FGWilson - P2000 (2000kVA Prime)
FGWilson - P2000 (2000kVA Prime)
FGWilson - P2000 (2000kVA Prime)
com
P2000/P2250E
Image for illustration purposes only.
Voltage, Frequency Prime Standby Engine Make & Model: Perkins® 4016TAG2A
400V, 50 Hz 2000.0 kVA / 1600.0 kW 2250.0 kVA / 1800.0 kW Alternator manufactured for
Leroy Somer
FG Wilson by:
- / - - / -
Alternator Model: LL9324H
Ratings at 0.8 power factor. Control Panel: DCP-10
Please refer to the output ratings technical data section for Base Frame: Heavy Duty Fabricated Steel
specific generator set outputs per voltage. Circuit Breaker Type: / 3 Pole ACB-Option
Frequency: 50 Hz 60 Hz
Engine Speed: rpm 1500 -
Prime Rating
These ratings are applicable for supplying continuous electrical power Fuel Tank Capacity:
(at variable load) in lieu of commercially purchased power. There is no -
litres (US gal)
limitation to the annual hours of operation and this model can supply 10%
Fuel Consumption: l/hr (US gal/hr)
overload power for 1 hour in 12 hours.
(100% Load) - Prime 425.7 (112.5) -
Standby Rating
These ratings are applicable for supplying continuous electrical power (at - Standby 486.8 (128.6) -
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
Available Options
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m FG Wilson offer a range of optional features to tailor our generator
(328 ft) A.S.L. 30% relative humidity. sets to meet your power needs. Options include:
Fuel consumption data at full load with diesel fuel with specific gravity of z Upgrade to CE Certification
0.85 and conforming to BS2869: 1998, Class A2.
z A wide range of Sound Attenuated Enclosures
z A variety of generator set control and synchronising panels
z Additional alarms and shutdowns
z A selection of exhaust silencer noise levels
For further information on all of the standard and optional features
accompanying this product please contact your local Dealer or visit:
www.FGWilson.com
5799 (228.3) 2298 (90.5) 3068 (120.8) 15135 (33367) 15451 (34064)
Dry = With Lube Oil Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22.
Generator set pictured may include optional accessories.
Engine Technical Data Air Systems 50 Hz 60 Hz
60 Hz - - -
(Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869,
Class A2)
Alternator Physical Data Alternator Operating Data
Alternator
50 Hz 60 Hz
Performance Data:
Motor Starting
6816 6351 5754
Capability* kVA
Short Circuit
300 300 300
Capacity** %
Documentation
A full set of operation and maintenance manuals and circuit wiring diagrams.
The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.
Warranty
All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's
warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com.