Calculo Termico Area 300 m2
Calculo Termico Area 300 m2
Calculo Termico Area 300 m2
Tai Loy
Prepared By:
Corporacion Uezu
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 12 0.560 No No
Roof #1 Description: Flat roof, 4" heavy weight concrete deck with no insulation, no ceiling below
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 A 0.189 D
Wall #1 Description: Concrete wall, 6" thick, 80 lb/ft³, siding, no insulation or finish
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.270 10 10
Partition #1 Description: Frame partition, wood/insulated metal framing, siding exterior, no insulation or finish
Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.900 0.680 0.850 2 0.640
Wall Wall Glass Wall Net Wall Avg Glass Avg Glass Avg
Direction Area Area Area U-Factor U-Factor Shd.Coef
N 0.0 0.0 0.0 0.000 0.000 0.000
NE 0.0 0.0 0.0 0.000 0.000 0.000
E 0.0 0.0 0.0 0.000 0.000 0.000
SE 0.0 0.0 0.0 0.000 0.000 0.000
S 0.0 0.0 0.0 0.000 0.000 0.000
SW 0.0 0.0 0.0 0.000 0.000 0.000
W 0.0 0.0 0.0 0.000 0.000 0.000
NW 0.0 0.0 0.0 0.000 0.000 0.000
Totals 0.0 0.0 0.0 0.000 0.000 0.000
Check Figures
Total Building Supply Air (based on a 19° TD): 4,807 CFM
Total Building Vent. Air (10.92% of Supply): 525 CFM
Total Conditioned Air Space: 2,628 Sq.ft
Supply Air Per Unit Area: 1.8291 CFM/Sq.ft
Area Per Cooling Capacity: 187.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0053 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 14.02 Tons
Check Figures
Total Air Handler Supply Air (based on a 19° TD): 4,807 CFM
Total Air Handler Vent. Air (10.92% of Supply): 525 CFM
Total Conditioned Air Space: 2,628 Sq.ft
Supply Air Per Unit Area: 1.8291 CFM/Sq.ft
Area Per Cooling Capacity: 187.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0053 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 14.02 Tons
January
200,000 February
March
150,000 April
Btuh May
June
100,000 July
August
50,000 September
October
0 November
8am 9am 10am 11am 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8pm 9pm 10pm December
Hours of Operation
Building Net Load
200,000
January
February
150,000
March
April
May
Btuh 100,000
June
July
August
50,000
September
October
November
0
8am 9am 10am 11am 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8pm 9pm 10pm December
Hours of Operation
January
February
100,000 March
April
May
Btuh
50,000 June
July
August
0 September
8am 9am 10am 11am 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8pm 9pm 10pm
October
November
-50,000 December
Hours of Operation
January
50,000
February
March
40,000
April
May
Btuh 30,000
June
July
20,000
August
September
10,000
October
November
0
8am 9am 10am 11am 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8pm 9pm 10pm December
Hours of Operation
Roof - 20.52%
Air Handler
#1
Net Gain Lighting - 12.26%
168,283
Btuh
Partition - 6.51%
Equipment - 6.13%
People - 26.31%
Partition - 8.95%
Roof - 29.59%
Room #1
Net Gain
122,384 People - 36.18%
Btuh
Lighting - 16.85%
Equipment - 8.43%