Active Harmonic Filters - Design and Installation Assistance
Active Harmonic Filters - Design and Installation Assistance
Active Harmonic Filters - Design and Installation Assistance
Introduction
Active Harmonic Filters are available in two ranges, the low power Accusine SWP
range and the larger Accusine PCS range. Both are discussed in separate chapters.
This document aims to assist with the integration of the Active Filter in the power
distribution and deals with some specifics associated with this technology. This note
is valid for filters being used for Harmonic Compensation. Other filter modes have
not been considered in this note.
Cross Resistance
section in in Ohm/m
mm2
1.0 0.018
1.5 0.012
2.5 0.0074
4.0 0.0046
Example:
Primary CT rating:
Cable: Twisted and/or shielded pairs. Keep the twisting going all the way to
the CT terminals.
Protection:
Power Cables :
Power Cables should be rated at 125% of the filter rating current to avoid
excessive heating. The phase sequence of the 3-phase power wires feeding the
active filter must be positive sequence, i.e. a phase rotation meter should
indicate clockwise.
Accusine PCS utilises a significant airflow to cool the units. Filters must be kept clean
to prevent the units from tripping on over temperature. The Accusine is not suited to
an extreme dusty environment.
Dimensions:
General Considerations
Some loads powered off distribution boards may have “exposed” capacitors. These
loads may require blocking chokes, or alternatively move the feed for the distribution
board to upstream from the filter.
Cross Resistance
section in in Ohm/m
mm2
1.0 0.018
1.5 0.012
2.5 0.0074
4.0 0.0046
Example:
Primary CT rating:
9 of 14
Acceptable primary ratings are: 300 / 500 / 600 / 1000 /1500 / 2000 /
3000 / 4000 / 5000 / 6000. The maximum primary rating is 6000Amp.
However accurate performance at low loads the requires the CT to
match load. Typically a reasonable accuracy down to 10% of the CT
rating can be expected.
Preferred option due to optimum CT Four set’s of CT’s required for the filter
sizing and only one set of CT’s
required Sizing of CT’s need careful consideration to
optimise performance
Can only be used when CT can be
mounted to see all none linear loads
without seeing linear loads or power
factor correction
12 of 14
Protection:
20 Amp filter: 32 Amp Breaker B curve, ref. 25873
30 Amp filter: 40 Amp Breaker B curve, ref. 25874
45 Amp filter: 63 Amp Breaker B curve, ref. 25876
60 Amp filter: 80 Amp Breaker B curve, ref. 18349
90 Amp filter: (63 Amp Breaker B curve, ref. 25876) x2
120 Amp filter: (80 Amp Breaker B curve, ref. 18349) x2
Power Cables:
Bottom entry
Power Cables should be rated at 125% of the filter rating current to avoid
excessive heating. The phase sequence of the 3-phase power wires feeding the
active filter must be positive sequence, i.e. a phase rotation meter should
indicate clockwise.
Dimensions:
General Considerations
Some loads powered off distribution boards may have “exposed” capacitors. These
loads may require blocking chokes, or alternatively move the feed for the distribution
board to upstream from the filter.