User - Manual GW-DLMS-232-SL7 - 5.102 - en
User - Manual GW-DLMS-232-SL7 - 5.102 - en
User - Manual GW-DLMS-232-SL7 - 5.102 - en
P/N: GW-DLMS-232-SL7
Edition 2.0
MARCOM SRL
Phone +390458204747
Email: [email protected]
Via Mezzacampagna 52 (int. 29)
www.marcomweb.it
Revision Sheet
Revision Sheet
Release Date Revision Description
No.
Rev. 0 10/05/14 User’s Manual Template and Checklist
Rev. 1 10/06/16 Conversion to new format
Rev. 2 26/02/17 New HomeDLMS page
Rev. 3 15/05/18 Meter configuration
Rev. 4 20/05/18 New hardware configuration pages.
Rev. 5 04/06/19 New user login
Rev. 6 03/07/19 Unit of measure table
TABLE OF CONTENTS
Page #
DLMS (Device Language Message Specification) Protocol is used in meters field and specifically in
electric Energy meter to readout consumption and other values. The reference standard is EC 62056.
This standard defines services which permit to read objects, OBIS defined. Inside these objects are
mapped running meter values using standard profiles.
By Gateway DLMS-MODBUS is possible to read DLMS energy meter’s data using MODBUS RTU or
MODBUS TCP protocol. The gateway is completely transparent to DLMS protocol, so user must know
only Modbus protocol.
This Gateway version reads data from up to two counters through the RS232 ports and provides value
to RS485 port MODBUS RTU slave and on an Ethernet port Modbus TCP Server (up to 3 client
connections).
1.2.1 Connections
To view the web pages containing the data read from the counter you need to connect to the network
using the Ethernet RJ45 port available on the gateway. By a web browser, just type the default address
192.168.0.122.
In case of connection failure ensure that you have on your network card address on a subnet
192.168.0.X.
This brings us to the main screen of the Gateway with the values common to all Meter
From this page, through the links at the top of the page, you can browse web pages that contain the
data for the single Meter or go on the configuration pages of the Gateway (Home PLC).
In order to activate communication with energy meter user must insert in proper field Serial code Meter
x the serial numbers of connected meters.
It’s possible to change baud rate of the port connected to meter from Serial port baud rate selection
in case meter works with speed different from 9600 that usually is standard.
Time between readouts can be set from 10 to 3600 seconds.
String debug is useful to understand the communication with meters.
With GATEWAY REBOOT button you can force the gateway to reboot.
The confirmation of the changes is recorded using the Submit button.
To change the gateway settings, such as IP address, you need access to the configuration pages
through the link HomePLC in the header of web pages that contain the data read from the counters.
The Home page summarizes the main information concerning the gateway as the serial and with the
navigation bar on the left you can move between the pages.
Credentials to login and modify parameters are: Username = User, Password = UserDlms.
Changes in gateway settings are applied to the gateway after a power reboot.
To change the parameters of the serial connections (baud rate, parity) and ethernet, such as the IP
address, just go to the Devices page and, by clicking on the gear icon for the selected port, a popup will
open with the settings.
To change the modbus node of the RTU or TCP server, open the Protocols page and modify the
parameters of the desired interface.
The data read from the meters are placed in the Holding Register area.
A copy of the values is also present in the 4x20000 holding register area.
Refresh time of the values is approximately: Time between readouts * N, where N is the number of
energy meters connected to gateway and configured with a serial number different from zero in
HomeDLMS.
Modbus addresses in the table are base 1; depending on used Modbus master, sometimes is required
to swap words to read data correctly.
COM 0 COM 1
0 4x41046 4x41086 UDINT 1.8.0 Active Energy - Import - Total
1 4x41048 4x41088 UDINT 1.8.0* Active Energy - Import - Total - previous period
2 4x41050 4x41090 UDINT 2.8.0 Active Energy - Export - Total
3 4x41052 4x41092 UDINT 2.8.0* Active Energy - Export - Total - previous period
4 4x41054 4x41094 UDINT 5.8.0 Reactive Energy Q1 - Total
5 4x41056 4x41096 UDINT 5.8.0* Reactive Energy Q1 - Total - previous period
6 4x41058 4x41098 UDINT 8.8.0 Reactive Energy Q4 - Total
7 4x41060 4x41100 UDINT 8.8.0* Reactive Energy Q4 - Total - previous period
8 4x41062 4x41102 UDINT 6.8.0 Reactive Energy Q2 - Total
9 4x41064 4x41104 UDINT 6.8.0* Reactive Energy Q2 - Total - previous period
10 4x41066 4x41106 UDINT 7.8.0 Reactive Energy Q3 - Total
11 4x41068 4x41108 UDINT 7.8.0* Reactive Energy Q3 - Total - previous period
The order of magnitude of the units of measurement of the values read by the meter can change during
the life of an electric meter, therefore the following table shows the modbus addresses of the
multiplicative factor of the energy torches: 0 = Kilo, 1 = Mega, 2 = Giga.
COM 0 COM 1
0 4x41300 4x41320 UINT 1.8.0 Active Energy - Import - Total
1 4x41301 4x41321 UINT 1.8.0* Active Energy - Import - Total - previous period
2 4x41302 4x41322 UINT 2.8.0 Active Energy - Export - Total
3 4x41303 4x41323 UINT 2.8.0* Active Energy - Export - Total - previous period
4 4x41304 4x41324 UINT 5.8.0 Reactive Energy Q1 - Total
5 4x41305 4x41325 UINT 5.8.0* Reactive Energy Q1 - Total - previous period
6 4x41306 4x41326 UINT 8.8.0 Reactive Energy Q4 - Total
7 4x41307 4x41327 UINT 8.8.0* Reactive Energy Q4 - Total - previous period
8 4x41308 4x41328 UINT 6.8.0 Reactive Energy Q2 - Total
9 4x41309 4x41329 UINT 6.8.0* Reactive Energy Q2 - Total - previous period
10 4x41310 4x41330 UINT 7.8.0 Reactive Energy Q3 - Total
11 4x41311 4x41331 UINT 7.8.0* Reactive Energy Q3 - Total - previous period