B TB
J1 J2
345mm
9
345mm
CONTROL LINE
T4
T6
T7
T1
T2
T3
T5
CIRCUIT # A
CONTROL LINE
374mm 6
COMPRESSOR #1
COMPRESSOR #4-POWER LINE ADD FOR CCH OPTION
COMPRESSOR #3-POWER LINE POWER LINE
COMPRESSOR #2-POWER LINE
* * 14 AUXILLARY CONTACTOR 4
25
Schematic &
Termination Diagram RAUP 400-500
-
LPCO2
44 LPCO 2
45
45
COM 0 WARNING : - CONTACT INPUTS ONLY J4 T2 T3
HPCO2
46 HPCO 2 - NO AC SIGNAL AT INPUTS ALM/NC
OL 3 COM
COM 0 ALM/NO
OL 4 TRIP
HMWT 3 7 SEGMENT DISPLAY CODE TABLE LIGHT
COM 0 7 Segment Display Error Description
-- NORMAL
2
HMWT 4 L1 LPCO 1 Error
S1 H1 HPCO 1 Error
TO TEMP. CONTROLLER STEP 1
COM 0
O1
O2
OL 1 Error
OL 2 Error
CIRCUIT A N L (240 V)
TO TEMP. CONTROLLER STEP 2
2
S2 t1 HMWT 1 Error
t2 HMWT 2 Error
TO TEMP. CONTROLLER STEP 3
S3 L2 LPCO 2 Error
COM 0 H2 HPCO 2 Error
240V/21, 8V
t4 HMWT 4 Error
S1 - S4 THERMOSTAT STATUS
INPUT: USE BLACK COLOR 0.5 SQMM. OUTPUT: USE BLACK 1 SQMM.
NOTES:
INTERLOCK
4 PRESS SW3 BUTTON FOR SHOW THE MEMORABLE ERROR.
IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.
26
Schematic &
Termination Diagram RAUP 600
2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER HMWT HIGH MOTOR WINDING T-STAT
IS INSTALLED
OL 1, 2, 3, 4 EXTERNAL OVER LOAD, COMPRESSOR
3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF-OL INTERNAL PROTECTOR, EVAPORATOR FAN
INTERLOCK
EVF-C STARTER, EVAPORATOR FAN
START
EVF-C
C1 C2 C3 C4
3
T1 MCB
32 31
T2
EVF INTERLOCK
T3
30
J2 INPUT J1 WARNING
33 HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
STARTER CONTROLLER BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
POWER
33
240V
30 MODULE BEFORE SERVICING CAN CAUSE
SUPPLY SEVERE PERSONAL INJURY OR DEATH.
240 0
L1 L2 L3 N E
30
31
J3 J3 J3 J3
J3
32C
32D
32A
32B
C4 C2 C3 C1 32
30
30
C5 37 30 36 30 35 30 34 30 31
30 FOR CCH 32 FOR CCH
OPTION OPTION FOR CCH
32 33 30 OPTION
32 A1 A2 A1 A2 A1 A2 32
MCB
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11
C5 32D 32C 32B 32A
B-C4 B-C3 FOR CCH A-C2 A-C1
OPTION
95 95 95 95 32
55 54 53 44 43 42 JUMPER
{
TO J2 TO J1 TO STARTER
CONTROLLER TX1
J2
27
Schematic &
Termination Diagram RAUP 600
PT
L1 L2 L3 N E E
5T2
5T3
5T1
7
1TB5
1000mm
2 8 9
B-C4 B-C3 A-C2 A-C1
10
8
MCB
J3 J4 J5 500mm C5
240V/21, 8V
11 12 15 12 15 12 15 12 15
TX1
9
STARTER OL4 14 OL3 14 OL2 14 OL1 14
CONTROLLER 4
MODULE 582mm
1
CIRCUIT # B TB
345mm
J1 J2 9
CONTROL LINE
345mm
T4
T6
T2
T3
T5
T7
T1
CIRCUIT # A
374mm 6 CONTROL LINE
* * 15 AUXILLARY CONTACTOR 4
28
Schematic &
Termination Diagram RAUP 600
-
LPCO2
50 LPCO 2 T2 T3
51
51
COM 0 WARNING : - CON TAC T INPUTS ON LY ALM/NC
HPCO2
52 HPCO 2 - NO AC SIGNA L AT INPUTS COM
OL3
53 OL 3 ALM/NO
54
COM 0
OL4
54 TRI P
55 OL 4 LIGH T
HMWT3
56 HMW T 3 7 SEGMEN T DISPL AY CODE TABLE
57
57 COM 0 7 Segment Displa y Error Descr iption
HMWT4 -- NORMA L
2
58 HMW T 4 L1 LPCO 1 Error
t4 HMW T 4 Error
S1 - S4 THERMOS TAT S TATUS
INPU T: USE BLA CK COLOR 0.5 SQMM. OUTPU T: USE BLA CK 1 SQMM.
NO TES:
1 DASHED LINES INDIC ATE RECOMMENDED FIELD
WIRING B Y O THERS . DASHED LINE ENCLOSURES
TERMIN ATION (CONTR OL) AND/OR D ASHED DEVICE OUTLINES INDIC ATE
COMPONENTS PR OVIDED B Y THE FIELD . PHAN TOM
LINE ENCLOSURES INDIC ATE ALTERN ATE
CIRCUIT R Y OR AVAILABLE SALES OPTIONS .
N SOLID LINE INDIC ATES FAC TOR Y WIRING.
INTERLOCK
4 PRESS SW3 B UT TON FOR SHO W THE MEMORABLE ERR OR.
TB T1 T2 T3 THE 7-SEG WIL L OFF FOR 2 SECONDS BEFORE DISPL AY THE
MOMORABLE ERR OR CODES TH AT ARE THE CA USES OF
EA CH LOCK OU T. AFTER TH AT THE 7-SEG WIL L OFF FOR
C O IL
C3 C2
C O IL
IMPO R TAN T
USE COPPER CONDUC T ORS ON LY
T O PREVEN T EQ UIPMEN T DAMA GE.
UNI T TERMINALS ARE NO T DESIGNED
T O ACCEP T AN Y O THER WIRING.
035-0766G
29
Installation Checklist
This list must checked off by the installer to ensure correct installation before the unit start up.
Unit acceptance
Check for damage, if any, on transportation
Check for equipment shipped against delivery slip
Check lifting system
Unit positioning
Remove packaging
Check position of unit
Check unit is level
Check clearance around condenser
Check clearance required for maintenance access
Check position of rubber pads
Refrigerant circuit
Check filter dryer and sight glass presence
Check oil traps presence on discharge line (if there vertical risers>3m)
Check pitch for horizontal lines (1cm/m)
Check refrigerant presence
Electrical equipment
Check direction of rotation of compressors and fan motors
Check installation and rating of mains power switch/fuse
Check that electrical connections comply with specification
Check that electrical connections match information on manufacturer’s identification plate
Check electrical connections and connections to mains power switch
General
Check available cooling charge (50% of rated installation load)
Check with other handling installation works
Comments:........................................................................................................................................................................
..........................................................................................................................................................................................
..........................................................................................................................................................................................
..........................................................................................................................................................................................
Order No ...........................................................................................................................................................................
Work site:..........................................................................................................................................................................
30
Commissioning Log Sheet
PROJECT NAME :
DEALER/CONTRACTOR :
DATE COMMISSIONED :
1.Nameplate information
Model No. Serial No.
Voltage RLA
2. Compressor (S)
A. Voltage at Compressor Terminals
Comp. No. 1: T1 T2 T3
Comp. No. 2: T1 T2 T3
Comp. No. 3: T1 T2 T3
Comp. No. 4: T1 T2 T3
Voltage Imbalance : Comp. “1” Comp. “2”
B. Amp Draw
Comp. No. 1: T1 T2 T3
Comp. No. 2: T1 T2 T3
Comp. No. 3: T1 T2 T3
Comp. No. 4: T1 T2 T3
3. Operating Conditions
A. Circuit “A”
Discharge Pressure. Suction Pressure
Liquid Line Pressure. Suction Line Temp.
Liquid Line Temp. SuperHeat
Subcooling. Evap. Entering Air Temp. (DB/WB)
Amblent Temp. Evap. Discharge Air Temp. (DB/WB)
B. Circuit “B”
Discharge Pressure. Suction Pressure
Liquid Line Pressure. Suction Line Temp.
Liquid Line Temp. SuperHeat
Subcooling. Evap. Entering Air Temp. (DB/WB)
Amblent Temp. Evap. Discharge Air Temp. (DB/WB)
4. Controls
5. Refrigerant Piping
Evacuation Level System Charge
31
RAUP-IOM002-0806
August 2006
RAUP-IOM002-0705
http://www.tranethailand.com Trane has a policy of continuous product and product data implement and reserves the
A Business of American Standard Company right to change design and specifications without notice.