Cascade Control uses the output of the primary controller to manipulate the setpoint of the
secondary controller as if it were the final control element.
Secondary loop process dynamics must be at least four times as fast as primary loop
process dynamics.
Secondary loop must have influence over the primary loop.
Secondary loop must be measured and controllable.
Control of heat exchanger outlet temperature using steam flow as secondary loop.
Cascade Control Modes
In most applications, the control loop is not functioning as a cascade loop all the time. The
operator (in the case of batch control, the batch control program) has the ability to change
modes. Following is the typical selection of modes of operation available for a cascade control
loop. Manual and Auto are usually used during startup while cascade is used for normal
operation.
Tracking:
In A, Manual mode, the set point of the flow controller tracks the actual flow variable.
In B, Auto mode, the output of the temperature controller tracks the setpoint of the flow
controller.
In C, Cascade mode, the temperature controller manipulates the setpoint of the flow controller.
Therefore, when switching from one mode to another there is no sudden change in the output
to the valve.
Windup
If the secondary controller cannot deliver enough flow, even with its valve wide open, to bring
the primary measured variable to its set point, the primary controller will "windup" and continue
to increase the flow setpoint above the maximum flow. Later, when the flow is sufficient to bring
the primary measurement to its set point, the primary controller must take the time to "wind
down" the secondary set point to the actual flow before the valve begins to close.
By connecting the secondary measurement to the external feedback of the primary, we can
eliminate the windup problem.