TL-1P35A-EL-SLD-0015 - Rev.A1 - SLD For AC UPS (1U64-SS19-UPS-501)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

3Ph, 3W, 415V, 50Hz 3Ph, 3W, 415V, 50Hz 3Ph, 3W, 415V, 50Hz NOTES:
POWER SUPPLY POWER SUPPLY POWER SUPPLY
FROM 1U64-SS19-EPMCC-344 BUS A FROM 1U64-SS19-EPMCC-344 BUS B FROM 1U64-SS19-EPMCC-344 BUS B 1. FOR SYMBOL AND LEGENDS REFER TL-1P35A-EL-SLD-0001 SHEET 02 OF 02.
(SEE DWG. NO. TL-1P35A-EL-SLD-0007) (SEE DWG. NO. TL-1P35A-EL-SLD-0007) (SEE DWG. NO. TL-1P35A-EL-SLD-0007) 2. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH AC UPS SPECIFICATION
L TP-1ZZZA-EL-SPE-0006 AND DATASHEET TL-1P35A-EL-DAT-0011. L
3. REFER CLAUSE 8.6.2 OF "TP-1ZZZA-EL-SPE-0006" FOR OPERATION
1RX3CX120 sqmm 1RX3CX120 Sq.mm. 1RX3CX240 Sq.mm.
PHILOSOPHY OF AC UPS.
4. REFER CLAUSE 9.12.2 OF "TP-1ZZZA-EL-SPE-0006” FOR METERING
1U64-SS19-UPS-501A SURGE PROTECTION DEVICE 1U64-SS19-UPS-501B SURGE PROTECTION BYPASS (70 kVA)
(75kVA) SURGE PROTECTION DEVICE REQUIREMENT OF AC UPS.
(70 kVA)
(75kVA) (70 kVA)
(75kVA) DEVICE LOCATION : SRR2 5. REFER CLAUSE 9.12.4 OF "TP-1ZZZA-EL-SPE-0006” FOR ALARM REQUIREMENT
LOCATION : SRR2 LOCATION : SRR2 OF AC UPS.
VSS V CL.1.5 VSS V CL.1.5 VSS V CL.1.5 6. THIS SINGLE LINE DIAGRAM IS INDICATIVE ONLY. IT IS THE RESPONSIBILITY OF
THE VENDOR TO PROVIDE ALL NECESSARY COMPONENTS REQUIRED FOR THE
MCCB MCCB MCCB HZ
SAFE AND RELIABLE OPERATION OF THE AC UPS SYSTEM.
HZ HZ
3P (SEE NOTE-4) (SEE NOTE-4) 3P (SEE NOTE-4) 7. THE ALARMS SHALL BE WIRED TO TERMINAL BLOCK FOR REMOTE
(SEE NOTE-9) (SEE NOTE-9) 3P (SEE NOTE-9)
CL.1.5 CL.1.5 CL.1.5 ANNUNCIATION AT ECS AS PER THE REQUIREMENT SPECIFIED IN I/O LIST
EXTERNAL 240VAC
K
DOCUMENT (TL-1P35A-EL-SCH-0003). K
POWER SUPPLY ASS A ASS A ASS A 8. UPS SHALL BE PROVIDED WITH NECESSARY ARRANGEMENTS FOR MONITORING
MODBUS TO
TCP/IP ECS AND ANALYZING THE BELOW PARAMETERS FOR PREDICTIVE MAINTENANCE OF
3Ph 3Ph BYPASS THE EQUIPMENT. MONITORING AND ASSET PERFORMANCE MANAGEMENT AND
INPUT, ISOLATION INPUT, ISOLATION TRANSFORMER ALL THESE PARAMETERS SHALL BE MADE AVAILABLE TO ECS THROUGH
TRANSFORMER (SEE NOTE-7) ETHERNET CONNECTIVITY VIA MODBUS TCP/IP PROTOCOL.
TRANSFORMER
- HUMIDITY
COMMON ALARM - TEMPERATURE
TO DCS RECTIFIER RECTIFIER - ONLINE GROUND FAULT MONITORING
MODBUS CONDITION
MONITORING - INTELLIGENT BATTERY MONITORING
TCP/IP 9. ALL INDICATING LAMPS SHALL BE CONSIDERED AS PER CLAUSE 9.12.3 OF
SYSTEM
"TP-1ZZZA-EL-SPE-0006".
DC DC 10. EACH UPS MODULE SHALL HAVE THE FACILITY OF INITIATING AUTOMATIC
CHOKE VOLTAGE (SEE NOTE-8)
J CHOKE PROGRAMMED AS WELL AS MANUAL BATTERY CAPACITY TEST FROM ITS J
STABILIZER
CONDENSER FRONT PANEL.
CONDENSER 11. EACH UPS SET SHALL BE PROVIDED WITH FAULT DIAGNOSTIC UNIT AS PER
CLAUSE 9.14 OF TP-1ZZZA-EL-SPE-0006.
V V 12. FOLLOWING SIGNALS SHALL BE WIRED TO UPS FROM ACDB:
V - OUTGOING FEEDER TRIP COMMON ALARM
- GROUND FAULT ALARM
A A A 13. DC CENTRE ZERO BI-DIRECTIONAL AMMETER TO INDICATE THE CHARGING AND
MCCB MCCB
3P 3P DISCHARGING CURRENT OF THE BATTERYSHALL BE PROVIDED.
BATTERY CONNECTION
14. IN CASE OF MAINS/RECTIFIER FAILURE OF BOTH UPS, THE BATTERY SHALL
FEED THE INVERTER WITHOUT ANY INTERRUPTION. DCS/ESD LOADS SHALL BE
SWITCHED ON FOR 30 MINS ONLY. FAS/TELECOM LOADS SHALL BE SWITCHED
I LOCATION : BATTERY ROOM, LOCATION : BATTERY ROOM, ON FOR 120 MINS. FEEDERS TO DCS/ESD (FEEDER TYPE M29) SHALL BE I
SRR2 INVERTER INVERTER MCCB SRR2 PROVIDED WITH TIMER.
A V V A NC

SEE NOTE-13 (SEE NOTE-4) (SEE NOTE-4) SEE NOTE-13


STATIC STATIC
1U64-SS19-BS-501C STATIC 1U64-SS19-BS-501D
BATTERY MCCB SWITCH SWITCH BATTERY MCCB
MCCB BOX HZ kW HZ kW SWITCH MCCB BOX
ON/OFF STATUS ON/OFF STATUS
Ex'd'. IIC, T3 Ex'd'. IIC, T3
V kVA V kVA

A A
1U64-SS19-BA-501C 1U64-SS19-BA-501D
1 x 100%, MCCB MCCB
NC 1 x 100%
H Ni-Cd, `-'Ah NO H
Ni-Cd,`-'Ah
120 MIN BATTERY MCCB MCCB 120 MIN BATTERY
BACKUP NC NC BACKUP

2RX2CX185 Sq.mm. 2RX2CX185 Sq.mm.

& OUTGOING FEEDER TRIP


1U64-SS19-ACDB-501

GROUND FAULT ALARM,


LOCATION: SRR 2 V V
G G

SIGNAL (NOTE-12)
EXTERNAL 240V AC MCCB MCCB
NC INTERLOCK
POWER SUPPLY NO

XX/1 A PF XX/1 A PF
A A
CL.1.0
THIS DRAWING IS THE PROPERTY OF NUMALIGARH REFINERY LTD. AND SHALL NOT BE REPRODUCED, COPIED, LENT OR DISPOSED WITHOUT NUMALIGARH REFINERY LTD. PERMISSION FOR OTHER PURPOSE.

CL.1.0

115V, 1PH, 50Hz, XXA AL BUS


F
ON ON REFERENCE DOCUMENTS F

DOC NO DOC TITLE


TIMER TL-1P35A-EL-SLD-0001 OVERALL KEY SINGLE LINE DIAGRAM
30 Min.
TL-1P35A-EL-SCM-0001 METERING & PROTECTION SCHEMATIC DIAGRAM FOR HV AND MV SYSTEM
TP-IZZZA-EL-SPE-0017 SPECIFICATION FOR CONDITION MONITORING AND ASSET
PERFORMANCE MANAGEMENT
TL-1P35A-EL-SCH-0003 ECS I/O LIST
TL-1P35A-EL-BLD-0001 BLOCK DIAGRAM OF ELECTRICAL CONTROL SYSTEM FOR SS# 19
SCHEMATIC TL-1P35A-EL-BLD-0002 BLOCK DIAGRAM FOR CONDITION MONITORING & ASSET
SCHEMATIC
E TYPE M28 TYPE M29 PERFORMANCE + MANAGEMENT FOR SS# 19 E
(FEEDER FOR FAS / TELECOM) (FEEDER FOR DCS / ESD) TP-1ZZZA-EL-BOD-0001 ENGINEERING DESIGN BASIS FOR ELECTRICAL
TP-1ZZZA-EL-SPE-0006 SPECIFICATION FOR AC UPS SYSTEM
FEEDER LIST FOR 1U64-SS19-ACDB-501 TL-1P35A-EL-DAT-0011 DATA SHEET FOR AC UPS
TL-1P35A-EL-CAL-0007 AC UPS AND BATTERY SIZING
VOLTAGE LOAD RATED FULL LOAD SCHEME
SR. NO. LOAD TAG NUMBER DESCRIPTION (V AC) TYPE POWER CURRENT FUSE RATING TYPE
CABLE SIZE
(KVA) (A) (A) (Sq.mm)

1 PDB-1 INSTRUMENT PDB-1 115 F 14.08 122 200 TYPE M29 2RX2CX240
2 PDB-1 INSTRUMENT PDB-1 115 F 14.08 122 200 TYPE M29 2RX2CX240
D D
3 PDB-2A INSTRUMENT PDB-2A 115 F 16 139 200 TYPE M29 1RX2CX240

4 PDB-2A INSTRUMENT PDB-2A 115 F 16 139 200 TYPE M29 1RX2CX240


A1 28-09-2022 ISSUED FOR REVIEW VKS ABR AKG
5 PDB-2B INSTRUMENT PDB-2B 115 F 11.52 100 150 TYPE M29 1RX2CX240
Owner
Rev. Date Reason for Issue Prepared Checked Approved Approved
6 PDB-2B INSTRUMENT PDB-2B 115 F 11.52 100 150 TYPE M29 1RX2CX240
7 PDB-3 INSTRUMENT PDB-3 (TELECOM & FAS PANEL) 115 F 2.88 25 40 TYPE M28 1RX2CX70
REVISION INDEX:
8 PDB-3 INSTRUMENT PDB-3 (TELECOM & FAS PANEL) 115 F 2.88 25 40 TYPE M28 1RX2CX70 EPC CONTRACTOR: ENGG. SUB CONTRACTOR:
9 PDB-5 INSTRUMENT PDB-5 (TELECOM & FAS PANEL) 115 F 2.24 19.5 40 TYPE M28 1RX2CX50 THERMAX LIMITED
C
10 PDB-5 INSTRUMENT PDB-5 (TELECOM & FAS PANEL) 115 F 2.24 19.5 40 TYPE M28 1RX2CX50
P&ES DIVISION,PUNE GS E&C PVT LTD C

(Earlier POWER DIVISION) MUMBAI


11 - ANAYZER BUILDING 115 F 2.4 21 32 TYPE M29 2RX2CX185

12 - ANAYZER BUILDING 115 F 2.4 21 32 TYPE M29 2RX2CX185 OWNER'S CONSULTANT


13 - UPS FEEDER FOR ECS SYSTEM 115 F 5 43 50 TYPE M29 1RX2CX120
TECHNIP ENERGIES INDIA LTD, CHENNAI
14 - UPS FEEDER FOR ECS SYSTEM 115 F 5 43 50 TYPE M29 1RX2CX120

15 - HVAC CONTROL PANEL SS19 115 F 0.24 2.1 6 TYPE M29 1RX2CX6 NRL's PO NO.: 4300071052-TEC/30.03.2022
16 - HVAC CONTROL PANEL SRR 115 F 0.24 2.1 6 TYPE M29 1RX2CX4 THERMAX CONTRACT NO.: DDC187
B B
17 SPARE-01 SPARE FEEDER 115 F - - 200 TYPE M29 2RX2CX240

18 SPARE-02 SPARE FEEDER 115 F - - 200 TYPE M29 2RX2CX240 NUMALIGARH REFINERY LIMITED
19 SPARE-03 SPARE FEEDER 115 F - - 150 TYPE M29 1RX2CX240 Life Cycle
PROJECT: NUMALIGARH REFINERY LIMITED Code:
20 SPARE-04 SPARE FEEDER 115 F - - 32 TYPE M29 2RX2CX185
UNIT/FACILITY: SULPHUR RECOVERY BLOCK 02
21 SPARE-05 SPARE FEEDER 115 F - - 50 TYPE M29 1RX2CX120 Scale:
HOLD: DRAWING TITLE: SINGLE LINE DIAGRAM - 115V AC UPS
22 SPARE-06 SPARE FEEDER 115 F - - 6 TYPE M29 1RX2CX6 NTS
1. RATING OF SYSTEM COMPONENTS SHALL BE 1U64-SS19-UPS-501 Drg.Size:
23 SPARE-07 SPARE FEEDER 115 F - - 40 TYPE M28 1RX2CX50 UPDATED BASED ON VENDOR INFORMATION
A 2. BATTERY SIZING SULPHUR RECOVERY BLOCK A1 A
24 SPARE-08 SPARE FEEDER 115 F - - 40 TYPE M28 1RX2CX50 3. CABLE SIZE Originator/ Asset Code Disc. Drawing Sequence Rev. Sheet
Contractor Type Number
TL 1P35A EL SLD 0015 A1 1 OF 1