Chapter 5
Field of View (FOV) Through an Infrared Window
The two questions most often asked by maintenance professionals getting ready to install infrared (IR)
inspection windows on electrical equipment are: “How many windows will I require per panel?” and “What
diameter window is best?” The answer depends on three considerations: the outside diameter of the
infrared camera lens, infrared camera field of view, and window field of view.

Infrared Camera Lens Diameter


In order to accurately measure temperature, an infrared camera’s lens must have full view of the objects
being measured. Partially obstructing a lens during imaging will introduce measurement errors for which
there is no compensation. Therefore, the first consideration in selecting windows is to ensure that the
window’s IR optic is larger than the outside diameter of the infrared camera lens that will be used.

Infrared Camera Field of View


Most infrared cameras are supplied with lenses that describe viewing angle in terms of degrees. With this
information it is possible to determine a camera’s field of view for any given distance. The formula for this
calculation is:

Field of View = {(tangent 1/2 viewing angle) x distance} x 2


To apply the above formula, follow these steps:

1. Determine your imager’s Field of View (in degrees) from the manufacturer’s specs.
2. Divide the value from Step 1 by 2
3. Use scientific calculator to determine tangent of number obtained in Step 2
4. Multiply number in Step 3 by distance from imager lens to object.
5. Multiply number in obtained in Step 4 by 2. This will be the width of the imager’s field of view at the
specified distance.

If your imager specifies different Field of View values for horizontal and vertical, it will be necessary to
calculate each value separately. Calculated values should be used for estimation purposes as actual values
may vary slightly.

Window Field of View (WFOV)


Typically, IR cameras equipped with a standard lens will have an FOV of approximately 24° horizontal and
20° vertical. It should be noted that changing lenses will change an infrared camera’s field of view.
Switching to a wide angle lens will typically double or triple a camera’s field of view. Using the
aforementioned specifications, a camera outfitted with a double wide lens would have an FOV of 48°
horizontal and 40° vertical. Since a wide angle lens may not always be available, it is advisable to calculate
camera FOV based upon a standard lens.

It should be noted that mathematically calculating imager field of view assumes that the FOV begins at the
panel cover and extends a distance (D) from the panel cover to the targeted components. Width (W) is
calculated by multiplying the distance (D) by the tangent of half the lens angle, then doubling the result.
This calculation assumes that FOV starts at a single point or vertex of the viewing angle; it does not take
window optic size into account. For infrared windows with large viewing panes such as IRISS’s CAP series,
the overall window field of view is increased by the width of the viewing pane.

To calculate the WFOV for different window sizes, simply subtract the camera lens diameter from the
imager’s calculated FOV and then add the diameter or width of the IR window’s optic that you intend to use.
The total is the WFOV, at the specified distance.
15 | iriss.com 10 Things You Need To Know About Infrared Windows
Click Here to Use The IRISS Free Online FOV Calculator

Example:
Camera FOV with 24° degree lens at 18 inches calculated using the above formula = 7.65 inches.
The camera lens diameter = 1.65 inches, therefore, the FOV of the camera = 6 inches.
• Using a 2 inch IR window would give an approximate WFOV of 8 inches
• Using a 3 inch IR window would give an approximate WFOV of 9 inches
• Using a 4 inch IR window would give an approximate WFOV of 10 inches
• Using a 34 inch IR window would give an approximate WFOV of 40 inches

It should be noted that the above fields of view are for perpendicular imaging. As discussed below, angling
one’s infrared camera can increase viewing area significantly.

The illustration in Figure 1 shows the area inside a cabinet that can be viewed through an IR window using a
camera with a 28° lens. A typical switchgear compartment is 20 inches deep, therefore:

W = 2D x (tangent of 14°)
W = 2 x 20 x 0.25 = 10 inches

The calculations in Figure 2 indicate that with a 28° FOV lens, a thermographer can view 10 inches
horizontally inside the panel. However, this calculation assumes the thermographer holds the camera fixed
and perpendicular to the window plane. More likely, the thermographer will vary the viewing angle up to
30° from perpendicular in all directions. This effectively increases the FOV area by a factor of three.

Camera Angled for 2X standard FOV

W = (2*20) x 0.25 x 2

W = 20 inches

Figure 1: Standard FOV calculation


with fixed viewing angle

Camera Angled for 3X standard FOV

W = (2*20) x 0.25 x 3

W = 30 inches

Figure 2: Standard FOV calculation


(varying the viewing angle)

Copyright ©2013 by IRISS, Inc. All rights reserved iriss.com | 16


Free Tech Byte: IR Window Sizing & Field of View Quick Reference Guide

Rule of Thumb
Based on numerous field tests for window FOV with a wide variety of cameras, most cameras have
generated a horizontal WFOV of roughly two to three times (2X to 3X) the distance to the target; and a
vertical WFOV of roughly 1.5X to 2X the distance to the target. This is based on cameras with a standard 24°
or similar lens, using a maximum angle of incidence of 30°.

Therefore, based on this rule of thumb, a window located 20 inches (51cm) from the intended targets would
allow the thermographer to gather data from points that were separated by 40 to 60 inches (1m to 1.5m)
side-to-side and separated by 30 to 40 inches (0.75m to 1m) top-to-bottom.

Note that it is impractical to use a multiplier in excess of 3X due to the difficulty matching the thermal image
to locations within the panel. Obstructions in the panel may also make it impractical. As previously
mentioned, viewing at too steep an angle can begin to affect other variables such as emissivity. Therefore,
IRISS, Inc. recommends a maximum of 3X as a “rule of thumb” multiplier.

Summary
1. To help ensure measurement accuracy, an IR window’s optic must be larger than the outside
diameter of the IR camera’s lens.
2. Every infrared camera has a Field of View (FOV) defined in degrees across a horizontal/vertical axis.
Note that FOV will vary depending on the lens used.
3. Windows Field of View (WFOV): The largest area that can be viewed through an infrared window
allowing for a maximum angle of incidence of 30° off perpendicular.
5. Rule of thumb for WFOV using a standard camera and lens is roughly 2 to 3 times the distance from
the window to the target.
6. Obstructions, such as phase dividers or cables, inside the cabinet may decrease actual field of view.

Want Help Navigating Your IR Window Needs? Click Here To Submit an Info Request