Micom P40 Agile: Ge Grid Solutions
Micom P40 Agile: Ge Grid Solutions
Micom P40 Agile: Ge Grid Solutions
Grid Solutions
Technical Manual
Transformer Protection IED
Hardware Version: M, P
Software Version: 91
Publication Reference: P64x-TM-EN-4.1
Contents
Chapter 1 Introduction 1
1 Chapter Overview 3
2 Foreword 4
2.1 Target Audience 4
2.2 Typographical Conventions 4
2.3 Nomenclature 5
3 Product Scope 6
3.1 Product Versions 6
3.2 Ordering Options 8
4 Features and Functions 9
4.1 Protection Functions 9
4.2 Control Functions 9
4.3 Measurement Functions 10
4.4 Communication Functions 10
5 Compliance 11
6 Functional Overview 12
Chapter 5 Configuration 73
1 Chapter Overview 75
2 Settings Application Software 76
3 Using the HMI Panel 77
ii P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 iii
Contents P64x
iv P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 v
Contents P64x
vi P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 vii
Contents P64x
viii P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 ix
Contents P64x
x P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 xi
Contents P64x
xii P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 xiii
Contents P64x
xiv P64x-TM-EN-4.1
P64x Contents
P64x-TM-EN-4.1 xv
Contents P64x
xvi P64x-TM-EN-4.1
Table of Figures
Figure 1: P64x version evolution 7
Figure 2: Functional overview 12
Figure 3: Hardware architecture 30
Figure 4: Exploded view of IED 31
Figure 5: Front panel (60TE) 33
Figure 6: HMI panel 34
Figure 7: Rear view of populated case 37
Figure 8: Terminal block types 38
Figure 9: Example—fitted IP2x shields (cabling omitted for clarity) 38
Figure 10: Rear connection to terminal block 39
Figure 11: Main processor board 40
Figure 12: Power supply board 41
Figure 13: Power supply assembly 42
Figure 14: Power supply terminals 43
Figure 15: Watchdog contact terminals 44
Figure 16: Rear serial port terminals 45
Figure 17: Input module - 1 transformer board 45
Figure 18: Input module schematic 46
Figure 19: Frequency response 47
Figure 20: Transformer board 48
Figure 21: Input board 49
Figure 22: Standard output relay board - 8 contacts 50
Figure 23: IRIG-B board 51
Figure 24: Fibre optic board 52
Figure 25: Rear communication board 53
Figure 26: Redundant Ethernet board 54
Figure 27: RTD board 56
Figure 28: RTD board 57
Figure 29: High Break relay output board 59
Figure 30: High Break contact operation 60
Figure 31: Software Architecture 64
Figure 32: Frequency Response (indicative only) 70
Figure 33: Navigating the HMI 78
Figure 34: Default display navigation 80
Figure 35: Compensation using biased differential characteristic 101
Figure 36: Transformer winding connections - part 1 103
Figure 37: Transformer winding connections - part 2 104
Figure 38: Magnetising inrush phenomenon 105
Table of Figures P64x
xviii P64x-TM-EN-4.1
P64x Table of Figures
P64x-TM-EN-4.1 xix
Table of Figures P64x
xx P64x-TM-EN-4.1
P64x Table of Figures
Figure 158: IED attached to redundant Ethernet star or ring circuit 340
Figure 159: IED and REB IP address configuration 341
Figure 160: Connection using (a) an Ethernet switch and (b) a media converter 342
Figure 161: Connection using (a) an Ethernet switch and (b) a media converter 346
Figure 162: Control input behaviour 362
Figure 163: Manual selection of a disturbance record 378
Figure 164: Automatic selection of disturbance record - method 1 379
Figure 165: Automatic selection of disturbance record - method 2 380
Figure 166: Configuration file extraction 381
Figure 167: Data file extraction 382
Figure 168: Data model layers in IEC61850 388
Figure 169: Edition 2 system - backward compatibility 393
Figure 170: Edition 1 system - forward compatibility issues 393
Figure 171: Example of Standby IED 394
Figure 172: Standby IED Activation Process 395
Figure 173: GPS Satellite timing signal 398
Figure 174: Timing error using ring or line topology 400
Figure 175: RADIUS server/client communication 418
Figure 176: Rack mounting of products 434
Figure 177: Terminal block types 435
Figure 178: 40TE case dimensions 440
Figure 179: 60TE case dimensions 441
Figure 180: 80TE case dimensions 442
Figure 181: RP1 physical connection 458
Figure 182: Remote communication using K-bus 459
Figure 183: Simulated input behaviour 465
Figure 184: Test example 1 466
Figure 185: Test example 2 467
Figure 186: Test example 3 468
Figure 187: Operating Characteristic Diagram 470
Figure 188: Trip Time Test Plane 470
Figure 189: Harmonic Restraint Test Plane 471
Figure 190: Possible terminal block types 482
Figure 191: Front panel assembly 484
P64x-TM-EN-4.1 xxi
Table of Figures P64x
xxii P64x-TM-EN-4.1
CHAPTER 1
INTRODUCTION
Chapter 1 - Introduction P64x
2 P64x-TM-EN-4.1
P64x Chapter 1 - Introduction
1 CHAPTER OVERVIEW
This chapter provides some general information about the technical manual and an introduction to the device(s)
described in this technical manual.
This chapter contains the following sections:
Chapter Overview 3
Foreword 4
Product Scope 6
Features and Functions 9
Compliance 11
Functional Overview 12
P64x-TM-EN-4.1 3
Chapter 1 - Introduction P64x
2 FOREWORD
This technical manual provides a functional and technical description of General Electric's P642, P643, P645, as
well as a comprehensive set of instructions for using the device. The level at which this manual is written assumes
that you are already familiar with protection engineering and have experience in this discipline. The description of
principles and theory is limited to that which is necessary to understand the product. For further details on general
protection engineering theory, we refer you to General Electric's publication NPAG, which is available online or
from our contact centre.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However we
cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would therefore be
very pleased to hear from you if you discover any errors, or have any suggestions for improvement. Our policy is to
provide the information necessary to help you safely specify, engineer, install, commission, maintain, and
eventually dispose of this product. We consider that this manual provides the necessary information, but if you
consider that more details are needed, please contact us.
All feedback should be sent to our contact centre via:
[email protected]
4 P64x-TM-EN-4.1
P64x Chapter 1 - Introduction
2.3 NOMENCLATURE
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used throughout
the manual. Some of these terms are well-known industry-specific terms while others may be special product-
specific terms used by General Electric. The first instance of any acronym or term used in a particular chapter is
explained. In addition, a separate glossary is available on the General Electric website, or from the General Electric
contact centre.
We would like to highlight the following changes of nomenclature however:
● The word 'relay' is no longer used to describe the device itself. Instead, the device is referred to as the 'IED'
(Intelligent Electronic Device), the 'device', or the 'product'. The word 'relay' is used purely to describe the
electromechanical components within the device, i.e. the output relays.
● British English is used throughout this manual.
● The British term 'Earth' is used in favour of the American term 'Ground'.
P64x-TM-EN-4.1 5
Chapter 1 - Introduction P64x
3 PRODUCT SCOPE
The MiCOM P64x range of devices preserve transformer service life by offering fast protection for transformer
faults. Hosted on an advanced IED platform, the P64x products incorporate Current Differential, Restricted Earth
Fault (REF),Thermal, and Overfluxing protection, plus backup protection for uncleared external faults. Further, the
P64x devices provide a range of transformer condition monitoring functions such as Through-fault monitoring,
loss of life statistics, RTD and CLIO protection functionality.
All devices also provide a comprehensive range of additional features to aid with power system diagnosis and fault
analysis.
Model variants cover two and three winding power transformers, with up to five sets of 3-phase CT inputs. Backup
overcurrent protection can be directionalised, if you select the optional 3-phase VT input.
The P64x range consists of three models; the P642, P643, and P645.
● The P642 provides 8 on-board CTs to support two-winding 3-phase power transformers and 1or 2 single-
phase voltage transformers to support directionalisation and a range of voltage-related functions.
● The P643 provides 12 on-board CTs to support three-winding 3-phase power transformers, a single-phase
voltage transformer and an optional three-phase voltage transformer to support directionalisation and a
range of voltage-related functions including undervoltage, overvoltage and residual overvoltage protection.
● The P645 provides 18 on-board CTs to support three-winding 3-phase power transformers and other
applications needing 5 sets of 3-phase current inputs, a single-phase voltage transformer and an optional
three-phase voltage transformer to support directionalisation and a range of voltage-related functions
including undervoltage, overvoltage and residual overvoltage protection.
The difference in model variants are summarised below:
Feature/Variant P642 P643 P645
Case 40TE 60TE/80TE 60TE/80TE
Number of CT Inputs 8 (6 Bias, 2 EF) 12 (9 bias, 3EF) 18 (15 Bias, 3EF)
Number of VT inputs 1 or 2 1 or 4 1 or 4
Number of bias inputs (3-phase CT sets) 2 3 5
Optically coupled digital inputs 8 - 12 16 - 40 16 - 40
Standard relay output contacts 8 - 12 8 - 24 8 - 24
Function keys No 10 10
Undervoltage/Overvoltage/Residual voltage protection No Yes Yes
Underfrequency/Overfrequency protection No Yes Yes
Overfluxing protection 1-phase only 1-phase + 3-phase 1-phase + 3-phase
Programmable LEDs 8 red 18 tri-colour 18 tri-colour
6 P64x-TM-EN-4.1
P64x Chapter 1 - Introduction
J, K
02
P64x-TM-EN-4.1 7
Chapter 1 - Introduction P64x
8 P64x-TM-EN-4.1
P64x Chapter 1 - Introduction
Note:
If item is enclosed in brackets, this indicates that the feature is an ordering option.
P64x-TM-EN-4.1 9
Chapter 1 - Introduction P64x
10 P64x-TM-EN-4.1
P64x Chapter 1 - Introduction
5 COMPLIANCE
The device has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all target markets. A detailed description of these criteria can be found in the Technical
Specifications chapter.
P64x-TM-EN-4.1 11
Chapter 1 - Introduction P64x
6 FUNCTIONAL OVERVIEW
47
IN-HV
50N/51N 50N/51N
IN-LV EF-1 EF-3 51V 51V
50N/51N 50N/51N DT IDMT
EF-2 EF-4
I-LV
DIFF
Thru CTS
IN-TV
I-TV
virtual
I-TV
Always Available Transformer Differential
BINARY MEASO
CLIO I/O
RTDs MEASI
Protection P64x
Optional or Specific
E00073
12 P64x-TM-EN-4.1
CHAPTER 2
SAFETY INFORMATION
Chapter 2 - Safety Information P64x
14 P64x-TM-EN-4.1
P64x Chapter 2 - Safety Information
1 CHAPTER OVERVIEW
This chapter provides information about the safe handling of the equipment. The equipment must be properly
installed and handled in order to maintain it in a safe condition and to keep personnel safe at all times. You must
be familiar with information contained in this chapter before unpacking, installing, commissioning, or servicing the
equipment.
This chapter contains the following sections:
Chapter Overview 15
Health and Safety 16
Symbols 17
Installation, Commissioning and Servicing 18
Decommissioning and Disposal 24
Regulatory Compliance 25
P64x-TM-EN-4.1 15
Chapter 2 - Safety Information P64x
The documentation provides instructions for installing, commissioning and operating the equipment. It cannot,
however cover all conceivable circumstances. In the event of questions or problems, do not take any action
without proper authorisation. Please contact your local sales office and request the necessary information.
16 P64x-TM-EN-4.1
P64x Chapter 2 - Safety Information
3 SYMBOLS
Throughout this manual you will come across the following symbols. You will also see these symbols on parts of
the equipment.
Caution:
Refer to equipment documentation. Failure to do so could result in damage to the
equipment
Warning:
Risk of electric shock
Warning:
Risk of damage to eyesight
Earth terminal. Note: This symbol may also be used for a protective conductor (earth) terminal if that terminal
is part of a terminal block or sub-assembly.
Note:
The term 'Earth' used in this manual is the direct equivalent of the North American term 'Ground'.
P64x-TM-EN-4.1 17
Chapter 2 - Safety Information P64x
Plan carefully, identify any possible hazards and determine how best to move the product. Look at other ways of
moving the load to avoid manual handling. Use the correct lifting techniques and Personal Protective Equipment
(PPE) to reduce the risk of injury.
Caution:
All personnel involved in installing, commissioning, or servicing this equipment must be
familiar with the correct working procedures.
Caution:
Consult the equipment documentation before installing, commissioning, or servicing
the equipment.
Caution:
Always use the equipment as specified. Failure to do so will jeopardise the protection
provided by the equipment.
Warning:
Removal of equipment panels or covers may expose hazardous live parts. Do not touch
until the electrical power is removed. Take care when there is unlocked access to the
rear of the equipment.
Warning:
Isolate the equipment before working on the terminal strips.
Warning:
Use a suitable protective barrier for areas with restricted space, where there is a risk of
electric shock due to exposed terminals.
Caution:
Disconnect power before disassembling. Disassembly of the equipment may expose
sensitive electronic circuitry. Take suitable precautions against electrostatic voltage
discharge (ESD) to avoid damage to the equipment.
18 P64x-TM-EN-4.1
P64x Chapter 2 - Safety Information
Warning:
NEVER look into optical fibres or optical output connections. Always use optical power
meters to determine operation or signal level.
Warning:
Testing may leave capacitors charged to dangerous voltage levels. Discharge
capacitors by reducing test voltages to zero before disconnecting test leads.
Caution:
Operate the equipment within the specified electrical and environmental limits.
Caution:
Before cleaning the equipment, ensure that no connections are energised. Use a lint
free cloth dampened with clean water.
Note:
Contact fingers of test plugs are normally protected by petroleum jelly, which should not be removed.
Caution:
Equipment intended for rack or panel mounting is for use on a flat surface of a Type 1
enclosure, as defined by Underwriters Laboratories (UL).
Caution:
To maintain compliance with UL and CSA/CUL, install the equipment using UL/CSA-
recognised parts for: cables, protective fuses, fuse holders and circuit breakers,
insulation crimp terminals, and replacement internal batteries.
Caution:
Where UL/CSA listing of the equipment is required for external fuse protection, a UL or
CSA Listed fuse must be used for the auxiliary supply. The listed protective fuse type is:
Class J time delay fuse, with a maximum current rating of 15 A and a minimum DC
rating of 250 V dc (for example type AJT15).
Caution:
Where UL/CSA listing of the equipment is not required, a high rupture capacity (HRC)
fuse type with a maximum current rating of 16 Amps and a minimum dc rating of 250 V
dc may be used for the auxiliary supply (for example Red Spot type NIT or TIA).
For P50 models, use a 1A maximum T-type fuse.
For P60 models, use a 4A maximum T-type fuse.
P64x-TM-EN-4.1 19
Chapter 2 - Safety Information P64x
Caution:
Digital input circuits should be protected by a high rupture capacity NIT or TIA fuse with
maximum rating of 16 A. for safety reasons, current transformer circuits must never be
fused. Other circuits should be appropriately fused to protect the wire used.
Caution:
CTs must NOT be fused since open circuiting them may produce lethal hazardous
voltages
Warning:
Terminals exposed during installation, commissioning and maintenance may present a
hazardous voltage unless the equipment is electrically isolated.
Caution:
Tighten M4 clamping screws of heavy duty terminal block connectors to a nominal
torque of 1.3 Nm.
Tighten captive screws of terminal blocks to 0.5 Nm minimum and 0.6 Nm maximum.
Caution:
Always use insulated crimp terminations for voltage and current connections.
Caution:
Always use the correct crimp terminal and tool according to the wire size.
Caution:
Watchdog (self-monitoring) contacts are provided to indicate the health of the device
on some products. We strongly recommend that you hard wire these contacts into the
substation's automation system, for alarm purposes.
Caution:
Earth the equipment with the supplied PCT (Protective Conductor Terminal).
Caution:
Do not remove the PCT.
Caution:
The PCT is sometimes used to terminate cable screens. Always check the PCT’s integrity
after adding or removing such earth connections.
20 P64x-TM-EN-4.1
P64x Chapter 2 - Safety Information
Caution:
Use a locknut or similar mechanism to ensure the integrity of stud-connected PCTs.
Caution:
The recommended minimum PCT wire size is 2.5 mm² for countries whose mains supply
is 230 V (e.g. Europe) and 3.3 mm² for countries whose mains supply is 110 V (e.g. North
America). This may be superseded by local or country wiring regulations.
For P60 products, the recommended minimum PCT wire size is 6 mm². See product
documentation for details.
Caution:
The PCT connection must have low-inductance and be as short as possible.
Caution:
All connections to the equipment must have a defined potential. Connections that are
pre-wired, but not used, should be earthed, or connected to a common grouped
potential.
Caution:
Check voltage rating/polarity (rating label/equipment documentation).
Caution:
Check CT circuit rating (rating label) and integrity of connections.
Caution:
Check protective fuse or miniature circuit breaker (MCB) rating.
Caution:
Check integrity of the PCT connection.
Caution:
Check voltage and current rating of external wiring, ensuring it is appropriate for the
application.
Warning:
Do not open the secondary circuit of a live CT since the high voltage produced may be
lethal to personnel and could damage insulation. Short the secondary of the line CT
before opening any connections to it.
P64x-TM-EN-4.1 21
Chapter 2 - Safety Information P64x
Note:
For most General Electric equipment with ring-terminal connections, the threaded terminal block for current transformer
termination is automatically shorted if the module is removed. Therefore external shorting of the CTs may not be required.
Check the equipment documentation and wiring diagrams first to see if this applies.
Caution:
Where external components such as resistors or voltage dependent resistors (VDRs) are
used, these may present a risk of electric shock or burns if touched.
Warning:
Take extreme care when using external test blocks and test plugs such as the MMLG,
MMLB and P990, as hazardous voltages may be exposed. Ensure that CT shorting links
are in place before removing test plugs, to avoid potentially lethal voltages.
Warning:
Data communication cables with accessible screens and/or screen conductors,
(including optical fibre cables with metallic elements), may create an electric shock
hazard in a sub-station environment if both ends of the cable screen are not connected
to the same equipotential bonded earthing system.
i. The installation shall include all necessary protection measures to ensure that no
fault currents can flow in the connected cable screen conductor.
ii. The connected cable shall have its screen conductor connected to the protective
conductor terminal (PCT) of the connected equipment at both ends. This connection
may be inherent in the connectors provided on the equipment but, if there is any doubt,
this must be confirmed by a continuity test.
iii. The protective conductor terminal (PCT) of each piece of connected equipment shall
be connected directly to the same equipotential bonded earthing system.
iv. If, for any reason, both ends of the cable screen are not connected to the same
equipotential bonded earth system, precautions must be taken to ensure that such
screen connections are made safe before work is done to, or in proximity to, any such
cables.
vi. Equipment temporarily connected to this product for maintenance purposes shall be
protectively earthed (if the temporary equipment is required to be protectively
earthed), directly to the same equipotential bonded earthing system as the product.
Warning:
Small Form-factor Pluggable (SFP) modules which provide copper Ethernet connections
typically do not provide any additional safety isolation. Copper Ethernet SFP modules
must only be used in connector positions intended for this type of connection.
22 P64x-TM-EN-4.1
P64x Chapter 2 - Safety Information
4.9 UPGRADING/SERVICING
Warning:
Do not insert or withdraw modules, PCBs or expansion boards from the equipment
while energised, as this may result in damage to the equipment. Hazardous live
voltages would also be exposed, endangering personnel.
Caution:
Internal modules and assemblies can be heavy and may have sharp edges. Take care
when inserting or removing modules into or out of the IED.
P64x-TM-EN-4.1 23
Chapter 2 - Safety Information P64x
Caution:
Before decommissioning, completely isolate the equipment power supplies (both poles
of any dc supply). The auxiliary supply input may have capacitors in parallel, which may
still be charged. To avoid electric shock, discharge the capacitors using the external
terminals before decommissioning.
Caution:
Avoid incineration or disposal to water courses. Dispose of the equipment in a safe,
responsible and environmentally friendly manner, and if applicable, in accordance with
country-specific regulations.
24 P64x-TM-EN-4.1
P64x Chapter 2 - Safety Information
6 REGULATORY COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated using a technical file.
P64x-TM-EN-4.1 25
Chapter 2 - Safety Information P64x
26 P64x-TM-EN-4.1
CHAPTER 3
HARDWARE DESIGN
Chapter 3 - Hardware Design P64x
28 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
1 CHAPTER OVERVIEW
This chapter provides information about the product's hardware design.
This chapter contains the following sections:
Chapter Overview 29
Hardware Architecture 30
Mechanical Implementation 31
Front Panel 33
Rear Panel 37
Boards and Modules 39
P64x-TM-EN-4.1 29
Chapter 3 - Hardware Design P64x
2 HARDWARE ARCHITECTURE
The main components comprising devices based on the Px4x platform are as follows:
● The housing, consisting of a front panel and connections at the rear
● The Main processor module consisting of the main CPU (Central Processing Unit), memory and an interface
to the front panel HMI (Human Machine Interface)
● A selection of plug-in boards and modules with presentation at the rear for the power supply,
communication functions, digital I/O, analogue inputs, and time synchronisation connectivity
All boards and modules are connected by a parallel data and address bus, which allows the processor module to
send and receive information to and from the other modules as required. There is also a separate serial data bus
for conveying sampled data from the input module to the CPU. These parallel and serial databuses are shown as a
single interconnection module in the following figure, which shows typical modules and the flow of data between
them.
Keypad
Output relay boards Output relay contacts
Processor module
Front panel HMI
LCD
Opto-input boards Digital inputs
LEDs
I/O
Front port
CTs Power system currents
Memory
Interconnection
V00233
30 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
3 MECHANICAL IMPLEMENTATION
All products based on the Px4x platform have common hardware architecture. The hardware is modular and
consists of the following main parts:
● Case and terminal blocks
● Boards and modules
● Front panel
The case comprises the housing metalwork and terminal blocks at the rear. The boards fasten into the terminal
blocks and are connected together by a ribbon cable. This ribbon cable connects to the processor in the front
panel.
The following diagram shows an exploded view of a typical product. The diagram shown does not necessarily
represent exactly the product model described in this manual.
The products are available in panel-mount or standalone versions. All products are nominally 4U high. This equates
to 177.8 mm or 7 inches.
The cases are pre-finished steel with a conductive covering of aluminium and zinc. This provides good grounding
at all joints, providing a low resistance path to earth that is essential for performance in the presence of external
noise.
The case width depends on the product type and its hardware options. There are three different case widths for
the described range of products: 40TE, 60TE and 80TE. The case dimensions and compatibility criteria are as
follows:
Case width (TE) Case width (mm) Case width (inches)
40TE 203.2 8
P64x-TM-EN-4.1 31
Chapter 3 - Hardware Design P64x
Note:
Not all case sizes are available for all models.
32 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
4 FRONT PANEL
P64x-TM-EN-4.1 33
Chapter 3 - Hardware Design P64x
Note:
As the LCD display has a resolution of 16 characters by 3 lines, some of the information is in a condensed mnemonic form.
4.1.3 KEYPAD
The keypad consists of the following keys:
4 arrow keys to navigate the menus (organised around the Enter key)
34 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
A read key for viewing larger blocks of text (arrow keys now used for
scrolling)
2 hot keys for scrolling through the default display and for control of
setting groups. These are situated directly below the LCD display.
The port is intended for temporary connection during testing, installation and commissioning. It is not intended to
be used for permanent SCADA communications. This port supports the Courier communication protocol only.
Courier is a proprietary communication protocol to allow communication with a range of protection equipment,
and between the device and the Windows-based support software package.
You can connect the unit to a PC with a USB cable up to 5 m in length.
The inactivity timer for the front port is set to 15 minutes. This controls how long the unit maintains its level of
password access on the front port. If no messages are received on the front port for 15 minutes, any password
access level that has been enabled is cancelled.
Note:
The front USB port does not support automatic extraction of event and disturbance records, although this data can be
accessed manually.
Caution:
When not in use, always close the cover of the USB port to prevent contamination.
P64x-TM-EN-4.1 35
Chapter 3 - Hardware Design P64x
36 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
5 REAR PANEL
The MiCOM Px40 series uses a modular construction. Most of the internal workings are on boards and modules
which fit into slots. Some of the boards plug into terminal blocks, which are bolted onto the rear of the unit.
However, some boards such as the communications boards have their own connectors. The rear panel consists of
these terminal blocks plus the rears of the communications boards.
The back panel cut-outs and slot allocations vary. This depends on the product, the type of boards and the
terminal blocks needed to populate the case. The following diagram shows a typical rear view of a case populated
with various boards.
Note:
This diagram is just an example and may not show the exact product described in this manual. It also does not show the full
range of available boards, just a typical arrangement.
Not all slots are the same size. The slot width depends on the type of board or terminal block. For example, HD
(heavy duty) terminal blocks, as required for the analogue inputs, require a wider slot size than MD (medium duty)
terminal blocks. The board positions are not generally interchangeable. Each slot is designed to house a particular
type of board. Again this is model-dependent.
The device may use one or more of the terminal block types shown in the following diagram. The terminal blocks
are fastened to the rear panel with screws.
● Heavy duty (HD) terminal blocks for CT and VT circuits
● Medium duty (MD) terminal blocks for the power supply, opto-inputs, relay outputs and rear
communications port
● MiDOS terminal blocks for CT and VT circuits
● RTD/CLIO terminal block for connection to analogue transducers
P64x-TM-EN-4.1 37
Chapter 3 - Hardware Design P64x
,
Figure 8: Terminal block types
Note:
Not all products use all types of terminal blocks. The product described in this manual may use one or more of the above
types.
38 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
6.1 PCBS
A PCB typically consists of the components, a front connector for connecting into the main system parallel bus via
a ribbon cable, and an interface to the rear. This rear interface may be:
● Directly presented to the outside world (as is the case for communication boards such as Ethernet Boards)
● Presented to a connector, which in turn connects into a terminal block bolted onto the rear of the case (as is
the case for most of the other board types)
6.2 SUBASSEMBLIES
A sub-assembly consists of two or more boards bolted together with spacers and connected with electrical
connectors. It may also have other special requirements such as being encased in a metal housing for shielding
against electromagnetic radiation.
Boards are designated by a part number beginning with ZN, whereas pre-assembled sub-assemblies are
designated with a part number beginning with GN. Sub-assemblies, which are put together at the production
stage, do not have a separate part number.
P64x-TM-EN-4.1 39
Chapter 3 - Hardware Design P64x
The main processor board performs all calculations and controls the operation of all other modules in the IED,
including the data communication and user interfaces. This is the only board that does not fit into one of the slots.
It resides in the front panel and connects to the rest of the system using an internal ribbon cable.
The LCD and LEDs are mounted on the processor board along with the front panel communication ports.
The memory on the main processor board is split into two categories: volatile and non-volatile. The volatile
memory is fast access SRAM, used by the processor to run the software and store data during calculations. The
non-volatile memory is sub-divided into two groups:
● Flash memory to store software code, text and configuration data including the present setting values.
● Supercapacitor-backed SRAM to store disturbance, event, fault and maintenance record data.
There are two board types available depending on the size of the case:
● For models in 40TE cases
● For models in 60TE cases and larger
40 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
The power supply board provides power to the unit. One of three different configurations of the power supply
board can be fitted to the unit. This is specified at the time of order and depends on the magnitude of the supply
voltage that will be connected to it.
There are three board types, which support the following voltage ranges:
● 24/54 V DC
● 48/125 V DC or 40-100V AC
● 110/250 V DC or 100-240V AC
The power supply board connector plugs into a medium duty terminal block. This terminal block is always
positioned on the right hand side of the unit looking from the rear.
The power supply board is usually assembled together with a relay output board to form a complete subassembly,
as shown in the following diagram.
P64x-TM-EN-4.1 41
Chapter 3 - Hardware Design P64x
The power supply outputs are used to provide isolated power supply rails to the various modules within the unit.
Three voltage levels are used by the unit’s modules:
● 5.1 V for all of the digital circuits
● +/- 16 V for the analogue electronics such as on the input board
● 22 V for driving the output relay coils.
All power supply voltages, including the 0 V earth line, are distributed around the unit by the 64-way ribbon cable.
The power supply board incorporates inrush current limiting. This limits the peak inrush current to approximately
10 A.
Power is applied to pins 1 and 2 of the terminal block, where pin 1 is negative and pin 2 is positive. The pin
numbers are clearly marked on the terminal block as shown in the following diagram.
42 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
6.4.1 WATCHDOG
The Watchdog contacts are also hosted on the power supply board. The Watchdog facility provides two output
relay contacts, one normally open and one normally closed. These are used to indicate the health of the device
and are driven by the main processor board, which continually monitors the hardware and software when the
device is in service.
P64x-TM-EN-4.1 43
Chapter 3 - Hardware Design P64x
44 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
An additional serial port with D-type presentation is available as an optional board, if required.
The input module consists of the main input board coupled together with an instrument transformer board. The
instrument transformer board contains the voltage and current transformers, which isolate and scale the
analogue input signals delivered by the system transformers. The input board contains the A/D conversion and
digital processing circuitry, as well as eight digital isolated inputs (opto-inputs).
The boards are connected together physically and electrically. The module is encased in a metal housing for
shielding against electromagnetic interference.
P64x-TM-EN-4.1 45
Chapter 3 - Hardware Design P64x
Noise Noise
filter filter
Parallel Bus
Buffer
Transformer
board
VT
or
CT
VT
or
CT
V00239
A/D Conversion
The differential analogue inputs from the CT and VT transformers are presented to the main input board as shown.
Each differential input is first converted to a single input quantity referenced to the input board’s earth potential.
The analogue inputs are sampled and converted to digital, then filtered to remove unwanted properties. The
samples are then passed through a serial interface module which outputs data on the serial sample data bus.
The calibration coefficients are stored in non-volatile memory. These are used by the processor board to correct
for any amplitude or phase errors introduced by the transformers and analogue circuitry.
Opto-isolated inputs
The other function of the input board is to read in the state of the digital inputs. As with the analogue inputs, the
digital inputs must be electrically isolated from the power system. This is achieved by means of the 8 on-board
optical isolators for connection of up to 8 digital signals. The digital signals are passed through an optional noise
filter before being buffered and presented to the unit’s processing boards in the form of a parallel data bus.
This selectable filtering allows the use of a pre-set filter of ½ cycle which renders the input immune to induced
power-system noise on the wiring. Although this method is secure it can be slow, particularly for inter-tripping. This
can be improved by switching off the ½ cycle filter, in which case one of the following methods to reduce ac noise
should be considered.
● Use double pole switching on the input
● Use screened twisted cable on the input circuit
46 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
The opto-isolated logic inputs can be configured for the nominal battery voltage of the circuit for which they are a
part, allowing different voltages for different circuits such as signalling and tripping.
Note:
The opto-input circuitry can be provided without the A/D circuitry as a separate board, which can provide supplementary
opto-inputs.
1
Ideal anti-alias filter response
0.8
0.4
Fourier response with
anti-alias filter
0.2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Alias frequency
50 Hz 600 Hz 1200 Hz
V00301
For power frequencies that are not equal to the selected rated frequency, the harmonics are attenuated to zero
amplitude. For small deviations of +/-1 Hz, this is not a problem but to allow for larger deviations, frequency
tracking is used.
Frequency tracking automatically adjusts the sampling rate of the analog to digital conversion to match the
applied signal. In the absence of a suitable signal to amplitude track, the sample rate defaults to the selected rated
frequency (Fn). If the a signal is in the tracking range of 45 to 66 Hz, the relay locks onto the signal and the
measured frequency coincides with the power frequency. The outputs for harmonics up to the 23rd are zero. The
device frequency tracks off any voltage or current in the order VA/VB/VC/IA/IB/IC down to 10% Vn for voltage and
5%In for current.
P64x-TM-EN-4.1 47
Chapter 3 - Hardware Design P64x
The transformer board hosts the current and voltage transformers. These are used to step down the currents and
voltages originating from the power systems' current and voltage transformers to levels that can be used by the
devices' electronic circuitry. In addition to this, the on-board CT and VT transformers provide electrical isolation
between the unit and the power system.
The transformer board is connected physically and electrically to the input board to form a complete input module.
For terminal connections, please refer to the wiring diagrams.
48 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
The input board is used to convert the analogue signals delivered by the current and voltage transformers into
digital quantities used by the IED. This input board also has on-board opto-input circuitry, providing eight optically-
isolated digital inputs and associated noise filtering and buffering. These opto-inputs are presented to the user by
means of a MD terminal block, which sits adjacent to the analogue inputs HD terminal block.
The input board is connected physically and electrically to the transformer board to form a complete input module.
The terminal numbers of the opto-inputs are as follows:
Terminal Number Opto-input
Terminal 1 Opto 1 -ve
Terminal 2 Opto 1 +ve
Terminal 3 Opto 2 -ve
Terminal 4 Opto 2 +ve
Terminal 5 Opto 3 -ve
Terminal 6 Opto 3 +ve
Terminal 7 Opto 4 -ve
Terminal 8 Opto 4 +ve
Terminal 9 Opto 5 -ve
Terminal 10 Opto 5 +ve
Terminal 11 Opto 6 -ve
Terminal 12 Opto 6 +ve
Terminal 13 Opto 7 –ve
Terminal 14 Opto 7 +ve
Terminal 15 Opto 8 –ve
Terminal 16 Opto 8 +ve
P64x-TM-EN-4.1 49
Chapter 3 - Hardware Design P64x
This output relay board has 8 relays with 6 Normally Open contacts and 2 Changeover contacts.
The output relay board is provided together with the power supply board as a complete assembly, or
independently for the purposes of relay output expansion.
There are two cut-out locations in the board. These can be removed to allow power supply components to
protrude when coupling the output relay board to the power supply board. If the output relay board is to be used
independently, these cut-out locations remain intact.
The terminal numbers are as follows:
Terminal Number Output Relay
Terminal 1 Relay 1 NO
Terminal 2 Relay 1 NO
Terminal 3 Relay 2 NO
Terminal 4 Relay 2 NO
Terminal 5 Relay 3 NO
Terminal 6 Relay 3 NO
Terminal 7 Relay 4 NO
Terminal 8 Relay 4 NO
Terminal 9 Relay 5 NO
Terminal 10 Relay 5 NO
50 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
The IRIG-B board can be fitted to provide an accurate timing reference for the device. The IRIG-B signal is
connected to the board via a BNC connector. The timing information is used to synchronise the IED's internal real-
time clock to an accuracy of 1 ms. The internal clock is then used for time tagging events, fault, maintenance and
disturbance records.
IRIG-B interface is available in modulated or demodulated formats.
The IRIG-B facility is provided in combination with other functionality on a number of additional boards, such as:
● Fibre board with IRIG-B
● Second rear communications board with IRIG-B
● Ethernet board with IRIG-B
● Redundant Ethernet board with IRIG-B
There are three types of each of these boards; one type which accepts a modulated IRIG-B input, one type which
accepts a demodulated IRIG-B input and one type which accepts a universal IRIG-B input.
P64x-TM-EN-4.1 51
Chapter 3 - Hardware Design P64x
This board provides an interface for communicating with a master station. This communication link can use all
compatible protocols (Courier, IEC 60870-5-103, MODBUS and DNP 3.0). It is a fibre-optic alternative to the metallic
RS485 port presented on the power supply terminal block. The metallic and fibre optic ports are mutually exclusive.
The fibre optic port uses BFOC 2.5 ST connectors.
The board comes in two varieties; one with an IRIG-B input and one without:
52 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
The optional communications board containing the secondary communication ports provide two serial interfaces
presented on 9 pin D-type connectors. These interfaces are known as SK4 and SK5. Both connectors are female
connectors, but are configured as DTE ports. This means pin 2 is used to transmit information and pin 3 to receive.
SK4 can be used with RS232, RS485 and K-bus. SK5 can only be used with RS232 and is used for electrical
teleprotection. The optional rear communications board and IRIG-B board are mutually exclusive since they use
the same hardware slot. However, the board comes in two varieties; one with an IRIG-B input and one without.
P64x-TM-EN-4.1 53
Chapter 3 - Hardware Design P64x
This board provides dual redundant Ethernet together with an IRIG-B interface for timing.
Different board variants are available, depending on the redundancy protocol and the type of IRIG-B signal
(unmodulated and modulated). The available redundancy protocols are:
● RSTP (Rapid Spanning Tree Protocol)
● PRP (Parallel Redundancy Protocol)
● Failover
IRIG-B Connector
● Centre connection: Signal
● Outer connection: Earth
54 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
LEDs
LED Function On Off Flashing
Green Link Link ok Link broken
Yellow Activity Running PRP, RSTP traffic
RJ45 connector
Pin Signal name Signal definition
1 TXP Transmit (positive)
2 TXN Transmit (negative)
3 RXP Receive (positive)
4 - Not used
5 - Not used
6 RXN Receive (negative)
7 - Not used
8 - Not used
P64x-TM-EN-4.1 55
Chapter 3 - Hardware Design P64x
The RTD board provides two banks of 15 terminals to support ten RTD inputs, of the type PT100, Ni100, or Ni120,
depending on the product. There are three terminals for each RTD, therefore 30 terminals altogether. The RTD
board fits into slot B or slot C, depending on the model variant.
The terminal numbers of the RTDs are as follows:
Terminal Number RTD connection
Terminal 1 RTD1 wire 1
Terminal 2 RTD1 wire 2
Terminal 3 RTD1 wire 3
Terminal 4 RTD2 wire 1
Terminal 5 RTD2 wire 2
Terminal 6 RTD2 wire 3
Terminal 7 RTD3 wire 1
Terminal 8 RTD3 wire 2
Terminal 9 RTD3 wire 3
Terminal 10 RTD4 wire 1
Terminal 11 RTD4 wire 2
Terminal 12 RTD4 wire 3
Terminal 13 RTD5 wire 1
Terminal 14 RTD5 wire 2
Terminal 15 RTD5 wire 3
Terminal 16 RTD6 wire 1
56 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
The CLIO board provides two banks of 15 terminals to support four current loop inputs and four current loop
outputs. There are three terminals for each input and three for each output, therefore 24 of the terminals are used
altogether. The CLIO board fits into slot B or slot C, depending on the model variant.
The terminal numbers of the current loop inputs and outputs are as follows:
P64x-TM-EN-4.1 57
Chapter 3 - Hardware Design P64x
58 P64x-TM-EN-4.1
P64x Chapter 3 - Hardware Design
A High Break output relay board is available as an option. It comprises four normally open output contacts, which
are suitable for high breaking loads.
A High Break contact consists of a high capacity relay with a MOSFET in parallel with it. The MOSFET has a varistor
placed across it to provide protection, which is required when switching off inductive loads. This is because the
stored energy in the inductor causes a high reverse voltage that could damage the MOSFET, if not protected.
When there is a control input command to operate an output contact the miniature relay is operated at the same
time as the MOSFET. The miniature relay contact closes in nominally 3.5 ms and is used to carry the continuous
load current. The MOSFET operates in less than 0.2 ms, but is switched off after 7.5 ms.
When the control input is reset, the MOSFET is again turned on for 7.5 mS. The miniature relay resets in nominally
3.5 ms before the MOSFET. This means the MOSFET is used to break the load. The MOSFET absorbs the energy
when breaking inductive loads and so limits the resulting voltage surge. This contact arrangement is for switching
DC circuits only.
The board number is:
● ZN0042 001
P64x-TM-EN-4.1 59
Chapter 3 - Hardware Design P64x
Databus on off
control input
MOSFET reset
Relay contact
Closed
Load current
V00246
Warning:
These relay contacts are POLARITY SENSITIVE. External wiring must comply with the polarity
requirements described in the external connection diagram to ensure correct operation.
60 P64x-TM-EN-4.1
CHAPTER 4
SOFTWARE DESIGN
Chapter 4 - Software Design P64x
62 P64x-TM-EN-4.1
P64x Chapter 4 - Software Design
1 CHAPTER OVERVIEW
This chapter describes the software design of the IED.
This chapter contains the following sections:
Chapter Overview 63
Sofware Design Overview 64
System Level Software 65
Platform Software 68
Protection and Control Functions 69
P64x-TM-EN-4.1 63
Chapter 4 - Software Design P64x
These elements are not distinguishable to the user, and the distinction is made purely for the purposes of
explanation. The following figure shows the software architecture.
Supervisor task
Records
and control
Protection
settings
Platform Software Layer
Event, fault,
Remote
disturbance,
Settings database communications
maintenance record
Sampling function interfaces
logging
V00300
The software, which executes on the main processor, can be divided into a number of functions as illustrated
above. Each function is further broken down into a number of separate tasks. These tasks are then run according
to a scheduler. They are run at either a fixed rate or they are event driven. The tasks communicate with each other
as and when required.
64 P64x-TM-EN-4.1
P64x Chapter 4 - Software Design
P64x-TM-EN-4.1 65
Chapter 4 - Software Design P64x
At the conclusion of the initialization software the supervisor task begins the process of starting the platform
software.
At the successful conclusion of all of these tests the unit is entered into service and the application software is
started up.
66 P64x-TM-EN-4.1
P64x Chapter 4 - Software Design
A restart should clear most problems that may occur. If, however, the diagnostic self-check detects the same
problem that caused the IED to restart, it is clear that the restart has not cleared the problem, and the device takes
itself permanently out of service. This is indicated by the ‘’health-state’ LED on the front of the device, which
switches OFF, and the watchdog contact which switches ON.
P64x-TM-EN-4.1 67
Chapter 4 - Software Design P64x
4 PLATFORM SOFTWARE
The platform software has three main functions:
● To control the logging of records generated by the protection software, including alarms, events, faults, and
maintenance records
● To store and maintain a database of all of the settings in non-volatile memory
● To provide the internal interface between the settings database and the user interfaces, using the front
panel interface and the front and rear communication ports
The logs are maintained such that the oldest record is overwritten with the newest record. The logging function
can be initiated from the protection software. The platform software is responsible for logging a maintenance
record in the event of an IED failure. This includes errors that have been detected by the platform software itself or
errors that are detected by either the system services or the protection software function. See the Monitoring and
Control chapter for further details on record logging.
4.3 INTERFACES
The settings and measurements database must be accessible from all of the interfaces to allow read and modify
operations. The platform software presents the data in the appropriate format for each of the interfaces (LCD
display, keypad and all the communications interfaces).
68 P64x-TM-EN-4.1
P64x Chapter 4 - Software Design
P64x-TM-EN-4.1 69
Chapter 4 - Software Design P64x
The Fourier components are calculated using single-cycle Fourier algorithm. This Fourier algorithm always uses
the most recent 24 samples from the 2-cycle buffer.
Most protection algorithms use the fundamental component. In this case, the Fourier algorithm extracts the power
frequency fundamental component from the signal to produce its magnitude and phase angle. This can be
represented in either polar format or rectangular format, depending on the functions and algorithms using it.
The Fourier function acts as a filter, with zero gain at DC and unity gain at the fundamental, but with good
harmonic rejection for all harmonic frequencies up to the nyquist frequency. Frequencies beyond this nyquist
frequency are known as alias frequencies, which are introduced when the sampling frequency becomes less than
twice the frequency component being sampled. However, the Alias frequencies are significantly attenuated by an
anti-aliasing filter (low pass filter), which acts on the analog signals before they are sampled. The ideal cut-off point
of an anti-aliasing low pass filter would be set at:
(samples per cycle) ´ (fundamental frequency)/2
At 24 samples per cycle, this would be nominally 600 Hz for a 50 Hz system, or 720 Hz for a 60 Hz system.
The following figure shows the nominal frequency response of the anti-alias filter and the Fourier filter for a 24-
sample single cycle fourier algorithm acting on the fundamental component:
1
Ideal anti-alias filter response
0.8
0.4
Fourier response with
anti-alias filter
0.2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Alias frequency
50 Hz 600 Hz 1200 Hz
V00301
70 P64x-TM-EN-4.1
P64x Chapter 4 - Software Design
P64x-TM-EN-4.1 71
Chapter 4 - Software Design P64x
72 P64x-TM-EN-4.1
CHAPTER 5
CONFIGURATION
Chapter 5 - Configuration P64x
74 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
1 CHAPTER OVERVIEW
Each product has different configuration parameters according to the functions it has been designed to perform.
There is, however, a common methodology used across the entire product series to set these parameters.
Some of the communications setup can only be carried out using the HMI, and cannot be carried out using
settings applications software. This chapter includes concise instructions of how to configure the device,
particularly with respect to the communications setup, as well as a description of the common methodology used
to configure the device in general.
This chapter contains the following sections:
Chapter Overview 75
Settings Application Software 76
Using the HMI Panel 77
Configuring the Data Protocols 87
Date and Time Configuration 93
Phase Rotation 96
P64x-TM-EN-4.1 75
Chapter 5 - Configuration P64x
76 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
The keypad provides full access to the device functionality using a range of menu options. The information is
displayed on the LCD.
Keys Description Function
Function keys (not all models) For executing user programmable functions
P64x-TM-EN-4.1 77
Chapter 5 - Configuration P64x
Note:
As the LCD display has a resolution of 16 characters by 3 lines, some of the information is in a condensed mnemonic form.
Alarm message
V00437
Figure 33: Navigating the HMI
If there are alarms present, the yellow Alarms LED will be flashing and the menu display will read as follows:
78 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
Alarms / Faults
Present
HOTKEY
Even though the device itself should be in full working order when you first start it, an alarm could still be present,
for example, if there is no network connection for a device fitted with a network card. If this is the case, you can
read the alarm by pressing the 'Read' key.
ALARMS
NIC Link Fail
If the device is fitted with an Ethernet card, you will first need to connect the device to an active Ethernet network
to clear the alarm and get the default display.
If there are other alarms present, these must also be cleared before you can get into the default display menu
options.
11:09:15
23 Nov 2011
HOTKEY
Description (user-defined)
For example:
Description
MiCOM P14NB
HOTKEY
P64x-TM-EN-4.1 79
Chapter 5 - Configuration P64x
Plant Reference
MiCOM
HOTKEY
Access Level
For example:
Access Level
3
HOTKEY
In addition to the above, there are also displays for the system voltages, currents, power and frequency etc.,
depending on the device model.
NERC compliant
banner
System Current
Access Level
Measurements
System Voltage
System Frequency
Measurements
System Power
Plant Reference
Measurements
V00403
If the device is cyber-secure but is not yet configured for NERC compliance (see Cyber-security chapter), a warning
will appear when moving from the "NERC compliant" banner. The warning message is as follows:
80 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
You will have to confirm with the Enter button before you can go any further.
Note:
Whenever the IED has an uncleared alarm the default display is replaced by the text Alarms/ Faults present. You cannot
override this default display. However, you can enter the menu structure from the default display, even if the display shows
the Alarms/Faults present message.
Enter Password
1. A flashing cursor shows which character field of the password can be changed. Press the up or down cursor
keys to change each character (tip: pressing the up arrow once will return an upper case "A" as required by
the default level 3 password).
2. Use the left and right cursor keys to move between the character fields of the password.
3. Press the Enter key to confirm the password. If you enter an incorrect password, an invalid password
message is displayed then the display reverts to Enter password. On entering a valid password a message
appears indicating that the password is correct and which level of access has been unlocked. If this level is
sufficient to edit the selected setting, the display returns to the setting page to allow the edit to continue. If
the correct level of password has not been entered, the password prompt page appears again.
4. To escape from this prompt press the Clear key. Alternatively, enter the password using the Password
setting in the SYSTEM DATA column. If the keypad is inactive for 15 minutes, the password protection of the
front panel user interface reverts to the default access level.
To manually reset the password protection to the default level, select Password, then press the CLEAR key instead
of entering a password.
Note:
In the SECURITY CONFIG column, you can set the maximum number of attemps, the time window in which the failed attempts
are counted and the time duration for which the user is blocked.
P64x-TM-EN-4.1 81
Chapter 5 - Configuration P64x
Press Clear To
Reset Alarms
3. To clear all alarm messages, press the Clear key. To return to the display showing alarms or faults present,
and leave the alarms uncleared, press the Read key.
4. Depending on the password configuration settings, you may need to enter a password before the alarm
messages can be cleared.
5. When all alarms are cleared, the yellow alarm LED switches off. If the red LED was on, this will also be
switched off.
Note:
To speed up the procedure, you can enter the alarm viewer using the Read key and subsequently pressing the Clear key. This
goes straight to the fault record display. Press the Clear key again to move straight to the alarm reset prompt, then press the
Clear key again to clear all alarms.
Note:
Sometimes the term "Setting" is used generically to describe all of the three types.
82 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
It is convenient to specify all the settings in a single column, detailing the complete Courier address for each
setting. The above table may therefore be represented as follows:
Setting Column Row Description
SYSTEM DATA 00 00 First Column definition
Language (Row 01) 00 01 First setting within first column
Password (Row 02) 00 02 Second setting within first column
Sys Fn Links (Row 03) 00 03 Third setting within first column
… … …
VIEW RECORDS 01 00 Second Column definition
Select Event [0...n] 01 01 First setting within second column
Menu Cell Ref 01 02 Second setting within second column
Time & Date 01 03 Third setting within second column
… … …
MEASUREMENTS 1 02 00 Third Column definition
IA Magnitude 02 01 First setting within third column
IA Phase Angle 02 02 Second setting within third column
IB Magnitude 02 03 Third setting within third column
… … …
The first three column headers are common throughout much of the product ranges. However the rows within
each of these column headers may differ according to the product type. Many of the column headers are the
same for all products within the series. However, there is no guarantee that the addresses will be the same for a
particular column header. Therefore you should always refer to the product settings documentation and not make
any assumptions.
P64x-TM-EN-4.1 83
Chapter 5 - Configuration P64x
8. Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is
automatically discarded if it is not confirmed within 15 seconds.
9. For protection group settings and disturbance recorder settings, the changes must be confirmed before
they are used. When all required changes have been entered, return to the column heading level and press
the Down cursor key. Before returning to the default display, the following prompt appears.
Update settings?
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
Note:
For the protection group and disturbance recorder settings, if the menu time-out occurs before the changes have been
confirmed, the setting values are discarded. Control and support settings, howeverr, are updated immediately after they are
entered, without the Update settings? prompt.
These functions are enabled or disabled in the Direct Access cell in the CONFIGURATION column.
Use the right cursor keys to enter the SETTING GROUP menu.
¬Menu User01®
SETTING GROUP 1
Nxt Grp Select
Select the setting group with Nxt Grp and confirm by pressing Select. If neither of the cursor keys is pressed within
20 seconds of entering a hotkey sub menu, the device reverts to the default display.
84 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
Press the right cursor key twice to get to the first control input, or the left cursor key to get to the last control input.
¬STP GP User02®
Control Input 1
EXIT SET
Now you can execute the chosen function (Set/Reset in this case).
If neither of the cursor keys is pressed within 20 seconds of entering a hotkey sub menu, the device reverts to the
default display.
FUNCTION KEYS
Fn Key Status
0000000000
The next cell down (Fn Key 1) allows you to activate or disable the first function key (1). The Lock setting allows a
function key to be locked. This allows function keys that are set to Toggled mode and their DDB signal active
‘high’, to be locked in their active state, preventing any further key presses from deactivating the associated
function. Locking a function key that is set to the Normal mode causes the associated DDB signals to be
permanently off. This safety feature prevents any inadvertent function key presses from activating or deactivating
critical functions.
P64x-TM-EN-4.1 85
Chapter 5 - Configuration P64x
FUNCTION KEYS
Fn Key 1
Unlocked
The next cell down (Fn Key 1 Mode) allows you to set the function key to Normal or Toggled. In the Toggle mode
the function key DDB signal output stays in the set state until a reset command is given, by activating the function
key on the next key press. In the Normal mode, the function key DDB signal stays energised for as long as the
function key is pressed then resets automatically. If required, a minimum pulse width can be programmed by
adding a minimum pulse timer to the function key DDB output signal.
FUNCTION KEYS
Fn Key 1 Mode
Toggled
The next cell down (Fn Key 1 Label) allows you to change the label assigned to the function. The default label is
Function key 1 in this case. To change the label you need to press the enter key and then change the text on
the bottom line, character by character. This text is displayed when a function key is accessed in the function key
menu, or it can be displayed in the PSL.
FUNCTION KEYS
Fn Key 1 Label
Function Key 1
Subsequent cells allow you to carry out the same procedure as above for the other function keys.
The status of the function keys is stored in non-volatile memory. If the auxiliary supply is interrupted, the status of
all the function keys is restored. The IED only recognises a single function key press at a time and a minimum key
press duration of approximately 200 ms is required before the key press is recognised. This feature avoids
accidental double presses.
86 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
Note:
Not all protocols are available on all products
You configure most of the communication settings using the HMI. Depending on the model, you will also need to
use the settings applications software to carry out some of the configuration, such as the IEC61850 configurator.
Detailed information on configuring the data protocols can be found in the communications chapter.
COMMUNICATIONS
RP1 Protocol
Courier
4. Move down to the next cell (RP1 Address). This cell controls the address of the RP1 port on thje device. Up to
32 IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so
that messages from the master control station are accepted by one IED only. Courier uses an integer
number between 1 and 254 for the Relay Address. It is set to 255 by default, which has to be changed. It is
important that no two IEDs share the same address.
COMMUNICATIONS
RP1 Address
100
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity timer
controls how long the IED waits without receiving any messages on the rear port before revoking any
password access that was enabled and discarding any changes. For the rear port this can be set between 1
and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins.
P64x-TM-EN-4.1 87
Chapter 5 - Configuration P64x
6. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
7. Move down to the next cell (RP1 Card Status). This cell is not settable. It displays the status of the chosen
physical layer protocol for RP1.
COMMUNICATIONS
RP1 Card Status
K-Bus OK
8. Move down to the next cell (RP1 Port Config). This cell controls the type of serial connection. Select between
K-Bus or RS485.
COMMUNICATIONS
RP1 Port Config
K-Bus
9. If using EIA(RS)485, the next cell (RP1 Comms Mode) selects the communication mode. The choice is either
IEC 60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no parity. If using K-Bus this cell will not
appear.
COMMUNICATIONS
RP1 Comms Mode
IEC 60870 FT1.2
10. If using EIA(RS)485, the next cell down controls the baud rate. Three baud rates are supported; 9600, 19200
and 38400. If using K-Bus this cell will not appear as the baud rate is fixed at 64 kbps.
COMMUNICATIONS
RP1 Baud rate
19200
COMMUNICATIONS
RP1 Protocol
DNP3.0
4. Move down to the next cell (RP1 Address). This cell controls the DNP3.0 address of the IED. Up to 32 IEDs can
be connected to one spur, therefore it is necessary for each IED to have a unique address so that messages
from the master control station are accepted by only one IED. DNP3.0 uses a decimal number between 1
and 65519 for the Relay Address. It is important that no two IEDs have the same address.
COMMUNICATIONS
RP1 Address
1
88 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud rates are
supported by the IED 1200 bps, 2400 bps, 4800 bps, 9600 bps, 19200 bps and 38400 bps. Make sure that
the baud rate selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames. The
parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on the IED is
the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. Move down to the next cell (RP1 Time Sync). This cell affects the time synchronisation request from the
master by the IED. It can be set to enabled or disabled. If enabled it allows the DNP3.0 master to
synchronise the time on the IED.
COMMUNICATIONS
RP1 Time Sync
Enabled
COMMUNICATIONS
RP1 Protocol
IEC 60870-5-103
P64x-TM-EN-4.1 89
Chapter 5 - Configuration P64x
4. Move down to the next cell (RP1 Address). This cell controls the IEC 60870-5-103 address of the IED. Up to 32
IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so that
messages from the master control station are accepted by one IED only. IEC 60870-5-103 uses an integer
number between 0 and 254 for the address. It is important that no two IEDs have the same IEC 60870 5 103
address. The IEC 60870-5-103 address is then used by the master station to communicate with the IED.
COMMUNICATIONS
RP1 address
162
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Two baud rates are
supported by the IED, 9600 bits/s and 19200 bits/s. Make sure that the baud rate selected on the
IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Meas Period). The next cell down controls the period between
IEC 60870-5-103 measurements. The IEC 60870-5-103 protocol allows the IED to supply measurements at
regular intervals. The interval between measurements is controlled by this cell, and can be set between 1
and 60 seconds.
COMMUNICATIONS
RP1 Meas Period
30.00 s
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. The next cell down (RP1 CS103Blcking) can be used for monitor or command blocking.
COMMUNICATIONS
RP1 CS103Blcking
Disabled
9. There are three settings associated with this cell; these are:
Setting: Description:
Disabled No blocking selected.
When the monitor blocking DDB Signal is active high, either by energising an opto input or control input,
Monitor Blocking reading of the status information and disturbance records is not permitted. When in this mode the device
returns a "Termination of general interrogation" message to the master station.
When the command blocking DDB signal is active high, either by energising an opto input or control input,
Command Blocking all remote commands will be ignored (i.e. CB Trip/Close, change setting group etc.). When in this mode the
device returns a "negative acknowledgement of command" message to the master station.
90 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
3. Move to the first cell down (RP1 protocol). This is a non settable cell, which shows the chosen
communication protocol – in this case Modbus.
COMMUNICATIONS
RP1 Protocol
Modbus
4. Move down to the next cell (RP1 Address). This cell controls the Modbus address of the IED. Up to 32 IEDs
can be connected to one spur, therefore it is necessary for each IED to have a unique address so that
messages from the master control station are accepted by only one IED. Modbus uses a decimal number
between 1 and 247 for the Relay Address. It is important that no two IEDs have the same address.
COMMUNICATIONS
RP1 Address
1
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity timer
controls how long the IED waits without receiving any messages on the rear port before it reverts to its
default state, including revoking any password access that was enabled. For the rear port this can be set
between 1 and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins
6. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud rates are
supported by the IED 1200 bits/s, 2400 bits/s, 4800 bits/s, 9600 bits/s, 19200 bits/s and 38400 bits/s. Make
sure that the baud rate selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
7. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames. The
parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on the IED is
the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
8. Move down to the next cell (Modbus IEC Time). This cell controls the order in which the bytes of information
are transmitted. There is a choice of Standard or Reverse. When Standard is selected the time format
complies with IEC 60870-5-4 requirements such that byte 1 of the information is transmitted first, followed
by bytes 2 through to 7. If Reverse is selected the transmission of information is reversed.
COMMUNICATIONS
Modbus IEC Time
Standard
P64x-TM-EN-4.1 91
Chapter 5 - Configuration P64x
IEC 61850 allows IEDs to be directly configured from a configuration file. The IED’s system configuration
capabilities are determined from an IED Capability Description file (ICD), supplied with the product. By using ICD
files from the products to be installed, you can design, configure and test (using simulation tools), a substation’s
entire protection scheme before the products are installed into the substation.
To help with this process, the settings application software provides an IEC 61850 Configurator tool, which allows
the pre-configured IEC 61850 configuration file to be imported and transferred to the IED. As well as this, you can
manually create configuration files for all products, based on their original IED capability description (ICD file).
Other features include:
● The extraction of configuration data for viewing and editing.
● A sophisticated error checking sequence to validate the configuration data before sending to the IED.
Note:
Some configuration data is available in the IEC61850 CONFIG. column, allowing read-only access to basic configuration data.
Any new configuration sent to the IED is automatically stored in the inactive configuration bank, therefore not
immediately affecting the current configuration.
Following an upgrade, the IEC 61850 Configurator tool can be used to transmit a command, which authorises
activation of the new configuration contained in the inactive configuration bank. This is done by switching the
active and inactive configuration banks. The capability of switching the configuration banks is also available using
the IEC61850 CONFIG. column of the HMI.
The SCL Name and Revision attributes of both configuration banks are available in the IEC61850 CONFIG. column
of the HMI.
92 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
P64x-TM-EN-4.1 93
Chapter 5 - Configuration P64x
3. Ensure that the IED is receiving valid time synchronisation messages by checking that the PTP Status cell
reads Valid Master.
4. Check that Act. Time Source cell reads PTP. This indicates that the IED is using PTP as the source for its
time. Note that If IRIG-B or SNTP have been selected as the Primary Source, these must first be
disconnected before the device can switch to PTP as the active source.
5. Once the IED is using PTP as the active time source, adjust the time offset of the universal coordinated time
on the Master Clock equipment, so that local time is displayed.
6. Check that the time, date and month are correct in the Date/Time cell.
The LocalTime Offset setting allows you to enter the local time zone compensation from -12 to + 12 hours at 15
minute intervals.
94 P64x-TM-EN-4.1
P64x Chapter 5 - Configuration
These settings are described in the DATE AND TIME settings table in the configuration chapter.
P64x-TM-EN-4.1 95
Chapter 5 - Configuration P64x
6 PHASE ROTATION
The product provides a facility to maintain correct operation of all the protection functions even when the system
is running in a reverse phase sequence. This is achieved by the Phase Sequence setting in the SYSTEM CONFIG
column, and is available for all four setting groups.
You can configure the Phase Sequence setting to Standard ABC or Reverse ABC. This setting does not
perform any internal phase swapping of the analog channels.
The Phase Sequence setting affecs the sequence component calculation as follows (In this example, the positive
and negative sequence currents are shown. The same principle applies to voltages):
Standard ABC
Reverse ABC
Standard ABC
● Phase A: Use IA and VBC
● Phase B: Use IB and VCA
● Phase C: Use IC and VAB
Reverse ABC
● Phase A: Use IA and -VBC
● Phase B: Use IB and -VCA
● Phase C: Use IC and -VAB
96 P64x-TM-EN-4.1
CHAPTER 6
98 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
1 CHAPTER OVERVIEW
P64x-TM-EN-4.1 99
Chapter 6 - Transformer Differential Protection P64x
100 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
CTs may be close to saturation so a high bias current is needed. More differential current is then needed to trip the
circuit breakers, allowing greater security from external faults and less risk of maloperation.
This is achieved by defining an operating current characteristic. Often a triple slope characteristic is used as shown
below.
Operate region
Idiff
K2
Restraint region
K1
Is1
Is2 Ibias
V00664
Idiff is the differential current, which is the vector sum of all the current inputs. Ibias is a current which is
proportional to the scalar sum of all currents entering and leaving the zone. The bias current is used to calculate
an operating current. If the differential current calculated by the IED is above the operation current, then the
device will trip (providing no blocking signals are asserted).
The characteristic can be defined by setting certain parameters such as the minimum operating current Is1 (Iset
1), Is2 (Iset 2), K1 and K2. Is1 sets the minimum operating current. Is2 sets the level of bias current at which the
steeper slope sets in. Constants K1 and K2 define the slopes. A High Set Threshold is usually defined, which ensures
the device will operate for very high currents, even if blocking signals are present.
The slope parts of the characteristic curve provide stability for external faults that cause CT saturation. The high
bias current region of the characteristic curve has a steeper slope than the low bias current region in order to
improve the stability even further for high-current external faults. The first slope, K1, compensates for CT errors
and tap changer errors. The second slope, K2, compensates for CT saturation. Is1 should be set above transient
overfluxing and Is2 should be considered as the transformer full load current. The CTs are sized according to the
transformer full load current.
In some transformers, the windings are split at the centre point and terminals are brought out so that they can
also be interconnected. These windings can be zig-zag connected (Z-connected).
The more common connection types are:
● Y-y
● Y-d
● Y-z
● D-d
● D-y
● D-z
To differentiate between the low and high voltage sides of the transformer, a standard convention has been
adopted whereby lower case is used for the low voltage side and upper case is used for the high voltage side.
P64x-TM-EN-4.1 101
Chapter 6 - Transformer Differential Protection P64x
Not only can the primary and secondary be connected as a star or a delta, each phase can also be reversed
resulting in a large choice of possible connections. In reality, however, only a few of these are used, because we
generally require that the phase shifts between the primary windings and their secondary counterparts be
consistent. This reduces the common connection types to those shown in the table below.
You will notice that the naming convention specifying the connection type in the first column also has a number
appended to it. This number, called the clock face vector, or vector group number represents the phase shift
between the current in a low voltage winding with respect to its counterpart on the high voltage winding. This
corresponds to the position of the number of a standard clock face. The table and diagram below shows examples
of connections with the clock vectors Midnight, 1 o’ clock, 6 o’ clock and 11 o’clock, which is equivalent to a phase
shift of 0°, -30°, -180° and +30° respectively.
Vector Group Phase shift
Yy0 0°
Dd0 0°
Dz0 0°
Yd1 -30°
Dy1 -30°
Dz1 -30°
Yd5 -150°
Dy5 -150°
Dz5 -150°
Yy6 180°
Dd6 180°
Dz6 180°
Yd11 +30°
Dy11 +30°
Dz11 +30°
102 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
A2 a2 A1 A2 a2 a1
Dd0 C A c a B1 B2 b2 b1 0°
C2 B2 C1 C2 c2 c1
c2 b2
B b
n
A2 a4
A1 A2 a4
a3 a2 a1
Dz0 C A B1 B2 b4 0°
b3 b2 b1
C2 B2 b4 C1 C2 c4
B c4
c3 c2 c1
a2 YN
A2 c A1 A2 a2 a1
a
Yd1 c2 -30°
B1 B2 b2 b1
b
C1 C2 c2 c1
C2 B2 b2
yn
a2
A2
A1 A2 a2 a1
Dy1 A B c2 B2 b2 b1 -30°
B1
C2 B2 C1 C2 c2 c1
C b2
YN n
A2
a4 A1 A2 a4
a3 a2 a1
Yz1 B1 B2 b4 -30°
c4 b3 b2 b1
C2 B2
C1 C2 c4
b4
c3 c2 c1
YN
A2 c2
A1 A2 a1
b a2
Yd5 b2
c -150°
B1 B2 b1
b2
C2 B2 a C1 C2 c1
a2 c2
yn
A2 c2
A1 A2 a2 a1
Dy5 A B
B1 B2 b2 b1 -150°
b2
C2 B2 C1 C2 c2 c1
C
a2
YN n
A2 c4 a3 a2
A1 A2 a4 a1
b4
Yz5 B1 B2 b3 b2
b1 -150°
b4
C2 B2 C1 C2 c4 c3 c2 c1
a4
V03125
P64x-TM-EN-4.1 103
Chapter 6 - Transformer Differential Protection P64x
C2 B2
a1 C1 C2 c2 c1
A2 b1 b c1
A1 A2 a2 a1
Dd6 C A B1 B2 b2 b1 180°
a c
C2 B2 C1 C2 c2 c1
B a1
n
A2
c3 A2 a3 a4 a2 a1
b3
Dz6 C A B2 b3 b4 b2 b1 180°
C2 B2 c C2 c3 c4 c2 c1
B
a3
YN
a2 A1 A2 a2
A2 b a1
Yd11 a b2 B1 B2 b2 30°
b1
c C1 C2 c2
C2 B2 c2 c1
a2 yn
A2
A1 A2 a2 a1
Dy11 A B b2 30°
B1 B2 b2 b1
C2 B2
C C1 C2 c2 c1
c2
YN n
A2 a4
A1 A2 a4 a3 a2
a1
Yz11 B1 B2 b4
b3 b2 30°
b4
b1
C2 B2 c3 c2
C1 C2 c4
c4 c1
V03126
104 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
+Fm
Steady state
-Fm
2Fm
Switch on at voltage
zero – No residual flux
V03123
P64x-TM-EN-4.1 105
Chapter 6 - Transformer Differential Protection P64x
We can see that inrush current is a regularly occurring phenomenon and should not be considered a fault, as we
do not wish the protection device to issue a trip command whenever a transformer is switched on at an
inconvenient point during the input voltage cycle. This presents a problem to the protection device, because it
should always trip on an internal fault. The problem is that typical internal transformer faults may produce
overcurrents which are not necessarily greater than the inrush current. Furthermore, faults tend to manifest
themselves on switch on, due to the high inrush currents. For this reason, we need to find a mechanism that can
distinguish between fault current and inrush current. Fortunately, this is possible due to the different natures of the
respective currents. An inrush current waveform is rich in harmonics, especially 2nd harmonics, whereas an
internal fault current consists only of the fundamental. We can therefore develop a restraining method based on
the 2nd harmonic content of the inrush current. The mechanism by which this is achieved, is called second
harmonic blocking.
E03107
Such waveforms have a significant 5th harmonic content. We can therefore develop a restraining method based
on the 5th harmonic content of the inrush current. The mechanism by which this is achieved, is called fifth
harmonic blocking.
106 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
3 IMPLEMENTATION
To enable or disable Differential Protection, set Diff Protection in the CONFIGURATION column and Trans Diff in the
DIFF PROTECTION column of the of the relevant settings group.
Note:
To minimise imbalances due to tap changer operation, current inputs to the differential element should be set according to
the mid-tap position and not the nominal voltage. The Ref Vector Group setting provides a reference vector group to which
all other vector groups are referenced. Typically, this is set to 0°.
P64x-TM-EN-4.1 107
Chapter 6 - Transformer Differential Protection P64x
function uses the vector sum of the current terminal inputs (on a phase by phase basis) as the input to the
calculation for that winding.
You associate these current inputs with the system transformer windings with the settings HV CT Terminals, LV CT
Terminals and TV CT Terminals in the SYSTEM CONFIG column as follows:
Setting P642 P643 P645
00001
00011
001
HV CT Terminals 01 00111
011
01011
01111
10000
11000
100
LV CT Terminals 10 11100
110
11010
11110
00100
01100
TV CT Terminals 010
00110
01110
Where the terminals T1 to T5 correspond to the bits in the binary string as follows (1 = in use, 0 = not in use). The bit
order starts with T1 on the right-hand side. For example:
If a CT is assigned to more than one winding, then an alarm is issued (CT Selection Alm). When this DDB signal is
asserted, the protection is also blocked.
108 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
S ref I nom ,n
I ref ,n = K amp ,n =
3Vnom , n S ref
3Vnom, n
where:
● Sref = common reference power for all ends
● Iref,n = reference current for the respective CT input
● Kamp,n = amplitude-matching factor for the respective CT input
● Inom,n = primary nominal currents for the respective CT input
● Vnom,n = primary nominal voltage for the respective CT input
The device also checks that the matching factors are within their permissible ranges. The matching factors must
satisfy the condition:
0.05 <= Kamp <= 15 for standard CTs
0.05 <= Kamp <= 20 for sensitive CTs
P64x-TM-EN-4.1 109
Chapter 6 - Transformer Differential Protection P64x
If any of the ratio correction factors in two-winding applications are out of range, the CT para mismatch alarm is
asserted. In multi-winding applications, the alarm is asserted if the ratio correction factor of the CTs associated
with HV or LV windings are out of range or the ratio correction factor of the CTs associated to TV winding is greater
than 15 for standard CTs and 20 for sensitive CTs.
If the ratio correction factor of the CT associated to TV winding is lower than 0.05, this current is removed from the
differential calculation, as shown in the logic diagram.
If the CT para mismatch alarm is asserted the protection is also blocked.
The phase current measured values of the windings of the protected object are always scaled by the relevant
matching factors. These are then available for further processing. Consequently, all threshold values and
measured values refer back to the relevant reference currents rather than to the transformer nominal currents or
the nominal currents of the device.
The bias current is defined as half of the scalar sum of the CT current inputs:
110 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
The tripping characteristic has two knees. The first knee is dependent on the settings of Is1 and K1. The second
knee is defined by the setting Is2. The lower slope provides stability for low external faults. The higher slope
provides stability for high through fault conditions, since transient differential currents may be present due to
current transformer saturation.
Idiff/Inom
Is-HS2
K2
Operate region
K1
Is1
TC and CT errors
Once the differential and bias currents are calculated, the following comparisons are made and an operate/
restrain signal is obtained:
For the flat slope range: 0 ≤ Ibias max ≤ Is1/K1
If the differential current is above the adjustable Is-HS1 threshold, the device will trip if in the Operate region, but
not in the restrain region. However, second harmonic blocking and overfluxing blocking are NOT taken into
account. The High Set 1 resets when the differential and bias currents are in the restraint area.
If the differential current is above the adjustable Is-HS2 threshold, bias current is not taken into account and the
device will trip regardless. As with High Set 1, second harmonic blocking and overfluxing blocking are NOT taken
into account. The High Set 2 element resets when the differential current drops below 0.95*Is-HS2.
P64x-TM-EN-4.1 111
Chapter 6 - Transformer Differential Protection P64x
112 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
The transient bias technique uses a time decay constant, stability coefficients, and some differential function
settings to provide a dynamic bias characteristic. The following diagram shows the behaviour during an external
fault. For the device to trip, the fundamental of the differential current should be above the operating current at
max bias + transient bias.
1.6
1
I (pu)
0.8
0.6
0.4
0.2
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
t(s)
V03109
The transient bias function enhances the stability of the differential element during external faults and allows for
the time delay in CT saturation caused by small external fault currents and high X/R ratios.
No transient bias is produced under load switching conditions, or when the CT comes out of saturation.
P64x-TM-EN-4.1 113
Chapter 6 - Transformer Differential Protection P64x
changes, but the differential current only increases after the time to saturation. The external fault detection DDBs
are asserted if the following conditions are fulfilled:
The delta bias start signal is asserted first. The delta bias start signal and the delta differential start signal are
asserted if the delta bias and delta differential currents are greater than 0.65 Is1 respectively.
The time difference between the assertion of the delta bias start signal and the assertion of the delta differential
signal is greater than the time to saturation. The minimum time to saturation is 2.5 ms for a 50 Hz system and 2.08
ms for a 60 Hz system.
The ratio of delta differential to delta bias is smaller than a fixed threshold when the delta bias start signal is
asserted.
The External Fault Detection algorithm is on a per phase basis. If an external fault is detected on phase A, B or C,
signals External fault A, External fault B or External fault C are asserted. The external fault detector resets after 6
seconds from the start or after 25 cycles from the start if the current is less than 0.9Is1.
The following figure shows the time to saturation for an external fault.
114 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
I/KA
-1
I/KA
2.5
0.0
-2.5
-5.0
1.0
0.5
0.0
PU
1.5
1.0
0.5
V03124
P64x-TM-EN-4.1 115
Chapter 6 - Transformer Differential Protection P64x
Idiff/Inom
Is-HS2
K2
Operate region
Is-CTS
K1
Is1
TC and CT errors
Idiff/Inom
Is-HS2
K2
Operate region
K-cctfail
Is-CTS
K1
Is1
TC and CT errors
Is-cctfail
116 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
1
IA2H Diff Start &
&
CT Saturation A IB5H Diff Start
1
No Gap A & Id Bias Start B & Id Bias Trip B
1
External Fault A
1
IB2H Diff Start &
&
CT Saturation B IC5H Diff Sta rt
1
No Gap B & Id Bias Start C & Id Bias Trip C
External Fault B
1
IC2H Diff Start &
&
CT Saturation C
1
No Gap C &
External Fault C
V03113
P64x-TM-EN-4.1 117
Chapter 6 - Transformer Differential Protection P64x
4 HARMONIC BLOCKING
Any phase N
Idiff(2 fn)/Idiff(fn) > Setting Counter = 0
Counter + = 1
N
Counter >= 2
Block 1-phase
Drop-off
Low-set diff
Y Block 3-phase
Cross Block enabled
Low-set diff
Return
V03111
118 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
Idiffa
Idiffafundamental
fundamental
Idiffb
Idiffbfundamental
fundamental
Idiffc
Idiffcfundamental
fundamental
V00706
P64x-TM-EN-4.1 119
Chapter 6 - Transformer Differential Protection P64x
Any phase N
Idiff(5 fn)/Idiff(fn) > Setting Counter = 0
Counter + = 1
N
Counter >= 2
Block 1-phase
Drop-off
Low-set diff
Return
V03112
120 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
Id biased
delay
5th harmonic
Overfluxing detection
& Idiff Trip
Id biased
Trip
2nd harmonic
Inrush detection
& Idiff HS1 Trip
1 Idiff Trip
Idiff HS2 Trip
No Gap detection
1
&
CT Saturation
External Fault
Change Is1 to
Is-CTS in
restraint mode K2
CT Supervision K1
Is1 &
Is2
Idiff > Is-HS1
V03114
P64x-TM-EN-4.1 121
Chapter 6 - Transformer Differential Protection P64x
5 APPLICATION NOTES
Note:
Differential protection alone may not achieve the full sensitivity required, and other protection functions such as REF may
have to be incorporated in conjunction with the differential protection.
The number of biased differential inputs required for an application depends on the transformer and its primary
connections. We recommend, where possible, that a set of biased CT inputs is used for each set of current
transformers. According to IEEE C37.110-2007, separate current inputs should be used for each power source to
the transformer. If the secondary windings of the current transformers from two or more supply breakers are
connected in parallel, under heavy through fault conditions, differential current resulting from the different
magnetizing characteristics of the current transformers flows in the IED. This current only flows through one
current input in the device and can cause maloperation. If each CT is connected to a separate current input, the
total fault current in each breaker provides restraint. You should only connect CT secondary windings in parallel
when both circuits are outgoing loads. In this condition, the maximum through fault level is restricted solely by the
power transformer impedance.
The P64x IED achieves stability for through faults in two ways, both of which are essential for correct relay
operation. The first consideration is the correct sizing of the current transformers. The second is by providing a bias
characteristic as shown below:
122 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
Idiff/Inom
Is-HS2
K2
Operate region
K1
Is1
TC and CT errors
P64x-TM-EN-4.1 123
Chapter 6 - Transformer Differential Protection P64x
90 MVA
132 kV/33 kV
YNd9
400:1 2000:1
A a
B b
C c
Protected zone
Earthing
transformer
B B
D D D
P642
V03115
124 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
Vector correction and zero sequence filtering are automatically performed by virtue of the LV Vector Group setting
and the HV Grounding and LV Grounding settings.
The ratio correction factors are calculated as follows:
where:
● Sref = common reference power for all ends
● Kamp, T1CT, T2CT = ratio correction factor of T1 CT or T2 CT windings
● Inom, T1CT, T2CT = primary nominal currents of the main current transformers
● Vnom, HV,LV = primary nominal voltage of HV or LV windings
These matching factors are also displayed in the SYSTEM CONFIG column (Match Factor CT1 and Match Factor
CT2)
Now set the current differential parameters as follows:
Setting in GROUP 1 DIFF PROTECTION Value
Trans Diff Enabled
Set Mode Advance
Is1 200.0e-3 PU
K1 30.00%
Is2 1.000 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 10.00 PU
HS2 Status Disbled
Zero seq filt HV Enabled
Zero seq filt LV Enabled
IH2 Diff Block Enabled
IH2 Diff Set 20%
Cross Blocking Enabled
CT Saturation Enabled
No Gap Enabled
IH5 Diff Block Enabled
P64x-TM-EN-4.1 125
Chapter 6 - Transformer Differential Protection P64x
126 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
175/175/30 MVA
230/115/13.8 kV
YNynd1
+5% / -15% TV
800:5 19 taps 2000:5
HV
a
A
b
B
c
C
Earthing
Protected zone transformer
c
LV
1200:5
B B
D D D
P645
V03116
Figure 53: P645 used to protect an autotransformer with loaded delta winding
Since the transformer has an on load tap changer on the HV side, the nominal voltage of the HV winding must be
set to the mid tap voltage level. According to the nameplate data, the mid tap voltage is 218.5 kV. The mid tap
voltage can also be calculated as follows:
(5 − 15)
100 +
Mid tap voltage = 2 × 230 = 218.5kV
100
P64x-TM-EN-4.1 127
Chapter 6 - Transformer Differential Protection P64x
Vector correction and zero sequence filtering are automatically performed by virtue of the LV Vector Group setting
and the HV Grounding and LV Grounding settings.
The device calculates the ratio correction factors as follows:
128 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
where:
● Sref = common reference power for all ends
● Kamp, T1CT, T2CT, T3CT = ratio correction factor of T1 CT, T2 CT, or T3 windings
Inom, T1CT, T2CT, T3CT = primary nominal currents of the main current transformers
● Vnom, HV, LV, TV = primary nominal voltage of HV, LV, or TV windings
These matching factors are also displayed in the SYSTEM CONFIG column (Match Factor CT1 and Match Factor
CT2)
Now set the current differential parameters as follows:
Setting in GROUP 1 DIFF PROTECTION Value
Trans Diff Enabled
Set Mode Advance
Is1 200.0e-3 PU
K1 30.00%
Is2 1.000 PU
K2 80.00%
tdiff 0s
Is-CTS 1.500 PU
Is-HS1 10.00 PU
HS2 Status Disabled
Zero seq filt HV Enabled
Zero seq filt LV Enabled
Zero seq filt TV Enabled
IH2 Diff Block Enabled
IH2 Diff Set 20%
Cross Blocking Enabled
CT Saturation Enabled
No Gap Enabled
IH5 Diff Block Enabled
IH5 Diff Set 35%
Circuitry Fail Disabled
The winding configuration is set to HV + LV + TV. The CT on the HV line side is connected to T1 CT, the CT on the HV
neutral side is connected to T2 CT, and the CT on the LV side is connected to T3 CT.
P64x-TM-EN-4.1 129
Chapter 6 - Transformer Differential Protection P64x
B c
1200 :5
Protected
zone
B B
D D D
P643
V03117
Figure 54: P643 used to protect an autotransformer with unloaded delta winding
130 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
Vector correction and zero sequence filtering are automatically performed by virtue of the LV Vector Group setting
and the HV Grounding and LV Grounding settings.
It is preferable to have the ratio correction factors equal to or close to 1.
Applying Kirchoff's law, assume that the full load current is flowing, that an equivalent source is connected to the
HV winding and that an equivalent load is connected to the LV winding. The current distribution is as follows:
S 175 ×106
I FLC − HV = = = 439 A
3Vnom , HV 3 × 230 ×103
S 175 ×106
I FLC − LV = = = 878 A
3Vnom, LV 3 × 115 ×103
175/175/30 MVA
230 /115 /13.8 kV
YNynd1
230 kV - +5%/-15% - 19 taps
a 878 Ð0°
439 Ð0° 439 Ð0° A
Equivalent b 878 Ð-120°
load
439 Ð-120° 439 Ð-120° B
c 878 Ð-240°
439 Ð-120° 439 Ð120° C
1200:5
1200:5 1200:5
V03118
P64x-TM-EN-4.1 131
Chapter 6 - Transformer Differential Protection P64x
The reference power is set to 175 MVA and the nominal voltage in HV, LV and TV windings is set to 230 kV. In this
application, you do not need to consider the mid tap voltage, even though, there is an on load tap changer on the
HV side.
The device calculates the ratio correction factors as follows:
The differential element does not protect the tertiary winding. Unloaded delta-connected tertiary windings are
often not protected. If protection is required, the delta winding can be earthed at one point through a current
transformer used to provide instantaneous overcurrent protection for the tertiary winding.
132 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
B
Phase & amplitude Circuit Breaker 1
Correction
B
+
Zero sequence filtering
B
B
Phase & amplitude Circuit Breaker 2
B
Correction
+
Zero sequence filtering
B
B
Phase & amplitude Circuit Breaker 3
Correction
B
+
Zero sequence filtering
B
B
Phase & amplitude Circuit Breaker 4
Correction
B
+
Zero sequence filtering
B
B
Phase & amplitude Circuit Breaker 5
B
Correction
+
Zero sequence filtering
B
115kV
D D D
P645
V03119
P64x-TM-EN-4.1 133
Chapter 6 - Transformer Differential Protection P64x
Note:
* This is the maximum load (including overloads) that would be handled by the busbar.
Note:
** This disables the zero sequence filters.
Note:
*** This is the system voltage.
Note:
**** This setting has no impact on the differential protection. It is used by other functions such as the thermal and through-
fault monitoring elements which are not required for busbar protection.
134 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
Note:
Set the Circuitry Fail alarm to Enabled and set K-cctfail to 15% to allow the maximum composite error of 10% that may be
introduced by class 10P current transformers. Is-cctfail is typically set between 5 to 20% to prevent CT noise and differential
current caused by load imbalance. This element is typically delayed by 5 s.
Note:
CT supervision should be used to prevent maloperation if there is an open circuited CT secondary. The CTS feature can be
used to desensitize the biased differential protection. To do this, raise the differential current pickup setting Is1 to the value of
Is-CTS.
Idiff/Inom
4
3.8
3.6
3.4 K2 = 80%
3.2
3
2.8
2.6 Is-CTS
2.4
2.2
2
1.8
1.6
1.4 Is1
1.2
1
0.8
0.6
0.4
0.2 Is-cctfail > 10%
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Ibias/Inom
V03120
P64x-TM-EN-4.1 135
Chapter 6 - Transformer Differential Protection P64x
As per IEEE C37.109-2006 the properties of shunt reactors can be summarized as follows:
● Dry air-air core type reactors: no magnetizing inrush during energization as there is no iron core. The peak
current during energization might be as high as 2 Ö2Inominal due to transient offset. Air core type reactors
are normally used up to 34.5 kV and often installed on the transformer tertiary winding.
● Oil-immersed type reactors: the gapped iron-core type might experience severe energizing inrush. The
coreless type experiences less severe magnetizing inrush.
Consider the following shunt reactor:
Busbar A Busbar B
T1 CT T2 CT
400 :5 400:5
Bk 1 Bk 2 Bk 3
500 kV
163 .3 MVA
T3 CT
1000 :1
V03121
The bias differential element in the P643 would be used to protect the reactor. In a reactor application the low set
differential element Is1, should be set between 10%-15%. Inrush current in a shunt reactor does not appear as a
differential current like that which appears in a transformer, unless the CT saturates after some time due to long
DC time constant. Though the level of second harmonic in many cases can be relatively high, there are many
cases with no or very low content of harmonics in the differential current. Since the level of 2nd harmonic is small
in shunt reactors compared with transformers, the high set 1 differential element, Is-HS1, can be set to 250% of
the reactor current at rated voltage.
Set the following parameters in the SYSTEM CONFIG column:
Setting in GROUP 1 SYSTEM CONFIG Value
Winding Config HV+LV
Winding Type Conventional
HV CT Terminals 011
LV CT Terminals 100
Ref Power S 163.3 MVA
Ref Vector Group 0
HV Connection Y-Wye
HV Grounding Ungrounded
HV Nominal 500.0 kV
HV Rating 163.3 MVA
% Reactance 40.00%
136 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
P64x-TM-EN-4.1 137
Chapter 6 - Transformer Differential Protection P64x
V03122
In the majority of applications, the reference vector group setting Ref Vector Group is set to 0. However there are
occasional applications where it may be desirable to set it to a value other than 0.
One example is to increase the sensitivity for phase-to-phase faults where it is used to protect a YNyn0
transformer. In this scenario, the P64x would normally apply a -30° phase shift to both HV and LV windings due to
the way it works. However, by setting the reference vector group to 1, the device knows it does not have to apply a
-30° shift in its calculations, thus increasing its sensitivity to phase-to-phase faults.
138 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
HV TV
LV
Isolator
open signal
P645
V00696
We do not want the standard differential protection or low impedance REF protection to operate, as this may have
repercussions on the rest of the system. In this case, Stub Bus protection should be used, when available. Stub Bus
protection is achieved by using the isolator status , applying this to an opto-input and combining it with a phase
overcurrent element (linked to the relevant winding) to provide a trip signal for the relevant circuit breakers.
P64x-TM-EN-4.1 139
Chapter 6 - Transformer Differential Protection P64x
Idiff Trip
Blocking 100
Idiff Trip
& Dwell Output R4
0
HV UndCurrent Activation
& S
89 a Q HV StubBus Act
Input L1 R
89b
&
Input L2
HV StubBus Trip
100
Tripping Output R1
& Dwell
POC 1 I>3 Trip
0
This example applies to the HV element only . The LV and TV elements follow the same principles .
In this example , the following applies :
140 P64x-TM-EN-4.1
P64x Chapter 6 - Transformer Differential Protection
The following table provides the maximum sensitivity and its corresponding matching factor for different CT types:
Matching factor for typical setting
CT Type Max. sensitivity Permitted Matching Factor range
Is1 = 0.02 pu
Standard 43 mA 0.05 - 15 4.65
Sensitive 13 mA 0.05 - 20 15.38
A series of external faults were simulated to determine the CT requirements for the differential function, by using a
state of the art Real Time Digital Simulation system (RTDS). We performed these tests with different X/R ratios, CT
burdens, fault currents, fault types and points on the current waveform.
To achieve through-fault stability, the K dimensioning factor must comply with the following expressions:
P64x-TM-EN-4.1 141
Chapter 6 - Transformer Differential Protection P64x
A series of internal and external faults were simulated to determine the CT requirements for the differential
function. We performed these tests with different X/R ratios, CT burdens, fault currents, fault types and points on
the current waveform.
The system conditions, CT dimensioning factor and CT kneepoint voltage are as follows:
142 P64x-TM-EN-4.1
CHAPTER 7
144 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
1 CHAPTER OVERVIEW
P64x-TM-EN-4.1 145
Chapter 7 - Transformer Condition Monitoring P64x
Transformer Losses
The losses in a transformer are shown in the following diagram:
Transformer Losses
Core Losses
Copper Losses Stray Losses Apparent Losses
(Iron Losses)
The flow of the magnetising current through the resistance of the winding creates a real but generally relatively
small I2R loss and voltage drop. The loss that is due to this magnetizing current in the primary winding is called the
apparent loss.
Time-varying fluxes in iron-based materials, cause losses called core losses, or iron losses. These iron losses are
divided into two categories; hysteresis losses and eddy-current losses.
The sum of copper losses and the stray losses is called the load loss. Copper losses are due to the flow of load
currents through the primary and secondary windings. They are equal to I2R, and they heat up the wires and
cause voltage drops. Stray losses are due to the stray capacitance and leakage inductance. Stray capacitance
exists between turns, between one winding and another, and between windings and the core.
146 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
To calculate the Top Oil and hotspot winding temperature, the device takes into consideration the ratio of the
actual load to the rated load. If the monitored winding is set to HV, LV, or TV, the rated load is determined by the
HV rating, LV rating, or TV rating settings respectively and the Irated setting. If the monitored winding is set as
the the biased current, the rated load is calculated using the Sref power rating setting in the SYSTEM CONFIG
column and the Irated setting in the THERMAL PROTECTION column.
The thermal overload model is executed once every power cycle. The thermal overload trip can be based on either
hot spot temperature or top oil temperature, or both.
The device has up to three hot spot stages and up to three top oil stages. The tripping signal, Top Oil T>x Trip, is
asserted when the top oil (measured or calculated) temperature is above the setting, Top Oil>x Set, and the time
delay, tTop Oil>x Set has elapsed. Also, the tripping signal, Hotspot>x Trip, is asserted when the hottest-spot
(calculated only) temperature is above the setting, Hotspot>x Set, and the time delay, tHotspot>x Set has elapsed.
Max [ I HVArms , I HVBrms , I HVCrms ] Max [ I LVArms , I LVBrms , I LVCrms ] Max [ ITVArms , ITVBrms , ITVCrms ]
+ +
HV _ FLCSref LV _ FLCSref TV _ FLCSref
I bias =
2
P64x-TM-EN-4.1 147
Chapter 7 - Transformer Condition Monitoring P64x
where:
● HV_FLCSref = HV full load current at the reference power
● LV_FLCSref = LV full load current at the reference power
● TV_FLCSref = TV full load current at the reference power
Note:
"True RMS" refers to the RMS value of a non-sinusoidal waveform including the fundamental and all other components.
You can either measure the ambient temperature directly, or set it in the Ambient T setting. The ultimate top oil rise
is given by the following equation:
n
K u2 R + 1
∆ΘTO ,U = ∆ΘTO , R ⋅
R +1
where:
Ku = the ratio of actual load to rated load
R = the ratio of the load loss at rated load to no load loss (Rated NoLoadLoss setting)
n = Oil exponent (Oil exp n setting)
QTO,R = Top Oil rise over ambient temperature at rated load (Top Oil Overamb setting)
The load current used in the calculations is the RMS value.
148 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
where:
● QH = Hotspot (winding) temperature
● QTO = Top Oil temperature
● DQH = Hotspot rise above top oil temperature
The top oil temperature, hot spot temperature, ambient temperature and pre-trip time left are available as a
measured value in the MEASUREMENT 3 column.
If you need a more accurate representation of the transformer thermal state, you can use temperature monitoring
devices (RTDs or CLIO), which target specific areas. For short period overloads, RTD, CLIO and overcurrent
protection techniques provide better protection.
The PSL provides a signal indicating that the transformer is de-energised (TFR De-energised). This signal is
asserted when all the circuit breakers are open. In this case, the transformer no-load losses are not considered. As
a result, the top oil and hottest spot temperatures are equal to the ambient temperature when the monitored
current is zero. If this signal is removed, the top oil and hottest spot temperatures are not equal to the ambient
temperature even when the monitored current is zero. In this case the top oil and hottest spot temperatures will
increase according to the described equations.
2.3.1 RECOMMENDATIONS
Monitored Winding
You can set the monitored winding to HV, LV, TV or Biased Current. We recommend setting it to Biased
Current to provide an overall thermal condition for the transformer.
Ambient Temperature
Ambient temperature is an important factor when determining the load capability of a transformer, because you
add it to the temperature rise due to loading to determine the operating temperature. IEEE C57.91-1995 states
that transformer ratings are based on an average ambient temperature of 30°C.
The Ambient T Source setting defines whether the ambient temperature should be set to an average level or
measured directly using a CLI or RTD input. When measuring the ambient temperature, it should be averaged over
a 24-hour period.
P64x-TM-EN-4.1 149
Chapter 7 - Transformer Condition Monitoring P64x
Winding Exponent
IEEE C57.91-1995 suggests the following winding and oil exponents.
Type of cooling m (winding exponent) n ( oil exponent)
OA 0.8 0.8
FA 0.8 0.9
Non-directed FOA or FOW 0.8 0.9
Directed FOA or FOW 1.0 1.0
Suggested limits of temperature for loading above nameplate power transformers with 65° C rise
Top Oil temperature 110°C
Hotspot conductor temperature 180°C
150 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
Note:
OD (oil directed) indicates that oil from heat exchangers (radiators) is forced through the windings. WF (Water Forced) states
that the oil is externally cooled by pumped water.
Thermal characteristics for a 600 MVA 432/23.5 kV ODWF cooled generator transformer
Specification Value
No load losses (core losses) 237 kW
Load losses at nominal tap 1423 kW
Load losses at maximum current tap 1676 kW
Oil time constant 2.2 hr
Oil exponent 1.0
Top Oil rise over ambient temperature at rated load 46.6 K
Winding time constant at Hotspot location 9 mins
Winding hottest spot rise over Top Oil temperature at rated load 33.1K
Winding exponent 2.0
Thermal characteristics for a IEC 60354 figures based on medium-large power transformers OD cooled
Specification Value
Oil time constant 1.5 hr
Oil exponent 1.0
Top Oil rise over ambient temperature at rated load 49 K
Winding time constant at Hotspot location 5-10 mins
Winding hottest spot rise over Top Oil temperature at rated load 29 K
Winding exponent 2.0
P64x-TM-EN-4.1 151
Chapter 7 - Transformer Condition Monitoring P64x
B
A+ B B
L ( Θ H ,r ) Θ H ,r + 273 −
e
Θ H ,r + 273 Θ H + 273
FAA = = B
=e
L ( ΘH )
A+
Θ H + 273
e
152 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
If a 65°C average winding rise transformer is considered, the equation for FAA is as follows:
B B
−
383 Θ H + 273
FAA = e
If a 55°C average winding rise transformer is considered, the equation for FAA is as follows:
B B
−
368 Θ H + 273
FAA = e
where:
● L(QH) = life hours at winding hottest-spot temperature
● QH,r = hottest-spot temperature at rated load
● B = constant B from life expectancy curve. This parameter is set by the user. IEEE Std. C57.91-1995
recommends a B value of 15000.
The residual life hours at reference hottest-spot temperature is updated every hour as follows:
3600
∑F i =1
AA,i (Θ H )
Lres (Θ H , r ) = Lres , p (Θ H , r ) −
3600
where:
● Lres,p(QH,r) = residual life hours at reference temperature one hour ago
● FAA,i(QH) = mean aging acceleration factor, as calculated above (calculated every second)
The accumulated loss of life is updated in non-volatile memory once per hour. It is possible to reset this to a new
value if required; for example if the device is applied in a new location with a pre-aged resident transformer.
The rate of loss of life (ROLOL) in percentage per day is as follows. It is updated every day:
24
ROLOL = ⋅ FAA, m (Θ H ) ⋅100%
L (Θ H , r )
The mean aging acceleration factor, FAA,m, is as follows. It is updated every day:
N N
∑ FAAn ⋅ ∆tn ∑ FAAn
n =1 n =1
FAA, m = N
=
∑ ∆tn N
n =1
where:
● FAA,n is calculated every power cycle
● Dtn = 1 cycle
● FAA,m states the latest one-day statistics of FAA. When the device is energized for the first time, FAA,m default
value is 1.
Lres (Θ H , r )
Lres ( FAA,m ) =
FAA, m
P64x-TM-EN-4.1 153
Chapter 7 - Transformer Condition Monitoring P64x
Note:
Tensile strength or degree of polymerization (D.P.) retention values were determined by sealed tube aging on well-dried
insulation samples in oxygen-free oil.
Note:
Refer to I.2 in annex I of the IEEE Std. C57.91-1995 for discussion of the effect of higher values of water and oxygen and also
for the discussion on the basis given above.
You should set the designed Hotspot temperature setting (Designed HS temp) to 110°C if the transformer is rated
65°C average winding rise. If the transformer is rated 55°C average winding rise, set it to 95°C.
As recommended by IEEE C57.91-1995, set the Constant B Set setting to 5000.
If the calculated aging acceleration factor is greater than the setting FAA> Set and the time delay tFAA> Set has
elapsed, the FAA alarm DDB signal is activated.
If the calculated loss of life is greater than the setting LOL>1 Set and the time delay tLOL> Set has elapsed, the
LOL alarm DDB signal is activated.
3.2.2 EXAMPLE
Consider a new 65°C average winding rise rated transformer whose life hours figure at designed maximum
Hotspot temperature is 180,000 hrs. As a result, you set the Life Hours at HS setting to 180,000, and the
Designed HS temp setting to 110.0°C. Set Constant B Set to 15,000 as recommended by IEEE. The aging
acceleration factor takes into consideration the constant B and the hottest spot temperature calculated by the
thermal function. For a distribution transformer, IEEE suggests 200°C as the limit for the maximum hot spot
temperature. The aging acceleration factor alarm will be asserted when 70% of the 200°C has been reached. The
aging acceleration factor is calculated as follows:
B B B B
− 383 − 0.7×200 + 273
383 hottest − spot −tempt + 273
FAA = e =e
= 17.2
Therefore:
FAA>set should be set to 17.2. tFAA> Set may be set to 10.00 min. LOL>1 Set may be set to 115,000 hrs, if
it is considered that the transformer has 65,000 hrs left (Life Hours at HS – hours left = 180,000 – 65,000 = 115,000
hrs). tLOL> Set may be set to 10.00 min. Finally, the Reset Life Hours setting determines the value of the LOL
154 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
measurement once the Reset LOL command is executed. The default value is zero because considering a new
transformer, after testing the thermal function the LOL measurement should be reset to zero.
You should perform certain tests to determine the age of an old transformer. Please obtain advice from the
transformer manufacturer.
P64x-TM-EN-4.1 155
Chapter 7 - Transformer Condition Monitoring P64x
Categories I and II consider only the transformer short-circuit impedance, whereas categories III and IV consider
the system short-circuit impedance at the transformer location as well as transformer short-circuit impedance.
The short-circuit impedance is expressed as a percentage of the transformer rated voltage and the rated power of
the transformer.
A single-stage alarm is available for through-fault monitoring. The alarm is issued if the maximum cumulative I2t in
the three phases exceeds the TF I2t> Alarm setting. A through fault event is recorded if any of the phase currents
is larger than the TF I> Trigger setting. You should always set TF I> Trigger greater than the overload capability of
the transformer.
156 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
TF I > Trigger
&
IA2t 1
& Throu fa ult Alm
TF I 2t> Alarm
TF Recorder trig
IB magnitude
TF I > Trigger
&
IB2t
TF I 2t> Ala rm
IC magnitude
TF I > Trigger
&
IC2t
TF I 2t> Alarm
V03201
Example
The through fault monitoring element can monitor either the HV, the LV or the TV winding. In three winding
applications, you should monitor the winding through which the highest current would flow during an external
fault. Fault studies are required to determine the maximum through fault current and which winding carries the
most current. For example, consider the following autotransformer:
P64x-TM-EN-4.1 157
Chapter 7 - Transformer Condition Monitoring P64x
175/175/30 MVA
230/115/13.8 kV
YNynd1
+5% / -15% TV
800:5 19 taps 2000:5
HV
a
A
b
B
c
C
Earthing
Protected zone transformer
c
LV
1200:5
B B
D D D
P645
V03116
Figure 64: P645 used to protect an autotransformer with loaded delta winding
Consider the case where an equivalent source and load are connected to the 230 kV terminal and an equivalent
source and load are connected to the 115 kV terminal, but only the load is connected to the 13.8 kV terminal. An
external fault on the 230 kV side would be fed by the source on the 115 kV side. Therefore, the current would
mainly flow from the 115 kV side to the 230 kV side. If the external fault occurs on the 115 kV side, the through-
fault current would flow from the 230 kV side to the 115 kV side. If an external fault occurs on the 13.8 kV side, the
through fault current would flow from the 230 kV and 115 kV sides to the 13.8 kV side. The source and transformer
impedances determine the fault current level.
Set the TF I> Trigger setting above the maximum overload. According to IEEE Std. C57.109-1993, values of 3.5 or
less times normal base current may result from overloads instead of faults. TF I> Trigger may be set to 3.85 pu. If
the monitored current is above this level and no differential element has started, then the I2t is calculated.
To set the TF I2t> Alarm consider the maximum through fault current and the maximum time duration. The
maximum through-fault current may be determined as 1/X, where X is the transformer impedance. This
approximation is valid when the source is strong, so that its impedance is small compared with the transformer
impedance. If the transformer has an impedance of 10%, the maximum through fault current is calculated as:
158 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
1/X = 1/0.1 = 10 pu
P64x-TM-EN-4.1 159
Chapter 7 - Transformer Condition Monitoring P64x
5 RTD PROTECTION
Prolonged overloading of transformers may cause their windings to overheat, resulting in premature aging of the
insulation, or in extreme cases, insulation failure. To protect against this, resistive temperature sensing devices
(RTDs) can be used to measure temperatures at various locations within a transformer. RTDs work by using the
resistance versus temperature characteristic of metals. When metal heats up, its resistance changes. This can be
used to feed back temperature information, which can be used by protection devices for temperature monitoring,
alarming, or making protection decisions.
Probes are usually placed in areas of the equipment that are susceptible to overheating or heat damage. This
could protect against winding Hotspot overheating or overtemperature in the insulating oil.
Direct temperature measurement can provide more reliable thermal protection than thermal model calculations.
Note:
Do Not select RTD options if RTD board is not fitted.
RTD 1 RTD 1
RTD 10 RTD 10
IED IED
V03202
You can enable or disable each RTD using the Select RTD setting in the RTD PROTECTION column of the relevant
settings group. The setting contains a binary string of ten digits to represent the 10 RTDs in sequence from right to
left. For example if you set Select RTD to 0000000111, RTD1, RTD2 and RTD3 would be enabled and the associated
settings would be visible in the menu.
You set the temperature setting for the alarm stage for each RTD in the RTD Alarm Set cells and the alarm stage
time delay in the RTD Alarm Dly cells.
Likewise, you set the trip stage for each RTD in the RTD Trip Set cells and the trip stage time delay in the RTD Trip
Dly cells.
Should the measured resistance of an RTD be outside of the permitted range, an RTD failure alarm is raised,
indicating an open or short circuit RTD input. These conditions are signalled by the DDB signals RTD Open Cct, RTD
Short Cct and RTD Data Error. These DDB statuses are also shown in the MEASUREMENTS 3 column.
DDB signals are also available to indicate the alarm and trip of the each and any RTD. You can set the monitor bit
cells in the COMMISSION TESTS column to view the statuses of these signals.
160 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
RTD 1 Alarm
RTD Open Cct
RTD Value
RTD 1 Trip
RTD Open Cct
Note: This diagram does not show all stages. Other stages follow similar principles.
V03203
P64x-TM-EN-4.1 161
Chapter 7 - Transformer Condition Monitoring P64x
6 CLIO PROTECTION
To help with monitoring the condition of a power systems, various transducers such as vibration monitors,
tachometers, voltage, current and pressure transducers can be used to extract useful metrics from the system.
Such transducers work by converting the measured data into currents, which can then be fed into instrumentation
device such as meters or IEDs. This mechanism is called CLIO protection. CLIO stands for Current Loop Input
Output.
Transducers have current ranges associated with the full scale of what they are measuring. Typically these ranges
are 0-1 mA, 0-10 mA, 0-20 mA, or 4-20 mA.
Note:
Do Not select CLIO options if CLIO board is not fitted.
162 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
Maximum
ADC ADC
Minimum Count Minimum Count
4095 4095
0 0
0 mA 1 mA Current I/P 0 mA 10 mA Current I/P
0 - 1 mA 0 - 10 mA
1.0836 mA 22.7556 mA
Minimum
ADC ADC
Minimum Count Count
4095 4095
0 0
0 mA 20 mA Current I/P 0 mA 4 mA 20 mA Current I/P
0 - 20 mA 4 - 20 mA 22.7556 mA
22.7556 mA
E03204
Note:
If the Maximum is set less than the Minimum, the slopes of the graphs will be negative.
Power-on diagnostics and continuous self-checking of the current loop inputs are integrated into the hardware.
When a failure is detected, the protection associated with all the current loop inputs is disabled and a single alarm
DDB signal (CL Card I/P Fail) is set and an alarm is raised. A maintenance record with an error code is also
recorded with additional details about the type of failure.
For the 4 – 20 mA input range, a current level below 4 mA indicates that there is a fault with the transducer or the
wiring. An instantaneous undercurrent alarm element is available, with a setting range from 0 to 4 mA. This
element controls a DDB output signal for each CL input (CL(n)I< Fail Alm), where (n) is the number of the CL input.
You can then map this to a user defined alarm if required.
Hysteresis is implemented for each protection element. For ‘Over’ protection, the drop-off/pick-up ratio is 95%, for
‘Under’ protection, the ratio is 105%.
A timer block input is available for each current loop input stage. This will reset the CL input timers of the relevant
stage if energized. If a current loop input is blocked, the protection and alarm timer stages and the 4 – 20 mA
undercurrent alarm associated with that input are blocked. The blocking signals may be useful for blocking the
current loop inputs when the CB is open for example.
DDB signals are available for each current loop input to indicate the start of alarm and trip stages. These are CLI(n)
Alarm Start, and CLI(n) Trip Start, CLI(n) Alarm and CLI(n) Trip, where (n) is the number of the current loop input.
The Monitor Bit cells of the COMMISSIONTESTS column can be configured to show the state of the DDB signals.
P64x-TM-EN-4.1 163
Chapter 7 - Transformer Condition Monitoring P64x
The current loop input starts are mapped internally to the Any Start DDB signal.
RTD Value
CLI1 Trip Start
V3205 Note: This diagram does not show all stages. Other stages follow similar principles.
164 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
1 mA 10 mA
Relay Relay
Measurement Measurement
0 mA 0 mA
Minimum Maximum Minimum Maximum
0 - 1 mA 0 - 10 mA
Minimum
20 mA 20 mA
4 mA
Relay Relay
Measurement 0 mA Measurement
0 mA
Minimum Maximum Minimum Maximum
0 - 20 mA 4 - 20 mA
E03206
Note:
If the Maximum is set less than the Minimum, the slopes of the graphs will be negative.
The transducers inside the device are of the current output type. This means that the correct value of output is
always maintained over the load range specified. The range of load resistance varies a great deal, depending on
the design and the value of output current. Transducers with a full-scale output of 10 mA will normally feed any
load up to a value of 1000 ohms (compliance voltage 10V). This equates to an approximate cable length of 15 km.
We recommend using a screened cable, earthed at one end. This helps reduce interference on the output current
signal. The table below shows typical cable impedances per kilometer for common cables. The compliance voltage
dictates the maximum load that a transducer output can feed. Therefore, the 20 mA output will be restricted to a
maximum load of 500 ohms.
Cable 1/0.6 mm 1/0.85 mm 1/1.38 mm
CSA (mm2) 0.28 0.57 1.50
R (ohms/km) 65.52 32.65 12.38
You can connect the receiving equipment at any point in the output loop and install additional equipment later.
You do not need to adjust the transducer output, providing the compliance voltage is not exceeded.
Where you use the output current range for control purposes, you may wish to fit appropriately rated diodes, or
Zener diodes, across the terminals of each of the units in the series loop. This will guard against the possibility of
their internal circuitry becoming open circuit. In this way, a faulty unit in the loop does not cause all the indications
P64x-TM-EN-4.1 165
Chapter 7 - Transformer Condition Monitoring P64x
to disappear, because the constant current nature of the transducer output simply raises the voltage and
continues to force the correct output signal around the loop.
The device provides power-on diagnostics and continuous self-checking of the current loop hardware. If a failure is
detected, all the current loop output functions are disabled and an alarm signal (CL Card O/P Fail) is raised. A
maintenance record (with an error code) is also produced, which provides additional details about the type of
failure.
The Maximum and Minimum settings allow you to enter the range of physical or electrical quantities measured by
the transducer. These are without units, however, you can enter the transducer function and the unit of the
measurement using the 16-character user-defined CL Input Label. For example, if using an input to monitor a
power measuring transducer, the text could be “Active Power (MW)”.
You need to set the alarm and trip thresholds within the range of physical or electrical quantities. The device will
convert the current input value into its corresponding transducer measuring value for the protection calculation.
For example if the CL input minimum is -1000 and the CL input maximum is 1000 for a 0 to 10 mA input, an input
current of 10 mA is equivalent to a measurement value of 1000, 5 mA is 0, and 0 mA is -1000.
These values are available for display in the CLIO Input (n) cells in the MEASUREMENTS 3 menu. The top line shows
the CL Input Label and the bottom line shows the measurement value.
166 P64x-TM-EN-4.1
P64x Chapter 7 - Transformer Condition Monitoring
The relationship of the output current to the value of the measured values is of vital importance and needs careful
consideration. Any receiving equipment must be used within its rating but, if possible, you should apply some kind
of standard.
One of the objectives is to monitor the voltage over a range of values, so you need an upper limit, for example
120%. However, this may lead to difficulties when it comes to scaling an instrument.
The same considerations apply to current transducer outputs and with added complexity to power transducers
outputs, where both the voltage and current transformer ratios must be taken into account.
Some of these difficulties do not need to be considered if the transducer is only feeding, for example, a SCADA
outstation. Any equipment, which can be programmed to apply a scaling factor to individual inputs can
accommodate most signals. The main consideration is to ensure that the transducer is capable of providing a
signal right up to the full-scale value of the input.
P64x-TM-EN-4.1 167
Chapter 7 - Transformer Condition Monitoring P64x
168 P64x-TM-EN-4.1
CHAPTER 8
170 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
1 CHAPTER OVERVIEW
The device provides extensive Restricted Earth Fault functionality. This chapter describes the operation of this
function including the principles of operation, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 171
REF Protection Principles 172
Restricted Earth Fault Protection Implementation 178
Second Harmonic Blocking 183
Application Notes 184
P64x-TM-EN-4.1 171
Chapter 8 - Restricted Earth Fault Protection P64x
Load
REF
IED protection zone
V00620
The current transformers measuring the currents in each phase are connected in parallel. The currents from all
three phases are summed to form a differential current, sometimes known as a spill current. Under normal
operating conditions the currents of the three phases add up to zero resulting in zero spill current. A fault on the
star side will also not result in a spill current, as the fault current would simply circulate in the delta windings.
However, if any of the three delta windings were to develop a fault, the impedance of the faulty winding would
change and that would result in a mismatch between the phase currents, resulting in a spill current. If the spill
current is large enough, it will trigger a trip command.
The following figure shows a REF protection arrangement for the star side of a delta-star transformer.
REF
protection zone
Load
IED
V00621
Here we have a similar arrangement of current transformers connected in parallel. The difference is that we need
to measure the zero sequence current in the neutral line as well. An external unbalanced fault causes zero
sequence current to flow through the neutral line, resulting in uneven currents in the phases, which could cause
172 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
the protection to maloperate. By measuring this zero sequence current and placing it in parallel with the other
three, the currents are balanced, resulting in stable operation. Now only a fault inside the star winding can create
an imbalance sufficient to cause a trip.
87
1.0
IF IF
Source
IS Current p.u.
(x full load)
Pickup
IS
0.2
IF
64
20% 100%
Winding not protected
87
10
IF 8 IF
Source Current p.u.
IS (x full load) 6
2 IS
IF
64 20% 40% 60% 80% 100%
P64x-TM-EN-4.1 173
Chapter 8 - Restricted Earth Fault Protection P64x
In this case, the value of fault current (IF) varies with the fault location in a complex manner.
A restricted earth fault element is connected to measure IF directly. This provides very sensitive earth fault
protection.
For solidly earthed systems, the operating current for the transformer differential protection is still significant for
faults over most of the winding. For this reason, independent REF protection may not have been previously
considered, especially where an additional device would have been needed. But with this product, it can be
applied without extra cost.
174 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
CTs will provide a lower-impedance path compared with the device input impedance. The principle has been used
for more than half a century. Some advantages of using High Impedance REF are listed below:
● It provides a simple proven algorithm, which is fast, robust and secure.
● It is less sensitive to CT saturation.
Phase A
Phase A
Phase B
Phase B
Phase C
Phase C
I Phase A
I Phase A
I Phase B
I Phase B
I Phase C
I Phase C
I Neutral
IED IED
Connecting IED to star winding for Low Connecting IED to delta winding for Low
Impedance REF Impedance REF
V00679
Differential current
Higher
slope
Operate region
Lower slope
Restraint region
Minimum operating current
Bias current
First knee point Second knee point
V00677
The flat area of the characteristic is the minimum differential current required to cause a trip (operate current) at
low bias currents. From the first kneepoint onwards, the operate current increases linearly with bias current, as
shown by the lower slope on the characteristic. This lower slope provides sensitivity for internal faults. From the
P64x-TM-EN-4.1 175
Chapter 8 - Restricted Earth Fault Protection P64x
second knee point onwards, the operate current further increases linearly with bias current, but at a higher rate.
The second slope provides stability under through fault conditions.
Note:
In Restricted Earth Fault applications, Bias Current Compensation is also known as Low Impedance REF.
Healthy CT Saturated CT
Protected
circuit
A-G
Zm1 Zm2
I = Is + IF
RCT1 RCT2
I IF
RL1 IS RL3
Vs RST
R
RL2 RL4
V00671
When subjected to heavy through faults the line current transformer may enter saturation unevenly, resulting in
imbalance. To ensure stability under these conditions a series connected external resistor is required, so that most
of the unbalanced current will flow through the saturated CT. As a result, the current flowing through the device
will be less than the setting, therefore maintaining stability during external faults.
Voltage across REF element Vs = IF (RCT2 + RL3 + RL4)
Stabilising resistor RST = Vs/Is –RR
where:
● IF = maximum secondary through fault current
● RR = device burden
● RCT = CT secondary winding resistance
● RL2 and RL3 = Resistances of leads from the device to the current transformer
● RST = Stabilising resistor
High Impedance REF can be used for either delta windings or star windings in both solidly grounded and
resistance grounded systems. The connection to a modern IED are as follows:
176 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
Phase A
Phase A
Phase B
Phase B
Phase C
Phase C
I Phase A
I Phase B
I Phase C
RSTAB I Neutral
I Neutral RSTAB
IED IED
Connecting IED to star winding for High Connecting IED to delta winding for High
Impedance REF Impedance REF
V00680
P64x-TM-EN-4.1 177
Chapter 8 - Restricted Earth Fault Protection P64x
High impedance REF is not blocked by Current Transformer Supervision or Stub Bus Protection.
Where the terminals T1 to T5 correspond to the bits in the binary string as follows (1 = in use, 0 = not in use). The bit
order starts with T1 on the right-hand side. For example:
178 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
If a CT is assigned to more than one winding, then an alarm is issued (CT Selection Alm). When this DDB signal is
asserted, the protection is also blocked.
I diff = I A + I B + I C + K I N
( )
The bias current is as follows:
1
I bias =
2
{
max I A , I B , I C + K I N }
where:
● K = Neutral CT ratio / Line CT ratio
● IN = current measured by the neutral CT
P64x-TM-EN-4.1 179
Chapter 8 - Restricted Earth Fault Protection P64x
I DIFF
Operate K2
Restrain
I S1 K1
I S2 I BIAS
E04021
Note:
Is1 and Is2 are relative to the line CT, which is always the reference CT.
180 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
No transient bias is produced under load switching conditions, or when the CT comes out of saturation.
REF HV Start
Id iff HV I diff
DT
Is1
& REF Trip HV
Ibias HV Is2 I bias
Blk REF HV
CTS HV 1
HV-LZREF sf OOR
Enabled
V00708
1 I op
Ie < − [ IREF > Is ]
n CT ratio
2. The maximum current setting to achieve a specific primary operating current with a given current
transformer magnetizing current:
I op
[ IREF > Is ] < − nI e
CT ratio
3. The protection primary operating current for a particular operating current with a particular level of
magnetizing current:
P64x-TM-EN-4.1 181
Chapter 8 - Restricted Earth Fault Protection P64x
To achieve the required primary operating current with the current transformers that are used, you must select a
current setting for the high impedance element, as shown in item 2 above. You can calculate the value of the
stabilising resistor (RST) in the following manner.
Vs I ( R + 2 RL )
Rst = = F CT
[ IREF > Is ] [ IREF > Is ]
where:
● RCT = the resistance of the CT winding
● RL = the resistance of the lead from the CT to the IED.
Note:
The above formula assumes negligible relay burden.
We recommend a stabilizing resistor, which is continuously adjustable up to its maximum declared resistance.
182 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
Idiff f undamental HV
Is-HS1 &
& REF I H2 S tart HV
IH2 REF S et HV Note: S ame principle ap plies for LV and TV wind ings
V00705
P64x-TM-EN-4.1 183
Chapter 8 - Restricted Earth Fault Protection P64x
5 APPLICATION NOTES
Primary Secondary
A a
V2 V1
B b
c
C
V00681
An earth fault on such a winding causes a current which is dependent on the value of earthing impedance. This
earth fault current is proportional to the distance of the fault from the neutral point since the fault voltage is
directly proportional to this distance.
The ratio of transformation between the primary winding and the short circuited turns also varies with the position
of the fault. Therefore the current that flows through the transformer terminals is proportional to the square of the
fraction of the winding which is short circuited.
The earthing resistor is rated to pass the full load current IFLC = V1/Ö3R
Assuming that V1 = V2 then T2 = Ö3T1
For a fault at x PU distance from the neutral, the fault current If = xV1/Ö3R
Therefore the secondary fault current referred to the primary is Iprimary = x2.IFLC/Ö3
If the fault is a single end fed fault, the primary current should be greater than 0.2 pu (Is1 default setting) for the
differential protection to operate. Therefore x2/Ö3 > 20%
The following diagram shows that 41% of the winding is protected by the differential element.
184 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
X in % Idiff in %
10 0.58
20 2.31
30 5.20
59% of unprotected winding
40 9.24
50 14.43
60 20.00
70 28.29
80 36.95 41% of protected winding
90 46.77
100 57.74
V00682
Phase A
Phase B
Phase C
I Phase A
I Phase B
I Phase C
Neutral CT 200:1
I Neutral
IN IED
V00683
P64x-TM-EN-4.1 185
Chapter 8 - Restricted Earth Fault Protection P64x
Another advantage of Low Impedance REF protection is that you can use a neutral CT with a lower ratio than the
line CTs in order to provide better earth fault sensitivity. In the bias calculation, the device applies a scaling factor
to the neutral current. This scaling factor is as follows:
Scaling factor = K = Neutral CT ratio / Line CT ratio
This results in the following differential and bias current equations:
I diff = I A + I B + I C + K I N
( )
1
I bias =
2
{
max I A , I B , I C + K I N }
5.2.3 PARAMETER CALCULATIONS
Consider a solidly earthed 90 MVA 132 kV transformer with a REF-protected star winding. Assume line CTS with a
ratio of 400:1.
Is1 is set to 10% of the winding nominal current:
CTy
CTx
Neutral CT N
V00754
Figure 84: Low-Z REF for dual CB application with different phase CT ratios
The low impedance REF function can be used in dual breaker (breaker-and-a-half) applications. The line CT ratios
can be different. In this case the low impedance REF differential and bias current formulae are calculated as
follows:
186 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
( )
I diff ( REF ) = IACTx + IB CTx + IC CTx + K1 IACTy + K1 IB CTy + K1 IC CTy + K 2 IN
1
I bias ( REF ) =
2 { ( )( )(
max IACTx + K1 IACTy , IB CTx + K1 IB CTy , IC CTx + K1 IC CTy + K 2 IN
) }
where:
● CTx and CTy (T1, T2, T3, T4 or T5) are the current inputs associated with a particular winding (given in the
settings HV CT Terminals, LV CT Terminals and TV CT Terminals respectively)
● K1 = CTy Ratio/CTx Ratio (Scaling Factor K1)
● K2 = Neutral CT Ratio/CTx Ratio (Scaling Factor K2)
● Reference: CTx, which is the same as T1-CT
Note:
The above formulae are valid for autotransformers and conventional transformers when the Phase CT Ratios are different
(CTx ≠ CTy) and the reference is CTx
T1 CT T2 CT
Low
Impedance
REF
TN1 CT
T3 CT T4 CT T5 CT
V00707
Figure 85: Low-Z REF for dual CB application with same phase CT ratios
The low impedance REF function can be used in dual breaker (breaker-and-a-half) applications. The line CT ratios
may be identical. In this case the Restricted Earth Fault (REF) Low Impedance (Z) Differential and Bias current
formulae are calculated as follows:
P64x-TM-EN-4.1 187
Chapter 8 - Restricted Earth Fault Protection P64x
n
I diff ( REF ) = ∑ ( IA
n =1
TxCT
)
+ IBTxCT + IC TxCT + K n I TN1 CT
n
∑ IATxCT
n =1
1 n
I bias ( REF ) = max ∑ IB TxCT + K n I TN1 CT
2 n =1
n
∑ IC TxCT
n =1
where:
● Tx CT = T1, T2, T3, T4 or T5.
● Kn = TN1 CT Ratio/ Tx CT Ratio
● TN1 CT Ratio = Neutral CT Ratio.
● Reference: Tx CT.
where:
● VK = kneepoint voltage
● K = CT dimensioning factor
● In = rated current
● RCT = resistance of CT secondary winding
● RL = Resistance of a single lead from device to current transformer
● Rr = resistance of any other protection devices sharing the current transformer
188 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
where:
● VK = kneepoint voltage
● K = CT dimensioning factor
● In = rated current
● RCT = resistance of CT secondary winding
● RL = Resistance of a single lead from device to current transformer
● Rr = resistance of any other protection devices sharing the current transformer
CT1
A a
B b
c
C
TN1 CT
TN2 CT
TN3 CT
CTN Rst
Varistor
V00684
P64x-TM-EN-4.1 189
Chapter 8 - Restricted Earth Fault Protection P64x
CT1
A
a
B
b
C c
TN 1 CT
TN 2 CT
Varistor TN 3 CT
Rst
V00685
CT2
a
CT1
A
b
CTN
B
c
TN1 CT
Varistor
Rst
V00686
190 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
A 400:1
a
RCT
B b
RL
c
C
RL
RL
Transformer: High Z
RCT
90 MVA REF
33/132 kV
Dyn11, X = 5% RL
Buderns:
RCT = 0.5 W
RL = 0.98 W
V00687
P64x-TM-EN-4.1 191
Chapter 8 - Restricted Earth Fault Protection P64x
Note:
K can reach a maximum value of approximately 1.
Note:
The kneepoint voltage value used in the above formula should be the actual voltage obtained from the CT magnetizing
characteristic and not a calculated value.
Note:
One stabilizing resistor, Alstom part No. ZB9016 756, and one varistor, Alstom part No. 600A/S1/S256 might be used.
192 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
where:
● Vp = Peak voltage developed by the CT under internal fault conditions
● Vk = Current transformer kneepoint voltage
● Vf = Maximum voltage that would be produced if CT saturation did not occur
● I'f = Maximum internal secondary fault current
● RCT = Current transformer secondary winding resistance
● RL = Maximum lead burden from current transformer to relay
● RST = Relay stabilising resistor
You should always use Metrosils when the calculated values are greater than 3000 V. Metrosils are connected
across the circuit to shunt the secondary current output of the current transformer from the device to prevent very
high secondary voltages.
Metrosils are externally mounted and take the form of annular discs. Their operating characteristics follow the
expression:
V = CI0.25
where:
● V = Instantaneous voltage applied to the Metrosil
● C = Constant of the Metrosil
● I = Instantaneous current through the Metrosil
With a sinusoidal voltage applied across the Metrosil, the RMS current would be approximately 0.52 x the peak
current. This current value can be calculated as follows:
4
2VS ( RMS )
I RMS = 0.52
C
where:
● VS(RMS) = RMS value of the sinusoidal voltage applied across the metrosil.
This is due to the fact that the current waveform through the Metrosil is not sinusoidal but appreciably distorted.
The Metrosil characteristic should be such that it complies with the following requirements:
● The Metrosil current should be as low as possible, and no greater than 30 mA RMS for 1 A current
transformers or 100 mA RMS for 5 A current transformers.
● At the maximum secondary current, the Metrosil should limit the voltage to 1500 V RMS or 2120 V peak for
0.25 second. At higher device voltages it is not always possible to limit the fault voltage to 1500 V rms, so
higher fault voltages may have to be tolerated.
The following tables show the typical Metrosil types that will be required, depending on relay current rating, REF
voltage setting etc.
The Metrosil units normally recommended for use with 1Amp CTs are as shown in the following table:
P64x-TM-EN-4.1 193
Chapter 8 - Restricted Earth Fault Protection P64x
Note:
Single pole Metrosil units are normally supplied without mounting brackets unless otherwise specified by the customer.
In some situations single disc assemblies may be acceptable, contact General Electric for detailed applications.
Note:
The Metrosils recommended for use with 5 Amp CTs can also be used with triple pole devices and consist of three single pole
units mounted on the same central stud but electrically insulated from each other. To order these units please specify "Triple
pole Metrosil type", followed by the single pole type reference. Metrosil for higher voltage settings and fault currents are
available if required.
194 P64x-TM-EN-4.1
P64x Chapter 8 - Restricted Earth Fault Protection
where:
● IF = maximum external fault level
● RCT = resistance of CT secondary winding
● RL = resistance of a single lead from device to current transformer
The assumption that one CT is completely saturated for an external fault does not describe what actually happens
when asymmetric CT saturation occurs. The CT that saturates will only saturate during parts of each current
waveform cycle. This means that the spill current waveform seen by the differential element will be highly non-
sinusoidal. The sensitivity to non-sinusoidal spill waveforms for through-faults will be a function of the REF
frequency response, the REF operating time, the REF current setting and the wave shapes.
The frequency response and the operating speed are factors that are inherent to the design. Spill current wave
shapes will be related to the ratio of the CT kneepoint voltage (VK) to the circuit impedance. The stability voltage is
determined by the current setting and the stabilising resistor. The stability of the High Impedance REF function
during through faults is determined by the ratio VK/VS. Where VK is the CT knee point voltage and VS is the stability
voltage.
The relationship between the VK/VS ratio and the required stability factor K has been found to be of a general form
for various designs that have undergone conjunctive testing. It is the absolute values of VK/VS and K that vary in
the relationship for different device designs.
Once stability has been considered, the next performance factor to take into account is the operating time for
internal faults. The CT kneepoint voltage as a multiple of the protection stability voltage setting (VK/VS) will govern
the operating time of a differential relay element for heavy internal faults with transiently offset fault current
waveforms. With the aid of the operating time curves derived for the device, it is possible to identify the ratio VK/VS
that is required to achieve a desired average operating speed for internal faults.
The approach with older electromechanical high impedance relays was to use an universally safe K factor of 1.0,
but the older relays operated quickly with a lower VK/Vs ratio. With more modern IEDs, it is desirable to identify the
optimum K factor for stability, so that the required VK/Vs ratio for stability and operating speed will not make CT
kneepoint voltage requirements worse than traditional requirements.
The high impedance REF CT requirements are shown in the following figure. They are valid for:
5 £ X/R £ 120 and 0.5In £ 40In
0.4 0.06
0.5
0.05
Average operating time
0.6
0.7 0.04
0.8 Average operating time (red curve) 0.03
K
Unstable
0.9 0.02
K (blue curve)
1.0
Stable 0.01
1.1
1.2 0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
VK /VS
V00752
P64x-TM-EN-4.1 195
Chapter 8 - Restricted Earth Fault Protection P64x
If we take the example where the average operating time is 38 ms, the above graphical operations reveal that
Vk/Vs = 4 and K = 0.95.
For best accuracy we recommend class X or class 5P current transformers (CTs). The CT requirements for high
impedance REF protection are generally lower than those for differential protection. If the line CTs for high
impedance REF protection are the same as those used for differential protection, the differential CT requirements
cover both differential and high impedance REF applications. However if the line CTs for high impedance REF are
not the same as those used for differential protection, the high impedance REF CT requirements can be obtained
by using the graph shown above.
196 P64x-TM-EN-4.1
CHAPTER 9
198 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
1 CHAPTER OVERVIEW
The P642, P643, P645 provides a wide range of current protection functions. This chapter describes the operation
of these functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 199
Overcurrent Protection Principles 200
Phase Overcurrent Protection 211
Voltage Dependent Overcurrent Element 219
Negative Sequence Overcurrent Protection 222
Earth Fault Protection 226
Second Harmonic Blocking 232
P64x-TM-EN-4.1 199
Chapter 9 - Current Protection Functions P64x
To ensure that only the necessary circuit breakers are tripped and that these are tripped with the smallest possible
delay, the IEDs in the protection scheme need to co-ordinate with each other. Various methods are available to
achieve correct co-ordination between IEDs in a system. These are:
● By means of time alone
● By means of current alone
● By means of a combination of both time and current.
Grading by means of current alone is only possible where there is an appreciable difference in fault level between
the two locations where the devices are situated. Grading by time is used by some utilities but can often lead to
excessive fault clearance times at or near source substations where the fault level is highest.
For these reasons the most commonly applied characteristic in co-ordinating overcurrent devices is the IDMT
(Inverse Definite Minimum Time) type.
The second requirement means that the protection scheme should be designed such that only the circuit
breaker(s) in the protection zone where the fault occurs, should trip.
These two criteria are actually in conflict with one another, because to satisfy (1), we increase the risk of shutting
off healthy parts of the grid, and to satisfy (2) we purposely introduce time delays, which increase the amount of
time a fault current will flow. With IDMT protection applied to radial feeders, this problem is exacerbated by the
nature of faults in that the protection devices nearest the source, where the fault currents are largest, actually
need the longest time delay.
IDMT characteristics are described by operating curves. Traditionally, these were defined by the performance of
electromechanical relays. In numerical protection, equations are used to replicate these characteristics so that
they can be used to grade with older equipment.
The old electromechanical relays countered this problem somewhat due to their natural operate time v. fault
current characteristic, whereby the higher the fault current, the quicker the operate time. The characteristic typical
of these electromechanical relays is called Inverse Definite Minimum Time or IDMT for short.
200 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
These equations and corresponding curves governing these characteristics are very well known in the power
industry.
Standard Inverse
This characteristic is commonly known as the 3/10 characteristic, i.e. at ten times setting current and TMS of 1 the
relay will operate in 3 seconds.
The characteristic curve can be defined by the mathematical expression:
0.14
top = T 0.02
I
−1
Is
The standard inverse time characteristic is widely applied at all system voltages – as back up protection on EHV
systems and as the main protection on HV and MV distribution systems.
In general, the standard inverse characteristics are used when:
● There are no co-ordination requirements with other types of protective equipment further out on the
system, e.g. Fuses, thermal characteristics of transformers, motors etc.
● The fault levels at the near and far ends of the system do not vary significantly.
● There is minimal inrush on cold load pick up. Cold load inrush is that current which occurs when a feeder is
energised after a prolonged outage. In general the relay cannot be set above this value but the current
should decrease below the relay setting before the relay operates.
Very Inverse
This type of characteristic is normally used to obtain greater time selectivity when the limiting overall time factor is
very low, and the fault current at any point does not vary too widely with system conditions. It is particularly
suitable, if there is a substantial reduction of fault current as the distance from the power source increases. The
steeper inverse curve gives longer time grading intervals. Its operating time is approximately doubled for a
reduction in setting from 7 to 4 times the relay current setting. This permits the same time multiplier setting for
several relays in series.
The characteristic curve can be defined by the mathematical expression:
13.5
top = T
I
−1
Is
Extremely Inverse
With this characteristic the operating time is approximately inversely proportional to the square of the current. The
long operating time of the relay at peak values of load current make the relay particularly suitable for grading with
fuses and also for protection of feeders which are subject to peak currents on switching in, such as feeders
supplying refrigerators, pumps, water heaters etc., which remain connected even after a prolonged interruption of
supply.
P64x-TM-EN-4.1 201
Chapter 9 - Current Protection Functions P64x
For cases where the generation is practically constant and discrimination with low tripping times is difficult to
obtain, because of the low impedance per line section, an extremely inverse relay can be very useful since only a
small difference of current is necessary to obtain an adequate time difference.
Another application for this relay is with auto reclosers in low voltage distribution circuits. As the majority of faults
are of a transient nature, the relay is set to operate before the normal operating time of the fuse, thus preventing
perhaps unnecessary blowing of the fuse.
Upon reclosure, if the fault persists, the recloser locks itself in the closed position and allows the fuse to blow to
clear the fault.
This characteristic is also widely used for protecting plant against overheating since overheating is usually an I2t
function.
This characteristic curve can be defined by the mathematical expression:
80
top = T 2
I
−1
Is
120
top = T
I
−1
Is
In the above equations:
● top is the operating time
● T is the time multiplier setting
● I is the measured current
● Is is the current threshold setting.
The ratio I/Is is sometimes defined as ‘M’ or ‘PSM’ (Plug Setting Multiplier).
These curves are plotted as follows:
202 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
1000.00
100.00
10.00
1.00
Very Inverse (VI)
0.10
1 10 100
β
top = T α + L+C
M −1
and the IEC 60255 IDMT Reset equation is:
β
tr = T α
1− M
where:
● top is the operating time
● tr is the reset time
● T is the Time Multiplier setting
● M is the ratio of the measured current divided by the threshold current (I/Is)
● β is a constant, which can be chosen to satisfy the required curve characteristic
● α is a constant, which can be chosen to satisfy the required curve characteristic
● C is a constant for adding Definite Time (Definite Time adder)
● L is a constant (usually only used for ANSI/IEEE curves)
The constant values for the IEC IDMT curves are as follows:
Curve Description b constant a constant L constant
IEC Standard Inverse Operate 0.14 0.02 0
IEC Standard Inverse Reset 8.2 6.45 0
P64x-TM-EN-4.1 203
Chapter 9 - Current Protection Functions P64x
1
top = K
0.236
0.339 −
M
where:
● top is the operating time
● K is the Time Multiplier setting
● M is the ratio of the measured current divided by the threshold current (I/Is)
Note:
* When using UK Long Time Inverse, UK Rectifier or RI for the Operate characteristic, DT (Definite Time) is always used for the
Reset characteristic.
β
top = TD α + L+C
M −1
and the IEEE IDMT Reset equation is:
β
tr = TD α
1− M
where:
● top is the operating time
● tr is the reset time
● TD is the Time Dial setting
● M is the ratio of the measured current divided by the threshold current (I/Is)
● b is a constant, which can be chosen to satisfy the required curve characteristic
● a is a constant, which can be chosen to satisfy the required curve characteristic
● C is a constant for adding Definite Time (Definite Time adder)
● L is a constant (usually only used for ANSI/IEEE curves)
204 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
Note:
* When using UK Long Time Inverse or UK Rectifier for the Operate characteristic, DT is always used for the Reset
characteristic.
P64x-TM-EN-4.1 205
Chapter 9 - Current Protection Functions P64x
1000 1000
0.025 0.025
0.075 0.075
10 10
Time in seconds
Time in seconds
0.100 0.100
0.300 0.300
1 1
0.500 0.500
0.700 0.700
0.900 0.900
0.1 0.1
1.000 1.000
1.200 1.200
0.01 0.01
0.5 5 50 0.5 5 50
Current in Multiples of Setting Current in Multiples of Setting
E00757
1000
100 TMS
0.05
100
0.025
0.5
0.075
10
1
Time in seconds
Time in seconds
0.100 10
5
0.300
1 10
0.500 1
0.700 30
0.900 50
0.1 0.1
1.000
70
1.200
0.01 100
0.01
0.5 5 50 0.5 5 50
Current in Multiples of Setting Current in Multiples of Setting
E00758
Figure 93: IEC Extremely inverse and IEEE moderate inverse curves
206 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
10000 10000
TD TD
0.5 0.5
100 100
1 1
Time in seconds
Time in seconds
5 5
10 10
10 10
1 30 1 30
50 50
0.1 0.1
70 70
E00759
Figure 94: IEEE very and extremely inverse curves
P64x-TM-EN-4.1 207
Chapter 9 - Current Protection Functions P64x
IDMT/DT
Threshold
& & & Trip Sign al
Function inhibit
Voltage
Directional Check
Current
An energising quantity is either a voltage input from a system voltage transformer, a current input from a system
current transformer or another quantity derived from one or both of these. The energising quantities are extracted
from the power system. The signals are converted to digital quantities where they can be processed by the IEDs
internal processor.
In general, an energising quantity, be it a current, voltage, power, frequency, or phase quantity, is compared with a
threshold value, which may be settable, or hard-coded depending on the function. If the quantity exceeds (for
overvalues) or falls short of (for undervalues) the threshold, a signal is produced, which when gated with the
various inhibit and blocking functions becomes the Start signal for that protection function. This Start signal is
generally made available to Fixed Scheme Logic (FSL) and Programmable Scheme Logic (PSL) for further
processing. It is also passed through a timer function to produce the Trip signal. The timer function may be an
IDMT curve, or a Definite Time delay, depending on the function. This timer may also be blocked with timer
blocking signals and settings. The timer can be configured by a range of settings to define such parameters as the
type of curve, The Time Multiplier Setting, the IDMT constants, the Definite Time delay etc.
In General Electric products, there are usually several independent stages for each of the functions, and for three-
phase functions, there are usually independent stages for each of the three phases.
Typically some stages use an Inverse Definite Minumum time (IDMT) timer function, and others use a Definite Time
timer (DT) function. If the DT time delay is set to '0', then the function is known to be "instantaneous". In many
instances, the term 'instantaneous protection" is used loosely to describe Definite Time protection stages, even
when the stage may not theoretically be instantaneous.
Many protection functions require a direction-dependent decision. Such functions can only be implemented where
both current and voltage inputs are available. For such functions, a directional check is required, whose output can
block the Start signal should the direction of the fault be wrong.
Note:
In the logic diagrams and descriptive text, it is usually sufficient to show only the first stage, as the design principles for
subsequent stages are usually the same (or at least very similar). Where there are differences between the functionality of
different stages, this is clearly indicated.
208 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
This feature may be useful in certain applications, such as when grading with upstream electromechanical
overcurrent relays, which have inherent reset time delays. If you set the hold timer to a value other than zero, the
resetting of the protection element timers will be delayed for this period. This allows the element to behave in a
similar way to an electromechanical relay. If you set the hold timer to zero, the overcurrent timer for that stage will
reset instantaneously as soon as the current falls below a specified percentage of the current setting (typically
95%).
Another situation where the timer hold facility may be used to reduce fault clearance times is for intermittent
faults. An example of this may occur in a plastic insulated cable. In this application it is possible that the fault
energy melts and reseals the cable insulation, thereby extinguishing the fault. This process repeats to give a
succession of fault current pulses, each of increasing duration with reducing intervals between the pulses, until the
fault becomes permanent.
When the reset time is instantaneous, the device will repeatedly reset and not be able to trip until the fault
becomes permanent. By using the Timer Hold facility the device will integrate the fault current pulses, thereby
reducing fault clearance time.
P64x-TM-EN-4.1 209
Chapter 9 - Current Protection Functions P64x
+Fm
Steady state
-Fm
2Fm
Switch on at voltage
zero – No residual flux
V03123
We can see that inrush current is a regularly occurring phenomenon and should not be considered a fault, as we
do not wish the protection device to issue a trip command whenever a transformer is switched on at an
inconvenient point during the input voltage cycle. This presents a problem to the protection device, because it
should always trip on an internal fault. The problem is that typical internal transformer faults may produce
overcurrents which are not necessarily greater than the inrush current. Furthermore, faults tend to manifest
themselves on switch on, due to the high inrush currents. For this reason, we need to find a mechanism that can
distinguish between fault current and inrush current. Fortunately, this is possible due to the different natures of the
respective currents. An inrush current waveform is rich in harmonics, especially 2nd harmonics, whereas an
internal fault current consists only of the fundamental. We can therefore develop a restraining method based on
the 2nd harmonic content of the inrush current. The mechanism by which this is achieved, is called second
harmonic blocking.
210 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
Note:
Stages 3 and 4 can have definite time characteristics only.
P64x-TM-EN-4.1 211
Chapter 9 - Current Protection Functions P64x
Where the terminals T1 to T5 correspond to the bits in the binary string as follows (1 = in use, 0 = not in use). The bit
order starts with T1 on the right-hand side. For example:
If a CT is assigned to more than one winding, then an alarm is issued (CT Selection Alm). When this DDB signal is
asserted, the protection is also blocked.
212 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
IDMT/DT
I> Threshold*1
& & POC 1 I>1 Trip A
POC1 IA2H Start
I> Blocking
&
2H Blocks I>1
Timer Setting s
IDMT/DT
I> Threshold*1
& & POC 1 I>1 Trip B
POC1 IB2H Start
I> Blocking
&
2H Blocks I>1
Timer Setting s
IDMT/DT
I> Threshold*1
& & POC 1 I>1 Trip C
POC1 IC2H Start
I> Blocking
&
2H Blocks I>1 1 POC1 I>1 Start
Timer Setting s
*1 The threshold set tin gs are influence d by Vo ltage Control Overcurrent functionality
V00672
Phase Overcurrent Modules are level detectors that detect when the current magnitude exceeds a set threshold.
When this happens, the Phase Overcurrent Module in question issues a signal, which is gated with some blocking
signals to produce the Start signal. This Start signal is gated with other blocking signals and applied to the
IDMT/DT timer module. It is also made available directly to the user for use in the PSL. For each stage, there are
three Phase Overcurrent Modules, one for each phase. The three Start signals from each of these phases are OR'd
together to create a 3-phase Start signal.
The outputs of the IDMT/DT timer modules are the trip signals which are used to drive the tripping output relay.
These tripping signals are also OR'd together to create a 3-phase Trip signal.
The IDMT/DT timer modules can be blocked by:
● A Phase Overcurrent Timer Block (I>(n) Timer Block)
If any one of the above signals is high, or goes high before the timer has counted out, the IDMT/DT timer module is
inhibited (effectively reset) until the blocking signal goes low again. There are separate phase overcurrent timer
block signals, which are independent for each overcurrent stage.
P64x-TM-EN-4.1 213
Chapter 9 - Current Protection Functions P64x
These can be set via the Front panel HMI or with the settings application software.
The Phase Overcurrent threshold setting can be influenced by theVoltage Controlled Overcurrent functions, if this
functionality is available and used.
Under system fault conditions, the fault current vector lags its nominal phase voltage by an angle depending on
the system X/R ratio. The IED must therefore operate with maximum sensitivity for currents lying in this region. This
is achieved by using the IED characteristic angle (RCA). This is the is the angle by which the current applied to the
IED must be displaced from the voltage applied to the IED to obtain maximum sensitivity.
The device provides a setting I> Char Angle, which is set globally for all overcurrent stages. It is possible to set
characteristic angles anywhere in the range –95° to +95°.
A directional check is performed based on the following criteria:
Directional forward
-90° < (angle(I) - angle(V) - RCA) < 90°
Directional reverse
-90° > (angle(I) - angle(V) - RCA) > 90°
214 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
As well as directionalising a particular winding current, for models with more than two winding inputs, you can
directionalise individual inputs if they are associated with that winding.
For close up three-phase faults, all three voltages will collapse to zero and no healthy phase voltages will be
present. For this reason, the device includes a synchronous polarisation feature that stores the pre-fault voltage
information and continues to apply this to the directional overcurrent elements for a time period of 3.2 seconds.
This ensures that either instantaneous or time-delayed directional overcurrent elements will be allowed to operate,
even with a three-phase voltage collapse.
P64x-TM-EN-4.1 215
Chapter 9 - Current Protection Functions P64x
IDMT/DT
I> Threshold
& & POC1 I>1 Trip
IA
VAB
I>1 Direction
Non-Directional
Directional FWD Directional
Directional REV check
Notes: Shown for phase A only. Same principle applies f or phases B and C.
This diagram does not show all st ages. Ot her stages f ollow similar p rinciples.
V00689
The directional overcurrent logic works the same way as non-directional logic except that there is a Directional
Check function, based on the following criteria:
● Directional forward: -90° < (angle(I) - angle(V) - RCA) < 90°
● Directional reverse: -90° > (angle(I) - angle(V) - RCA) > 90°
When the element is selected as directional, blocking of the Voltage Transformer Supervision (VTS Block) is
available (I>Blocking cell). When the relevant bit is set to 1, operation of the VTS will block the stage if
directionalised. When set to 0, the stage will revert to non-directional on operation of the VTS.
216 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
times are usually not possible. Sensitive settings are not possible because the pickup should allow overloading of
the transformer when required. Fast operating times are not possible because of the grading required with respect
to downstream overcurrent relays. To allow fast operating times, phase instantaneous overcurrent functions with
low transient overreach are required.
The pickup of the time delayed overcurrent element can be set to 125-150% of the maximum MVA rating to allow
overloading of the transformer according to IEEE Std. C37.91-2000.
As recommended by IEEE Std. C37.91-2000, you should set the instantaneous overcurrent element to pick up at a
value higher than the maximum asymmetrical through fault current. This is usually the fault current through the
transformer for a low-side three-phase fault. For instantaneous elements, variations in settings of 125–200% are
common. For elements subject to transient overreach, a pickup of 175% of the calculated maximum low-side
three-phase symmetrical fault current generally provides sufficient margin to avoid false tripping for a low-side
bus fault, while still providing protection for severe internal faults. Due to low transient overreach of the third and
fourth overcurrent stages, you may set the instantaneous overcurrent element to 120-130% of the through-fault
level, thus ensuring stability for through faults. The instantaneous pickup setting should also consider the effects of
transformer magnetising inrush current.
In summary, there are a few application considerations to make when applying overcurrent devices to protect a
transformer:
● When applying overcurrent protection to the HV side of a power transformer it is usual to apply a high set
instantaneous overcurrent element in addition to the time delayed low-set, to reduce fault clearance times
for HV fault conditions. Typically, this will be set to approximately 1.3 times the LV fault level, so that it will
only operate for HV faults. A 30% safety margin is sufficient due to the low transient overreach of the third
and fourth overcurrent stages. Transient overreach defines the response of a relay to DC components of
fault current and is quoted as a percentage. A device with a low transient overreach will be largely
insensitive to a DC offset and may therefore be set more closely to the steady state AC waveform.
● The second requirement for this element is that it should remain inoperative during transformer
energisation, when a large primary current flows for a transient period. In most applications, the
requirement to set the device above the LV fault level will automatically result in settings that will be above
the level of magnetising inrush current.
With the third and fourth overcurrent stages, it is possible to apply settings corresponding to 40% of the peak
inrush current while maintaining stability for the condition.
Where an instantaneous element is required to accompany the time delayed protection, as described above, you
should use the third or fourth overcurrent stages as these have wider setting ranges.
P64x-TM-EN-4.1 217
Chapter 9 - Current Protection Functions P64x
33 kV
R1 R2
OC/EF OC/EF
SBEF
R3 R4
DOC/DEF DOC/DEF
OC/EF OC/EF
11 kV
R5
OC/EF
Loads
E00603
In the application shown in the diagram, a fault at ‘F’ could result in the operation of both R3 and R4 resulting in
the loss of supply to the 11 kV busbar. Hence, with this system configuration, it is necessary to apply directional
protection devices at these locations set to 'look into' their respective transformers. These devices should co-
ordinate with the non-directional devices, R1 and R2, to ensure discriminative operation during such fault
conditions.
In such an application, R3 and R4 may commonly require non-directional overcurrent protection elements to
provide protection to the 11 kV busbar, in addition to providing a back-up function to the overcurrent devices on
the outgoing feeders (R5).
For this application, stage 1 of the R3 and R4 overcurrent protection would be set to non-directional and time
graded with R5, using an appropriate time delay characteristic. Stage 2 could then be set to directional (looking
back into the transformer) and also have a characteristic which provides correct co-ordination with R1 and R2.
Directionality for each of the applicable overcurrent stages can be set in the directionality cells (I>1 Direction).
Note:
The principles outlined for the parallel transformer application are equally applicable for plain feeders that are operating in
parallel.
218 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
Start
No
End
V00673
P64x-TM-EN-4.1 219
Chapter 9 - Current Protection Functions P64x
Each of the stages can be set to HV Winding, LV Winding, TV Winding, T1, T2, T3, T4, or T5. If the current signal
chosen for a VCO stage does not belong to the winding where the VT is located, then the VCO element is blocked
and a configuration error alarm is asserted.
The operating characteristic of the current setting when voltage controlled mode is selected is as follows:
Current
setting
Measured voltage
Voltage threshold setting
E00642
Figure 101: Modification of current pickup level for voltage controlled overcurrent protection
In the P643 and P6455, VCO requires an optional three-phase VT to be fitted, and in the P642 it requires that two
single-phase VTs are fitted. In P643/5, the phase-to-phase voltages are derived from the measured phase-to-
neutral voltages. In the P642, two phase-to-phase voltages are measured and the third one is calculated. In the
P642 Vab and Vbc are measured, then Vca is calculated.
220 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
I> Set
KI> Set
E00760
Figure 102: Modification of current pickup level for voltage restrained overcurrent protection
In P643 and P645 models, VRO requires an optional three-phase VT to be fitted, whereas, the P642 model requires
that two single-phase VTs are fitted. Also, in P643 and P645 models, the phase-to-phase voltages are derived from
the measured phase-to-neutral voltages. In the P642, two phase-to-phase voltages are measured and the third
one is calculated. In the P642 Vab and Vbc are measured, then Vca is calculated.
This protection mode is considered to be better suited to Generator-Transformer applications.
P64x-TM-EN-4.1 221
Chapter 9 - Current Protection Functions P64x
222 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
IDMT/DT
I2>1 Current Set
& & NPOC1 I 2>1 Trip
CTS B lock
NPOC1 I nhibit
NPOC1 I 2>1 TB lk
V00674
For Negative Phase Sequence Overcurrent Protection, the energising quanitity I2> is compared with the threshold
voltage I2>1 Current Set. If the value exceeds this setting a start signal is generated, provided there are no blocks.
5% hysteresis is built into the comparator such that the drop-off value is 0.95 x of the current set threshold.
The function can be blocked by an Inhibit signal or by a CTS blocking signal.
The start signal is fed into a timer to produce the trip signal. The timer can be blocked by the timer block signal
This diagram and description applies to each stage of each element, where x is the number of the element and n
is the number of the stage.
P64x-TM-EN-4.1 223
Chapter 9 - Current Protection Functions P64x
IDMT/DT
I2>1 Current Set
& & & NPOC1 I 2>1 Trip
CTS B lock
NPOC1 I nhibit
I2>1 Direction
V2
Directional
I2> V2pol Set
check
NPOC1 I 2>1 TB lk
Note: This diagram does not sho w all stages. Other stages follow similar principles.
V00675
Directionality is achieved by comparing the angle between the negative phase sequence voltage and the negative
phase sequence current. The element may be selected to operate in either the forward or reverse direction. A
suitable characteristic angle setting (I2>Char Angle) is chosen to provide optimum performance. This setting
should be set equal to the phase angle of the negative sequence current with respect to the inverted negative
sequence voltage (–V2), in order to be at the centre of the directional characteristic.
For the negative phase sequence directional elements to operate, the device must detect a polarising voltage
above a minimum threshold, I2>V2pol Set. This must be set in excess of any steady state negative phase
sequence voltage. This may be determined during the commissioning stage by viewing the negative phase
sequence measurements in the device.
When the element is selected as directional (directional devices only), a VTS blocking option is available. When the
relevant bit is set to 1, operation of the Voltage Transformer Supervision (VTS) will block the stage. When set to 0,
the stage will revert to non-directional.
224 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
protection should be set to coordinate with the low-side phase and earth elements for phase-to-earth and phase-
to-phase faults.
The current pick-up threshold must be set higher than the negative phase sequence current due to the maximum
normal load imbalance. This can be set practically at the commissioning stage, making use of the measurement
function to display the standing negative phase sequence current. The setting should be at least 20% above this
figure.
Where the negative phase sequence element needs to operate for specific uncleared asymmetric faults, a precise
threshold setting would have to be based on an individual fault analysis for that particular system due to the
complexities involved. However, to ensure operation of the protection, the current pick-up setting must be set
approximately 20% below the lowest calculated negative phase sequence fault current contribution to a specific
remote fault condition.
For the negative phase sequence directional elements to operate, the device must detect a polarising voltage
above a minimum threshold, I2> V2pol Set. This must be set in excess of any steady state negative phase
sequence voltage. This may be determined during the commissioning stage by viewing the negative phase
sequence measurements in the device.
P64x-TM-EN-4.1 225
Chapter 9 - Current Protection Functions P64x
Depending on the device model, it will provide one or more of the above means for Earth fault protection.
226 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
IDMT/ DT
IN>1 Current
& & EF1 IN>1 Trip
CTS Block
EF 1 IN>1 TBlk
V00690
The Earth Fault current is compared with a set threshold for each stage of each element. If it exceeds this
threshold, a Start signal is triggered, providing it is not blocked. This can be blocked by the second harmonic
blocking function, or an Inhibit Earth Fault DDB signal.
The timer can be blocked by the relevant timer block signal.
Earth Fault protection can follow the same IDMT characteristics as described in the Overcurrent Protection
Principles section. Please refer to this section for details of IDMT characteristics.
The diagram and description applies to all stages of all earth fault elements.
I
top = 5.8 − 1.35 log e
IN > Setting
where:
top is the operating time
I is the measured current
IN> Setting is an adjustable setting, which defines the start point of the characteristic
Note:
Although the start point of the characteristic is defined by the "ΙN>" setting, the actual current threshold is a different setting
called "IDG Ιs". The "IDG Ιs" setting is set as a multiple of "ΙN>".
Note:
When using an IDG Operate characteristic, DT is always used with a value of zero for the Rest characteristic.
An additional setting "IDG Time" is also used to set the minimum operating time at high levels of fault current.
P64x-TM-EN-4.1 227
Chapter 9 - Current Protection Functions P64x
10
8 IDGIsIsSetting
IDG SettingRange
Range
time (seconds)
(seconds)
7
6
Operating time
5
Operating
3
IDG Time
IDG Time Setting
Setting Range
Range
2
0
1 10 100
I/IN>
V00611
Note:
Residual voltage is nominally 180° out of phase with residual current. Consequently, the DEF elements are polarised from the
"-Vres" quantity. This 180° phase shift is automatically introduced within the device.
228 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
The device derives this voltage internally from the 3-phase voltage input tha must be supplied from either a 5-limb
VT or three single-phase VTs. A three-limb VT has no path for residual flux and is therefore unsuitable to supply the
device.
IDMT/DT
IN>1 Current
& & & EF1 IN>1 Trip
CTS B lock
IN> Direction
VN
IN Directional
check
Low Current
EF 1 IN>1 TB lk
This diagram does no t show all st ages. Ot her stages f ollow similar p rinciples.
V00691
Figure 107: Directional EF logic with neutral voltage polarization (single stage)
Voltage Transformer Supervision (VTS) selectively blocks the directional protection or causes it to revert to non-
directional operation. When selected to block the directional protection, VTS blocking is applied to the directional
checking which effectively blocks the Start outputs as well.
P64x-TM-EN-4.1 229
Chapter 9 - Current Protection Functions P64x
sequence source impedance to negligible levels. If this voltage is less than 0.5 volts the device will stop providing
directionalisation.
The directional criteria with negative sequence polarisation is given below:
● Directional forward: -90° < (angle(I2) - angle(V2 + 180°) - RCA) < 90°
● Directional reverse : -90° > (angle(I2) - angle(V2 + 180°) - RCA) > 90°
IDMT/DT
IN>1 Current
& & & EF1 IN>1 Trip
CTS B lock
IN> Direction
V2
V2
I2
Directional
check
IN> I2pol Set
EF 1 IN>1 TB lk
This diagram d oes no t show all st ages. Ot her stages f ollow similar principles.
V00692
Figure 108: Directional Earth Fault logic with negative phase sequence polarisation (single stage)
Voltage Transformer Supervision (VTS) selectively blocks the directional protection or causes it to revert to non-
directional operation. When selected to block the directional protection, VTS blocking is applied to the directional
checking which effectively blocks the Start outputs as well.
The directional criteria with negative sequence polarisation is given below:
● Directional forward: -90° < (angle(I2) - angle(V2 + 180°) - RCA) < 90°
● Directional reverse : -90° > (angle(I2) - angle(V2 + 180°) - RCA) > 90°
230 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
A Neutral Earthing Resistor (NER) is used to limit the earth fault level to a particular value. It is possible that under
an earth fault condition a flashover of the NER could occur, which could lead to a dramatic increase in the earth
fault current. For this reason, it may be appropriate to apply two-stage SBEF protection. The first stage should
have suitable current and time characteristics which coordinate with downstream earth fault protection. The
second stage may then be set with a higher current setting but with zero time delay, providing fast clearance of an
earth fault which gives rise to an NER flashover.
The remaining two stages are available for customer-specific applications.
P64x-TM-EN-4.1 231
Chapter 9 - Current Protection Functions P64x
Second harmonic blocking is applicable to all stages of each of the elements. For POC, 2nd harmonic blocking can
be applied to each phase individually (phase segregated), or to all three phases at once (cross-block).
The function works by identifying and measuring the inrush currents present at switch on. It does this by
comparing the value of the second harmonic current components to the value of the fundamental component. If
this ratio exceeds the set thresholds, then the blocking signal is generated. The threshold is defined by the settings
IH2 I> Set and IH2 IN> Set for Phase Overcurrent protection and Earth Fault protection respectively.
We only want the function to block the protection if the fundamental current component is within the normal
range. If this exceeds the normal range, then this is indicative of a fault, which must be protected. For this reason
there is another settable trigger IH2 IN> Unblock for Phase Overcurrent protection and IH2 I> Unblock for Earth
fault protection, which when exceeded, stops the 2nd harmonic blocking function.
Each overcurrent protection element has an I>Blocking setting with which the stages to be blocked can be
selected.
232 P64x-TM-EN-4.1
P64x Chapter 9 - Current Protection Functions
&
IA fundament al
& POC1 IH2 Any St
IH2 I> Unblock
1
&
IA fu ndament al
&
Low current (hard-coded)
IC 2nd harmonic
&
Low current (hard-coded)
V00703
P64x-TM-EN-4.1 233
Chapter 9 - Current Protection Functions P64x
IN fundamental
Note: This diagram does not show all stages. Other stages follow similar principles.
V00704
234 P64x-TM-EN-4.1
CHAPTER 10
CB FAIL PROTECTION
Chapter 10 - CB Fail Protection P64x
236 P64x-TM-EN-4.1
P64x Chapter 10 - CB Fail Protection
1 CHAPTER OVERVIEW
The device provides a Circuit Breaker Fail Protection function. This chapter describes the operation of this function
including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 237
Circuit Breaker Fail Protection 238
Circuit Breaker Fail Implementation 239
Circuit Breaker Fail Logic 241
Application Notes 243
P64x-TM-EN-4.1 237
Chapter 10 - CB Fail Protection P64x
238 P64x-TM-EN-4.1
P64x Chapter 10 - CB Fail Protection
You can configure the CBF elements CB Fail 1 Timer and CBF Fail 2 Timer to operate for trips triggered by
protection elements within the device. Alternatively you can use an external protection trip by allocating one of the
opto-inputs to the External Trip DDB signal in the PSL.
You can reset the CBF from a breaker open indication (from the pole dead logic) or from a protection reset. In these
cases resetting is only allowed if the undercurrent elements have also been reset. The resetting mechanism is
determined by the settings Volt Prot Reset and Ext Prot Reset.
The resetting options are summarised in the following table:
Initiation (Menu Selectable) CB Fail Timer Reset Mechanism
The resetting mechanism is fixed (e.g. 50/51/46/21/87)
Current based protection
IA< operates AND IB< operates AND IC< operates AND IN< operates
The resetting mechanism is fixed.
Sensitive Earth Fault element
ISEF< Operates
Three options are available:
● All I< and IN< elements operate
Non-current based protection (e.g. 27/59/81/32L)
● Protection element reset AND all I< and IN< elements operate
● CB open (all 3 poles) AND all I< and IN< elements operate
Three options are available.
● All I< and IN< elements operate
External protection
● External trip reset AND all I< and IN< elements operate
● CB open (all 3 poles) AND all I< and IN< elements operate
P64x-TM-EN-4.1 239
Chapter 10 - CB Fail Protection P64x
240 P64x-TM-EN-4.1
P64x Chapter 10 - CB Fail Protection
Any Trip
1 S
Extern CB1 Trip Q
R 1 Trip St ate
T1 IA< Start
T1 IB< Start
&
T1 IC< St art
T1 IN< St art
VN>1 Trip
F>1 Trip
CLI1 Trip
CB1 Closed
1
&
Note on SR Latches
S All latches are reset dominant and are triggered on the
positive edge. If the edge occurs while the reset is active,
Q
the detect ion of t he edge is delayed until the reset
Ext Prot Reset & R becomes non-active.
Prot Reset & I<
I< Only 1
CB Open & I<
&
Extern CB1 Trip
&
1
&
V00694
P64x-TM-EN-4.1 241
Chapter 10 - CB Fail Protection P64x
CB Fail 1 Status
Enabled
Disabled 1
Trip St ate
CB Fail 2 Status
Enabled &
& CB1 BkTrip 3ph
Disabled
Reset State
1
T1 IA< Start
1
CT1A ZCD
T1 IB< Start
1
CT1B ZCD
&
T1 IC< St art
1
CT1C ZCD
Note: This diagram does not show all stages. Other stages follow similar principles.
T1 IN< St art
1
CT1 In ZCD
V00695
242 P64x-TM-EN-4.1
P64x Chapter 10 - CB Fail Protection
5 APPLICATION NOTES
For any protection function requiring current to operate, the device uses operation of undercurrent elements to
detect that the necessary circuit breaker poles have tripped and reset the CB fail timers. However, the
undercurrent elements may not be reliable methods of resetting CBF in all applications. For example:
● Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a line connected voltage transformer. Here, I< only gives a reliable reset method if the
protected circuit would always have load current flowing. In this case, detecting drop-off of the initiating
protection element might be a more reliable method.
● Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a busbar connected voltage transformer. Again using I< would rely on the feeder
normally being loaded. Also, tripping the circuit breaker may not remove the initiating condition from the
busbar, and so drop-off of the protection element may not occur. In such cases, the position of the circuit
breaker auxiliary contacts may give the best reset method.
P64x-TM-EN-4.1 243
Chapter 10 - CB Fail Protection P64x
CBF resets:
1. Undercurrent element asserts
2. Undercurrent element asserts and the
breaker status indicates an open position
3. Protection resets and the undercurrent
Fault occurs element asserts
CBF Safety
Protection Maximum breaker reset margin
Normal operating time clearing time time time
operation
t
Local 86 Remote CB
operating clearing time
time
The following examples consider direct tripping of a 2-cycle circuit breaker. Typical timer settings to use are as
follows:
Typical Delay For 2 Cycle Circuit
CB Fail Reset Mechanism tBF Time Delay
Breaker
CB interrupting time + element reset time (max.) + error in tBF
Initiating element reset 50 + 50 + 10 + 50 = 160 ms
timer + safety margin
CB auxiliary contacts opening/ closing time (max.) + error in tBF
CB open 50 + 10 + 50 = 110 ms
timer + safety margin
CB interrupting time + undercurrent element (max.) + safety
Undercurrent elements 50 + 25 + 50 = 125 ms
margin operating time
Note:
All CB Fail resetting involves the operation of the undercurrent elements. Where element resetting or CB open resetting is
used, the undercurrent time setting should still be used if this proves to be the worst case.
Where auxiliary tripping relays are used, an additional 10-15 ms must be added to allow for trip relay operation.
244 P64x-TM-EN-4.1
CHAPTER 11
246 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
1 CHAPTER OVERVIEW
The device provides a wide range of voltage protection functions. This chapter describes the operation of these
functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 247
Undervoltage Protection 248
Overvoltage Protection 251
Residual Overvoltage Protection 254
Negative Sequence Overvoltage Protection 258
P64x-TM-EN-4.1 247
Chapter 11 - Voltage Protection Functions P64x
2 UNDERVOLTAGE PROTECTION
Undervoltage conditions may occur on a power system for a variety of reasons, some of which are outlined below:
● Undervoltage conditions can be related to increased loads, whereby the supply voltage will decrease in
magnitude. This situation would normally be rectified by voltage regulating equipment such as AVRs (Auto
Voltage Regulators) or On Load Tap Changers. However, failure of this equipment to bring the system
voltage back within permitted limits leaves the system with an undervoltage condition, which must be
cleared.
● If the regulating equipment is unsuccessful in restoring healthy system voltage, then tripping by means of
an undervoltage element is required.
● Faults occurring on the power system result in a reduction in voltage of the faulty phases. The proportion by
which the voltage decreases is dependent on the type of fault, method of system earthing and its location.
Consequently, co-ordination with other voltage and current-based protection devices is essential in order to
achieve correct discrimination.
● Complete loss of busbar voltage. This may occur due to fault conditions present on the incomer or busbar
itself, resulting in total isolation of the incoming power supply. For this condition, it may be necessary to
isolate each of the outgoing circuits, such that when supply voltage is restored, the load is not connected.
Therefore, the automatic tripping of a feeder on detection of complete loss of voltage may be required. This
can be achieved by a three-phase undervoltage element.
● Where outgoing feeders from a busbar are supplying induction motor loads, excessive dips in the supply
may cause the connected motors to stall, and should be tripped for voltage reductions that last longer than
a pre-determined time.
The undervoltage stages can be configured either as phase-to-neutral or phase-to-phase voltages in the V<
Measur't Mode cell.
There is no Timer Hold facility for Undervoltage.
Stage 2 can have definite time characteristics only. This is set in the V<2 Status cell.
Outputs are available for single or three-phase conditions via the V< Operate Mode cell for each stage.
248 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
Note: This diagram doe s not show a ll stag es. Other stag es follow similar principles.
VTS Fast Block only ap plies f or d irectiona l models.
V00803
Figure 114: Undervoltage - single and three phase tripping mode (single stage)
The Undervoltage protection function detects when the voltage magnitude for a certain stage falls short of a set
threshold. If this happens a Start signal, signifying the "Start of protection", is produced. This Start signal can be
blocked by the VTS Fast Block signal and an All Poles Dead signal. This Start signal is applied to the timer module
to produce the Trip signal, which can be blocked by the undervoltage timer block signal (V<(n) Timer Block). For
each stage, there are three Phase undervoltage detection modules, one for each phase. The three Start signals
from each of these phases are OR'd together to create a 3-phase Start signal (V<(n) Start), which can be be
activated when any of the three phases start (Any Phase), or when all three phases start (Three Phase), depending
on the chosen V< Operate Mode setting.
The outputs of the timer modules are the trip signals which are used to drive the tripping output relay. These
tripping signals are also OR'd together to create a 3-phase Trip signal, which are also controlled by the V< Operate
Mode setting.
If any one of the above signals is low, or goes low before the timer has counted out, the timer module is inhibited
(effectively reset) until the blocking signal goes high.
In some cases, we do not want the undervoltage element to trip; for example, when the protected feeder is de-
energised, or the circuit breaker is opened, an undervoltage condition would obviously be detected, but we would
not want to start protection. To cater for this, an All Poles Dead signal blocks the Start signal for each phase. This
is controlled by the V<Poledead Inh cell, which is included for each of the stages. If the cell is enabled, the relevant
stage will be blocked by the integrated pole dead logic. This logic produces an output when it detects either an
open circuit breaker via auxiliary contacts feeding the opto-inputs or it detects a combination of both
undercurrent and undervoltage on any one phase.
P64x-TM-EN-4.1 249
Chapter 11 - Voltage Protection Functions P64x
250 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
3 OVERVOLTAGE PROTECTION
Overvoltage conditions are generally related to loss of load conditions, whereby the supply voltage increases in
magnitude. This situation would normally be rectified by voltage regulating equipment such as AVRs (Auto Voltage
Regulators) or On Load Tap Changers. However, failure of this equipment to bring the system voltage back within
permitted limits leaves the system with an overvoltage condition which must be cleared.
Note:
During earth fault conditions on a power system there may be an increase in the healthy phase voltages. Ideally, the system
should be designed to withstand such overvoltages for a defined period of time.
The overvoltage stages can be configured either as phase-to-neutral or phase-to-phase voltages in the V>
Measur't Mode cell.
There is no Timer Hold facility for Overvoltage.
Stage 2 can have definite time characteristics only. This is set in the V>2 Status cell.
Outputs are available for single or three-phase conditions via the V> Operate Mode cell for each stage.
P64x-TM-EN-4.1 251
Chapter 11 - Voltage Protection Functions P64x
t
V>1 Voltage Set & V>1 Trip A/ AB
0
t
V>1 Voltage Set & V>1 Trip B/ BC
0
t
V>1 Voltag e Set & V>1 Trip C/CA
0
1
&
V>1 Timer Block 1 V>1 Trip
&
V> Operate mode &
Any Ph ase
Thre e Pha se
Notes: This diagram does n ot show all stage s. Other stage s follo w similar principles.
VTS Fast Block only ap plies f or directiona l mode ls.
V00 804
Figure 115: Overvoltage - single and three phase tripping mode (single stage)
The Overvoltage protection function detects when the voltage magnitude for a certain stage exceeds a set
threshold. If this happens a Start signal, signifying the "Start of protection", is produced. This Start signal can be
blocked by the VTS Fast Block signal. This start signal is applied to the timer module to produce the Trip signal,
which can be blocked by the overvoltage timer block signal (V>(n) Timer Block). For each stage, there are three
Phase overvoltage detection modules, one for each phase. The three Start signals from each of these phases are
OR'd together to create a 3-phase Start signal (V>(n) Start), which can then be activated when any of the three
phases start (Any Phase), or when all three phases start (Three Phase), depending on the chosen V> Operate Mode
setting.
The outputs of the timer modules are the trip signals which are used to drive the tripping output relay. These
tripping signals are also OR'd together to create a 3-phase Trip signal, which are also controlled by the V> Operate
Mode setting.
If any one of the above signals is low, or goes low before the timer has counted out, the timer module is inhibited
(effectively reset) until the blocking signal goes high.
252 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
This type of protection must be co-ordinated with any other overvoltage devices at other locations on the system.
Transformers can typically withstand a 110% overvoltage condition continuously. The withstand times for higher
overvoltages should be declared by the transformer manufacturer.
To prevent operation during earth faults, the element should operate from the phase-phase voltages. To achieve
this, you set V>1 Measur’t Mode to Phase-Phase and V>1 Operating Mode set to Three-phase. You should
typically set the overvoltage threshold V>1 Voltage Set to 100% - 120% of the nominal phase‑phase voltage. You
should also set the time delay to prevent unwanted tripping of the delayed overvoltage protection function due to
transient over voltages, which do not pose a risk to the transformer. A typical delay setting would be 1 s - 3 s, with
a longer delay being applied for lower voltage threshold settings.
The second stage can be used to provide instantaneous high-set over voltage protection. The typical threshold
setting to be applied, V>2 Voltage Set, would typically be 130 - 150% of the nominal phase‑phase voltage. For
instantaneous operation, you should set the time delay to 0 s.
If you select phase-to-neutral operation, take care to ensure that the element will grade with other protections
during earth faults, where the phase-neutral voltage can rise significantly.
This type of protection must be coordinated with any other overvoltage devices at other locations on the system.
P64x-TM-EN-4.1 253
Chapter 11 - Voltage Protection Functions P64x
254 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
804
VN>1 Start
VN
VN>1 Voltage Set & 700
& IDMT/DT VN>1 Trip
832
VTS Fast Block
418
VN>1 Timer Blk
V00802
The Residual Overvoltage module (VN>) is a level detector that detects when the voltage magnitude exceeds a set
threshold, for each stage. When this happens, the comparator output produces a Start signal (VN>(n) Start), which
signifies the "Start of protection". This can be blocked by a VTS Fast block signal. This Start signal is applied to the
timer module. The output of the timer module is the VN> (n) Trip signal which is used to drive the tripping output
relay.
P64x-TM-EN-4.1 255
Chapter 11 - Voltage Protection Functions P64x
E S IED F
ZS ZL
VA
VA
VC VB VC VB VC VB
VA VRES
VRES
VA
VB VB VB
VC VC VC
VRES = ZS0
X3E
2ZS1 + ZS0 + 2ZL1 + ZL0
E00800
As can be seen from the above diagram, the residual voltage measured on a solidly earthed system is solely
dependent on the ratio of source impedance behind the protection to the line impedance in front of the protection,
up to the point of fault. For a remote fault far away, the ZS/ZL: ratio will be small, resulting in a correspondingly
small residual voltage. Therefore, the protection only operates for faults up to a certain distance along the system.
The maximum distance depends on the device setting.
256 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
E S IED F
ZS ZL
N
ZE
VA - G
S R VA - G
G,F G,F
G,F
VC - G VC - G VC - G
VB - G VB - G VB - G
VB - G VB - G VB - G
VA - G VA - G
VC - G VC - G VC - G
ZS0 + 3ZE
VRES = X3E
2ZS1 + ZS0 + 2ZL1 + ZL0 + 3Z
E
E00801
An impedance earthed system will always generate a relatively large degree of residual voltage, as the zero
sequence source impedance now includes the earthing impedance. It follows then that the residual voltage
generated by an earth fault on an insulated system will be the highest possible value (3 x phase-neutral voltage),
as the zero sequence source impedance is infinite.
P64x-TM-EN-4.1 257
Chapter 11 - Voltage Protection Functions P64x
V2> Start
V2
Start
V2> Voltage Set & & DT V2> Trip
Counter
V2> Accelerate
V00805
The Negative Voltage Sequence Overvoltage module (V2>) is a level detector that detects when the voltage
magnitude exceeds a set threshold. When this happens, the comparator output Overvoltage Module produces a
Start signal (V2> Start), which signifies the "Start of protection". This can be blocked by a VTS Fast block signal.
This Start signal is applied to the DT timer module. The output of the DT timer module is the V2> Trip signal which
is used to drive the tripping output relay.
The V2> Accelerate signal accelerates the operating time of the function, by reducing the number of confirmation
cycles needed to start the function. At 50 Hz, this means the protection Start is reduced by 20 ms.
258 P64x-TM-EN-4.1
P64x Chapter 11 - Voltage Protection Functions
Note:
Standing levels of NPS voltage (V2) are displayed in the V2 Magnitude cell of the MEASUREMENTS 1 column.
The operation time of the element depends on the application, but a typical setting would be in the region of 5
seconds.
P64x-TM-EN-4.1 259
Chapter 11 - Voltage Protection Functions P64x
260 P64x-TM-EN-4.1
CHAPTER 12
262 P64x-TM-EN-4.1
P64x Chapter 12 - Frequency Protection Functions
1 CHAPTER OVERVIEW
The device provides a range of frequency protection functions. This chapter describes the operation of these
functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 263
Overfluxing Protection 264
Frequency Protection 270
P64x-TM-EN-4.1 263
Chapter 12 - Frequency Protection Functions P64x
2 OVERFLUXING PROTECTION
If a power transformer is connected to an active load such as a generator, it is possible that the ratio of voltage to
frequency exceeds certain limits. This will result in Overfluxing, sometimes known as overexcitation. An excessively
high voltage or excessively low frequency causes the V/f ratio to rise, producing high flux densities in the magnetic
core of the transformer. Overfluxing causes the transformer core to saturate resulting in stray flux in non-
laminated components not designed to carry flux. This in turn causes eddy currents in solid components (e.g. core
bolts and clamps) and end-of-core laminations causing rapid overheating and damage. Transformer
manufacturers provide information about the V/f capability as a function of time. The limit is either in the form of a
curve or a set-point with a time delay.
Transformer overfluxing might arise for the following reasons:
● High system voltage
● Generator full load rejection
● Increased voltage due to light loading of transmission lines (Ferranti effect)
● Low system frequency
● Generator excitation at low speed with Automatic Voltage Regulator (AVR) in service
● Geomagnetic disturbance (effects of solar radiation)
● Low frequency earth current circulation through a transmission system
The initial effect of overfluxing is to increase the magnetising current for a transformer. This current will be seen as
a differential current, which could cause the device to maloperate, therefore some sort of restraint is needed. The
fifth harmonic component of the current is used to block the differential element during mild or short term
overfluxing conditions.
Persistent overfluxing however, may result in thermal damage or degradation of a transformer as a result of
overheating.
The following protection strategy is therefore advisable to address potential overfluxing conditions:
● Maintain protection stability during transient overfluxing by blocking the differential protection
● Ensure tripping for persistent overfluxing by applying the overfluxing protection. It is common practice to
use the overfluxing element to protect the transformer during system disturbance, especially on large
network transformers.
264 P64x-TM-EN-4.1
P64x Chapter 12 - Frequency Protection Functions
In addition to tripping stages 1 to 4, an Alarm stage is also provided (V/Hz> Alm) for each of the elements. This can
be used to indicate an unhealthy condition.
10000
t=TMS/(M-1) 2
1000
operating time (s)
100
TMS = 12
TMS = 8
10 TMS= 4
TMS = 2
TMS = 1
1
1.05 1.15 1.25 1.35 1.45 1.55
V00864 M = (V/f)/Setting
The IDMT characteristic is implemented as a thermal function. The internal IDMT timer is treated as a thermal
replica with a cooling characteristic. After a V/Hz excursion, the timer should reset according to the reset cooling
characteristic. Otherwise, if the unit is subjected to another V/Hz excursion before it has cooled to normal
condition, damage could occur before the V/Hz trip point is reached.
A linear reset curve with a Reset Time (V/Hz>x tReset) setting is used for this purpose. The actual reset time left is:
Reset time = tReset * IDMTtimer/tTarget
P64x-TM-EN-4.1 265
Chapter 12 - Frequency Protection Functions P64x
To make use of the time delayed overfluxing protection, the device must be supplied with a voltage signal which is
representative of the primary system voltage on the source side of the transformer. This is defined by the Ref
Voltage setting in the OVERFLUXING column.
The following diagram explains the reset characteristic. It will take tReset time for the thermal replica to reset
completely to zero after it has reached 100% of V/f>1 trip at stage 1. If the thermal replica has not reached 100%
of V/f>1 Trip, the reset time will be reduced proportionally. For example, if the reset time is set to 100 seconds, and
the thermal replica has only reached 50% of V/f> Trip when V/Hz resets, the reset time will be 50 seconds as
shown in stage 2. If another V/Hz excursion appears before the first reset reaches V/f Reset, the V/Hz time delay
takes the reset time left into consideration, as shown in stage 3.
V/f>1 Reset
tReset
V/f in p.u.
V00868
V00863
266 P64x-TM-EN-4.1
P64x Chapter 12 - Frequency Protection Functions
V/f
DT
V/Hz Alarm Set & 3Ph V/Hz> Alarm
Note: The diagram is for a 3 -phase VT. The logic for a 1 -phase VT is the same.
This diagram does not show all stages. Other stages follow similar principles.
V00867
P64x-TM-EN-4.1 267
Chapter 12 - Frequency Protection Functions P64x
where:
● The VT secondary voltage at rated primary volts is 110 V
● The rated frequency is 50 Hz
You should set the overfluxing alarm stage threshold V/Hz Alarm Set, lower than the trip stage setting, to provide
an indication that abnormal conditions are present and to alert an operator to adjust system parameters
accordingly.
You should choose the time delay settings to match the withstand characteristics of the protected transformer. For
an inverse time characteristic, set the time multiplier setting, V/Hz>1 Trip TMS such that the operating
characteristic closely matches the withstand characteristic of transformer. For definite time trip stages, set the
time delay V/Hz>(n) Trip Delay cells. The alarm stage time delay is set in the V/Hz Alarm Delay cell.
You can use PSL to combine the stages to create a multi-stage V/Hz trip operating characteristic, as shown below:
Note:
Consult the manufacturers’ withstand characteristics before formulating these settings.
V/Hz>1
V/Hz>4
V/Hz(%)
V/Hz>3
V/Hz>2
Multi-
Characteristic
V00865 V/Hz(%)
268 P64x-TM-EN-4.1
P64x Chapter 12 - Frequency Protection Functions
V/Hz>2 Trip
V/Hz>3 Trip
1 R14 V/Hz Trip
E00866
P64x-TM-EN-4.1 269
Chapter 12 - Frequency Protection Functions P64x
3 FREQUENCY PROTECTION
Power generation and utilisation needs to be well balanced in any industrial, distribution or transmission network.
These electrical networks are dynamic entities, with continually varying loads and supplies, which are continually
affecting the system frequency. Increased loading reduces the system frequency and generation needs to be
increased to maintain the frequency of the supply. Conversely decreased loading increases the system frequency
and generation needs to be reduced. Sudden fluctuations in load can cause rapid changes in frequency, which
need to be dealt with quickly.
Unless corrective measures are taken at the appropriate time, frequency decay can go beyond the point of no
return and cause widespread network collapse, which has dire consequences.
Normally, generators are rated for a particular band of frequency. Operation outside this band can cause
mechanical damage to the turbine blades. Protection against such contingencies is required when frequency does
not improve even after load shedding steps have been taken. This type of protection can be used for operator
alarms or turbine trips in case of severe frequency decay.
Clearly a range of methods is required to ensure system frequency stability. The frequency protection in this device
provides both underfrequency and overfrequency protection.
Frequency Protection is implemented in the FREQ PROTECTION column of the relevant settings group.
270 P64x-TM-EN-4.1
P64x Chapter 12 - Frequency Protection Functions
Freq 1155
Averaging F<1 Start
DT
1161
F<1 Setting & F<1 Trip
F<1 Status
Enabled
890
All Poles Dead
1
Freq Not Found 1370
1149
F<1 Timer Block
V00861
If the frequency is below the setting and not blocked the DT timer is started. If the frequency cannot be
determined, the function is blocked.
P64x-TM-EN-4.1 271
Chapter 12 - Frequency Protection Functions P64x
1159
Freq Averaging F>1 Start
DT
1165
F>1 Setting & F>1 Trip
F>1 Status
Enabled
890
All Poles Dead
1
Freq Not Found 1370
1153
F>1 Timer Block
V00862
If the frequency is above the setting and not blocked, the DT timer is started and after this has timed out, the trip is
produced. If the frequency cannot be determined, the function is blocked.
272 P64x-TM-EN-4.1
CHAPTER 13
274 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
1 CHAPTER OVERVIEW
As well as providing a range of protection functions, the product includes comprehensive monitoring and control
functionality.
This chapter contains the following sections:
Chapter Overview 275
Event Records 276
Disturbance Recorder 283
Measurements 284
Current Input Exclusion Function 286
Circuit Breaker Control 288
Pole Dead Function 293
P64x-TM-EN-4.1 275
Chapter 13 - Monitoring and Control P64x
2 EVENT RECORDS
General Electric devices record events in an event log. This allows you to establish the sequence of events that led
up to a particular situation. For example, a change in a digital input signal or protection element output signal
would cause an event record to be created and stored in the event log. This could be used to analyse how a
particular power system condition was caused. These events are stored in the IED's non-volatile memory. Each
event is time tagged.
The event records can be displayed on an IED's front panel but it is easier to view them through the settings
application software. This can extract the events log from the device and store it as a single .evt file for analysis on
a PC.
The event records are detailed in the VIEW RECORDS column. The first event (0) is always the latest event. After
selecting the required event, you can scroll through the menus to obtain further details.
If viewing the event with the settings application software, simply open the extracted event file. All the events are
displayed chronologically. Each event is summarised with a time stamp (obtained from the Time & Date cell) and a
short description relating to the event (obtained from the Event Text cell. You can expand the details of the event
by clicking on the + icon to the left of the time stamp.
The following table shows the correlation between the fields in the setting application software's event viewer and
the cells in the menu database.
Field in Event Viewer Equivalent cell in menu DB Cell reference User settable?
Left hand column header VIEW RECORDS ® Time & Date 01 03 No
Right hand column header VIEW RECORDS ® Event Text 01 04 No
Description SYSTEM DATA ® Description 00 04 Yes
Plant reference SYSTEM DATA ® Plant Reference 00 05 Yes
Model number SYSTEM DATA ® Model Number 00 06 No
Address Displays the Courier address relating to the event N/A No
Event type VIEW RECORDS ® Menu Cell Ref 01 02 No
Event Value VIEW RECORDS ® Event Value 01 05 No
Evt Unique Id VIEW RECORDS ® Evt Unique ID 01 FE No
The Select Event setting allows access to individual event records, with the latest event stored at position 0. This
setting also defines the maximum number of records available.
In addition to the event log, there are two logs which contain duplicates of the last 5 maintenance records and the
last 5 fault records. The purpose of this is to provide convenient access to the most recent fault and maintenance
events.
276 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
Standard events are further sub-categorised internally to include different pieces of information. These are:
● Protection events (starts and trips)
● Maintenance record events
● Platform events
Note:
The first event in the list (event 0) is the most recent event to have occurred.
P64x-TM-EN-4.1 277
Chapter 13 - Monitoring and Control P64x
Alarm Status 1
Bit no. Bit Mask (hex) Alarm Description
0 0x00000001 Not Used
1 0x00000002 Not Used
2 0x00000004 Setting Group selection by DDB inputs invalid
3 0x00000008 CB Status Alarm
4 0x00000010 RTD Thermal Alarm
5 0x00000020 RTD Open Circuit Failure
6 0x00000040 RTD Short Circuit Failure
7 0x00000080 RTD Data Inconsistency Error
8 0x00000100 RTD Board Failure
9 0x00000200 Current Loop Input 1 Alarm
10 0x00000400 Current Loop Input 2 Alarm
11 0x00000800 Current Loop Input 3 Alarm
12 0x00001000 Current Loop Input 4 Alarm
13 0x00002000 Current Loop Input 1 Undercurrent Fail Alarm
14 0x00004000 Current Loop Input 2 Undercurrent Fail Alarm
15 0x00008000 Current Loop Input 3 Undercurrent Fail Alarm
16 0x00010000 Current Loop Input 4 Undercurrent Fail Alarm
17 0x00020000 Out of Service Alarm
18 0x00040000 Frequency Out of Range Alarm
19 0x00080000 UNUSED
20 0x00100000 UNUSED
21 0x00200000 UNUSED
22 0x00400000 Current Loop Input Failure
23 0x00800000 Current Loop Input Output Failure
24 0x01000000 VCO1 Configuration Alarm
25 0x02000000 VCO2 Configuration Alarm
26 0x04000000 UNUSED
27 0x08000000 CTS Fail Alarm
28 0x10000000 Circuitry FLT Alm
29 0x20000000 VTS VT Fail Alarm
30 0x40000000 Thermal Pre-trip Alarm
31 0x80000000 Aging Acceleration Factor (FAA) alarm
Alarm Status 2
Bit no. Bit Mask (hex) Alarm Description
0 0x00000001 LOL alarm
1 0x00000002 Breaker Fail Any Trip
2 0x00000004 CB Fail Alarm T1
3 0x00000008 CB Fail Alarm T2
4 0x00000010 CB Fail Alarm T3
5 0x00000020 CB Fail Alarm T4
6 0x00000040 CB Fail Alarm T5
278 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
Alarm Status 3
Bit no. Bit Mask (hex) Alarm Description
0 0x00000001 Battery Fail alarm indication
1 0x00000002 Failure
2 0x00000004 unused
3 0x00000008 Enrolled GOOSE IED absent alarm indication
4 0x00000010 Network Interface Card not fitted/failed alarm
5 0x00000020 Network Interface Card not responding alarm
6 0x00000040 Network Interface Card fatal error alarm indication
7 0x00000080 Network Interface Card software reload alarm
8 0x00000100 Bad TCP/IP Configuration Alarm
9 0x00000200 Bad OSI Configuration Alarm
10 0x00000400 Network Interface Card link fail alarm indication
11 0x00000800 Main card/NIC software mismatch alarm indication
12 0x00001000 IP address conflict alarm indication
13 0x00002000 unused
14 0x00004000 unused
P64x-TM-EN-4.1 279
Chapter 13 - Monitoring and Control P64x
Alarm Status 4
Bit no. Bit Mask (hex) Alarm Description
0 0x00000001 User Alarm 1 (0=Self-reset, 1=Manual reset)
1 0x00000002 User Alarm 2 (0=Self-reset, 1=Manual reset)
2 0x00000004 User Alarm 3 (0=Self-reset, 1=Manual reset)
3 0x00000008 User Alarm 4 (0=Self-reset, 1=Manual reset)
4 0x00000010 User Alarm 5 (0=Self-reset, 1=Manual reset)
5 0x00000020 User Alarm 6 (0=Self-reset, 1=Manual reset)
6 0x00000040 User Alarm 7 (0=Self-reset, 1=Manual reset)
7 0x00000080 User Alarm 8 (0=Self-reset, 1=Manual reset)
8 0x00000100 User Alarm 9 (0=Self-reset, 1=Manual reset)
9 0x00000200 User Alarm 10 (0=Self-reset, 1=Manual reset)
10 0x00000400 User Alarm 11 (0=Self-reset, 1=Manual reset)
11 0x00000800 User Alarm 12 (0=Self-reset, 1=Manual reset)
12 0x00001000 User Alarm 13 (0=Self-reset, 1=Manual reset)
13 0x00002000 User Alarm 14 (0=Self-reset, 1=Manual reset)
14 0x00004000 User Alarm 15 (0=Self-reset, 1=Manual reset)
15 0x00008000 User Alarm 16 (0=Self-reset, 1=Manual reset)
16 0x00010000 User Alarm 17 (0=Self-reset, 1=Manual reset)
17 0x00020000 User Alarm 18 (0=Self-reset, 1=Manual reset)
18 0x00040000 User Alarm 19 (0=Self-reset, 1=Manual reset)
19 0x00080000 User Alarm 20 (0=Self-reset, 1=Manual reset)
20 0x00100000 User Alarm 21 (0=Self-reset, 1=Manual reset)
21 0x00200000 User Alarm 22 (0=Self-reset, 1=Manual reset)
22 0x00400000 User Alarm 23 (0=Self-reset, 1=Manual reset)
280 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
V01234
The event is logged as soon as the fault recorder stops. The time stamp assigned to the fault corresponds to the
start of the fault. The timestamp assigned to the fault record event corresponds to the time when the fault
recorder stops.
Note:
We recommend that you do not set the triggering contact to latching. This is because if you use a latching contact, the fault
record would not be generated until the contact has been fully reset.
P64x-TM-EN-4.1 281
Chapter 13 - Monitoring and Control P64x
The IED contains a separate register containing the latest maintenance records. This provides a convenient way of
viewing the latest maintenance records and saves searching through the event log. You access these fault records
using the Select Maint setting.
The maintenance record has a number of extra menu cells relating to the maintenance event. These parameters
are Maint Text, Maint Type and Maint Data. They contain details about the maintenance event selected with the
Select Maint cell.
282 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
3 DISTURBANCE RECORDER
The disturbance recorder feature allows you to record selected current and voltage inputs to the protection
elements, together with selected digital signals. The digital signals may be inputs, outputs, or internal DDB signals.
The disturbance records can be extracted using the disturbance record viewer in the settings application software.
The disturbance record file can also be stored in the COMTRADE format. This allows the use of other packages to
view the recorded data.
The integral disturbance recorder has an area of memory specifically set aside for storing disturbance records. The
number of records that can be stored is dependent on the recording duration. The minimum duration is 0.1 s and
the maximum duration is 10.5 s.
When the available memory is exhausted, the oldest records are overwritten by the newest ones.
Each disturbance record consists of a number of analogue data channels and digital data channels. The relevant
CT and VT ratios for the analogue channels are also extracted to enable scaling to primary quantities.
The fault recording times are set by a combination of the Duration and Trigger Position cells. The Duration cell
sets the overall recording time and the Trigger Position cell sets the trigger point as a percentage of the duration.
For example, the default settings show that the overall recording time is set to 1.5 s with the trigger point being at
33.3% of this, giving 0.5 s pre-fault and 1 s post fault recording times.
With the Trigger Mode set to Single, if further triggers occurs whilst a recording is taking place, the recorder will
ignore the trigger. However, with the Trigger Mode set to Extended, the post trigger timer will be reset to zero,
extending the recording time.
You can select any of the IED's analogue inputs as analogue channels to be recorded. You can also map any of the
opto-inputs output contacts to the digital channels. In addition, you may also map a number of DDB signals such
as Starts and LEDs to digital channels.
You may choose any of the digital channels to trigger the disturbance recorder on either a low to high or a high to
low transition, via the Input Trigger cell. The default settings are such that any dedicated trip output contacts will
trigger the recorder.
It is not possible to view the disturbance records locally via the front panel LCD. You must extract these using
suitable setting application software such as MiCOM S1 Agile.
P64x-TM-EN-4.1 283
Chapter 13 - Monitoring and Control P64x
4 MEASUREMENTS
284 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
The device also calculates the per-phase and three-phase power factors.
These power values increment the total real and total reactive energy measurements. Separate energy
measurements are maintained for the total exported and imported energy. The energy measurements are
incremented up to maximum values of 1000 GWhr or 1000 GVARhr at which point they reset to zero. It is possible
to reset these values using the menu or remote interfaces using the Reset demand cell.
These measurements are contained in the MEASUREMENTS 2 column.
P64x-TM-EN-4.1 285
Chapter 13 - Monitoring and Control P64x
Note: This diagram doe s not show all stages. Other stag es follow similar principles.
V01231
P643
CT1 Excluded
CT3 Excluded
P645
CT1 Excluded
CT2 Excluded
CT4 Excluded
CT5 Excluded
V01232
Only one current input can be excluded from the P643 and a maximum of three current inputs can be excluded
from the P645. An alarm DDB (Insuff No. of CT) is issued when more than the maximum number of current inputs
are excluded. The status of the exclusion DDB signals (CTx Excluded) is stored in the device's internal non-volatile
memory. An alarm (Disc CT Invalid) is raised if the stored statuses do not match the statuses after the power
supply is re-established. When the Disc CT Invalid DDB signal is asserted, all protection functions using the
relevant CT inputs are blocked.
Note:
For the differential element to operate correctly, the number of CTs used cannot be less than 2. Also CTs should be excluded
one at a time.
286 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
1 CB1 2 CB2
Autotransformer
230/115/13.8 kV
Auxiliary
services
CB4 CB5
V01236
The current transformer associated with CB1 is connected to the T1 CT input. Auxiliary contacts from CB1 isolators
1 and 2 must be connected to an opto-input as follows.
+V DC
98b - 1
Opto input 14 1 CT1 Exclu E na
98b - 2
Opto input 14
-V DC
V01233
When isolators 1 and 2 are open, the opto-input L14 is energized and CT1 Exclu Ena is asserted. To set CT1
Excluded, T1 CT Phase A, B and C undercurrent elements must also be asserted.
P64x-TM-EN-4.1 287
Chapter 13 - Monitoring and Control P64x
Circuit Breaker control is only possible if the circuit breaker in question provides auxiliary contacts. The CB Status
Input cell in the CB CONTROL column must be set to the type of circuit breaker. If no CB auxiliary contacts are
available then this cell should be set to None, and no CB control will be possible.
For local control, the CB control by cell should be set accordingly.
The output contact can be set to operate following a time delay defined by the setting Man Close Delay. One
reason for this delay is to give personnel time to safely move away from the circuit breaker following a CB close
command.
The control close cycle can be cancelled at any time before the output contact operates by any appropriate trip
signal, or by activating the Reset Close Dly DDB signal.
The length of the trip and close control pulses can be set via the Trip Pulse Time and Close Pulse Time settings
respectively. These should be set long enough to ensure the breaker has completed its open or close cycle before
the pulse has elapsed.
If an attempt to close the breaker is being made, and a protection trip signal is generated, the protection trip
command overrides the close command.
If the CB fails to respond to the control command (indicated by no change in the state of CB Status inputs) an
alarm is generated after the relevant trip or close pulses have expired. This alarm can be viewed on the LCD
display, remotely, or can be assigned to an output contact using the programmable scheme logic (PSL).
Note:
The CB Healthy Time set under this menu section is applicable to manual circuit breaker operations only.
The device includes the following options for control of a single circuit breaker:
● The IED menu (local control)
● The Hotkeys (local control)
● The function keys (local control)
● The opto-inputs (local control)
● SCADA communication (remote control)
288 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
CB control using the hotkey is achieved by pressing the right-hand button directly below LCD screen. This button is
only enabled if:
● The CB Control by setting is set to one of the options where local control is possible (option 1,3,5, or 7)
● The CB Status Input is set to '52A', '52B', or 'Both 52A and 52B'
If the CB is currently closed, the command text on the bottom right of the LCD screen will read Trip. Conversely, if
the CB is currently open, the command text will read Close.
If you execute a Trip, a screen with the CB status will be displayed once the command has been completed. If
you execute a Close, a screen with a timing bar will appear while the command is being executed. This screen
also gives you the option to cancel or restart the close procedure. The time delay is determined by the Man Close
Delay setting in the CB CONTROL menu. When the command has been executed, a screen confirming the present
status of the circuit breaker is displayed. You are then prompted to select the next appropriate command or exit.
If no keys are pressed for a period of 5 seconds while waiting for the command confirmation, the device will revert
to showing the CB Status. If no key presses are made for a period of 25 seconds while displaying the CB status
screen, the device will revert to the default screen.
To avoid accidental operation of the trip and close functionality, the hotkey CB control commands are disabled for
10 seconds after exiting the hotkey menu.
The hotkey functionality is summarised graphically below:
Default Display
HOTKEY CB CTRL
Hotkey Menu
CB closed CB open
TRIP EXIT CONFIRM CANCEL EXIT CLOSE CANCEL CONFIRM CANCEL RESTART
E01209
P64x-TM-EN-4.1 289
Chapter 13 - Monitoring and Control P64x
The programmable function key LEDs have been mapped such that they will indicate yellow whilst the keys are
activated.
Note:
Not all models provide function keys.
290 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
Protection Trip
Trip
Remote
Control
Trip Close
Remote
Control
Close
Local
Remote
Trip Close
E01207
P64x-TM-EN-4.1 291
Chapter 13 - Monitoring and Control P64x
&
Init close CB 1 Close in Pro g
Trip Command In 1
1
Ext. Trip 3ph
Control Trip
CB Open 3 ph
CB hea lthy window
CB Closed 3 ph
& Man CB Unhealthy
CB He alt hy
V01290
292 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
It can also be used to block operation of underfrequency and undervoltage elements where applicable.
This is necessary so that a pole dead indication is still given even when an upstream breaker is opened. The
undervoltage and undercurrent thresholds have the following, fixed, pick-up and drop-off levels:
● VA<, VB<, VC<, these level detectors operate on phase voltages and have a fixed setting, Pick-up level = 10 V
(Vn = 100/120 V), 40 V (Vn = 380/480 V), Drop Off level = 30 V (Vn = 100/120 V), 120V (Vn = 380/480 V).
● VAB<, VBC<, these level detectors operate on phase-phase voltages and have a fixed setting, Pick-up level =
70 V (Vn = 100/120 V), Drop Off level = 95 V (Vn = 100/120 V).
● IA<, IB<, IC<, these level operate on phase currents and have a fixed setting, Pick-up level = 0.05 In, Drop Off
level = 0.055 In.
Note:
f the VT is connected at the busbar side, auxiliary contacts (52a or 52b) must be connected to the device for a correct pole
dead indication.
P64x-TM-EN-4.1 293
Chapter 13 - Monitoring and Control P64x
VAB
VCA
Hardcoded threshold
IB
VAB
VCA
Hardcoded threshold
IC
VBC
1 Any Po le Dead
Hardcoded threshold &
VCA
& All Poles Dead
Hardcoded threshold
CB1 Closed
3Ph CB Open
Terminal HV
Selection
Terminal LV
Selection
V01228
294 P64x-TM-EN-4.1
P64x Chapter 13 - Monitoring and Control
IA
VA
Hardcoded threshold
IB
VB
Hardcoded threshold
IC
VC
1 Any Po le Dead
Hardcoded threshold
Terminal HV Terminal TV
Selection Selection
P643: 001 CB1 Closed & 3Ph CB_Open P643: 010 CB2 Closed & 3Ph CB Open
P645: 00001
CB5 Closed
& 3Ph CB Open
P645: 11000 CB4 Closed
V01229
If both the line current and voltage fall below a certain threshold the device will initiate a Pole Dead condition. The
undervoltage (V<) and undercurrent (I<) thresholds are hardcoded internally.
If one or more poles are dead, the device will indicate which phase is dead and will also assert the Any Pole Dead
DDB signal. If all phases are dead the Any Pole Dead signal would be accompanied by the All Poles Dead signal.
If the VT fails, a VTS Slow Block signal is taken from the VTS logic to block the Pole Dead indications that would be
generated by the undervoltage and undercurrent thresholds. However, the VTS logic will not block the Pole Dead
indications if they are initiated by a CBx Closed signal. A CBx closed signal is inverted and automatically initiates a
Pole Dead condition regardless of the current and voltage measurement.
P64x-TM-EN-4.1 295
Chapter 13 - Monitoring and Control P64x
High
Opto Input 7 1 CB1 Closed
V01230
296 P64x-TM-EN-4.1
CHAPTER 14
SUPERVISION
Chapter 14 - Supervision P64x
298 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
1 CHAPTER OVERVIEW
This chapter describes the supervison functions.
This chapter contains the following sections:
Chapter Overview 299
Voltage Transformer Supervision 300
Current Transformer Supervision 305
Trip Circuit Supervision 308
P64x-TM-EN-4.1 299
Chapter 14 - Supervision P64x
The first condition would require VTS to block the voltage-dependent functions.
In the second condition, voltage dependent functions should not be blocked, as tripping is required.
To differentiate between these two conditions overcurrent level detectors are used (VTS I> Inhibit and VTS I2>
Inhibit). These prevent a VTS block from being issued in case of a genuine fault. These elements should be set in
excess of any non-fault based currents on line energisation (load, line charging current, transformer inrush current
if applicable), but below the level of current produced by a close-up three-phase fault.
300 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
If the line is closed where a three-phase VT failure is present, the overcurrent detector will not operate and a VTS
block will be applied. Closing onto a three-phase fault will result in operation of the overcurrent detector and
prevent a VTS block being applied.
P64x-TM-EN-4.1 301
Chapter 14 - Supervision P64x
IA
IB
1
VTS I> Inhibit
IC
VA
Hardcoded threshold
VB
&
Hardcoded threshold 1 & S
Q
VC R 1
& VTS Slow Block
Hardcoded threshold
Delt a IA
Hardcoded threshold
V2
I2
MCB/VTS
VTS Status
Indicat ion
Blocking
1 S 1 VT Fail Alarm
Any Pole Dead & Q
R
&
VTS Acc Ind
V01224 Note: This diagram does not show all stages. Other stages follow similar principles.
302 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
IA
IB
1
VTS I> Inhibit
IC
VAB
Hardcoded threshold
&
VBC 1 & S
Q
R 1
Hardcoded threshold & VTS Slow Block
Delt a IA
Hardcoded threshold
V2
I2
MCB/VTS
VTS Status
Indicat ion
Blocking
1 S 1 VT Fail Alarm
Any Pole Dead & Q
R
&
VTS Acc Ind
V01225 Note: This diagram does not show all stages. Other stages follow similar principles.
Figure 140: VTS logic (P643 and P645 with 3-phase VTs)
For the P643 and P645, a 3-phase VT is used and each of the input voltages VA, VB and VC are with respect to
earth. For the P642, two single-phase VTs are used and the two input voltages VA and VB are phase-to-phase
voltages
P64x-TM-EN-4.1 303
Chapter 14 - Supervision P64x
As can be seen from the diagram, the VTS function is inhibited if:
● An All Poles Dead DDB signal is present
● A phase overcurrent condition exists
● A Negative Phase Sequence current exists
● If the phase current changes over the period of 1 cycle
The NPS voltage and current detection criteria (used for the case when one or two voltage inputs are lost) is
inhibited if an Any Pole Dead signal is present.
304 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
If the I2/I1 ratio is greater than the high set value, CTS I2/I1>2 at all ends, it is almost certainly a genuine fault
condition, thus the CTS will not operate. If this ratio is detected at one end only, one of the following conditions
may be present:
● A CT problem
● A single end fed fault condition
The positive sequence current I1 is used to confirm whether it is a CT problem or not. If I1 is greater than the
setting CTS I1 at all terminals, it must be a CT problem and CTS is allowed to operate. If this condition is detected at
only one end, the device assumes it is caused by either an inrush condition or a single-end fed internal fault. In this
case, CTS operation is blocked.
The CTS status setting under the CT SUPERVISION sub-heading can be set to either indication or
restraint. In indication mode, the CTS alarm time delay is automatically set to zero. If a CT failure is present, an
alarm would be issued without delay, but the differential protection would remain unrestricted. In restraint mode,
the differential protection is blocked for 20 ms after CT failure has been detected, after which the restraint region
of the bias characteristic increases according to the setting Is-CTS , which has been defined in the DIFF
PROTECTION column.
Idiff/In
Operating region K2
Is-CTS
K1
Is1
Restraint region
The low impedance REF, earth fault and NPS overcurrent protection functions are internally blocked by CTS when a
CT failure is detected in the relevant CT. However, earth fault protection is immune to CTS blocking if IN> input is
set to measured.
P64x-TM-EN-4.1 305
Chapter 14 - Supervision P64x
The CTS monitors the positive and negative sequence currents of all CTs (2 to 5, depending on the model). A faulty
CT is determined if the following conditions are present at the same time:
● The positive sequence current in at least two current inputs exceeds the set release threshold I1 (CTS I1
setting under the SUPERVISON column). This also means that CTS can only operate if minimum load current
of the protected object is present.
● A high set ratio of negative to positive sequence current, CTS I2/I1>2, is exceeded at one end.
● At all other ends the ratio of negative to positive sequence current is less than a low set value, CTS I2/I1> 1,
or no significant current is present (positive sequence current is below the release threshold I1).
Only a single or double phase CT failure can be detected by this logic. The probability of symmetrical three-phase
CT failures is very low, therefore in practice this is not a significant problem.
Inhibit CTS 1
1
Inrush detector & CTS Blk
CT Exclusion Alarm
1
CTS Status
Indication
Restrain
V01227
306 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
1 2
I1 = ( I A + aI B + a 2 I C ) =
3 3
1 1
I1 = ( I A + a 2 I B + aI C ) =
3 3
The ratio of negative to positive sequence current is 50%, therefore a typical setting of 40% might be used.
The low set ratio of negative to positive sequence current, CTS I2/I1>1, should be set above the maximum load
unbalance. In practise, the levels of standing negative phase sequence current present on the system govern this
minimum setting. This can be determined from a system study, or by making use of the device's measurement
facilities at the commissioning stage. If the latter method is adopted, it is important to take the measurements
during maximum system load conditions, to ensure that all single-phase loads are accounted for. A 20% setting
might be used.
If the following information is recorded by the relay during commissioning:
I full load = 500 A
I2 = 50 A
Therefore I2/I1 ratio is given by I2/I1 = 50/500 = 0.1
To allow for tolerances and load variations a setting of 20% of this value may be typical. Therefore set CTS I2/I1>1
= 20%.
Due to the sensitive settings suggested above, a long time delay is necessary to ensure a true CT failure. We
recommend using the default setting for this time time delay. After the CTS Time Delay expires (CTS Time Delay),
the CTS Fail Alarm is asserted.
P64x-TM-EN-4.1 307
Chapter 14 - Supervision P64x
Note:
A 52a CB auxiliary contact follows the CB position. A 52b auxiliary contact is the opposite.
+ve
Blocking diode
52B
When the CB is closed, supervision current passes through the opto-input, blocking diode and trip coil. When the
CB is open, supervision current flows through the opto-input and into the trip coil via the 52b auxiliary contact.
This means that Trip Coil supervision is provided when the CB is either closed or open, however Trip Path
supervision is only provided when the CB is closed. No supervision of the trip path is provided whilst the CB is open
(pre-closing supervision). Any fault in the trip path will only be detected on CB closing, after a 400 ms delay.
308 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
Trip Circuit Voltage Opto Voltage Setting with R1 Fitted Resistor R1 (ohms)
110/125 48/54 2.7k
220/250 110/125 5.2k
Warning:
This Scheme is not compatible with Trip Circuit voltages of less than 48 V.
0 0
Opto Input dropoff Straight *Output Relay
400 0
50
& pickup Latching LED
0
User Alarm
The opto-input can be used to drive a Normally Closed Output Relay, which in turn can be used to drive alarm
equipment. The signal can also be inverted to drive a latching programmable LED and a user alarm DDB signal.
The DDO timer operates as soon as the opto-input is energised, but will take 400 ms to drop off/reset in the event
of a trip circuit failure. The 400 ms delay prevents a false alarm due to voltage dips caused by faults in other
circuits or during normal tripping operation when the opto-input is shorted by a self-reset trip contact. When the
timer is operated the NC (normally closed) output relay opens and the LED and user alarms are reset.
The 50 ms delay on pick-up timer prevents false LED and user alarm indications during the power up time,
following a voltage supply interruption.
+ve
52B
R1 Opto-input 1
Circuit Breaker
-ve
R2 Opto-input 2
V01215
P64x-TM-EN-4.1 309
Chapter 14 - Supervision P64x
When the breaker is closed, supervision current passes through opto input 1 and the trip coil. When the breaker is
open current flows through opto input 2 and the trip coil. No supervision of the trip path is provided whilst the
breaker is open. Any fault in the trip path will only be detected on CB closing, after a 400 ms delay.
Warning:
This Scheme is not compatible with Trip Circuit voltages of less than 48 V.
0 0
1 dropoff straight *Output Relay
400 0
50
& pickup Latching LED
0
User Alarm
In TCS scheme 2, both opto-inputs must be low before a trip circuit fail alarm is given.
+ve
R3
Output Relay Trip coil
Trip path 52A
R2
52B
When the CB is closed, supervision current passes through the opto-input, resistor R2 and the trip coil. When the
CB is open, current flows through the opto-input, resistors R1 and R2 (in parallel), resistor R3 and the trip coil. The
310 P64x-TM-EN-4.1
P64x Chapter 14 - Supervision
supervision current is maintained through the trip path with the breaker in either state, therefore providing pre-
closing supervision.
Warning:
This Scheme is not compatible with Trip Circuit voltages of less than 48 V.
0 0
Opto Input dropoff Straight *Output Relay
400 0
50
& pickup Latching LED
0
User Alarm
P64x-TM-EN-4.1 311
Chapter 14 - Supervision P64x
312 P64x-TM-EN-4.1
CHAPTER 15
314 P64x-TM-EN-4.1
P64x Chapter 15 - Digital I/O and PSL Configuration
1 CHAPTER OVERVIEW
This chapter introduces the PSL (Programmable Scheme Logic) Editor, and describes the configuration of the digital
inputs and outputs. It provides an outline of scheme logic concepts and the PSL Editor. This is followed by details
about allocation of the digital inputs and outputs, which require the use of the PSL Editor. A separate "Settings
Application Software" document is available that gives a comprehensive description of the PSL, but enough
information is provided in this chapter to allow you to allocate the principal digital inputs and outputs.
This chapter contains the following sections:
Chapter Overview 315
Configuring Digital Inputs and Outputs 316
Scheme Logic 317
Configuring the Opto-Inputs 319
Assigning the Output Relays 320
Fixed Function LEDs 321
Configuring Programmable LEDs 322
Function Keys 324
Control Inputs 325
P64x-TM-EN-4.1 315
Chapter 15 - Digital I/O and PSL Configuration P64x
316 P64x-TM-EN-4.1
P64x Chapter 15 - Digital I/O and PSL Configuration
3 SCHEME LOGIC
The product is supplied with pre-loaded Fixed Scheme Logic (FSL) and Programmable Scheme Logic (PSL).
The Scheme Logic is a functional module within the IED, through which all mapping of inputs to outputs is handled.
The scheme logic can be split into two parts; the Fixed Scheme Logic (FSL) and the Programmable Scheme Logic
(PSL). It is built around a concept called the digital data bus (DDB). The DDB encompasses all of the digital signals
(DDBs) which are used in the FSL and PSL. The DDBs included digital inputs, outputs, and internal signals.
The FSL is logic that has been hard-coded in the product. It is fundamental to correct interaction between various
protection and/or control elements. It is fixed and cannot be changed.
The PSL gives you a facility to develop custom schemes to suit your application if the factory-programmed default
PSL schemes do not meet your needs. Default PSL schemes are programmed before the product leaves the
factory. These default PSL schemes have been designed to suit typical applications and if these schemes suit your
requirements, you do not need to take any action. However, if you want to change the input-output mappings, or
to implement custom scheme logic, you can change these, or create new PSL schemes using the PSL editor.
The PSL consists of components such as logic gates and timers, which combine and condition DDB signals.
The logic gates can be programmed to perform a range of different logic functions. The number of inputs to a logic
gate are not limited. The timers can be used either to create a programmable delay or to condition the logic
outputs. Output contacts and programmable LEDs have dedicated conditioners.
The PSL logic is event driven. Only the part of the PSL logic that is affected by the particular input change that has
occurred is processed. This minimises the amount of processing time used by the PSL ensuring industry leading
performance.
The following diagram shows how the scheme logic interacts with the rest of the IED.
Goose inputs
V02011
P64x-TM-EN-4.1 317
Chapter 15 - Digital I/O and PSL Configuration P64x
Example:
Date/time: This cell displays the date and time when the PSL scheme was downloaded to the IED.
Example:
18 Nov 2002
08:59:32.047
Grp(n) PSL ID: This cell displays a unique ID number for the downloaded PSL scheme.
Example:
Grp(n) PSL ID
ID - 2062813232
318 P64x-TM-EN-4.1
P64x Chapter 15 - Digital I/O and PSL Configuration
P64x-TM-EN-4.1 319
Chapter 15 - Digital I/O and PSL Configuration P64x
Note:
Contact Conditioners are only available if they have not all been used. In some default PSL schemes, all Contact Conditioners
might have been used. If that is the case, and you want to use them for something else, you will need to re-assign them.
On the toolbar there is another button associated with the relay outputs. The button looks like this:
This is the "Contact Signal" button. It allows you to put replica instances of a conditioned output relay into the PSL,
preventing you having to make cross-page connections which might detract from the clarity of the scheme.
320 P64x-TM-EN-4.1
P64x Chapter 15 - Digital I/O and PSL Configuration
You enable the automatic self-resetting with the Sys Fn Links cell in the SYSTEM DATA column. A '0' disables self
resetting and a '1' enables self resetting.
The reset occurs when the circuit is reclosed and the Any Pole Dead signal has been reset for three seconds
providing the Any Start signal is inactive. The reset is prevented if the Any Start signal is active after the breaker
closes.
The Trip LED logic is as follows:
Any Trip S
Q Trip LED Trigger
Reset R
1
Reset Relays/LED
Sys Fn Links
Trip LED S/Reset
3s
&
Any Start
V01211
P64x-TM-EN-4.1 321
Chapter 15 - Digital I/O and PSL Configuration P64x
DDB signals are mapped in the PSL and used to illuminate the LEDs. For single-coloured programmable LEDs there
is one DDB signal per LED. For tri-coloured LEDs there are two DDB signals associated with the LED. Asserting LED
# Grn will illuminate the LED green. Asserting LED # Red will illuminate the LED red. Asserting both DDB signals will
illuminate the LED amber.
The illumination of an LED is controlled by means of a conditioner. Using the conditioner, you can decide whether
the LEDs reflect the real-time state of the DDB signals, or whether illumination is latched pending user intervention.
To map an LED in the PSL you should use the LED Conditioner button in the toolbar to import it. You then condition
it according to your needs. The output(s) of the conditioner respect the attribute you have assigned.
The toolbar button for a tri-colour LED looks like this:
Note:
LED Conditioners are only available if they have not all been used up, and in some default PSL schemes they might be. If that
is the case and you want to use them for something else, you will need to re-assign them.
On the toolbar there is another button associated with the LEDs. For a tri-coloured LED the button looks like this:
It is the "LED Signal" button. It allows you to put replica instances of a conditioned LED into the PSL, preventing you
having to make cross-page connections which might detract from the clarity of the scheme.
322 P64x-TM-EN-4.1
P64x Chapter 15 - Digital I/O and PSL Configuration
Note:
All LED DDB signals are always shown in the PSL Editor. However, the actual number of LEDs depends on the device
hardware. For example, if a small 20TE device has only 4 programmable LEDs, LEDs 5-8 will not take effect even if they are
mapped in the PSL.
P64x-TM-EN-4.1 323
Chapter 15 - Digital I/O and PSL Configuration P64x
8 FUNCTION KEYS
For most models, a number of programmable function keys are available. This allows you to assign function keys
to control functionality via the programmable scheme logic (PSL). Each function key is associated with a
programmable tri-colour LED, which you can program to give the desired indication on activation of the function
key.
These function keys can be used to trigger any function that they are connected to as part of the PSL. The function
key commands are found in the FUNCTION KEYS column.
Each function key is associated with a DDB signal as shown in the DDB table. You can map these DDB signals to
any function available in the PSL.
The Fn Key Status cell displays the status (energised or de-energised) of the function keys by means of a binary
string, where each bit represents a function key starting with bit 0 for function key 1.
Each function key has three settings associated with it, as shown:
● Fn Key (n), which enables or disables the function key
● Fn Key (n) Mode, which allows you to configure the key as toggled or normal
● Fn Key (n) label, which allows you to define the function key text that is displayed
The Fn Key (n) cell is used to enable (unlock) or disable (unlock) the function key signals in PSL. The Lock setting has
been provided to prevent further activation on subsequent key presses. This allows function keys that are set to
Toggled mode and their DDB signal active ‘high’, to be locked in their active state therefore preventing any
further key presses from deactivating the associated function. Locking a function key that is set to the “Normal”
mode causes the associated DDB signals to be permanently off. This safety feature prevents any inadvertent
function key presses from activating or deactivating critical functions.
When the Fn Key (n) Mode cell is set to Toggle, the function key DDB signal output will remain in the set state
until a reset command is given. In the Normal mode, the function key DDB signal will remain energised for as long
as the function key is pressed and will then reset automatically. In this mode, a minimum pulse duration can be
programmed by adding a minimum pulse timer to the function key DDB output signal.
The Fn Key Label cell makes it possible to change the text associated with each individual function key. This text
will be displayed when a function key is accessed in the function key menu, or it can be displayed in the PSL.
The status of all function keys are recorded in non-volatile memory. In case of auxiliary supply interruption their
status will be maintained.
Note:
All function key DDB signals are always shown in the PSL Editor. However, the actual number of function keys depends on the
device hardware. For example, if a small 20TE device has no function keys, the function key DDBs mapped in the PSL will not
take effect.
324 P64x-TM-EN-4.1
P64x Chapter 15 - Digital I/O and PSL Configuration
9 CONTROL INPUTS
The control inputs are software switches, which can be set or reset locally or remotely. These inputs can be used to
trigger any PSL function to which they are connected. There are three setting columns associated with the control
inputs: CONTROL INPUTS, CTRL I/P CONFIG and CTRL I/P LABELS. These are listed in the Settings and Records
appendix at the end of this manual.
P64x-TM-EN-4.1 325
Chapter 15 - Digital I/O and PSL Configuration P64x
326 P64x-TM-EN-4.1
CHAPTER 16
COMMUNICATIONS
Chapter 16 - Communications P64x
328 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
1 CHAPTER OVERVIEW
This product supports Substation Automation System (SAS), and Supervisory Control and Data Acquisition (SCADA)
communication. The support embraces the evolution of communications technologies that have taken place since
microprocessor technologies were introduced into protection, control, and monitoring devices which are now
ubiquitously known as Intelligent Electronic Devices for the substation (IEDs).
As standard, all products support rugged serial communications for SCADA and SAS applications. By option, any
product can support Ethernet communications for more advanced SCADA and SAS applications.
P64x-TM-EN-4.1 329
Chapter 16 - Communications P64x
2 COMMUNICATION INTERFACES
The products have a number of standard and optional communication interfaces. The standard and optional
hardware and protocols are summarised below:
Port Availability Physical layer Use Data Protocols
Front Standard RS232 Local settings Courier
Rear Port 1 RS232 / RS485 / K- SCADA Courier, MODBUS, IEC60870-5-103, DNP3.0
Standard
(RP1 copper) Bus Remote settings (order option)
Rear Port 1 SCADA Courier, MODBUS, IEC60870-5-103, DNP3.0
Optional Fibre
(RP1 fibre) Remote settings (order option)
Rear Port 2 RS232 / RS485 / K- SCADA SK4: Courier only
Optional
(RP2) Bus Remote settings SK5: InterMicom only
IEC 61850 or DNP3 IEC 61850, Courier (tunnelled) or DNP3.0
Ethernet Optional Ethernet
Remote settings (order option)
Note:
Optional communications boards are always fitted into slot A.
Note:
It is only possible to fit one optional communications board, therefore RP2 and Ethernet communications are mutually
exclusive.
330 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
3 SERIAL COMMUNICATION
The physical layer standards that are used for serial communications for SCADA purposes are:
● EIA(RS)485 (often abbreviated to RS485)
● K-Bus (a proprietary customization of RS485)
EIA(RS)232 is used for local communication with the IED (for transferring settings and downloading firmware
updates).
RS485 is similar to RS232 but for longer distances and it allows daisy-chaining and multi-dropping of IEDs.
K-Bus is a proprietary protocol quite similar to RS485, but it cannot be mixed on the same link as RS485. Unlike
RS485, K-Bus signals applied across two terminals are not polarised.
It is important to note that these are not data protocols. They only describe the physical characteristics required
for two devices to communicate with each other.
For a description of the K-Bus standard see K-Bus (on page332) and General Electric's K-Bus interface guide
reference R6509.
A full description of the RS485 is available in the published standard.
P64x-TM-EN-4.1 331
Chapter 16 - Communications P64x
Note:
Some devices may be able to provide the bus bias, in which case external components would not be required.
6 – 9 V DC
180 Ω bias
Master 120 Ω
180 Ω bias
0V 120 Ω
V01000
Warning:
It is extremely important that the 120 Ω termination resistors are fitted. Otherwise
the bias voltage may be excessive and may damage the devices connected to the
bus.
3.3 K-BUS
K-Bus is a robust signalling method based on RS485 voltage levels. K-Bus incorporates message framing, based on
a 64 kbps synchronous HDLC protocol with FM0 modulation to increase speed and security.
The rear interface is used to provide a permanent connection for K-Bus, which allows multi-drop connection.
A K-Bus spur consists of up to 32 IEDs connected together in a multi-drop arrangement using twisted pair wiring.
The K-Bus twisted pair connection is non-polarised.
It is not possible to use a standard EIA(RS)232 to EIA(RS)485 converter to convert IEC 60870-5 FT1.2 frames to K-
Bus. A protocol converter, namely the KITZ101, KITZ102 or KITZ201, must be used for this purpose. Please consult
General Electric for information regarding the specification and supply of KITZ devices. The following figure
demonstrates a typical K-Bus connection.
332 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
C C C
RS232 K-Bus
Note:
An RS232-USB converter is only needed if the local computer does not provide an RS232 port.
Further information about K-Bus is available in the publication R6509: K-Bus Interface Guide, which is available on
request.
P64x-TM-EN-4.1 333
Chapter 16 - Communications P64x
334 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Note:
The protocol you require must be selected at the time of ordering.
P64x-TM-EN-4.1 335
Chapter 16 - Communications P64x
Devices such as printers that have a single Ethernet port can be connected to either of the networks but will not
directly benefit from the PRP principles. Such devices are called Singly Attached Nodes (SAN). For devices with a
single Ethernet port that need to connect to both LANs, this can be achieved by employing Ethernet Redundancy
Boxes (sometimes abbreviated to RedBox). Devices with a single Ethernet port that connect to both LANs by
means of a RedBox are known as Virtual DAN (VDAN).
The figure below summarises DAN, SAN, VDAN, LAN, and RedBox connectivity.
DAN DAN
SAN DAN
LAN B
LAN A
REDUNDANCY
BOX
VDAN
VDAN
E01028
In a DAN, both ports share the same MAC address so it does not affect the way devices talk to each other in an
Ethernet network (Address Resolution Protocol at layer 2). Every data frame is seen by both ports.
When a DAN sends a frame of data, the frame is duplicated on both ports and therefore on both LAN segments.
This provides a redundant path for the data frame if one of the segments fails. Under normal conditions, both LAN
segments are working and each port receives identical frames.
336 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
MiCOM H382
SCADA or DS Agile
DS Agile gateways
Ethernet
Up to
C C
6 links C264
L/R L/R C
L/R C
RS485
TX copper link
FX optical fibre Ethernet
E01070 RS485, RS422
P64x-TM-EN-4.1 337
Chapter 16 - Communications P64x
Source
Singly Attached
Nodes
Only about half of the network bandwidth is available in HSR for multicast or broadcast frames because both
duplicate frames A & B circulate the full ring.
338 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Source
C frame
A frame B frame
Singly Attached
Nodes
D frame
Destination V01031
For unicast frames, the whole bandwidth is available as both frames A & B stop at the destination node.
P64x-TM-EN-4.1 339
Chapter 16 - Communications P64x
T1000 switch
LINK
RX
PC SCADA
TX
reset LINK
RX
TX
DS Agile gateways
C C
C C C C C C
The RSTP implementation in this product is compatible with any devices that use RSTP.
RSTP can recover network faults quickly, but the fault recovery time depends on the number of devices on the
network and the network topology. A typical figure for the fault recovery time is 300ms. Therefore, RSTP cannot
achieve the “bumpless” redundancy that some other protocols can.
Refer to IEEE 802.1D 2004 standard for detailed information about the opration of the protocol.
340 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Note:
IP1 and IP2 are different but use the same subnet mask.
PRP/HSR
If using PRP or HSR, you configure the REB IP address using the PRP/HSR Configurator software.
P64x-TM-EN-4.1 341
Chapter 16 - Communications P64x
RSTP
If using RSTP, you configure the REB IP address using the PRP/HSR Configurator software.
RJ45
Ethernet switch
Media
Converter
TXA RXA TXB RXB
TX RX
IED IED
(a) (b)
V01806
Figure 160: Connection using (a) an Ethernet switch and (b) a media converter
342 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Select the device you wish to configure. The MAC address of the selected device is highlighted.
P64x-TM-EN-4.1 343
Chapter 16 - Communications P64x
344 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
that source address to determine how to forward or filter the frame. Otherwise the frame is forwarded to all the
ports in the Ethernet switch (broadcast).
General tab
The Filtering Database contains two types of entry; static and dynamic. The Static Entries are the source addresses
entered by an administrator. The Dynamic Entries are the source addresses learnt by the switch process. The
Dynamic Entries are removed from the Filtering Database after the Ageing Time. The Database holds a maximum
of 1024 entries.
1. To access the forwarding database functions, if required, click the Filtering Database button in the main
window.
2. To view the Forwarding Database Size, Number of Static Entries and Number of Dynamic Entries, click Read
Database Info.
3. To set the Aging Time, enter the number of seconds in the text box and click the Set button.
P64x-TM-EN-4.1 345
Chapter 16 - Communications P64x
RJ45
Ethernet switch
Media
Converter
TX1 RX1 TX2 RX2
TX RX
IED IED
(a) (b)
V01803
Figure 161: Connection using (a) an Ethernet switch and (b) a media converter
346 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Note:
Due to the time needed to establish the RSTP protocol, wait 25 seconds between connecting the PC to the IED and clicking the
Identify Device button.
The redundant Ethernet board connected to the PC is identified and its details are listed.
● Device address
● MAC address
● Version number of the firmware
● SNTP IP address
● Date & time of the real-time clock, from the board.
P64x-TM-EN-4.1 347
Chapter 16 - Communications P64x
Maximum value
S.No Parameter Default value (second) Minimum value (second)
(second)
1 Bridge Max Age 20 6 40
2 Bridge Hello Time 2 1 10
3 Bridge Forward Delay 15 4 30
4 Bridge Priority 32768 0 61440
Note:
When assigning the bridge priority, make sure the root of the network is the Ethernet switch, not the IEDs. This reduces the
number of hops to reach all devices in the network. Also make sure the priority values for all IEDs are higher than that of the
switch.
348 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
configure the redundancy IP address for the General Electric proprietary Self Healing Protocol and Dual Homing
Protocol.
Switch hardware
General Electric switches are stand-alone devices (H3xx, H6x families) or embedded in a computer device rack, for
example MiCOM C264 (SWDxxx, SWRxxx, SWUxxx Ethernet boards) or PC board (MiCOM H14x, MiCOM H15x,
MiCOM H16x).
Switch range
There are 3 types of General Electric switches:
● Standard switches: SWU (in C264), H14x (PCI), H34x, H6x
● Redundant Ring switches: SWR (in C264), H15x (PCI), H35x,
● Redundant Dual Homing switches: SWD (in C264), H16x (PCI), H36x
Switch Manager allows you to allocate an IP addresses for General Electric switches. Switches can then be
synchronized using the Simple Network Time Protocol (SNTP) or they can be administrated using the Simple
Network Management Protocol (SNMP).
All switches have a single 6-byte MAC address.
Redundancy Management
Standard Ethernet does not support a loop at the OSI link layer (layer 2 of the 7 layer model). A mesh topology
cannot be created using a standard Hub and switch. Redundancy needs separate networks using hardware in
routers or software in dedicated switches using STP (Spanning Tree Protocol). However, this redundancy
mechanism is too slow for one link failure in electrical automation networks.
General Electric has developed its own Redundancy ring and star mechanisms using two specific Ethernet ports of
the redundant switches. This redundancy works between General Electric switches of the same type. The two
redundant Ethernet connections between General Electric switches create one private redundant Ethernet LAN.
The Ethernet ports dedicated to the redundancy are optical Ethernet ports. The General Electric redundancy
mechanism uses a single specific address for each Ethernet switch of the private LAN. This address is set using DIP
switches or jumpers.
Switch Manager monitors the redundant address of the switches and the link topology between switches.
5.8.1 INSTALLATION
Network IP address
IP addressing is needed for time synchronization of GE switches and for SNMP management.
Switch Manager is used to define IP addresses of GE switches. These addresses must be in the range of the system
IP, depending on the IP mask of the engineering PC for substation maintenance.
GE switches have a default multicast so the 3rd word of the IP address is always 254.
Installation procedure
Run Setup.exe and follow the on-screen instructions.
P64x-TM-EN-4.1 349
Chapter 16 - Communications P64x
5.8.2 SETUP
1. Make sure the PC has one Ethernet port connected to the GE switch.
2. Configure the PC's Ethernet port on the same subnet as the GE switch.
3. Select User or Admin mode. In User mode enter the user name as User, leave the password blank and click
OK. In Admin mode you can not upload the firmware on the Ethernet repeaters.
4. In Admin mode enter the user name as Admin, enter the password and click OK. All functions are available
including Expert Maintenance facilities.
5. Click the Language button in the bottom right of the screen and select your language.
6. If several Ethernet interfaces are used, in the Network board drop-down box, select the PC Network board
connected to the GE switch. The IP and MAC addresses are displayed below the drop-down box.
7. Periodically click the Ring Topology button (top left) to display or refresh the list of GE switches that are
connected.
350 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
5.8.9 VLAN
The Virtual Local Area Network (VLAN) is a technique used to split an interconnected physical network into several
networks. This technique can be used at all ISO/OSI levels. The VLAN switch is mainly at OSI level 1 (physical VLAN)
which allows communication only between some Ethernet physical ports.
Ports on the switch can be grouped into Physical VLANs to limit traffic flooding. This is because it is limited to ports
belonging to that VLAN and not to other ports.
Port-based VLANs are VLANs where the packet forwarding decision is based on the destination MAC address and
its associated port. You must define outgoing ports allowed for each port when using port-based VLANs. The VLAN
only governs the outgoing traffic so is unidirectional. Therefore, if you wish to allow two subscriber ports to talk to
each other, you must define the egress port for both ports. An egress port is an outgoing port, through which a
data packet leaves.
To assign a physical VLAN to a set of ports:
1. Select the address of the device in the main window.
2. Click the VLAN button, a new screen appears.
3. Use the checkboxes to select which ports will be in the same VLAN. By default all the ports share the same
VLAN.
P64x-TM-EN-4.1 351
Chapter 16 - Communications P64x
6 DATA PROTOCOLS
The products supports a wide range of protocols to make them applicable to many industries and applications.
The exact data protocols supported by a particular product depend on its chosen application, but the following
table gives a list of the data protocols that are typically available.
The relationship of these protocols to the lower level physical layer protocols are as follows:
IEC 60870-5-103
MODBUS IEC 61850
Data Protocols
DNP3.0 DNP3.0
Courier Courier Courier Courier
Data Link Layer EIA(RS)485 Ethernet EIA(RS)232 K-Bus
Physical Layer Copper or Optical Fibre
6.1 COURIER
This section should provide sufficient detail to enable understanding of the Courier protocol at a level required by
most users. For situations where the level of information contained in this manual is insufficient, further
publications (R6511 and R6512) containing in-depth details about the protocol and its use, are available on
request.
Courier is an General Electric proprietary communication protocol. Courier uses a standard set of commands to
access a database of settings and data in the IED. This allows a master to communicate with a number of slave
devices. The application-specific elements are contained in the database rather than in the commands used to
interrogate it, meaning that the master station does not need to be preconfigured. Courier also provides a
sequence of event (SOE) and disturbance record extraction mechanism.
For either of the rear ports, both the IED address and baud rate can be selected using the front panel menu or by
the settings application software.
352 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
With the exception of the Disturbance Recorder settings, changes made to the control and support settings are
implemented immediately and stored in non-volatile memory. Changes made to the Protection settings and the
Disturbance Recorder settings are stored in ‘scratchpad’ memory and are not immediately implemented. These
need to be committed by writing to the Save Changes cell in the CONFIGURATION column.
Method 1
This uses a combination of three commands to perform a settings change:
First, enter Setting mode: This checks that the cell is settable and returns the limits.
1. Preload Setting: This places a new value into the cell. This value is echoed to ensure that setting corruption
has not taken place. The validity of the setting is not checked by this action.
2. Execute Setting: This confirms the setting change. If the change is valid, a positive response is returned. If
the setting change fails, an error response is returned.
3. Abort Setting: This command can be used to abandon the setting change.
This is the most secure method. It is ideally suited to on-line editors because the setting limits are extracted before
the setting change is made. However, this method can be slow if many settings are being changed because three
commands are required for each change.
Method 2
The Set Value command can be used to change a setting directly. The response to this command is either a
positive confirm or an error code to indicate the nature of a failure. This command can be used to implement a
setting more rapidly than the previous method, however the limits are not extracted. This method is therefore most
suitable for off-line setting editors such as MiCOM S1 Agile, or for issuing preconfigured control commands.
P64x-TM-EN-4.1 353
Chapter 16 - Communications P64x
Event Types
The IED generates events under certain circumstances such as:
● Change of state of output contact
● Change of state of opto-input
● Protection element operation
● Alarm condition
● Setting change
● Password entered/timed-out
354 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
The Menu Database contains tables of possible events, and shows how the contents of the above fields are
interpreted. Fault and Maintenance records return a Courier Type 3 event, which contains the above fields plus two
additional fields:
● Event extraction column
● Event number
These events contain additional information, which is extracted from the IED using column B4. Row 01 contains a
Select Record setting that allows the fault or maintenance record to be selected. This setting should be set to the
event number value returned in the record. The extended data can be extracted from the IED by uploading the text
and data from the column.
The PSL settings can be uploaded and downloaded to and from the IED using this mechanism. The settings
application software must be used to edit the settings. It also performs checks on the validity of the settings before
they are transferred to the IED.
P64x-TM-EN-4.1 355
Chapter 16 - Communications P64x
COMMUNICATIONS
RP1 Protocol
Courier
4. Move down to the next cell (RP1 Address). This cell controls the address of the RP1 port on thje device. Up to
32 IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so
that messages from the master control station are accepted by one IED only. Courier uses an integer
number between 1 and 254 for the Relay Address. It is set to 255 by default, which has to be changed. It is
important that no two IEDs share the same address.
COMMUNICATIONS
RP1 Address
100
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity timer
controls how long the IED waits without receiving any messages on the rear port before revoking any
password access that was enabled and discarding any changes. For the rear port this can be set between 1
and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins.
6. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
7. Move down to the next cell (RP1 Card Status). This cell is not settable. It displays the status of the chosen
physical layer protocol for RP1.
COMMUNICATIONS
RP1 Card Status
K-Bus OK
356 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
8. Move down to the next cell (RP1 Port Config). This cell controls the type of serial connection. Select between
K-Bus or RS485.
COMMUNICATIONS
RP1 Port Config
K-Bus
9. If using EIA(RS)485, the next cell (RP1 Comms Mode) selects the communication mode. The choice is either
IEC 60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no parity. If using K-Bus this cell will not
appear.
COMMUNICATIONS
RP1 Comms Mode
IEC 60870 FT1.2
10. If using EIA(RS)485, the next cell down controls the baud rate. Three baud rates are supported; 9600, 19200
and 38400. If using K-Bus this cell will not appear as the baud rate is fixed at 64 kbps.
COMMUNICATIONS
RP1 Baud rate
19200
If the optional fibre optic port is fitted, a menu item appears in which the active port can be selected. However the
selection is only effective following the next power up.
P64x-TM-EN-4.1 357
Chapter 16 - Communications P64x
The IED address and baud rate can be selected using the front panel menu or by the settings application software.
6.2.2 INITIALISATION
Whenever the device has been powered up, or if the communication parameters have been changed a reset
command is required to initialize the communications. The device will respond to either of the two reset
commands; Reset CU or Reset FCB (Communication Unit or Frame Count Bit). The difference between the two
commands is that the Reset CU command will clear any unsent messages in the transmit buffer, whereas the
Reset FCB command does not delete any messages.
The device will respond to the reset command with an identification message ASDU 5. The Cause of Transmission
(COT) of this response will be either Reset CU or Reset FCB depending on the nature of the reset command. The
content of ASDU 5 is described in the IEC 60870-5-103 section of the Menu Database, available from General
Electric separately if required.
In addition to the above identification message, it will also produce a power up event.
When the Config Mode cell is set to Std+UserConfig, the DDB masks become visible in the PROTOCOL CFG
column. These masks function in a similar way to the DDB masks in the RECORD CONTROL column. Editing these
masks controls the DDB signals that are enabled for communication of the equivalent IEC 60870-5-103 private
range signal, as listed in the IEC 60870-5-103 profile in the Menu Database.
358 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Within these masks, only individual DDBs that are equivalent to IEC 60870-5-103 private range signals are
editable. By default, all of the individual DDBs that are equivalent to IEC 60870-5-103 private range signals are set
to 0 (zero), that is disabled for communication. Setting any individual DDB to 1 (one), enables the equivalent IEC
60870-5-103 private range signal for communication.
Within these masks, individual DDBs that are either equivalent to IEC 60870-5-103 standard range signals, or do
not have any equivalent IEC 60870-5-103 private range signal, are not editable.
The IEC 60870-5-103 profile in the Menu Database contains a complete listing of all events produced by the
device.
From Software Version 91 onwards, the IEC 60870-5-103 private range signals can be individually selected for GI
reporting. Set the Config Mode cell to Std+UserConfig, and configure the DDB masks as required.
6.2.8 COMMANDS
A list of the supported commands is contained in the Menu Database. The device will respond to other commands
with an ASDU 1, with a cause of transmission (COT) indicating ‘negative acknowledgement’.
Note:
IEC 60870-5-103 only supports up to 8 records.
P64x-TM-EN-4.1 359
Chapter 16 - Communications P64x
COMMUNICATIONS
RP1 Protocol
IEC 60870-5-103
4. Move down to the next cell (RP1 Address). This cell controls the IEC 60870-5-103 address of the IED. Up to 32
IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so that
messages from the master control station are accepted by one IED only. IEC 60870-5-103 uses an integer
number between 0 and 254 for the address. It is important that no two IEDs have the same IEC 60870 5 103
address. The IEC 60870-5-103 address is then used by the master station to communicate with the IED.
COMMUNICATIONS
RP1 address
162
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Two baud rates are
supported by the IED, 9600 bits/s and 19200 bits/s. Make sure that the baud rate selected on the
IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Meas Period). The next cell down controls the period between
IEC 60870-5-103 measurements. The IEC 60870-5-103 protocol allows the IED to supply measurements at
regular intervals. The interval between measurements is controlled by this cell, and can be set between 1
and 60 seconds.
COMMUNICATIONS
RP1 Meas Period
30.00 s
360 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. The next cell down (RP1 CS103Blcking) can be used for monitor or command blocking.
COMMUNICATIONS
RP1 CS103Blcking
Disabled
9. There are three settings associated with this cell; these are:
Setting: Description:
Disabled No blocking selected.
When the monitor blocking DDB Signal is active high, either by energising an opto input or control input,
Monitor Blocking reading of the status information and disturbance records is not permitted. When in this mode the device
returns a "Termination of general interrogation" message to the master station.
When the command blocking DDB signal is active high, either by energising an opto input or control input,
Command Blocking all remote commands will be ignored (i.e. CB Trip/Close, change setting group etc.). When in this mode the
device returns a "negative acknowledgement of command" message to the master station.
The IED address and baud rate can be selected using the front panel menu or by the settings application software.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 stop bit and optional configurable parity
bit.
P64x-TM-EN-4.1 361
Chapter 16 - Communications P64x
Control Input
(Latched)
Aliased Control
Input
(Latched)
Control Input
(Pulsed )
Aliased Control
Input
(Pulsed )
The pulse width is equal to the duration of one protection iteration
V01002
Many of the IED’s functions are configurable so some of the Object 10 commands described in the following
sections may not be available. A read from Object 10 reports the point as off-line and an operate command to
Object 12 generates an error response.
Examples of Object 10 points that maybe reported as off-line are:
● Activate setting groups: Ensure setting groups are enabled
● CB trip/close: Ensure remote CB control is enabled
362 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
P64x-TM-EN-4.1 363
Chapter 16 - Communications P64x
The devices use the DNP 3.0 Slave Source Code Library version 3 from Triangle MicroWorks Inc.
This document, in conjunction with the DNP 3.0 Basic 4 Document Set, and the DNP Subset Definitions Document,
provides complete information on how to communicate with the devices using the DNP 3.0 protocol.
This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 2. It also contains many
Subset Level 3 and above features.
DNP 3.0
Device Profile Document
Vendor Name: General Electric
Device Name: MiCOM P40Agile Protection Relays – compact and modular range
Models Covered: All models
Highest DNP Level Supported*: For Requests: Level 2
*This is the highest DNP level FULLY supported. Parts of level 3 are For Responses: Level 2
also supported
Device Function: Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported (the complete list is described in the
DNP 3.0 Implementation Table):
For static (non-change event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08 (limited quantity), and 17 and 28 (index)
are supported in addition to the request qualifier code 06 (no range (all points))
Static object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded with qualifiers 00 or 01
Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28
For change-event object requests, qualifiers 17 or 28 are always responded
16-bit and 32-bit analogue change events with time may be requested
The read function code for Object 50 (time and date) variation 1 is supported
Analogue Input Deadbands, Object 34, variations 1 through 3, are supported
Floating Point Analogue Output Status and Output Block Objects 40 and 41 are supported
Sequential file transfer, Object 70, variations 2 through 7, are supported
Device Attribute Object 0 is supported
Maximum Data Link Frame Size (octets): Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets) Transmitted: Configurable (100 to 2048). Default 2048
Received: 249
Maximum Data Link Retries: Fixed at 2
Maximum Application Layer Retries: None
Requires Data Link Layer Confirmation: Configurable to Never or Always
Requires Application Layer Confirmation: When reporting event data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Timeouts while waiting for:
Data Link Confirm: Configurable
364 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
DNP 3.0
Device Profile Document
Complete Application Fragment: None
Application Confirm: Configurable
Complete Application Response: None
Others:
Data Link Confirm Timeout: Configurable from 0 (Disabled) to 120s, default 10s.
Application Confirm Timeout: Configurable from 1 to 120s, default 2s.
Select/Operate Arm Timeout: Configurable from 1 to 10s, default 10s.
Need Time Interval (Set IIN1-4): Configurable from 1 to 30, default 10min.
Application File Timeout 60 s
Analog Change Event Scan Period: Fixed at 0.5s
Counter Change Event Scan Period Fixed at 0.5s
Frozen Counter Change Event Scan Period Fixed at 1s
Maximum Delay Measurement Error: 2.5 ms
Time Base Drift Over a 10-minute Interval: 7 ms
Sends/Executes Control Operations:
Write Binary Outputs: Never
Select/Operate: Always
Direct Operate: Always
Direct Operate - No Ack: Always
Count > 1 Never
Pulse On Always
Pulse Off Sometimes
Latch On Always
Latch Off Always
Queue Never
Clear Queue Never
Note: Paired Control points will accept Pulse On/Trip and Pulse On/Close, but only single point will accept the Pulse Off control command.
Reports Binary Input Change Events when no specific variation Configurable to send one or the other
requested:
Reports time-tagged Binary Input Change Events when no specific Binary input change with time
variation requested:
Sends Unsolicited Responses: Never
Sends Static Data in Unsolicited Responses: Never
No other options are permitted
Default Counter Object/Variation: Configurable, Point-by-point list attached
Default object: 20
Default variation: 1
Counters Roll Over at: 32 bits
Sends multi-fragment responses: Yes
Sequential File Transfer Support:
Append File Mode No
Custom Status Code Strings No
Permissions Field Yes
P64x-TM-EN-4.1 365
Chapter 16 - Communications P64x
DNP 3.0
Device Profile Document
File Events Assigned to Class No
File Events Send Immediately Yes
Multiple Blocks in a Fragment No
Max Number of Files Open 1
366 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
20 6 16-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 0 Frozen Counter - Any Variation 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
21 1 32-Bit Frozen Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 2 16-Bit Frozen Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 5 32-Bit Frozen Counter with Time of 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Freeze 06 (no range, or all) 17, 28 (index - see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
21 6 16-Bit Frozen Counter with Time of 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Freeze 06 (no range, or all) 17, 28 17, 28 (index - see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
21 9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
21 10 16-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
`22 0 Counter Change Event - Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
22 1 32-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see without Time 07, 08 (limited qty)
note 1)
22 2 16-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
without Time 07, 08 (limited qty)
22 5 32-Bit Counter Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
22 6 16-Bit Counter Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
23 0 Frozen Counter Event (Variation 0 1 (read) 06 (no range, or all)
is used to request default 07, 08 (limited qty)
variation)
23 1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see 07, 08 (limited qty)
note 1)
23 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
23 5 32-Bit Frozen Counter Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
23 6 16-Bit Frozen Counter Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
30 0 Analog Input - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
P64x-TM-EN-4.1 367
Chapter 16 - Communications P64x
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
30 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
30 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 5 Short floating point 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
32 0 Analog Change Event - Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
32 1 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see without Time 07, 08 (limited qty)
note 1)
32 2 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
without Time 07, 08 (limited qty)
32 3 32-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
32 4 16-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
32 5 Short floating point Analog 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Change Event without Time 07, 08 (limited qty)
32 7 Short floating point Analog 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Change Event with Time 07, 08 (limited qty)
34 0 Analog Input Deadband (Variation 1 (read) 00, 01 (start-stop)
0 is used to request default 06 (no range, or all)
variation) 07, 08 (limited qty)
17, 27, 28 (index)
34 1 16 Bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34 2 32 Bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34 3 Short Floating Point Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Deadband 06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
40 0 Analog Output Status (Variation 0 1 (read) 00, 01 (start-stop)
is used to request default 06 (no range, or all)
variation) 07, 08 (limited qty)
17, 27, 28 (index)
40 1 32-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
40 2 16-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
368 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
40 3 Short Floating Point Analog 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Output Status 06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
41 1 32-Bit Analog Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 2 16-Bit Analog Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 3 Short Floating Point Analog 3 (select) 17, 27, 28 (index) 129 response echo of request
Output Block 4 (operate)
5 (direct op)
6 (dir. op, noack)
1 1 (read) 07 (limited qty = 1) 129 response 07 (limited qty = 1)
50 (default - see Time and Date
note 1)
2 (write) 07 (limited qty = 1)
60 0 Not defined
60 1 Class 0 Data 1 (read) 06 (no range, or all)
60 2 Class 1 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
60 3 Class 2 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
60 4 Class 3 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
70 0 File Event - Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
70 2 File Authentication 29 (authenticate) 5b (free-format) 129 response 5B (free-format)
70 3 File Command 25 (open) 5b (free-format)
27 (delete)
70 4 File Command Status 26 (close) 5b (free-format) 129 response 5B (free-format)
30 (abort)
70 5 File Transfer 1 (read) 5b (free-format) 129 response 5B (free-format)
70 6 File Transfer Status 129 response 5B (free-format)
70 7 File Descriptor 28 (get file info) 5b (free-format) 129 response 5B (free-format)
Note:
A Default variation refers to the variation responded to when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
P64x-TM-EN-4.1 369
Chapter 16 - Communications P64x
Note:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded to when a request is sent with qualifiers 17 or
28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded to with qualifiers
00 or 01. For change-event objects, qualifiers 17 or 28 are always responded to.
370 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Note:
Code numbers 10 through to 126 are reserved for future use.
P64x-TM-EN-4.1 371
Chapter 16 - Communications P64x
3. Move to the first cell down (RP1 protocol). This is a non-settable cell, which shows the chosen
communication protocol – in this case DNP3.0.
COMMUNICATIONS
RP1 Protocol
DNP3.0
4. Move down to the next cell (RP1 Address). This cell controls the DNP3.0 address of the IED. Up to 32 IEDs can
be connected to one spur, therefore it is necessary for each IED to have a unique address so that messages
from the master control station are accepted by only one IED. DNP3.0 uses a decimal number between 1
and 65519 for the Relay Address. It is important that no two IEDs have the same address.
COMMUNICATIONS
RP1 Address
1
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud rates are
supported by the IED 1200 bps, 2400 bps, 4800 bps, 9600 bps, 19200 bps and 38400 bps. Make sure that
the baud rate selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames. The
parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on the IED is
the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. Move down to the next cell (RP1 Time Sync). This cell affects the time synchronisation request from the
master by the IED. It can be set to enabled or disabled. If enabled it allows the DNP3.0 master to
synchronise the time on the IED.
COMMUNICATIONS
RP1 Time Sync
Enabled
372 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
If the device supports DNP Over Ethernet, the configuration related settings are done in the folder DNP Over
Ethernet.
6.4 MODBUS
This section describes how the MODBUS standard is applied to the Px40 platform. It is not a description of the
standard itself. The level at which this section is written assumes that the reader is already familiar with the
MODBUS standard.
The MODBUS protocol is a master/slave protocol, defined and administered by the MODBUS Organization For
further information on MODBUS and the protocol specifications, please see the Modbus web site
(www.modbus.org).
The MODBUS interface uses ‘RTU’ mode communication rather than ‘ASCII’ mode as this provides more efficient
use of the communication bandwidth. This mode of communication is defined by the MODBUS standard.
The IED address and baud rate can be selected using the front panel menu or by the settings application software.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 parity bit with 1 stop bit, or 2 stop bits (a
total of 11 bits per character).
P64x-TM-EN-4.1 373
Chapter 16 - Communications P64x
Note:
The "extended memory file" (6xxxx) is not supported.
Note:
MODBUS convention is to document register addresses as ordinal values whereas the actual protocol addresses are literal
values. The MiCOM relays begin their register addresses at zero. Therefore, the first register in a memory page is register
address zero. The second register is register address 1 and so on.
Note:
The page number notation is not part of the address.
374 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
For each of the above registers a value of 0 represents the most recent stored record. The following registers can
be read to indicate the numbers of the various types of record stored.
● 30100: Number of stored records
● 30101: Number of stored fault records
● 30102: Number of stored maintenance records
Each fault or maintenance record logged causes an event record to be created. If this event record is selected, the
additional registers allowing the fault or maintenance record details will also become populated.
If a fault record or maintenance record is directly selected using the manual mechanism then the data can be read
from the register ranges specified above. The event record data in registers 30103 to 30111 will not be available.
It is possible using register 40401(G6 data type) to independently clear the stored relay event/fault and
maintenance records. This register also provides an option to reset the device indications, which has the same
effect on the relay as pressing the clear key within the alarm viewer using the HMI panel menu.
P64x-TM-EN-4.1 375
Chapter 16 - Communications P64x
Records extracted over MODBUS from Px40 devices are presented in COMTRADE format. This involves extracting
an ASCII text configuration file and then extracting a binary data file.
Each file is extracted by reading a series of data pages from the IED The data page is made up of 127 registers,
giving a maximum transfer of 254 bytes per page.
The following set of registers is presented to the master station to support the extraction of uncompressed
disturbance records:
MODBUS registers
MODBUS Register Name Description
Provides the status of the relay as bit flags:
b0: Out of service
b1: Minor self test failure
b2: Event
b3: Time synchronization
3x00001 Status register b4: Disturbance
b5: Fault
b6: Trip
b7: Alarm
b8 to b15: Unused
A ‘1’ on b4 indicates the presence of a disturbance
Indicates the total number of disturbance records currently stored in the
3x00800 No of stored disturbances
relay, both extracted and non-extracted.
Indicates the unique identifier value for the oldest disturbance record
Unique identifier of the oldest stored in the relay. This is an integer value used in conjunction with the
3x00801
disturbance record ‘Number of stored disturbances’ value to calculate a value for manually
selecting records.
This register is used to manually select disturbance records. The values
written to this cell are an offset of the unique identifier value for the
Manual disturbance record
4x00250 oldest record. The offset value, which ranges from 0 to the Number of
selection register
stored disturbances - 1, is added to the identifier of the oldest record to
generate the identifier of the required record.
This register is used during the extraction process and has a number of
commands. These are:
b0: Select next event
Record selection command b1: Accept event
4x00400
register b2: Select next disturbance record
b3: Accept disturbance record
b4: Select next page of disturbance data
b5: Select data file
3x00930 - 3x00933 Record time stamp These registers return the timestamp of the disturbance record.
This register informs the master station of the number of registers in the
3x00802 No of registers in data page
data page that are populated.
These 127 registers are used to transfer data from the relay to the master
3x00803 - 3x00929 Data page registers
station. They are 16-bit unsigned integers.
The disturbance record status register is used during the extraction
Disturbance record status
3x00934 process to indicate to the master station when data is ready for
register
extraction. See next table.
This is used to select the required data file format. This is reserved for
4x00251 Data file format selection
future use.
376 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Note:
Register addresses are provided in reference code + address format. E.g. 4x00001 is reference code 4x, address 1 (which is
specified as function code 03, address 0x0000 in the MODBUS specification).
The disturbance record status register will report one of the following values:
P64x-TM-EN-4.1 377
Chapter 16 - Communications P64x
Start
Get number of
disturbances from
register 3x00800
End
V01003
Method 1
Method 1 is simpler and is better at extracting single disturbance records (when the disturbance recorder is polled
regularly).
378 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Start
Is disturbance bit No
(bit 4) set?
Yes
Error
Method 2
Method 2 is more complex to implement but is more efficient at extracting large quantities of disturbance records.
This may be useful when the disturbance recorder is polled only occasionally and therefore may have many stored
records.
P64x-TM-EN-4.1 379
Chapter 16 - Communications P64x
Start
FirstTime = True
FirstTime = True
Is disturbance bit
(bit 4) set? No
Yes
No
FirstTime = False
380 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Start
(Record selected)
To parent
procedure
Read DR status value Busy
from register 3x00934
Check DR status
for error
conditions or Error
Busy status
Page ready
Read number of
registers in data page
from address 3x00802
V01006
P64x-TM-EN-4.1 381
Chapter 16 - Communications P64x
Start
(Configuration
complete)
To parent
procedure
Read DR status value Busy
from register 3x00934
Check DR status
for error
conditions or Error
Busy status
Page ready
Read number of
registers in data page
from address 3x00802
Record complete (mark Store data to binary file Send ‘Get next page of
record as extracted; in the order the data data’ to register
automatic extraction only) were received 4x00400
V01007
During the extraction of the COMTRADE files, an error may occur, which will be reported on the DR Status register
3x00934. In this case, you must take action to re-start the record extraction or to abort according to the table
below.
Value State Description
This will be the state reported when no record is selected; such as after power on or after a record has
0 Idle
been marked as extracted.
1 Busy The relay is currently processing data.
2 Page ready The data page has been populated and the master station can now safely read the data.
Configuration
3 All of the configuration data has been read without error.
complete
4 Record complete All of the disturbance data has been extracted.
Disturbance An error occurred during the extraction process where the disturbance being extracted was overwritten
5
overwritten by a new record.
382 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
In addition to the basic editing of the protection setting groups, the following functions are provided:
● Default values can be restored to a setting group or to all of the relay settings by writing to register 4x0402.
● It is possible to copy the contents of one setting group to another by writing the source group to register
40406 and the target group to 4x0407.
The setting changes performed by either of the two operations defined above are made to the scratchpad area.
These changes must be confirmed by writing to register 4x0405.
The active protection setting groups can be selected by writing to register 40404. An illegal data response will be
returned if an attempt is made to set the active group to one that has been disabled.
P64x-TM-EN-4.1 383
Chapter 16 - Communications P64x
Key to table:
● m = milliseconds: 0 to 59,999
● I = minutes: 0 to 59
● H = hours: 0 to 23
● W = day of the week: 1 to 7 starting from Monday
● D = day of the month: 1 to 31
● M = month of the year: 1 to 12 starting from January
● Y = year of the century: 0 to 99
● R = reserved: 0
● SU = summertime: 0 = GMT, 1 = summertime
● IV = invalid: 0 = invalid value, 1 = valid value
Since the range of the data type is only 100 years, the century must be deduced. The century is calculated as the
one that will produce the nearest time value to the current date. For example: 30-12-99 is 30-12-1999 when
received in 1999 & 2000, but is 30-12-2099 when received in 2050. This technique allows 2 digit years to be
accurately converted to 4 digits in a ±50 year window around the current date.
The invalid bit has two applications:
● It can indicate that the date-time information is considered inaccurate, but is the best information available.
● It can indicate that the date-time information is not available.
The summertime bit is used to indicate that summertime (day light saving) is being used and, more importantly, to
resolve the alias and time discontinuity which occurs when summertime starts and ends. This is important for the
correct time correlation of time stamped records.
The day of the week field is optional and if not calculated will be set to zero.
The concept of time zone is not catered for by this data type and hence by the relay. It is up to the end user to
determine the time zone. Normal practice is to use UTC (universal co-ordinated time).
384 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Note:
The G29 values must be read in whole multiples of three registers. It is not possible to read the G28 and G27 parts with
separate read commands.
The Three-phase Active Power displayed on the measurement panel on the front display of the IED would be 21.94
MW
The registers related to the Three-phase Active Power are: 3x00327, 3x00328, 3x00329
Register Address Data read from these registers Format of the data
3x00327 116 G28
3x00328 2 G27
P64x-TM-EN-4.1 385
Chapter 16 - Communications P64x
Register Address Data read from these registers Format of the data
3x00329 57928 G27
The Equivalent G27 value = [216 * Value in the address 3x00328 + Value in the address 3x00329] = 216*2 + 57928 =
189000
The Equivalent value of power G29 = G28 * Equivalent G27 =116 * 189000 =21.92 MW
Note:
The above calculated value (21.92 MW) is same as the power value measured on the front panel display.
COMMUNICATIONS
RP1 Protocol
Modbus
4. Move down to the next cell (RP1 Address). This cell controls the Modbus address of the IED. Up to 32 IEDs
can be connected to one spur, therefore it is necessary for each IED to have a unique address so that
messages from the master control station are accepted by only one IED. Modbus uses a decimal number
between 1 and 247 for the Relay Address. It is important that no two IEDs have the same address.
COMMUNICATIONS
RP1 Address
1
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity timer
controls how long the IED waits without receiving any messages on the rear port before it reverts to its
default state, including revoking any password access that was enabled. For the rear port this can be set
between 1 and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins
386 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
6. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud rates are
supported by the IED 1200 bits/s, 2400 bits/s, 4800 bits/s, 9600 bits/s, 19200 bits/s and 38400 bits/s. Make
sure that the baud rate selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
7. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames. The
parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on the IED is
the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
8. Move down to the next cell (Modbus IEC Time). This cell controls the order in which the bytes of information
are transmitted. There is a choice of Standard or Reverse. When Standard is selected the time format
complies with IEC 60870-5-4 requirements such that byte 1 of the information is transmitted first, followed
by bytes 2 through to 7. If Reverse is selected the transmission of information is reversed.
COMMUNICATIONS
Modbus IEC Time
Standard
The standard adheres to the requirements laid out by the ISO OSI model and therefore provides complete vendor
interoperability and flexibility on the transmission types and protocols used. This includes mapping of data onto
P64x-TM-EN-4.1 387
Chapter 16 - Communications P64x
Ethernet, which is becoming more and more widely used in substations, in favour of RS485. Using Ethernet in the
substation offers many advantages, most significantly including:
● Ethernet allows high-speed data rates (currently 100 Mbps, rather than tens of kbps or less used by most
serial protocols)
● Ethernet provides the possibility to have multiple clients
● Ethernet is an open standard in every-day use
● There is a wide range of Ethernet-compatible products that may be used to supplement the LAN installation
(hubs, bridges, switches)
Data Attributes
stVal q t PhA PhB PhC
Data Objects
Pos A
Logical Nodes : 1 to n
LN1: XCBR LN2: MMXU
V01008
388 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Layer Description
Identifies the major functional areas within the IEC 61850 data model. Either 3 or 6 characters are
used as a prefix to define the functional group (wrapper) while the actual functionality is identified by
Wrapper/Logical Node Instance a 4 character Logical Node name suffixed by an instance number.
For example, XCBR1 (circuit breaker), MMXU1 (measurements), FrqPTOF2 (overfrequency protection,
stage 2).
This next layer is used to identify the type of data you will be presented with. For example, Pos
Data Object
(position) of Logical Node type XCBR.
This is the actual data (measurement value, status, description, etc.). For example, stVal (status value)
Data Attribute
indicating actual position of circuit breaker for Data Object type Pos of Logical Node type XCBR.
The IEC 61850 compatible interface standard provides capability for the following:
● Read access to measurements
● Refresh of all measurements at a standard rate.
● Generation of non-buffered and buffered reports on change of status or measurement
● SNTP time synchronization over an Ethernet link. (This is used to synchronize the IED's internal real time
clock.
● GOOSE peer-to-peer communication
● Disturbance record extraction by IEC 61850 MMS file transfer. The record is extracted as an ASCII format
COMTRADE file
Note:
Setting changes are not supported in the current IEC 61850 implementation. Currently these setting changes are carried out
using the settings application software.
P64x-TM-EN-4.1 389
Chapter 16 - Communications P64x
390 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
IEC 61850 allows IEDs to be directly configured from a configuration file. The IED’s system configuration
capabilities are determined from an IED Capability Description file (ICD), supplied with the product. By using ICD
files from the products to be installed, you can design, configure and test (using simulation tools), a substation’s
entire protection scheme before the products are installed into the substation.
To help with this process, the settings application software provides an IEC 61850 Configurator tool, which allows
the pre-configured IEC 61850 configuration file to be imported and transferred to the IED. As well as this, you can
manually create configuration files for all products, based on their original IED capability description (ICD file).
Other features include:
● The extraction of configuration data for viewing and editing.
● A sophisticated error checking sequence to validate the configuration data before sending to the IED.
Note:
Some configuration data is available in the IEC61850 CONFIG. column, allowing read-only access to basic configuration data.
Any new configuration sent to the IED is automatically stored in the inactive configuration bank, therefore not
immediately affecting the current configuration.
Following an upgrade, the IEC 61850 Configurator tool can be used to transmit a command, which authorises
activation of the new configuration contained in the inactive configuration bank. This is done by switching the
active and inactive configuration banks. The capability of switching the configuration banks is also available using
the IEC61850 CONFIG. column of the HMI.
The SCL Name and Revision attributes of both configuration banks are available in the IEC61850 CONFIG. column
of the HMI.
P64x-TM-EN-4.1 391
Chapter 16 - Communications P64x
To configure the product for edition 1, start with the edition 1 ICD file. This can be done in one of two ways:
1. Using the system engineering process of an IEC 61850 system. In this case, import either the edition 1 ICD
file (for example “P545____91A_ED1.ICD”) or the edition 2 ICD file (for example “P545____91A_ED2.ICD”), as
applicable, into the System Configuration Tool. Perform the system configuration, then export the
configured file (.SCD or CID). Import this configured file into MiCOM S1 Agile’s IEC 61850 Configurator.
2. Using the IED Configurator tool to manually configure the product. Launch the IED Configurator tool. Select
File, New and then check only the Edition 1 or Edition 2 box, as applicable, and then proceed to select the
product model and software version. Configure the parameters manually and save the MCL file.
In either case, the edition 1 or edition 2 configuration is activated in the product by sending the configuration file to
the product from the IED Configurator and switching it to the Active Bank, after which the Ethernet application will
restart with the new configuration.
Edition 2 implementation requires use of version 3.8 of the IEC 61850 configurator, which is installed with version
2.0.1 of MiCOM S1 Agile.
392 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Ed2
MMS
C C
L/ R
GOOSE
BAY
Ed1 devices in Ed2 system:
GOOSE OK
MMS OK
TOOLS (SCL files) OK V01056
Figure 169: Edition 2 system - backward compatibility
An Edition 2 IED cannot normally operate within an Edition 1 IEC 61850 system. An Edition 2 IED can work for
GOOSE messaging in a mixed system, providing the client is compatible with Edition 2.
Ed1
MMS
C C
L/ R
GOOSE
BAY
Ed1 devices in Ed2 system:
GOOSE OK
MMS Not OK
TOOLS (SCL files) Not OK V01057
Figure 170: Edition 1 system - forward compatibility issues
P64x-TM-EN-4.1 393
Chapter 16 - Communications P64x
Of these, only ENS and ENC types are available from a MiCOM P40 IED when publishing GOOSE messages, so Data
Objects using these Common Data Classes should not be published in mixed Edition 1 and Edition 2 systems.
For compatibility between Edition 1 and Edition 2 IEDs, SCL files using SCL schema version 2.1 must be used. For a
purely Edition 2 system, use the schema version 3.1.
Standby
BAY(S) BAY1 BAY N
Station/Process Bus
Yard Yard
394 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
See the example below. If a failure occurs in the Bay 1 protection IED (MP2), we could disable this device and
activate a standby protection IED to replace its functionality.
Standby
BAY(S) BAY1 BAY N
(5) (2)
Station/Process Bus
(4)
Yard Yard
Test
Device SC MU1 SC MU2 SC MU1 SC MU2
P64x-TM-EN-4.1 395
Chapter 16 - Communications P64x
Note:
For IEC 60870-5-103, Read Only Mode function is different from the existing Command block feature.
396 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.
P64x-TM-EN-4.1 397
Chapter 16 - Communications P64x
8 TIME SYNCHRONISATION
In modern protection schemes it is necessary to synchronise the IED's real time clock so that events from different
devices can be time stamped and placed in chronological order. This is achieved in various ways depending on the
chosen options and communication protocols.
● Using the IRIG-B input (if fitted)
● Using the SNTP time protocol (for Ethernet IEC 61850 versions + DNP3 OE)
● By using the time synchronisation functionality inherent in the data protocols
GPS satellite
IRIG-B
V01040
The IRIG-B time code signal is a sequence of one second time frames. Each frame is split up into ten 100 mS slots
as follows:
● Time-slot 1: Seconds
● Time-slot 2: Minutes
● Time-slot 3: Hours
● Time-slot 4: Days
● Time-slot 5 and 6: Control functions
● Time-slots 7 to 10: Straight binary time of day
398 P64x-TM-EN-4.1
P64x Chapter 16 - Communications
The first four time-slots define the time in BCD (Binary Coded Decimal). Time-slots 5 and 6 are used for control
functions, which control deletion commands and allow different data groupings within the synchronisation strings.
Time-slots 7-10 define the time in SBS (Straight Binary Second of day).
8.2 SNTP
SNTP is used to synchronise the clocks of computer systems over packet-switched, variable-latency data
networks, such as IP. SNTP can be used as the time synchronisation method for models using IEC 61850 over
Ethernet.
The device is synchronised by the main SNTP server. This is achieved by entering the IP address of the SNTP server
into the IED using the IEC 61850 Configurator software described in the settings application software manual. A
second server is also configured with a different IP address for backup purposes.
This function issues an alarm when there is a loss of time synchronisation on the SNTP server. This could be
because there is no response or no valid clock signal.
The HMI menu does not contain any configurable settings relating to SNTP, as the only way to configure it is using
the IEC 61850 Configurator. However it is possible to view some parameters in the COMMUNICATIONS column
under the sub-heading SNTP parameters. Here you can view the SNTP server addresses and the SNTP poll rate in
the cells SNTP Server 1, SNTP Server 2 and SNTP Poll rate respectively.
The SNTP time synchronisation status is displayed in the SNTP Status cell in the DATE AND TIME column.
P64x-TM-EN-4.1 399
Chapter 16 - Communications P64x
When using end-to-end mode, the IED can be connected in a ring or line topology using RSTP or Self Healing
Protocol without any additional Transparent Clocks. But because the IED is a slave-only device, additional
inaccuracy is introduced. The additional error will be less than 1ms for a network of eight devices.
Grand Master
L o c k e d
A la rm
RSTP Network
<8 Hops, so <1ms
additional timing error
V01061
400 P64x-TM-EN-4.1
CHAPTER 17
CYBER-SECURITY
Chapter 17 - Cyber-Security P64x
402 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
1 OVERVIEW
In the past, substation networks were traditionally isolated and the protocols and data formats used to transfer
information between devices were often proprietary.
For these reasons, the substation environment was very secure against cyber-attacks. The terms used for this
inherent type of security are:
● Security by isolation (if the substation network is not connected to the outside world, it cannot be accessed
from the outside world).
● Security by obscurity (if the formats and protocols are proprietary, it is very difficult to interpret them).
The increasing sophistication of protection schemes, coupled with the advancement of technology and the desire
for vendor interoperability, has resulted in standardisation of networks and data interchange within substations.
Today, devices within substations use standardised protocols for communication. Furthermore, substations can be
interconnected with open networks, such as the internet or corporate-wide networks, which use standardised
protocols for communication. This introduces a major security risk making the grid vulnerable to cyber-attacks,
which could in turn lead to major electrical outages.
Clearly, there is now a need to secure communication and equipment within substation environments. This
chapter describes the security measures that have been put in place for our range of Intelligent Electronic Devices
(IEDs).
Note:
Cyber-security compatible devices do not enforce NERC compliance, they merely facilitate it. It is the responsibility of the user
to ensure that compliance is adhered to as and when necessary.
P64x-TM-EN-4.1 403
Chapter 17 - Cyber-Security P64x
The threats to cyber-security may be unintentional (e.g. natural disasters, human error), or intentional (e.g. cyber-
attacks by hackers).
Good cyber-security can be achieved with a range of measures, such as closing down vulnerability loopholes,
implementing adequate security processes and procedures and providing technology to help achieve this.
Examples of vulnerabilities are:
● Indiscretions by personnel (users keep passwords on their computer)
● Bad practice (users do not change default passwords, or everyone uses the same password to access all
substation equipment)
● Bypassing of controls (users turn off security measures)
● Inadequate technology (substation is not firewalled)
To help tackle these issues, standards organisations have produced various standards. Compliance with these
standards significantly reduces the threats associated with lack of cyber-security.
404 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
3 STANDARDS
There are several standards, which apply to substation cyber-security. The standards currently applicable to
General Electric IEDs are NERC and IEEE1686.
Standard Country Description
NERC CIP (North American Electric Reliability
USA Framework for the protection of the grid critical Cyber Assets
Corporation)
BDEW (German Association of Energy and Water Requirements for Secure Control and Telecommunication
Germany
Industries) Systems
ICS oriented then Relevant for EPU completing existing standard
ANSI ISA 99 USA
and identifying new topics such as patch management
International Standard for substation IED cyber-security
IEEE 1686 International
capabilities
IEC 62351 International Power system data and Comm. protocol
ISO/IEC 27002 International Framework for the protection of the grid critical Cyber Assets
NIST SP800-53 (National Institute of Standards and
USA Complete framework for SCADA SP800-82and ICS cyber-security
Technology)
CPNI Guidelines (Centre for the Protection of National Clear and valuable good practices for Process Control and SCADA
UK
Infrastructure) security
P64x-TM-EN-4.1 405
Chapter 17 - Cyber-Security P64x
406 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
P64x-TM-EN-4.1 407
Chapter 17 - Cyber-Security P64x
● IED functions and features are assigned to different password levels. The assignment is fixed.
● The audit trail is recorded, listing events in the order in which they occur, held in a circular buffer.
● Records contain all defined fields from the standard and record all defined function event types where the
function is supported.
● No password defeat mechanism exists. Instead a secure recovery password scheme is implemented.
● Unused ports (physical and logical) may be disabled.
408 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
4 CYBER-SECURITY IMPLEMENTATION
General Electric IEDs have always been and will continue to be equipped with state-of-the-art security measures.
Due to the ever-evolving communication technology and new threats to security, this requirement is not static.
Hardware and software security measures are continuously being developed and implemented to mitigate the
associated threats and risks.
From Software Version 90 onwards, the MiCOM P40 Agile products provide enhanced security through the
following features:
● An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS)
client that is managed centrally, enables user attribution, provides accounting of all user activities, and uses
secure standards based on strong cryptography for authentication and credential protection. In other
words, this option uses a RADIUS.
● Server for user authentication. There is provision for both remote (RADIUS) and local (device) authentication.
● A Role-Based Access Control (RBAC) system that provides a permission model that allows access to the
device operations and configurations based on specific roles and individual user accounts configured on
the AAA server. That is, Administrator, Engineer, Operator, and Viewer roles are used.
● Security event reporting through both proprietary event logs and the Syslog protocol for supporting Security
Information Event Management (SIEM) systems for centralised cybersecurity monitoring.
● Encryption of passwords – stored within the IED, in network messages between the MiCOM S1 Agile
software and the IED, and in network messages between the RADIUS server and the IED (subject to the
RADIUS server configuration).
P64x-TM-EN-4.1 409
Chapter 17 - Cyber-Security P64x
5.1 ROLES
The P40 Agile products provide 4 specific roles to which individual user accounts can be configured:
● VIEWER (Level 0) Read some, Write minimal
● OPERATOR (Level 1) Read All, Write Few
● ENGINEER (Level 2) Read All, Write Some
● ADMINISTRATOR (Level 3) Read All, Write All
Only one role of one type is allowed to be logged in at a time. For example, one Operator can be logged in but not
a second Operator at the same time. This prevents subsets of settings from being changed at the same time.
Roles are mapped to Access Level definitions:
VIEWER - No password required - Read access to Security features, Model Number, Serial Number, S/W version,
Description, Plant reference, Security code (UI Only), Encryption key (UI Only), User Banner and security related cells.
This role will allow maximum concurrent access provided by P40. Viewer is the default role
OPERATOR – Operator password required - Read access to all data and settings. Write access to Primary/
Secondary selector, Operator password setting, Password reset cell and log extraction cells (record selector). This
role will not allow concurrent access.
ENGINEER – Engineer password required - Read access to all data and settings. Write access to Reset demands
and counters. This role will not allow concurrent access.
ADMINISTRATOR – Administrator password required - Read access to all data and settings. Write access to All
settings, PSL, IED Config, Security settings (port disabling etc). This role can enable the bypass mode and forcefully
logout any other role. This role will not allow concurrent access.
The IED defines the following roles with reference to the roles defined by IEC 62351-8.
P40 Roles IEC 62351- 8 Roles Access Level
VIEWER VIEWER Level 0
OPERATOR OPERATOR Level 1
ENGINEER ENGINEER Level 2
ADMINISTRATOR SECADM + SECAUD Level 3
By default, the IED is delivered with default factory roles account and passwords. These default passwords are
shown in the below table.
Role Default Password
ADMINISTRATOR ChangeMe1#
ENGINEER ChangeMe1#
OPERATOR ChangeMe1#
VIEWER NA
Note:
It is strongly recommended that the password for the Administrator be changed from the default. Changing the passwords
for the other roles is optional.
410 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
'Firmware lock' is not supported by the P40 Agile IED. Firmware upgrade is not managed by the main software. The
process involves using a dedicated firmware loading software tool. There is no access or control to this process via
the main product firmware.
5.2 PERMISSIONS
Authentication and authorization are two different processes. An authenticated user cannot perform any action on
the IED unless a privilege has been explicit granted to him/her to do so. This is the concept of “least privileges”
access.
Privileges must be granted to users through roles. A role is a collection of privileges, and roles are granted to users.
Each user is associated to only one role. The privilege/role matrix is stored on the IED. This is known as Role-Based-
Access Control (RBAC).
On successful user authentication, the IED will load the user’s role list. If the user’s role changes, the user must
logout and log back in to exercise his/her privileges.
Existing User level/permission mapping in P40 are:
Role Meaning Read Operation Write Operation
SYSTEM DATA column:
Description
Plant Reference
Model Number
Serial Number
S/W Ref.
Read Some
Access Level Password Entry
VIEWER Write
Security Feature LCD Contrast (UI only)
Minimal
SECURITY CONFIG column:
User Banner
Attempts Remain
Blk Time Remain
Fallback PW level
Security Code (UI only)
All data and settings are All items writeable at "Viewer".
Read All
OPERATOR readable. Select Event, Main and Fault (upload)
Write Few
Poll Measurements Extract Events (e.g. via MiCOM S1 Agile)
All items writeable at "Operator".
Setting Cells that change visibility (Visible/Invisible).
Setting Values (Primary/Secondary) selector
Read All All data and settings are
Commands:
ENGINEER Write readable.
Reset Indication
Some Poll Measurements
Reset Demand
Reset Statistics
Reset CB Data / counters
P64x-TM-EN-4.1 411
Chapter 17 - Cyber-Security P64x
412 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
6 AUTHENTICATION
6.2 BYPASS
In Bypass Auth. mode, the IED does not provide security - any user can login. IED does not validate user and
password. The bypass security feature provides an easier access, with no authentication and encryption for
situations when this is considered safe. Only the Administrator can enable Bypass mode.
There are five modes for authentication bypass:
1. Disabled – no interfaces in Bypass Auth. mode (normal authentication is active)
2. Local & Remote
a. Front Panel;
b. Front Port
c. Rear Ports
d. Ethernet
P64x-TM-EN-4.1 413
Chapter 17 - Cyber-Security P64x
6.3 LOGIN
A user can only login through the following methods:
● Front Panel User Interface
● Using MiCOM S1 Agile, connected to either the Front Port, Rear Port 1 or 2, or NIC (Ethernet) interface.
414 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
LOGIN SUCCESS
OPERATOR
LOGIN FAILED
For front panel authentication, this is shown for 2 seconds on the LCD.
For S1 Agile authentication, this is a pop-up dialog that the user must click to acknowledge.
P64x-TM-EN-4.1 415
Chapter 17 - Cyber-Security P64x
If the keypad is inactive for configured UI inactivity timer, user logout message is displayed. And front panel user
interface reverts to the Viewer access level.
Currently in the P40, the inactivity timer for both front port and HMI is fixed to 15 minutes. Already, RP1
InactivTimer and RP2 InactivTimer settings control the inactivity timer for RP1 and RP2. There are two new
settings to support configurable inactivity timer for front port and front panel user interface:
● FP InactvTimer
● UI InactivTimer
Administrator, Operator and Engineer roles will accept only one session to the device at one time. Only Viewer
allows 4 concurrent sessions at one time.
Only one user session is allowed from all the access methods mentioned below:
● Front Panel Push buttons
● Front Port (serial) FP1
● Rear Port 1 (RP1)
● Rear Port 2 (RP2)
● Ethernet Port (NIC)
Minimum
Setting Name Description Min Max Default Units
Permissions
Number of failed authentications before the device blocks
0 (lockout
Attempts Limit subsequent authentication attempts for the lockout period. A 99 3 - Administrator
disabled)
value of 0 means Lockout is disabled.
The period of time in seconds a user is prevented from logging
Lockout Period 1 5940 5 sec Administrator
in, after being locked out.
FP Inactivity Timer is the time of idleness on Front Port before 0 (no
FP InactivTimer a logged in user is automatically logged out and revert the Inactivity 30 10 min Administrator
access level to the viewer role Timeout)
UI Inactivity Timer is the time of idleness on Front Panel 0 (no
UI InactivTimer before a logged in user is automatically logged out and revert Inactivity 30 10 min Administrator
the access level to the viewer role Timeout)
The recommended settings for Attempts Limit is 3 and Lockout Period is 5 sec to discourage brute force
attacks. If the Lockout period is too large, anybody can lockout Device users.
Each user account records how long it has been locked if the account is locked.
Each user account records how many times it has consecutively failed to login. User account failed times include
all interfaces login attempts. For example, if the Attempts Limit setting is 3 and the operator failed to login from
front panel 2 times, and they changed to login from the Courier interface, but failed again, then the Operator
would be locked out.
When the IED is powered on, these Attempts Limit counter resets to zero.
When the user account exceeds the Attempts Limit it is locked for Lockout period, at that time Attempt limit
resets to zero.
The locked user account will be unlocked automatically, after the configured “Lockout Period” is expired.
416 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
All user accounts need to wait until the lockout period expires. No user can unlock the locked account.
If the locked account attempts to login the IED from the Front Panel, the following text is displayed (example):
OPERATOR
IS LOCKED
Usernames are specific to each user account, such as Engineer, Operator and Administrator for Device
authentication.
When supporting both RBAC enabled interfaces and non-RBAC interfaces (such as Modbus), the P40 handles
features such as user-locking feature as follows
● If an RBAC user exceeds the invalid password limit, that user gets locked for all the interfaces.
● On a non-RBAC interface, if an Access Level exceeds the invalid password limit, P40 only blocks that.
6.6 LOGOUT
Each user should Log out after reading or configuring the IED.
Both S1 Agile and the Front Panel provide a one-step logout.
The user can only log out from the front panel, if they logged in from the front panel. If the user logged in from S1
Agile, they have to logout from S1 Agile.
ENTER TO LOGOUT
CLEAR TO CANCEL
If you decide not to log out (i.e. you cancel), the following message is displayed for 2 seconds.
LOGOUT CANCELLED
ADMINISTRATOR
P64x-TM-EN-4.1 417
Chapter 17 - Cyber-Security P64x
Caution:
It is recommended that user passwords are changed periodically.
6.10 RADIUS
When the Auth. Method setting is configured as Server Only or Server + Device, a user must log in with a
username and password that has been predefined on the Radius server.
This log in can be performed from any interface, as described in the Login section. The IED will authenticate the
user to the active RADIUS server, over the Ethernet connection.
Groups User
Access Request
User login RADIUS
IED Client
Access
Accept
(User Role)
User RADIUS Server Active Directory
V01100
418 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
The username must consist of uppercase letters (A to Z) and digits (0 to 9) only. No lowercase letters or special
characters are allowed.
Each RADIUS user must have a password that meets the password policy of the Active Directory (not the password
policy of the P40) and have one of the four roles assigned in the Active Directory.
The number of RADIUS users is not limited by the IED.
RADIUS password changes are done in the Active Directory (after password expiration).
The RADIUS implementation queries the Role ID vendor attribute and establish the logged in user security context
with that role.
RADIUS Config. Value
Vendor ID 2910
Vendor Attribute 1
P40 Role Values
Administrator 3
Engineer 2
Operator 1
Viewer 0
P64x-TM-EN-4.1 419
Chapter 17 - Cyber-Security P64x
Setting Minimum
Description Min Max Default Units
Name Permissions
EAP-TTLS-MSCHAP2
RADIUS Authentication protocol to be used by PAP PAP EAP-TTLS-
- Administrator
Security Radius server. EAP-PEAP-MSCHAP2 PAP
PAP EAP-TTLS-PAP
RADIUS Timeout in seconds between re-
1 900 2 sec Administrator
Timeout transmission requests
RADIUS
Number of retries before giving up 1 99 10 - Administrator
Retries
RADIUS Shared Secret used in authentication. It is
1 character 16 characters ChangeMe1# - Administrator
Secret only displayed as asterisks.
The data cell RADIUS Status indicates the status of the currently-selected RADIUS server. This will display either
Disabled, Server OK, or Failed.
Note:
It is recommended that the shared secret be changed from the default before using Radius authentication.
The IED does not support exchange of CA certificates. The RADIUS server may send a certificate but the IED will not
verify it.
6.11 RECOVERY
420 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
Note:
Restoring defaults to all settings includes the rear communication port settings, which may result in communication via the
rear port being disrupted if the new (default) settings do not match those of the master station.
Data (events, DR, fault records, protection counters etc) is left untouched. When decommissioning critical cyber
IEDs, users may want to clear all data and events as well.
This reset procedure can be only accomplished through front panel exclusively and cannot be done over any other
interface. As soon as the security code is displayed on the front panel User Interface, a validity timer is started. This
validity timer is set to 72 hours and is not configurable. This provides enough time for the Contact Centre to
manually generate and send a recovery password. The Service Level Agreement (SLA) for recovery password
generation is one working day, so 72 hours is sufficient time, even allowing for closure of the Contact Centre over
weekends and bank holidays.
The procedure is:
The security code is displayed on confirmation. The validity timer is then started. The security code can only be
read from the front panel.
This reset procedure can be only accomplished through front panel exclusively and cannot be done over the
Ethernet/serial port, but only when physically present in front of the IED. In the event of losing all passwords (if the
Administrator forgets their password) the user could reset the IED to default passwords, following the procedure
below:
1. User navigates to Security Code cell in SECURITY CONFIG column
2. To prevent accidental reading of the IED Security Code, the cell will initially display a warning message:
PRESS ENTER TO
READ SEC. CODE
P64x-TM-EN-4.1 421
Chapter 17 - Cyber-Security P64x
RESET PASSWORD?
ENTER or CLEAR
Note:
Restoring passwords to defaults does not affect any other settings and does not provoke reboot of the IED. The protection and
control functions of the IED are always maintained.
KEY:
HMI = Human Machine Interface
FPort = Front Port
RPrt = Rear Port
Lvl = Level
422 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
REAR PORT 1 TO BE
DISABLED.CONFIRM
Note:
It is not possible to disable a port from which the disabling port command originates.
We do not generally advise disabling the physical Ethernet port.
Note:
The port disabling setting cells are not provided in the settings file. It is only possible to do this using the HMI front panel.
Note:
If any of these protocols are enabled or disabled, the Ethernet card will reboot.
P64x-TM-EN-4.1 423
Chapter 17 - Cyber-Security P64x
424 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
Each new event has an incremented unique number, therefore missing events appear as gap in the sequence. The
unique identifier forms part of the event record that is read or uploaded from the IED.
Note:
It is no longer possible to clear Event, Fault, Maintenance, and Disturbance Records.
P64x-TM-EN-4.1 425
Chapter 17 - Cyber-Security P64x
7.2 SYSLOG
Security events are also logged to a remote syslog server.
All login and logout attempts from local and central authentication, whether successful or failed, are logged. The
contents of each successful or failed, login and logout security event include a specific username.
The security log cannot be cleaned by any of the available roles.
The contents of each login and/or logout security event include the relevant interface. The following interfaces are
supported:
Interface Abbr.
Front Port FP
Rear Port 1 RP1
Rear Port 2 RP2
Ethernet NET
Front Panel UI
The following events are available to be logged to the syslog server:
Event Categorisation Severity
Login - Authentication successful Informational (6)
Login - Authentication Failure Informational (6)
Logout Informational (6)
RADIUS Server Unavailable Alert (1)
Session timeout Informational (6)
Account Locked Notice (5)
User accessed while locked Notice (5)
ByPass Activate Notice (5)
ByPass Deactivate Notice (5)
Password Change Notice (5)
Recovery password is entered to reset the passwords Notice (5)
Settings / Configuration Changed Notice (5)
Settings / Configuration uploaded
Notice (5)
(to S1 Agile)
Event Records uploaded Notice (5)
Default settings restored Notice (5)
Notice (5)
Notice (5)
Active Setting Group Changed
Notice (5)
Notice (5)
Notice (5)
Default user curves restored
Notice (5)
Notice (5)
426 P64x-TM-EN-4.1
P64x Chapter 17 - Cyber-Security
The IED is a Syslog client that supports two Syslog servers. The following settings are available in the
COMMUNICATIONS column.
Min.
Setting Name Description Min Max Default Units
Permission
The IP address of the target Syslog
SysLog Pri IP 0.0.0.0 223.255.255.254 0.0.0.0 - Administrator
server (Primary)
The IP address of the target Syslog
SysLog Sec IP 0.0.0.0 223.255.255.254 0.0.0.0 - Administrator
server (Secondary)
The UDP port number of the target
SysLog Port 1 65535 514 - Administrator
Syslog server
P64x-TM-EN-4.1 427
Chapter 17 - Cyber-Security P64x
428 P64x-TM-EN-4.1
CHAPTER 18
INSTALLATION
Chapter 18 - Installation P64x
430 P64x-TM-EN-4.1
P64x Chapter 18 - Installation
1 CHAPTER OVERVIEW
This chapter provides information about installing the product.
This chapter contains the following sections:
Chapter Overview 431
Handling the Goods 432
Mounting the Device 433
Cables and Connectors 435
Case Dimensions 440
P64x-TM-EN-4.1 431
Chapter 18 - Installation P64x
Caution:
Before lifting or moving the equipment you should be familiar with the Safety
Information chapter of this manual.
432 P64x-TM-EN-4.1
P64x Chapter 18 - Installation
Caution:
Do not use conventional self-tapping screws, because they have larger heads and could
damage the faceplate.
Alternatively, you can use tapped holes if the panel has a minimum thickness of 2.5 mm.
For applications where the product needs to be semi-projection or projection mounted, a range of collars are
available.
If several products are mounted in a single cut-out in the panel, mechanically group them horizontally or vertically
into rigid assemblies before mounting in the panel.
Caution:
Do not fasten products with pop rivets because this makes them difficult to remove if
repair becomes necessary.
Caution:
Risk of damage to the front cover molding. Do not use conventional self-tapping
screws, including those supplied for mounting MiDOS products because they have
slightly larger heads.
Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of the tier.
P64x-TM-EN-4.1 433
Chapter 18 - Installation P64x
Products can be mechanically grouped into single tier (4U) or multi-tier arrangements using the rack frame. This
enables schemes using products from different product ranges to be pre-wired together before mounting.
Use blanking plates to fill any empty spaces. The spaces may be used for installing future products or because the
total size is less than 80TE on any tier. Blanking plates can also be used to mount ancillary components. The part
numbers are as follows:
434 P64x-TM-EN-4.1
P64x Chapter 18 - Installation
Caution:
Before carrying out any work on the equipment you should be familiar with the Safety
Section and the ratings on the equipment’s rating label.
MiCOM products are supplied with sufficient M4 screws for making connections to the rear mounted terminal
blocks using ring terminals, with a recommended maximum of two ring terminals per terminal.
If required, M4 90° crimp ring terminals can be supplied in three different sizes depending on wire size. Each type is
available in bags of 100.
Part number Wire size Insulation color
ZB9124 901 0.25 - 1.65 mm2 (22 – 16 AWG) Red
ZB9124 900 1.04 - 2.63 mm2 (16 – 14 AWG) Blue
P64x-TM-EN-4.1 435
Chapter 18 - Installation P64x
Caution:
Protect the auxiliary power supply wiring with a maximum 16 A high rupture capacity
(HRC) type NIT or TIA fuse.
Use a wire size of at least 2.5 mm2 terminated with a ring terminal.
Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring
terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced to 2.63
mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each terminated in a
separate ring terminal.
The wire should have a minimum voltage rating of 300 V RMS.
Note:
To prevent any possibility of electrolytic action between brass or copper ground conductors and the rear panel of the product,
precautions should be taken to isolate them from one another. This could be achieved in several ways, including placing a
nickel-plated or insulating washer between the conductor and the product case, or using tinned ring terminals.
Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring
terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced to 2.63
mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each terminated in a
separate ring terminal.
The wire should have a minimum voltage rating of 300 V RMS.
Caution:
Current transformer circuits must never be fused.
Note:
If there are CTs present, spring-loaded shorting contacts ensure that the terminals into which the CTs connect are shorted
before the CT contacts are broken.
Note:
For 5A CT secondaries, we recommend using 2 x 2.5 mm2 PVC insulated multi-stranded copper wire.
436 P64x-TM-EN-4.1
P64x Chapter 18 - Installation
Caution:
Protect the opto-inputs and their wiring with a maximum 16 A high rupture capacity
(HRC) type NIT or TIA fuse.
P64x-TM-EN-4.1 437
Chapter 18 - Installation P64x
Note:
For models equipped with redundant Ethernet connections the product must be partially dismantled to set the fourth octet of
the second IP address. This ideally, should be done before installation.
438 P64x-TM-EN-4.1
P64x Chapter 18 - Installation
must be made using a screened 3-core cable with a total resistance less than 10 Ω. The cable should have a
minimum voltage rating of 300 V RMS.
A 3-core cable should be used even for 2-wire RTD applications, as it allows for the cable’s resistance to be
removed from the overall resistance measurement. In such cases the third wire is connected to the second wire at
the point where the cable is joined to the RTD.
The screen of each cable must only be earthed (grounded) at one end, preferably at the IED end and must be
continuous. Multiple earthing (grounding) of the screen can cause circulating current to flow along the screen. This
induces noise and is also unsafe.
You should minimize the noise pick-up in the RTD cables by keeping them close to earthed (grounded) metal
casings and avoid areas of high electromagnetic and radio interference. The RTD cables should not be run
adjacent to or in the same conduit as other high voltage or current cables.
A typical cable specification would be:
● Each core: 7/0.2 mm copper conductors heat resistant PVC insulated
● Nominal conductor area: 0.22 mm2 per core
● Screen: Nickel-plated copper wire braid heat resistant PVC sheathed
The following extract may be useful in defining cable recommendations for the RTDs:
Noise pick up by cables can be categorized into three types:
● Resistive
● Capacitive
● Inductive
Resistive coupling requires an electrical connection to the noise source. Assuming the wire and cable insulation are
in good condition and the junctions are clean, this can be dismissed. Capacitive coupling requires sufficient
capacitance to the noise source. This is a function of the dielectric strength between the signal cable on the noise
source and the power of the noise source. Inductive coupling occurs when the signal cable is adjacent to a wire
carrying the noise or it is exposed to a radiated EMF.
Standard screened cable is normally used to protect against capacitively-coupled noise. However for this to be
effective, the screen should only be bonded to the system ground at one point. Otherwise a current could flow and
the noise would be coupled into the signal wires of the cable. There are different types of screening available, but
the most commonly used are aluminium foil wrap, or tin-copper braid. Foil screens are good for low to medium
frequencies and braid is good for high frequencies. High-fidelity screen cables provide both types.
Protection against inductive coupling requires careful cable routing and magnetic shielding. The latter can be
achieved with steel-armoured cable and steel cable trays. The cable armour must be grounded at both ends so
the EMF of the induced current cancels the field of the noise source and shields the cables conductors from it.
However, the system ground must be designed such that it does not bridge two isolated ground systems. This
could be hazardous and defeat the objectives of the original grounding design. The cable should be laid in the
cable trays as close as possible to the metal of the tray. Under no circumstance should any power cable be in or
near to the tray. Power cables should only cross the signal cables at 90 degrees and never be adjacent to them.
Both the capacitive and inductive screens must be contiguous from the RTD probes to the IED terminals. The best
types of cable are those provided by the RTD manufacturers. These are usually three conductors, known as a triad,
which are screened with foil. Such triad cables are available in armoured forms as well as multi-triad armoured
forms.
P64x-TM-EN-4.1 439
Chapter 18 - Installation P64x
5 CASE DIMENSIONS
Not all products are available in all case sizes.
AB BA
168.00
177.0
159.00 (4U)
AB BA
200.00
Note: If mouting plate is required
use flush mounting cut out
dimensions
All dimensons in mm
240.00
Front view Incl. wiring
177.00
157.5
max.
C
Side view
206.00 25.00 E01411
Figure 178: 40TE case dimensions
440 P64x-TM-EN-4.1
P64x Chapter 18 - Installation
E01409
P64x-TM-EN-4.1 441
Chapter 18 - Installation P64x
159.00 168.00
407.10
240.00
Incl. wiring
157.5
177.00 max.
SIDE VIEW
413.2
25.00
FRONT VIEW
E01410
Figure 180: 80TE case dimensions
442 P64x-TM-EN-4.1
CHAPTER 19
COMMISSIONING INSTRUCTIONS
Chapter 19 - Commissioning Instructions P64x
444 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
1 CHAPTER OVERVIEW
This chapter contains the following sections:
Chapter Overview 445
General Guidelines 446
Commissioning Test Menu 447
Commissioning Equipment 450
Product Checks 452
Setting Checks 462
IEC 61850 Edition 2 Testing 464
Checking the Differential Element 469
Protection Timing Checks 472
Onload Checks 474
Final Checks 476
P64x-TM-EN-4.1 445
Chapter 19 - Commissioning Instructions P64x
2 GENERAL GUIDELINES
General Electric IEDs are self-checking devices and will raise an alarm in the unlikely event of a failure. This is why
the commissioning tests are less extensive than those for non-numeric electronic devices or electro-mechanical
relays.
To commission the devices, you (the commissioning engineer) do not need to test every function. You need only
verify that the hardware is functioning correctly and that the application-specific software settings have been
applied. You can check the settings by extracting them using the settings application software, or by means of the
front panel interface (HMI panel).
The menu language is user-selectable, so you can change it for commissioning purposes if required.
Note:
Remember to restore the language setting to the customer’s preferred language on completion.
Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or Safety Guide SFTY/4LM as well as the ratings on the
equipment’s rating label.
Warning:
With the exception of the CT shorting contacts check, do not disassemble the device
during commissioning.
446 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Note:
When the Test Mode cell is set to Contacts Blocked, the relay output status indicates which contacts would operate if
the IED was in-service. It does not show the actual status of the output relays, as they are blocked.
Caution:
When the cell is in Test Mode, the Scheme Logic still drives the output relays, which
could result in tripping of circuit breakers. To avoid this, set the Test Mode cell to
Contacts Blocked.
Note:
Test mode and Contacts Blocked mode can also be selected by energising an opto-input mapped to the Test Mode
signal, and the Contact Block signal respectively.
P64x-TM-EN-4.1 447
Chapter 19 - Commissioning Instructions P64x
Note:
When the Test Mode cell is set to Contacts Blocked the Relay O/P Status cell does not show the current status of the
output relays and therefore cannot be used to confirm operation of the output relays. Therefore it will be necessary to monitor
the state of each contact in turn.
Note:
When the status in both Red LED Status and Green LED Status cells is ‘1’, this indicates the LEDs illumination is yellow.
448 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Caution:
The monitor/download port is not electrically isolated against induced voltages on
the communications channel. It should therefore only be used for local
communications.
P64x-TM-EN-4.1 449
Chapter 19 - Commissioning Instructions P64x
4 COMMISSIONING EQUIPMENT
Specialist test equipment is required to commission this product. We recognise three classes of equipment for
commissioning :
● Recommended
● Essential
● Advisory
Recommended equipment constitutes equipment that is both necessary, and sufficient, to verify correct
performance of the principal protection functions.
Essential equipment represents the minimum necessary to check that the product includes the basic expected
protection functions and that they operate within limits.
Advisory equipment represents equipment that is needed to verify satisfactory operation of features that may be
unused, or supplementary, or which may, for example, be integral to a distributed control/automation scheme.
Operation of such features may, perhaps, be more appropriately verified as part of a customer defined
commissioning requirement, or as part of a system-level commissioning regime.
450 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
P64x-TM-EN-4.1 451
Chapter 19 - Commissioning Instructions P64x
5 PRODUCT CHECKS
These product checks are designed to ensure that the device has not been physically damaged prior to
commissioning, is functioning correctly and that all input quantity measurements are within the stated tolerances.
If the application-specific settings have been applied to the IED prior to commissioning, you should make a copy of
the settings. This will allow you to restore them at a later date if necessary. This can be done by:
● Obtaining a setting file from the customer.
● Extracting the settings from the IED itself, using a portable PC with appropriate setting software.
If the customer has changed the password that prevents unauthorised changes to some of the settings, either the
revised password should be provided, or the original password restored before testing.
Note:
If the password has been lost, a recovery password can be obtained from General Electric.
Warning:
The following group of tests should be carried out without the auxiliary supply being
applied to the IED and, if applicable, with the trip circuit isolated.
The current and voltage transformer connections must be isolated from the IED for these checks. If a P991 test
block is provided, the required isolation can be achieved by inserting test plug type P992. This open circuits all
wiring routed through the test block.
Before inserting the test plug, you should check the scheme diagram to ensure that this will not cause damage or
a safety hazard (the test block may, for example, be associated with protection current transformer circuits). The
sockets in the test plug, which correspond to the current transformer secondary windings, must be linked before
the test plug is inserted into the test block.
Warning:
Never open-circuit the secondary circuit of a current transformer since the high
voltage produced may be lethal and could damage insulation.
If a test block is not provided, the voltage transformer supply to the IED should be isolated by means of the panel
links or connecting blocks. The line current transformers should be short-circuited and disconnected from the IED
terminals. Where means of isolating the auxiliary supply and trip circuit (for example isolation links, fuses and MCB)
are provided, these should be used. If this is not possible, the wiring to these circuits must be disconnected and the
exposed ends suitably terminated to prevent them from being a safety hazard.
452 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Warning:
Check the rating information under the top access cover on the front of the IED.
Warning:
Check that the IED being tested is correct for the line or circuit.
Warning:
Record the circuit reference and system details.
Warning:
Check the CT secondary current rating and record the CT tap which is in use.
Carefully examine the IED to see that no physical damage has occurred since installation.
Ensure that the case earthing connections (bottom left-hand corner at the rear of the IED case) are used to
connect the IED to a local earth bar using an adequate conductor.
Note:
Use a magnetic bladed screwdriver to minimise the risk of the screws being left in the terminal block or lost.
Pull the terminal block away from the rear of the case and check with a continuity tester that all the shorting
switches being used are closed.
5.1.3 INSULATION
Insulation resistance tests are only necessary during commissioning if explicitly requested.
Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation tester at a DC
voltage not exceeding 500 V. Terminals of the same circuits should be temporarily connected together.
The insulation resistance should be greater than 100 MW at 500 V.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the IED.
Caution:
Check that the external wiring is correct according to the relevant IED and scheme
diagrams. Ensure that phasing/phase rotation appears to be as expected.
P64x-TM-EN-4.1 453
Chapter 19 - Commissioning Instructions P64x
Note:
The IED can withstand an AC ripple of up to 12% of the upper rated voltage on the DC auxiliary supply.
Warning:
Do not energise the IED or interface unit using the battery charger with the battery
disconnected as this can irreparably damage the power supply circuitry.
Caution:
Energise the IED only if the auxiliary supply is within the specified operating ranges.
If a test block is provided, it may be necessary to link across the front of the test plug
to connect the auxiliary supply to the IED.
Warning:
The current and voltage transformer connections must remain isolated from the IED
for these checks. The trip circuit should also remain isolated to prevent accidental
operation of the associated circuit breaker.
The following group of tests verifies that the IED hardware and software is functioning correctly and should be
carried out with the supply applied to the IED.
454 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Caution:
Before applying a contrast setting, make sure that it will not make the display so
light or dark such that menu text becomes unreadable. It is possible to restore the
visibility of a display by downloading a setting file, with the LCD Contrast set within
the typical range of 7 - 11.
Note:
If the auxiliary supply fails, the time and date will be maintained by the supercapacitor. Therefore, when the auxiliary supply is
restored, you should not have to set the time and date again. To test this, remove the IRIG-B signal, and then remove the
auxiliary supply. Leave the device de-energised for approximately 30 seconds. On re energisation, the time should be correct.
When using IRIG-B to maintain the clock, the IED must first be connected to the satellite clock equipment (usually a
P594/RT430), which should be energised and functioning.
1. Set the IRIG-B Sync cell in the DATE AND TIME column to Enabled.
2. Ensure the IED is receiving the IRIG-B signal by checking that cell IRIG-B Status reads Active.
3. Once the IRIG-B signal is active, adjust the time offset of the universal co coordinated time (satellite clock
time) on the satellite clock equipment so that local time is displayed.
4. Check that the time, date and month are correct in the Date/Time cell. The IRIG-B signal does not contain
the current year so it will need to be set manually in this cell.
5. Reconnect the IRIG-B signal.
If the time and date is not being maintained by an IRIG-B signal, ensure that the IRIG-B Sync cell in the DATE AND
TIME column is set to Disabled.
1. Set the date and time to the correct local time and date using Date/Time cell or using the serial protocol.
P64x-TM-EN-4.1 455
Chapter 19 - Commissioning Instructions P64x
If any of these LEDs are ON then they should be reset before proceeding with further testing. If the LEDs
successfully reset (the LED goes off), no testing is needed for that LED because it is obviously operational.
456 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Please refer to the wiring diagrams for details of the terminal connections.
1. You should connect a 100 ohm resistor across each RTD in turn. The resistor needs to have a very small
tolerance (0.1%). You must connect the RTD common return terminal to the correct RTD input, otherwise the
device will report an RTD error.
2. Check that the corresponding temperature displayed in the MEASUREMENTS 3 column of the menu is 0°C
+/-2°C. This range takes into account the 0.1% resistor tolerance and device accuracy of +/-1°C. If a resistor
of lower accuracy is used during testing, the acceptable setting range needs to be increased.
P64x-TM-EN-4.1 457
Chapter 19 - Commissioning Instructions P64x
For K-Bus applications, pins 17 and 18 are not polarity sensitive and it does not matter which way round the wires
are connected. EIA(RS)485 is polarity sensitive, so you must ensure the wires are connected the correct way round
(pin 18 is positive, pin 17 is negative).
If K-Bus is being used, a Kitz protocol converter (KITZ101, KITZ102 OR KITZ201) will have been installed to convert
the K-Bus signals into RS232. Likewise, if RS485 is being used, an RS485-RS232 converter will have been installed.
In the case where a protocol converter is being used, a laptop PC running appropriate software (such as MiCOM S1
Agile) can be connected to the incoming side of the protocol converter. An example for K-bus to RS232 conversion
is shown below. RS485 to RS232 would follow the same principle, only using a RS485-RS232 converter. Most
modern laptops have USB ports, so it is likely you will also require a RS232 to USB converter too.
458 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
C C C
RS232 K-Bus
Fibre Connection
Some models have an optional fibre optic communications port fitted (on a separate communications board). The
communications port to be used is selected by setting the Physical Link cell in the COMMUNICATIONS column, the
values being Copper or K-Bus for the RS485/K-bus port and Fibre Optic for the fibre optic port.
P64x-TM-EN-4.1 459
Chapter 19 - Commissioning Instructions P64x
Note:
If a PC connected to the IED using the rear communications port is being used to display the measured current, the process
will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will determine whether the
displayed values are in primary or secondary Amperes.
The measurement accuracy of the IED is +/- 1%. However, an additional allowance must be made for the accuracy
of the test equipment being used.
460 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Note:
If a PC connected to the IED using the rear communications port is being used to display the measured current, the process
will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will determine whether the
displayed values are in primary or secondary Amperes.
The measurement accuracy of the IED is +/- 1%. However, an additional allowance must be made for the accuracy
of the test equipment being used.
P64x-TM-EN-4.1 461
Chapter 19 - Commissioning Instructions P64x
6 SETTING CHECKS
The setting checks ensure that all of the application-specific settings (both the IED’s function and programmable
scheme logic settings) have been correctly applied.
Note:
If applicable, the trip circuit should remain isolated during these checks to prevent accidental operation of the associated
circuit breaker.
Note:
The device name may not already exist in the system shown in System Explorer. In this case, perform a Quick Connect to the
IED, then manually add the settings file to the device name in the system. Refer to the Settings Application Software help for
details of how to do this.
462 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
8. Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is
automatically discarded if it is not confirmed within 15 seconds.
9. For protection group settings and disturbance recorder settings, the changes must be confirmed before
they are used. When all required changes have been entered, return to the column heading level and press
the down cursor key. Before returning to the default display, the following prompt appears.
Update settings?
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
Note:
If the menu time-out occurs before the setting changes have been confirmed, the setting values are also discarded.
Control and support settings are updated immediately after they are entered, without the Update settings prompt.
It is not possible to change the PSL using the IED’s front panel HMI.
Caution:
Where the installation needs application-specific PSL, the relevant .psl files, must be
transferred to the IED, for each and every setting group that will be used. If you do
not do this, the factory default PSL will still be resident. This may have severe
operational and safety consequences.
P64x-TM-EN-4.1 463
Chapter 19 - Commissioning Instructions P64x
The following table summarises the IED behaviour under the different modes:
IED Test Mode Setting Result
Disabled ● Normal IED behaviour
● Protection remains enabled
● Output from the device is still active
Test ● IEC 61850 message output has the 'quality' parameter set to 'test'
● The device only responds to IEC61850 MMS messages from the client with the
'test' flag set
● Protection remains enabled
● Output from the device is disabled
Contacts Blocked ● IEC 61850 message output has quality set to ‘test’
● The device only responds to IEC 61850 MMS messages from the client with the
'test' flag set
Setting the Test or Contacts Blocked mode puts the whole IED into test mode. The IEC 61850 data object Beh in all
Logical Nodes (except LPHD and any protection Logical Nodes that have Beh = 5 (off) due to the function being
disabled) will be set to 3 (test) or 4 (test/blocked) as applicable.
464 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
LPHD1
Incoming data
processed
Real GOOSE 2 messages
Reception buffer
V01058
P64x-TM-EN-4.1 465
Chapter 19 - Commissioning Instructions P64x
Station/Process Bus
q = test No output
Yard Yard
SC MU1 Switchgear
MU1 MU1
Test Test
Device Device
V01062
466 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Station/Process Bus
Simulated q = test No output
values
Yard Yard
Test
Device SC MU1 Switchgear
MU1 MU1
V01063
P64x-TM-EN-4.1 467
Chapter 19 - Commissioning Instructions P64x
Station/Process Bus
Simulated q = test Trip output
values
Yard Yard
Test
Device SC MU1 Switchgear
MU1 MU1
V01064
Note:
When the IED Test Mode cell is set to Contacts Blocked, the Relay O/P Status cell does not show the current status of the
output relays so cannot be used to confirm operation of the output relays. Therefore it is necessary to monitor the state of
each contact in turn.
468 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Note:
If this test has been successfully performed there is no need to carry out the tests described in the protection timing checks
section.
P64x-TM-EN-4.1 469
Chapter 19 - Commissioning Instructions P64x
V01503
V01504
470 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
I2f/Idiff [%]
V01505
P64x-TM-EN-4.1 471
Chapter 19 - Commissioning Instructions P64x
Note:
If using the default PSL, use output relay 3 as this is already mapped to the DDB signal Trip Command Out.
4. Connect the output relay so that its operation will trip the test set and stop the timer.
5. Connect the current output of the test set to the A-phase current transformer input.
If the I>1 Directional cell in the OVERCURRENT column is set to Directional Fwd, the current should
flow out of terminal 2. If set to Directional Rev, it should flow into terminal 2.
If the I>1 Directional cell in the OVERCURRENT column has been set to Directional Fwd or
Directional Rev, the rated voltage should be applied to terminals 20 and 21.
6. Ensure that the timer starts when the current is applied.
Note:
If the timer does not stop when the current is applied and stage 1 has been set for directional operation, the connections may
be incorrect for the direction of operation set. Try again with the current connections reversed.
472 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
Note:
With the exception of the definite time characteristic, the operating times given are for a Time Multiplier Setting (TMS) or Time
Dial Setting (TDS) of 1. For other values of TMS or TDS, the values need to be modified accordingly.
Note:
For definite time and inverse characteristics there is an additional delay of up to 0.02 second and 0.08 second respectively.
You may need to add this the IED's acceptable range of operating times.
Caution:
On completion of the tests, you must restore all settings to customer specifications.
P64x-TM-EN-4.1 473
Chapter 19 - Commissioning Instructions P64x
10 ONLOAD CHECKS
Warning:
Onload checks are potentially very dangerous and may only be carried out by
qualified and authorised personnel.
Onload checks can only be carried out if there are no restrictions preventing the energisation of the plant, and the
other devices in the group have already been commissioned.
Remove all test leads and temporary shorting links, then replace any external wiring that has been removed to
allow testing.
Warning:
If any external wiring has been disconnected for the commissioning process, replace
it in accordance with the relevant external connection or scheme diagram.
474 P64x-TM-EN-4.1
P64x Chapter 19 - Commissioning Instructions
If the Local Values cell is set to Secondary, the values displayed should be equal to the applied secondary
voltage. The values should be within 1% of the applied secondary voltages. However, an additional allowance must
be made for the accuracy of the test equipment being used.
If the Local Values cell is set to Primary, the values displayed should be equal to the applied secondary voltage
multiplied the corresponding voltage transformer ratio set in the CT & VT RATIOS column. The values should be
within 1% of the expected values, plus an additional allowance for the accuracy of the test equipment being used.
Note:
This check applies only for Measurement Modes 0 (default), and 2. This should be checked in the MEASURE’T. SETUP column
(Measurement Mode = 0 or 2). If measurement modes 1 or 3 are used, the expected power flow signing would be opposite to
that shown above.
In the event of any uncertainty, check the phase angle of the phase currents with respect to their phase voltage.
P64x-TM-EN-4.1 475
Chapter 19 - Commissioning Instructions P64x
11 FINAL CHECKS
1. Remove all test leads and temporary shorting leads.
2. If you have had to disconnect any of the external wiring in order to perform the wiring verification tests,
replace all wiring, fuses and links in accordance with the relevant external connection or scheme diagram.
3. The settings applied should be carefully checked against the required application-specific settings to ensure
that they are correct, and have not been mistakenly altered during testing.
4. Ensure that all protection elements required have been set to Enabled in the CONFIGURATION column.
5. Ensure that the IED has been restored to service by checking that the Test Mode cell in the COMMISSION
TESTS column is set to Disabled.
6. If the IED is in a new installation or the circuit breaker has just been maintained, the circuit breaker
maintenance and current counters should be zero. These counters can be reset using the Reset All Values
cell. If the required access level is not active, the device will prompt for a password to be entered so that the
setting change can be made.
7. If the menu language has been changed to allow accurate testing it should be restored to the customer’s
preferred language.
8. If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the cover so that the
protection is put into service.
9. Ensure that all event records, fault records, disturbance records, alarms and LEDs and communications
statistics have been reset.
Note:
Remember to restore the language setting to the customer’s preferred language on completion.
476 P64x-TM-EN-4.1
CHAPTER 20
478 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
1 CHAPTER OVERVIEW
The Maintenance and Troubleshooting chapter provides details of how to maintain and troubleshoot products
based on the Px4x and P40Agile platforms. Always follow the warning signs in this chapter. Failure to do so may
result injury or defective equipment.
Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on the
equipment’s rating label.
The troubleshooting part of the chapter allows an error condition on the IED to be identified so that appropriate
corrective action can be taken.
If the device develops a fault, it is usually possible to identify which module needs replacing. It is not possible to
perform an on-site repair to a faulty module.
If you return a faulty unit or module to the manufacturer or one of their approved service centres, you should
include a completed copy of the Repair or Modification Return Authorization (RMA) form.
This chapter contains the following sections:
Chapter Overview 479
Maintenance 480
Troubleshooting 488
Repair and Modification Procedure 492
P64x-TM-EN-4.1 479
Chapter 20 - Maintenance and Troubleshooting P64x
2 MAINTENANCE
Although some functionality checks can be performed from a remote location, these are predominantly restricted
to checking that the unit is measuring the applied currents and voltages accurately, and checking the circuit
breaker maintenance counters. For this reason, maintenance checks should also be performed locally at the
substation.
Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on the
equipment’s rating label.
2.1.1 ALARMS
First check the alarm status LED to see if any alarm conditions exist. If so, press the Read key repeatedly to step
through the alarms.
After dealing with any problems, clear the alarms. This will clear the relevant LEDs.
2.1.2 OPTO-ISOLATORS
Check the opto-inputs by repeating the commissioning test detailed in the Commissioning chapter.
480 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
Caution:
Replacing PCBs requires the correct on-site environment (clean and dry) as well as
suitably trained personnel.
Caution:
If the repair is not performed by an approved service centre, the warranty will be
invalidated.
Caution:
Before carrying out any work on the equipment, you should be familiar with the
contents of the Safety Information section of this guide or the Safety Guide SFTY/4LM,
as well as the ratings on the equipment’s rating label. This should ensure that no
damage is caused by incorrect handling of the electronic components.
Warning:
Before working at the rear of the device, isolate all voltage and current supplying it.
Note:
The current transformer inputs are equipped with integral shorting switches which will close for safety reasons, when the
terminal block is removed.
P64x-TM-EN-4.1 481
Chapter 20 - Maintenance and Troubleshooting P64x
Caution:
If the top and bottom access covers have been removed, some more screws with
smaller diameter heads are made accessible. Do NOT remove these screws, as they
secure the front panel to the device.
Note:
There are four possible types of terminal block: RTD/CLIO input, heavy duty, medium duty, and MiDOS. The terminal blocks are
fastened to the rear panel with slotted or cross-head screws depending on the type of terminal block. Not all terminal block
types are present on all products.
Warning:
Before removing the front panel to replace a PCB, you must first remove the auxiliary
power supply and wait 5 seconds for the internal capacitors to discharge. You should
also isolate voltage and current transformer connections and trip circuit.
482 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
Caution:
Before removing the front panel, you should be familiar with the contents of the Safety
Information section of this guide or the Safety Guide SFTY/4LM, as well as the ratings
on the equipment’s rating label.
Caution:
Do not remove the screws with the larger diameter heads which are accessible when
the access covers are fitted and open. These screws hold the relay in its mounting
(panel or cubicle).
Caution:
The internal circuitry is now exposed and is not protected against electrostatic
discharge and dust ingress. Therefore ESD precautions and clean working conditions
must be maintained at all times.
Note:
To ensure compatibility, always replace a faulty PCB with one of an identical part number.
P64x-TM-EN-4.1 483
Chapter 20 - Maintenance and Troubleshooting P64x
Note:
After replacing the main processor board, all the settings required for the application need to be re-entered. This may be done
either manually or by downloading a settings file.
V01601
484 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
6. Fit the replacement PCB carefully into the correct slot. Make sure it is pushed fully back and that the
securing screws are refitted.
7. Reconnect all connections at the rear.
8. Refit the front panel.
9. Refit and close the access covers then press the hinge assistance T-pieces so they click back into the front
panel moulding.
10. Once the unit has been reassembled, commission it according to the Commissioning chapter.
Caution:
With non-mounted IEDs, the case needs to be held firmly while the module is
withdrawn. Withdraw the input module with care as it suddenly comes loose once the
friction of the terminal blocks is overcome.
Note:
If individual boards within the input module are replaced, recalibration will be necessary. We therefore recommend
replacement of the complete module to avoid on-site recalibration.
Caution:
Before removing the front panel, you should be familiar with the contents of the Safety
Information section of this guide or the Safety Guide SFTY/4LM, as well as the ratings
on the equipment’s rating label.
P64x-TM-EN-4.1 485
Chapter 20 - Maintenance and Troubleshooting P64x
The power supply board is fastened to an output relay board with push fit nylon pillars. This doubled-up board is
secured on the extreme left hand side, looking from the front of the unit.
1. Remove front panel.
2. Pull the power supply module forward, away from the rear terminal blocks and out of the case. A
reasonable amount of force is needed due to the friction between the contacts of the terminal blocks.
3. Separate the boards by pulling them apart carefully. The power supply board is the one with two large
electrolytic capacitors.
4. Before reassembling the module, check that the number on the round label next to the front edge of the
PCB matches the slot number into which it will be fitted. If the slot number is missing or incorrect, write the
correct slot number on the label
5. Reassemble the module with a replacement PCB. Push the inter-board connectors firmly together. Fit the
four push fit nylon pillars securely in their respective holes in each PCB.
6. Slot the power supply module back into the housing. Push it fully back onto the rear terminal blocks.
7. Refit the front panel.
8. Refit and close the access covers then press the hinge assistance T-pieces so they click back into the front
panel moulding.
9. Once the unit has been reassembled, commission it according to the Commissioning chapter.
2.6 RECALIBRATION
Recalibration is not needed when a PCB is replaced, unless it is one of the boards in the input module. If any of the
boards in the input module is replaced, the unit must be recalibrated.
Although recalibration is needed when a board inside the input module is replaced, it is not needed if the input
module is replaced in its entirety.
Although it is possible to carry out recalibration on site, this requires special test equipment and software. We
therefore recommend that the work be carried out by the manufacturer, or entrusted to an approved service
centre.
486 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
2.7 CLEANING
Warning:
Before cleaning the device, ensure that all AC and DC supplies and transformer
connections are isolated, to prevent any chance of an electric shock while cleaning.
Only clean the equipment with a lint-free cloth dampened with clean water. Do not use detergents, solvents or
abrasive cleaners as they may damage the product's surfaces and leave a conductive residue.
P64x-TM-EN-4.1 487
Chapter 20 - Maintenance and Troubleshooting P64x
3 TROUBLESHOOTING
488 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
P64x-TM-EN-4.1 489
Chapter 20 - Maintenance and Troubleshooting P64x
490 P64x-TM-EN-4.1
P64x Chapter 20 - Maintenance and Troubleshooting
P64x-TM-EN-4.1 491
Chapter 20 - Maintenance and Troubleshooting P64x
If required, an acceptance of the quote must be delivered before going to the next stage.
5. Send the product to the repair centre
○ Address the shipment to the repair centre specified by your local contact
○ Make sure all items are packaged in an anti-static bag and foam protection
○ Make sure a copy of the import invoice is attached with the returned unit
○ Make sure a copy of the RMA form is attached with the returned unit
○ E-mail or fax a copy of the import invoice and airway bill document to your local contact.
492 P64x-TM-EN-4.1
CHAPTER 21
TECHNICAL SPECIFICATIONS
Chapter 21 - Technical Specifications P64x
494 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
1 CHAPTER OVERVIEW
This chapter describes the technical specifications of the product.
This chapter contains the following sections:
Chapter Overview 495
Interfaces 496
Performance of Transformer Differential Protection and Monitoring Functions 499
Performance of Current Protection Functions 501
Performance of Voltage Protection Functions 504
Performance of Frequency Protection Functions 505
Performance of Monitoring and Control Functions 506
Measurements and Recording 508
Regulatory Compliance 510
Mechanical Specifications 511
Ratings 512
Power Supply 513
Input / Output Connections 515
Environmental Conditions 517
Type Tests 518
Electromagnetic Compatibility 519
P64x-TM-EN-4.1 495
Chapter 21 - Technical Specifications P64x
2 INTERFACES
496 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
P64x-TM-EN-4.1 497
Chapter 21 - Technical Specifications P64x
498 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
Accuracy
Pick-up Formula +/-5% or 20 mA, whichever is greater
Drop-off 0.95 x formula +/- 5%
Pick-up and drop-off repeatability < 1%
Low set differential element operate time (High
< 33 ms (currents applied at 1.2x pickup level or higher)
Break contact)
Low set differential element operate time (Standard
< 36 ms (currents applied at 1.2x pickup level or higher)
Contact)
High set 1 differential element operate time
< 15 ms (currents applied at 2x pickup level or higher)
(Transient Bias disabled)
High set 2 differential element operate time
< 25 ms (currents applied at 2x pickup level or higher)
(High Break contact)
< 33 ms, whichever is greater (currents applied at 1.2x pickup level or
DT operate time (High Break contact)
higher
< 36 ms, whichever is greater (currents applied at 1.2x pickup level or
DT operate time (Standard contact)
higher
Operate time repeatability < 2 ms
Disengagement time < 15 ms
2nd harmonic blocking pick-up Setting +/-5% of setting
2nd harmonic blocking drop-off 0.95 x setting +/-5%
5th harmonic blocking pick-up Setting +/-5% of setting
5th harmonic blocking drop-off 0.95 x setting +/-5%
P64x-TM-EN-4.1 499
Chapter 21 - Technical Specifications P64x
500 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
Accuracy
Additional tolerance due to increasing X/R ratios +/-5% over the X/R ratio of 1 to 120
Overshoot of overcurrent elements < 40 ms
Disengagement time < 30 ms
Accuracy
IDMT pick-up 1.05 x Setting +/-5%
DT pick-up Setting +/-5% or 20 mA, whichever is greater
Drop-off (IDMT and DT) 0.95 x setting +/-5% or 20 mA, whichever is greater
IDMT operate +/-5% of expected operating time or 40 ms, whichever is greater
IEEE reset +/-5% or 50 ms, whichever is greater
DT operate +/-2% of setting or 50 ms, whichever is greater
DT reset Setting +/-5%
Characteristic UK IEC 60255-3 1998
Characteristic US IEEE C37.112 1996
Accuracy
Directional boundary pickup (RCA +/-90%) +/-2°
Directional boundary hysteresis < 3°
Directional boundary repeatability <1%
Directional voltage pick-up +/-5% or 50 mV, whichever is greater
Directional voltage drop-off 0.95 x setting +/-5% or 50 mV, whichever is greater
Directional voltage repeatability <3%
Accuracy
Voltage threshold pick-up Setting +/- 5%
Voltage threshold drop-off 1.05 x setting +/- 5%
Current threshold pick-up Formula +/- 5%
Current threshold drop-off 0.95 x formula +/- 5%
Accuracy
IDMT pick-up 1.05 x Setting +/-5%
P64x-TM-EN-4.1 501
Chapter 21 - Technical Specifications P64x
Accuracy
DT pick-up Setting +/-5%, or 20 mA, whichever is greater
Measured drop-off (IDMT and DT) 0.95 x setting +/-5% or 20 mA, whichever is greater
Derived drop-off (IDMT and DT) 0.9 x setting +/-5% or 20 mA, whichever is greater
IDMT Operate +/-5% or 40 ms, whichever is greater*
IEEE reset +/-5% or 40 ms, whichever is greater
Pick-up and drop-off repeatability < 2%
DT operate time +/-2% or 50 ms, whichever is greater
DT reset time +/- 5%
Note:
Reference conditions: TMS = 1, TD = 1, IN> = 1A, operating range = 2-16In
502 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
P64x-TM-EN-4.1 503
Chapter 21 - Technical Specifications P64x
504 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
P64x-TM-EN-4.1 505
Chapter 21 - Technical Specifications P64x
506 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
P64x-TM-EN-4.1 507
Chapter 21 - Technical Specifications P64x
8.1 GENERAL
CLIO
Current loop input accuracy +/- 1% of full scale
Current loop input drop-off under threshold Setting +/- 1% of full scale
Current loop input drop-off over threshold Setting +/- 1% of full scale
Current loop input sampling interval 50 ms
508 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
CLIO
20 Hz to 70 Hz: +/- 2% setting or 150 ms, whichever is greater
Current loop input DT operate time
5 Hz to 20 Hz: +/- 2% setting or 200 ms, whichever is greater
20 Hz to 70 Hz: < 200 ms, whichever is greater
Current loop input instantaneous operate time
5 Hz to 20 Hz: < 300 ms, whichever is greater
Current loop output conversion interval 50 mS
< 1.07 s (1 s refresh rate)
Current loop output latency
< 70 ms (0.5 cycle refresh rate)
Current loop output accuracy +/- 5% of full scale
Repeatability < 5%
< 4 kohms (0-1 mA)
Current loop input load resistance
< 300 ohms (0-10 mA / 0-20mA / 4-20mA)
Isolation between input channels and case/earth/other
2 kV RMS for 1 minute
circuits
10 V (0-1 mA / 0-10 mA)
Current loop output compliance voltage
8.8V (0-20 mA / 4-20 mA)
Current loop output open circuit voltage < 15V
P64x-TM-EN-4.1 509
Chapter 21 - Technical Specifications P64x
9 REGULATORY COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated using a technical file.
510 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
10 MECHANICAL SPECIFICATIONS
40TE
Case Types* 60TE
80TE
Weight (40TE case) 7 kg – 8 kg (depending on chosen options)
Weight (60TE case) 9 kg – 12 kg (depending on chosen options)
Weight (80TE case) 13 kg - 16 kg (depending on chosen options)
Dimensions in mm (w x h x l) (40TE case) W: 206.0 mm H: 177.0 mm D: 243.1 mm
Dimensions in mm (w x h x l) (60TE case) W: 309.6 mm H: 177.0 mm D: 243.1 mm
Dimensions in mm (w x h x l) (80TE case) W 413.2 mm H 177.0 mm D 243.1 mm
Mounting Panel, rack, or retrofit
Note:
*Case size is product dependent.
Against dust and dripping water (front face) IP52 as per IEC 60529:1989/A2:2013
Protection against dust (whole case) IP50 as per IEC 60529:1989/A2:2013
Protection for sides of the case (safety) IP30 as per IEC 60529:1989/A2:2013
Protection for rear of the case (safety) IP10 as per IEC 60529:1989/A2:2013
P64x-TM-EN-4.1 511
Chapter 21 - Technical Specifications P64x
11 RATINGS
AC Measuring Inputs
Nominal frequency 50 Hz or 60 Hz (settable)
Operating range 45 to 65 Hz
Phase rotation ABC or CBA
Note:
* A single input is used for both 1A and 5A applications. 1 A or 5 A operation is determined by means of software in the
product’s database.
Note:
These specifications are applicable to all CTs.
AC Voltage Inputs
Nominal voltage 100 V to 120 V
Nominal burden per phase < 0.06 VA at Vn
2 x Vn (continuous operation)
Thermal withstand
2.6 x Vn (for 10 seconds)
Linear up to 200 V (100/120 V supply)
Linearity
Linear up to 800 V (380/400 V supply)
512 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
12 POWER SUPPLY
Quiescent burden 11 W
2nd rear communications port 1.25 W
Each relay output burden 0.13 W per output relay
Each opto-input burden (24 – 27 V) 0.065 W max
Each opto-input burden (30 – 34 V) 0.065 W max
Each opto-input burden (48 – 54 V) 0.125 W max
Each opto-input burden (110 – 125 V) 0.36 W max
Each opto-input burden (220 – 250 V) 0.9 W max
P64x-TM-EN-4.1 513
Chapter 21 - Technical Specifications P64x
20 ms at 87 V (half load)
50 ms at 110 V (half load)
50 ms at 98 V (full load)
110-250V DC SUPPLY
100 ms at 160 V (half load)
100% interruption without de-energising
100 ms at 135 V (full load)
200 ms at 210 V (half load)
200 ms at 174 V (full load)
40-100V AC SUPPLY 50 ms at 32 V (half load)
100% voltage dip without de-energising 10 ms at 32 V (full load)
100-240V AC SUPPLY
50 ms at 80 V (full and half load)
100% voltage dip without de-energising
Note:
Maximum loading = all inputs/outputs energised.
Note:
Quiescent or 1/2 loading = 1/2 of all inputs/outputs energised.
12.4 SUPERCAPACITOR
514 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
Nominal battery
Logic levels: 60-80% DO/PU Logic Levels: 50-70% DO/PU Logic Levels: 58-75% DO/PU
voltage
24/27 V Logic 0 < 16.2V, Logic 1 > 19.2V Logic 0 <12V, Logic 1 > 16.8V Logic 0 <15.7V, Logic 1 > 18V
30/34 Logic 0 < 20.4V, Logic 1 > 24V Logic 0 < 15V, Logic 1 > 21V Logic 0 < 19.7V, Logic 1 > 22.5V
48/54 Logic 0 < 32.4V, Logic 1 > 38.4V Logic 0 < 24V, Logic 1 > 33.6V Logic 0 < 31.3V, Logic 1 > 36V
110/125 Logic 0 < 75V, Logic 1 > 88V Logic 0 < 55.V, Logic 1 > 77V Logic 0 < 72.5V, Logic 1 > 82.5V
220/250 Logic 0 < 150V, Logic 1 > 176V Logic 0 < 110V, Logic 1 > 154V Logic 0 < 145V, Logic 1 > 165V
Note:
Filter is required to make the opto-inputs immune to induced AC voltages.
P64x-TM-EN-4.1 515
Chapter 21 - Technical Specifications P64x
Make, carry and break ac inductive 10 A for 1.5 s, 10000 operations (subject to the above limits)
Loaded contact 10000 operations min.
Unloaded contact 100000 operations min.
Operate time < 5 ms
Reset time < 10 ms
516 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
14 ENVIRONMENTAL CONDITIONS
P64x-TM-EN-4.1 517
Chapter 21 - Technical Specifications P64x
15 TYPE TESTS
15.1 INSULATION
Note:
Exceptions are communications ports and normally-open output contacts, where applicable.
518 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
16 ELECTROMAGNETIC COMPATIBILITY
P64x-TM-EN-4.1 519
Chapter 21 - Technical Specifications P64x
520 P64x-TM-EN-4.1
P64x Chapter 21 - Technical Specifications
Note:
Compliance is achieved using the opto-input filter.
P64x-TM-EN-4.1 521
Chapter 21 - Technical Specifications P64x
522 P64x-TM-EN-4.1
APPENDIX A
ORDERING OPTIONS
Appendix A - Ordering Options P64x
524 P64x-TM-EN-4.1
P64x Appendix A - Ordering Options
P64x-TM-EN-4.1 A1
Appendix A - Ordering Options P64x
A2 P64x-TM-EN-4.1
P64x Appendix A - Ordering Options
P64x-TM-EN-4.1 A3
Appendix A - Ordering Options P64x
A4 P64x-TM-EN-4.1
APPENDIX B
526 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B1
Appendix B - Settings and Signals P64x
B2 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B3
Appendix B - Settings and Signals P64x
B4 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B5
Appendix B - Settings and Signals P64x
B6 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B7
Appendix B - Settings and Signals P64x
B8 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
Start Elements3 01 0A 0 (For fault record use only. The associated Modbus
registers cannot be accessed unless a fault record is
selected.)
Data Format as per data type G27.
V/Hz> Alm Start1
V/Hz>1 Start1
V/Hz>2 Start1
V/Hz>3 Start1
V/Hz>4 Start1
V/Hz> Alm Start2
V/Hz>1 Start2
P64x-TM-EN-4.1 B9
Appendix B - Settings and Signals P64x
B10 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B11
Appendix B - Settings and Signals P64x
B12 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B13
Appendix B - Settings and Signals P64x
B14 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B15
Appendix B - Settings and Signals P64x
B16 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B17
Appendix B - Settings and Signals P64x
B18 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B19
Appendix B - Settings and Signals P64x
B20 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B21
Appendix B - Settings and Signals P64x
B22 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B23
Appendix B - Settings and Signals P64x
B24 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B25
Appendix B - Settings and Signals P64x
B26 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B27
Appendix B - Settings and Signals P64x
B28 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B29
Appendix B - Settings and Signals P64x
No
V/Hz W2 Reset 04 40 No Yes
[Indexed String]
This command resets the overfluxing protection for the 1-phase VT
RTD 1
RTD 1 04 60 Data
[Courier Number (decimal)]
This cell displays the label of RTD 1.
RTD 2
RTD 2 04 61 Data
[Courier Number (decimal)]
This cell displays the label of RTD 2.
RTD 3
RTD 3 04 62 Data
[Courier Number (decimal)]
This cell displays the label of RTD 3.
RTD 4
RTD 4 04 63 Data
[Courier Number (decimal)]
This cell displays the label of RTD 4.
RTD 5
RTD 5 04 64 Data
[Courier Number (decimal)]
B30 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B31
Appendix B - Settings and Signals P64x
B32 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B33
Appendix B - Settings and Signals P64x
B34 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B35
Appendix B - Settings and Signals P64x
B36 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B37
Appendix B - Settings and Signals P64x
B38 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B39
Appendix B - Settings and Signals P64x
B40 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B41
Appendix B - Settings and Signals P64x
B42 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B43
Appendix B - Settings and Signals P64x
B44 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B45
Appendix B - Settings and Signals P64x
B46 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B47
Appendix B - Settings and Signals P64x
B48 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B49
Appendix B - Settings and Signals P64x
B50 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B51
Appendix B - Settings and Signals P64x
B52 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B53
Appendix B - Settings and Signals P64x
B54 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B55
Appendix B - Settings and Signals P64x
B56 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B57
Appendix B - Settings and Signals P64x
B58 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B59
Appendix B - Settings and Signals P64x
B60 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B61
Appendix B - Settings and Signals P64x
B62 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B63
Appendix B - Settings and Signals P64x
B64 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B65
Appendix B - Settings and Signals P64x
B66 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B67
Appendix B - Settings and Signals P64x
B68 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B69
Appendix B - Settings and Signals P64x
B70 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B71
Appendix B - Settings and Signals P64x
B72 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B73
Appendix B - Settings and Signals P64x
B74 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B75
Appendix B - Settings and Signals P64x
B76 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B77
Appendix B - Settings and Signals P64x
B78 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
COMMISSION TESTS 0F 00
This column contains commissioning test settings
Data formatted as per data type G27.
Opto 1 Input State (0=Off, 1=Energised)
Opto 2 Input State (0=Off, 1=Energised)
Opto 3 Input State (0=Off, 1=Energised)
Opto 4 Input State (0=Off, 1=Energised)
Opto 5 Input State (0=Off, 1=Energised)
Opto 6 Input State (0=Off, 1=Energised)
Opto 7 Input State (0=Off, 1=Energised)
Opto 8 Input State (0=Off, 1=Energised)
Opto 9 Input State (0=Off, 1=Energised)
Opto 10 Input State (0=Off, 1=Energised)
Opto 11 Input State (0=Off, 1=Energised)
Opto 12 Input State (0=Off, 1=Energised)
Opto I/P Status 0F 01
Opto 13 Input State (0=Off, 1=Energised)
Opto 14 Input State (0=Off, 1=Energised)
Opto 15 Input State (0=Off, 1=Energised)
Opto 16 Input State (0=Off, 1=Energised)
Opto 17 Input State (0=Off, 1=Energised)
Opto 18 Input State (0=Off, 1=Energised)
Opto 19 Input State (0=Off, 1=Energised)
Opto 20 Input State (0=Off, 1=Energised)
Opto 21 Input State (0=Off, 1=Energised)
Opto 22 Input State (0=Off, 1=Energised)
Opto 23 Input State (0=Off, 1=Energised)
Opto 24 Input State (0=Off, 1=Energised)
Opto 25 Input State (0=Off, 1=Energised)
P64x-TM-EN-4.1 B79
Appendix B - Settings and Signals P64x
B80 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B81
Appendix B - Settings and Signals P64x
B82 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B83
Appendix B - Settings and Signals P64x
B84 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B85
Appendix B - Settings and Signals P64x
B86 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B87
Appendix B - Settings and Signals P64x
B88 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B89
Appendix B - Settings and Signals P64x
B90 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B91
Appendix B - Settings and Signals P64x
B92 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B93
Appendix B - Settings and Signals P64x
B94 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B95
Appendix B - Settings and Signals P64x
B96 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B97
Appendix B - Settings and Signals P64x
B98 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B99
Appendix B - Settings and Signals P64x
B100 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B101
Appendix B - Settings and Signals P64x
B102 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
0 or 1
Config Mode 1A 07 0
[Indexed String]
Setting to control the CS103 mode. Setting "Fixed" behaves as per original design, reporting CS103 information as per CS103 L&F info. When
"Std + UserConfig" is selected, this results in only the CS103 information that meets the CS103 Std Fun type is reported by default. All other
CS103 information is then user configurable. Please Note: CS103 information will follow the GI flag as per L&F. If it is configures for GI in L&F,
it will create spontaneous information plus GI, if not flagged for GI, it will only produce spontanous information.
High order word stored in 1st register
DDB 31 - 0 1A 40 0x00000000 Low order word stored in 2nd register
[Binary Flag (32-Bit)]
Control the DDB signals enabled in CS103 response messages
High order word stored in 1st register
DDB 63 - 32 1A 41 0x00000000 Low order word stored in 2nd register
[Binary Flag (32-Bit)]
Control the DDB signals enabled in CS103 response messages
P64x-TM-EN-4.1 B103
Appendix B - Settings and Signals P64x
B104 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B105
Appendix B - Settings and Signals P64x
B106 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B107
Appendix B - Settings and Signals P64x
B108 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
From 0 to 30 in steps of 1
FP InactivTimer 25 1B 10
[Courier Number (time-minutes)]
A configurable period of time when a user is automatically logged out on Front Port if they remain inactive for. Once log out, resetting of the
entered access-level back to 0.
Setting the inactivity timer settings to 0 disables session management and the automatic-logout feature is disabled (i.e. a logged in user
remains logged in forever; or until the user manually logs out)
From 0 to 30 in steps of 1
UI InactivTimer 25 1C 10
[Courier Number (time-minutes)]
A configurable period of time when a user is automatically logged out on UI if they remain inactive for. Once log out, resetting of the entered
access-level back to 0.
Setting the inactivity timer settings to 0 disables session management and the automatic-logout feature is disabled (i.e. a logged in user
remains logged in forever; or until the user manually logs out)
RBAC 25 30
Server + Device
Server only
Auth. Method 25 31 Server + Device
Device only
[Indexed string]
Configure the active Authentication method
From 0.0.0.0 to 223.255.255.255 in steps of 1
RADIUS Pri IP 25 32 0.0.0.0
[IP Parameters]
RADIUS Server 1 configured to provide Server Authentication service.
Setting this cell to 0.0.0.0 disables RADUIS Server 1
From 0.0.0.0 to 223.255.255.255 in steps of 1
RADIUS Sec IP 25 33 0.0.0.0
[IP Parameters]
RADIUS Server 2 configured to provide Server Authentication service.
Setting this cell to 0.0.0.0 disables RADUIS Server 2
From 1 to 65535 in steps of 1
RADIUS Auth Port 25 34 1812
[Unsigned Integer (32 bits)]
The destination TCP/IP port sent to both Primary and Secondary RADUIS servers.
On
On-blocked
Test
Test-blocked
Off
RADIUS Security 25 35 PAP EAP-TTLS-PAP
EAP-TTLS-MSCHAP2
PAP
EAP-PEAP-MSCHAP2
PAP EAP-TTLS-PAP
[Indexed string]
Option for choosing authentication scheme used by RADIUS server.
EAP-TTLS-MSCHAP2 - EAP Transport Layer Security (EAP-TLS) is an IETF open standard that uses the TLS protocol. Using TLS, a secure channel
is then established between Relay and Radius server.
The Microsoft version of Challenge-Handshake Authentication Protocol Version 2 (MS-CHAPv2) is a password based authentication method
that utilises the user account credentials (username and password) stored in Active Directory Domain Services to authenticate.
EAP-TTLS-MSCHAP2 represents the MSCHAPv2 method transferred over EAP-TTLS channel.
PAP - Password Authentication Protocol (PAP) is a password-based authentication protocol. PAP is considered a weak authentication scheme.
Protected Extensible Authentication Protocol (PEAP) is a protocol that encapsulates the Extensible Authentication Protocol (EAP) within an
encrypted and authenticated TLS tunnel.
P64x-TM-EN-4.1 B109
Appendix B - Settings and Signals P64x
From 1 to 99 in steps of 1
RADIUS Retries 25 37 10
[Unsigned Integer (8 bits)]
Define the times Relay will retry to request authentication from Radius server if no response.
From 33 to 122 in steps of 1
RADIUS Secret 25 38 ChangeMe1#
[ASCII Password (16)]
The shared secret is used by Radius server to verify the identity of IED.
Disabled
HMI-Only
Local
Bypass Auth. 25 40 Disabled
Remote
Local & Remote
[Indexed string]
Allow a user, when logged in as an administrator, to bypass the authentication requirements for specific interfaces.
RADIUS Status
RADIUS Status 25 FE Disabled
[Indexed string]
Reporting the status of Radius server.
Security Code
Security Code 25 FF
[ASCII Text (16 characters)]
This cell displays the 16-character security code required when requesting a recovery password. UI only cell.
USER ALARMS 28 00
This column contains settings for the User Alarms
Data formatted as per data type G27.
User Alarm 1 (0=Self-reset, 1=Manual reset)
User Alarm 2 (0=Self-reset, 1=Manual reset)
User Alarm 3 (0=Self-reset, 1=Manual reset)
User Alarm 4 (0=Self-reset, 1=Manual reset)
User Alarm 5 (0=Self-reset, 1=Manual reset)
User Alarm 6 (0=Self-reset, 1=Manual reset)
User Alarm 7 (0=Self-reset, 1=Manual reset)
User Alarm 8 (0=Self-reset, 1=Manual reset)
User Alarm 9 (0=Self-reset, 1=Manual reset)
User Alarm 10 (0=Self-reset, 1=Manual reset)
User Alarm 11 (0=Self-reset, 1=Manual reset)
User Alarm 12 (0=Self-reset, 1=Manual reset)
User Alarm 13 (0=Self-reset, 1=Manual reset)
User Alarm 14 (0=Self-reset, 1=Manual reset)
User Alarm 15 (0=Self-reset, 1=Manual reset)
User Alarm 16 (0=Self-reset, 1=Manual reset)
Manual Reset 28 01 0x00000000
User Alarm 17 (0=Self-reset, 1=Manual reset)
User Alarm 18 (0=Self-reset, 1=Manual reset)
User Alarm 19 (0=Self-reset, 1=Manual reset)
User Alarm 20 (0=Self-reset, 1=Manual reset)
User Alarm 21 (0=Self-reset, 1=Manual reset)
User Alarm 22 (0=Self-reset, 1=Manual reset)
User Alarm 23 (0=Self-reset, 1=Manual reset)
User Alarm 24 (0=Self-reset, 1=Manual reset)
User Alarm 25 (0=Self-reset, 1=Manual reset)
User Alarm 26 (0=Self-reset, 1=Manual reset)
User Alarm 27 (0=Self-reset, 1=Manual reset)
User Alarm 28 (0=Self-reset, 1=Manual reset)
User Alarm 29 (0=Self-reset, 1=Manual reset)
User Alarm 30 (0=Self-reset, 1=Manual reset)
User Alarm 31 (0=Self-reset, 1=Manual reset)
User Alarm 32 (0=Self-reset, 1=Manual reset)
[Binary Flag (32 bits)]
Set the user alarm is maunal reset or self reset
Labels 28 10 Sub-Heading
B110 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B111
Appendix B - Settings and Signals P64x
B112 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B113
Appendix B - Settings and Signals P64x
B114 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B115
Appendix B - Settings and Signals P64x
B116 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B117
Appendix B - Settings and Signals P64x
B118 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B119
Appendix B - Settings and Signals P64x
B120 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B121
Appendix B - Settings and Signals P64x
B122 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B123
Appendix B - Settings and Signals P64x
B124 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B125
Appendix B - Settings and Signals P64x
B126 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B127
Appendix B - Settings and Signals P64x
B128 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B129
Appendix B - Settings and Signals P64x
B130 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B131
Appendix B - Settings and Signals P64x
B132 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B133
Appendix B - Settings and Signals P64x
B134 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B135
Appendix B - Settings and Signals P64x
B136 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B137
Appendix B - Settings and Signals P64x
B138 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B139
Appendix B - Settings and Signals P64x
B140 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B141
Appendix B - Settings and Signals P64x
B142 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B143
Appendix B - Settings and Signals P64x
B144 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B145
Appendix B - Settings and Signals P64x
B146 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B147
Appendix B - Settings and Signals P64x
B148 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B149
Appendix B - Settings and Signals P64x
B150 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B151
Appendix B - Settings and Signals P64x
B152 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B153
Appendix B - Settings and Signals P64x
B154 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B155
Appendix B - Settings and Signals P64x
B156 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B157
Appendix B - Settings and Signals P64x
B158 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B159
Appendix B - Settings and Signals P64x
B160 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B161
Appendix B - Settings and Signals P64x
B162 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B163
Appendix B - Settings and Signals P64x
B164 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B165
Appendix B - Settings and Signals P64x
B166 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B167
Appendix B - Settings and Signals P64x
B168 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B169
Appendix B - Settings and Signals P64x
B170 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B171
Appendix B - Settings and Signals P64x
B172 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B173
Appendix B - Settings and Signals P64x
B174 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B175
Appendix B - Settings and Signals P64x
B176 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B177
Appendix B - Settings and Signals P64x
B178 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B179
Appendix B - Settings and Signals P64x
B180 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B181
Appendix B - Settings and Signals P64x
B182 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B183
Appendix B - Settings and Signals P64x
B184 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B185
Appendix B - Settings and Signals P64x
B186 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B187
Appendix B - Settings and Signals P64x
B188 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B189
Appendix B - Settings and Signals P64x
B190 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B191
Appendix B - Settings and Signals P64x
B192 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B193
Appendix B - Settings and Signals P64x
B194 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B195
Appendix B - Settings and Signals P64x
B196 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B197
Appendix B - Settings and Signals P64x
B198 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B199
Appendix B - Settings and Signals P64x
B200 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B201
Appendix B - Settings and Signals P64x
B202 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B203
Appendix B - Settings and Signals P64x
B204 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B205
Appendix B - Settings and Signals P64x
B206 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B207
Appendix B - Settings and Signals P64x
B208 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B209
Appendix B - Settings and Signals P64x
B210 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B211
Appendix B - Settings and Signals P64x
B212 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B213
Appendix B - Settings and Signals P64x
Front Port
Rear Port 1
Rear Port 2
Ethernet Port
Connected i/face BF 11
Courier Tunnel
IEC61850
DNP3OE
[Unsigned Integer (16 bits)]
Security Column
Security Column BF 12 25 00
[Menu Cell]
Port Disable
Port Disable BF 13 25 05
[Menu Cell]
Password Reset BF F0
B214 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B215
Appendix B - Settings and Signals P64x
B216 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B217
Appendix B - Settings and Signals P64x
B218 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B219
Appendix B - Settings and Signals P64x
B220 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B221
Appendix B - Settings and Signals P64x
B222 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B223
Appendix B - Settings and Signals P64x
B224 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B225
Appendix B - Settings and Signals P64x
B226 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B227
Appendix B - Settings and Signals P64x
B228 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B229
Appendix B - Settings and Signals P64x
B230 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B231
Appendix B - Settings and Signals P64x
B232 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B233
Appendix B - Settings and Signals P64x
B234 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B235
Appendix B - Settings and Signals P64x
B236 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B237
Appendix B - Settings and Signals P64x
B238 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B239
Appendix B - Settings and Signals P64x
B240 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B241
Appendix B - Settings and Signals P64x
B242 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B243
Appendix B - Settings and Signals P64x
B244 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B245
Appendix B - Settings and Signals P64x
B246 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B247
Appendix B - Settings and Signals P64x
B248 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B249
Appendix B - Settings and Signals P64x
B250 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B251
Appendix B - Settings and Signals P64x
B252 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B253
Appendix B - Settings and Signals P64x
B254 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B255
Appendix B - Settings and Signals P64x
B256 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B257
Appendix B - Settings and Signals P64x
B258 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B259
Appendix B - Settings and Signals P64x
B260 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B261
Appendix B - Settings and Signals P64x
B262 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B263
Appendix B - Settings and Signals P64x
B264 P64x-TM-EN-4.1
P64x Appendix B - Settings and Signals
P64x-TM-EN-4.1 B265
Appendix B - Settings and Signals P64x
B266 P64x-TM-EN-4.1
APPENDIX C
WIRING DIAGRAMS
Appendix C - Wiring Diagrams P64x
528 P64x-TM-EN-4.1
P64x Appendix C – Wiring Diagrams
P642 IO Option C 2 BIAS INPUT TRANSFORMER DIFFERENTIAL (8 I/P & 8 O/P + CLIO) WITH 1 POLE VT INPUT (40TE) 10P64203-1 J
IO Option C 2 BIAS INPUT TRANSFORMER DIFFERENTIAL (8 I/P & 8 O/P + CLIO) WITH 2 POLE VT INPUT (40TE) 10P64208-1 G
IO Option D 2 BIAS INPUT TRANSFORMER DIFFERENTIAL (12 I/P & 12 O/P) WITH 1 POLE VT INPUT (40TE) 10P64204-1 J
IO Option D 2 BIAS INPUT TRANSFORMER DIFFERENTIAL (12 I/P & 12 O/P) WITH 2 POLE VT INPUT (40TE) 10P64209-1 G
IO Option E 2 BIAS INPUT TRANSFORMER DIFFERENTIAL (8 I/P 12 O/P) WITH 1 POLE INPUT (40TE) 10P64205-1 J
IO Option E 2 BIAS INPUT TRANSFORMER DIFFERENTIAL (8 I/P 12 O/P) WITH 2 POLE INPUT (40TE) 10P64210-1 G
IO Option A 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/O & 16 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64301-1, 10P64301-2 F, I
IO Option A HIGH Z REF FOR 3 BIAS I/P TRANSFORMER DIFF SAME APPLIES TO WIRE HIGH Z REF FOR T2 &T3 10P64301-3 D
IO Option B 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/O & 16 O/P + RTD) WITH 4 POLE VT INPUTS (60TE) 10P64302-1, 10P64302-2 F, I
IO Option C 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/O & 16 O/P + CLIO) WITH 4 POLE VT INPUTS (60TE) 10P64303-1, 10P64303-2 G, I
IO Option D 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (24 I/O & 16 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64304-1, 10P64304-2 G, I
IO Option E 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/O & 24 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64305-1, 10P64305-2 F, I
IO Option F 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/P 20 O/P) WITH 4 POLE VT INPUT (60TE) 10P64306-1, 10P64306-2 F, I
P643
IO Option G 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 24 O/P) WITH 4 POLE VT INPUTS (80TE) 10P64307-1, 10P64307-2 C, D
IO Option H 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 16 O/P+RTD) WITH 4 POLE VT INPUTS (80TE) 10P64308-1, 10P64308-2 D, D
IO Option J 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 16 O/P+CLIO) WITH 4 POLE VT INPUTS (80TE) 10P64309-1, 10P64309-2 C, D
IO Option K 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 8 O/P+RTD+CLIO) WITH 4 POLE VT I/P (80TE) 10P64310-1, 10P64310-2 C, D
IO Option L 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 20 O/P) WITH 4 POLE VT INPUTS (80TE) 10P64311-1, 10P64311-2 C, D
IO Option M 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 12 O/P+RTD) WITH 4 POLE VT INPUTS (80TE) 10P64312-1, 10P64312-2 C, D
IO Option N 3 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/O & 12 O/P+CLIO) WITH 4 POLE VT INPUTS (80TE) 10P64313-1, 10P64313-2 C, D
IO Option A 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/P & 16 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64501-1, 10P64501-2 E, J
IO Option A HIGH Z REF FOR 5 BIAS I/P TRANSFORMER DIFF. SAME APPLIES TO WIRE HIGH Z REF FOR T2,T3,T4,T5 10P64501-3 G
IO Option B 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/P & 16 O/P + RTD) WITH 4 POLE VT INPUTS (60TE) 10P64502-1, 10P64502-2 E, I
IO Option C 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/P & 16 O/P + CLIO) WITH 4 POLE VT INPUTS (60TE) 10P64503-1, 10P64503-2 E, I
IO Option D 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (24 I/P & 16 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64504-1, 10P64504-2 E, I
IO Option E 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (16 I/P & 24 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64505-1, 10P64505-2 E, I
IO Option J 5 BIAS INPUT TRANSFORMER DIFF. (24 I/P & 24 O/P + CLIO & RTD) WITH 4 POLE VT INPUTS (80TE) 10P64506-1, 10P64506-2 F, I
IO Option K 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (24 I/P 20 O/P) WITH 4 POLE VT INPUTS (60TE) 10P64507-1, 10P64507-2 E, H
P645 IO Option P 5 BIAS INPUT TRANSFORMER DIFF. (24 I/P 20 O/P + CLIO & RTD)) WITH 4 POLE VT INPUTS (80TE) 10P64508-1, 10P64508-2 E, H
IO Option T 5 BIAS INPUT TRANSFORMER DIFF. (16 I/P 24 O/P + CLIO & RTD) WITH 4 POLE VT INPUTS (80TE) 10P64509-1, 10P64509-2 E, H
IO Option U 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 24 O/P) WITH 4 POLE VT INPUTS (80TE) 10P64514-1, 10P64514-2 C, D
IO Option V 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 16 O/P+RTD) WITH 4 POLE VT INPUTS (80TE) 10P64515-1, 10P64515-2 C, D
IO Option W 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 16 O/P+CLIO) WITH 4 POLE VT INPUTS (80TE) 10P64516-1, 10P64516-2 D, D
IO Option X 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 8 O/P+CLIO+RTD) WITH 4 POLE VT INPUTS (80TE) 10P64517-1, 10P64517-2 C, D
IO Option Y 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 20 O/P) WITH 4 POLE VT INPUTS (80TE) 10P64518-1, 10P64518-2 C, D
IO Option Z 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 12 O/P+RTD) WITH 4 POLE VT INPUTS (80TE) 10P64519-1, 10P64519-2 C, C
IO Option 1 5 BIAS INPUT TRANSFORMER DIFFERENTIAL (40 I/P & 12 O/P+CLIO) WITH 4 POLE VT INPUTS (80TE) 10P64520-1, 10P64520-2 C, D
* When selecting the applicable wiring diagram(s), refer to appropriate model’s Cortec.
P64x-TM-EN-4.1 C1
GE PROPRIETARY AND CONFIDENTIAL INFORMATION PART DESCRIPTION MATERIAL
This document is the property of General Electric Company ("GE") and contains proprietary information of GE. This document is loaned on the express condition that neither it nor the information contained therein shall be disclosed to others
without the express written consent of GE, and that the information shall be used by the recipient only as approved expressly by GE. This document shall be returned to GE upon its request. This document may be subject to certain restrictions
Date: Name: Drg Next Stage: Drg ECN No: Revision: Iteration:
Title: No:
Date: Chkd: 10PX4001 K 3
Sub-contractor reference: Linear Tol PLM Sht: Status:
CAD DATA 1:1 DIMENSIONS: mm mm: No:
Finish: Angular Tol
Grid Solutions A20022917 Next IN WORK
DO NOT SCALE
deg: Sht:
A
P1 P2 P2 P1 A
A A A A
S1 S2 S2 S1 B
T2 B B B B T1
C
C C C C C B A B C
PHASE ROTATION
PROTECTED
TRANSFORMER MiCOM P642 (PART) N
T1 C24 NOTE 3
A (1) n
C23
a
MiCOM P642 (PART)
b c
C26
C3
B (1) F11
WATCHDOG
C25 VFLUX CONTACT F12
C4 F13
C28 WATCHDOG
CONTACT F14
C (1) E1
D1
C27 RELAY 1 E2
D2 OPTO 1
E3
T2 C18
D3 RELAY 2 E4
A (2) OPTO 2 E5
D4
C17 RELAY 3 E6
D5
E7
C20 D6 OPTO 3
RELAY 4 E8
B (2) D7 E9
C19 D8 OPTO 4 RELAY 5 E10
D9 E11
C22
OPTO 5 RELAY 6 E12
C (2)
D10
E13
D11
C21 E14
OPTO 6 RELAY 7
D12 E15
GROUNDED WYE D13 E16
NEUTRAL TAILS D14 OPTO 7 E17
RELAY 8
E18
HV LV D15
NOTE 4 D16 OPTO 8
NOTE 2
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
CASE
EARTH
B
A
P1 P2 P2 P1 C
A A A A A B C
S1 S2 S2 S1
T2 B B B B T1
C C C C C B N
PHASE ROTATION NOTE 3
PROTECTED n
TRANSFORMER MiCOM P642 (PART)
T1 C24
a b c
A (1)
C1
C23
MiCOM P642 (PART)
C26 Vab OPTIONAL
C2
B (1) F11
C4 WATCHDOG
C25 CONTACT F12
Vflux F13
C28 WATCHDOG
C3 F14
CONTACT
C (1) E1
D1
C27 RELAY 1 E2
D2 OPTO 1
E3
T2 C18
D3 RELAY 2 E4
A (2) OPTO 2 E5
D4
C17 RELAY 3 E6
D5
E7
C20 D6 OPTO 3
RELAY 4 E8
B (2) D7 E9
C19 D8 OPTO 4 RELAY 5 E10
D9 E11
C22
OPTO 5 RELAY 6 E12
C (2) D10
E13
D11
C21 E14
OPTO 6 RELAY 7
D12 E15
GROUNDED WYE D13 E16
NEUTRAL TAILS D14 OPTO 7 E17
RELAY 8
E18
HV LV D15
NOTE 4 D16 OPTO 8
NOTE 2
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
CASE
EARTH
B
A
P1 P2 P2 P1 C
A A A A A B C
T2 S1 S2 S2 S1
B B B B T1
C C C C C B N
PHASE ROTATION NOTE 3
PROTECTED n MiCOM P642 (PART)
TRANSFORMER MiCOM P642 (PART)
T1 C24
a b c
A (1)
C1 B1
C23
B2 RTD 1
C26 Vab OPTIONAL B3
C2
B (1) B4
C4 B5 RTD 2
C25
B6
Vflux
C28 B7
C3
C (1) B8 RTD 3
F11 B9
D1 WATCHDOG
C27 F12
OPTO 1 CONTACT B10
D2
T2 C18 F13 B11 RTD 4
D3 WATCHDOG
CONTACT F14 B12
A (2) OPTO 2
D4 E1 B13
C17 RELAY 1 E2
D5 B14 RTD 5
C20 OPTO 3 E3 B15
D6
RELAY 2 E4 B16
B (2) D7
E5 B17 RTD 6
C19 D8 OPTO 4 RELAY 3 E6 B
B18
C22 D9 E7 B19
D10 OPTO 5 RELAY 4 E8 RTD 7
C (2) B20
E9 B21
D11
C21 RELAY 5 E10
OPTO 6 B22
D12
E11 B23 RTD 8
GROUNDED WYE D13 RELAY 6 E12 B24
NEUTRAL TAILS D14 OPTO 7 E13 B25
D15 E14 B26 RTD 9
HV LV RELAY 7
OPTO 8 E15 B27
B
NOTE 4 D16
NOTE 2 E16
COMMS B28
D17 E17
COMMON RELAY 8 B29 RTD 10
D18 CONNECTION E18 B30
P2 S2
F17
C (1) E3 B13
20mA
D1 RELAY 2 E4 B14
C27 1mA OUTPUT 4
D2 OPTO 1 E5
B15
T2 C18 RELAY 3 E6 CLIO
D3 B16
A (2) E7 20mA CURRENT LOOP
D4 OPTO 2
RELAY 4 E8 B17 INPUTS & OUTPUTS
C17 1mA INPUT 1
D5 E9 B18 NOTE 5
C20 D6 OPTO 3 RELAY 5 E10 B20
20mA
B (2) D7 E11
B21
RELAY 6 E12 1mA INPUT 2
C19 D8 OPTO 4
B22
E13
C22 D9 B24
E14 20mA
OPTO 5 RELAY 7
C (2) D10 E15 B25
1mA INPUT 3
D11 E16 B26
C21
D12 OPTO 6 E17
RELAY 8 B28
E18 20mA
GROUNDED WYE D13 B29
1mA INPUT 4
NEUTRAL TAILS D14 OPTO 7
B30
HV LV D15
NOTE 4 D16 OPTO 8 MiCOM P642 (PART)
NOTE 2
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17 NOTES:
B
A
P1 P2 P2 P1 C
A A A A A B C
S1 S2 S2 S1
T2 B B B B T1
C C C C C B N
PHASE ROTATION NOTE 3
PROTECTED n
TRANSFORMER MiCOM P642 (PART)
T1 C24 B1
20mA
a b c B2
A (1) 1mA OUTPUT 1
C1 B3
C23
B5
C26 Vab OPTIONAL 20mA
C2 F11 B6
B (1) WATCHDOG 1mA OUTPUT 2
C4 CONTACT F12 B7
C25 F13
WATCHDOG B9
Vflux F14 20mA
C28 CONTACT B10
C3 E1 1mA OUTPUT 3
C (1) RELAY 1 B11
E2
D1
C27 E3 B13
OPTO 1 20mA
D2 RELAY 2 E4
T2 C18 B14
1mA OUTPUT 4
D3 E5
A (2) B15
D4 OPTO 2 RELAY 3 E6 CLIO
B16
C17 E7 20mA CURRENT LOOP
D5
RELAY 4 E8 B17 INPUTS & OUTPUTS
C20 OPTO 3 1mA INPUT 1
D6 NOTE 5
E9 B18
B (2) D7 RELAY 5 E10 B20
OPTO 4 20mA
C19 D8 E11
B21
RELAY 6 E12 1mA INPUT 2
C22 D9
B22
OPTO 5 E13
C (2) D10
E14 B24
RELAY 7 20mA
D11
C21 E15 B25
OPTO 6 1mA INPUT 3
D12 E16 B26
GROUNDED WYE D13 E17
RELAY 8 B28
OPTO 7 E18 20mA
NEUTRAL TAILS D14
B29
1mA INPUT 4
HV LV D15
B30
NOTE 4 D16 OPTO 8
NOTE 2
COMMS
D17 MiCOM P642 (PART)
COMMON
D18 CONNECTION
P2 S2
F17 NOTES:
B
A
P1 P2 P2 P1 C
A A A A A B C
S1 S2 S2 S1
T2 B B B B T1
C C C C C B N
PHASE ROTATION NOTE 3
PROTECTED n
TRANSFORMER MiCOM P642 (PART)
T1 C24
a b c
A (1)
C1
C23
MiCOM P642 (PART)
C26 Vab OPTIONAL
C2
B (1)
C4
C25 B1
F11
Vflux WATCHDOG B2 OPTO 9
C28 CONTACT F12
C3
F13 B3
C (1) WATCHDOG
D1 CONTACT F14 B4 OPTO 10
C27
OPTO 1 E1
D2 B5
T2 C18 RELAY 1 E2
D3 B6 OPTO 11
E3
A (2) OPTO 2
D4 RELAY 2 E4 B7
C17 OPTO 12
D5 E5 B8
C20 OPTO 3 RELAY 3 E6
D6
E7
B (2) D7
RELAY 4 E8 B9
C19 D8 OPTO 4 RELAY 9
E9 B10
C22 D9 RELAY 5 E10 B11
OPTO 5 B12 RELAY 10
D10 E11
C (2)
RELAY 6 E12 B13
D11
C21 E13 B14
OPTO 6 RELAY 11
D12 B15
E14
D13 RELAY 7
GROUNDED WYE E15 B16
NEUTRAL TAILS D14 OPTO 7 B17
E16 RELAY 12
D15 E17 B18
HV LV RELAY 8
D16 OPTO 8 E18
NOTE 2 NOTE 4
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
B
A
P1 P2 P2 P1 C
A A A A A B C
S1 S2 S2 S1
T2 B B B B T1
C C C C C B N
PHASE ROTATION NOTE 3
PROTECTED n
TRANSFORMER MiCOM P642 (PART)
T1 C24
a b c
A (1)
C1
C23
MiCOM P642 (PART)
C26 Vab OPTIONAL
C2
B (1)
C4
C25
F11
Vflux WATCHDOG
C28 CONTACT F12
C3
F13
C (1) WATCHDOG
D1 CONTACT F14
C27 B3
OPTO 1 E1
D2
T2 C18 RELAY 1 E2 RELAY 9
D3 B4
E3
A (2) OPTO 2
D4 RELAY 2 E4 B7
C17
D5 E5 RELAY 10
C20 OPTO 3 RELAY 3 E6 B8
D6 HIGH BREAK
E7 B11 CONTACTS
B (2) D7
RELAY 4 E8
C19 D8 OPTO 4 RELAY 11
E9 B12
C22 D9 RELAY 5 E10 B15
D10 OPTO 5 E11
C (2) RELAY 12
D11 RELAY 6 E12 B16
C21 E13
D12 OPTO 6
E14
D13 RELAY 7
GROUNDED WYE E15
NEUTRAL TAILS D14 OPTO 7
E16
D15 E17
HV LV RELAY 8
D16 OPTO 8 E18
NOTE 2 NOTE 4
COMMS
D17
COMMON
D18 CONNECTION
P2 S2
F17
C C C C C B
C B A PHASE ROTATION
F13
OPTO 15
NOTES: 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
F14
P1 S1 TN3 C12 F15
P2 S2 (b) TERMINAL.
Y (TV) F16 OPTO 16
(c) PIN TERMINAL (P.C.B. TYPE)
C11 F17
2. SEE TABLE 1 FOR BIAS ASSIGNMENT TO ACTUAL WINDINGS. T1
COMMON
TN2 C14 F18 CONNECTION IS ALWAYS AN HV WINDING CONNECTION.
P1 S1
P2 S2 3. WYE GROUND INPUTS APPLICABLE FOR GROUNDED (EARTHED) WINDINGS.
Y (LV)
4. THE VT MAY BE CONNECTED ACROSS ANY PHASE-PHASE PAIR.
C13 (USED BY V/Hz W2 PROTECTION ONLY).
RST 5. (x2) DENOTES WINDINGS ENERGISED VIA TWO CT SETS. THE RELAY SOFTWARE
P1 S1 TN1 C16
SUMMATES A VIRTUAL WINDING CURRENT FROM THE TWO BIAS INPUTS.
Y (HV) 6. TV INPUTS ARE NOT MANDATORY IF THE TERTIARY HAS NO LOAD.
C15 7. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
CASE 8. THE VT STAR POINT MUST BE MADE EXTERNALLY AS SHOWN.
EARTH MiCOM P643 (PART)
METROSIL 9. THE MONITORED THREE PHASE VOLTAGE MAY BE CONNECTED HV, TV OR LV SIDE.
(USED BY V/Hz W1 PROTECTION AND OTHER VOLTAGE PROTECTION).
10. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C C C C C B
C B A PHASE ROTATION
C C C C C B
C B A PHASE ROTATION
T1
MiCOM P643 (PART)
T2 C24 D1
A (1) D2 OPTO 1 J11 B1
WATCHDOG
C23 D3 CONTACT J12 B2 OPTO 17
OPTO 2 J13
C26 D4 WATCHDOG B3
CONTACT J14
D5 B4 OPTO 18
B (1) H1
D6 OPTO 3 B5
C25 RELAY 1 H2
D7 H3 B6 OPTO 19
C28
D8 OPTO 4 RELAY 2 H4 B7
C (1) H5
D9 B8 OPTO 20
NOTE 2 C27 RELAY 3 H6
D10 OPTO 5 B9
T2 H7
C18 D11 B10 OPTO 21
RELAY 4 H8
P2 A (2) D12 OPTO 6 H9 B11
S2 C17 RELAY 5 H10 OPTO 22
D13 B12
OPTO 7 H11
C20 D14 B13
RELAY 6 H12
D15 B14 OPTO 23
S1 B (2) H13
D16 OPTO 8 B15
P1 C19 H14
RELAY 7
D17 H15 B16 OPTO 24
C22 COMMON
D18 H16 B17
CONNECTION
C (2) H17 COMMON
F1 RELAY 8 B18 CONNECTION
C21 H18
F2 OPTO 9
T3 E24 G1
F3
RELAY 9 G2
A (3) F4 OPTO 10 NOTE 7
G3 COMMS
E23 F5 RELAY 10 G4
F6 OPTO 11 G5 J17
E26
RELAY 11 G6
B (3) F7 SEE DRAWING
G7 EIA485/
F8 OPTO 12 10Px4001 KBUS
E25 RELAY 12 G8 J18
PORT
F9 G9
E28 J16
F10 OPTO 13 RELAY 13 G10 SCN
C (3)
F11 G11
E27 RELAY 14 J1
F12 OPTO 14 G12 AC OR DC
G13 J2 x AUX SUPPLY
F13
G14
F14 OPTO 15 RELAY 15
G15
F15 G16
F16 OPTO 16 G17
RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)
T1
MiCOM P643 (PART)
T2 C24 D1
A (1) D2 OPTO 1 J11
WATCHDOG
C23 D3 CONTACT J12
OPTO 2 J13 B1
C26 D4 WATCHDOG
J14 B2 RELAY 17
CONTACT
B (1) D5
H1 B3
D6 OPTO 3 RELAY 18
C25 RELAY 1 H2 B4
D7 H3 B5
C28 RELAY 19
D8 OPTO 4 RELAY 2 H4 B6
C (1) H5 B7
D9
NOTE 2 C27 RELAY 3 H6 B8 RELAY 20
D10 OPTO 5
T2 H7 B9
C18 D11 RELAY 4 H8 B10 RELAY 21
P2 A (2) D12 OPTO 6 H9 B11
S2 C17 RELAY 5 H10 B12 RELAY 22
D13
OPTO 7 H11 B13
C20 D14
RELAY 6 H12 B14
D15 RELAY 23
S1 B (2) H13 B15
D16 OPTO 8
P1 C19 H14 B16
RELAY 7
D17 H15 B17
C22 RELAY 24
COMMON H16 B18
D18 CONNECTION
C (2) H17
F1 RELAY 8
C21 H18
F2 OPTO 9
T3 G1
E24 F3 NOTE 7
RELAY 9 G2 COMMS
A (3) F4 OPTO 10
G3
E23 F5 RELAY 10 G4
F6 OPTO 11 G5 J17
E26
RELAY 11 G6 SEE DRAWING
B (3) F7 EIA485/
G7 10Px4001 KBUS
F8 OPTO 12 J18
E25 RELAY 12 G8 PORT
F9 G9 J16
E28
F10 OPTO 13 RELAY 13 SCN
G10
C (3)
F11 G11 J1
E27 OPTO 14 RELAY 14 G12 AC OR DC
F12 J2 x AUX SUPPLY
G13
F13
G14
F14 OPTO 15 RELAY 15
G15
F15 G16
F16 OPTO 16 G17
RELAY 16
SEE SHEET 2 FOR NOTES F17 G18
COMMON
F18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1
T3 B B TRANSFORMER B B T1
C B
C C C C PHASE ROTATION
C B A T1
T2 D24 E1 MiCOM P643 (PART)
A (1) E2 OPTO 1 M11 C1
WATCHDOG
D23 E3 CONTACT M12 C2 OPTO 25
OPTO 2 M13
D26 E4 WATCHDOG C3
CONTACT M14
E5 C4 OPTO 26
B (1) L1
E6 OPTO 3 C5
D25 RELAY 1 L2
E7 L3 C6 OPTO 27
D28
E8 OPTO 4 RELAY 2 L4 C7
C (1) L5
E9 C8 OPTO 28
NOTE 2 D27 RELAY 3 L6
E10 OPTO 5 C9
T2 L7
D18 E11 C10 OPTO 29
RELAY 4 L8
P2 A (2) E12 OPTO 6 L9 C11
S2 D17 RELAY 5 L10 OPTO 30
E13 C12
OPTO 7 L11
D20 E14 C13
RELAY 6 L12
E15 C14 OPTO 31
S1 B (2) L13
E16 OPTO 8 C15
P1 D19 L14
RELAY 7
E17 L15 C16 OPTO 32
D22 COMMON
E18 L16 C17
CONNECTION
C (2) L17 COMMON
G1 RELAY 8 C18 CONNECTION
D21 L18
G2 OPTO 9 B1
T3 F24 K1
G3 B2 OPTO 33
RELAY 9 K2
A (3) G4 OPTO 10 B3
K3
F23 G5 RELAY 10 K4 B4 OPTO 34
G6 OPTO 11 K5 B5
F26
RELAY 11 K6 OPTO 35
B (3) G7 B6
OPTO 12 K7
F25 G8 B7
RELAY 12 K8
G9 B8 OPTO 36
F28 K9
G10 OPTO 13 RELAY 13 K10 B9
C (3)
G11 K11 B10 OPTO 37
F27 OPTO 14 RELAY 14 K12
G12 B11
K13 OPTO 38
G13 B12
K14
G14 OPTO 15 RELAY 15 B13
K15
G15 K16 B14 OPTO 39
H17
CASE COMMON
EARTH H18 CONNECTION
MiCOM P643 (PART)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
D16 TN1
S1 P1
Y (HV)
D15
P1 P2 P2 P1
A A A A
S1 S2 PROTECTED S2 S1 T1
T3 B B TRANSFORMER B B
C B
C C C C PHASE ROTATION
C B A
T1 MiCOM P643 (PART)
T2 D24 E1 C1
A (1) E2 OPTO 1 M11 C2 OPTO 33
WATCHDOG
D23 E3 CONTACT M12 C3
OPTO 2 M13 OPTO 34
D26 E4 WATCHDOG C4
CONTACT M14
B (1) E5 C5
L1
E6 OPTO 3 C6 OPTO 35
D25 RELAY 1 L2
E7 L3 C7
D28
E8 OPTO 4 RELAY 2 L4 C8 OPTO 36
C (1) L5
E9 C9
NOTE 2 D27 RELAY 3 L6
E10 OPTO 5 C10 OPTO 37
T2 L7
D18 E11 C11
RELAY 4 L8
P2 A (2) E12 OPTO 6 L9 C12 OPTO 38
S2 D17 RELAY 5 L10
E13 C13
OPTO 7 L11 OPTO 39
D20 E14 C14
RELAY 6 L12
S1 B (2) E15 L13 C15
E16 OPTO 8 C16 OPTO 40
P1 D19 L14
RELAY 7
E17 L15 C17
D22 COMMON COMMON
E18 L16 C18
CONNECTION CONNECTION
C (2) L17
G1 RELAY 8
D21 L18
G2 OPTO 9
T3 K1
F24 G3
RELAY 9 K2
A (3) G4 OPTO 10
K3
F23 G5 RELAY 10 K4
G6 OPTO 11 K5
F26
RELAY 11 K6
B (3) G7
OPTO 12 K7
G8 B1
F25 RELAY 12 K8
G9 B2 RTD 1
F28 K9
OPTO 13 B3
G10 RELAY 13 K10
C (3) B4
G11 K11
B5 RTD 2
F27 OPTO 14 RELAY 14 K12
G12 B6
K13
G13 B7
K14
G14 OPTO 15 RELAY 15 B8 RTD 3
K15
B9
G15 K16
G16 OPTO 16 K17
RELAY 16
SEE SHEET 2 FOR NOTES G17 K18
B28
COMMON
G18 CONNECTION B29 RTD 10
H1 J1 B30
H2 OPTO 17 OPTO 25 J2
H3 J3
H4 OPTO 18 OPTO 26 J4
H5 J5
H6 OPTO 19 OPTO 27 J6 NOTE 7
COMMS
H7 J7
H8 OPTO 20 OPTO 28 J8
H9 J9
H10 OPTO 21 OPTO 29 J10 M17
H11 J11
SEE DRAWING EIA485/
H12 OPTO 22 OPTO 30 J12 10Px4001 KBUS
M18
H13 J13 PORT
OPTO 23 OPTO 31 M16
H14 J14 SCN
H15 J15
OPTO 24 OPTO 32 M1
H16 J16 AC OR DC
M2 x AUX SUPPLY
H17 J17
COMMON COMMON
H18 CONNECTION CONNECTION J18
CASE
EARTH
MiCOM P643 (PART)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
J7 H7 J7
OPTO 28 J8 H8 OPTO 20 OPTO 28 J8
J9 H9 J9 NOTE 7
OPTO 29 J10 H10 OPTO 21 OPTO 29 J10 COMMS
CASE
EARTH
MiCOM P643 (PART)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
C C C C C B
C B A PHASE ROTATION
T2 T1
D24 E1 MiCOM P643 (PART)
A (1) E2 OPTO 1 M11
WATCHDOG
D23 E3 CONTACT M12 B1
OPTO 2 M13
D26 E4 WATCHDOG B2 RTD 1
CONTACT M14
E5 B3
B (1) L1
OPTO 3 B4
D25 E6 RELAY 1 L2
B5 RTD 2
E7 L3
B6
D28
E8 OPTO 4 RELAY 2 L4
B7
C (1) L5
E9 B8 RTD 3
NOTE 2 D27 RELAY 3 L6
E10 OPTO 5 B9
T2 L7
D18 E11 RELAY 4 L8
P2 A (2) E12 OPTO 6 L9
B28
S2 D17 RELAY 5 L10
E13 B29 RTD 10
OPTO 7 L11
D20 E14 B30
RELAY 6 L12
S1 B (2) E15
L13
E16 OPTO 8
D19 L14
P1 RELAY 7
E17 L15 C1
D22 COMMON 20mA
E18 L16 C2
CONNECTION 1mA OUTPUT 1
C (2) L17
G1 RELAY 8 C3
D21 L18
G2 OPTO 9 C5
T3 20mA
F24 G3 C6
J1 1mA OUTPUT 2
A (3) G4 OPTO 10 OPTO 25 C7
J2
F23 G5 J3 C9
20mA
G6 OPTO 11 OPTO 26 C10
F26 J4 1mA OUTPUT 3
B (3) G7 J5 C11
G8 OPTO 12 OPTO 27 C13
F25 J6 20mA
G9 J7 C14
F28 1mA OUTPUT 4
G10 OPTO 13 OPTO 28 C15
J8
C (3) CLIO
G11 J9 C16
F27 20mA CURRENT LOOP
G12 OPTO 14 OPTO 29 C17 INPUTS & OUTPUTS
J10 1mA INPUT 1
G13 C18 NOTE 11
J11
G14 OPTO 15 OPTO 30 C20
J12 20mA
G15 J13 C21
1mA INPUT 2
G16 OPTO 16 OPTO 31 C22
J14
SEE SHEET 2 FOR NOTES G17 J15 C24
COMMON 20mA
G18 CONNECTION OPTO 32 J16 C25
1mA INPUT 3
H1 J17 C26
OPTO 17 COMMON
H2 J18 C28
CONNECTION 20mA
H3 K1 C29
1mA INPUT 4
H4 OPTO 18 OPTO 33 C30
K2
H5 K3
H6 OPTO 19 OPTO 34 K4
H7 K5
H8 OPTO 20 OPTO 35 NOTE 7
K6
COMMS
H9 K7
H10 OPTO 21 OPTO 36 K8
H11 K9
OPTO 22 M17
H12 OPTO 37 K10
H13 SEE DRAWING EIA485/
K11 10Px4001 KBUS
H14 OPTO 23 OPTO 38 M18
K12 PORT
H15 K13 M16
OPTO 24 SCN
H16 OPTO 39 K14
H17 K15 M1
COMMON AC OR DC
H18 CONNECTION OPTO 40 K16 M2 x AUX SUPPLY
CASE
EARTH K17
COMMON
CONNECTION K18
MiCOM P643 (PART)
H3
H4 OPTO 18
H5 J3
H6 OPTO 19
RELAY 17 NOTE 7
J4
H7 COMMS
H8 OPTO 20 J7
H9 RELAY 18
J8
H10 OPTO 21
J11 M17
H11
RELAY 19 SEE DRAWING
H12 OPTO 22 J12 EIA485/
10Px4001 KBUS
H13 J15 M18
PORT
H14 OPTO 23 M16
RELAY 20
J16 SCN
H15
H16 OPTO 24 M1
AC OR DC
H17 M2 x AUX SUPPLY
COMMON
H18 CONNECTION
CASE
EARTH
MiCOM P643 (PART)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
C C C C C B
C B A PHASE ROTATION
B (3) G8 OPTO 12 K7 B1
F25 G9 RELAY 10 B2 RTD 1
OPTO 13 K8 B3
G10
F28
K11 B4
G11
C (3) B5 RTD 2
G12 OPTO 14 RELAY 11
F27 K12 B6
G13 B7
K15
G14 OPTO 15 B8 RTD 3
RELAY 12
G15 K16 B9
G16 OPTO 16
G17
COMMON B28
SEE SHEET 2 FOR NOTES G18 CONNECTION RTD 10
B29
H1 B30
J1
H2 OPTO 17 OPTO 25 J2
H3 J3
H4 OPTO 18 OPTO 26 J4 NOTE 7
COMMS
H5 J5
H6 OPTO 19 OPTO 27 J6
H7 J7
H8 OPTO 20 OPTO 28 J8 M17
H9 J9 SEE DRAWING EIA485/
H10 OPTO 21 OPTO 29 J10 10Px4001 KBUS
M18
PORT
H11 J11
M16
H12 OPTO 22 OPTO 30 J12 SCN
H13 J13
M1
H14 OPTO 23 OPTO 31 J14 AC OR DC
M2 x AUX SUPPLY
H15 J15
H16 OPTO 24 OPTO 32 J16
H17 J17
COMMON COMMON
H18 CONNECTION CONNECTION J18
CASE
EARTH
MiCOM P643 (PART)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
T4 T3 T1
T2 C24
A (1)
C23
C26
B (1)
D1 MiCOM P645 (PART)
C25
D2 OPTO 1
C28
D3 J11
WATCHDOG
C (1) OPTO 2 CONTACT J12
D4
NOTE 2 C27 J13
D5 WATCHDOG
T2 CONTACT J14
C18 D6 OPTO 3
H1
P2 A (2) D7 RELAY 1 H2
S2 C17 D8 OPTO 4 H3
RELAY 2 H4
C20 D9
OPTO 5 H5
S1 D10
B (2) RELAY 3 H6
D11 H7
P1 C19
D12 OPTO 6 RELAY 4 H8
C22
D13 H9
C (2) OPTO 7 RELAY 5 H10
D14
C21 H11
D15
RELAY 6 H12
T3 E24 OPTO 8
D16 H13
P2 A (3) D17 H14
COMMON RELAY 7
S2 E23 D18 H15
CONNECTION
H16
E26 F1
H17
F2 OPTO 9 RELAY 8
S1 B (3) H18
F3
P1 E25 G1
F4 OPTO 10
RELAY 9 G2
E28
F5 G3
C (3) OPTO 11
F6 RELAY 10 G4
E27 G5 NOTE 7
F7
T4 RELAY 11 COMMS
E18 OPTO 12 G6
F8
G7
P2 A (4) F9
RELAY 12 G8
S2 E17 F10 OPTO 13
G9
F11 RELAY 13 G10
E20 J17
F12 OPTO 14 G11
S1 B (4) SEE DRAWING
RELAY 14 G12 EIA485/
F13 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 PORT
E22 G14
RELAY 15 J16
F15 G15 SCN
C (4) OPTO 16
F16 G16
E21 G17 J1
F17 RELAY 16 AC OR DC
T5 COMMON G18 J2 x AUX SUPPLY
E12 F18 CONNECTION
A (5)
E11
E14
B (5)
E13
E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH
a b c a b c
C2 VA C2 VA
a b c
C1 C1
C4 VB C4 VB
OPTIONAL
C3 C3
NOTE 6
E2 VC E2 VC
NOTE 8
E1 VN E1 VN
E4
1.
(a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
C13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
C16 TN1 S1 P1
Y (HV)
C15
T4 T3 T2 T1 C24
A (1)
C23
C26
B (1)
D1 MiCOM P645 (PART)
C25
D2 OPTO 1
C28
D3 J11
WATCHDOG
C (1) OPTO 2 J12
D4 CONTACT
NOTE 2 C27 J13
D5 WATCHDOG
CONTACT J14 B1
T2 C18 OPTO 3
D6 H1 B2 RTD 1
P2 A (2) D7 RELAY 1 H2 B3
S2 C17 D8 OPTO 4 H3 B4
RELAY 2 H4 B5 RTD 2
C20 D9
OPTO 5 H5 B6
S1 D10
B (2) RELAY 3 H6 B7
D11 H7 B8 RTD 3
P1 C19
D12 OPTO 6 RELAY 4 H8 B9
C22
D13 H9
C (2) OPTO 7 RELAY 5 H10
D14
C21 H11 B28
D15
RELAY 6 H12 B29 RTD 10
T3 E24 D16 OPTO 8
H13 B30
P2 A (3) D17 H14
COMMON RELAY 7
S2 E23 D18 H15
CONNECTION
H16
E26 F1
H17
F2 OPTO 9 RELAY 8
S1 B (3) H18
F3
P1 E25 G1
F4 OPTO 10
RELAY 9 G2
E28
F5 G3
C (3) OPTO 11
F6 RELAY 10 G4
E27 G5 NOTE 7
F7
RELAY 11 COMMS
T4 E18 OPTO 12 G6
F8
G7
P2 A (4) F9
RELAY 12 G8
S2 E17 F10 OPTO 13
G9
F11 RELAY 13 G10
E20 J17
F12 OPTO 14 G11
S1 B (4) SEE DRAWING
RELAY 14 G12 EIA485/
F13 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 PORT
E22 G14
RELAY 15 J16
F15 G15 SCN
C (4) OPTO 16
F16 G16
E21 G17 J1
F17 RELAY 16 AC OR DC
T5 COMMON G18 J2 x AUX SUPPLY
E12 F18 CONNECTION
A (5)
E11
E14
B (5)
E13 CASE
EARTH
E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH
a b c a b c
C2 VA C2 VA
a b c
C1 C1
C4 VB C4 VB
OPTIONAL
C3 C3
NOTE 6
E2 VC E2 VC
NOTE 8
E1 VN E1 VN
E4
C15
T4 T3 T2 T1
C24
A (1)
C23
C26
B (1)
MiCOM P645 (PART)
D1
C25 B1
OPTO 1 20mA
D2
C28 B2
D3 J11 1mA OUTPUT 1
WATCHDOG B3
C (1) OPTO 2 CONTACT J12
D4
NOTE 2 C27 J13 B5
WATCHDOG 20mA
D5 J14
T2 CONTACT B6
C18 D6 OPTO 3 1mA OUTPUT 2
H1
B7
P2 A (2) D7 RELAY 1 H2
B9
S2 D8 OPTO 4 H3 20mA
C17
RELAY 2 H4 B10
D9 1mA OUTPUT 3
C20 H5 B11
D10 OPTO 5
S1 B (2) RELAY 3 H6 B13
20mA
D11 H7
P1 C19 B14
D12 OPTO 6 RELAY 4 H8 1mA OUTPUT 4
C22 B15
D13 H9 CLIO
C (2) RELAY 5 H10 B16
OPTO 7 20mA CURRENT LOOP
D14
H11 B17 INPUTS & OUTPUTS
C21 1mA INPUT 1
D15 RELAY 6 H12 NOTE 11
B18
T3 E24 OPTO 8
D16 H13
B20
P2 A (3) H14 20mA
D17 RELAY 7
COMMON B21
S2 D18 H15 1mA INPUT 2
E23 CONNECTION
H16 B22
E26 F1
H17 B24
OPTO 9 RELAY 8 20mA
S1 F2 H18
B (3) B25
1mA INPUT 3
F3
P1 E25 G1 B26
F4 OPTO 10
RELAY 9 G2
E28 B28
F5 20mA
G3
C (3) B29
OPTO 11 RELAY 10 G4 1mA INPUT 4
F6
G5 B30
E27
F7
T4 RELAY 11 G6
E18 F8 OPTO 12
G7
P2 A (4) F9 NOTE 7
RELAY 12 G8 COMMS
S2 E17 F10 OPTO 13 G9
F11 RELAY 13 G10
E20 J17
OPTO 14 G11
S1 F12 SEE DRAWING
B (4) RELAY 14 G12 EIA485/
F13 10Px4001. KBUS
P1 E19 G13 J18
OPTO 15 PORT
F14 G14
E22 RELAY 15 J16
F15 G15 SCN
C (4) OPTO 16 G16
F16
E21 G17 J1
F17 RELAY 16 AC OR DC
COMMON G18 J2 x AUX SUPPLY
T5 E12 F18 CONNECTION
A (5)
E11
E14
B (5)
E13
E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH
T1
T4 T3 T2 C24
A (1)
C23
C26
B (1)
D1 MiCOM P645 (PART)
C25
D2 OPTO 1
C28
D3 J11
WATCHDOG
C (1) OPTO 2 CONTACT J12
D4
NOTE 2 C27 J13
D5 WATCHDOG B1
T2 CONTACT J14
C18 D6 OPTO 3 OPTO 17
H1 B2
P2 A (2) D7 RELAY 1 H2 B3
S2 C17 D8 OPTO 4 H3 OPTO 18
B4
RELAY 2 H4
C20 D9 B5
OPTO 5 H5
S1 D10 B6 OPTO 19
B (2) RELAY 3 H6
D11 H7 B7
P1 C19
D12 OPTO 6 RELAY 4 H8 OPTO 20
B8
C22
D13 H9
B9
C (2) OPTO 7 RELAY 5 H10
D14 B10 OPTO 21
C21 H11
D15 B11
RELAY 6 H12
T3 E24 OPTO 8
D16 H13 B12 OPTO 22
P2 A (3) D17 H14
RELAY 7 B13
S2 COMMON
E23 D18 CONNECTION H15 OPTO 23
B14
H16
E26 F1 B15
H17
F2 OPTO 9 RELAY 8 OPTO 24
S1 B (3) H18 B16
F3 B17
P1 E25 G1
F4 OPTO 10 COMMON
RELAY 9 G2 B18 CONNECTION
E28
F5 G3
C (3) OPTO 11
F6 RELAY 10 G4
E27 G5
F7
T4 OPTO 12 RELAY 11 G6
E18 F8 NOTE 7
G7 COMMS
P2 A (4) F9
RELAY 12 G8
S2 E17 F10 OPTO 13
G9
F11 RELAY 13 G10
E20 J17
F12 OPTO 14 G11
S1 B (4) SEE DRAWING
RELAY 14 G12 EIA485/
F13 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 PORT
E22 G14
RELAY 15 J16
F15 G15 SCN
C (4) OPTO 16
F16 G16
E21 G17 J1
F17 RELAY 16 AC OR DC
T5 COMMON G18 J2 x AUX SUPPLY
E12 F18 CONNECTION
A (5)
E11
E14
B (5)
E13
E16
C (5) * POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
CASE
E15 EARTH
a b c a b c
C2 VA C2 VA
a b c
C1 C1
C4 VB C4 VB
OPTIONAL
C3 C3
NOTE 6
E2 VC E2 VC
NOTE 8
E1 VN E1 VN
E4
T1
T4 T3 T2 C24
A (1)
C23
C26
B (1)
D1 MiCOM P645 (PART)
C25
D2 OPTO 1
C28
D3 J11
WATCHDOG
C (1) OPTO 2 CONTACT J12
D4
NOTE 2 C27 J13
D5 WATCHDOG
T2 CONTACT J14
C18 D6 OPTO 3
H1 B1
P2 A (2) D7 RELAY 1 H2 B2 RELAY 17
S2 C17 D8 OPTO 4 H3 B3
RELAY 2 H4 B4 RELAY 18
C20 D9
OPTO 5 H5 B5
S1 D10
B (2) RELAY 3 H6 B6 RELAY 19
D11 H7 B7
P1 C19
D12 OPTO 6 RELAY 4 H8 B8 RELAY 20
C22
D13 H9 B9
C (2) OPTO 7 RELAY 5 H10 B10 RELAY 21
D14
C21 H11 B11
D15
RELAY 6 H12 B12 RELAY 22
T3 OPTO 8
E24 D16 H13 B13
P2 A (3) D17 H14 B14
COMMON RELAY 7 RELAY 23
S2 E23 D18 H15 B15
CONNECTION
H16 B16
E26 F1
H17 B17
F2 OPTO 9 RELAY 8 RELAY 24
S1 B (3) H18 B18
F3
P1 E25 G1
F4 OPTO 10
RELAY 9 G2
E28
F5 G3
C (3) OPTO 11
F6 RELAY 10 G4
E27 G5
F7
T4 RELAY 11 G6
E18 F8 OPTO 12 NOTE 7
G7 COMMS
P2 A (4) F9
RELAY 12 G8
S2 E17 F10 OPTO 13
G9
F11 RELAY 13 G10
E20 J17
F12 OPTO 14 G11
S1 B (4) SEE DRAWING
RELAY 14 G12 EIA485/
F13 10Px4001. KBUS
P1 E19 G13 J18
F14 OPTO 15 PORT
E22 G14
RELAY 15 J16
F15 G15 SCN
C (4) OPTO 16
F16 G16
E21 G17 J1
F17 RELAY 16 AC OR DC
T5 COMMON G18 J2 x AUX SUPPLY
E12 F18 CONNECTION
A (5)
E11
E14
B (5)
E13
E16
B B A
C C B
A B C A B C
C
A B C
a b c a b c
C2 VA
C2 VA
a b c
C1
C1
C4 VB
C4 VB
OPTIONAL
C3
NOTE 6 C3
E2 VC
E2 VC
NOTE 8
E1 VN
E1 VN
E4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
A (1)
C23
D1
C26 OPTO 1
D2
B (1) D3 MiCOM P645 (PART)
C25 D4 OPTO 2
C28 D5 J11
WATCHDOG
D6 OPTO 3 CONTACT J12
C (1)
J13
NOTE 2 C27 D7 WATCHDOG
OPTO 4 CONTACT J14
T2 D8 B3
C18 H1
D9 RELAY 1 H2 RELAY 17
P2 A (2) B4
D10 OPTO 5 H3
S2 C17
RELAY 2 H4 B7
D11
C20 OPTO 6 H5 RELAY 18
D12
RELAY 3 H6 B8
S1 B (2) HIGH BREAK
D13
H7 B11 CONTACTS
P1 C19 D14 OPTO 7
RELAY 4 H8 RELAY 19
C22 D15 H9 B12
D16 OPTO 8 RELAY 5 H10 B15
C (2)
H11
C21 D17 RELAY 20
COMMON RELAY 6 H12 B16
T3 D18 CONNECTION
E24 H13
F1 H14
P2 A (3) RELAY 7
F2 OPTO 9 H15
S2 E23
F3 H16
E26 OPTO 10 H17
F4 RELAY 8
S1 B (3) H18 NOTE 7
F5 COMMS
E25 OPTO 11 G1
P1 F6
RELAY 9 G2
E28 F7
G3
F8 OPTO 12 RELAY 10
C (3) G4
F9 G5 J17
E27
F10 OPTO 13 RELAY 11 G6 SEE DRAWING
T4 E18 EIA485/
G7 10Px4001 KBUS
F11 J18
P2 A (4) RELAY 12 G8 PORT
F12 OPTO 14
S2 E17 G9 J16
F13 RELAY 13 SCN
G10
E20 OPTO 15
F14 G11 J1
S1 B (4) RELAY 14 G12 AC OR DC
F15
J2 x AUX SUPPLY
E19 OPTO 16 G13
P1 F16
G14
E22 F17 RELAY 15
COMMON G15
C (4) F18 CONNECTION G16
E21 G17
RELAY 16
G18
T5 E12
A (5)
E11
E14
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
B (5)
E13
E16 CASE
EARTH
C (5)
E15
SEE SHEET 2 FOR NOTES
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
D15
C (5)
F15
CASE
EARTH
SEE SHEET 2 FOR NOTES
* POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE
NEUTRAL TAILS (b) TERMINAL.
D13 8. DERIVED NEUTRAL POINT. SEE P64X/EN T/- - FOR DETAILS OF RESISTORS.
D16 TN1 S1 P1 9. FOR 0-10mA, 0-20mA, 4-20mA RANGE USE 20mA INPUTS & OUTPUTS
FOR 0-1mA RANGE USE 1mA INPUTS & OUTPUTS.
Y (HV)
D15
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
CASE
EARTH
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
a b c a b c
D2 VA D2 VA
a b c
D1 D1
D4 VB D4 VB
OPTIONAL
D3 D3
NOTE 6
F2 VC F2 VC
NOTE 8
F1 VN F1 VN
F4
GROUNDED WYE 1. (a) C.T. SHORTING LINKS MAKE BEFORE (b) DISCONNECT.
NEUTRAL TAILS
(b) TERMINAL.
TV LV HV
NOTE 3 (c) PIN TERMINAL (P.C.B. TYPE)
Grid Solutions
St Leonards Building
Redhill Business Park
Stafford, ST16 1WT, UK
+44 (0) 1785 250 070
[email protected]
© 2019 General Electric. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or
should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial
circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without
express written authority, is strictly prohibited.
P64x-TM-EN-4.1