1 Preface
1.1 Disclaimer
All technical content within this document can be modified without notice. The content of
the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or
accidental abuse, misuse, or use under abnormal conditions repairs are charged to the user.
Shanghai Sunfull Automation Co., Ltd will not be liable for accidental loss of use or inability
to use this product, such as loss of business income. Shanghai Sunfull Automation CO.,LTD
shall not be liable for consequences of improper use.
Email:[email protected]
QQ:564166173
TEL:021-58776098
website:http://www.opcmaster.com or http://www.bacnetchina.com
2 Overview
client scan software,easy to operate and quick scan speed from machine.
Support read and write present value property, export EXCEL etc.
Open BACnetScan.exe, click BACnet from list we can see BACnet Ethernet ,BACnet
1
Shanghai Sunfull Automation Co., LTD
2
Shanghai Sunfull Automation Co., LTD
If the machine or Server support BACnet IP, We will be on BACnet IP Settings before
3
Shanghai Sunfull Automation Co., LTD
Or right click BACnet IP and select BACnet IP Setting. As below Figure 3.2.2.
Dialogue box Network Communication Configuration as below Figure 3.2.3.We can see
the BACnet IP configuration interface and modify on it. The default wait time is 10000
4
Shanghai Sunfull Automation Co., LTD
milliseconds, if the device response is slow, the user should set the response to the waiting time
As the below figure, you can search instancenumber from 1 to 100.The scope of
Device“ and input IP address 192.168.1.119, you search the gataway from 1 network segment.
Right click BACnet IP and select “Search Device…” or click button. As below
Figure 3.2.4.
5
Shanghai Sunfull Automation Co., LTD
Searched BACnet Device 548625 in same Network segment as below Figuer 3.2.5.
Click Device ,property and valve on the right, right click Search Object or click button
6
Shanghai Sunfull Automation Co., LTD
Pay attention to check the " Auto Read properties" said at the time of scanning point,
After research objects, the user will read or write the object, select object and right click
7
Shanghai Sunfull Automation Co., LTD
After the operation to complete. We can see the current value as below Figure 3.2.8.
Pay attention to "Read Present Value” menu refers to read only the current value of this
attribute values.
8
Shanghai Sunfull Automation Co., LTD
Analog Value, Analog Output, the Binary Value, the Binary Output Value and Multi, Multi
- state - the state Output the six types of object support write operations.
set.see as below Figure 3.2.9 and Figure 3.2.10,present value changed as below Figure 3.2.11.
9
Shanghai Sunfull Automation Co., LTD
BACnet Ethernet as BACnet IP. Currently supported BACnet Ethernet equipment is less,
the more likely to encounter a edgerton controller, operation mode and BACnet IP are similar,
Serial port on the computer by RS232 to RS485 module connected to the scene of the
DDC. If there is no serial port on a computer, you can use the USB turn serial port to connect
When the machine support BACnetMS/TP protocol, click Tools select BACnet MS/TP
10
Shanghai Sunfull Automation Co., LTD
Or right click BACnet IP and select BACnet IP Setting. As below Figure 3.4.2.
In the pop up dialog box set communication parameters, MAC address cannot conflict
11
Shanghai Sunfull Automation Co., LTD
with the device MAC address, the default MAC address is 127, response latency defaults to
60000 milliseconds. Baud rate is 38400 by default, according to the actual situation, set up by
the user. Request timeout refers to the response time, the default timeout for 50 milliseconds As
Double-click“ BACnet MS/TP "nodes, or click the“ ”, and right click the mouse to
click the" search equipment..." Menu, you can also scan the RS485 bus BACent MS/TP
12
Shanghai Sunfull Automation Co., LTD
Search to the equipment Number within the same network segment (Device Instance
Number) for 10 BACnet MS/TP equipment, models for IOM3731 is Johnson. As below Figure
3.4.5.
13
Shanghai Sunfull Automation Co., LTD
Double-click " ", or click the toolbar button" " ,and right-click the mouse pop-up
14
Shanghai Sunfull Automation Co., LTD
Pay attention to check the " Auto Read properties" said at the time of scanning point,
After research objects, the user will read or write the object, select object and right click
15
Shanghai Sunfull Automation Co., LTD
Pay attention to "Read Present Value” menu refers to read only the current value of this
attribute values.
16
Shanghai Sunfull Automation Co., LTD
Analog Value, Analog Output, the Binary Value, the Binary Output Value and Multi, Multi
- state - the state Output the six types of object support write operations.
set.see as below Figure 3.4.9, present value changed as below Figure 3.4.10.
17
Shanghai Sunfull Automation Co., LTD
For BACnet MS/TP equipment, MAC address must assure the only (usually by dial the
18
Shanghai Sunfull Automation Co., LTD
code switch). Configuration software using the device's station number is the device ID DDC,
also requires only, Shanghai sunfull gateway can change device ID on the DDC by
BACnetScan. Advice is to put the device ID of DDC modified into and MAC address is
19
Shanghai Sunfull Automation Co., LTD
Find the device object, right click the mouse to click the modified Object ID..., as below
Figure 3.4.13.
In the pop up dialog to modify the ID number of the current equipment, if the
modification is successful, the following message window will prompt change device ID.
20
Shanghai Sunfull Automation Co., LTD
Export to EXCEL from all object we researched. Or the user can Export all object to
21
Shanghai Sunfull Automation Co., LTD
Also note that point of each attribute value can replicate, convenient user to edit . As
22
Shanghai Sunfull Automation Co., LTD
Or in the information window for the right mouse button pop-up shortcut menu, click the
23
Shanghai Sunfull Automation Co., LTD
Save the log file, the default name for BACnetScan log. As below Figure 3.6.3.
24
Shanghai Sunfull Automation Co., LTD
4 Common problems
Due to some BACnetIP device does not support all radio, such as Johnson NAE.
BACnetScan also does not support all broadcasting search, it will lead to more than one
problem is that when the PC is so, may produce less than BACnetIP search equipment. If you
encounter this problem, the communication parameter Settings, select the correct so you can
solve the problem. In addition when using BACnetScan ensure computer firewall closed.
4.2 Search to a BACnet IP device, but can't sweep equipment under the
point
In general is still running on the computer the other BACnet IP software, UDP port 47808
occupied lead to can't BACnetScan scanning equipment. If you encounter this problem, please
Due to the UDP port 47808 is occupied by a BACnetScan, please close BACnetScan can
solve.
25