'RAUP IOM-Aug06

Download as pdf or txt
Download as pdf or txt
You are on page 1of 35

Installation

Operation
Maintenance
Split System
Condensing Units
20-55 Tons

Models
RAUP 250, RAUP 300,
RAUP 400, RAUP 500, RAUP 600

August 2006 RAUP-IOM002-0806


Performance Data

Foreword

These installation operation and maintenance instructions are for the continued successful operation of this equipment. The
given as a guide to good practice in the installation, putting, into services of a qualified service technician should be employed
service, operation and periodic maintenance by the Trane Product through the medium of a maintenance contract with a reputable
user. They do not contain the full service procedures necessary service company.

Warranty

Warranty is based on the general terms and conditions of The limits are exceeded or if the control system or the electrical wiring
Trane Company. The warranty is void if the equipment is repaired is modified. Damage due to misuse, lack of maintenance or failure
or modified without the written approval of Trane, if the operating to comply with the manufacturer’s instructions or recommendations
is not covered by the warranty obligation.

Receiving/Handling

On arrival, inspect the unit before signing the delivery note. Specify If any concealed damage is discovered, stop unpacking the
any damage on the delivery note, and send a registered letter of shipment . Take photos of the damaged material if possible. Notify
protest to the last carrier of the goods within 72 hours of delivery. the Carrier immediately by phone and registered mail. Notify the
Notify the local Trane Sales Office at the same time. The unit local Trane Sales office. Concealed damage must be reported
should be totally inspected within 15 days of delivery. within 15 days of delivery.

(i)
Contents
Performance Data
Foreword (i)
Warranty (i)
Receiving / Handling (i)
Nomenclature 1
General Data 20-55 Ton Condensing Unit 2

Installation
General Information 3
Unit Nameplate 3
Machine Room Installation Requirements 3
Vibration Isolators (option) 3
Electrical Connections 5
Unit Start-up 5

Operation / Maintenance
Unit Operation 7
Seasonal start-up procedure 7

Maintenance
Maintenance 7
Weekly Maintenance 7
Maintenance Inspections 8

Compressor
Motor Winding Thermostat 9
Compressor Manifold Piping 9
Trouble Analysis 10 to 12

Dimensional Data
Dimensional Data Condensing Unit 13 to 17

Wiring Diagram
Schematic & Termination Diagram 18 to 29

Installation Checklist 30
Commissioning Log Sheet 31

(ii)
MODEL NOMENCLATURE

MODEL NOMENCLATURE
EG:
R A U P 2 5 0 D 1 B 0 A
1 2 3 4 5 6 7 8 9 10 11 12
Digit Description

R Remote Condensing Unit

A Air Cooled

U Unit Airflow-Upflow

P Development Sequence

250 Nominal Gross Capacity (MBH)


250 = 250 MBH 500 = 500 MBH
300 = 300 MBH 600 = 600 MBH
400 = 400 MBH

D Electrical Rating / Utilization Range


D = 380-415V / 3ph / 50Hz

1 Motor / Compressor Controls


0 = None (Termination Only)
1 = DOL (3 wire) Starter

B Minor Design Sequence

0 Factory Installed / Shipped Options


0 = None
1 = Corrosion Resistant Coated Fin
2 = Suction / Liquid Line Service Valves
3 = Crankcase Heater
4 = 1 and 2 (Corrosion Resistant Coated Fin & Service Valves)
5 = 1,2 and 3 (Corrosion Resistant Coated Fin / Service Valves & Crankcase Heater)
6 = 1 and 3 (Corrosion Resistant Coated Fin & Crankcase Heater)
7 = 2 and 3 (Service Valves & Crankcase Heater)

A Service Indicator

1
Table 1 General Data Outdoor Unit

UNIT MODELS RAUP250 RAUP300 RAUP400 RAUP500 RAUP600


POWER CONNECTION V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50
MCA1 A 53.59 57.54 91.07 101.45 109.03
PERFORMANCES2
Gross Cooling Capacity 2 kW (MBH) 73.9 (253) 90.3 (308) 113.9 (389) 147.9 (505) 180.5 (617)
Unit Capacity Steps (%) 100-50 100-50 100-75-50-25 100-75-50-25 100-75-50-25
Total Compressor Power Input 2 kW 25.2 26.8 36.2 50.4 53.6
Sound Power Level dB (A) 87 89 89 90 92
SYSTEM DATA
Refrigerant Type R22 R22 R22 R22 R22
No. Refrigerant Circuits 1 1 2 2 2
Refrigerant Connection Type Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge approximate per circuit lb (kg) 44 (20) 60.6 (27.5) 43 (19.5) 44 (20) 60.6 (27.5)
Suction Line OD in (mm) 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8
Liquid line OD in (mm) 7/8 7/8 7/8 7/8 7/8
COMPRESSOR
Compressor Type Scroll Scroll Scroll Scroll Scroll
No. Used 2 2 4 4 4
Model 13T+13T 15T+15T 2x(10T+10T) 2x(13T+13T) 2x(15T+15T)
Speed Number 1 1 1 1 1
Motor Number 1 1 1 1 1
V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50
RLA/LRA (each)2 A 22.9/145 24.2 /175 20.7/130 22.9/145 24.2 /175
Motor RPM rpm 2900 2900 2900 2900 2900
COIL
No. Used 1 1 2 2 2
Face Area sq ft (m2) 31.06 (2.88) 35.00 (3.25) 45.36 (4.21) 57.19 (5.31) 66.66 (6.21)
Tube Size OD in (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Tube Type Plain Plain Plain Plain Plain
Rows 3 3 3 3 3
Fin Type Uncoat Corrugated Fin
Fins per inch 12 12 12 12 12
Refrigerant Flow Control - - - - -
FAN
Fan Type Propeller Propeller Propeller Propeller Propeller
No. used 2 3 3 4 6
Diameter in (mm) (28) 710 (28) 710 (28) 710 (28) 710 (28) 710
No. of Blade 4 4 4 4 4
Pitch Angle degree 29 29 29 29 29
Drive Type Direct Direct Direct Direct Direct
Nominal Airflow 3 cfm (cmh) 11,500 (19,539) 15,000 (25,485) 17,100 (29,053) 22,280 (37,853) 29,400 (49,950)
MOTOR
No. of Motor 2 3 3 4 6
Motor hp (each) hp (kW) 0.4 (0.3) 0.4 (0.3) 0.4 (0.3) 0.4 (0.3) 0.4 (0.3)
No. of Speed 1 1 1 1 1
Motor Speed rpm 875 875 875 875 875
V/ph/Hz 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50
RLA/LRA (each) 1.03/2.80 1.03/2.80 1.03/2.80 1.03/2.80 1.03/2.80
DIMENSION (HxWxD)
Crated (Shipping) in 65x98x54 65x124x54 63x110x82 75x110x82 67x124x82
mm 1,642x2,489x1,372 1,642x3,150x1,372 1,591x2,794x2,083 1,895x2,794x2,083 1,692x3,150x2,083
Uncrated (Net) in 58x88x48 58x115x48 56x99x76 68x99x76 60x115x76
mm 1,465x2,229x1,206 1,465x2,910x1,206 1,414x2,513x1,920 1,718x2,513x1,920 1,515x2,910x1,920
WEIGHT
Crated (Shipping) lb (kg) 1,419.8 (644) 1,675.5 (760) 2,284 (1,036) 2,824 (1,281) 2,745 (1,245)
Uncrated (Net) lb (kg) 1,375.7 (624) 1,631.4 (740) 2,207 (1,001) 2,747 (1,246) 2,668 (1,210)
Minimum Outdoor Air Temperature for Mechanical cooling
Standard Ambient Operating Range F 59-133 59-133 59-133 59-133 59-133
C 15-45 15-45 15-45 15-45 15-45
High Pressure (cut out / cut in) psig 398 ± 14 / 313 ± 21
Low Pressure (cut out / cut in) psig 27 ± 7 / 45.5 ± 7

1
MCA - Minimum Circuit Ampacity is 125% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the motor RLA.
2
At 7 deg C SST and 35 deg C Ambient, 400V, Subcooling 8.3 K, Superheat 11.1 K.
3
Nominal Airflow is rated with standard air-dry coil.

2
Installation

Special lifting and moving instruction


A specific lifting method is recommended as follows:
1. Four lifting points are built into the unit
General Information 2. Slings and spreader bar to be provided by rigger and attached
to the four lifting points.
This manual cover the installation of the RAUP 250, RAUP 300 3. Minimum rated lifting capacity (vertical) of each sling and
(single circuit), and RAUP 400, RAUP 500, RAUP 600 (dual circuilts) spreader bar shall be no less than the tabulated unit shipping
air cooled condensing units. Installation procedures should weight.
be performed in the sequence that they appear in this manual. Do 4. Caution :The unit must be lifted with the utmost care Avoid
not destroy or remove the manual from the unit. The manual should shock load by lifting slowly and evenly.
should remain weather-protected with the unit until all installation
procedures are complete.
Figure 1

Lifting of the unit


Note: It is not the intention of this manual to cover all possible
variations in the systems that may occur or to provide
comprehensive information concerning every possible contingency
that may be encountered during an installation. If additional
information is required or if specific problems arise that are not
fully discussed in this manual, contact your local sales office.

Note: “Warnings” and “Cautions” appear at appropriate places in


this manual. Your personal safety and the proper operation of this
machine require that you follow them carefully. The Company
assumes on liability for installations or servicing performed by
unqualified personnel.

Unit nameplate

The unit nameplate gives the full model reference. The power
supply of the unit is specified and must not vary by more that 5%
of the specified voltage.

Machine room installation requirements

Foundation
A special base or foundation is not required when the floor is
level and of sufficient strength to support the unit's weight.

Lifting of the unit


Four lifting lugs are provided at the base of each unit for crane
lift. Attach cable slings to each lug (refer to Figure1) and install
a spreader bar between the cable to protect the unit. Make sure
that the lifting equipment is capable of handling the weight of the
unit.(Table 1)

Clearances
Provide sufficient clearance around the unit for performance of
service and maintenance. Caution unit operation is a function of
the air temperature. Any recycling of the air fed out by the fans
will increase the air intake temperature over the condense fins
and result in a high temperature out. Make sure nothing prevents
air flow to run through the unit coils. Refer to dimensional drawing Vibration Isolators (option)
recommended for detailed clearances, under “Dimensional Data”
section. Vibration isolators (rubber pads) are recommended and are to be
placed under the unit feet. The unit is levelled by placing the

3
Installation
Refrigerant circuit Pressure and leak testing
One circuit on sizes 250 and 300, and two circuits on When pressure and leak testing, these safety precautions
sizes 400, 500 and 600. Single circuit units will have must be adhered to:
two compressors manifolded. Both circuits of the four 1. Do not work in a closed area where refrigerant may
compressor units are manifolded. Refrigerant connections be leaking- a sufficient quantity of vapors may be
not connected are sealed and plugged. present to cause personal injury. Provide adequate
ventilation.
Refrigerant pipe connections 2. Do not use oxygen or ecetylene in place of refrigerant
Determination of the size of the pipe connections. and dry nitrogen for leak testing- a violent explosion
may result.
Liquid line 3. Always use a pressure regulator , valves and gauges
Size the liquid line on the basis of: to control drum and line pressures when pressure
1. Full load operating conditions. testing the system. Excessive pressures may cause
2. A pressure drop of 100 kPa maximum. line ruptures, equipment damage or an explosion
3. A liquid velocity not exceeding 3 m/s (to avoid resulting in personal injury.
hammer).
Pressure test the liquid line , and suction line at pressures
Suction line dictated by local codes.
Design the suction line to provide sufficient gas velocity
in both horizontal and ver tical runs to carry the Caution: Do not exceed the high pressure control
compressor oil and ensure a uniform rate of return to setting plus 0.7 bar. Test pressures on liquid line and
the compressor. Size the hot gas line on the basis of: on suction line must comply with local and national
1. Producing gas velocity in horizontal runs at least codes.
2.5 m/s at minimum operating conditions.
2. Producing gas velocity in vertical risers at least 5
m/s at minimum operating conditions. Charge enough refrigerant into the system to raise the
3. Gas velocity should not exceed 20 m/s under pressure to 1 bar. Using oil-pumped dry nitrogen, build
maximum load conditions. the system pressure to 7 bar.
4. Maximum pressure drop in suction line should not Check the piping and the evaporator unit for leaks with
exceed 20 kPa. a leak detector. Be very thorough in this test, checking
every possible point of leakage. If leaks are found
during the testing, release the test pressure, break the
Pitch the horizontal run of suction line toward the connection and make a new joint. Retest to make sure
evaporator. the connection is solid.

Refrigerant line isolation Field evacuation


Isolate the refrigerant lines from the building to prevent For field evacuation , use a rotary-style vacuum pump.
normal vibration in the lines from the building structure. Determine the pump size required for proper unit
Also avoid bypassing the isolation system on the unit by evacuation.
attaching the refrigerant piping or electric conduit too
rigidly.
Any unit vibration can travel along rigid pipes or conduits
to the building.

Ta ble 1A Electrical data


Model Unit Motor data
Power Voltage MCA Max.Fuse Size
1 2
Compressor Condenser fan
Connection Range @ 380V @ 380V Qty RLA @ 380V (each) LRA @ 380V (each) Qty hp (each) RLA @ 380V (each)
RAUP 250 380V/3ph/50Hz 340-440 53.59 76.49 2x(13T) 22.9 145 2 0.4 1.03
RAUP 300 380V/3ph/50Hz 340-440 57.54 81.74 2x(15T) 24.2 175 3 0.4 1.03
RAUP 400 380V/3ph/50Hz 340-440 91.07 111.77 4x(10T) 20.7 130 3 0.4 1.03
RAUP 500 380V/3ph/50Hz 340-440 101.45 124.35 4x(13T) 22.9 145 4 0.4 1.03
RAUP 600 380V/3ph/50Hz 340-440 109.03 133.23 4x(15T) 24.2 175 6 0.4 1.03

1
Note: MCA = Minimum circuit ampacity = 125% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan RLA.
2
Maximum fuse size = 225% of the largest compressor RLA plus 100% of the other compressor(s) RLA plus the sum of the condenser fan RLA.

4
Installation
When hooking a vacuum pump to a refrigeration system, Caution :
it is important to connect the pump to both the high and 1. All wiring should comply with local and national
low side of the system. codes. Type and location of disconnect switches
Follow the pump manufacturer’s directions as to the should comply with local and national codes. Install
proper methods of using the vacuum pump . disconnect switch near unit, within sight, for safety.
The lines used to connect the pump to the system should 2. Use copper conductors only for installation wiring.
be copper and of the largest diameter that can pratically Unit terminals are not designed to accept other type
be used. Using larger line sizes with minimum flow of wiring. The use of aluminium wire may cause
resistance can significantly reduce evacuation time. galvanic corrosion and/or overheating at the
Rubber or synthetic hoses are not acceptable for unit connection points with resultant equipment failure.
evacuation because they have moisture absorbing
characteristics which result in excessive rates of Unit Start-Up
outgassing and pressure rise during standing vacuum Preparation for start-up
test. This makes it impossible to determine if the unit has Before starting the unit, use the following procedures
a leak. to ensure that the unit is completely and
An electronic thermopile vacuum gauge should be installed properly installed and ready for start-up.
in the common line ahead of the vacuum pump shutoff The installer must make sure that the following points
valve as shown in Figure 2. Close Valve B and open are checked before the initial start-up.
Valve A. After several minutes, the gauge reading will 1. Inspect all wiring connections. Connections should
indicate the minimum blank-off pressure the pump is be clean and tight. Trace circuits to ensure that wiring
capable of pulling . Rotary pump should produce vacuum agrees with wiring diagrams provided with the unit.
of less than 100 microns. Information in the title block of the wiring diagram
Open Valve B and evacuate the system to a pressure of should match the data that appears on the unit
500 microns or less. Valve A must be closed when taking nameplate.
this reading. Once 500 microns or less is obtained, with 2. Close the unit power fused disconnect switch and
Valve A closed, a time versus pressure rise should be the manual disconnect switch.
performed. The maximum allowable rise over a 15 minute 3. Check the unit supply voltage to ensure that the
period is 200 microns. If pressure rise is greater than voltage is within the utilization range.
200 microns but levels off to a constant value, excessive 4. Check the compressor oil level.
moisture is present. If the pressure steadily continues to 5. Check with a phase-meter the direction of rotation
rise, a leak is indicated. of scroll Trane compressors or check the good
operation of the discharge and suction pressures.
6. As the various motors of the system are started,
Figure 2 check the direction of rotation and make sure that
the driven equipment is operating satisfactorily.
Vacuum pump connection.
7. Ensure sufficient cooling load available at day of
start-up (minimum of 50% of design load).
Preparation
Before putting the system into operation, perform these
service and check-out procedures :
1. Before making any electrical power connections make
sure that the insulation resistance of all power terminal
to earth is in accordance with the international electrical
codes. Measure the insulation of all electrical motors
using a 500 V DC tester and refer to the manufacturer’s
specifications.

Warning :
No motor should be started if the insulation resistance
is less than 2 mega ohms. Under no circumstances
should any voltage be applied to a motor while it is
under vacuum.
2. Check the unit supply voltage to ensure that the voltage
is within the utilization range.
Electrical Connections
Wiring diagrams are furnished with the units, but extra Caution :
copies may be obtained from the local Trane sales office. Phase unbalance must not exceed 2% . Supply for all
The installing contractor is to provide and install fused motors is to be within plus or minus 5% of the voltages
disconnect switches and the wiring up to the unit control specified on the compressor nameplate.
panel. Check all wiring connections and trace the circuits
to make sure that they agree with the wiring diagrams.
3. Place all refrigerant circuit valves in operating position.
5
Installation
4. Reset all controls equipped with a manual reset function. Oil level
Oil should be visible in the compressor, under full load, in
Refrigerant charging the compressor oil level sight glass. The unit was charged
After the refrigeration pipework system has been pressure with the proper amount of oil before shipping. Under normal
tested and evacuated, and meets the vacuum pressure operation, compressor oil is always expected to return to
requirements of paragraph <<Field evacuation>>, the compressor oil sump, and no additional oil should be added.
refrigerant may be charged as follows. Be sure to follow the For oil level indication, refer to compressor oil sight glass, as
start-up procedure at the same as charging the refrigerant. per Figure 3. If oil is within sight glass visibility, oil quantity
1. Loosely connect a cylinder of refrigerant to the 1/4” OD should be sufficient.
Charging Valve Located on the liquid line.
2. Open and close the valve on the refrigerant cylinder to Refrigerant pressures
purge the connection. Tighten the coupling nut. Observe operating pressures. If pressures are above or
3. Invert the refrigerant cylinder so that only liquid will enter below normal see <<Trouble Analysis>> section. Normal
the system operating pressures are in Table 2. A High & Low pressure
4. Allow the compressor to continue running throughout the settings are found in Table 1
remainder of the charging operation. Do not allow the
pressure to fall bellow 0.15 bar. Liquid line sight glass (Optional)
The flow of refrigerant through the sight glass should be
smooth and without bubbles. Bubbles indicate a refrigerant
Caution: shortage and probably a leak, or a restriction in the liquid
Do not attempt to start the compressor by blocking the line.
safety controls. Allow the condensing unit to function
in a normal manner. Superheat
Normal Superheat is 6 to 8 deg C. Overfeeding of the
evaporator results in high suction pressure, low superheat
5. Allow the system to continue functioning for approximately and possible liquid carryover. Inadequate or too high a
30 minutes. If during this period bubbles appear in the superheat is remedied by adjusting stem on the thermostatic
liquid line sight glass, add refrigerant. expansion valve (TEV). If this fails to correct the condition,
6.Leak-test the refrigerant circuit. then the valve cage or power element of the TEV may be
defective and should be replaced.
Start-up procedure
1. Start the unit by switching to <<On>> Caution:
2. After the unit has started, allow it to operate for at least 1. Excessive foaming indicates the presence of
15 minutes to stabilise operating pressures. Then check : refrigerant in the oil and will result insufficient
- compressor oil level. compressor lubrication. Turn off the motor and
- compressor and fan motor power consumption. investigate the cause.
- suction pressure. 2. An excess of the oil in the compressor can cause
- discharge pressure. problems in the same way as a lack of oil. Before
- liquid line sight glass. topping up , contact a qualified service technician.
- superheat. Use only Tranerecommended oils.
- subcooling.
Figure 3 - Compressor oil level
All readings and measurement should be logged.
Procedures are given below.

Maximum
oil level

Minimum
oil level
CAUTION
PHASE ROTATION IS CRITICAL
IF SUCTION PRESSURE DOSE NOT FALL TO EXPECTED
OPERTATING LEVEL WITHIN THIRTY (30) SECONDS
AFTER COMPRESSOR IS STARTED, COMPRESSOR
WARNING
1. Do NOT run the compressor on reverse rotation
ROTATION MAY BE REVERED. 2. Do NOT perform any pump down cycle with Scroll
compressor
TO REVERSE ROTATION, DISCONNECT ALL UNIT POWER 3. Do Not run the compressor below the setting of low
AND REVERSE ANY TWO (2) INCOMING POWER LEAD pressure switch
WIRES AT THE UNIT HIGH VOLTAGE TERMINAL BLOCK. 4. Do NOT by pass any safety devices when operating the
RECONNECT ALL UNIT POWER, RESTART UNIT, AND system.
RE-CHECK SUCTION PRESSURE. Failure to observe any of the above will cause severe
damage to the Scroll compressors.

6
Operation / Maintenance
Figure 3A
PIPING DETAILS OF REFRIGERANT COILS

SOLENOID
LIQUID VALVE
EXPANSION VALVE
CAPILLARY TUBES
STRAINER SIGHT
GLASS

EXPANSION VALVE
THERMAL BULBS

LIQUID LINE Method of Attaching


FROM RECEIVER Thermal Bulb to Suction Line
EXPANSION
VALVE

EXPANSION
VALVE

EXPANSION VALVE NOTE: REFER TO THE TRANE REFRIGERATION


EQUALIZER LINES MANUAL FOR COMPLETE SUCTION AND
LIQUID LINE PIPING ARRANGEMENTS.
SUCTION LINE THIS MANUAL ALSO EXPLAINS EXPAN-
TO COMPRESSOR SION VALVE INSTALLATION AND SUPER-
HEAT SETTING.

Manifolded Suction Headers

HP

4m/s LP
max. 4m
U-trap

8 to 12m/s
max. 4m
Evaporator Figure 3C
4m/s
Figure 3B Maintenance
Table 2 - Normal operating conditions
Ambient Temperature (C) The following maintenance are given as an essential part of
25 30 40 the required maintenance of this equipment. However the
services of a qualified services technician are required to
Discharge pressure (bar) 14-17 17-19 22-25 perform the periodic maintenance procedures as part of a
Suction pressure (bar) 4-6 4-6 4-6 regular maintenance contact. Perform all maintenance
procedures at the scheduled intervals. This will prolong the
life of the unit and reduce the possibility of costly equipment
Final checkout failure. Use an <<operator’s log>> to record a weekly
Run the unit sequentially through its stages of cooling.
Once proper unit operation is confirmed, perform these final <<operator condition history>> for this machine. The operating
steps: log for this unit can be a valuable diagnostic tool for service
1.Inspect the unit for debris and/or misplaced tools and personnel also, the operator, by noticing trends in the operating
hardware. conditions can often foresee and prevent problem situations
2.If the unit is operated immediately, be sure all valves are before they become serious. It may be required for inspection
in operating position.
3.Secure all panels including control panel in place. in the event of warranty claim.

Operation Weekly maintenance


1. Check the compressor oil level. The oil should cover 1/2
Operating the unit of the sight glass when running at full load. Before oil
Unit operation unit initialized by turning the control circuit is added allow the compressor to run continuously for 3-
switch in the control panel. 4 hours. Check the oil level every 30 minutes. If the level
Seasonal start-up procedure does not return to cover 1/2 of the sight glass contact a
1.Perform the applicable procedures outline under << Annual qualified service technician.
Maintenance>> in the Maintenance Section 2. Trane approved compressor oil:
2.Test the entire refrigerant system for leaks. Trane oil 015E.(R22 refrigerant)
3.Close the system master disconnect switch
4.Start the system
5.Check the operation of all interlocked equipment. Note:
6.Check oil level and operating pressures after the system The lubricating oils recognised by Trane have been
has been in operation for 15 to 20 minutes. subjected to extensive testing in out laboratories and
7.Check discharge pressure against <<Normal operating have been found to give the required satisfactory results
conditions>>. If the pressure is above or below the normal for use with Trance compressors.
level, stop the unit and correct the cause.
8.On Scrolls, compressor sightglass oil levels may be The use of any oil not conforming to Trane required
anywhere within the sightglass. Also 2 scrolls manifolded standard is at the sole responsibility of the user and
together will have different levels. could result in warranty cancellation.
7
Maintenance

Caution: Maintenance inspections


1. Excessive foaming indicates the presence of If the unit does not perform properly during these
refrigeration in the oil and will result in insufficient inspections, consult the <<Trouble Analysis>> section for
compressor lubrication. Turn off the motor and possible cause and recommended procedures. The
investigate the cause. following procedures should be carried out by a qualified
2. An excess of oil in the compressor can cause service technician as part of a maintenance contract.
problems in the same way as a lack of oil. Before
topping up, contact a qualified service technician.
Use only Trane recommended oil. The first and last visit will include the seasonal shut down
3. The flow of refrigerant through the sight glass should and start-up procedures, when applicable as detailed on
be smooth and without bubbles. Bubbles indicate a the section on <<operation>>. The visits should include
refrigerant shortage and probably a leak, or a restriction the following procedures :
in the liquid line. Contacta qualified service technician. - Inspect contacts of motor contactors.
Each sight glass is equipped with a moisture indicator. - Check setting and function of each system control.
The colour of the indicator element changes with the - Perform an oil analysis to determine the acidity of the
amount of moisture in the refrigerant, but also as a compressor oil and record the results.
function of temperature. It should indicate <<dry>>
refrigerant if it indicates <<wet>> run the unit for a Warning / Caution :
minimum of 12 hours and check again. If it remains The oil analysis procedure must be performed by a
consistently in <<caution>> or <<wet>> zones, contact qualified service technician. Incorrect interpretation
a qualified service technician. of analysis results can cause damage to the unit.
4. Run the compressor(s) for a minimum of two (2) hours The use of improper analysis procedures can cause
before taking the initial moisture level readings after a hazardous condition that may result in injury to service
start-up. The moisture indicator element is moisture personnel.
and temperature sensitive, so the system must be at - Refrigerant leak test.
normal operating temperatures to obtain correct - Check motor winding insulation (once per year).
moisture level readings.
Other procedures may be necessary, depending on the
age and usage of the equipment.
3. Observe operating pressures. If pressures are above or
below normal, see <<Trouble Analysis>> section. Normal Note :
operating pressures are in Table 2. It is important that the equipment is regularly serviced
4. Inspect entire system for any unusual conditions such as by a qualified service technician, at least once per
noisy compressor, loose access panels, leaky pipes of
year /1000 hours of operation , minimum frequency.
chattering contactors.
Failure to respect this requirement may result in
5. Note temperatures, pressures, date and time as well as
any observation in a machine log book. cancellation of Trane warranty and liability.

Annual maintenance A maintenance visit by a qualified service technician is


1.Remove corrosion from any surface and repaint. Check also recommended after the first 500 hours of operation
the condition of the gasket around the control panel door. after commissioning.
2.Perfor m all weekly maintenance procedures.

Table 2A
General interconnecting line sizes.
LENGTH OF INTERCONNECTING LINES(FT)**
0-20 21-40 41-60 61-80 81-100 101-120 121-140 141-160 161- 180 181-200
CONDENSING LINE SIZE - O.D.(IN.)
UNIT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT LIQ SUCT
5
RAUP 400 /8 1 5/8 7
/8 1 5/8 7
/8 1 5/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8 7
/8 2 1/8
7 5 7 5 7 1 7 1 7 1 1 1 1 1 1 1 1 1
RAUP 250,500 /8 1 /8 /8 1 /8 /8 2 /8 /8 2 /8 /8 2 /8 1 /8 2 /8 1 /8 2 /8 1 /8 2 /8 1 /8 2 /8
7
RAUP 300,600 /8 1 5/8 7
/8 2 5/8 7
/8 2 1/8 7
/8 2 1/8 1 1/8 2 1/8 1 1/8 2 1/8 1 1/8 2 1/8

** In shaded region, use 2 1/8 for all horizontal runs, and 1 5/8 for all vertical risers.
However, for correct and proper pipe sizing, it is
recommended to size piping based on Trane
recommended piping guide or use computer aided
software where applicable

8
Compressor

This sequence is of most importance


Compressor The scroll compressors in the RAUP
because it maximizes lubrication and
Motor Winding Ther mostat units do not unload. Instead, they are
ensure proper oil return. Secondly, the
staged on and off for various steps of
design of the oil return with equalizer
Each motor winding thermostat is a loading. This sequence is critical
is critical. The lead compressor must
pilot duty control designed to stop and must not be changed! Altering
always be in the lead in the sequence.
compressor operation if the motor this sequence in any way could cause
Should it fail, it locks out the circuit
windings become hot due to rapid compressor failure.
immedia tely, saving the other
cycling ,loss of charge, abnormally low compressor.
s u c t i o n t e m p e ra t u r e s, o r t h e
compressor running backwards.

Table 2B
Compressor Manifold Piping Compressor Sequencing
The compressor refrigerant piping Unit Control Circuit Circuit
manifold system was purposely designed Size Step Comp.1 Comp.2
to provide proper oil return to both
250 1 1 (50%) -
compressors; therefore, the original
refrigerant manifolding system should 300 2 1,2 (100%) -
not be modified in any way! 400 1 1 (50%) -
500 2 1,2 (100%) -
If a compressor replacement is required,
do not alter the compressor manifold 600 3 1,2 (100%) 3 (50%)
piping; improper oil retur n and 4 1,2 (100%) 3,4 (100%)
compressor failure could result.
If a suction filter is required, install it a
minimum of 18” upstream of the
compressor manifold piping.
See Figure 4 Note: 1, 2, 3 and 4 indicate which compressor in the unit is operat-
Caution : Altering the original ing. (%) indicates the amount of the circuit in the operation during a
manifold piping may cause oil given step. Refer to dimensional data for the location of the compressors
compressor failure. 1, 2, 3 and 4 in the RAUP unit.

Figure 4 :
Location Requirements for Suction
Line Filter Installation after Motor
Burnout

Oil Equalizer Line

Compressor 2 Compressor 1

Minimum 18 straight,
unobstructed piping
to suction line filter

Suction Line
Note: Anytime one compressor is
replaced, the oil charge for the (Compressor 1)
remaining compressor must be
replaced. Common
Suction Gas
from Evaporator

Suction Line Oil Seperator Tee


(Compressor 2)

9
Trouble Analysis

A. Compressor fails to start


Problems and symptoms Probable cause Recommended action.

Full voltage at motor terminal Burned-out motor. Repair or replace.


but motor will not run.
Inoperative motor starter. Burned-out holding coil or broken Repair or replace.
contacts.
Open contacts of safety control of Safety control of thermal overload Call Trane Service.
thermal overload. relays has cut outs.
Electric circuit test shows no current a) Power failure. Check for blown line fuse or
on line side of motor starter. broken leak.
b) Disconnect switch open. Determine why switch was
opened.
Electric circuit test show current Fuse down. Replace fuse Check load on motor.
on line but not on motor side or fuse.
Voltmeter does not read proper Low voltage Call power company.
voltage.
Motor starter holding coil is not Open control circuit. Locate open control and
energized. determine cause.
See individual control.
Compressor will not operate. Frozen compressor due to locked Replace Compressor.
or damaged mechanism
Open contact on high pressure Discharge pressure above cut-in See Complaint<<Discharge
switch. setting of high pressure cut-out pressure too high.>>
Discharge pressure above cut-in switch
setting.

B. Compressor stops
Problems and symptoms Probable Cause Recommended action

High pressure control has cut out. See H. See H.


Thermal overload relay has cut out. a)voltage too low a) contact power company.
b) cooling load or condensing b) see discharge pressure too.
temperature too high high.
Winding thermostat has cut out. Refrigerant shortage Repair leak, add refrigerant.

10
Trouble Analysis

C. Compressor shortcycles
Problems and symptoms Probable cause Recommended action

Suction pressure too low and Restricted liquid liner driver. Replace driver core.
frosting at driver.

Motor starts and stops frequently Faulty motor. Replace compressor.

D. Compressor runs Continuously


Problems and symptoms Probable cause Recommended action

High temperature in conditioned Excessively high cooling load Check infiltration and insulation
space of conditioned space.

Bubbles in sight glass a) Lack of refrigerant. a) Repair leak, add refrigerant.


b) Filter driver obstructed b) Replace driver core.

E. Compressor loses oil


Problems and symptoms Probable cause Recommended action

Oil level too low (sight glass). Insufficient oil charge. All oil.

Gradual drop of oil level. Clogged filter drier Replace.

Excessively cold suction. Liquid flooding back to compressor Readjust superheat setting
Noisy compressor and verify correct bulb
mounting.

F. Compressor is noisy

Problems and symptoms Probable cause Recommended action

Abnormally cold suction line: a) Liquid flood-back a) Check superheat and


compressor knocks. Valve bulb b) Expansion Valve stuck in open expansion.
attachment. position b) Repair or replace

Compressor noisy Incorrect direction of rotation Inverse the direction of rotation

G. System short of capacity

Problems and symptoms. Probable cause. Recommended action

Expansion valve hissed. Lack of refrigerant. Add refrigerant.

High pressure drop across Clogged filter-driver. Clean or replace.


filter-drier.
Superheat too high. Superheat set too high. Check superheat and adjust
expansion valve
Superheat too high. Excessive pressure drop in the Check superheat and reset thermal
thermal expansion valve. expansion valve

11
Trouble Analysis

H. Discharge pressure too high

Problems and symptoms Probable cause Recommended action

Too little or too warm condenser air. Excessively warm air leaving Clean coil, check fan and motor
condenser. for proper operation.
Restricted air flow. Cuts out on high pressure control.

Excessive discharge pressure. Air or noncondensible Remove air or non condensibles.


gas in system.

J. Discharge pressure too high

Problems and symptoms Probable cause Recommended action

Bubbles in sight glass. Lack of refrigerant. Repair leak and charge.

K. Discharge pressure too high

Problems and symptoms Probable cause Recommended action

Compressor runs continuously. Excessive load on evaporator Check system.

Abnormally cold suction line; liquid a) Expansion valve opens too far. a) Adjust superheat and check
flood-back to compressor. bulb attachment.
b) Expansion valve stuck in open b) Repair or replace.
position.

L. Discharge pressure too high


Problems and symptoms Probable cause Recommended action

Bubbles in sight glass. Lack of refrigerant. Repair leak, add refrigerant.

High pressure drop across Clogged filter drier. Replace.


filter-drier.

No refrigerant flow through Expansion valve power element has Replace valve power element.
expansion valve. lost charge.

Loss of capacity. Obstructed expansion valve. Clean or replace.

Superheat too high. Too much pressure drop in Check external equaliser of
evaporator. expansion valve.

This is by no means a complete analysis of the scroll provide the background necessary for him to recognize
refrigeration system. Instead, its intention is to familiarize and accurately correct or report any developing problem.
the operator with the operation of the scroll unit and

12
13
14
15
16
17
Schematic &
Termination Diagram RAUP 250

SCHEMATIC&TERMINATION DIAGRAM :-RAUP250


NOTE :-
SEE UNIT NAMEPLATE
FOR LINE VOLTAGE FOR RAUP250 - COMPRESSOR OVERLOAD ARE INTERNALLY PROTECTED
L1 L2 L3 N FUSED DISCONNECT SWITCH EVF-C / EVF-OL
LEGEND
DEVICE
DESCRIPTION
EVF DESIGNATION
LPCO LOW PRESSURE CUT-OUT
HPCO HIGH PRESSURE CUT-OUT
HMWT HIGH MOTOR WINDING T-STAT
START

FUSED
EVF-OL
STOP

OL 1, 2 INTERNAL OVER LOAD, COMPRESSOR


EVF-C

DISCONNECT
MCB

SWITCH EVF-OL INTERNAL PROTECTOR, EVAPORATOR FAN


EVF-C STARTER, EVAPORATOR FAN
PT L1 L2 L3 N EVF-C(AUX) A-C1, A-C2 STARTER, COMPRESSOR
EVF EVAPORATOR FAN
S1 SYSTEM SWITCH
CF 1, 2 FAN, CONDENSOR
MCB CIRCUIT BREAKER
C5 STARTER, CONDENSOR FAN
PT POWER TERMINALS

A-C1 A-C2 TB BLOCK, TERMINATION


C5 SUPPLIED & INSTALLED BY CUSTOMER
FACTORY INSTALLED
0L1 0L2 E 5T1 5T2 5T3
TB
TERMINATION BLOCK, CONTROL
TX1 TRANSFORMER 240V : 21V, 8V
C1, C2 COMPRESSOR
CCH CRANKCASE HEATER

C1 C2 NOTES:
1 DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
COMPR. 1 COMPR. 2 CF1 CF2 AND/OR DASHED DEVICE OUTLINES INDICATE
STEP 1 STEP 2 COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
3 2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER
T1 MCB IS INSTALLED
32 31
T2 3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF INTERLOCK INTERLOCK
T3
30

J2 INPUT J1
33
WARNING
HAZARDOUS VOLTAGE!
STARTER CONTROLLER
220V DISCONNECT ALL ELECTRIC POWER
POWER MODULE INCLUDING REMOTE DISCONNECTS
33 30
SUPPLY BEFORE SERVICING.
240 0
FAILURE TO DISCONNECT POWER
TX1 J5 J4 OUTPUT J3 BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.

PT
240 V - CONTROL WIRING

L1 L2 L3 N E

30

31

J3 J3
J3
32A

32B

C1 C2
30

34 30 35 30 FOR CCH C5 31
FOR CCH OPTION 36 30
OPTION A1 A2 A1 A2 32 33 30
32 FOR CCH
32
MCB

T1 T2 T3 T4 T5 T6 T7 OPTION
32A
32B C5
A-C1 A-C2
32

CCH1 CCH2

TO STARTER
CONTROLLER TX1
JUMPER J2

18
Schematic &
Termination Diagram RAUP 250

COMPONENT LAY-OUT/POWER WIRING :-RAUP250

POWER CABLE SHOWN IN COLOR


FOR ILLUSTRATION ONLY.
THE ACTUAL POWER CABLE
COLOR IS BLACK OR RED. TO ALL FAN MOTORS (IN PARALEL)
13

9 3
G RRR

S1
5
200mm 10 140mm
L1 L2 L3 N E
5T2
5T3
5T1

E 8
ADD FOR CCH OPTION
1TB5

800mm
TB

MODULE
CONTROLLER
STARTER

12 14 12 14
J1

2
MCB

A-C1 A-C2 C5
J3

390mm
T1
T2
T3
T4
T5
T6
T7

255mm

226mm
11
J2

8
J4

9
240V/24V

6 7 COMP. # 2
TX1

4
CONTROL LINE
J5
1

385mm

COMP. # 2, POWER LINE


COMP. # 1
CONTROL LINE
COMP. # 1, POWER LINE

NO. DESCRIPTION QTY.


1 STARTER CONTROLLER VERSION 1.1R 1
2 TRANSFORMER 240V/21V & 8V, 30VA 1
3 TERMINAL BLOCK, POWER TERMINAL 3
4 CIRCUIT BREAKER ABB, 1P (6A) 1
5 TERMINAL BLOCK, FAN MOTOR L 4

* 6 TERMINAL BLOCK, 3P 1
7 TERMINAL END PLATEL 1
POWER TOTAL
CABLE LENGTH 8 TERMINAL STOPPER 7
SIZE
9 TERMINAL RAIL, Total Length 700
2 _
COMP #1 6mm 10 WIRE DUCT, Total Length 1666

2
11 CONTACTOR FOR FAN MOTOR W/AUXILLARY CONTACT 1
COMP #2 6mm _
12 CONTACTOR FOR COMPRESSSOR 2
13 PANEL, STARTERL 1
** 14 AUXILLARY CONTACTOR 2

NOTE : * USE TERMINAL BLOCK, 7P FOR COMPRESSOR CRANKCASE HEATER OPTION


** ADD ONTO ITEM 14 FOR COMPRESSOR CRANKCASE HEATER OPTION

19
Schematic &
Termination Diagram RAUP 250

STARTER CONTROLLER MODULE - I/O WIRING :-RAUP250

INPUT TYPICAL WIRING FOR RAUP 250 OUTPUT


J1 J3
LPCO1
38 LPCO 1 COM 1 33
A-C1
39 RESET 1
COM 0 A CIRCUIT A-C1 34
39 RESET 2
HPCO1
40 HPCO 1 RESET 3 COMPRESSORS COM 2 33
A-C2
OL 1 SYSTEM RESET A-C2 35
RESET 1 = RESET CIRCUIT A ON ERROR
JUMPER COM 0 RESET 2 = RESET CIRCUIT B ON ERROR COM 3
OL 2 SYSTEM RESET : = RESET SYSTEM ON ERROR B-C3
COMP. : START-UP TIMING
HMWT 1 A CIRCUIT A-C1 ON DELAY TIME = 1 min COM 4
JUMPER COM 0 A CIRCUIT A-C2 ON DELAY TIME = 2 min B-C4
HMWT 2 FAN FOR COM 5 33
C5
- RAUP MODEL ONLY C5 36

-
LPCO 2
JUMPER COM 0 WARNING : - CONTACT INPUTS ONLY J4 T2 T3

HPCO 2 - NO AC SIGNAL AT INPUTS ALM/NC


OL 3 COM
JUMPER COM 0 ALM/NO
OL 4 TRIP
HMWT 3 7 SEGMENT DISPLAY CODE TABLE LIGHT
7 Segment Display
JUMPER COM 0 Error Description
-- NORMAL
HMWT 4 L1 LPCO 1 Error
2
S1 H1 HPCO 1 Error
TO TEMP. CONTROLLER STEP 1 O1 OL 1 Error
COM 0 O2 OL 2 Error
CIRCUIT A N L (240 V)
JUMPER t1 HMWT 1 Error
2
S2
t2 HMWT 2 Error
TO TEMP. CONTROLLER STEP 2
S3 L2 LPCO 2 Error
COM 0 H2 HPCO 2 Error
JUMPER O3 OL 3 Error
S4 O4 OL 4 Error
CIRCUIT B
t3 HMWT 3 Error J5
240V/21, 8V

t4 HMWT 4 Error
S1 - S4 THERMOSTAT STATUS
TX1

INPUT: USE BLACK COLOR 0.5 SQMM. OUTPUT: USE BLACK 1 SQMM.
TERMINATION (CONTROL)

N
NOTES:
32 33 30 1 DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
CONTROL BOX

AND/OR DASHED DEVICE OUTLINES INDICATE


COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE
C1 C2 CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
MCB

2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER


IS INSTALLED
T1 T2 T3 TB 3 REMOVE JUMPER TO INTERFACE WITH EVF
WARNING INTERLOCK
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER 4 PRESS SW3 BUTTON FOR SHOW THE MEMORABLE ERROR.
INCLUDING REMOTE DISCONNECTS THE 7-SEG WILL OFF FOR 2 SECONDS BEFORE DISPLAY THE
MOMORABLE ERROR CODES THAT ARE THE CAUSES OF
BEFORE SERVICING. EACH LOCKOUT. AFTER THAT THE 7-SEG WILL OFF FOR
EVF INTERLOCK

FAILURE TO DISCONNECT POWER 2 SECONDS AND RETURN TO DISPLAY THE EXISTING


BEFORE SERVICING CAN CAUSE ERROR/STATUS CODES.IF MORE THAN 1 ERROR HAPPENS,
THEY ARE DISPLAYED 2 SECOND EACH.IF THERE IS NOT ANY
SEVERE PERSONAL INJURY OR DEATH. MEMORABLE ERRORS,THE NORMAL CODE WILL BE DISPLAYED.
PRESS AND HOLD SW3 BUTTON FOR 4 SECONDS TO
IMPORTANT CLEAR THE MEMORABLE ERROR.

USE COPPER CONDUCTORS ONLY


TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED 3
TO ACCEPT ANY OTHER WIRING.

20
Schematic &
Termination Diagram RAUP 300

SCHEMATIC&TERMINATION DIAGRAM :-RAUP300


NOTE :-
SEE UNIT NAMEPLATE
FOR LINE VOLTAGE FOR RAUP300 - COMPRESSOR OVERLOAD ARE EXTERNALLY PROTECTED
L1 L2 L3 N FUSED DISCONNECT SWITCH EVF-C / EVF-OL
LEGEND
DEVICE
DESCRIPTION
EVF DESIGNATION
LPCO LOW PRESSURE CUT-OUT
HPCO HIGH PRESSURE CUT-OUT
HMW T HIGH MOTOR WINDING T-STAT
START

FUSED
EVF-OL
STOP

EVF-C

DISCONNECT OL1, 2 EXTERNAL OVER LOAD, COMPRESSOR


MCB

SWITCH EVF-O L INTERNAL PROTECTOR, EVAPORATOR FAN


EVF-C STARTER, EVAPORATOR FAN
PT L1 L2 L3 N EVF-C(AUX) A-C1, A-C2 STARTER, COMPRESSOR
EVF EVAPORATOR FAN
S1 SYSTEM SWITCH
CF 1, 2, 3 FAN, CONDENSOR
MCB CIRCUIT BREAKER
C5 STARTER, CONDENSOR FAN
PT POWER TERMINALS
A-C1 A-C2 TB BLOCK, TERMINATION
C5
SUPPLIED & INSTALLED BY CUSTOMER
FACTORY INSTALLED
0L1 0L2 E 5T1 5T2 5T3
TB
TERMINATION BLOCK, CONTROL
TX1 TRANSFORMER 240V : 21V, 8V
C1, C2 COMPRESSOR
CCH CRANKCASE HEATER
C1 C2
NOTES:
1 DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
COMPR. 1 COMPR. 2 CF1 CF2 CF3 AND/OR DASHED DEVICE OUTLINES INDICATE
STEP 1 STEP 2 COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
3 2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER
T1 MCB
IS INSTALLED
32 31
T2
3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF INTERLOCK
INTERLOCK
T3
30

J2 INPUT J1
33
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
STARTER CONTROLLER INCLUDING REMOTE DISCONNECTS
220V MODULE
POWER BEFORE SERVICING.
33 30
SUPPLY FAILURE TO DISCONNECT POWER
240 0
BEFORE SERVICING CAN CAUSE
TX1 J5 J4 OUTPUT J3 SEVERE PERSONAL INJURY OR DEATH.

IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.

PT
240 V - CONTROL WIRING

L1 L2 L3 N E

30

31

J3 J3
J3
32A

32B

C1 C2
30

30 30 C5 31
34 35
FOR CCH FOR CCH 36 30
OPTION A1 A2 A1 A2 OPTION 32 33 30
32 32 FOR CCH
MCB

T1 T2 T3 T4 T5 T6 T7 OPTION
32A 32B C5
A-C1 A-C2
95 95 32
OL1 OL2 CCH1 CCH2
96 96

TO STARTER
41 42 43 CONTROLLER TX1
{

J2
JUMPER
TO J1

21
Schematic &
Termination Diagram RAUP 300

COMPONENT LAY-OUT/POWER WIRING :-RAUP300


POWER CABLE SHOWN IN COLOR
FOR ILLUSTRATION ONLY.
THE ACTUAL POWER CABLE
COLOR IS BLACK OR RED.
TO ALL FAN MOTORS (IN PARALEL)
14

9 3
G R RR

S1
5
200mm 10 140mm
L1 L2 L3 N E
5T2
5T3
5T1

E 8
ADD FOR CCH OPTION
1TB5

800mm
TB

MODULE
CONTROLLER
STARTER

13 15 13 15
J1

2
MCB

A-C1 A-C2 C5
J3

390mm
T6
T7
T2
T3
T4
T5
T1

255mm

226mm
11
J2

8
J4

9 OL 1 OL 2
240V/24V

4 6 7 COMP. # 2
TX1

12 12
CONTROL LINE
J5
1

385mm

COMP. # 2, POWER LINE COMP. # 1


CONTROL LINE
COMP. # 1, POWER LINE

NO. DESCRIPTION QTY.


1 STARTER CONTROLLER VERSION 1.1 1
2 TRANSFORMER 240V/21V & 8V, 30VA 1
3 TERMINAL BLOCK, POWER TERMINAL 3
4 CIRCUIT BREAKER ABB, 1P (6A) 1
5 TERMINAL BLOCK, FAN MOTOR 4

* 6 TERMINAL BLOCK, 3P 1
7 TERMINAL END PLATE 1
POWER TOTAL
CABLE LENGTH 8 TERMINAL STOPPER 7
SIZE
9 TERMINAL RAIL, Total Length 700
2 _
COMP #1 6mm 10 PVC TRUNKING 1", Total Length T 1666

2
11 CONTACTOR, FAN 1
6mm _
COMP #2
12 OVERLOAD CONTACTOR 2
13 CONTACTOR FOR COMPRESSOR 2
14 PANEL, STARTERLA 1
** 15 AUXILLARY CONTACTOR 2

NOTE : * USE TERMINAL BLOCK, 7P FOR COMPRESSOR CRANKCASE HEATER OPTION


** ADD ONTO ITEM 15 FOR COMPRESSOR CRANKCASE HEATER OPTION

22
Schematic &
Termination Diagram RAUP 300

STARTER CONTROLLER MODULE - I/O WIRING :-RAUP300

INPUT TYPICAL WIRING FOR RAUP 300 OUTPUT


J1 J3
LPCO1
38 LPCO 1 COM 1 33
A-C1
39 RESET 1
39
COM 0 RESET 2 A CIRCUIT A-C1 34
HPCO1
40 HPCO 1 RESET 3 COMPRESSORS COM 2 33
A-C2
OL1 41 OL 1 SYSTEM RESET A-C2 35
42 RESET 1 = RESET CIRCUIT A ON ERROR
42
COM 0 RESET 2 = RESET CIRCUIT B ON ERROR COM 3
OL2
OL 2 SYSTEM RESET : = RESET SYSTEM ON ERROR
43 B-C3
COMP. : START-UP TIMING
HMWT1
44 HMWT 1 A CIRCUIT A-C1 ON DELAY TIME = 1 min COM 4
45
45
COM 0 A CIRCUIT A-C2 ON DELAY TIME = 2 min B-C4
HMWT2
46 HMWT 2 FAN FOR COM 5 33
C5
- RAUP MODEL ONLY C5 36

-
LPCO 2 WARNING : - CONTACT INPUTS ONLY
- NO AC SIGNAL AT INPUTS
JUMPER COM 0 J4 T2 T3

HPCO 2 ALM/NC
OL 3 COM
JUMPER COM 0 ALM/NO
OL 4 TRIP
HMWT 3 LIGHT
JUMPER COM 0 7 SEGMENT DISPLAY CODE TABLE
HMWT 4 7 Segment Display Error Description
2
-- NORMAL
S1 L1 LPCO 1 Error
TO TEMP. CONTROLLER STEP 1
COM 0 H1 HPCO 1 Error N L (240 V)
O1 OL 1 Error
JUMPER CIRCUIT A
2
S2 O2 OL 2 Error
t1 HMWT 1 Error
TO TEMP. CONTROLLER STEP 2
S3 t2 HMWT 2 Error
COM 0 L2 LPCO 2 Error
JUMPER H2 HPCO 2 Error
240V/21, 8V

S4 O3 OL 3 Error
O4 OL 4 Error
CIRCUIT B
J5
t3 HMWT 3 Error
TX1

t4 HMWT 4 Error
S1 - S4 THERMOSTAT STATUS

INPUT: USE BLACK COLOR 0.5 SQMM. OUTPUT: USE BLACK 1 SQMM.
TERMINATION (CONTROL)
NOTES:
N
CONTROL BOX

1 DASHED LINES INDICATE RECOMMENDED FIELD


WIRING BY OTHERS. DASHED LINE ENCLOSURES
32 33 30
C1 C2 AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
MCB

2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER


WARNING T1 T2 T3 TB
IS INSTALLED
HAZARDOUS VOLTAGE! 3 REMOVE JUMPER TO INTERFACE WITH EVF
INTERLOCK
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS 4 PRESS SW3 BUTTON FOR SHOW THE MEMORABLE ERROR.
BEFORE SERVICING. THE 7-SEG WILL OFF FOR 2 SECONDS BEFORE DISPLAY THE
MOMORABLE ERROR CODES THAT ARE THE CAUSES OF
FAILURE TO DISCONNECT POWER EACH LOCKOUT. AFTER THAT THE 7-SEG WILL OFF FOR
EVF INTERLOCK

BEFORE SERVICING CAN CAUSE 2 SECONDS AND RETURN TO DISPLAY THE EXISTING
SEVERE PERSONAL INJURY OR DEATH. ERROR/STATUS CODES.IF MORE THAN 1 ERROR HAPPENS,
THEY ARE DISPLAYED 2 SECOND EACH.IF THERE IS NOT ANY
IMPORTANT MEMORABLE ERRORS,THE NORMAL CODE WILL BE DISPLAYED.
PRESS AND HOLD SW3 BUTTON FOR 4 SECONDS TO
CLEAR THE MEMORABLE ERROR.
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED 3
TO ACCEPT ANY OTHER WIRING.

23
Schematic &
Termination Diagram RAUP 400-500

SCHEMATIC&TERMINATION DIAGRAM : RAUP400/500


NOTE :-
FOR RAUP400/500 - COMPRESSOR OVERLOAD ARE INTERNALLY PROTECTED

NOTES: LEGEND
SEE UNIT NAMEPLATE 1 DASHED LINES INDICATE RECOMMENDED FIELD
FOR LINE VOLTAGE WIRING BY OTHERS. DASHED LINE ENCLOSURES
DEVICE
DESCRIPTION
L1 L2 L3 N FUSED DISCONNECT SWITCH EVF-C / EVF-OL AND/OR DASHED DEVICE OUTLINES INDICATE DESIGNATION
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE LPCO LOW PRESSURE CUT-OUT
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING. HPCO HIGH PRESSURE CUT-OUT
EVF
2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER HMWT HIGH MOTOR WINDING T-STAT
IS INSTALLED
OL 1, 2, 3, 4 INTERNAL OVER LOAD, COMPRESSOR
3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF-OL INTERNAL PROTECTOR, EVAPORATOR FAN
INTERLOCK
EVF-C STARTER, EVAPORATOR FAN
A-C1, A-C2, B-C3, B-C4 STARTER, COMPRESSOR
START

EVF-OL
STOP
MCB

EVF EVAPORATOR FAN


EVF-C

FUSED
S1 SYSTEM SWITCH
DISCONNECT
CF 1, 2, 3, 4 FAN, CONDENSOR
SWITCH
EVF-C(AUX) MCB CIRCUIT BREAKER
L1 L2 L3 N
PT C5 STARTER, CONDENSOR FAN
PT POWER TERMINALS
TB TERMINATION BLOCK
SUPPLIED & INSTALLED BY CUSTOMER
FACTORY INSTALLED
TERMINATION BLOCK, CONTROL
TX1 TRANSFORMER 240V : 21V, 8V
C1, C2, C3, C4 COMPRESSOR
A-C1 A-C2 B-C3 B-C4
C5 CCH CRANKCASE HEATER

OL1 OL2 OL3 OL4 E 5T1 5T2 5T3 TB

C1 C2 C3 C4

COMPR. 1 COMPR. 2 COMPR. 3 COMPR. 4


STEP 1 STEP 3 STEP 2 STEP 4

CF1 CF2 CF3 CF4

3
T1 MCB
32 31
FOR RAUP500 ONLY
T2
EVF INTERLOCK
WARNING
HAZARDOUS VOLTAGE!
T3
30 DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
J2 INPUT J1 FAILURE TO DISCONNECT POWER
33 BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

STARTER CONTROLLER IMPORTANT


USE COPPER CONDUCTORS ONLY
POWER
33
240V
30 MODULE TO PREVENT EQUIPMENT DAMAGE.
SUPPLY UNIT TERMINALS ARE NOT DESIGNED
240 0 TO ACCEPT ANY OTHER WIRING.

TX1 J5 J4 OUTPUT J3

240 V - CONTROL WIRING


PT

L1 L2 L3 N E

30

31

J3 J3 J3 J3
J3
32C

32D
32A

32B

C4 C2 C3 C1 32
30

30

C5 37 30 36 30 35 30 34 30 31
30 FOR CCH 32 FOR CCH
OPTION OPTION FOR CCH
32 33 30 OPTION
32 A1 A2 A1 A2 A1 A2 32
MCB

T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11
C5 32D 32C 32B 32A
B-C4 B-C3 FOR CCH A-C2 A-C1
OPTION
32

CCH1 CCH2 CCH3 CCH4

JUMPER

TO STARTER
CONTROLLER TX1
J2

24
Schematic &
Termination Diagram RAUP 400-500

COMPONENT LAY-OUT/POWER WIRING : RAUP400/500

POWER CABLES SHOWN IN COLOR


FOR ILLUSTRATION ONLY.
THE ACTUAL POWER CABLE
COLOR IS BLACK OR RED. TO ALL FAN MOTORS (IN PARALEL)
G RRR
3 10 14 5

PT

L1 L2 L3 N E E
5T2
5T3
5T1

7
1TB5

1000mm

2 8 9
B-C4 B-C3 A-C2 A-C1
10
8
MCB

J3 J4 J5 500 mm C5
240V/21, 8V

11 12 14 12 14 12 14 12 14
TX1

9
STARTER
CONTROLLER 4

MODULE 582mm
1
CIRCUIT # B TB
J1 J2
345mm

9
345mm

CONTROL LINE
T4
T6
T7
T1
T2
T3

T5

CIRCUIT # A
CONTROL LINE
374mm 6

COMPRESSOR #1
COMPRESSOR #4-POWER LINE ADD FOR CCH OPTION
COMPRESSOR #3-POWER LINE POWER LINE
COMPRESSOR #2-POWER LINE

NO. DESCRIPTION QTY.


1 STARTER CONTROLLER 1
POWER TOTAL
CABLE LENGTH 2 TRANSFORMER 240 V/21 V & 8 V ; 30 VA 1
SIZE 3 TERMINAL BLOCK, POWER 3
2 _ 4 CIRCUIT BREAKER ABB, 1P, (6A) 1
COMP #1 6mm
5 TERMINAL BLOCK, FAN MOTOR 4
2 _ * 6 TERMINAL BLOCK, 3P 1
COMP #2 6mm
7 TERMINAL STOPPER 4
2 _ 8 DIN RAIL FOR MAGNETIC, Total Length 516
COMP #3 6mm
9 WIRE DUCT, Total Length 2646
2 10 TERMINAL BLOCK, N E 2
COMP #4 6mm _
11 CONTACTOR FOR FAN MOTOR WITH AUXILLARY CONTACT 1
12 CONTACTOR FOR COMPRESSOR 4
13 PANEL, STARTER 1

* * 14 AUXILLARY CONTACTOR 4

NOTE : * USE TERMINAL BLOCK, 7P FOR COMPRESSOR CRANKCASE HEATER OPTION


** ADD ONTO ITEM 14 FOR COMPRESSOR CRANKCASE HEATER OPTION

25
Schematic &
Termination Diagram RAUP 400-500

STARTER CONTROLLER MODULE - I/O WIRING :-RAUP400/500

INPUT TYPICAL WIRING FOR RAUP 400/500 OUTPUT


J1 J3
LPCO1
39 LPCO 1 RESET 1 COM 1 33
40 A-C1
COM 0 RESET 2 A CIRCUIT A-C1 34
40
HPCO1 RESET 3 COMPRESSORS
41 HPCO 1 COM 2 33
SYSTEM RESET A-C2
OL 1 RESET 1 = RESET CIRCUIT A ON ERROR A-C2 35

COM 0 RESET 2 = RESET CIRCUIT B ON ERROR COM 3 33


SYSTEM RESET : = RESET SYSTEM ON ERROR B-C3
OL 2 COMP. : START-UP TIMING B CIRCUIT B-C3 36
A CIRCUIT A-C1 ON DELAY TIME = 1 min
HMWT 1 COMPRESSORS COM 4 33
A CIRCUIT A-C2 ON DELAY TIME = 2 min B-C4
COM 0 B CIRCUIT B-C3 ON DELAY TIME = 1.5 min B-C4 37
B CIRCUIT B-C4 ON DELAY TIME = 2.5 min
HMWT 2 FAN FOR COM 5 33
RAUP MODEL ONLY
C5
- C5 38

-
LPCO2
44 LPCO 2
45
45
COM 0 WARNING : - CONTACT INPUTS ONLY J4 T2 T3
HPCO2
46 HPCO 2 - NO AC SIGNAL AT INPUTS ALM/NC
OL 3 COM
COM 0 ALM/NO
OL 4 TRIP
HMWT 3 7 SEGMENT DISPLAY CODE TABLE LIGHT
COM 0 7 Segment Display Error Description
-- NORMAL
2
HMWT 4 L1 LPCO 1 Error
S1 H1 HPCO 1 Error
TO TEMP. CONTROLLER STEP 1
COM 0
O1
O2
OL 1 Error
OL 2 Error
CIRCUIT A N L (240 V)
TO TEMP. CONTROLLER STEP 2
2
S2 t1 HMWT 1 Error
t2 HMWT 2 Error
TO TEMP. CONTROLLER STEP 3
S3 L2 LPCO 2 Error
COM 0 H2 HPCO 2 Error
240V/21, 8V

TO TEMP. CONTROLLER STEP 4 O3 OL 3 Error


S4 O4 OL 4 Error
CIRCUIT B
t3 HMWT 3 Error J5
TX2

t4 HMWT 4 Error
S1 - S4 THERMOSTAT STATUS

INPUT: USE BLACK COLOR 0.5 SQMM. OUTPUT: USE BLACK 1 SQMM.

NOTES:

TERMINATION (CONTROL) 1 DASHED LINES INDICATE RECOMMENDED FIELD


WIRING BY OTHERS. DASHED LINE ENCLOSURES
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
N LINE ENCLOSURES INDICATE ALTERNATE
CIRCUIT B CIRCUIT A CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
32 33 30 2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER
IS INSTALLED
3 REMOVE JUMPER TO INTERFACE WITH EVF
MCB

INTERLOCK
4 PRESS SW3 BUTTON FOR SHOW THE MEMORABLE ERROR.

C3 C2 TB T1 T2 T3 THE 7-SEG WILL OFF FOR 2 SECONDS BEFORE DISPLAY THE


COIL
COIL

MOMORABLE ERROR CODES THAT ARE THE CAUSES OF


EACH LOCKOUT. AFTER THAT THE 7-SEG WILL OFF FOR
2 SECONDS AND RETURN TO DISPLAY THE EXISTING
ERROR/STATUS CODES.IF MORE THAN 1 ERROR HAPPENS,
THEY ARE DISPLAYED 2 SECOND EACH.IF THERE IS NOT ANY
EVF INTERLOCK

MEMORABLE ERRORS,THE NORMAL CODE WILL BE DISPLAYED.


PRESS AND HOLD SW3 BUTTON FOR 4 SECONDS TO
CLEAR THE MEMORABLE ERROR.
C4 C1
WARNING
HAZARDOUS VOLTAGE!
CONTROL BOX 3
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.

26
Schematic &
Termination Diagram RAUP 600

SCHEMATIC&TERMINATION DIAGRAM :-RAUP600


NOTE :-
FOR RAUP600 - COMPRESSOR OVERLOAD ARE EXTERNALLY PROTECTED
NOTES: LEGEND
SEE UNIT NAMEPLATE
FOR LINE VOLTAGE 1 DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
DEVICE
L1 L2 L3 N FUSED DISCONNECT SWITCH EVF-C / EVF-OL DESCRIPTION
AND/OR DASHED DEVICE OUTLINES INDICATE DESIGNATION
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE LPCO LOW PRESSURE CUT-OUT
CIRCUITRY OR AVAILABLE SALES OPTIONS.
EVF SOLID LINE INDICATES FACTORY WIRING. HPCO HIGH PRESSURE CUT-OUT

2 REMOVE JUMPER WHEN TEMPERATURE CONTROLLER HMWT HIGH MOTOR WINDING T-STAT
IS INSTALLED
OL 1, 2, 3, 4 EXTERNAL OVER LOAD, COMPRESSOR
3 REMOVE JUMPER TO INTERFACE WITH EVF
EVF-OL INTERNAL PROTECTOR, EVAPORATOR FAN
INTERLOCK
EVF-C STARTER, EVAPORATOR FAN
START

A-C1, A-C2, B-C3, B-C4 STARTER, COMPRESSOR


EVF-OL
STOP
MCB

EVF-C

FUSED EVF EVAPORATOR FAN


S1 SYSTEM SWITCH
SWITCH CF 1, 2, 3, 4, 5, 6 FAN, CONDENSOR
EVF-C(AUX)
L1 L2 L3 N MCB CIRCUIT BREAKER
PT
C5 STARTER, CONDENSOR FAN
PT POWER TERMINALS
TB TERMINATION BLOCK
SUPPLIED & INSTALLED BY CUSTOMER
FACTORY INSTALLED
TERMINATION BLOCK, CONTROL
TX1 TRANSFORMER 240V : 21V, 8V

A-C1 A-C2 B-C3 B-C4 C1, C2, C3, C4 COMPRESSOR


C5
CCH CRANKCASE HEATER

E 5T1 5T2 5T3 TB


OL1 OL2 OL3 OL4

C1 C2 C3 C4

COMPR. 1 COMPR. 2 COMPR. 3 COMPR. 4


STEP 1 STEP 3 STEP 2 STEP 4

CF1 CF2 CF3 CF4 CF5 CF6

3
T1 MCB
32 31
T2
EVF INTERLOCK
T3
30

J2 INPUT J1 WARNING
33 HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
STARTER CONTROLLER BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
POWER
33
240V
30 MODULE BEFORE SERVICING CAN CAUSE
SUPPLY SEVERE PERSONAL INJURY OR DEATH.
240 0

TX1 J5 J4 OUTPUT J3 IMPORTANT


USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.

240 V - CONTROL WIRING


PT

L1 L2 L3 N E

30

31

J3 J3 J3 J3
J3
32C

32D
32A

32B

C4 C2 C3 C1 32
30

30

C5 37 30 36 30 35 30 34 30 31
30 FOR CCH 32 FOR CCH
OPTION OPTION FOR CCH
32 33 30 OPTION
32 A1 A2 A1 A2 A1 A2 32
MCB

T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11
C5 32D 32C 32B 32A
B-C4 B-C3 FOR CCH A-C2 A-C1
OPTION
95 95 95 95 32

OL 4 OL 3 OL 2 OL 1 CCH1 CCH2 CCH3 CCH4


96 96 96 96

55 54 53 44 43 42 JUMPER
{

TO J2 TO J1 TO STARTER
CONTROLLER TX1
J2

27
Schematic &
Termination Diagram RAUP 600

COMPONENT LAY-OUT/POWER WIRING :-RAUP600

POWER CABLES SHOWN IN COLOR


FOR ILLUSTRATION ONLY.
THE ACTUAL POWER CABLE
COLOR IS BLACK OR RED.

TO ALL FAN MOTORS (IN PARALEL)


3 10 13 5
G RR R

PT

L1 L2 L3 N E E
5T2
5T3
5T1

7
1TB5

1000mm

2 8 9
B-C4 B-C3 A-C2 A-C1
10
8
MCB

J3 J4 J5 500mm C5
240V/21, 8V

11 12 15 12 15 12 15 12 15
TX1

9
STARTER OL4 14 OL3 14 OL2 14 OL1 14
CONTROLLER 4

MODULE 582mm
1
CIRCUIT # B TB
345mm

J1 J2 9
CONTROL LINE
345mm
T4
T6
T2
T3

T5
T7
T1

CIRCUIT # A
374mm 6 CONTROL LINE

COMPRESSOR #4-POWER LINE ADD FOR CCH OPTION COMPRESSOR #1


COMPRESSOR #3-POWER LINE POWER LINE
COMPRESSOR #2-POWER LINE

NO. DESCRIPTION QTY.


1 STARTER CONTROLLER 1
POWER TOTAL
CABLE LENGTH 2 TRANSFORMER 240 V/21 V & 8 V ; 30 VA 1
SIZE 3 TERMINAL BLOCK, POWER 3
2 _ 4 CIRCUIT BREAKER ABB, 1P, (6A) 1
COMP #1 6mm
5 TERMINAL BLOCK, FAN MOTOR 4
2 _ * 6 TERMINAL BLOCK, 3P 1
COMP #2 6mm
7 TERMINAL STOPPER 4
2 _ 8 DIN RAIL FOR MAGNETIC, Total Length 516
COMP #3 6mm
9 WIRE DUCT, Total Length 2646
2 10 TERMINAL BLOCK, N E 2
COMP #4 6mm _
11 CONTACTOR FOR FAN MOTOR WITH AUXILLARY CONTACT 1
12 CONTACTOR FOR COMPRESSOR 4
13 PANEL, STARTER 1
14 OVERLOAD CONTACTOR 4

* * 15 AUXILLARY CONTACTOR 4

NOTE : * USE TERMINAL BLOCK, 7P FOR COMPRESSOR CRANKCASE HEATER OPTION


** ADD ONTO ITEM 15 FOR COMPRESSOR CRANKCASE HEATER OPTION

28
Schematic &
Termination Diagram RAUP 600

S TAR TER CONTR OLLER MODULE - I/O WIRING :-RA UP600

INPU T TYPICA L WIRING FOR RA UP600 OUTPU T


J1 J3
LPCO1
39 LPCO 1 RESE T 1 COM 1 33
40 A-C1
40
COM 0 RESE T 2 A CIRCUI T A-C1 34
HPCO1 RESE T 3 COMPRESSORS
41 HPCO 1 COM 2 33
SYSTEM RESE T A-C2
OL1
42 OL 1 RESE T 1 = RESE T CIRCUI T A ON ERR OR A-C2 35
43 RESE T 2 = RESE T CIRCUI T B ON ERR OR
COM 0 COM 3 33
B-C3
OL2
43 SYSTEM RESE T : = RESE T SYSTEM ON ERR OR
44 OL 2 COM P. : S TAR T-UP TIMING B CIRCUI T B-C3 36
A CIRCUI T A-C1 ON DEL AY TIME = 1 min
45 HMW T 1 COMPRESSORS COM 4 33
HMWT1
46
A CIRCUI T A-C2 ON DEL AY TIME = 2 min B-C4
46
COM 0 B CIRCUI T B-C3 ON DEL AY TIME = 1.5 min B-C4 37
HMWT2 B CIRCUI T B-C4 ON DEL AY TIME = 2.5 min
47 HMW T 2 FAN FOR COM 5 33
RA UP MODE L ON LY
C5
- C5 38

-
LPCO2
50 LPCO 2 T2 T3
51
51
COM 0 WARNING : - CON TAC T INPUTS ON LY ALM/NC
HPCO2
52 HPCO 2 - NO AC SIGNA L AT INPUTS COM
OL3
53 OL 3 ALM/NO
54
COM 0
OL4
54 TRI P
55 OL 4 LIGH T
HMWT3
56 HMW T 3 7 SEGMEN T DISPL AY CODE TABLE
57
57 COM 0 7 Segment Displa y Error Descr iption
HMWT4 -- NORMA L
2
58 HMW T 4 L1 LPCO 1 Error

TO TEM P. CONTR OLLER STE P 1


S1 H1 HPCO 1 Error N L (240 V)
O1 OL 1 Error
COM 0 O2 OL 2 Error
CIRCUI T A
TO TEM P. CONTR OLLER STE P 2
2
S2 t1 HMW T 1 Error
t2 HMW T 2 Error
TO TEM P. CONTR OLLER STE P 3
S3 L2 LPCO 2 Error
COM 0 H2 HPCO 2 Error
2 4 0 V /2 1 , 8 V

TO TEM P. CONTR OLLER STE P 4 O3 OL 3 Error


S4 O4 OL 4 Error
CIRCUI T B
t3 HMW T 3 Error J5
TX2

t4 HMW T 4 Error
S1 - S4 THERMOS TAT S TATUS

INPU T: USE BLA CK COLOR 0.5 SQMM. OUTPU T: USE BLA CK 1 SQMM.
NO TES:
1 DASHED LINES INDIC ATE RECOMMENDED FIELD
WIRING B Y O THERS . DASHED LINE ENCLOSURES
TERMIN ATION (CONTR OL) AND/OR D ASHED DEVICE OUTLINES INDIC ATE
COMPONENTS PR OVIDED B Y THE FIELD . PHAN TOM
LINE ENCLOSURES INDIC ATE ALTERN ATE
CIRCUIT R Y OR AVAILABLE SALES OPTIONS .
N SOLID LINE INDIC ATES FAC TOR Y WIRING.

32 33 30 2 REMO VE JUMPER WHEN TEMPER ATURE CONTR OLLER


CIRCUI T B CIRCUI T A IS INS TALLED
3 REMO VE JUMPER T O INTER FACE WITH EVF
MC B

INTERLOCK
4 PRESS SW3 B UT TON FOR SHO W THE MEMORABLE ERR OR.
TB T1 T2 T3 THE 7-SEG WIL L OFF FOR 2 SECONDS BEFORE DISPL AY THE
MOMORABLE ERR OR CODES TH AT ARE THE CA USES OF
EA CH LOCK OU T. AFTER TH AT THE 7-SEG WIL L OFF FOR
C O IL

C3 C2
C O IL

2 SECONDS AND RETURN T O DISPL AY THE EXISTING


ERR OR/S TATUS CODES .IF MORE THAN 1 ERR OR HAPPENS ,
E V F IN T E R L O C K

THE Y ARE DISPL AYED 2 SECOND EA CH.IF THERE IS NO T AN Y


MEMORABLE ERR ORS ,THE NORMA L CODE WIL L BE DISPL AYED .
PRESS AND HOLD SW3 B UT TON FOR 4 SECONDS TO
CLEAR THE MEMORABLE ERR OR.
C4 C1
3
WARNING
HAZARDOUS VO LTAGE!
CONTR OL BO X DISCONNEC T AL L ELECTRIC PO WER
INCLUDING REMO TE DISCONNECTS
BEFORE SE R VICING.
FAILURE T O DISCONNEC T PO WER
BEFORE SE R VICING CAN CA USE
SEVERE PERSONA L INJU R Y OR DE ATH.

IMPO R TAN T
USE COPPER CONDUC T ORS ON LY
T O PREVEN T EQ UIPMEN T DAMA GE.
UNI T TERMINALS ARE NO T DESIGNED
T O ACCEP T AN Y O THER WIRING.
035-0766G

29
Installation Checklist

RAUP Trane Air Cooled Condensing Unit

This list must checked off by the installer to ensure correct installation before the unit start up.

Unit acceptance
Check for damage, if any, on transportation
Check for equipment shipped against delivery slip
Check lifting system

Unit positioning
Remove packaging
Check position of unit
Check unit is level
Check clearance around condenser
Check clearance required for maintenance access
Check position of rubber pads

Refrigerant circuit
Check filter dryer and sight glass presence
Check oil traps presence on discharge line (if there vertical risers>3m)
Check pitch for horizontal lines (1cm/m)
Check refrigerant presence

Electrical equipment
Check direction of rotation of compressors and fan motors
Check installation and rating of mains power switch/fuse
Check that electrical connections comply with specification
Check that electrical connections match information on manufacturer’s identification plate
Check electrical connections and connections to mains power switch

General
Check available cooling charge (50% of rated installation load)
Check with other handling installation works

Comments:........................................................................................................................................................................
..........................................................................................................................................................................................

..........................................................................................................................................................................................

..........................................................................................................................................................................................

Signature: ................................................. Name ............................................................................................................

Order No ...........................................................................................................................................................................

Work site:..........................................................................................................................................................................

Please return to your Trane Service Agency

30
Commissioning Log Sheet

START-UP ENGINEER/TECHNICIAN NAME:

PROJECT NAME :

DEALER/CONTRACTOR :

SALES OFFICE LOCATION :

DATE COMMISSIONED :

1.Nameplate information
Model No. Serial No.

Voltage RLA

2. Compressor (S)
A. Voltage at Compressor Terminals
Comp. No. 1: T1 T2 T3
Comp. No. 2: T1 T2 T3
Comp. No. 3: T1 T2 T3
Comp. No. 4: T1 T2 T3
Voltage Imbalance : Comp. “1” Comp. “2”

Comp. “3” Comp. “4”

B. Amp Draw
Comp. No. 1: T1 T2 T3
Comp. No. 2: T1 T2 T3
Comp. No. 3: T1 T2 T3
Comp. No. 4: T1 T2 T3

3. Operating Conditions
A. Circuit “A”
Discharge Pressure. Suction Pressure
Liquid Line Pressure. Suction Line Temp.
Liquid Line Temp. SuperHeat
Subcooling. Evap. Entering Air Temp. (DB/WB)
Amblent Temp. Evap. Discharge Air Temp. (DB/WB)

B. Circuit “B”
Discharge Pressure. Suction Pressure
Liquid Line Pressure. Suction Line Temp.
Liquid Line Temp. SuperHeat
Subcooling. Evap. Entering Air Temp. (DB/WB)
Amblent Temp. Evap. Discharge Air Temp. (DB/WB)

4. Controls

A. All Fans Operating [ ] Yes


Properly? [ ] No Fan Inoperative

5. Refrigerant Piping
Evacuation Level System Charge

31
RAUP-IOM002-0806

August 2006

RAUP-IOM002-0705

http://www.tranethailand.com Trane has a policy of continuous product and product data implement and reserves the
A Business of American Standard Company right to change design and specifications without notice.

You might also like