BACnetScan en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

Shanghai Sunfull Automation Co.

, LTD

BACnetScan
User Manual

Shanghai Sunfull Automation Co., LTD

I
Shanghai Sunfull Automation Co., LTD

目录

1 Preface .................................................................................................................................................. 1

1.1 Disclaimer ...................................................................................................................................... 1


1.2 Technical Support ........................................................................................................................... 1
2 Overview............................................................................................................................................... 1
3 Configuration And Operation ............................................................................................................ 1
3.1 Language Settings .......................................................................................................................... 2
3.2 Scanning BACnet IP ....................................................................................................................... 3
3.2.1 BACnet IP Settings ................................................................................................................ 3
3.2.2 Search BACnet IP .................................................................................................................. 5
3.2.3 Search Object ......................................................................................................................... 6
3.2.4 Read Properties ...................................................................................................................... 7
3.2.5 Write Present Value ................................................................................................................ 8
3.3 Scanning BACnet Ethernet ........................................................................................................... 10
3.4 Scanning BACnetMS/TP .............................................................................................................. 10
3.4.1 BACnetMS/TP Settings ....................................................................................................... 10
3.4.2 Search BACnetMS/TP ......................................................................................................... 12
3.4.3 Search Object ....................................................................................................................... 14
3.4.4 Read Properties .................................................................................................................... 15
3.4.5 Write Present Value .............................................................................................................. 17
3.4.6 Modify Object ID ................................................................................................................. 18
3.5 Export to EXCEL ......................................................................................................................... 21
3.6 Save logs....................................................................................................................................... 23
4 Common problems ............................................................................................................................ 25
4.1 Connot serach BACnet IP ............................................................................................................. 25
4.2 Search to a BACnet IP device, but can't sweep equipment under the point.................................. 25

4.3 After using BACnetScan, BACnetIP software on the PC is not normal ....................................... 25

II
Shanghai Sunfull Automation Co., LTD

1 Preface

1.1 Disclaimer

All technical content within this document can be modified without notice. The content of
the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or
accidental abuse, misuse, or use under abnormal conditions repairs are charged to the user.
Shanghai Sunfull Automation Co., Ltd will not be liable for accidental loss of use or inability
to use this product, such as loss of business income. Shanghai Sunfull Automation CO.,LTD
shall not be liable for consequences of improper use.

1.2 Technical Support

 Email:[email protected]

 QQ:564166173

 TEL:021-58776098

 website:http://www.opcmaster.com or http://www.bacnetchina.com

2 Overview

BACnetScan was developed by Shanghai Sunfull Automation Co., LTD, It is a BACnet

client scan software,easy to operate and quick scan speed from machine.

 Support BACnet Ethernet, BACnet IP and BACnet MSTP.

 Support read and write present value property, export EXCEL etc.

 Supoort Chinese and English Language.

3 Configuration And Operation

Open BACnetScan.exe, click BACnet from list we can see BACnet Ethernet ,BACnet

IP and BACnet MS/TP. As below figure 3.1.

1
Shanghai Sunfull Automation Co., LTD

Figure 3.1 open BACnetScan

3.1 Language Settings

Click “View” menu, select Language Setting, as below Figure 3.1.1.

Figure 3.1.1 Language Setting

2
Shanghai Sunfull Automation Co., LTD

Select language as below Figure 3.1.2.

Figure 3.1.2 Select Language

3.2 Scanning BACnet IP

3.2.1 BACnet IP Settings

If the machine or Server support BACnet IP, We will be on BACnet IP Settings before

scanning, click Tools select BACnet IP Setting. As below Figure 3.2.1.

3
Shanghai Sunfull Automation Co., LTD

Figure 3.2.1 BACnet IP Setting

Or right click BACnet IP and select BACnet IP Setting. As below Figure 3.2.2.

Figure 3.2.2 BACnet IP Setting

Dialogue box Network Communication Configuration as below Figure 3.2.3.We can see

the BACnet IP configuration interface and modify on it. The default wait time is 10000

4
Shanghai Sunfull Automation Co., LTD

milliseconds, if the device response is slow, the user should set the response to the waiting time

for a bit longer .

As the below figure, you can search instancenumber from 1 to 100.The scope of

instancenuber is setted by yourself.

When the IP address of BACnet gateway is 192.168.2.88, Select “Register Foreign

Device“ and input IP address 192.168.1.119, you search the gataway from 1 network segment.

Figure 3.2.3 Network Communication Configuration

3.2.2 Search BACnet IP

Right click BACnet IP and select “Search Device…” or click button. As below
Figure 3.2.4.

5
Shanghai Sunfull Automation Co., LTD

Figure 3.2.4 Search Device

Searched BACnet Device 548625 in same Network segment as below Figuer 3.2.5.

Figure 3.2.5 Search device

3.2.3 Search Object

Click Device ,property and valve on the right, right click Search Object or click button

,as below Figure 3.2.6.

6
Shanghai Sunfull Automation Co., LTD

Figure 3.2.6 Search Object

Pay attention to check the " Auto Read properties" said at the time of scanning point,

automatically read all attributes of the point also.

3.2.4 Read Properties

After research objects, the user will read or write the object, select object and right click

Read Properties or click “ ” as below Figure 3.2.7.

7
Shanghai Sunfull Automation Co., LTD

Figure 3.2.7 Read Properties

After the operation to complete. We can see the current value as below Figure 3.2.8.

Figure 3.2.8 Read present value

Pay attention to "Read Present Value” menu refers to read only the current value of this

attribute values.

3.2.5 Write Present Value

8
Shanghai Sunfull Automation Co., LTD

Analog Value, Analog Output, the Binary Value, the Binary Output Value and Multi, Multi

- state - the state Output the six types of object support write operations.

Write value to Analog Output,3001483.Present value is 0, written to the value of 1 ,click

set.see as below Figure 3.2.9 and Figure 3.2.10,present value changed as below Figure 3.2.11.

Figure 3.2.9 Write Present Value

Figure 3.2.10 Write value

9
Shanghai Sunfull Automation Co., LTD

Figure 3.2.11 present-value change to 1.00

3.3 Scanning BACnet Ethernet

BACnet Ethernet as BACnet IP. Currently supported BACnet Ethernet equipment is less,

the more likely to encounter a edgerton controller, operation mode and BACnet IP are similar,

there is no need to do.

3.4 Scanning BACnetMS/TP

Serial port on the computer by RS232 to RS485 module connected to the scene of the

DDC. If there is no serial port on a computer, you can use the USB turn serial port to connect

RS232 to RS485 module.

3.4.1 BACnetMS/TP Settings

When the machine support BACnetMS/TP protocol, click Tools select BACnet MS/TP

Setting as below Figure 3.4.1.

10
Shanghai Sunfull Automation Co., LTD

Figure 3.4.1 BACnet MS/TP Setting

Or right click BACnet IP and select BACnet IP Setting. As below Figure 3.4.2.

Figure 3.4.2 BACnet MS/TP Setting

In the pop up dialog box set communication parameters, MAC address cannot conflict

11
Shanghai Sunfull Automation Co., LTD

with the device MAC address, the default MAC address is 127, response latency defaults to

60000 milliseconds. Baud rate is 38400 by default, according to the actual situation, set up by

the user. Request timeout refers to the response time, the default timeout for 50 milliseconds As

below Figure 3.4.3.

Figure 3.4.3 Serial Port Communication Cofiguration

3.4.2 Search BACnetMS/TP

Double-click“ BACnet MS/TP "nodes, or click the“ ”, and right click the mouse to

click the" search equipment..." Menu, you can also scan the RS485 bus BACent MS/TP

equipment. As below Figure 3.4.4.

12
Shanghai Sunfull Automation Co., LTD

Figure 3.4.4 Search Device

Search to the equipment Number within the same network segment (Device Instance

Number) for 10 BACnet MS/TP equipment, models for IOM3731 is Johnson. As below Figure

3.4.5.

13
Shanghai Sunfull Automation Co., LTD

Figure 3.4.5 Searched Device 10

3.4.3 Search Object

Double-click " ", or click the toolbar button" " ,and right-click the mouse pop-up

context menu click on" search..." .As below Figure 3.4.6.

14
Shanghai Sunfull Automation Co., LTD

Figure 3.4.6 Search Object

Pay attention to check the " Auto Read properties" said at the time of scanning point,

automatically read all attributes of the point also.

3.4.4 Read Properties

After research objects, the user will read or write the object, select object and right click

Read Properties or click “ ” as below Figure 3.4.7.

15
Shanghai Sunfull Automation Co., LTD

Figure 3.4.7 Read Properties

Pay attention to "Read Present Value” menu refers to read only the current value of this

attribute values.

16
Shanghai Sunfull Automation Co., LTD

Figure 3.4.8 Object Property

3.4.5 Write Present Value

Analog Value, Analog Output, the Binary Value, the Binary Output Value and Multi, Multi

- state - the state Output the six types of object support write operations.

Write value to Binary Output,10029.Present value is 0, written to the value of 1 ,click

set.see as below Figure 3.4.9, present value changed as below Figure 3.4.10.

17
Shanghai Sunfull Automation Co., LTD

Figure 3.4.9 Write Present Value

Figure 3.4.10 present-value change to 1.00

3.4.6 Modify Object ID

For BACnet MS/TP equipment, MAC address must assure the only (usually by dial the
18
Shanghai Sunfull Automation Co., LTD

code switch). Configuration software using the device's station number is the device ID DDC,

also requires only, Shanghai sunfull gateway can change device ID on the DDC by

BACnetScan. Advice is to put the device ID of DDC modified into and MAC address is

consistent, BACnetScan methods to modify the device ID function is as follows.

Frist, BACnetScan scanning equipment. As below Figure 3.4.11.

Figure 3.4.11 Modify Object ID

Or click Edit select Modify Object ID as below Figure 3.4.12.

19
Shanghai Sunfull Automation Co., LTD

Figure 3.4.12 Modify Object ID

Find the device object, right click the mouse to click the modified Object ID..., as below

Figure 3.4.13.

Figure 3.4.13 Modify Object ID

In the pop up dialog to modify the ID number of the current equipment, if the

modification is successful, the following message window will prompt change device ID.

20
Shanghai Sunfull Automation Co., LTD

3.5 Export to EXCEL

Export to EXCEL from all object we researched. Or the user can Export all object to

X2Modbus, X2BACnet and X2OPC, easy to edit , as below Figure 3.5.1.

Figure 3.5.1 Export to EXCEL

Figure 3.5.2 Export to EXCEL

21
Shanghai Sunfull Automation Co., LTD

Figure 3.5.3 Open the EXCEL

Also note that point of each attribute value can replicate, convenient user to edit . As

below Figure 3.5.4.

Figure 3.5.4 Copy Object Property

22
Shanghai Sunfull Automation Co., LTD

3.6 Save logs

Click View, select Save Log, as below Figure 3.6.1.

Figure 3.6.1 Select Save Log

Or in the information window for the right mouse button pop-up shortcut menu, click the

"save log..." ,as below Figure 3.6.2.

23
Shanghai Sunfull Automation Co., LTD

Figure 3.6.1 Select Save Log

Save the log file, the default name for BACnetScan log. As below Figure 3.6.3.

Figure 3.6.3 Save Log

24
Shanghai Sunfull Automation Co., LTD

4 Common problems

4.1 Connot serach BACnet IP

Due to some BACnetIP device does not support all radio, such as Johnson NAE.

BACnetScan also does not support all broadcasting search, it will lead to more than one

problem is that when the PC is so, may produce less than BACnetIP search equipment. If you

encounter this problem, the communication parameter Settings, select the correct so you can

solve the problem. In addition when using BACnetScan ensure computer firewall closed.

4.2 Search to a BACnet IP device, but can't sweep equipment under the
point

In general is still running on the computer the other BACnet IP software, UDP port 47808

occupied lead to can't BACnetScan scanning equipment. If you encounter this problem, please

close other software can solve .

4.3 After using BACnetScan, BACnetIP software on the PC is not normal

Due to the UDP port 47808 is occupied by a BACnetScan, please close BACnetScan can

solve.