13monitoreo Vibracion Axial

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

▣ Outline and Sensor Dimensions ▣ Control and Alarm Output

AVM-KM18-05-05/07/10 Control Output Descriptions


• If an indication(that is, a vibration value) is
continuously higher than the high vibration

AXIAL VIBRATION MONITOR set-point for the set delay time, the high
vibration output contact is deactivated, if not,
it is activated at once.
Treatment and User’s Manual • If an indication(that is, a vibration value) is
continuously higher than the slow down
vibration set-point for the set delay time,
the slow down vibration output contact is
activated, if not, it is deactivated at once.
AVM-KM30-10-05/07/10, AVM-KM30-13-05/07/10 • When the high vibration output is energized,
the related high vibration red LED is on.
• When the slow down vibration output is
energized, the related slow down red LED
※ VIBRATION(mm) IS FOR THE PEAK TO PEAK VALUE. is on.

≤ 18V ○ • This function is used to check whether the


POWER
18V ~ 29V ○ ○ ○ ○ sensor is correctly installed or not.
SUPPLY
≥ 29V ○ • The low limit of a valid detecting range is
Thank you very much for selecting KOMECO products. KOMECO do always try to
CLOSED ○ ○ ○ ○ ○ the lowest value that unit can detect.
provide products with safety and stability. SENSOR • The high limit of a valid detecting range is
OPEN ○
Please read this manual carefully before you use this unit that measures the ≤ LOW LIMIT ○
the highest value that unit can detect.
SENSING • Users can't change above limit values.
vibration of metal materials of the target and indicates its value. ▣ I/O Wiring NORMAL ○ ○ ○ ○
RANGE If want to change limit values, be sure to
≥ HIGH LIMIT ○
▣ Model Number • Please supply the power after check POWER FAILURE/
make an inquiry to http://www.komeco.net
(KOMECO) about them.
A V M - K M 3 0 - 1 0 - 07 the correct connection of I/O cables. ALARM OUTPUT
• The output current is for the peak to (N.C) ※ If you need other information, please
05 : 05 m peak vibration with delay time.
Sensor Cable Length ERROR MESSAGE(FND) VIB. 99.11 99.11 99.22 99.33 99.44 refer to above contents, particularly,
07 : 07 m • The output voltage from the BNC- INDICATION(GREEN LED) ON OFF OFF OFF OFF OFF "▣ specifications" part.
OUT pin is for the distance from the
10 : 10 m
sensor to the target with near real-
05 : 05 mm
Measurement Range 10 : 10 mm
time. ▣ Cautions
• You can arbitrary choose the contact
type of the SLOW DOWN, the VIBR-
Sensor Type
13 : 13 mm
Diameter : 30 mm
ATION HIGH, and the POWER FAIL- WARNING
URE/ALARM.
Maker
Kumoh Mach.&Elec. Co., Ltd. ※ If you need other information, please This unit is not designed for safety device, therefore when this unit is applied at
refer to above contents, particularly, dangers application such as series human injury, series property damage, be sure
Abbreviation Axial Vibration Monitor "▣ Specifications" part.
to install fail-safe device.
▣ Specifications ▣ Sensor Installation

Model Number
AVM-KM18-05-05 AVM-KM30-10-05 AVM-KM30-13-05 Installation Procure CAUTION
AVM-KM18-05-07 AVM-KM30-10-07 AVM-KM30-13-10 1. Mount a sensor at desired mounting position
Items 1. Please don't tighten the nuts excessively when you install a sensor or a monitor.
AVM-KM18-05-10 AVM-KM30-10-10 AVM-KM30-13-10 properly, that is, at a distance from the
2. Be sure to wire an I/O cable or a sensor cable after power turns off.
Model Number BAW-018-PF-1-K BAW-030-PF-1-K BAW-030-PF-1-K target on engine crank case.
3. Check a voltage regulation of the power not to exceed the related power voltage in order to prevent
Output Current Current Current 2. Connect a sensor cable to monitor.
human injury from a wrong usage.
3. Turn on the power.
Sensor Installation Flush Mount Flush Mount Flush Mount 4. Be sure that a detecting distance and a detecting vibration can be different for the plated target.
Ambient Temperature(℃) -10 ~ +60 -10 ~ +60 -10 ~ +60 4. Please read a current mounted position( ) 5. If a sensor or a monitor get a strong shock by the hammer, it will be damaged.
displayed on the monitor by pressing the 6. If the sensor cable is arbitrary extended, malfunction or failure of unit can be occurred because of noise.
Protection(DIN40050) IP67 IP67 IP67
both and buttons simultaneously. If you inevitably want to extend a sensor cable, please make an inquiry to http://www.komeco.net
Sensor Mounting Distance(mm) 4.00 8.50 6.50
5. Next, please move the sensor just as much about it.
Measurement Range(mm) 1.50 ~ 6.50 3.50 ~ 13.50 2.50 ~ 15.50
as difference between the desired mounting 7. Be careful of a sensor mounting distance. If an engineer of mounting a sensor install a sensor too much
Maximum Vibration
5.00 10.00 13.00 position and the current mounted position. close to metal material of the target, the sensor may be broken down because the target can be move to
(Peak to Peak, mm) 6. And then, perform No. 5 repeatedly until the the sensor.
Sensing Linearity (mm) 5.00 10.00 13.00 difference between the desired mounting
Power Voltage(V) DC24V±25% DC24V±25% DC24V±25% position and the current mounted position is ◂Avoid sunshine, water, ◂ If a power line or high
Supply Power(W) 3.36 3.36 3.36 nearly zero. please don't use this voltage near by sensor
Ambient Temperature(℃) -10 ~ +60 -10 ~ +60 -10 ~ +60 ※ If the sensor is not mounted over safe unit at outdoors as cable malfunction can
Ambient Humidity(%,RH) ≤90 ≤90 ≤90 measuring interval, the sensor may be much as possible. be occurred. Be careful.
broken down. Necessary, an engineer of
Storage Temperature(℃) -30 ~ +80(Non-freezing) -30 ~ +80(Non-freezing) -30 ~ +80(Non-freezing)
mounting a sensor must obey the ◂ Avoid using the sensor
Storage Humidity(%,RH) ≤95 ≤95 ≤95
installation procure. of the monitor in a place
Protection IP67 IP67 IP67 ◂ Please don't shock to
※ If you need other information, please chemicals, articularly
4+1.6×Vibration(mm), the detecting sensor.
Output Current(mA) 4+3.2×Vibration(mm) 4+1.6×Vibration(mm) refer to above contents, particularly, strong alkali acid, nitric
Vibration where Vibration ≤ 10mm "▣ Specifications" part. acid , slovents etc.
Maximum Load(Ω) 800 800 800
※ Above cautions must be kept because malfunction or failure of unit can be
Position
Output Voltage(V/mm) 1.00 1.00 1.00 ▣ Set System Parameters and Readout occurred.
Maximum Output(V) 6.50 13.00 13.00
Set of System Parameters
Contact Type NO, NC NO, NC NO, NC
Items Methods
Slow Maximum Load 50V, 10A 50V, 10A 50V, 10A
Down Setting Range(mm) 0.00 ~ 5.00 0.00 ~ 10.00 0.00 ~ 13.00
Adjustment of the set-point by turning ▣ Main Products
SLOW DOWN the screw on and readout of the set
Delay Time(Sec) 0 ~ 300 0 ~ 300 0 ~ 300
Contact Type NO, NC NO, NC NO, NC -point( ) by pressing button. ■ Tacho System
High Maximum Load 50V, 10A 50V, 10A 50V, 10A Adjustment of the set-point by turning √ Engine Tacho System
HIGH
Vibration Setting Range(mm) 0.00 ~ 5.00 0.00 ~ 10.00 0.00 ~ 13.00 the screw on and readout of the set √ Turbocharger Tacho System
VIBRATION √ Propeller Tacho System
Delay Time(Sec) 0 ~ 300 0 ~ 300 0 ~ 300 -point( ) by pressing button. KOMECO do always try to satisfy a customer with a
Contact Type NO, NC NO, NC NO, NC ■ Temperature Monitoring System
Adjustment and readout an arrow of good quality.
Maximum Load 50V, 10A 50V, 10A 50V, 10A SLOW DOWN 1: 20Sec 2: 40Sec 3: 60Sec 4: 80Sec √ Temperature Sensor
System
Normal Source Voltage(V) 18 ~ 29 18 ~ 29 18 ~ 29 TIME 5:100Sec 6:120Sec 7:140Sec 8:160Sec √ Temperature Monitor
■ Head Office
Status Sensor Status CLOSED CLOSED CLOSED SETTING 9:180Sec A:200Sec B:220Sec C:240Sec ■ Vibration System #62-4, Seoburi, Gijang-eup, Gijang-gun, Busan, Korea.
Sensing Range(mm) 1.50 ~ 6.50 3.50 ~ 13.50 2.50 ~ 15.50 D:260Sec E:280Sec F:300Sec √ Sensor Tel. : 82-51-724-5070 ~ 1
Identification of System Parameters √ Monitor Fax. : 82-51-724-5175
Delay Slow Down(Sec) 0 ~ 300 0 ~ 300 0 ~ 300
Time High Vibration(Sec) 0 ~ 300 0 ~ 300 0 ~ 300 Items Methods ■ Annunciator ■ Changwon Office
SLOW DOWN √ Group Annunciator No. 719 on the seventh floor, Shinwol Complex Store
Indication(%) ±5 ±5 ±5 readout of by pressing button.
√ Programmable Annunciator Shinwol-dong, Changwon City, Kyungnam
Accuracy Output Current(%) ±5 ±5 ±5 HIGH VIBRATION readout of by pressing button. Tel. : 82-55-274-1967
√ Cable Supervision
Delay Time(%) ±10 ±10 ±10 Fax. : 82-55-274-1968
Current Mounted readout of by pressing both ■ Level Switch
MAN B&W ENGINE Position
MAN B&W ENGINE and buttons simultaneously.
Applied Engine Types 50MC/60MC/70MC/80MC SULZER ENGINE
26MC/35MC/42MC
/90MC/98MC The changed slow down delay time will be valid after the power is re-supplied. NO050207-IDT-RD-KM-I001
AXIAL VIBRATION MONITOR
(MODEL : AVM-KM30-13)

USER'S MANUAL (VER 2.03)

Printed in 2003.02.12

#62-4, SEOBU-RI, GIJANG-EUP,


GIJANG-GUN BUSAN, KOREA.
TEL. : 82-51-724-5070 ~ 1
FAX. : 82-51-724-5175
H-Page : http://www.komeco.net
Contents

1. SYSTEM DESCRIPTIONS ---------------------------------------- 1

2. FUNCTIONAL DESCRIPTIONS ---------------------------------------- 1

3. TROUBLE SHOOTING ---------------------------------------- 3

1) Standard procedures ---------------------------------------- 3

2) Check of power supply to probe --------------------------------- 3

3) Check of the electronic cabinet during power on ------------------- 5

4) Check of the electronic cabinet for probe input & display ------------ 6

5) Check of the electronic cabinet for current output ------------------- 7

6) Check of the electronic cabinet for Slow Down Output ------------------- 8

7) Check of the electronic cabinet for Vibration High Alarm Output ------------ 9

8) Check of the electronic cabinet for Power Fail Output ------------------- 10

9) Check of the Probe ---------------------------------------- 11

10) Check of the electronic cabinet for Voltage Output ------------------- 12

4. SYSTEM SET-UP ---------------------------------------- 13

5. SPECIFICATIONS ---------------------------------------- 15

APPENDICES
AXIAL VIBRATION LIMITS FOR SAFE ENGINE OPERATION
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

SYSTEM DESCRIPTIONS 시스템 개요

The AVM-KM30-13 (Axial Vibration Monitor AVM-KM30-13 (지름이 30mm 프로브로 축방


with 30mm diameter probe) is a control and 향 진동 측정)은 제어와 감시 시스템이 디젤 엔
monitoring system capable of measuring axial 진의 크랭크샤프트 축의 진동을 측정하는 기능을
crankshaft vibrations on diesel engines. The 제공한다. 이 시스템은 메인 엔진에 바로 장착할
system is designed to be mounted directly 수 있다. 이 시스템은 아날로그와 디지털 기술의
onto the main engine. The system consists 조합으로 설계된 유닛과 인덕티브 아날로그 센서
of a control unit based on analog and digital (프로브)로 조합되어 있다.
technology and an inductive analog proximity AVM-KM30-13은 0.00에서 13.00mm까지 피크
sensor(probe). -대-피크 진동를 측정할 수 있다.
The AVM-KM30-13 is capable of measuring KOMECO에서 제공되는 프로브는 크랭크샤프트
0.00~13.00 mm peak-to-peak displacement. 와 프로브 사이의 거리에 직접적으로 비례하는
The probe supplied by KOMECO delivers a 전류 신호를 출력하여 AVM-KM30-13 제어 유
current signal directly proportional to the 닛으로 제공된다.
between the probe and the crankshaft to the
control unit.

FUNCTIONAL DESCRIPTIONS 기능 설명

The control unit converts the current signal 제어 유닛은 입력된 프로브 신호를 변환해서 크
from the probe to a value of 1 volt per mm 랭크샤프트로부터 떨어진 거리 mm당 1V를 “크
displacement of the crankshaft. This signal is 랭크샤프트 위치 출력” 단자를 통해 분석용으로
sent to the "Crankshaft Position Output" 서 출력해준다.
primary used for test. 이 신호는 500㎲의 샘플링으로 출력된다. 그러므
The sampling time is 500㎲. So, this 로 변환신호는 원래 신호의 실제 값이다.
converted signal is real value to raw signal.
진동의 피크-대-피크 값은 4자리로 디스플레이
The peak-to-peak value of the displacement
되며, 해상도는 0.01mm이고 “Alarm/Monitoring
is displayed on an internal four-digit display
Current Output” 단자로 4~20mA 전류 신호로
with a resolution of 0.01mm and sent
출력된다. 만약 진동이 10.00mm를 벗어나면 전
through a voltage-to-current converter, to
류는 4mA로 떨어지게 되고 진동 값 Display는
the "Alarm/ Monitoring Current Output", as a
4~20mA current signal. If a vibration is over 13.00mm까지 이루어진다.
than 10.00mm then a output current is 4mA. 만약 Probe로부터 피크-대-피크 변위(진동)가 감
However, a indication is enable to display 소할 경우에 “Alarm/Monitoring Current Output”
over 0 ~ 13.00 mm. 은 즉시 떨어지지 않으며 점차적으로 실제 피크-
When the peak-to-peak displacement signal 대-피크 변위(진동) 값으로 떨어진다.
from the probe decreases, the value of the 이 변환신호는 실시간으로 해석되지 않는다. 왜냐
display and the "Alarm/Monitoring Current 하면 피크-대-피크를 실시간으로 해석할 수 없기
Output" will not follow immediately, but fall 때문이다.
slowly to the actual peak-to-peak displace-
ment. The converted signal is processed in a
analytical method. This output signal is not
real value to raw signal, because it is not
processed on real time base.

1
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

The "Power Fail Output", an on/off signal 제어 유닛은 전원이 불안정(18V이하, 29V이상)
with a potential-free contact(NO) or normal 할 경우 노말 오픈(NO) 혹은 노말 클로즈(NC)로
-close contact(NC), is set if the power 신호를 출력해주고 내부 디스플레이 모듈에
source is lower than 18V or higher than “99.11”이 디스플레이 된다. 만약 정상적인 전원
29V. In an occasion, "99.11" is displayed on 이 공급되면 디스플레이 되던 “99.11” 에러 메시
an internal four-digit display. When the 지는 자동으로 리셋될 것이고 알람출력신호도 복
power is normal "99.11" will automatically 귀될 것이다.
reset and activated contact will release. 만약 사용자가 셋팅한 진동 값 이상의 피크-대-
The "Vibration High Alarm Output", an on/off 피크가 셋팅된 "Slow Down Delay Time" 시간
signal with a potential-free contact(NO) or 이상 동안 계속해서 센서로부터 검출되면 노말
normal-close contact(NC), is activate if the 오픈(NO) 혹은 노말 클로즈(NC)로 신호를 출력
peak-to-peak signal exceeds a setpoint of 해준다. 이 신호의 리셋은 피크-대-피크의 신호
the high vibration for mare than the "Slow 가 셋팅한 값 이하로 떨어지자마자 즉시 이루어
Down Delay Time". The reset of the "VIB. 진다. 셋팅 값을 확인 하려면 “HIGH VIB.
HIGH" output occurs as soon as the VIEW" 버튼을 누른 상태에서 FND에 디스플레이
peak-to-peak signal has dropped below the 값을 통해서 확인한다. 이에 필요한 값 셋팅은
setpoint. The setpoint for "Vibration High “HIGH VIB. VIEW"를 누른 상태에서 "VIB.
Alarm Output" is shown on the display by HIGH"의 가변조정부로 조정한다.
pressing the "HIGH VIB. VIEW" button. 슬로우다운 출력 신호는 사용자가 셋팅한 값 이
Setting of the setpoint for "High Vibration 상의 피크-대-피크 진동이 “슬로우다운 시간” 이
Output" is done by pressing the "HIGH VIB. 상동안 연속적으로 검출되면 노말 오픈(NO) 혹은
VIEW" and adjusting the "VIB. HIGH" 노말 클로즈(NC)로 동작한다. 이 신호의 리셋은
potentiometer. 피크-대-피크의 신호가 셋팅한 값 이하로 떨어지
The "Slow Down Output", an on/off signal 자마자 즉시 이루어진다.
with a potential-free contact(NO) or normal- 셋팅 값을 확인하려면 “SLOW DOWN VIEW"버
close contact(NC), is set if the peak-to-peak 튼을 누른 상태에서 FND에 디스플레이 값을 통
signal exceeds a setpoint for more than the 해서 확인한다. 이에 필요한 값 셋팅은 “SLOW
"Slow Down Delay Time". The setpoint and DOWN VIEW"를 누른 상태에서 "SLOW DOWN"
the "Slow Down Delay Time" are internal 의 가변조정부로 조정한다.
adjustable. The reset of the "Slow Down “알람 발생 지연시간” 셋팅은 “SLOW DOWN
Output" and the "Slow Down Delay Time" TIME SETTING" 스위치를 아래의 값에 준하도
occurs as soon as the peak-to-peak signal 록 맞춰서 조정한다.
has dropped below the setpoint.
The setpoint for "Slow Down Output" is
shown on the display by pressing the "SLOW
DOWN VIEW" button. Setting of the setpoint
for "Slow Down Output" is done by pressing
the "SLOW DOWN VIEW" button and
adjusting the "SLOW DOWN" potentiometer.
Setting of the slow down delay time is done
by setting the "SLOW DOWN TIME
SETTING" switch to one of the following
positions.

2
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

0 = 0 sec. 6 = 120 sec. C = 240 sec. 0 = 0 sec. 6 = 120 sec. C = 240 sec.
1 = 20 sec. 7 = 140 sec. D = 260 sec. 1 = 20 sec. 7 = 140 sec. D = 260 sec.
2 = 40 sec. 8 = 160 sec. E = 280 sec. 2 = 40 sec. 8 = 160 sec. E = 280 sec.
3 = 60 sec. 9 = 180 sec. F = 300 sec. 3 = 60 sec. 9 = 180 sec. F = 300 sec.
4 = 80 sec. A = 200 sec. 4 = 80 sec. A = 200 sec.
5 = 100 sec. B = 220 sec. 5 = 100 sec. B = 220 sec.

Recommended initial setting : 100 sec. 추천하는 슬로우 다운 시간 : 100 sec.

User range setting provide advantage that 유저 레인지 셋팅은 사용자가 프로브(센서)를 엔
end users can easily mount a probe(sensor) 진에 장착할 때 설치거리를 확인하기 위한 특수
onto engine without a special mount jig. If 한 도구 없이 수해하도록 편의성을 제공한다. 만
an end user mounts a probe (sensor) closer 약 사용자가 프로브를 장착할 때 로우 셋팅 값보
from the crankshaft than low set value, 다 더 가까이 프로브를 장착할 경우에는 “99.33”
"99.33" is displayed on an internal four-digit 을 디스플레이하여 설치의 부적합을 알린다. 그리
display. And if an end user mounts a 고 하이 셋팅 값보다 더 멀리 프로브를 장착할
probe(sensor) far away from crankshaft than 경우에도 “99.44”를 디스플레이하여 설치의 부적
high set value, "99.44" is displayed on an 합을 알려준다. 유저 레인지 셋팅은 KOMECO에
internal four-digit display. User range low or 서만 가능하다.
high setting can only done by KOMECO. 만약 프로브 선이 단락되거나 단선될 경우 디스
The short-circuit/disruption of the probe 플레이 상에 “99.22”가 나타날 것이다. “99.33”
cable will be indicated on the display by 그리고 “99.44”의 에러 메시지는 알람세팅 값 확
"99.22". The "99.33" and "99.44" error 인 시 쓰이는 두 버튼을 동시에 눌러 해제시킬
messages can be recovered by pressuring 수 있다.
two view buttons simultaneously.

TROUBLE SHOOTING 고장 점검

I. Standard procedures I. 절차
In case of suspected malfunction, a structur- 만약 정상동작이 되지 않는다고 의심되면 체계적
ed system test should be carried out. By 인 테스트가 이루어져야 한다. 제품에 대해서 다
following the below steps, a complete 음과 같은 단계로 테스트가 이루어진다면 문제점
system test is carried out, and an 을 확인할 수 있을 것이다.
identification of the problem should be
possible.
II. 프로브에 대한 전원 공급 체크
II. Check of power supply to probe K11(+)와 K13(-)에 전원을 공급한다. 전원을 공
Connect the power supply to K11(+), 급하면 처음에 88.88이 디스플레이되고, 약 1초
K13(-). 후에 다음과 같은 값들이 디스플레이된다. 이것은
The display will indicate "88.88". After one 사용자가 셋팅한 값을 스캔하기 위한 것이다.
second the control unit will scan the value 1.00 : 슬로우 다운 진동 셋팅 값 스캔
user's of setting.
1.00 : Scanning the set value of slow down
vibration

3
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

2.00 : Scanning the set value of vibration 2.00 : 과진동 알람 셋팅 값 스캔


high alarm 3.00 : 사용자 로우 레인지 셋팅 값 스캔
3.00 : Scanning the set value of user range 4.00 : 사용자 하이 레인지 셋팅 값 스캔
low 5.00 : 슬로우 다운 시간 셋팅 값 스캔
4.00 : Scanning the set value of user range K21(+)와 K23(-)에 전압을 체크한다.
high Vp의 값이 14.5~15.5V이면 정상이며 만약 그렇
5.00 : Scanning the set value of slow down 지 않으면 제어 유닛을 바꿔야 한다.
time
Check the voltage on K21(+), K23(-).
For the AVM-KM30-13 the Vp readout
should be 14.5~15.5 V.
If not, the circuit board may be defective
and should be replaced.

4
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

III. Check of the electronic cabinet III. 전원을 공급했을 경우 증상 체크


during power on K21와 K22에 저항 Res1을 연결하라(Res1 =
Connect resistor Res1 to K21 and K22(Res1 2k2 = 2.2k, 이것은 KOMECO의 A/S 영역이
= 2k2 = 2.2㏀, not part of KOMECO A/S 아니다).
scope of supply) 전원이 공급되면 디스플레이 상에 88.88이 디스
When the power is turned on the display will 플레이된 후 셋팅 값을 스캔한다.
indicate 88.88. After one second the control 스캔하는 데는 약 20초 정도 소요된다. 그 후 정
will scan the value user's of setting. 상적인 동작이 이루어지면 디스플레이는 0.00~
After the scanning is terminated the display 0.05mm가 될 것이다.
will return to normal condition and indicate 만약 위와 같은 동작이 이루어지지 않는다면 제
0.00~0.05mm. 어 유닛을 바꿔야 한다.
If not, the circuit board may be defective
and should be replaced.

5
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

IV. Check of the electronic cabinet for IV. 프로브 입력과 디스플레이 증상 체크
probe input & display Res1과 Res2를 K21, K22에 병렬로 연결한다.
Connect Res1 and Res2 in parallel to K21 Res2를 계속적으로 접속과 분리를 반복하면 디
and K22. 스플레이가 변하고 그 값은 3.00-4.00mm 사이
By continuously connecting and disconnecting 의 값이 된다.
Res2 the display will change indication. 계속적으로 접속시켜 놓든지 분리시켜 놓으면 디
For the AVM-KM30-13 the readout will be 스플레이 값은 점차적으로 0.00~0.05mm로 된
3.00~4.00mm. 다.
By permanently disconnecting or connecting 만약 정상적으로 동작하지 않으면 제어 유닛을
Res2 the display will return slowly to indi- 바꿔야 한다.
cating 0.00~0.05mm.
If not, the circuit board may be defective
and should be replaced.

6
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

V. Check of the electronic cabinet for V. 전류 출력 증상 체크


current output 전류 메타를 K31과 K32에 연결한다.
Connect an amp-meter to K31 and K32. Res2를 계속적으로 접속과 분리를 반복하면 디
By continuously disconnecting and connecting 스플레이가 변한다. Iout 은 아래의 공식에 의해
Res2 the display will change indication. 디스플레이된 값에 따라서 변한다.
Iout will follow the value in the display Iout[mA] = 1.6× (디스플레이 값[mm]) +4 ,
according to the following formula: 단, 디스플레이 값이 10.00mm 이하인 경우.
Iout[mA] = 1.6 × (display indication[mm]) + 4, 만약 Iout의 출력이 공식에 따라서 변하지 않으면
where a display indication is lower than 10.00. 제어 유닛을 바꿔야 한다.
If Iout differs significantly from the above
formula, the circuit board may be defective
and should be replaced.

7
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

VI. Check of the electronic cabinet for VI. 슬로우 다운 출력 증상 체크


Slow Down Output 저항 측정기를 K42와 K43(노말 오픈, NO), K41
Connect an ohm-meter to K42 and K43 for 과 K43(노말 클로즈, NC)에 연결한다.
Normal-Open(NO), to K41 and K42 for SLOW DOWN TIME SETTING을 “0”으로 맞춘
Normal-Close(NC). 다.
Adjust the "SLOW DOWN TIME SETTING" to 전원을 공급한다.
position "0". SLOW DOWN을 약 2.00mm에 맞춘다.
Connect the power source to K11(+) and Res2를 계속적으로 접속과 분리하면 디스플레이
K13(-). 가 변한다.
Adjust the "SLOW DOWN" to approximately 계속적으로 접속시켜 놓든지 분리시켜 놓으면 디
2.0mm. 스플레이 값은 점차적으로 0.00-0.05mm로 된다.
By continuously disconnecting and connecting
Res2 the display will change indication.
By permanently disconnecting or connecting
Res2 the display will return slowly to an
indication of 0.00-0.05mm.

8
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

At display indications higher than the adjusted 만약 표시 값이 SLOW DOWN에서 셋팅한 값보


SLOW DOWN the Slow Down Output relay will 다 높으면 슬로우 다운 출력 릴레이가 동작한다:
be activated: Rsd = 0Ω Rsd = 0Ω
for Normal-Open(NO), 노말 오픈(NO) 에 대하여,
Rsd = ∞Ω Rsd = ∞Ω
for Normal-Close(NC). 노말 클로즈(NC) 에 대하여.
At display indications lower than the adjusted 만약 표시 값이 SLOW DOWN에서 셋팅한 값보
SLOW DOWN the Slow Down Output relay will 다 낮은 값으로 떨어지면 릴레이는 동작을 멈춘
be deactivated : Rsd = ∞Ω 다.
for Normal-Open(NO), Rsd = ∞Ω
Rsd = 0Ω 노말 오픈(NO) 에 대하여,
for Normal-Close(NC). Rsd = 0Ω
If not, the circuit board may be defective 노말 클로즈(NC) 에 대하여.
and should be replaced. 만약 정상적으로 동작하지 않으면 제어 유닛을
바꿔야 한다.

VII. Check of the electronic cabinet VII. 과진동 알람 증상 체크


for Vibration High Alarm Output 저항 측정기를 K52와 K53(노말 오픈, NO), K51
Connect an ohm-meter to K52 and K53 for 과 K53(노말 클로즈, NC)에 연결한다.
Normal-Open(NO), to K51 and K52 for 전원을 공급한다.
Normal-Close(NC). HIGH VIB.를 약 2.00mm에 맞춘다.
Connect the power source to K11(+) and Res2를 계속적으로 접속과 분리를 반복하면 디
K13(-). 스플레이가 변한다.
Adjust the HIGH VIB. to approximately 2.00 계속적으로 접속시켜 놓든지 분리시켜 놓으면 디
mm. 스플레이 값은 점차적으로 0.00-0.05mm로 된다.
By continuously disconnecting and connecting 만약 표시 값이 HIGH VIB.에서 셋팅한 값보다
Res2 the display will change indication. 높으면 바이브레이션 하이 알람 출력 릴레이가
By permanently disconnecting or connecting 동작한다:
Res2 the display will return slowly to an Rsd = 0Ω , 노말 오픈(NO) 에 대하여,
indication of 0.00-0.05mm. Rsd = ∞Ω ,노말 클로즈(NC) 에 대하여.
At display indications higher than the 만약 표시 값이 HIGH VIB.에서 셋팅한 값보다
adjusted HIGH VIB. the Vibration High Alarm 낮은 값으로 떨어지면 릴레이는 동작을 멈춘다.
Output relay will be activated: Rsd = ∞Ω , 노말 오픈(NO) 에 대하여,
Rsd = 0Ω for Normal-Open(NO), Rsd = 0Ω ,노말 클로즈(NC) 에 대하여.
Rsd = ∞Ω for Normal-Close(NC).
만약 정상적으로 동작하지 않으면 제어 유닛을
At display indications lower than the
바꿔야 한다.
adjusted HIGH VIB. the Vibration High Alarm
Output relay will be deactivated :
Rsd = ∞Ω for Normal-Open(NO),
Rsd = 0Ω for Normal-Close(NC).
If not, the circuit board may be defective
and should be replaced.

9
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

VIII. Check of the electronic cabinet VIII. 전원 불안정 증상 체크


for Power Fail Output 저항 측정기를 K62와 K63(노말 오픈, NO), K61
Connect an ohm-meter to K62 and K63 for 과 K63(노말 클로즈, NC)에 연결한다.
Normal-Open(NO), to K61 and K62 for 전원을 공급한다.
Normal-Close(NC). 전원을 18V 이하로 떨어뜨리거나 29V 이상으로
Connect the power source to K11(+) and 올리면 “99.11”이 디스플레이되고 전원 불안정
K13(-). 알람 출력 릴레이가 동작한다.
By falling the power source down below 18V Rsd = 0Ω , 노말 오픈(NO), Rsd = ∞Ω ,노말 클
or raising it up above 29V the readout will 로즈(NC).
be "99.11" and the Power Failure Alarm
Output relay will activated:
Rsd = 0Ω for Normal-Open(NO), Rsd = ∞Ω for
Normal-Close(NC).

10
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

By setting the power source between 18V 전원이 18V에서 29V사이로 공급되면 디스플레
and 29V the display will return to an 이 값은 0.00~0.05mm로 되며, 릴레이는 동작을
indication of 0.00~0.05mm and the Power 멈춘다.
Failure Alarm Output relay will be Rsd = ∞Ω , 노말 오픈(NO), Rsd = 0Ω ,노말 클
deactivated : Rsd = ∞Ω for Normal-Open 로즈(NC).
(NO), Rsd = 0Ω for Normal-Close(NC). 만약 정상적으로 동작하지 않으면 제어 유닛을
If not, the circuit board may be defective 바꿔야 한다.
and should be replaced.

IX. Check of the Probe XI. 프로브 증상 체크


Connect the power supply and an amp-meter 전원을 공급하고 전류 메타를 프로브에 연결한다.
to the probe. 프로브에 쇠 조각을 움직이면서 이동하면 Ip가 변
First, check the connection by moving a 동한다. 만약 Ip가 변동하지 않으면 프로브나 프
piece of metal back and forth in front of the 로브 선에 이상이 있는 것이다.
probe. If no variation in Ip is found, the 만약 Ip가 표준값과 전혀 다르면 프로브를 바꿔야
probe or the probe cable may be defective. 한다.
If Ip varies, check Ip vs. the distance to the
metal. If measurements(mA vs. mm) differ
significantly from the calibration data found
on the probes calibration sheet, the probe
should be replaced.

11
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

X. Check of the electronic cabinet for X. 출력 전압 증상 체크


Voltage Output K21, 22, 23에 프로브 선을 연결한다.
Connect the probe cable to K21,22,23. 전압계를 BNC 단자에 연결한다.
Connect an voltmeter to the BNC. Res1을 계속적으로 접속해 놓으면 출력 전압은
By connecting Res1 the voltage output will 7.40V가 될 것이다. Res1과 Res2를 계속적으로
be 7.40V. By connecting Res1 and Res2 the 접속해 놓으면 출력 전압은 10.60V가 될 것이다.
voltage output will be 10.60V. 만약 접속과 분리를 계속적으로 반복하면 디스플
By continuously connecting and disconnecting 레이가 변하고 Vout은 7.40에서 10.60V까지 변한
Res2 the voltage output will change from 7.4 다. 0.00에서 13.00V 까지 측정 가능하고 3.50
to 10.6V. ~13.00 범위에서는 선형성이 유지된다.
The measurement range is from 0.00 to 정상적으로 동작이 되지 않으며 제어 유닛을 바
13.00 V and the value is linear on the range 꿔야 한다.
from 3.50 to 13.0V. If Vp is not significantly
proportional to the distance the circuit board
may defective and should be replaced.

12
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

SYSTEM SET-UP 시스템 셋업


After mounting the probe and connecting the 프로브를 장착한 후에 제어 유닛에 연결하면 시
circuit board, the Axial Vibration Monitor is 스템 셋업을 위한 준비가 된 것이다.
ready for set-up.

13
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

The installation procedure is following: 설치 절차는 다음과 같다:


First, mount the axial vibration monitor 첫째, 모니터를 엔진 사이드에 설치한다.
(display unit) on an diesel engine. 둘째, 엔진크랭크 케이스에 센서를 적절한 위치에
Second, mount a sensor(probe) at desired 설치한다. 즉 측정 대상물(크랭크샤프트)와 센서
mounting position properly, that is a distance 사이의 거리를 2.5~15.5mm 범위 안에 적당히
from the target on engine crank case 설치한다.
Third, connect a sensor cable to monitor. 셋째, 센서를 모니터에 결선한다.
Fourth, turn on the power. 넷째, 모니터에 전원을 공급한다.
Fifth, read a current mounted position 다섯째, 두개의 셋팅값 확인 버튼을 동시에 누른
displayed on the monitor by pressing the 상태에서 센서설치를 확인한다.
both view buttons simultaneously. 마지막으로 원하는 위치와 설치된 센서와의
Finally, please move the sensor just as much 차이만큼 센서를 이동하여 원하는 위치에 센서를
as difference between the desired mounting 설치한다.
position and the current mounted position.
Please, repeat fifth and final procedures until
a sensor is mounted at desired point.

14
"YJBM 7JCSBUJPO .POJUPS "7.,. 6TFST .BOVBM

SPECIFICATIONS

OPERATING
TEMPERATURE RANGE : -10℃ to 60℃

OPERATING HUMIDITY : Less than 95% RH(Non-Condensing)

PROTECTION : IP67

MEASURING RANGE : Max. : 13.00 mm Peak to Peak(+/- 6.50 mm)


Linearity : 13.00 mm Peak to Peak(+/- 6.50mm)

POWER SUPPLY : Supply voltage : 24 Volt DC +/- 20 %


Max. current consumption : 140mA

PROBE : Type : Balluff BAW-030-PF-1-K


1)
Mounting distance : 8.50 mm
ALARM/MONITORING
CURRENT OUTPUT : Output : 4 ~ 20 mA
Max. load : 800 Ohm
0 mm Peak to Peak → 4 mA
10 mm Peak to Peak → 20 mA
> 10 mm Peak to Peak → 4 mA
Iout[mA] = 1.6 × (displacement in mm Peak to Peak) + 4
where, a displacement is lower than the 10 mm

SLOW DOWN OUTPUT : Potential free contact(NO, NC)


Max. load : 50 Volt 10A
VIBRATION HIGH
ALARM OUTPUT : Potential free contact(NO, NC)
Max. load : 50 Volt 10A
POWER SOURCE&SYSTEM
FAILURE OUTPUT : Potential free contact(NO, NC)
Max. load : 50 Volt 10A
SLOW DOWN
ADJUSTMENT : 0.00 to 10.00 mm
VIBRATION HIGH
ADJUSTMENT : 0.00 to 10.00 mm

SLOW DOWN DELAY TIME : 0 ~ 300 sec. adjustable in step of 20 sec.


CRANKSHAFT
POSITION OUTPUT : Output voltage : 0 ~ 13 Volt
Max. output current : 10 mA
Output : 1.0 volt change per mm displacement of the
crankshaft

ACCURACY : Probe input to display, crankshaft position output


and alarm monitoring current output : +/- 5 %
Slowdown delay time : +/- 10 %

WEIGHT : 3.3kg

DIMENSION : 157(W) × 195(H)

Note
1) : The user can install a probe at wanted mounting distance only if a distance between the crankshaft and the probe
is not absolutely over the normal range. For example, it is 8.50 mm for an Man B&W diesel engine and is 6.50
mm for a sulzer type diesel engine. It is at user's option to select a cable length of the probe.

15