Product characteristics
■■ As standard for metrological class 2, fulfils the
requirement of technical guideline 9 of PTB
■■ Permitted temperature range: 5... 120 °C
■■ Suitable for water glycol heat carriers
(without conformity assessment)
■■ Downpipe and riser pipe versions also available in the
special short overall lengths 135 mm (for qp 3.5 and 6)
and 150 mm (for qp 10)
■■ Flange versions as standard in pressure stage PN 25
■■ Optimal for combination with the heat meter
calculator ZENNER multidata WR3 or
other standard calculators
Technical data sheet Flow sensor IMF
Water
Heat carrier water-glycol mixture (without conformity assessment)
*
optionally
Dimensions IMF
2
Technical data sheet Flow sensor IMF
Water
Heat carrier water-glycol mixture (without conformity assessment)
206 (ST) 231 (ST)
Height H1 mm 195 195 195 195 195
197 (FA) 212 (FA)
Width B mm 95 95 95 95 95 110 110
Weight approx. kg 3.1 3.1 3.1 3.1 3.1 5.5 5.5
*
optionally
3
Technical data sheet Flow sensor IMF
Subject to technical modifications. We accept no liability for any errors or misprints. ZRI_SAP163937_190517_EN
Counter output
class according to EN 1434-2 OA
Switch variants Reed contact
Polarity reversal possible
Duration of the pulse ≥ 100 ms
Pulse break ≥ 100 ms
Bounce time ≥ 1 ms
Input magnitude 30 V
Greatest input current 27 mA
Protection resistor 68 Ohm
Pulse value In accordance with the details on the type plate
Connection line length, max. 25 m