SECTION 16251 Automatic Transfer Switches
SECTION 16251 Automatic Transfer Switches
SECTION 16251 Automatic Transfer Switches
SECTION 16251
AUTOMATIC TRANSFER SWITCHES
16251-1
05-01M
16251-2
05-01M
16251-3
05-01M
16251-4
05-01M
b. Where used with molded case circuit breakers or power air circuit
breakers with long-time and instantaneous trip, transfer switch
withstand and closing rating shall equal or exceed the available
short circuit current shown on the drawings, but shall not be less
than the following:
16251-5
05-01M
1. Operating Mechanism:
a. Actuated by an electrical operator.
b. Electrically and mechanically interlocked so that the main contact
cannot be closed simultaneously in both normal and emergency
position.
c. Normal and emergency main contacts shall be mechanically locked in
position by the operating linkage upon completion of transfer.
Release of the locking mechanism shall be possible only by normal
operating action.
d. Shall not include a neutral position.
e. Contact transfer time shall not exceed six cycles.
f. Do not use as a current carrying part. Components and mechanical
interlocks shall be insulated or grounded.
2. Contacts:
a. For switches 400 amperes and larger, protect main contacts by
separate arcing contacts and magnetic blowouts for each pole. Arc
quenching provisions equivalent to magnetic blowouts will be
considered acceptable.
b. Current carrying capacity of arcing contacts shall not be used in
the determination of the transfer switch rating, and shall be
separate from the main contacts.
c. Main and arcing contacts shall be visible for inspection with
cabinet door open and barrier covers removed.
3. Manual Operator:
a. Capable of operation in either direction under no load.
b. Capable of operation by one person.
c. Provide a warning sign to caution against operation when
energized.
4. Replaceable Parts:
a. Include the main and arcing contact individually or as units,
relays, and control devices.
b. Switch contacts and accessories are to be replaceable from the
front without removing the switch from the cabinet and without
removing main conductors.
5. Sensing Relays:
a. Provide voltage-sensing relays in each phase of the normal power
supply.
16251-6
05-01M
16251-7
05-01M
//G. In-Phase Band Monitor: Monitor shall control the operation of the
transfer switch. It shall monitor the voltage and frequency of the
normal and emergency voltage //.
H. Auxiliary Relay: Provide an auxiliary pre-signal relay on all automatic
transfer switches, which will feed elevator loads for use as elevator
control.
2.4 TRANSFER SWITCH OPERATION
SPEC WRITER NOTE: Use Paragraphs A, B, and
C for single transfer switch
installations, and paragraphs D, E, F, G
and H for multiple transfer switch
installations.
//A. A voltage decrease in one or more phases of the normal power source to
less than 70 percent of normal shall initiate the transfer sequence. The
transfer switch shall start the engine-generator unit after a time delay
of two or three seconds to permit override of momentary dips in the
normal power source. The time-delay shall be field adjustable from zero
to fifteen seconds.
B. The transfer switch shall transfer the load from normal to emergency
source when the frequency and voltage of the engine-generator unit have
attained 90 percent of rated value.
C. The transfer switch shall retransfer the load from emergency to normal
source upon restoration of normal supply in all phases to 90 percent or
more of normal voltage, and after a time delay. The time delay shall be
field adjustable from five to twenty-five minutes (preset for twenty-
five minutes). Should the emergency source fail during this time, the
transfer switch shall immediately transfer to the normal source whenever
it becomes available. After restoring to normal source the generator
shall continue to run for five minutes unloaded before shut down. Time
delay shall be adjustable from zero to fifteen minutes. //
//D. Engine Start: A voltage decrease, at any transfer switch, in one or more
phases of the normal power source to less than 70 percent of normal
shall start the engine-generator unit after a time delay of two to three
seconds. The time delay shall be field adjustable from zero to fifteen
seconds.
E. Transfer to Emergency (Emergency System Loads): Transfer switches for
emergency system loads shall transfer their loads from normal to
16251-8
05-01M
16251-9
05-01M
16251-10
05-01M
16251-11