PA13-SERIES PACKAGED AIR CONDITIONERS

Cooling Capacities: 23,000 to 56,500


SEER: 13.0

GREEN REFRIGERANT R-410A

FRONT (INDOOR AIRFLOW) END OF UNIT

BACK (OUTDOOR AIRFLOW) END OF UNIT

Standard Engineered Features Field Installed Accessories


Air Conditioner Compressor: Compressor Control Module: Optional Field Installed Electric Heat
Reciprocating compressors with Built in off delay timer adjustable from Strips:
crankcase heaters are standard on 2, 30 seconds to 5 minutes. 2 minute With automatic limit and thermal cutoff.
2½ and 3 ton models. Scroll on delay if power interrupt. 120 • Field installed heater package for all
compressors are used on all other second bypass for low pressure models.
models and no crankcase heaters control, and both soft and manual • Features slide in field assembly with
are required. lockouts for high and low pressure various BTUH outputs.
controls. Alarm output for alarm relay. • Permits stocking of only one unit.
R-410A Refrigerant:
Designed with R 410A (HFC) non Phase Rotation Monitor: Optional Field Installed Low Ambient
ozone depleting refrigerant in Standard on all 3 phase models. Control:
compliance with the Montreal protocol Protects against reverse rotation if Cycles outdoor fan motor below 55°F
and 2010 EPA requirements. power supply is not properly outdoor temperature to maintain acceptable
connected. condensing pressure.
ECM Indoor Blower Motor:
Features an electronically commutated High & Low Pressure Switches are
motor providing super high efficiency, Auto-Reset
low sound levels and soft start Built in lockout circuit resets from the
capabilities. The motor is self room thermostat. Provides commercial
adjusting to provide the proper airflow quality protection to the compressor.
rate for a broad range of static
Pre-Painted 20 Gauge Zinc Coated
pressure in ducted installations without
Steel Cabinet:
user adjustment or wiring changes.
Cleaned, rinsed, sealed and dried
Aluminum Finned Copper Coils: before the polyurethane primer is
Grooved tubing and enhanced applied. The cabinet is handsomely
louvered fin for maximum heat finished with a baked on textured
transfer and energy efficiency. enamel, which allows it to withstand
1000 hours of salt spray tests per
Outdoor coil is constructed with
ASTM B117 03.
special corrosion resistant
hydrophilic fin stock with 2 layer Pre-Painted 16 Gauge Zinc Coated
coating. (1st layer blue acrylic Unit Base:
primer; 2nd layer clear topcoat.) The unit base is treated with the
same paint coatings as the cabinet
Thermal Expansion Valves:
above, insuring years of service.
Models with reciprocating
compressors have bleed TXV, Top Discharge Outdoor Fan:
models with scroll compressor have Efficiently moves air quietly for
non bleed TXV. effective heat exchange.
Discharge Muffler: Electrical Components & Controls:
Standard on 2½ and 3 ton models. Readily accessible for easier service.
Liquid Line Filter Drier:
Protects system against moisture.
Form No. S3383-509
Supersedes S3383-908
Page 1 of 8
Cooling Capacities and Efficiency Ratings
MODELS P h ase B TU H SEER
PA13242-A 1 23,000 13.00
PA13302-A 1 29,000 13.00
PA13362-A, -B 1 and 3 34,000 13.00
PA13422-A, -B, -C 1 and 3 43,000 13.50
PA13482-A, -B, -C 1 and 3 46,500 13.00
PA13602-A, -B, -C 1 and 3 56,500 13.00
Tested and Certified in accordance with ARI Standard 210/240 2003.

General Specifications
Model PA13242-A PA13302-A PA13362-A PA13362-B PA13422-A PA13422-B PA13422-C PA13482-A PA13482-B PA13482-C PA13602-A PA13602-B PA13602-C

Electric Rating –
230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-3 230/208-60-1 230/208-60-3 460-60-3 230/208-60-1 230/208-60-3 460-60-3 230/208-60-1 230/208-60-3 460-60-3
60 Hz – Circuit A
Operating Voltage Range 197 - 253 197 - 253 197 - 253 187 - 253 197 - 253 187 - 253 414 -506 197 - 253 187 - 253 414 -506 197 - 253 187 - 253 414 -506

Minimum Circuit Ampacity 4 15 18 24 16 33 23 12 33 29 14 39 26 17

BC SC 9 11 15 10 21 15 8 22 14 8 26 16 9

Field Wire Size 3 12 10 8 12 10 10 14 8 10 12 8 10 10

Ground Wire Size 12 10 8 12 10 10 14 8 10 14 8 10 12

Delay Fuse – Max 2 20 25 35 20 50 35 15 50 40 20 60 40 25

Total unit Amps – 230/208 10.8/11.8 13.3/14.8 16.4/18.4 17.0/13.3 16.2/18.1 14.1/15.4 10.4 23.0/24.7 16.9/18.0 10.7 25.3/28.9 17.7/19.9 11.9

Compressor – Circuit A

Compressor Type Recip. Recip. Recip. Recip. Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Volts 230/208 230/208 230/208 230/208 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460

Rated Load Amps 7.5/8.5 9.5/11 12/14 7.6/8.9 11.8/13.7 8.3/9.6 7.7 17/18.7 10.9/12 7.7 19.3/22.9 11.7/13.9 8.6

Lock Rotor Amps 48/48 57/57 74/74 75/75 115/115 115/115 50 117/117 83.1/83.1 50 134/134 110/110 52

Fan Motor and


C o n d en ser
Fan Motor – HP 1/6 - 825 1/6 - 825 1/6 - 825 1/6 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825

Fan Motor Amps 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Fan – Dia./CFM 24"/2700 24"/2600 24"/2600 24"/2600 24"/3400 24"/3400 24"/3400 24"/3400 24"/3400 24"/3400 24"/3400 24"/3400 24"/3400

Motor and Evaporator


Blower Motor – HP 1 1/3 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM

Blower Motor – Amps 2.2 2.7 3.3 3.3 3.9 3.9 3.9 4.5 4.5 4.5 5.0 5.0 5.0

Charge (R-410 oz ) 75 85 120 120 160 160 160 160 160 160 160 160 160

Shipping Weight (pounds) 360 410 410 410 440 440 490 440 440 490 450 450 500

1 ECM = Electronically Commutated Motor


2 Maximum time delay fuse or HACR type circuit breaker for protection of field wiring devices.
3 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
4 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to National Electric Code (latest revision), Article 310 for power
conductor sizing.

Indoor Blower Performance 1


2 3 4
Rated MAX Continuous Rated Rated
MODEL
ESP ESP Airflow Cooling Electric Heat
C FM C FM
PA1324 0.10 0.50 600 800 1000
PA1330 0.15 0.50 750 1000 1000
PA1336 0.15 0.50 825 1100 1100
PA1342 0.20 0.50 925 1400 1400
PA1348 0.20 0.50 1025 1550 1750
PA1360 0.20 0.50 1150 1750 1750
1 Motor will deliver consistent CFM through voltage supply range with no deterioration (197 253V for all 230/208V models).
2 Continuous CFM is the total air being circulated during continuous (manual fan) mode.
3 Will occur automatically with a call for “Y” for cooling mode operation.
4 Will occur automatically with a call for “W1” for heating mode operation.

Form No. S3383-509


Supersedes S3383-908
Page 2 of 8
Optional Field Installed Electric Heater Packages
Optional field installed electric heater packages are available for 5 through 15Kw
capacities. The heater packages are UL listed to be field installed into the basic unit.
They feature prewired control circuit wiring with plug in connector. Simply slide the
heater into the unit, plug in the pretested control circuit and connect the separate high
voltage circuit wiring.

IMPORTANT: While this electrical data is presented as a guide, it is important to


electrically connect properly sized fuses and conductor wires in accordance with the
National Electrical Code and all existing local codes.

Optional Field Installed Heater Packages Are Only To Be Used With The Models
As Indicated Below
Heater
P ackag e Volts & PA13242-A PA13302-A PA13362-A PA13362-B PA13422-A PA13422-B PA13422-C PA13482-A PA13482-B PA13482-C PA13602-A PA13602-B PA13602-C
Model P h ase

EHP323-A05 240/208-1 X X X

EHP323-A10 240/208-1 X X X

EHP323-A15 240/208-1 X X

EHP323-B09 240/208-3 X

EHP323-B15 240/208-3 X

EHP513-A05 240/208-1 X X X

EHP513-A10 240/208-1 X X X

EHP513-A15 240/208-1 X X X

EHP513-B09 240/208-3 X X X

EHP513-B15 240/208-3 X X X

EHP513-C09 460-3 X X X

EHP513-C15 460-3 X X X

Optional Field Installed Electric Heater Table — 2 through 5 Ton


Htr. KW & Capacity Htr. KW & Capacity
Circuit B
@ 240 Volts (480) @ 208 Volts 240/208V Heater
Heater Unit
Htr. Internal 3 1 2 2
P ackag e Volts N o.
Amps Circuit Min. Max. Over Field Ground
Model No. P h ases KW B TU H KW B TU H Field
(480) Breaker Circuit Current Pow er Wire
Circuits
Ampacity Protection Wiring Siz e
EHP323-A05 240/208-1 5 17,100 3.75 12,800 20.8/18.1 1 26/23 30/25 10/10 10
EHP323-A10 240/208-1 10 34,100 7.50 26,000 41.6/36.2 30/60 1 53/46 60/50 6/8 10
EHP323-A15 240/208-1 15 51,200 11.25 38,400 62.5/54.1 1 79/68 80/70 4/4 8
EHP513-A05 240/208-1 5 17,100 3.75 12,800 20.8/18.1 1 26/23 30/25 10/10 10
EHP513-A10 240/208-1 10 34,100 7.50 26,000 41.6/36.2 30/60 1 53/46 60/50 6/8 10
EHP513-A15 240/208-1 15 51,200 11.25 38,400 62.5/54.1 1 79/68 80/70 4/4 8
EHP323-B09 240/208-3 9 30,700 6.75 23,000 21.7/18.7 1 28/24 30/25 10/10 10
None
EHP323-B15 240/208-3 15 51,200 11.25 38,400 36.2/31.2 1 46/39 50/40 8/8 10
EHP513-B09 240/208-3 9 30,700 6.75 23,000 21.7/18.7 1 28/24 30/25 10/10 10
None
EHP513-B15 240/208-3 15 51,200 11.25 38,400 36.2/31.2 1 46/39 50/40 8/8 10
EHP513-C09 480-3 9 30,700 10.8 1 14 15 14 14
None
EHP513-C15 480-3 15 51,200 18 1 28 30 10 12
1 Maximum size of the time delay fuse or HACR circuit breaker for protection of field wiring devices.
2 Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring
must conform to the National Electric Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for
power conductor sizing.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all existing local codes.
Form No. S3383-509
Supersedes S3383-908
Page 3 of 8
Page
Cooling Application Data — Outdoor Temperature 1

Form No.
C ooling Outdoor Temperature°F
Model D .B ./W.B .2 C apacity 55°F 60°F 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F

4 of 8
Total C ooli ng 30,100 29,000 27,900 26,750 25,650 24,550 23,500 22,400 21,300 20,100 18,850 17,650 16,450 15,200
75/62
Sensi ble C ooli ng 20,600 20,100 19,700 19,250 18,800 18,400 17,950 17,500 17,100 16,650 16,200 15,750 15,250 14,800

Supersedes S3383-908
S3383-509
Total C ooli ng 31,900 30,750 29,650 28,500 27,400 26,300 25,200 24,100 23,000 21,800 20,600 19,400 18,200 17,000
PA1324 80/67
Sensi ble C ooli ng 20,750 20,250 19,800 19,300 18,800 18,300 17,750 17,250 16,700 16,350 15,000 15,700 15,350 15,000
Total C ooli ng 35,600 34,350 33,150 31,950 30,750 29,600 28,450 27,300 26,150 24,650 23,200 21,750 20,250 18,800
85/72
Sensi ble C ooli ng 20,900 20,450 19,950 19,500 19,000 18,500 18,000 17,500 16,950 16,600 16,300 15,950 15,600 15,250
Total C ooli ng 38,150 36,700 35,300 33,900 32,500 31,100 29,700 28,300 26,850 25,450 24,000 22,550 21,100 19,700
75/62
Sensi ble C ooli ng 27,050 26,450 25,850 25,250 24,600 24,050 23,450 22,900 22,300 21,600 20,850 20,150 19,400 18,700
Total C ooli ng 40,400 38,950 37,550 36,100 34,700 33,300 31,850 30,450 29,000 27,600 26,200 24,800 23,400 22,000
PA1330 80/67
Sensi ble C ooli ng 27,300 26,650 25,950 25,300 24,600 23,900 23,200 22,500 21,800 21,200 20,650 20,050 19,500 18,900
Total C ooli ng 45,050 43,550 42,000 40,450 38,900 37,400 35,950 34,450 32,950 31,200 29,500 27,750 26,050 24,300
85/72
Sensi ble C ooli ng 27,500 26,850 26,200 25,550 24,850 24,200 23,500 22,800 22,150 21,550 20,950 20,400 19,800 19,200
Total C ooli ng 43,200 41,700 40,200 38,700 37,150 35,750 34,350 32,900 31,500 29,600 27,750 25,850 23,950 22,100
75/62
Sensi ble C ooli ng 48,150 45,450 42,800 40,100 37,450 34,350 31,250 28,150 25,050 24,050 23,000 21,950 20,900 19,850
Total C ooli ng 45,750 44,250 42,700 41,200 39,700 38,300 36,850 35,450 34,000 32,150 30,300 28,400 26,550 24,700
PA1336 80/67
Sensi ble C ooli ng 48,400 45,650 42,900 40,150 37,400 34,200 30,950 27,750 24,500 23,600 22,750 21,850 21,000 20,100
Total C ooli ng 51,050 49,400 47,800 46,150 44,500 43,050 41,550 40,100 38,600 36,350 34,100 31,850 29,550 27,300
85/72
Sensi ble C ooli ng 48,850 46,100 43,350 40,550 37,800 34,600 31,350 28,100 24,900 24,000 23,100 22,200 21,300 20,400
Total C ooli ng 54,250 52,450 50,650 48,900 47,100 45,300 43,450 41,650 39,850 38,150 36,450 34,750 33,100 31,400
75/62
Sensi ble C ooli ng 39,500 38,700 37,950 37,150 36,400 35,650 34,950 34,250 33,550 32,500 31,400 30,300 29,250 28,150
Total C ooli ng 57,400 55,650 53,850 52,100 50,300 48,500 46,650 44,850 43,000 41,400 39,850 38,250 36,700 35,100
PA1342 80/67
Sensi ble C ooli ng 39,900 39,000 38,100 37,250 36,350 35,450 34,600 33,700 32,800 31,950 31,100 30,200 29,350 28,500
Total C ooli ng 64,050 62,150 60,250 58,300 56,400 54,500 52,650 50,750 48,850 46,850 44,850 42,850 40,800 38,800
85/72
Sensi ble C ooli ng 40,200 39,350 38,450 37,600 36,750 35,900 35,050 34,150 33,300 32,450 31,550 30,700 29,800 28,950
Total C ooli ng 57,550 55,700 53,900 52,050 50,250 48,452 46,650 44,850 43,100 41,100 39,100 37,150 35,150 33,200
75/62
Sensi ble C ooli ng 42,200 41,300 40,400 39,500 38,600 37,700 36,850 35,950 35,100 34,050 33,050 32,000 30,950 29,950
Total C ooli ng 60,850 59,050 57,250 55,450 53,650 51,850 50,100 48,300 46,500 44,600 42,750 40,850 39,000 37,100
PA1348 80/67
Sensi ble C ooli ng 42,600 41,600 40,550 39,550 38,550 37,500 36,450 35,350 34,300 33,500 32,700 31,900 31,100 30,300
Total C ooli ng 67,900 66,000 64,050 62,100 60,150 58,350 56,500 54,650 52,800 50,450 48,100 45,750 43,400 41,000
85/72
Sensi ble C ooli ng 42,950 41,950 40,950 39,950 38,950 37,950 36,900 35,850 34,850 34,026 33,200 32,400 31,600 30,800
Total C ooli ng 66,400 64,550 62,700 60,900 59,050 57,350 55,700 54,000 52,350 49,800 47,300 44,750 42,250 39,700
75/62
Sensi ble C ooli ng 46,950 46,250 45,550 44,850 44,200 43,850 43,550 43,250 42,900 40,750 38,550 36,350 34,200 32,000
Total C ooli ng 70,250 68,450 66,650 64,850 63,050 61,400 59,800 58,150 56,500 54,100 51,650 49,250 46,800 44,400
PA1360 80/67
Sensi ble C ooli ng 47,450 46,600 45,800 44,950 44,150 43,600 43,050 42,500 41,950 40,050 38,150 36,200 34,300 32,400
Total C ooli ng 78,350 76,450 74,500 72,600 70,700 69,050 67,450 65,800 64,200 61,200 58,150 55,150 52,100 49,100
85/72
Sensi ble C ooli ng 47,800 47,000 46,200 45,450 44,650 44,100 43,600 43,100 42,600 40,650 38,700 36,800 34,850 32,900

1 Be ow 55°F un t requ res a f e d nsta ed ow amb ent contro mode CMA-28


2 Return a r temperature °F
Slab Mounting at Ground Level

Air Outlet Side


The distance between
outside wall and unit View
1 inch clearance
between duct and varies with installation Elevated Mounting Platforms (Field Constructed)
any combustible requirements Package Unit
material if distance
between outside
wall and unit is less Supply Duct
than 3 feet (needed
on electric heat Mounting Slab
units only)
Return Duct
1/4 inch per foot
slope away
from building

12" min. if in Platform can be as


Building Ground Level 32°F or lower climate shown or solid

48" min. Both legs must rest


Poured concrete, on surface of platform
Airflow & Service Access Clearances brick, or block

Nearest Structure
Top
Heater Package Control Panel Compressor
Access Access 36" min Access View

Heater Package Control Panel


24" min
Comp-
ressor

12" min. if in

Nearest Structure
Blower 32°F or lower climate

Building
Air Inlet
and
Blower Motor

Metal frame Both legs must rest

Supply and Return Ducts


48" min. on surface of platform
MIS-2144 A

Condenser fan
and motor access
from top
Blower Service 24" min Leave 60" min
Access above fan
Air nlet

Page
Nearest Structure MIS-2143 A

Form No.
Supersedes
5 of 8
S3383-908
S3383-509
Unit Dimensions

W
L

A
D

B
Compressor
access door
Control panel door
High voltage knockout
Low voltage knockout
Heater package knockout Supply opening
C
Heater package access panel
Drain access Return opening

F
Condenser fan

H Condenser air
intake grille

Blower motor
access door 47 11/16"
G
Condenser air
intake grille
Unit Dimension Chart
Supply Size Return Size Unit Overall Dimensions Unit General Dimensions
Unit A C B C H (height) L (length) W (width) D E F G
PA/PH1324,1330,1336 5.875 32.875 13.875 32.875 26.25 53.25 38.125 23.25 1.125 1.375 35.625
PA/PH1342,1348,1360 9.875 37.875 15.875 37.875 33.25 55.25 42.375 30.25 15 2.375 38.125

MIS 2142 A

Optional Control Modules — Field Installed


Field Installed Part Applicable To Description
CMA-28 All Models Low Ambient Control
CMC-15 All -A Models Compressor Start Kit

Form No. S3383-509


Supersedes S3383-908
Page 6 of 8
Optional Equipment — Roof Hood
• Shipped knocked down • Built in filter
• Polyester baked enamel galvanneal cabinet • Fresh air damper assembly provides up to 15% outside air.
• Heavy insulation 1/2 inch • Requires prefabricated roof curb 9042-003 or 9042-004.
Order separately.
Model No. Applicable To Shipping Weight
RHP313-A 2, 2-1/2 and 3 ton models 110
RHP513-A 3-1/2, 4 and 5 ton models 120
† Equivalent units - Shipping

Performance and Application Data — RHP


RHP313-A Ventilation Air RHP513-A BFAD Ventilation Air
Supply Air Supply Air
Ventilation Air (CFM)
Static Ventilation Air (CFM) Static
0.00 N/A N/A 133 183 226 260 283 290 304 320 370 0.00 N/A N/A 80 165 215 250 280 310 340 370 400
0.20 N/A N/A 133 183 226 260 283 290 304 N/A N/A 0.20 N/A N/A 80 165 215 250 280 310 340 370 400
0.40 N/A N/A 133 183 2.26 260 283 290 N/A N/A N/A 0.40 N/A N/A 80 165 215 250 280 310 340 370 400

Return Static 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 Return Static 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50

D 38 1/4
AIR CONDITIONING UNIT X A WIDTH
Unit Dimensions
ROOF HOOD
R oof H ood Nominal 1"
Model Model Tonnage A C D Filter
FILTER
C
PA1324 / PH1324 2 Ton (1) 16 x 16
RHP313-A PA1330 / PH1330 2½ Ton 38-1/8 26 53-1/4 and
FRESH AIR PA1336 / PH1336 3 Ton (1) 16 x 20
OPENING
PA1342 / PH1342 3½ Ton
RHP513-A PA1348 / PH1348 4 Ton 42 33 55-1/4 (2) 16 x 20
12 1/2" PA1360 / PH1360 5 Ton
MIS 2254

Optional Equipment — Pre-Fabricated Roof Curb


• Heavy gauge galvanized with wood nailing strip.
• Prefabricated roof curb requires roof hood RHP313-A & RHP513-A.
Order separately.
Model No. Applicable To E U.† Shipping Weight
9042-003 2, 2-1/2 and 3 ton models .80 144
RETURN AIR SUPPLY AIR
9042-004 3-1/2, 4 and 5 ton models .80 160
1 1/2"
† Equ valent units - Shipping
H J

Heavy gauge galvanized with wood nailing strip, welded/leakproof one piece
construction ready to install.

Used With
R oof H ood Heat Pump and
Model Model A B C1 D E F J1 H1 Air Conditioning Units
9042-003
RHP313-A 80-3/8 40-1/4 37-1/4 38-3/8 35-3/8 42 14-3/4 19-1/8 All 2, 2-1/2, & 3 Ton Models
(P36 Curb)
9042-004
RHP513-A 82-3/8 44-1/8 41-1/8 38-3/8 35-3/8 44 14-3/4 19-1/8 All 3-1/2, 4 & 5 Ton Models
(P60 Curb)
1 Duct Sizing Information:
Return air dimension “C” is length / Supply air dimension “C” is length.
Return air dimension “H” is width / Supply air dimension “J” is width.
Form No. S3383-509
Supersedes S3383-908
Page 7 of 8
Optional Equipment — Energy Recovery Ventilator
• Assures continuous supply of fresh air and reduction of all indoor air pollutants. IAQ ASHRAE 62.1 Model N o. Shipping Weight
• Provides 250 to 400 CFM (adjustable) of outside air and exhaust. Efficiencies up to 77% heating and 65% cooling. ERVR-A3D -X (230/208V) 125 lbs.
• Designed for easy installation on roof hoods RHP313 A and RHP513 A.
ERVR-C 3D -X (460) 125 lbs.
PERFORM ANCE AND APPLI CATI ON DATA - ERVR-A3C
Summer Cooling Performance
(Indoor Design Conditions 75 DB/62 WB)
Ambient VENTILATION RATE - 400 CFM VENTILATION RATE - 325 CFM VENTILATION RATE - 250 CFM
O.D. 63% Efficiency 64% Efficiency 65% Efficiency
DB/WB F VLT V LS V LL HRT HRS HRL VLT V LS V LL HRT HRS HRL VLT V LS V LL HRT HRS HRL

75 19,080 12,960 6,120 12,020 8,164 3,855 15,502 10,530 4,972 9,921 6,739 3,182 11,925 8,100 3,825 7,751 5,265 2,486
105 70 12,960 12,960 0 8,164 8,164 0 10,530 10,530 0 6,739 6,739 0 8,100 8,100 0 5,265 5,265 0
65 12,960 12,960 0 8,164 8,164 0 10,530 10,530 0 6,739 6,739 0 8,100 8,100 0 5,265 5,265 0
80 28,080 10,800 17,280 17,690 6,804 10,886 22,815 8,775 14,040 14,601 5,616 8,985 17,550 6,750 10,800 11,407 4,387 7,019
75 19,080 10,800 8,280 12,020 6,804 5,216 15,502 8,775 6,727 9,921 5,616 4,305 11,925 6,750 5,175 7,751 4,387 3,363
100 70 10,980 10,800 180 6,917 6,804 113 8,921 8,775 146 5,709 5,616 93 6,862 6,750 112 4,460 4,387 73
65 10,800 10,800 0 6,804 6,804 0 8,775 8,775 0 5,616 5,616 0 6,750 6,750 0 4,387 4,387 0
60 10,800 10,800 0 6,804 6,804 0 8,775 8,775 0 5,616 5,616 0 6,750 6,750 0 4,387 4,387 0
80 28,080 8,640 19,440 17,690 5,443 12,247 22,815 7,020 15,795 14,601 4,492 10,108 17,550 5,400 12,150 11,407 3,510 7,897
75 19,080 8,640 10,440 12,020 5,443 6,577 15,502 7,020 8,482 9,921 4,492 5,428 11,925 5,400 6,525 7,751 3,510 4,241
95 70 10,980 8,640 2,340 6,917 5,443 1,474 8,921 7,020 1,901 5,709 4,492 1,216 6,862 5,400 1,462 4,460 3,510 950
65 8,640 8,640 0 5,443 5,443 0 7,020 7,020 0 4,492 4,492 0 5,400 5,400 0 3,510 3,510 0
60 8,640 8,640 0 5,443 5,443 0 7,020 7,020 0 4,492 4,492 0 5,400 5,400 0 3,510 3,510 0
80 28,080 6,480 21,600 17,690 4,082 13,608 22,815 5,265 17,550 14,601 3,369 11,232 17,550 4,050 13,500 11,407 2,632 8,774
75 19,080 6,480 12,600 12,020 4,082 7,938 15,502 5,265 10,237 9,921 3,369 6,552 11,925 4,050 7,875 7,751 2,632 5,118
90 70 10,980 6,480 4,500 6,917 4,082 2,835 8,921 5,265 3,656 5,709 3,369 2,340 6,862 4,050 2,812 4,460 2,632 1,828
65 6,480 6,480 0 4,082 4,082 0 5,265 5,265 0 3,369 3,369 0 4,050 4,050 0 2,632 2,632 0
60 6,480 6,480 0 4,082 4,082 0 5,265 5,265 0 3,369 3,369 0 4,050 4,050 0 2,632 2,632 0
80 28,080 4,320 23,760 17,690 2,721 14,968 22,815 3,510 19,305 14,601 2,246 12,355 17,550 2,700 14,850 11,407 1,755 9,652
75 19,080 4,320 14,760 12,020 2,721 9,298 15,502 3,510 11,992 9,921 2,246 7,675 11,925 2,700 9,225 7,751 1,755 5,996
85 70 10,980 4,320 6,660 6,917 2,721 4,195 8,921 3,510 5,411 5,709 2,246 3,463 6,862 2,700 4,162 4,460 1,755 2,705
65 4,320 4,320 0 2,721 2,721 0 3,510 3,510 0 2,246 2,246 0 2,700 2,700 0 1,755 1,755 0
60 4,320 4,320 0 2,721 2,721 0 3,510 3,510 0 2,246 2,246 0 2,700 2,700 0 1,755 1,755 0
75 19,080 2,160 16,920 12,020 1,360 10,659 15,502 1,755 13,747 9,921 1,123 8,798 11,925 1,350 10,575 7,751 877 6,873
70 10,980 2,160 8,820 6,917 1,360 5,556 8,921 1,755 7,166 5,709 1,123 4,586 6,862 1,350 5,512 4,460 877 3,583
80
65 3,780 2,160 1,620 2,381 1,360 1,020 3,071 1,755 1,316 1,965 1,123 842 2,362 1,350 1,012 1,535 877 658
60 2,160 2,160 0 1,360 1,360 0 1,755 1,755 0 1,123 1,123 0 1,350 1,350 0 877 877 0
70 10,980 0 10,980 6,917 0 6,917 8,921 0 8,921 5,709 0 5,709 6,862 0 6,862 4,460 0 4,460
75 65 3,780 0 3,780 2,381 0 2,381 3,071 0 3,071 1,965 0 1,965 2,362 0 2,362 1,535 0 1,535
60 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
PACKAGE UNIT
Legend:
Winter Heating Performance
VLT = Ventilation Load - Total
(Indoor Design Conditions 70°F DB) VLS = Ventilation Load - Sensible
ROOF HOOD

Ambient VENTILATION RATE VLL = Ventilation Load - Latent


O.D. 400 CFM 75% Efficiency 325 CFM 76% Efficiency 250 CFM 77% Efficiency HRT = Heat Recovery - Total
HRS = Heat Recovery - Sensible
DB°F WVL WHR WVL WHR WVL WHR HRL = Heat Recovery - Latent
WVL = Winter Ventilation Load ROOF CURB
65 2,160 1,620 1,755 1,333 1,350 1,039 WHR = Winter Heat Recovery
ROOF
60 4,320 3,240 3,510 2,667 2,700 2,079
55 6,480 4,860 5,265 4,001 4,050 3,118
50 8,640 6,480 7,020 5,335 5,400 4,158
MIS 2253
45 10,800 8,100 8,775 6,669 6,750 5,197
40 12,960 9,720 10,530 8,002 8,100 6,237
RETURN DUCT SUPPLY DUCT
35 15,120 11,340 12,285 9,336 9,450 7,276
30 17,280 12,960 14,040 10,670 10,800 8,316
25 19,440 14,580 15,795 12,004 12,150 9,355
20 21,600 16,200 17,550 13,338 13,500 10,395
15 23,760 17,820 19,305 14,671 14,850 11,434

UNI T DI M ENSI ONS


Model Width Depth Height Shipping Weight
ERVR * 32-3/4 18-3/4 18-3/4 125 lbs.

* Does not include 1" mounting brackets on each side of ERVR.

Bard Manufacturing Company, Inc. Due to our continuous product improvement Form No.
Bryan, Ohio 43506 policy, all specifications subject to change S3383
www.bardhvac.com without notice. May, 2009