Interbus-S S1 381-0343xx
for
DCE Control & Power Units
Emhart Teknologies
TUCKER GmbH, Max-Eyth-Straße 1, 35394 Gießen
Tel.: 0641/405-0; Fax: 0641/405-383; Mail: [email protected]
DCE Customer Interface Interbus-S S1 381-0343xx
F/O to
X501 H502 H501 central CPU
H403
24V
+24V
+5V +24V Customer Interface Interbus-S
E 110 381x B362x
H207
IBS State
J203 H102 H101
H201
J202
X203
[:]J101 8 - DIP - 1
H308 H301
Indication LED’s
State Interbus-S
H201 CC - Cable Check
H202 BA - Bus Active
H203 RD - Remote Bus Disabled
H204 FO1 - Diagnostics range f/o interface incomming
H205 FO2 - Diagnostics range f/o interface outgoing
H206 TR - Transmit/Receive (PCP active)
H207 Ul - Status SUPI3 (LED remains lit = Interbus active)
DIP 7 Changing the point in time for the generation of the WC signal (FK).
OFF Æ WC is generated directly after the weld.
7 - Output byte 0
8 - Output byte 1
9 - Output byte 2
10 - Output byte 3
11 - Output byte 4
12 - Output byte 5
Function Jumpers:
J101 - Standard open (only for flash programming in BSL mode)
Connection plugs:
X203 - External diagnostic Interbus
X502 - Power supply 24V outputs for external units (e. g. for f/o converter)
Configuration Interbus-S:
ID-Code # Interbus: 0x03 (general subscribers with digital I/O’s)
Protocol Interface:
Data length: Process data: 3 words input / 3 words output
The bus-transfer of the bytes of an data word is effected in the order High-Byte -
Low-Byte.
SOW
Weld cycle
WIP WOP
Weld complete *
Inside tolerance
SOW
Weld complete *
Inside tolerance
No fault
Restart
Weld cycle with fault, receipt with “Forced WC“ Weld cycle with fault, receipt with “Reset fault“
SOW
Weld cycle
FAULT FAULT
Weld complete
Inside tolerance
No fault
Forced WC
Reset fault
SOW
Weld cycle
WIP WOP
Weld complete *
Inside tolerance
SOW
Weld cycle
FAULT
Weld complete *
Inside tolerance
No fault
Rest fault
* The point in time for the generation of the WC signal depends upon DIP switch 7
Maintenance counter
For preventive maintenance of the collets warning signals are generated by the
customer interface. When 80 % and/or 98 % of the maximum programmed value is
reached, the corresponding output signals are activated.
The reference value in this respect is the value set in the DCE for the welding
quantity counter, at which the DCE generates a fault. For the respective output this
value is set in the "Programming maintenance counter" menu under the point "Fault
at" (see also "DCE programming instructions").
Outlet: X ----------------
Programming output.<↓>
The value set under the point "Collet warning" is of no significance for the generation
of the warning signals at the customer interface.
By means of the reset inputs "Reset service life counter" the corresponding welding
quantity counters in the DCE are set to zero irrespective of their current value. Thus
any imminent warning signals of the DCE and the customer interface are also reset.
Example:
Setting Collet warning at 2000
Collet fault at 3000
• After 2000 welds the DCE generates the maintenance warning
"Maintenance collet".
• After 2400 welds (80 % of 3000) the signal "80 % service life reached" is
activated.
• After 2940 welds (98 % of 3000) the signal "98 % service life reached" is
activated.