X10 User Manual
X10 User Manual
X10 User Manual
EARTH LEAKAGE
RELAY
USER MANUAL
PREFACE
Before You Start
Please read this manual thoroughly before installation, operation and
maintenance of the relay.
Disclaimer
Mikro shall not be liable for errors contained herein including any
incidental and/or consequential damages arising from the use of this
material. Mikro also reserves the right to vary the product from that
described in this material without prior notice.
Precautions
Please observe the following safety precautions before and during the
installation of the relay:
Do not perform megger, hi-pot or any high voltage stress test with the
relay connected to the system.
Please note that incorrect installation may impair the operation or even
damage the relay. There is no user servicable part in the relay. Tamper-
ing with it may damage the relay, result in injury and also voiding any
warranty.
I
CONTENTS
Preface ....................................................................................... I
Contents ..................................................................................... II
1. Introduction
1.1 Symbols and Definition ................................................... 1
1.2 Case Dimension ............................................................... 2
2. Installation Guide
2.1 Mounting ......................................................................... 3
2.2 Rear Termination Description ......................................... 4
2.3 Wiring .............................................................................. 5
3. Front Panel
3.1 Description ...................................................................... 6
3.2 Keypad ............................................................................ 7
3.3 LEDs ................................................................................ 7
4. Menu
4.1 Default Display ............................................................... 8
4.2 Main Menu ...................................................................... 9
4.3 Sub Menu ........................................................................ 10
4.3.1 MEASUREMENT Menu ................................... 10
4.3.2 RECORDs Menu ................................................ 10
4.3.2.1 Fault Record ....................................... 10
4.3.2.2 Event Record ...................................... 11
4.3.3 CONFIGURATIONS Menu ............................... 12
4.3.3.1 Op Parameter Menu ............................ 12
4.3.3.2 Date and Time Menu .......................... 12
4.3.3.3 Group Select Menu ............................. 13
4.3.3.4 Display Menu ..................................... 13
4.3.3.5 List of Parameters Displayed During
Display Scroll ..................................... 14
II
4.3.4 PROTECTION G1/G2 Menu ............................. 15
4.3.4.1 In1 Prot Menu ..................................... 15
4.3.4.2 In2 Prot Menu ..................................... 16
4.3.5 INPUT Menu ...................................................... 16
4.3.5.1 Input 1 ................................................. 16
4.3.5.2 Input Function .................................... 16
4.3.6 OUTPUT Menu .................................................. 17
4.3.6.1 Relay1 ................................................. 17
4.3.6.2 Relay2 ................................................. 17
4.3.7 COMMUNICATION Menu ............................... 18
5. Password .................................................................................... 19
6. Alarm ......................................................................................... 20
8. MODBUS
8.1 Modbus Protocol ............................................................ 24
8.2 Modbus Functions .......................................................... 25
8.3 Modbus Registers ........................................................... 27
8.4 Modbus Event Record .................................................... 31
8.5 Modbus Alarm Record ................................................... 33
8.6 Modbus Fault Record ..................................................... 34
8.7 Modbus Mapping Format ............................................... 35
III
1. Introduction
The purpose of this manual is to provide information necessary to
install, operate and maintain the X10 earth leakage relay. It has two
configurable output relays, one IRF relay, one configurable logic input
and MUST operate together with Mikro’s ZCT. Using the front panel
keys, the user can easily navigate through the user-friendly menu, read
measurements, status and change settings. The alarm/trip records are
displayed on the back-lit LCD. There is a RS485 port on the rear termi-
nals. Using MODBUS-RTU protocol, most information can be read or
modified through the serial communication port.
In this manual and on the relay, unless otherwise specified, the follow-
ing symbols and abbreviations shall apply throughout:-
1
1.2 Case dimension
Front
96mm
View
96mm
Side
90mm
View
20mm 105mm
2
2. Installation Guide
2.1 Mounting
Cut a square hole on the panel. The recommended hole size is 91mm x
91mm. Insert the relay through the pre-cut hole.
− 0.5mm
Panel
Cutout
91 +
91 +
− 0.5mm
Slide the retainer clip along the slots on both sides of the relay until the
relay is tightly secured on the panel. The retainer clips can be removed
by lifting the tab lightly at the handle end.
Upper and
bottom slots
Retainer
clips
3
2.2 Rear Terminal Description
4
2.3 Wiring
(Note 1)
1
5 RL1:
Earth
Uaux 2
4 Trip contact
L3
L2
L1
N
6 RL2:
7 Programmable
8 contact
ZCT
(Note 2) 14 RL3:
15 IRF contact
16
10
11 Digital Input 1
(Note 3)
24
23 +
20 Termination
shunt trip Resistor
or + 19
contactor
18
RS485
17
(Note 4)
LOAD X10 Communication
cable shield
Note 1: The EARTH wire must not pass through the ZCT
Note 2: The relay must work together with Mikro’s ZCT
Note 3: External series resistor 18k ohm, 2W is required for input
voltage greater than 94Vac or 132Vdc
Note 4: Short terminals 18 and 20 for commnication data lines
termination. Applicable only for relays located at the head and
tail ends of the communication lines
5
3. Front Panel
3.1 Description
Trip ALARM
b g
c h
ESC i
d
CLEAR TEST/
e RECORD
f x10 j
k
f. Model no
6
3.2 Keypad
Keypad Description
ESC a) To exit from menu and submenu (Note 5)
b) To cancel setting value change
UP a) Scroll up the menu
b) Increase the setting value
DOWN a) Scroll down the menu
b) Decrease the setting value
ENTER a) To enter submenu
b) To confirm setting value change
CLEAR a) To clear/reset the user resettable alarm
b) When the alarm record is empty, press to scroll
through dedicated parameter. (Note 5)
TEST/ a) To display alarm records.
RECORD b) To display successive records, press the RECORD
key again.
c) If there’s no alarm, press and hold the RECORD key
key for 5 seconds to run the test function
Note 5: Press and hold either the ESC or CLEAR keys for 1.5 seconds
to return to the default display from any submenu. Subsequent press the
CLEAR key to scroll through the real-time relay status and active group
of protection setting. Refer to section 4.3.3.4 for more details.
3.3 LEDs
7
4. Menu
4.1 Default Display
ENTER
Page 0 Leakage Refer to 4.2
12mA
ESC
UP DOWN
Page 1 ESC Output 1 2 3
001
UP DOWN
Page 2 ESC Input 1
0
UP DOWN
Page 3 ESC Date* 12/03/2013
Time* 08:05:30am
Page 3: Displays real-time date and time. Date and time format is
configurable. Refer to section 4.3.3.2 for more information.
8
4.2 Main Menu
Default Display
UP DOWN
ESC ENTER
1. MEASUREMENTS Refer to section 4.3.1
ESC
UP DOWN
ESC ENTER
2. RECORDS Refer to section 4.3.2
ESC
UP DOWN
ESC ENTER
3. CONFIGURATION Refer to section 4.3.3
ESC
UP DOWN
ESC ENTER
4. PROTECTION G1 Refer to section 4.3.4
ESC
UP DOWN
ESC ENTER
5. PROTECTION G2 Refer to section 4.3.4
ESC
UP DOWN
ESC ENTER
6. INPUT Refer to section 4.3.5
ESC
UP DOWN
ESC ENTER
7. OUTPUT Refer to section 4.3.6
ESC
UP DOWN
ESC ENTER
8. COMMUNICATION Refer to section 4.3.7
ESC
9
4.3 Sub Menu
Whenever a leakage fault trips, the event is recorded in the fault record.
The information about the fault type, fault current, date, time and the
protection setting at the time of trip is recorded.
The user can view the details of the fault record by navigating to the
desired record and pressing the ENTER key followed by the UP or
DOWN key to scroll through the details of the record or the ESC key
back to fault display.
10
ENTER
In1 Trip [2] 12/03/2014
08:05:30am A B
ESC
UP DOWN UP DOWN
ESC Active Group ESC In Thres
Group 1 30mA
UP DOWN UP DOWN
ESC Frequency Set ESC Time delay
50Hz 0.10s
UP DOWN UP DOWN
ESC In Sensing ESC In Trip
RMS 33mA
UP DOWN
A B
Whenever any event happened to the relay, the event is recorded in the
event record. The information about the type of event, event status, date
and time is recorded. User can view the event date and time by pressing
the ENTER key or press the ESC key to return.
ENTER
Relay 1 [2] 12/03/2014
Latched 08:05:30am
ESC
11
4.3.3 CONFIGURATIONS Menu
3.CONFIGURATION ENTER 3.1 Op Parameter ENTER Refer to section
4.3.3.1
ESC ESC
UP DOWN
ENTER
3.2 Date & Time Refer to section
ESC 4.3.3.2
UP DOWN
ENTER
3.3 Group Select Refer to section
ESC 4.3.3.2
UP DOWN
ENTER
3.4 Display Refer to section
ESC 4.3.3.2
12
Display Description
Time Set the time (hh:mm:ss)
Time Format Set the time format for display. For the 12-hours
format, am/pm is added immediately after the
seconds’ digit
13
4.3.3.5 List of Parameter Displayed During Display Scroll:
Display Description
Leakage Real-time protection current display
Output Real-time output contact physical status
Input Real-time input port physical status
Date, Time Real-time display the current date and time
Frequency Nominal frequency setting
Sensing Protection sensing current setting
Active Group Active protection group setting
In1 Prot? In1 protection enable status setting
In1 Trip Rst In1 protection trip reset method setting
In1 Thres In1 protection threshold setting
In1 Time Dly In1 time delay setting
In1 Alrm? In1 protection alarm enable status setting
In1 Alrm Rst In1 alarm reset method setting
In1 Alrm Thres In1 alarm threshold setting
In2 Prot? In2 protection enable status setting
In2 Trip Rst In2 protection trip reset method setting
In2 Thres In2 protection threshold setting
In2 Time Dly In2 time delay setting
In2 Alrm? In2 protection alarm enable status setting
In2 Alrm Rst In2 alarm reset method setting
In2 Alrm Thres In2 alarm threshold setting
14
4.3.4 PROTECTION G1/G2 Menu
15
4.3.4.2 In2 Prot Menu
In2 Prot menu has a similar content as the In1 Prot menu. It is
applicable to the second set of the protection settings.
4.3.5.1 Input 1
Display Description
Ip1 Func Sets function of Input 1. Refer to section 4.3.5.2
for details
Ip1 Type Selects the input port 1 activation logic. Active
High is when voltage is applied to the input termi-
nals. Active Low is when input terminals are open
Aux timer Sets the auxiliary tripping timer. Only configu-
rable if the input function is set to Aux
16
4.3.6 OUTPUT Menu
4.3.6.1 Relay 1
Display Description
Failsafe Sets rhe relay activation logic:
No (Normal), Yes (Inverse)
Reset Sets the relay reset method:
Manual (latched), Auto (Unlatched)
Trip function
ZCT fault? Assigns the ZCT fault trip to RL1 (Note 7)
In1 trip? Assigns the In1 trip to RL1 (Note 7, 8)
In2 trip? Assigns the In2 trip to RL1 (Note 7, 8)
Pnl tst trip? Assigns the front panel test trip to RL1 (Note 7)
Ip tst trip? Assigns the input test trip to RL1 (Note 7)
Rem trip? Assigns the remote command trip to RL1 (Note 7)
Aux trip? Assigns the Aux input trip to RL1 (Note 7)
4.3.6.2 Relay 2
Display Description
Failsafe Refer to section 4.3.6.1
Reset Refer to section 4.3.6.1
Trip function
ZCT fault? Assigns the ZCT fault trip to RL2
In1 trip? Assigns the In1 trip to RL2 (Note 8)
17
In2 trip? Assigns the In2 trip to RL2 (Note 8)
Pnl tst trip? Assigns the front panel test trip to RL2
Ip tst trip? Assigns the input test trip to RL2
Rem trip? Assigns the remote command trip to RL2
Aux trip? Assigns the Aux input trip to RL2
Alarm function
In1 alrm? Assigns the In1 alarm to RL2
In2 alrm? Assigns the In2 alarm to RL2
Block alrm? Assigns the blocking alarm to RL2
Setting Assigns the setting conflict alarm to RL2. Hap-
conflict? pens when the protection group setting is set to
input but the input port is not assigned to this
function. Refer to sections 4.3.3.3 and 4.3.5.1 for
more details
18
5. Password
Password Protection
Relay settings can be viewed anytime but locked from being changed.
A password is required for changing the settings. The password consists
of four digits. The factory default password is 0000.
The programming mode is indicated with the letter “P” on the right
hand side of the display. The letter “P” remains displayed as long as
the password is active. This mode is exited if no key is pressed for 2
minutes.
Password Entry
The password is requested as soon as the modification of a parameter
is initiated. The user enters each one of the 4 digits by using the UP or
DOWN key and validates each digit by pressing the ENTER key. If
the ESC key is pressed in between, the password entry is terminated.
The display returns to the point of the preceding menu. Press the EN-
TER key again to modify the setting. If no key is pressed after 2 min-
utes, the settings are locked. A new password request must be initiated
for any subsequent setting change.
Changing Password
To change the password, go to the Op Parameter Password menu.
Enter the current password to unlock, after which the display shows
the current password. Press the ENTER key again to enter the new
password.
19
6. Alarm
Alarm Type
Alarms are divided into two categories: user resettable and non-
resettable types.
For the user non-resettable type, the alarm is self reset by the relay once
the alarm condition is removed.
For the user resettable type, the user must ensure the cause of the
alarm is removed before the alarm can be cleared.
Eg: To clear “ZCT fault” alarm, the user must resolve the hardware
ZCT connection problem before the alarm can be cleared.
Alarm Condition
During an alarm condition, the alarm LED blinks and the alarm record
pops up. Press any key to acknowledge the alarm. Once acknowledged,
the alarm LED will be changed to continuous on.
Alarm Viewing
Press the RECORD key once. Press the RECORD key again to view
successive records. Alternatively, in the alarm, press the UP or DOWN
key to scroll through the records.
Alarm Clearing
To clear a single alarm, use the RECORD key to navigate to the desired
alarm and press the CLEAR key. To clear all records, use the RECORD
key to navigate until the display shows “Clear all alarm?” and press
the CLEAR key.
20
7. Technical Data
PROTECTION
Setting group Group 1 or Group 2
Setting sub-group In1 or In2
Frequency 50Hz or 60Hz
Current sensing True RMS or Fundamental
EARTH LEAKAGE PROTECTION
Leakage? Yes or No
Sensitivity setting 30mA, 0.05 to 1.00A (step=0.05A),
1.00 to 10.0A (step=0.25A)
Time delay setting Instantaneous, 0.1-3.0s (step=0.1s)
ALARM
Alarm? Yes or No
Alarm reset Manual or Auto
Alarm threshold 50-80% (step=5%)
TEST
Test Panel key, input port, remote command
MISCELLANEOUS PROTECTION
Blocking logic Yes or No
Auxiliary trip Yes or No
Auxiliary timer 0 to 600s (step=0.01s)
RECORDS
Alarm records Up to 30 records
Event records Up to 250 records
Fault records Up to 50 records
COMMUNICATION
Hardware interface Isolated RS485
Protocol Modbus-RTU
ID 1 to 255
REAL-TIME LEAKAGE CURRENT DISPLAY
Range 10mA to 12.0A
ZERO PHASE CURRENT TRANSFORMER (ZCT)
ZCT type Mikro standard type ZCT
21
AUXILIARY POWER SUPPLY
Rated voltage 100~240VAC or 140~340VDC
Operating voltage 85~265VAC or 110~370VDC
Rated frequency 50 or 60Hz
Power consumption 6VA max
INDICATORS
Display 2x16-digit LCD
Trip Red indicator
Alarm Yellow indicator
LOGIC INPUT
Input type Optically isolated
Rated voltage 50-270VAC or 20-380VDC
External series resistor 18k ohm, 2W
required for voltage greater than 94VAC
or 132VDC
OUTPUT CONTACT
Rated voltage 240VAC
Contact arrangement Change-over
Continuous carry 5A, AC1
Expected electrical life 50,000 operations at rated load
Expected mechanical life 5,000,000 operations
MECHANICAL
Mounting type Front panel flush mounting
Dimension (mm) 96W x 96H x 125L
Enclosure protection IP63 at panel. IP30 at body
Approximate weight 0.6kg (excluding ZCT)
TEMPERATURE
Pollution degree 2
Operating temperature -100C to +550C
Storage temperature -200C to +700C
Humidity 5% to 95%, non condensing
22
PRODUCT REFERENCE STANDARD
IEC 60947-2 Annex M
ELECTROMAGNETIC COMPATIBILITY
IEC 61000-4-2 8kV, air discharge
Electrostatic discharge 8kV, contact discharge
IEC 61000-4-3 10V/m, 80MHz to 1GHz
Radiated RF immunity
IEC 61000-4-4 4kV power port
Electrical fast transient 2kV signal port
IEC 61000-4-5 4kV power port
Surge 2kV signal port
IEC 61000-4-6 10Vrms, 0.15 to 80MHz
Conducted RF immunity
IEC 61000-4-8 100A/m, 1s
Power frequency magnetic
IEC 61000-4-11 100% 200ms
Voltage interruption
IEC 61000-4-18 2.50kV common mode
Damped oscilatory wave 1.25kV differential mode
CISPR 11 0.15-30MHz, 56-66dB
Conducted emission
CISPR 11 30-230MHz, 30dB, 10m
Radiated emission 230-1000MHz, 37dB, 10m
SAFETY TEST
IEC 60255-5 2kV high voltage dielectric test
Insulation 5kV high voltage impulse test
ENVIRONMENT
IEC 60068-2-6
23
8 MODBUS
8.1 MODBUS Protocol
The RS485 port is located at the rear terminals and uses the MODBUS
-RTU protocol. The communication setting is set in the COMMUNI-
CATION Menu from the front panel or RS485 port. When changes
are made through the RS485 port, modifications are restricted to the
communication protocol registers or addresses ranging from 0211h
to 0214h. The changes take place immediately after the acknowledge
message is sent.
Items (b) & (c) can only be modified through the front panel. Reading
the password register will always return 0000h.
Prior to writing data to the database, the user MUST ensure that the
relay front panel access password is not active. Otherwise, the data
write is void. The front panel access password status can be checked by
reading the database interlocking bit on the relay status register or bit
10 of address 0010h. Reading of the database registers is not affected.
24
8.2 MODBUS Functions
25
Error
Communication address 1 byte 1 to 255
Error code 1 byte 0x90
Exception code 1 byte 0x01 or 02 or 03 or 04
CRC 2 bytes 2-byte CRC
26
8.3 MODBUS Registers
27
Addr Parameter For- Unit Range
(Hex) mat
0206 Year F7 year 0-199 (as 2xxx)
month, 1-12, 1-31
0207 Month, Day F10
day
0208 Hour, Minute F11 hour, min 0-23, 0-59
0209 Milliseconds F7 ms 0-59999 (0-59.999s)
Date: 0-1,
020A Date & time format F12 data, time
Time: 0-1
020B Change group by... F13 --- 0=menu, 1=input
020C Setting group F6 --- 0=Grp1, 1=Grp2
020D LCD backlight on time F7 minute 1-60
LCD backlight 0=low, 1=medium,
020E F6 ---
brightness 2=high
Clear key to scroll
020F F6 --- 0=No, 1=Yes
setting
0210 Communication? F6 --- 0=No, 1=Yes
0=2400, 1=4800,
0211 Baudrate F7 bps 2=9600, 3=19200,
4=38400
0=none, 1=odd
0212 Parity F6 ---
2=even
0213 Stop bits F6 --- 0=1bit, 1=2bits
0214 MODBUS address F6 --- 1-255
0215 Password F1 --- 0000 (read only)
0216 Remote set parameters F6 --- 0=No, 1=Yes
0217-
Reserved --- --- ---
023F
level, 0-1,
0240 Input 1 function F14
option 0-6
0241 Input 1 reset option F18 Bit field Bit: 0-2
0242 Input 1 Aux delay F8 1/100sec 0-60000 (600s)
0243-
Reserved --- --- ---
026F
28
Addr Parameter For- Unit Range
(Hex) mat
0270 RL1 function F17 Bit field Bit: 0-1
0271 RL1 trip options F16 Bit field Bit: 0-6 (read only)
0272-
Reserved --- --- ---
0274
0275 RL2 function F17 Bit field Bit 0-1
0276 RL2 trip options F16 Bit field Bit 0-6
0277 RL2 alarm options F15 Bit field Bit 0-3
0278-
Reserved --- --- ---
027F
Protection Group 1. Read/Write. Function 03h, 04h, 06h or 10h
0300 Leakage 1 (In1)? F6 --- 0=Disable, 1=Enable
0301 In1 trip reset F6 --- 0=Manual, 1=Auto
0302 In1 sensitivity F9 mA 30-10000 (0.03-10A)
0303 In1 time delay F8 ms 0-3000 (step=100)
0304 In1 alarm? F6 0=Disable, 1=Enable
0305 In1 alarm reset F6 0=Manual, 1=Auto
0306 In1 alarm threshold F7 % 50-80 (step=5)
0307 Reserved --- --- ---
0308 Leakage 2 (In2)? F6 --- 0=Disable, 1=Enable
0309 In2 trip reset F6 --- 0=Manual, 1=Auto
030A In2 sensitivity F9 mA 30-10000 (0.03-10A)
030B In2 time delay F8 ms 0-3000 (step=100)
030C In2 alarm? F6 0=Disable, 1=Enable
030D In2 alarm reset F6 0=Manual, 1=Auto
030E In2 alarm threshold F7 % 50-80 (step=5)
031F Reserved --- --- ---
Protection Group 2. Read/Write. Function 03h, 04h, 06h or 10h
0400- Same as Protection Group 1 except addresses are 04xx instead
041F of 03xx
Addresses 0000-001F, 0210, 0215, 0216 and 0271 are read only. Writ-
ing on them has no effect.
29
Addr Parameter For- Unit Range
(Hex) mat
Fault Records. Read only. Function 03h or 04h
1000 Fault record 1
: :
1031 Fault record 50
Event Records. Read only. Function 03h or 04h
2000 Event record 1
: :
20F9 Rvent record 250
Alarm Records. Read only. Function 03h or 04h
3000 Fault record 1
: :
301D Fault record 30
30
8.4 MODBUS Event Record
31
Word number 5: Word number 6:
Code Code Description Data Description
22 Default data 0=Alarm cleared 1=Alarm pickup
23 Setting conflict 0=Alarm cleared 1=Alarm pickup
24 Calibration data error 0=Alarm cleared 1=Alarm pickup
25 ADC error 0=Alarm cleared 1=Alarm pickup
26 EEPROM error 0=Alarm cleared 1=Alarm pickup
27 RTC data lost 0=Alarm cleared 1=Alarm pickup
28 RTC error 0=Alarm cleared 1=Alarm pickup
29 Synchronise clock --- ---
30 Group change 0=Active grp 1 1=Active grp 2
31 Frequency change 0=50Hz 1=60Hz
32 Panel data change Address of setting being changed
33 Remote data change Address of setting being changed
34 Password reset 0=Local 1=Remote
35 Acknowledge alarm 0=Local 1=Remote
32
8.5 MODBUS Alarm Records
Each alarm record consists of 6 words:
Word Description Format Units Range
1 Year F7 year 0-199 (as 2000-2199)
2 Month,day F10 month, day 1-12. 1-31
3 Hour, minute F11 hour, min 0-23, 0-59
4 Milliseconds F7 ms 0-59999
5 Record code See below
6 Reserved Reserved
Alarm Record Code
Word number 5: Word number 6:
Code Code Description Data Description
1 In1 alarm ---
2 In2 alarm ---
3 ZCT fault ---
4 In1 trip Trip fault current
5 In2 trip Trip fault current
6 Panel button test trip ---
7 Input test trip ---
8 Remote command trip ---
9 Aux trip ---
10 Blocking alarm ---
20 Relay 1 ON ---
21 Relay 1 latched ---
22 Relay 2 ON ---
23 Relay 2 latched ---
24 IRF relay OFF ---
25 Watchdog reset ---
26 Calibration data error ---
27 ADC error ---
28 EEPROM error ---
29 RTC data lost ---
30 RTC error ---
31 Firmware updated ---
32 Default data ---
33 Setting conflict ---
Alarm codes 32 and 33 are non-resettable. Others are resettable.
33
8.6 MODBUS Fault Records
34
8.7 MODBUS Mapping Format
Code Description
F1 2 bytes ASCII character
F2 Unsigned integer - Relay status.
Bit 0: EEPROM data failure
Bit 1: Calibration data failure
Bit 2: RTC data lost
Bit 3: RTC error
Bit 4: ADC error
Bit 10: Modbus database registers interlocking status
Bit 11: Rear port (RS485) unread fault record
Bit 14: Rear port (RS485) unread alarm record
F3 Unsigned integer - LED status.
Bits 0-1: Trip LED (1=ON, 2=blink)
Bits 2-3: Alarm LED (1=ON, 2=blink)
F4 Unsigned integer - Input status.
Bit 0: Input 1 (0=Open, 1=Closed)
F5 Unsigned integer - Output status.
Bit 0: Relay 1 or Trip contact (0=Off, 1=On)
Bit 1: Relay 2 or Programmable contact (0=Off, 1=On)
Bit 2: Relay 3 or IRF contact (0=Off, 1=On)
F6 Unsigned integer - Miscellaneous.
A numeric value representation of certain options or func-
tions. Refer to the ‘range’ column of the register for details
F7 Unsigned integer - A numeric value of certain units.
Refer to the individual register ‘Unit’ and ‘Range’ for details
E.g. 50 may represent 50% or 50 seconds
F8 Unsigned integer - A scaled numeric of certain units
Refer to the individual register ‘Únit’ and ‘Range’ for details
E.g. 125 may represent 1.25A or 12.5s
F9 Unsigned integer - Sensitivity setting and the unit is mA.
Valid data: 30, 50-1000 (step=50), 1000-10000 (step=250)
E.g. 500 is 500mA or 2000 is 2.0A
35
Code Description
F10 Unsigned integer.
High byte: month
Low byte: day
F11 Unsigned integer.
High byte: hour (24-hour format).
Low byte: minute
F12 Unsigned integer - Date and time format for relay display.
High byte: Date format. 0=DD/MM/YYYY;
1=MM/DD/YYYY
Low byte: Time format. 0=12 hours; 1=24 hours
F13 Unsigned integer - Change Group by...
0=Change group by menu
1=Change group by level of digital input
F14 Unsigned integer - Input function.
High byte - integer data
0: Active low or when no power is applied
1: Active high or when power is supplied to the input port
36
Code Description
F16 Unsigned integer - Relay trip status.
Bit 0: ZCT fault
Bit 1: In1 trip
Bit 2: In2 trip
Bit 3: Panel button test trip
Bit 4: Input test trip
Bit 5: Remote command trip
Bit 6: Aux trip
F17 Unsigned integer - Relay operation status.
Bit 0: Latch status (0=manual/latched, 1=auto/unlatched)
Bit 1: Failsafe function (0=No, 1=Yes)
F18 Unsigned integer - Input reset option.
Bit 0: Alarm reset
Bit 1: Trip reset
Bit 2: Output contact reset
F19 Unsigned integer - remote command.
High byte:
1: Reset alarm/trip
2: Acknowledge alarm/trip
3: Reset display to default menu page
6: Remote trip
10: Delete alarm record
Low Byte:
For high byte=3, set to display page 0-3, refer to section 4.1
for the page assignments, .
For high byte=10, 0=delete all record, n=delete record n
37
38
(423468-T)
No. 1, Jln TP7/7, Sime UEP Industrial Park,
40400 Shah Alam,
Selangor Darul Ehsan,
Malaysia
Tel: +603-51927155
Fax: +603-51927166
Website: www.itmikro.com
E-mail: [email protected] 1.00