RTHD - RTHD 400TR 0.5856kWpTR-2 - Consolidated Customer Package
RTHD - RTHD 400TR 0.5856kWpTR-2 - Consolidated Customer Package
RTHD - RTHD 400TR 0.5856kWpTR-2 - Consolidated Customer Package
Unit Overview
Chiller Model Water-Cooled Optimus (TM)
Refrigeration Capacity 400.0 tons
Cooling Efficiency 0.5915 kW/ton
Compressor Configuration D2
Evaporator Configuration G3
Condenser Configuration G3
IPLV.IP 0.4829 kW/ton
NPLV.IP 0.4934 kW/ton
Unit Voltage 460.V/60.Hz/3Ph
Refrigerant Type Refrigerant charge R134a
Oil Cooler With Oil Cooler
Agency Listing C/UL listing
Pressure Vessel Code ASME pressure vessel code
ASHRAE 90.1 Compliance ASHRAE up to 2016
A-weighted sound pressure 83 dBA
RTHDUD2F***UAG3W4LALG3D
Model Number 2LAL*VCQ*EXAB*XY***D*UT7*X
XXXVXX
Evaporator Information
Fluid Properties Flow Rate Construction Features
Fluid Type Water Design Flow 955.9 gpm Number of Passes 4 pass
Fluid Concentration 0.00 % Min Flow 466.0 gpm Tube Type Water only
Freeze Point 32.00 F Fluid Pressure Drop Left hand evaporator
Connection Side
connection
Fluid Temperatures Design PD 16.8 ft H2O
0.000100 hr-sq ft-deg
Evaporator Leaving 44.00 F Min PD 3.81 ft H2O Fouling Factor
F/ Btu
Evaporator Entering 54.00 F
Condenser Information
Fluid Properties Flow Rate Construction Features
Fluid Type Water Design Flow 1233 gpm Number of Passes 2 pass
Fluid Concentration 0.00 % Min Flow 589.0 gpm Tube Type 0.025" - enhanced
Fluid Temperatures Fluid Pressure Drop Left hand condenser
Connection Side
connection
Condenser Leaving 95.00 F Design PD 12.6 ft H2O
0.000250 hr-sq ft-deg
Condenser Entering 86.00 F Min PD 3.23 ft H2O Fouling Factor
F/ Btu
Unit Electrical
Unit Voltage 460.V/60.Hz/3Ph Run load amps/AFD input amps 328.50 A
Compressor Starter Wye-delta Min Circuit Ampacity 410.62 A
Total Power 236.6 kW Max Overcurrent Protection 700.00 A
Power Line Conn. Type Circuit breaker Starter Expected Inrush 730.00 A
Short Circuit Current Rating 10000.00 A Motor Locked Rotor Amps 2366.00 A
Max RLA 476
Physical Information
Dimensions Weights Charge
Length 147.700 in Operating Weight 21641.0 lb Refrigerant 700.0 lb
Width 70.300 in Shipping Weight 19508.0 lb Oil 12.00 gal
Height 80.000 in
Warranty
Standard Warranty
Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to
support the applicable operating weight (i.e. including completed piping, and full operating charges of
refrigerant, oil and water). The expectation of Trane equipment is that piping is fully supported by an
independent structure/system, without being connected to the waterbox. Once in place, the unit must
be level within 1/2" across the length and width of the unit. The Trane Company is not responsible for
equipment problems resulting from an improperly designed or constructed foundation.
General
Exposed metal surfaces are painted with air-dry beige direct to metal single component paint prior to
shipment. Each unit ships with a full operating charge of refrigerant and oil. Molded elastomeric
isolation pads are supplied for placement. Start-up and operator instruction by factory trained service
personnel is included.
Agency Listing
The chiller is UL listed to U.S. and Canadian safety standards.
Compressor - Motor
Semi-hermetic, direct-drive, rotary compressor with capacity control slide valve and differential
refrigerant pressure oil flow system. Four pressure lubricated rolling element bearing groups support
the rotating assembly.
Motor is a suction gas cooled, hermetically sealed, two-pole, squirrel cage induction-type.
Evaporator
Shells are carbon steel plate. Evaporator is designed, tested and stamped in accordance with ASME
Code for refrigerant side working pressure of 200 psig (1379 kPa).
All tube sheets are carbon steel. Evaporator tubes are individually replaceable. Tubes are externally
finned, internally enhanced seamless copper with lands at both tube sheets. Evaporator tubes are 1
inch (25.4 mm) in diameter. Tubes are mechanically expanded into tube sheets and mechanically
fastened to tube supports.
Water pass arrangements are with grooved connections 150 psig (1034.2 kPa) waterside.
Connections are left-handed. Waterside is hydrostatically tested at 1 1/2 times design working
pressure.
Oil Cooler
Unit has an oil cooler incorporated into the chiller oil circuit to provide reliable operation with low
design evaporator temperatures and/or high design condenser temperatures.
The single-phase, dual frequency 50 or 60 Hz, motor can be selected with 115 V and can be powered
directly from control power transformer at unit.
Valves are 8 inch (203.2 mm) in diameter and 150 psig (1034.2 kPa).
Refrigerant Circuit
An electronically controlled expansion valve maintains proper refrigerant flow.
2022/08/02 19:03:00 Page 12 of 14
Job Name: Melia Caracas 400TR Unit Tag: RTHD 400TR 0.
Prepared For: FEIBO Quantity: 1
Unit Controls
All unit controls are housed in an enclosure with removable plates to allow for customer connection of
power wiring and remote interlocks. All controls, including sensors, are factory mounted and tested
prior to shipment. Microcomputer controls provide all control functions including startup and shut down,
leaving chilled water temperature control, evaporator and condenser flow proving, compressor speed
control and loading, electronic expansion valve modulation, anti-recycle logic, and load limiting.
The Trane Symbio (TM) 800 controller, utilizing Adaptive Control microprocessor, automatically takes
action to avoid unit shut-down due to abnormal operating conditions associated with low evaporator
refrigerant temperature, high condensing temperature, or current overload. Should the abnormal
operating condition continue until a protective limit is violated, the unit will be shut down. Unit
protective functions of the Symbio (TM) 800 include: low evaporator refrigerant pressure, high
condenser refrigerant pressure, low oil flow, critical sensor or detection circuit faults, current overload,
high compressor discharge temperature, communications lost between modules, electrical distribution
faults, phase loss, phase imbalance, phase reversal, external and emergency stop, momentary power
loss, under/over voltage, and loss of evaporator or condenser water flow.
Unit Display
A full color TD-7 AdaptiView touch screen display indicates all important unit parameters, in logical
groupings on various screens. The parameters including chilled water set point, leaving chilled water
temperature, entering condenser water temperature, evaporator and condenser refrigerant
temperatures and pressures, compressor data, and all pertinent electrical information. The display
also provides on screen trending graphs of predefined parameters as well as customizable trend
graphs based on user defined parameters. The display also provides indication of the chiller top level
operating modes with detailed sub-mode reports available with a single key press, as well as
diagnostics annunciation and date and time stamped diagnostic history.
Operator Interface
Factory mounted to the door of the control panel, and tested after build completion, the operator
interface has an LCD touchscreen display for operator input with scrolling tabs for tabulated sets of
information. All information is displayed in clear language format. An evaporator report, condenser
report, compressor report, ASHRAE report, operator settings, service settings, service tests, and
diagnostics may be accessed. Some service settings and tests are accessed through the TechView
service tool.
The data contained in the evaporator, condenser, compressor, and ASHRAE reports includes:
Setpoints, water and air temperatures, refrigerant levels, refrigerant temperatures, superheat,
refrigerant approach, oil pressure, flow switch status, EXV position, head pressure control command,
compressor starts and run-time, line voltage, line phase percent RLA, Amps, and Volts.
Starter is a Wye-Delta closed transition configuration. Starter reduces expected inrush to 33 percent of
rated motor Locked Rotor Amps. UL 1995 type enclosure with top power wiring access and three-
phase solid-state overload protection. The starter is factory mounted and completely prewired to the
compressor motor and the control panel. Factory installed and wired 600VA-control power transformer
provides all unit control power (120 Vac secondary) as well as the display module power (24 Vac
secondary).
Starter Disconnect
A standard-interrupting molded-case circuit breaker is provided with through-the-door handle to
disconnect the main power, and comes pre-wired from the factory, with terminal block power
connections.
Insulation
Low temperature surfaces are covered with factory installed 3/4 inch (19.05 mm) Armaflex II or equal
(k=0.28) insulation, including the evaporator and water boxes, suction line, and motor housing. 3/8"
foam insulation will be used on the liquid level sensor and gas pump assembly, including piping. Lifting
lugs, base plates and service valves will not include insulation.
Warranty
A First Year Parts Warranty is included, covering parts for the complete unit.
Shipment Packaging
Unit is provided with shrink-wrapped opaque plastic, with UV protection and rust inhibitor, around
entire unit for shipment.