1 Status indicators
2 OPLC to EX-A1 connection port 2
3 Power supply connection points
4 EX-A1 to expansion module
connection port
2 3
Before using this product, it is the responsibility of the user to read and understand this document and
any accompanying documentation.
All examples and diagrams shown herein are intended to aid understanding, and do not guarantee
operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product in accordance with local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
This document is intended to aid trained and competent personnel in the installation of this equipment as
defined by the European directives for machinery, low voltage, and EMC. Only a technician or engineer trained
in the local and national electrical standards should perform tasks associated with the device’s electrical wiring.
Failure to comply with appropriate safety guidelines can result in severe personal injury or
property damage. Always exercise proper caution when working with electrical equipment.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Leave a minimum of 10mm space for ventilation between the top and bottom edges of the
device and the enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
DIN-rail mounting
Snap the device onto the DIN rail as shown below; the module will be squarely situated on the DIN rail.
(3.66")
93mm
POWER
44.5mm
(1.75")
2
3.5mm
(0.137")
80mm
1 4mm (3.15")
(0.55") 60mm
(2.362")
Screw-Mounting
The figure on the next page is drawn to scale. It may be used as a guide for screw-mounting the module.
Mounting screw type: either M3 or NC6-32.
80mm
(3.15")
5.8mm 68.4mm
(0.228") (2.693")
4mm
(0.16")
(3.346")
(3.66")
93mm
85mm
4mm (x2)
(0.16")
M90 EX-A1
Earth
POWER
I/O
expansion
port
Pin #1 1 D- 1 1
8 D+ 8 8
2 CK-
4 CK+ 2 2
3 0V 4 4
6 0V Connect to earth near the M90
To avoid damaging the system, do not connect or disconnect the device when the
power is on.
1 2
Component identification
1 Module-to-module connector
2 Protective cap
Wiring
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
Do not connect the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s 0V pin.
In the event of voltage fluctuations or non-conformity to voltage power supply specifications,
connect the device to a regulated power supply.
Double-check all the wiring before turning on the power supply.
Wiring Procedures
2 2
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm –3.31 mm ) for all wiring purposes.
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure that a proper connection can be made.
4. Tighten enough to keep the wire from pulling free.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·m).
Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break.
Install at maximum distance from high-voltage cables and power equipment.
A non-isolated power supply can be used provided that a 0V signal is connected to the chassis.
Note that both the OPLC and the EX-A1 must be connected to the same power supply.
POWER
Circuit protection
12VDC or device
24VDC 0V
power +V
supply
Accessories
EX1-CA050 0.5 meter communication cable
EX1-CA100* 1 meter communication cable
EX1-CA200 2 meter communication cable
EX1-CA400 4 meter communication cable
IO-CAP Protective cap, used to cover the connection port of the final I/O module in the system
*EX1-CA100 is provided with the EX-A1 adapter; other cables are available by separate order.
Adapter
Expansion module
0 1 2 3 4 5 6 7
identification number
The formula below is used to assign addresses for I/O modules used in conjunction with the OPLC.
X is the number representing a specific module’s location (0-7). Y is the number of the input or output on that
specific module (0-15).
The number that represents the I/O’s location is equal to:
32 + x • 16 + y
Examples
Input #3, located on expansion module #2 in the system, will be addressed as I 67,
67 = 32 + 2 • 16 + 3
Output #4, located on expansion module #3 in the system, will be addressed as O 84,
84 = 32 + 3 • 16 + 4.
EX90-DI8-RO8 is a stand-alone I/O module. Even if it is the only module in the configuration, the EX90-DI8-
RO8 is always assigned the number 7.
Its I/Os are addressed accordingly.
Example
Input #5, located on an EX90-DI8-RO8 connected to an OPLC will be addressed
as I 149, 149 = 32 + 7 • 16 + 5
About Unitronics
Unitronics Industrial Automation Systems has been producing PLCs, automation software and accessory
devices since 1989.
Unitronics’ OPLC controllers combine full-function PLCs and HMI operating panels into single, compact units.
These HMI + PLC devices are programmed in a single, user-friendly environment. Our clients save I/O points,
wiring, space, and programming time; elements that translate directly into cost-efficiency.
Unitronics supports a global network of distributors and sales representatives, as well as a U.S. subsidiary.
For more information regarding Unitronics products, contact your distributor, Unitronics headquarters via email:
[email protected], or visit the Unitronics website at http://www.unitronics.com/.
Under no circumstances will Unitronics be liable or responsible for any consequential damage that may
arise as a result of installation or use of this equipment, and is not responsible for problems resulting
from improper or irresponsible use of this device.
No part of this document may be used for any purpose other than for the purposes specifically indicated
herein nor may it be reproduced or transmitted in any form or by any means, electronic or mechanical,
including photocopying and/or recording, for any purpose without written permission from Unitronics.
The information appearing in this document is for general purposes only. Unitronics makes no warranty
of any kind with regard to the information appearing in this document, including, but not limited to,
0implied warranties of merchantability and/or fitness for a particular use or purpose. Unitronics assumes
no responsibility for the results, direct and/or indirect, of any misuse of the information appearing in this
document nor for any use of the Unitronics products referred to herein in any manner deviating from the
recommendations made in this document. Unitronics assumes no responsibility for the use of any parts,
components, or other ancillary appliances including circuitry other than as recommended hereunder or
other than that embodied in the Unitronics product.
Unitronics retains all rights to its proprietary assets including, but not limited to its software products
which are copyrighted and shall remain the property of Unitronics. Copyright protection claimed includes
all Forms and matters of copyrightable materials and information legally allowed including but not limited
to material generated from the software programs which are displayed on the screen of the Unitronics
products such as styles, templates, icons, screen displays, looks, etc. Duplication and/or any
unauthorized use thereof are strictly prohibited without prior written permission from Unitronics.
All brand or product names are used for identification purpose only and may be trademarks or registered
trademarks of their respective holders.
Unitronics reserves the right to revise this publication from time to time and to amend its contents and
related hardware and software at any time. Technical updates (if any) may be included in subsequent
editions (if any).
Unitronics product sold hereunder can be used with certain products of other manufacturers at the user’s
sole responsibility.
5408-0002-1