Manual Detector DL4
Manual Detector DL4
Manual Detector DL4
$- MODEL SERIES
DGAB DL4 4A2.3-GS QSA3
DGAC DL6 6A3.4-GS QSA4
DGAD DL6T 6AT3.4-GS QSA6
DGAE
GENERATOR AND DETECTOR CONTROL
Voltage Regulator
The voltage regulator circuit is connected directly to the
AC generator. Because it regulates excitation in
DUAL RANGE responseto generator output, the regulator is covered in
AC VOLTMETER detail in Section 6, Generator and Voltage Regulator.
Control Heater
DUAL RANGE The optional control heater providesa means of humidity/
AC AMMETER temperature control for the control box interior. The
heater protects the components from varying environ-
mental conditions during extended periods of nonuse.
The heater element is controlled by an adjustable ther-
mostat. See Figure 2-2. The resistance of the element is
192 ohms, and dissipates 75 watts at 120 VAC.
Indicator Lamps
Depending on the genset model and the options
ordered, the control might have a 4-, 7-, lo-, or 12-lamp
EMERGENCYSTOP BUTTON monitoring system. Refer to the applicable lamp des-
(OPTIONAL)
criptions that follow. Red lamps when lit indicate genset
shutdown.
FIGURE 3-1. DC CONTROL PANEL
RUN (green) This lamp comes on when both starter-
The components shown in Figure 3-1 are standard disconnect circuits are opened after genset start.
unless identified as optional in the following descrip-
tions. The panel has 4, 7, 10 or 12 indicator lamps. PRE LO OIL PRES (yellow) lndicates engine oil
pressure is marginally low.
Oil Pressure Gauge: lndicates lubricating oil pressure
in the engine (wired to a sensor unit on the engine). PRE HIGH ENG TEMP (yellow) lndicates engine
temperature is marginally high.
Water Temperature Gauge: lndicates temperature of
circulating coolant in the engine (wired to a sensor unit LOW OIL PRES (red) lndicates engine has shut
on the engine). down because of critically low oil pressure.
Battery Charge Rate DC Voltmetec Indicatesthe battery HI ENG TEMP (red) lndicates engine has shut down
charging voltage. because of critically high engine temperature, or a
low coolant level.
Oil Temperature Gauge (Optional): lndicates tempera-
ture of lubricating oil in the engine (wired to a sensor unit OVERSPEED (red) lndicates engine has shut down
on the engine). because of excessive speed.
Tachsmeter(0ptional):Providesconstant monitor of engine OVERCRANK (red) lndicates the starter has been
r/min. locked out because of excessive cranking time.
LOW ENG TEMP (yellow) lndicates the engine CONTROL PANEL INTERIOR
temperature is marginally low for starting. lndicates
The following describes the engine control components
inoperative coolant heater on gensets with this
option. and how they function (Figures 3-1, 3-2). Some of the
following descriptions may not apply depending on
LO FUEL (yellow) lndicates fuel supply is marginally options included on each individual control system.
low. Engine Control Monitor (ECM-All)
This solid state printed circuit board monitors basic
SWITCH OFF (flashing red) lndicates genset is not engine control system functions (Figure 3-3). This
in automatic start operation mode.
includes starting, stopping, and fault system operation.
Terminal blocks are included for making remote con-
FAULT 1 (red) A customer installed auxiliary equip- nections and adding further control options.
ment fault switch. The lamp is part of the timed
factory-set (10 second) shutdown circuit.
The ECM provides the following functions for genset
FAULT 2 (red) A customer installed auxiliary equip- protection:
ment fault switch. The lamp is part of the factory set,
non-timed delayed shutdown circuit. Overcrank: Limits engine cranking to 75 seconds. If
engine fails to start, the module lights a fault lamp and
opens the cranking circuit. The cycle cranking option
allows three 15-second cranking cycles with two 15-
second rest periods on 10- and 12-light controls.
3-2
0verspeed:Shuts down the engine immediately if over- Pre-Low Oil Pressure: Sensor and lamp option pro-
speed occurs and turns on the fault lamp. The sensor vides an alarm indicating that oil pressure is marginally
switch is mounted in the end bell on the generator shaft. low, 20 psi (138 kPa) or less. The cause should be found
It is factory adjusted to shut down 1800 r/min gensets at and corrected as soon as possible. This fault is delayed
2200 f100 r/min, and 1500 r/min gensets at 1900 +I00 with low oil pressure functio:,.
rlmin.
High Engine Temperature: Shuts down the engine
Low Oil Pressure:Shuts down the engine immediately if immediately if coolant temperature rises above 222°F
oil pressure drops below 14 psi (97kPa) and turas on a (106°C)and turns on a fault lamp. The fault is time
fault lamp. The fault is time delayed about 10 seconds delayed about 10 seconds following starter disconnect
following starter disconnect and is inhibited during and is inhibited during cranking. This delay allows cool-
cranking. The delay allows oil pressure to rise to normal ant in a hot engine time to circulate and return the water
before the electronic control module monitors the jacket temperature to normal before the electronic con-
pressure. trol module monitors the system.
BLOCk D I A G R A M
LO F U E L
I SW O F F
I
LET -4 TB1-6 IS SIGNAL MODE SELECTABLE AS FOLLOWS:
P R L LOP
SW OF1 B e
srop
LAMP TEST ' R E S E T
44 :\, F 4
>!I
SW OFF
LO F U F L
P2-2:W7 P2-3:W6 POSITION
A
FUNCTION MODE
NON-SHUTDOWN
B SHUTDOWN
p : : ; : : ; :
RMT
0 5 IN
OC DISC I N
S T A R T SOL
PI 6
-7
nRnuun
3-4
Pre-High Engine Temperature:Sensor and lamp option
provides an alarm that engine temperature is marginally
high, 202°F (94°C). The cause should be found and
corrected as soon as possible. This fault is delayed with
the high engine temperature function.
-
Low Coolant Level an optional solid-state sensor/
K l t RELAY
switch that provides engine shutdown if coolant level
falls too low. It also turns on the high enginetemperature
fault lamp.
A13
TBZ
-5 All-TB1J
0-
mEm
LOP 8
@
nm g
FAULTIl
FAULT%?
LET
LOW FUEL
SWITCH OFF
- 2 " - - -
PCB ASSY -ALARM R E L A Y 112VI
3-6
Time Delayed Start/Stop, and Preheat Module
(A15)
BLOCK DIAGRAM This optional module includes the preheat feature with
B.
the time delayed start/stop option. See Figure 3-6. The
functions are as follows.
PCB A S S Y - T D S T 8 S P P H T ( 1B 2 V I
R E V C WI
R I c.w.
- -
T O INCREASE R2
A
W2 B A
Automatic: With S12 in the Remote position, a start F3 - B+ out fuse (15-ampere) to protect circuit board.
command to the control activates the Time Delayed
StartIStop and Preheat Module (A15), which initializes F4 - Main ECM circuit fuse (5-ampere)to protect circuit
its time delay start and preheat period. board paths and components on the ECM.
Upon completion of the time delay startlpreheat period, F5 - Gauge fuse (5-ampere) to protect circuit board,
the ECM begins the cranking and startup by energizing gauges on the front panel, and all associated wiring.
Run Relay (K7) as described in Manual starting.
High Engine Temperature (HET) and Low Oil Pressure
After the engine successfully cranks and the starter (LOP) faults are time delayed about 10 seconds follow-
disconnects, input signals from either start disconnect ing starter disconnect and are inhibited during crank-
system of the ECM will activate the Start Disconnect ing. This allows the coolant in a hot engine some time to
Relay of Module A1 5 (K1).This deactivates the preheat circulate and return the water jacket to normal tempera-
output and programs the module for Time Delayed Stop ture before the ECM begins monitoring it. It also allows
mode. the oil pressure to build to normal before monitoring this
system. Following this delay, these faults become
immediate shutdowns for engine protection.
If conditions are correct, the engine will start and the Continuous operation of the genset also dependson the
starter will disconnect. If not, the overcrank fault circuit proper oil pressure and engine temperature being main-
times out to energize Fault Relay (K6). This opens the tained, and also any customer required fault conditions
start circuit of the ECM. The reset switch (S11) must be connected to the ECM.
pushed to clear any fault before attempting to restart.
Stopping Sequence
Start-Disconnect Sequence Placing the Run/Stop/Remote switch at Stop position
When the genset starts, output voltage from the DC de-energizes Run Relay K7. This opens the circuit
alternator, or from the Magnetic Pickup Module, ener- through the ECM (K2) and de-energizes the genset fuel
gizes Start-Disconnect relay K14. Relay K14 then solenoid (stops fuel flow which stops the engine).
closes its normally-open contacts to illuminate the con-
trol panel RUN lamp. Also, when the genset starts, out- Emergency Shutdown
put voltage from the generator stator energizes Starter- The K6 fault relay energizes when fault sensors respond
Disconnect relay K10. Energizing K10 closes its to any one of several fault conditions such as overcrank,
normally-open contacts and illuminates a Remote Run low oil pressure, low coolant, high engine temperature,
lamp (if equipped). overspeed, overlunder voltage output. Energizing the
K6 fault relay opens its normally-closed (N.C.) contacts
After the starter disconnects, the LOP and HET fault and closes its normally-open (N.O.) contacts.
shutdowns will remain inhibited for another 10 seconds
to allow oil pressure and engine temperature to stabilize Opening K6 N.C. contacts disconnects B+ from the
within the operating range. Power Relays K3 and K2. This stops cranking (if the
engine is being cranked) and shuts off the fuel flow.
Normal Operating Parameters Closing one of the K6 contacts activates the K8 relay.
After a successful engine start-up, with all conditions This relay breaks power to the fault interface relays so
satisfied, the engine will gain rlmin to the governor that only the indicator associated with the fault will acti-
setting. Should the engine go into an overspeed condi- vate. Closing the other N.O. contacts of K6 connects B+
tion, the Magnetic Pickup Module (A16) will reach the to the remote alarm terminal.
trip point and ground the ECM overspeed circuit to
cause shutdown. Emergency Stop Switch
Pushing in the Emergency Stop button energizes the
If the genset does not use Magnetic P i c k u p fault shutdown circuit and stops the genset. Pull out the
Module/toothed-wheel speed sensing, a mechanical Emergency Stop button to reset the fault circuit.
overspeed switch is used. Either means of controlling
overspeed activates the overspeed fault lamp. After the
problem is corrected, starting will not occur until the
Reset switch is pressed.
Section 4. Engine Control Service
TROUBLESHOOTING PROCEDURES 8 Review troubleshooting information as outlined in
Regardless of the controller model the genset is the Operator's manual.
equipped with, basic troubleshooting is fundarrientally
the same. The basic fault conditions are as follows: 8 Check all modifications, repairs, or parts replace-
ments performed since the last satisfactory opera-
A. Engine does not crank. tion of the genset. A poor wire connection, an open
switch or circuit breaker, or a loose plug-in device
B. Engine cranks, but does not start. are all potential problems that can be eliminated by
a visual check.
C. Engine starts, but stops after running several
8 Unless absolutely sure that panel instruments are
seconds.
accurate, use portable test meters for trouble-
shooting.
D. Genset is in operation,then a fault condition occurs.
Because the troubleshooting tables in this section Remember to keep the problem solving process factual
include informationabout various control options, read and methodical, and always use safe troubleshooting
through this section to identify which options relate to practices.
the specific genset. This will save time when an actual
fault condition occurs. Before starting the troubleshoot-
ing procedures, make the following simple checks.
Many troubleshooting procedures present hazards that can result in severe personal injury or
death. Only qualified service personnel with knowledge of fuels, electricity, andmachinery hazards
should perform service procedures. Review safety precautions on page ii.
1. Overcrank Fault
shutdown lamp
illuminated.
2. Fault shutdown occurs, Lamp burned out. Depress Lamp Test switch
but no fault lamp S11 to check fault lamps.
indication.
Possible defective Refer to Symptom 3.
ECM board A1 1.
1 TABLE 4-3. ENGINE STARTS BUT STOPS AFTER RUNNING SEVERAL SECONDS. I
SYMPTOM CAUSE CORRECTIVE ACTION
Fixed Setpoint
If shutdown occurs before
limit, replace A16 module.
Adjustable Setpoint
If shutdown occurs before
desired, setpoint, readjust
module A16. If adjustment does
not correct fault conditions,
replace module A16.
I TABLE 4-3. ENGINE STARTS BUT STOPS RUNNING AFTER SEVERAL SECONDS. (Continued) I
I SYMPTOM
C. High Engine
Temperature.
CAUSE
Low coolant level
in engine.
CORRECTIVE ACTION
Replenish as necessary.
1. Fault indicator
lamp illuminated.
F4-(Main) - 5 Ampere
F2- (Fuel solenoid or
ignition) - 20 ampere
WATER
SENDER +' A
I / :<
LQ
PRE-HIGH
ENGINE
TEMPERATURE
SWITCH
PRE-LOW OIL
PRESSURE
SWITCH
-- WATW
sB(DER
,
PRE-HIGH
ENGINE
TEMPERATURE
!WITCH
HIGH ENGINE
VlEW A-A
VIEW B-B
4-9
Section 5. Generator and Voltage
Regulator
GENERATOR DESCRIPTION A ball bearing in the end bell supports the rotor shaft.
The generator is a four-pole, revolving field, brushless The end bell is attached with four studs that thread into
exciter design. Single and three phase generators are the generator adapter casting. The exciter stator mounts
available in both 50 and 60 hertz. in the end bell; the exciter rotor and its rotating rectifier
assemblies mount on the rotor shaft. Within the end bell,
The generator rotor is directly coupled to the engine leads F1(+) and F2(-), from the exciter stator winding,
flywheel with a flexible drive disc (Figure 5-1). The connect to the output terminals of the voltage regulator.
engine speed determines output frequency. A centrifu-
gal blower on the drive disc pulls cooling air through the
end bell and discharges it through an outlet near the
blower.
ROTOR
-*m-
MAIN FIELD
---
a
ROTOR
-- -
- -0-DC --
I
1
EXCITER I 1 1
1
MAIN
FIELD
I
-------
VOLTAGE LOAD
REGULATOR
Operating Stability
Different regulator gain compensation is required for
different generator sizes and exciter/main field time
constants. The voltage regulator is switch-selectable to
FRONT METER a kilowatt range that best suits the genset application.
PANELS
a Switches S2 andS3: Determinethe mode of regula- See Section 7 of this manual for replacement and
tion (Torque-Matched or Non-Torque-Matched). adjustment procedures.
Refer to Table 5-1.
R32
VOLTAGE ADJUST '
5-4
LINE CIRCUIT BREAKER
Depending on site specifications and code require-
ments, an optional line circuit breaker may be mounted ,u
CONTROL
in the generator AC output box. 1 PANEL
i
Description
All factory supplied line circuit breakers are thermal and
magnetic trip type. Depending on customer require-
ments, the breaker may also include shunt trip and
remote alarm connections. Review the following func-
tions/requirements and Figure 5-6.
Accidental starting of the generator 6.3 AC Output Voltage Too High or Low.
IBEECI set can cause severe personal injury
or death during service procedures. Be sure to disable 6.4 Exciter Field Breaker Trips.
the generator set by disconnecting the starting battery
cables (negative [-I cable first). 6.5 Unbalanced AC Output Voltage.
gloves and apron when servicing battery. After determining the problem, refer to the applicable
troubleshooting flow chart. Start at the chart upper left-
A few simple checksand a valid troubleshooting proce- hand corner and answer all the questions either YES or
dure can quickly locate the trouble source and cut ser- NO. Follow the chart until the problem is found, perform-
vice time. The following are inspection areas often over- ing the referenced Adjustment and Test Procedure(s)
looked when troubleshooting. following the flow charts.
Check all modifications, repairs, and replacements The referenced components in the flow charts and in
performed since the last satisfactory operation of the Adjustment and Test Procedures can be found on
the set to be sure that all generator leads are cor- the electrical schematic in Figure 6-1, and on assembly
rectly connected. A loose or incorrect wire terminal and wiring diagrams in Section 10 of this manual.
connection, or an open circuit breaker overlooked
when replacing a part could cause problems. A
thorough visual check can quickly eliminate these
potential problems.
6- 1
COMPONENT DESCRIPTION
REF. DESCRIPTION
-
LNO
LCi23jT
=
, 1;
NOTES
1. See generator connection diagram 625-2108 in Section 10 for
input connections.
2. Dashed components and leads indicate when used.
3. This figure is for reference only. Use the d.ctrical schematic
specific to the application when troubleshooting.
C
Is control panel field breaker CB21 on
(fully-in pos~tion)?
Replace defectcve field b r w k u
4
I
Remove one lead from breaker and
NO check cont~nu~ty
wlth ohmmeter Is
I breaker open?
4
Yes
I
Flash the exc~terstator per TEST
I [B] Does AC output voltage build up?
:
res~dualvoltage across the leads 5 to
10 VAC or more now?
I No
i
Check lead continuity between
voltage regulatorITB1-2 and maln
Is exciter stator voltage across
voltage regulator/TB-9 and 10 equal -NO stator lead 7, and between voltage
regulatorITB1-3 and stator lead 8
I
Yes
I I Check exclter stator wlrlng for
shorts per TEST [J] Replace bad
wlrlng I
Check exclter stator wlrlng for
Check rectlf~ersCR1 - CR6 on
opens per TEST [J] Replace bad
exc~terrotor per TEST [Dl Replace
IaCAUTION
] TOavoidpossible damage to the new
voltage regulator board, do not
--
b
Check maln stator wlndlngs per
replace until all external problems have been Test [HI Replace i f bad
corrected.
CHART 6-2. UNSTABLE AC OUTPUT VOLTAGE, ENGINE STABLE AT RATED SPEED
Many troubleshooting procedures present hazards which can result in severe personal injury or
1 -should perform service
death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards
procedures. Review safety precautions on page ii.
No
I
Check wirlng harness from
regulator assembly to the end bell
per TEST [J]. Check okay?
FN0 Repair wiring or replace as required.
I
Check voltage regulator
adjustment/switch settings per
- Is voltage stable within specifications
at no load to full load range of
generator set?
I
No
w I
m
r
Replace voltage regulator To avoid possible damage to the new
per TEST [C]. voltage regulator board, do not
replace until a l l external problems have been
corrected.
~ w A R N ~Many
N Gtroubleshooting
eath.
procedures present hazards which can result in severe personal injury or
~ qualifiedservice
Only personnel with knowledge of fue/s, electricity, and machinery hazards
should perform service procedures. Review safety precautions on page ii.
Yes
I No I,
i
Set r / m ~ nper instructions in the
appropr~ateengine manual
Is voltage w ~ t h ~spectt~cat~ons
n at
swltch sett~ngsper TEST [K]
-- no load to full load range of generator set?
Check okay? I
No
A
I Check rotat~ngrectifiers in
excuter rotor per TEST [Dl.
Replace if bad.
adjustments and connections
per TEST [K].
I
Check exciter stator winding
Many troubleshooting procedures present hazards which can result in severe personal injury or
AWARNING death. Only qualifiedservicepersonnel with knowledge of fuels, electricity, andmachinary hazards
should perform service procedures. Review safety precautions on page ii.
D~sconnectload from generator (tr~p Reconnect load and check each phase
AC breaker if used). Is output NO for balanced current. If not within
stdl unbalanced? 10% of each other, redistribute the load.
Many troubleshooting procedures present hazards which can result in severe personal injury or
death. Only qualifiedservicepersonnel with knowledge of fuels, electricity, andnuchinery hazards
should perform service procedures. Review safety precautions on page ii.
I I
Ygs
- - -- -
-
I
not immediately known, stop
generator set and investigate cause
Circuit overload (per site-
established procedures).
GENERAL
The following tests and adjustments can be performed FLASHING THE EXCITER FIELD
without disassembly of the generator. They should be
used for testing the generator components and regula- If the residual voltage is missing, it might be necessary to
tor together with the troubleshooting flow charts in Sec- restore magnetism by flashing the exciter field. This
tion 6. All resistance measurements must be made with requires a 12-volt battery, 10-ampere fuse, momentary-
the genset stopped and battery disconnected (negative on switch, and 12-ampere diode assembled as shown
[-I cable first) to prevent instrument damage. in Figure 7-2.
F: TO EXCITER FIELD
\ U
CB21
FIELD
CIRCUIT TB21
BREAKER TERMINAL BOARD
7-1
During Genset Operation
1. Connect the positive (+) lead to terminal 9, and the AC VOLTAGE REGULATOR REPLACEMENT
negative (-) lead to terminal 10 on the voltage regu- Use the following procedureto replace the voltage regu-
lator (Figure 7-1). lator assembly shown in Figure 7-1.
ROTATING RECTIFIERS
Two different rectifier assemblies make up the rotating
rectifier bridge assembly, Figure 7-3. Using an ohmme-
ter, test each CR rectifier using negative (-)and positive
-
(+) polarities. Use the following procedure.
CA-1010-9
Use 23 to 26 inch pounds (2.6 to 2.9 Nom) torque when replacing nuts CA-1010-11
of F1+ and F2- leads, CR1, CR2, CR3, CR4, CR5, and CR6.
FIGURE 7-4. TESTING EXCITER STATOR
Testing for Grounds 20.0 DL4 0.645 ohms f10%
Connect a Megger or insulation resistance meter that 25.0 DL6
applies 500 VDC or more between the field and the 40.0 DL6T
exciter stator lamination. See Figure 7-4. Be sure both DGAB
exciter leads are disconnected from the terminal block. DGAC
Reading should be 100,000 ohms or greater. If not, the DGAD
exciter stator is questionable and might require removal DGAE
for oven drying and retest. A shorted stator must be 4A2.3
replaced. 6A3.4
6AT3.4
EXCITER ROTOR
ASSEMBLY
WHEATSTONE RESISTANCE
BRIDGE OR METER
DIGITAL OHMMETER
TESTING WINDING FOR GROUNDS
CONNECTION DIAGRAM
a-101012
1. Remove rotor leads F1+ and F2- from the rotating Testing For Open or Shorted Windings
rectifier assemblies. Test for continuity across stator coil leads. Each coil
should have equal resistance. Use an accurate instru-
Be sure to remove both rotor
/nCAUTION\ leads so the rotating rectifiers
are isolated. Failure to do this will damage the
ment for this test such as a Wheatstone Bridge. Resist-
ance readings should be as shown in Table 7-2 at 77OF
(25°C) +10 percent. See Figure 7-7 for determining the
rectifiers. stator stack length.
2. Connect test leads between one of the two leads If a winding is shorted, open or grounded, replace the
and the rotor shaft. Meter should read 100,000 ohms stator assembly. Before replacing the assembly, check
or greater. leads for broken wires or insulation.
3. If less than 100,000 ohms, the rotor is questionable
and might require removal for oven drying and Testing For Grounds
retest. Use a Megger or insulation resistance meter which app-
lies 500 VDC or more at the test leads. Test each stator
4. Replace a grounded rotor with a new identical part. winding for short to laminations. If less than 100,000
ohms, the stator is questionable and might require re-
moval for oven drying and retest.
GENERATOR
CROSS-SECTION
VIEW
STACK
LENGTH
(LAMINATION)
TESTING WINDING RESISTANCE
MEGGER OR
INSULATION
RESISTANCE
PANELS
R32
'AGE P
\
TB1-2 -3 AC INPUT VOLTS R34
TB1-3 -4 CROSS-CURRENT COMPENSP.TIGN DO NOT ADJUST
TBl-7 -8 VOLTAGE ADJUSTING RHEOSTAT (SEE TEXT)
TB1-9 -10 EXCITER FIELD
7-8
EEEEGI Contact with high vonage can
cause severe personal injury or
death. Do not touch any exposed wiring or compo-
nents with any part of the body, clothing, tool or
jewelry. Do not use non-insulated tools inside the
control. Stand on an insulating mat or dry wood TRIP
platform when the control doors are open.
OFF
4. With no load on the generator, turn the Phase Selec- RESET
tor switch to read output voltage/current while per-
forming the following adjustments.
dure [K].
Voltage Drop Check:This test is done with the conduc- 2. Check security of the wire connections.
tors connected, genset operating, and load applied. As a
precaution against electrical shock, place an insulating 3. Apply the appropriate signal voltage (12-VDC; 240-,
mat or a dry wood platform on the floor to stand on when 480-VAC). The shunt-trip solenoid should energize
taking measurements. and trip the breaker open.
Contact with high voltage can cause 4. If the breaker did not trip open, remove the signal
severe personal injury or death. Do source. Perform continuity check of interconnect
not touch any exposed wiring or components with any wiring and shunt-trip solenoid lead wires. Replace
body part, clothing, tool orjewelry. Stand on an insulat- interconnect wiring if defective.
ing mat or dry wood platform when taking
measurements. Checking Auxiliary Contacts: If equipped, the breaker
will have three leads for wiring to an internal single-
1. Operate the genset with the breaker in the On posi- pole, double throw switch. The switch allows connec-
tion and load applied. tion of a remote annunciator (see installation wiring
diagrams).
2. Take voltage readings at the line connections, then
the load connections. Perform continuity checks of the switch with the breaker
in On and Off positions to confirm operation.
3. There should only be slight variation in the voltage
dropped across each pole of the breaker. Unequal Adjusting Magnetic Trip Operation: If equipped with
-
or excessive millivolt drops across the complete front-adjustable magnetic trip controls, the short circuit
breaker, or one pole, indicates contaminated con- protection feature for each pole of the breaker can be
tacts or loose connections. adjusted equally or individually as required. Surge cur-
rent above the trip settings will actuate the trip mecha-
4. Stop the genset by placing the Run/Stop/Remote nism. These adjustors are set equally to the high posi-
switch in Stop position and disconnecting the bat- tion at the factory. Consult on-site requirements and
tery negative (-) cable. adjust to proper position.
Accidental starting of the 13. Use a hoist and safe lifting device (stator handling
generator set can cause severe tongs, nylon lifting strap or chain and lifting hooks)
personal injury or death during service proce- to support the main stator assembly.
dures. Be sure to disable the generator set by dis-
connecting the starting battery cables (negative[-] Generator components are
cable first). heavy and can result in severe
personal injury during removal. Use the recom-
2. Remove screws securing the back grille to the rear mended removal techniques and keep hands and
of the generator. feet clear while removing mounting bolts.
3. Remove screws securing the output box cover. 14. Remove screws and lock washers securing the
main stator assembly to the engine adapter.
4. Open control box doors and disconnect the genera-
tor control wires. Check wire stamping legibility to 15. Remove the main stator being careful not to touch or
ease reassembly (if necessary, attach identification drag it on the rotor. Place the stator on its side and
with tape). Arrange leads so they can be withdrawn block to prevent rolling, especially if placed on a
easily through the control box grommet opening. workbench.
5. Remove four screws (5/16-18) and lock washers Falling, heavy objects can cause
securing the control box to the generator output severe personal injury or death.
box. Carefully lift the control box free of leads and Be sure to block or support heavy objects to pre-
set aside. vent falling. Wearprotective shoes and keep hands
and feet clear.
6. Remove all leads from the circuit breaker and free
the output box of all electric conduit. 16. Using a hoist and sling to support the rotor, carefully
remove the capscrews that attach the drive disk to
7. Remove four 3/8-inch nuts securing the upper and the engine flywheel (Figure 8-1).
lower output box brackets at the rear of the end bell.
17. Remove the rotor assembly and place upon wood
8. Remove three capscrews at the front of the output block in the horizontal position. The drive disk and
box. Two capscrews are on the outside (5116-18 x fan should not be resting on anything or distortion
1.25 and flat washers), and one inside the output might occur.
box beside the breaker (5/16-18 x 0.62).
18. Remove bolts that hold the drive disk and fan to the
rotor shaft.
/
OVERSPEED
SWITCH
ASSEMBLY
8-2
19. Use a gear puller to remove the end bearing from 7. Apply a thin film of grease to the mating surfaces of
the rotor shaft (Figure 8-2). If reusing the bearing, be the end bearing and the end bell. Install the end bell
sure to apply puller to the inner race. over the stator stud bolts. Do not install nuts and
lock washers until later.
:i
21. Remove the generator field leads from the exciter
rotor and slide the exciter off the rotor shaft.
REASSEMBLY
Reassembly procedures are basically the reverse of
disassembly. Use the following steps as a guide. Apply DETAIL B
torque as specified in Figure 8-3.
DJUST SCREW
3. Press the end bearing onto the rotor shaft. Spacing
between the shaft end and bearing side surface
20 FT LBS (27 Nm
.)
must be as specified in Figure 8-3.
1 1. Installfour (318-16) nuts and lockwashers to the end 18.The rlmin at which the overspeed switch shuts
bell studs; then three capscrews and flat washers at down the genset can be changed by the adjust
the front of the AC box. Torque the end bell nuts to screw. Turning this screw in or out changes the
20 ft-lb (27Nom). magnetic air gap. When set correctly, the switch
closes and shuts down 60 hertz gensets at 2100
f90 rlmin; 50 hertz gensets at 1900*I00 rlmin. On
12. Tighten the output box capscrews. Using a lead QSA model gensets the overspeed switch is set to
hammer, tap the end bell at the horizontal and verti- shut down 60 hertz gensets at 2400 i150 rlmin; 50
cal plane to relieve stress. Retorque the four end hertz gensets at 21 00 f150 rlmin.
bell nuts.
An accurate frequency meter or strobotach is
13. Assemble wire conduit to the generator output box. needed to check the overspeed trip point when the
Connect the generator, load, and auxiliary wires to engine speed is increased (see the engine service
the AC circuit breaker (if used). manual). The air gap must not be less than 0.005
inch (0.13 mm).
14. Set the control box on the output box. Route all con- W N Contact~wlth high voltage wlres
trol leads through grommet in control box bottom. can cause severe personal Injury or death.
Secure control box with four screws and lock- Some model generator sets can have exposed
washers. wlre termlnals when making this adjustment.
Be sure the generator set battery is dlscon-
15. Carefully connect all control leads to their marked nected (negailve 1-1 lead flrst) to prevent start-
terminations. ing before making an adjustment -4
Section 9. Miscellaneous
GENERAL TRAILER OPTION (QSA-SERIES)
This section contains basic service and maintenance
Trailer Brakes
informationfor miscellaneous components that might not The trailer uses a system called surge braking. When
be referencedelsewhere in this manual, or in other Onan the tow vehicle brakes are applied, the push of the trailer
literature. The components are mostly "model specific." toward the tow vehicle automatically synchronizes its
braking with the tow vehicle. The actuator telescopes
together and applies force to the master cylinder that
supplies hydraulic pressure to the brakes. See Figure
9-1. A breakaway system applies the trailer brakes
should both the coupling and safety chains fail.
9-1
Brake Maintenance tions, the actuator should be flushed periodically with
a high pressure water hose. Grease bearings and oil all
1. Before towing, check the brake fluid level in the
moving parts after the unit has dried. At the end of
reservoir. It should be at least half full. If not, add
season when unit is stored, remove the brake drums
DOT 3 brake fluid. Check for leaks and repair as and clean inside the brakes. Pack the wheel bearings
required.
before installing drum.
2. Examine the actuator for bent parts or wear.
Replace parts as necessary and make sure mount- Trailer WiringILighting
ing bolts are tight and welds not cracked. There are Check the trailer wiring and operation as follows. Table
no adjustments on the brake actuator. 9-1 lists the wire color codes and their purpose.
Readjust the brake shoes to reduce actuator stroke TABLE 9-1. WIRING COLOR CODES
length if it exceeds 1 inch (25 mm). The length of the
roller path on top of the actuator, when it is fully COLOR PURPOSE
extended, is the same as stroke length. Brake shoe I
Braking power can dimish when 1. Check that the white (ground) wire of the trailer
LAWARNING actuator stroke length exceeds harness is connected to the trailer frame; and that
1 inch (25 mm), leading to a serious road accident. the white (ground) wire of the tow vehicle is con-
Check actuator stroke length regularly, and ser- nected to its frame or body. Be sure the tie points are
vice the brakes if necessary. free of corrosion and are a good electrical bond.
This is very important.
3. Before each towing, wipe the coupler and ball clean
and add a film of grease. Doing so will extend their 2. If turn signals do not work properly, check the tow
life while eliminating squeaking. vehicle flasher. Many flashers used in automobile
applications will not carry the additional load of the
4. Bleeding the Brakes: Use the following procedure trailer turn signals. Install only a heavy duty flasher.
to bleed the brake system. Also make sure that the light bulbs are good and
have the correct replacement.
A. Fill the system with DOT-3 heavy duty hydraulic
fluid using a pressure type brake bleeder. This 3. The trailer tail lights should come on with the head-
type bleeder is available at your local automo- lights; the trailer turn signals should flash simul-
tive jobber. Follow the manufacturer's direc- taneously with the tow vehicle turn signals; the
tions. trailer brake lights should come on and go off with
each application and release of the brake pedal.
B. Install bleeder hose on first wheel to be bled.
Submerge loose end of hose in a glass con- 4. If the trailer turn signal lights flash opposite to the
tainer of brake fluid to observe bubbling. towing vehicle, the yellow and green wire connec-
tions from the tow vehicle connector have been
C. Loosen bleeder screw one turn. Bleeding is reversed. Correct problem by reversing the wire
complete for the wheel when bubbling stops. Be connections.
sure to close the bleeder screw securely.
FLOAT
.
SKID-BASE
SWITCHES FUEL TANK
Control switch is in ON position. The control should be wired to shut down the
If AC power is available for pumping. genset (optional) as continued operation will allow
IfDC power is available for internal logic circuits air to enter the engine injection pump necessitating
(connections to the engine starting battery bleeding to restart the engine. (See Operator's
might be required). Manual). After restoring the tank fuel level, reset
circuit with the RESET switch. This switch also res-
HI FUEL: Red lamp comes on if fuel has reached an tores engine operation if the tank control has been
abnormally high level. It indicates a possible failure connected to shut down the engine.
of the "pump-off" float switch (Figure 9-4). The lamp
can be turned off with the RESET switch after the BASIN: Red lamp comes on if fuel has flooded the
fuel level drops to normal. The lamp will come back optional safety basin surrounding the fuel tank. It
on again during the next pumping cycle if the fault indicates possible failure of both the "pump-off
remains. and "high fuel" float switches. The basin float switch
turns off the fuel pump. The pump cannot function
Diesel fuel is highly flammable again until the basin is drained of fuel and the circuit
and can cause severe personal reset with the RESET switch.
injury or death and loss of property if ignited. Con-
tinued operation with a HI FUEL fault can lead to -
BLANK For customer use.
spillage of large quantities of fuel if the high fuel
float switch fails. PUMP: Green lamp is on when the pump is running.
It will come on and go off as fuel is pumped to
-
LO FUEL: Red lamp comes on if fuel level has maintain tank level. The lamp does not come on
dropped abnormally low. It indicates possible fail- when the EMERGENCY RUN switch is used.
ure of the "pump-on" float switch, a fuel restriction,
low fuel supply, or a defective fuel pump. The lamp
can be turned off with the RESET switch after the
fuel level rises to normal. The lamp will come back
on again during the next pumping cycle if the fault
remains.
SYSTEM READ
BLANK PUMPON
RED GREEN
FIGURE 9-3. CONTROL FRONT PANEL
9-4
Switches and Circuit Breakers:
Circuit continuity through these control panel compo-
nents can be checked with an ohmmeter after all power
is removed. The following text describes their function.
9-6
C B I O I - 2 POLE AC C I R C U I T
COLUMN I BREAKER. 1 5 AMP. 7 . 5 AMP
LLPTH
5 1 0 2 - 2 POLE SWITCH
P I 0 3 - 120/24OV PUMP MOTOR
CR106- R E C T I F I E R BRIDGE
@ DS I 2 1 B A S I N F AUI T LAMP
0 5 1 2 7 - H I G H F U t L FAlJLT LAMP
K I 0 8 - H I G H 6UEL S t 1 @. 2i. 38
K 3 0 PUMP RCLAY 0 3 . 30
NOTES:
I . SCHEMATIC KEY:
EACH COMPONENT I S LOCATED BY PART
NUMBER. ON THE RIGHT HAND S I D E . A
DESCRIPTION I S G I V E N OF THE PART AND I T S
K108 FUNCTIONAL LOCATIONS.
1 s -lo-++ TBI-l l H I G H FUEI. FAULT CONTACTS
K109
TBI-I~--++ TBI-13 LOW FUEL FAULT CONTACTS
Kl I0
181. 14 -++ THI 15 LOW SHUTDOWN FAlJL CONTACTS
N/O CCUTAClS
K I2 ON L I N E S 21 A K ) 41
TBI - lb-+l- TBI 17 B A S I N FALJLT CCJNIACTS
K I 18
Tap-26 18:'-2/ S Y ' J T E M K t A U Y CflNTAC!'; 2 S I L K S C R E E N ONAN "98 5 4 5 Of C I R C U I T S C H M A T I C LOCATED ON
THE l N S l L i E TOP OF THE COVER
1 , 1 ,4 I N A L rAOL1 ~ O b J l A
1'~
S T W C I TFRMINAL JUMPERS ARC S L P P L I E U BETWEEN T E R N I N A L S b h 7
WITH THF FACTORY S U P P L I E D 240 A i CONVECTION FUF. 120 VAC FIELd
, ,;, 3'
OPCRATION PLACE ONE JCIMPER BETWEEN TERMINALS 5 b b A N 1 T K
Sf CONLI JIINPLR B k l W t F Y 7 A N 0 8 CHANGk J L M ' f PS ON
IPANSIORMFR I F F DUII'PED Si k S I L K S C R E E N ONAN (98-5954
8 111 1HL IP1S101 OF - H E COVER FOG F a L 1?0/240 C W V E R S I O N
Ih?STRlJL !ON5
9-7
PUMP
MOTOR
PUMP
OUTLET BROWN RED
BLACK BLACK
TERMINAL NO
I
P103-GND
WHITE
4 8
WHITE
PUMP
INLET
CONNECTIONS
1. Remove the end bell cover for access to the motor 1. Connect the float switch wiring harness plug to
wiring terminals. receptacle J5 on the PCB (Printed Circuit Board).
2. Reconnect the brown motor lead from terminal 3 to 2. Connect the 5 leads of the pump wiring harness to
terminal 6, and the red lead from terminal 2 to termi- the appropriate terminals on the control PCB.
nal 3. 3. Connect a 120 VAC or 240 VAC power supply to the
3. Cut the ring terminal connector from the white lead appropriate control terminals. The control is set up
and strip the insulation 1/ 2 inch (12 mm) for splicing at the factory for connection to 240 VAC. Make sure
to the wire harness lead marked PLUS-WHITE. selector switch S103 on the control PCB is in the
4. Connect the 5 leads of the wiring harness to the down position for 240V. If the power supply is to be
appropriate motor terminals or splice. Replace the 120 VAC, make the following reconnections:
end bell cover.
A. Remove the two jumpers between terminals
TB1-6 and TBl-7. Connect one jumper between
terminals TB1-5 and TB1-6, and the other
between terminals T B l - 7 and TB1-8.
B. Move selector switch S103 on the PCB to the up
position for 120V.
i 2
Y
3
1
1 5 6 7 8 9 10
N/C VALVE
I I t2 ,J Id $5 ,a r7 18
II
19 20 21
(4
rl
TB I 22 U W &o i. 27 ZB
3 =v
0000000000 TBZ a.
J6
0 0 0 0 0 0 0 0 0 0 0 0 0
J3
O(ooj
1 0
\
-
VOLTAGE \
RECONNECTlON
SWITCH (Sf) mWAmR WAIN ClRIlIT mENm
n w m u r
CLOSED
?. .-&€-Ell.- - ."."---. --
M U E l I R 7"
MER - M Y E R
YI PVSI 10 R Y '
1 CIRCUIT BREAKER
i
@ @
CIRCUIT BREAKER
(CBl4)
2
.
0 "3i 1 1 1 "LC 2 Vd, \
V i) 0 CIRCUIT BREAKER
OUTPUT TERMINALS
(HARD-WIRE) GROUND
T".
8
0 ce
1 lib &Mi 10 I* iC L*
- --
0 I C
TERMINAL BLOCK,
--- -
R
--- -
-
- e
-1 -
RECEPTACLES
GENERATOR LEAD
(TB-2) I
I
-- -2
I
e R
ACCESS
COVER
TXl-XI TO VR21-2
TX1-X2 TO VR21-4
S1-35 TO TB21-23
TB1-LO TO GROUND
-
H5
nents for troubleshooting, or to remove the panel HI H3
-
370 OHMS b
Transformer TX1
This transformer eliminates the need for changing leads
at the voltage regulator when different voltages are
selected by the voltage reconnection switch (S1). The
five transformer lead connections are shown on the
voltage reconnection panel schematic Figure 9-10.
CONTROL
BOX
n ,
ACTUATOR
MOUNTING
BRACKET
I1 ACTUATOR
1 ARM
\ LINKAGE
STOP ASSEMBLY
s
also included at the end of this section. LOCKNUT
MPU (Magnetic Pickup):The pickup is threaded into the FIGURE 9-15. MAGNETIC PICKUP ADJUSTMENT
top of the generator flywheel housing and secured with a
lock nut. The flywheel teeth moving past the magnetic
face of the MPU generates an AC voltage that is coupled
to the Controller. Refer to the wiring diagram in Figure
9-18 for component wire terminations. The following
checks will establish a functioning unit
Governor AdjustmentICalibration
This section contains information on adjusting the
optional electronic governor. The adjustments
covered are to the stop screws on the injection pump
FIGURE 9-16. ELECTRONIC GOVERNOR CONTROLLER mechanical governor (Figure 9-14), and to the GAIN and
SPEED screws on the Controller (Figure 9-18).
Actuator:The Actuator (Figure 9-17) controls the injec-
tion pump throttle lever. It receives input from the Con-
Contact with rotating machinery can
troller, which in turn receives input from the MPU. Afew result in severe personal injury or
operational checks can establish a functioning unit as
death. Keep hands and fingers clear while performing
follows:
tests on operating equipment.
Wipe the Actuator shaft and linkage if dirty with a
1. Check the governor Actuator linkage to see that it
clean, dry rag.
does not bind through its full travel. The linkage
should be as shown in Figure 9-14.
Check the end bearings on the linkage assembly. If
worn, replace. Prior to adjusting the governor controller, be sure that terminals
7 and 8 are jumpered.
The Actuator must be securely mounted.
2. Attach a tachometer to the engine or a frequency
Check wiring for corroded or loose connections. meter to the generator if the control panel does not
have one of these meters.
n
MAGNmC
PICKUP
When using a frequency meter to determine engine speed, 9. Connect full rated load to the genset and observe
multiplyfrequency by 30 tocalculateengine speed. Example: 30 the frequency meter. If the genset cannot manage
X 60 = 1800 rlmin. the load, stop the genset and shorten the governor
rod by one-half turn. Repeat the procedure until the
3. Set the Controller GAlN adjustment (Figure 9-18) to
genset is able to manage the load, then tighten the
the second mark from zero.
locknuts.
4. Disconnect the governor rod from the throttle lever.
10. Connect 1 /4 rated load. Turn the GAlN screw on the
Controller clockwise until the Actuator becomes
5. Place Run/Stop/Remote switch in Run position to
unstable (hunts). It might be necessary to nudge the
start the genset.
Actuator lever by hand to cause it to begin hunting.
Back off the adjustment until operation is again
6. Adjust the right stop screw on the mechanical gov-
stable.
ernor to obtain a frequency of 72 Hz (2,160r/min) for
60 Hz gensets (62 Hz [I860 rlmin] for 50 Hz
11. Stop the genset and wait for 30 seconds to allow the
gensets). It might be necessary to loosen the left
turbo to coast down (if equipped). Restartthe genset
stop screw depending on direction of adjustment.
and check for speed overshoot. If the genset has an
overspeed shutdown, check the linkage for binding
7. Adjust the left stop screw to just take up the slack,
and make necessary repairs.
then tighten the locknut. Be careful not to bind the
shaft by setting the screw too tightly.
12. Restart the genset and check for frequency and
stability under various loads. Correct as necessary.
8. Stop the genset and attach the governor rod to the
throttle lever. Start the genset and operate without
13. Stop the genset and remove tachometer or fre-
load. Adjust the SPEED screw on the Controller to
quency meter if previously attached. The electronic
obtain 60 Hz or 50 Hz as appropriate.
governor is now calibrated.
Many troubleshooting procedures present hazards that can result in severe personal injury or
1 - 1should perform service
death. Only qualified service personnel with knowledge of fuels, electricity, andmachinery hazards
procedures. Review safety precautions on page ii.
/
1
r ~ c t u a t o hunts
operation.
r during r ~ i n k a bearings
I
~e sticking or binding.
I
Lubricate or replace.
I
i-- Improper governor adjustment
- -
See Calibration section for
adjustment.
Many troubleshooting procedures present hazards that can result in severe personal injury or
@@&%I death. Only qualifiedservice personnel with knowledge of fuels, electricity, andmachinery hazards
should perform service procedures. Review safety precautions on page ii.
2. Apply power to the Controller and If Actuator does not get to full
momentarily connect the Actuator lead to fuel, check Actuator leads. If
Terminal 4 (-). Actuator should go to full fuel voltage is less than specified,
position, and DC voltage (between terminals check for loose or poor
3 (+) and 4 (-) should be greater connections to battery.
than 80% of supply.
FAN SPACER
BLOWER
AIR INLET
GUARD
LOCKWASHER
BLOWER \
fi BACKING
ISOLATOR
RUBBER
ISOUTORS v
CONE RETAINERS
OUTER
CIRCUMFERENCE
HOLES
9-21
This section consists of the wiring diagrams referenced 10-Light DC Control-Pages 10-6 and 10-7
in the text. It should be noted that they are typical, and
that wiring and component specifications are subject to 7-Light DC ControCPages 10-8 and 10-9
change. Contact your Distributor if you do not have the 12-Light DC ControCPages 10-10 and 10-1 1
applicable wiring diagrams.
Voltage Regulator Installation and Generator
The following drawings are included: Reconnections-Page 10-12
AC Control without Meters-Page 10-2 Generator Reconnections (Model QS)-Page
AC Control with Meters-Page 10-3 10-13
4-Light DC Control-Pages 10-4 and 10-5 Engine Monitor PC Boards-Page 10-14.
LEFT SIDE DOOR (REAR I N S
.
5 . SEE VOLTAGE REGULATOR INSTALLATION FOR CONNECTIONS
.
TO VR2 1 CB2 1 AND TB2 1
WITHOUT METERS
10-2
WIRING DIAGRAM
LEFT SIDE DOOR BACK WALL O F CABINET RIGHT SIDE DOOR NOTES:
(REAR I N S I D E VIEW) ( I N S I D E VIEW) (REAR I N S I D E VIEW) I . A L L CCMPCNENTS SHOMN I N GE-ENERGIZED POSITICN.
10-6
STARTER
CONFIGURATION
18-5
c n ~ a t m~ ; b - ~ .ab-
=
I
P C P
a + a b - m
C f
+
P P f
L C
P C P C 4 P f 4
o w o w o w m o w
2 1 2 1
, ,
W W
a a
n n I
+ 3
YD & UC GENERATORS FOR QS MODELS
18 -
- 518 -
18 -
518
L z L z
3 PHASE RECONNECTABLE I PHASE RECONNECTABLE
LI
TI
LO
LO
LO
-8
-9 19 I1 I
12
L3 L2
NOTES :
3. CONTROL
THESE CONNECTIONS ARE FOR SPEC E " L " WITH THE STANDARDIZED
1- VOLTAGE CODE
10-13
-
18 -
518 18 518
- -
L z L z
3 PHASE RECONNECTABLE I PHASE RECONNECTABLE
l T I
VOLTAGE CODE
CONT
INPUT
TR9, 1 1 1
SECONDARY NRRENT TRANYCX1VER CCNV 1 ~ 2
NOTES:
3 . THESE CONNECTIONS ARE FOR SPEC E " L " WITH THE STANDARDIZED
CONTROL
12-LIGHT DC CONTROL WIRING DIAGRAM, SHEET 1
10-10
d
cr3
WC3
I-H
cr LL
az
I-0
(/I 0
I G N I T I O N SYSTEM
STARTER
CONFIGURATION
i2VDCI24VDC
A1 I-TB1-3
ALTERNATOR C O N F I G U R A T I O N S
12 V O L T / 2 4 V O L T
MOTOROLA
10-7
WIRING D I A G R A M
. . .
10-4
ZONE 5 - B , C , D
==-
10-3
Onan Corporation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
612-574-5000
Telex: 275477
Fax: 612-574-8087