Screw Conveyor Applications VFD Settings: S.No Parameters Specification Set Value

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SCREW CONVEYOR APPLICATIONS VFD SETTINGS

S.NO PARAMETERS SPECIFICATION SET VALUE


1 P0 Torque Boost 2.5 HZ
2 P1 Maximum frequency 50hz
3 p4 motor 1 low speed 35hz
4 P5 motor 2 low speed 30hz
5 P7 Acceleration time 1sec
6 P8 deacceleration time 1.0sec
7 P9 Electronic thermal O/L relay first motor 28 Amps
8 P13 Starting frequency 0hz
9 P14 Load pattern Selection 1
10 P18 High speed maximum frequency 50hz
11 P19 base frequency voltage 9999
12 P22 Stall prevention operation selection 200%
13 P24 motor 2 high speed 50hz
14 P25 motor 1 high speed 50hz
15 P29 Acceleration&deacceleration pattern selection 2
16 P44 second acceleration time 1sec
17 P45 second deacceleration time 1.6sec
18 P46 second torque boost 2%
19 P47 second V/F (base frequency) 50hz
20 P48 second stall prevention operation level 150%
21 P51 Second Electronic thermal O/L relay
22 P79 operation mode selection 3
23 P80 motor capacity 15 kw
24 P81 NO.of motor poles 4
25 P83 rated motor voltage 415
26 P89 speed control gain(advanced magnetic flux vector) 200
27 P183 MRS terminal function 3
28 P190 RUN terminal function selection 0
29 P292 automatic acceleratin /deacceleration 0
30 P450 second applied motor 0
31 P571 Holding time at astart 9999

Note: P51 To be set depends on FLY ASH MOTOR Amps rating

You might also like