High Voltage Testing Measurement Equipment Catalog
High Voltage Testing Measurement Equipment Catalog
High Voltage Testing Measurement Equipment Catalog
EQUIPMENT CATALOG
high voltage
testing equipment
high voltage
testing equipment
high voltage
testing equipment
KEP Power Testing Ltd. aims to deliver quality High Voltage testing equipment
to the utilities, testing service companies, electrical contractors and large industrials
worldwide.
Our wide product range includes technically advanced, portable Test Van
solutions for integral HV maintenance, as well as easy to use products for High
Voltage testing, diagnostics, evaluation, and preventive maintenance testing
of electrical substation apparatus, power cables, and other objects designed to
operate under medium to high voltage conditions.
All our equipment is designed and manufactured according to Quality
Management System based on ISO 9001 standard, certified by Intertek plc., while
the in-house ISO/IEC 17025-certified calibration laboratory is ensuring the accuracy
of supplied apparatus.
Keeping in touch with our customers around the world, permanently combined
with market analysis and quick response to its changes makes KEP well-equipped
for developing progressive solutions for wide variety of customer needs.
www.kep.ua 1
high voltage
testing equipment TABLE OF CONTENTS
PRODUCTION FACILITIES..........................................................................................4
VEHICLE-BASED SYSTEMS
General overview ..................................................................................6
ETL-8V Compact vehicle-based systems..........................................8
ETL-40V Vehicle-based systems....................................................... 10
ETL-80V Vehicle-based systems....................................................... 14
COMPACT SYSTEMS
SWG-12/1100R Portable cable fault location system................ 16
STANDALONE EQUIPMENT
RIF-9 Digital impulse reflectometer................................................. 18
LFG-50, LFG-200 Low-frequency generator ............................... 20
PT-14 Tracer, P-900 Ground microphone ................................... 22
Cables for HV testing........................................................................ 23
2 www.kep.ua
high voltage
TABLE OF CONTENTS testing equipment
OIL TESTERS
OLT-80A Oil tester............................................................................................ 32
OLT-90A Oil tester............................................................................................ 32
OLT-100A Oil tester......................................................................................... 32
OLT-80M Oil tester........................................................................................... 32
OLT-90M Oil tester........................................................................................... 32
OLT-100M Oil tester........................................................................................ 32
C-80, C-100 Oil tester calibrator ................................................................. 35
Tangens-3M Oil dissipation factor meter................................................ 36
RESONANT TESTING SYSTEMS
UIG-25/50/70-180, UI-15/225 ................................................................. 37
UIG-35/70/100-750, UIG-35/70/100-800........................................... 38
PACKAGE..................................................................................................................... 40
DEALERS..................................................................................................................... 42
www.kep.ua 3
high voltage
testing equipment PRODUCTION FACILITIES
4 www.kep.ua
high voltage
PRODUCTION FACILITIES testing equipment
TURNING AND MILLING USING CNC TURNING AND MILLING USING CNC MILLING USING CNC
SF6 FILLING
HV COILS WINDING TRANSFORMERS WINDING STEEL SHEET CUTTING EQUIPMENT
ENGINEERING TEAM
www.kep.ua 5
high voltage
testing equipment
General overview
Discription
The new generation of KEP Vehicle-based systems for main parameters as well as a set of auxiliary equipment,
cable testing and fault locating provides you with high- which is delivered with the system, are object to change
efficient, safe and reliable work on all kinds of LV and MV upon customer's request.
cables used in power networks.
We always consider individual customer needs, thus
Safety
Our customer's safety is our first priority. KEP cable HV and LV connectors are made in a way to prevent
fault locating systems are built to meet all essential safety their wrong connection.
standards. As a base all our vehicle-based systems have: • Rear doors monitoring
• Earthing monitoring The system always monitors whether the rear doors
All systems have safety earthing, operational earthing of the vehicle (high-voltage compartment) are closed
and auxiliary earthing. The independent GCU-3 module firmly. If the responsible sensors return fault the system is
performs a permanent monitoring of resistance between stopped immediately.
safety earthing and operational earthing as well as a • Overvoltage protection
voltage between safety earthing (chassis) and auxiliary
earthing. System will be stopped if these parameters Inputs of a Time-Domain Reflectometer have
exceed the tolerance limits. overvoltage protection 400V CAT IV.
System base
Compact systems can be based on vehicles of a size Furniture options as well as auxiliary equipment (air
similar to VW Caddy. Full-size systems can be based on conditioner, additional heater, etc.) installed according to
vehicles of a size similar to Mercedes Sprinter. customer’s demands.
Vehicles for:
compact systems full-size systems
Application
The ETL-8V is an compact vehicle-based system,
which is used for the following purposes:
• Cable testing up to 8 kV DC
• Cable faulty place burning
• Fault prelocating using Time‑Domain
Reflectometer RIF‑9 working in:
• TDR mode
• Arc-Reflection mode
• Impulse Current Mode
• Voltage coupling mode
• Precise pinpointing with ground microphone
• Cable route tracing (optional).
Technical specifications
Parameter Value
GENERAL parameter
Input voltage, V 230 ± 23
Frequency, Hz 50 ± 1
Power consumption, kVA, max 1.0
TEST MODE
Output DC voltage range, kV 0–8
Output DC current range, mA 0 – 10
BURN MODE
Output DC voltage range, kV 0–8
Output DC current range, mA 0 – 100
SURGE MODE
Technical specifications
Parameter Value Parameter Value
Flexible voltage change during
GENERAL parameter
automatic operation
Input voltage, V 230 ± 23 Pinpointing with an acoustic
Frequency, Hz 50 ± 1 receiver
Power consumption, kVA, max 2.0
PRELOCATION MODE
TEST MODE
TDR / Arc reflection/
Output DC voltage range, kV 0 – 40 Methods Impulse current/
Output DC current range, mA 300 Voltage coupling
Automatic distance measuring
BURN MODE Saving cable parameters into
Output DC voltage range, kV 0 – 20 Reflectometer non‑volatile
Output DC current range, A 1 memory
Saving reflectograms either
SURGE MODE to Reflectometer non-volatile
4 / 8 / 16 / 32 memory or USB flash drive
Ranges, kV
(8 / 16 / 32) CABLE TRACING MODE
2000
Output energy, J, max Cable tracing using 50W audio-
(at each range)
frequency generator with
Timer set (automatic surge
5 – 15 frequencies 491/ 982/ 8440 Hz
mode), seconds
with a receiver
Manual single surge
Prelocation
The digital impulse reflectometer RIF-9, which is
a part of ETL-40 system, provides you with a precise
cable fault prior locating. The 10-inch color display with
a touchscreen makes it easier to navigate RIF-9 menu
and operate it.
RIF-9 is made in a shock- and dustproof plastic case
with a transporting belt. Its internal battery makes it
possible to use it as a standalone device for not less
than 8 hours.
Application
The ETL-80V is a modular system, which is used
for the following purposes:
• DC cable testing up to 80 kV
• Converting high-resistive cable faults into low-
resistive with a use of burn generator
• Prelocating faulty places with a use of Time
Domain Reflectometer RIF‑9
• Cable route tracing with a use of 200 W low-
frequency generator and receiver
• Precise pinpointing using a surge wave generator
with a ground microphone
Technical specifications
Parameter Value
GENERAL parameter
Input voltage, V 230 ± 23
Frequency, Hz 50 ± 1
3.0 (3.5 for 40A burn gener-
Power consumption, kVA, max
ator)
TEST MODE
Output DC voltage range, kV 0 – 80
Output DC current range, mA 0 – 580
BURN MODE
Output DC voltage range, kV 0 – 20
Output DC current range, mA 0 – 40
SURGE MODE
DC voltage ranges, kV 4 / 8 / 16 / 32
Description
The high-voltage unit of the system provides
with high-power up to 1100 Joules surges at 3; 6 and
12 kV ranges. At each range, the output voltage is
smoothly adjustable. The rate of surge waves can be
smoothly adjusted. The single manual shot option is
also included. The DC output mode is provided for
quick fault diagnostics. The 100 mA burn mode is
available.
Digital impulse reflectometer (TDR) RIF-9
provides you with 10.4-inch bright high-contrast
TFT display with touchscreen. The 800 × 600 pixels
resolution makes the picture sharp. The touchscreen
allows an operator navigate through the menu
fast and easy. An alternative way of navigation
is included. It is provided with a control knob.
RIF-9 integrates a multiple ways of fault includes software for PC (optional), which allows
prelocation. It can be used either as a standalone working with saved reflectograms. The firmware
device in TDR mode or in a conjunction with can be easily updated through USB interface by
HV‑module, working in arc reflection mode. inserting a flash drive.
RIF-9 has USB interface. The package content
Technical specifications
GENERAL parameter Value TDR parameter Value
Input voltage, V 230 ± 23 Distance measurement ranges, m @ 60/120/ 250/ 500/1000/2000/5000/
Frequency, Hz 50 ± 1 v/2 = 100 m/µs 10000/20000/50000/120000
Power consumption, kVA, max 1.0 0.5 @ v/2 = 100 m/µs
Resolution, m
Dimensions (W × H × D) , mm 731 × 1120 × 533 0.4 @ v/2 = 80 m/µs
Net weight, kg 113 Sampling rate, MHz 200
Gain, dB -33 – 104
HV-module parameter Output impedance (10 Ω steps), Ω 10 – 500
TESTING MODE Propagation velocity (v/2), m/µs 50.0 – 150.0
Output DC voltage, kV 0 – 12 Averaging reflectograms number, max 64
Output DC current, mA 1 / 10 Time domain accuracy 0.2 % of FS
BURNING MODE Pulse amplitude, V 45
Output DC voltage range, kV 0 – 12 Pulse width, ns 10 – 100 000
Output DC current range, mA 0 – 100 TDR (reflection measurement)
Operation modes
ARC (arc-reflection)
SURGE MODE Control Touchscreen and control knob
Ranges, kV 3 / 6 / 12 Connectivity RS-485, USB
3 – 15 or Internal data storage 4 Gb (not less than 1000
Surge rate, s single shot reflectograms with data)
Max. output energy, J 1100 Display 10.4”, 800 x 600 TFT, touch-sensitive
Package contents
Component Quantity
SWG-12/1100R 1
Bag for cables 1
User manual 1
Connecting cables set (may vary on
6 m each
customer’s demand)
Accessories
Bag for cabels
Component Quantity
LFG-50 Audio frequency generator 1
P-900 Surge wave locator set 1
Application
Battery powered digital impulse reflectometer
(TDR) RIF-9 designed for determining the distance
to a fault in communication and power cables.
Digital impulse reflectometer RIF-9 allows:
• Determining the distance to a fault or
discontinuity in symmetric and asymmetric
cables using a location (time domain reflection)
method
• Measuring the length of a cable (including those
wound on a drum) or distance to a fault or a short
circuit
• Storing and processing the results of
measurements both internally or using a supplied
PC software
• As part of a Cable Test Van, determining the
distance to a fault or discontinuity in cables with
length of up to 100 km for all possible fault types
without the need of preliminary full cable sheath
burning
Description
• RIF-9 provides you with 10.4-inch bright high-
contrast TFT display with touchscreen. The 800
× 600 pixels resolution makes the picture sharp.
The touchscreen allows an operator navigate
through the menu fast and easy. An alternative
way of navigation is included. It is provided with
a control knob.
• RIF-9 integrates a multiple ways of fault
prelocation. It can be used either as a standalone
device in TDR mode or in a conjunction with
HV-module (e.g. Cable test van or Surge wave
generator), working in arc reflection (ARC),
impulse current (ICE) and decay modes. A high-
capacity internal battery allows working up to 8
hours.
• RIF-9 has both RS-485 and USB interfaces.
The package content includes software for PC
(optional), which allows working with saved
reflectograms. The firmware is easily updated
through USB interface by inserting a flash drive.
Technical specifications
Parameter Value
Distance measurement ranges, 60 / 120 / 250 / 500 / 1000 / 2000 / 5000
m @ v/2 = 100 m/µs 10000 / 20000 / 50000 / 120000
Resolution, m 0.5 @ v/2 = 100 m/µs
0.4 @ v/2 = 80 m/µs
Sampling rate, MHz 200
Gain, dB -33 – 104
Output impedance (10 Ω steps), Ω 10 – 500
Propagation velocity (v/2), m/µs 50.0 – 150.0
Averaging reflectograms number, max 64
Time domain accuracy 0.2 % of FS
Pulse amplitude, V 45
Propagation velocity (v/2) resolution, m/us 0.1
Pulse width, ns 10 – 100 000
Operation modes TDR / ARC / ICE / Decay
Control Touchscreen and control knob
Connectivity RS-485, USB
4 Gb (not less than 1000
Internal data storage
reflectograms with data)
10.4”, 800 x 600 TFT,
Display
touch-sensitive
12 V (8 hours of operating
Internal battery
when fully charged)
Input 230 V 50 Hz
External power adaptor
Output 24 V DC
Power consumption, W, max 36
Dimensions (W × H × D), mm 366 × 178 × 270
Net weight (with internal battery), kg 8.0
Description
LFG-50 is a 50 W low-frequency generator with
ability to inject a signal of three frequencies via direct
connection to an object or via internal transmission loop
antenna, which is built-in a cover lid. Basic frequencies are
491, 982 and 8440 Hz. There are options of using a single-
frequency or multi-frequency signals at the output.
The power of LFG-50 output signal can be adjusted
up to 50 W with 2.5 W steps. This signal can be transmitted
constantly or broken into separate blocks of 50 % duty
cycle with 1 s repetition rate.
A load matching is made automatically. Main
parameters, such as output power, load impedance,
selected frequency are shown on OLED display. If a load
is higher than 1000 Ω LFG‑50 automatically switches
into output voltage setting mode. The output overload
protection will trip, when operating on short-circuit loops
(lower than 0.5 Ω).
Package contents
Component Quantity
LFG-50 1
Soft case 1
Power cable 1
Signal connecting wires 2
“Crocodile” connectors 3
User manual 1
Fuse 10 A 4
Fuse 1 A 1
LFG-200P
Specifications
Value
Parameter
LFG-50 LFG-200P
491 / 982 / 8440
Operating frequencies, Hz
(other - on request)
Max. Frequencies count, operated simultaneously 3
Output power range, W 0 – 50 0 – 200
Output power regulating step, W 2.5 10
Frequency selection manual
Operating modes continuous / pulse
Loop impedance matching range, Ω 0.5 – 1000
Maximum output voltage (RMS), V 300 600
Loop impedance matching mode auto
Measured parameters ranges:
output voltage, V RMS 0.1 – 300 0.1 – 600
output current, A RMS 0.01 – 9.99
resistance, Ohm 0.5 – 1000
phase angle, º 0 – 90
pulse duty cycle, % 50
Measurement error, %, of FS 5
Pulse repetition frequency, Hz 1
Internal battery:
type LiFePO4 –
operating voltage, V DC 12 –
battery life, hours not less than 1 –
average charging time, hours 3 –
Power supply:
input voltage, V 230 ± 10 %
input voltage frequency, Hz 50
power consumption from mains, VA, max 100 400
External power source (not included):
voltage, V 12 – 14
current, А, not less 8
Dimensions (W × H × D), mm 366 × 227 × 270 460 × 380 × 190
Net weight, kg, max 8 15
Application
Fast and accurate search for power cables and other
communications, identification of coating defects and the
depth, followed by mapping.
Technical specifications
Parameter Value
Operating frequencies, Hz 491 / 982 / 8440
Bandwidth:
RADIO mode, kHz 10 − 36
ONLINE mode, Hz 48 − 10 000
Sensitivity, μV 1
Track depth meas. error, %, max 5
Dimensions, mm 700 × 300 × 140
Net weight, kg, max 2.4
Ground
microphone P-900
Application
Ground microphone P-900 should be used with an auxiliary frequency You can also try to use it virtually
generator of 1024 ± 2 Hz / 2048 ± 2 Hz and no less than 200 W of output from our web-site (Adobe Flash
power at the load range from 0.5 to 200 Ohms (e.g., LFG-50) when searching Player required)
using the inductive method.
Technical specifications
Parameter Value
Sensitivity at max / min amplification 20 uV / 500 mV
Pass band (-3 dB) in “1024Hz” / ”2048Hz”
10 / 12
mode, Hz
Pass band in audio frequency mode, Hz 20 – 2200
Power source 5 АА × 1.2 V NiMh
Duty time, hours 16
Dimensions (W × H × D), mm 180 × 70 × 120
Net weight (batteries included) 0.65
Application
Flexible silicone frostproof high-voltage cables KEP-100, KharkovEnergoPribor as a means of testing and detecting
KEP-70 and KEP-70p are suitable for high-voltage testing both cable faults are are both supplied with flexible silicone
as part of ETL vans and separately, as well as for use in the frostproof highvoltage cables, which retains its flexibility at the
measuring circuits of tgδ insulation (KEP-12t). temperatures as low as minus 40˚С.
Сable test vans ETL-40V and ETL-80V made by
KEP-100 cable
cross section
Protective silicone
rubber sheath
KEP-100
Synthetic fiber
Screen
(tinned copper S = 4.0 мм2)
Semiconductive layer
Main insulation
silicone rubber
Semiconductive layer
KEP-70
Core (flexible tinned
copper S =4.0 mm2)
KEP-70p
Main insulation
silicone rubber
Semiconductive layer
Semiconductive layer
Screen
(100% aluminium foil) Cable drums for KEP-70
cables
PVC insulation
Core (flexible tinned
copper wire S =0.5 mm2)
Application
VLF-60 Cable Insulation Tester made by KEP is a very under test, which is non-destructive to insulation of
low frequency high potential tester that ensures efficient proper quality, but is enough to detect cable faults.
testing and fault location on medium voltage cables. Compared to DC cable testing, which can be damaging
Very low frequency (VLF) testing involves applying to good insulation, VLF testing does not have such a
frequency in the range of 0.01 to 0.1 Hz to the cable detrimental effect on the cable being tested.
Technical specifications
Parameter Value
Output Voltage
Sinusoidal 0 – 62 kV peak / 0 – 44 kV RMS
DC ± 0 – 60 kV
Squarewave 0 – 60 kV
Accuracy ±1%
Resolution 0.1 kV
Output Curent
Sinusoidal (RMS) 26 mA
DC / Squarewave 40 mA
Accuracy ±1%
Resolution 1 μA
0.01 – 0.1Hz in steps of 0.01 Hz (default 0.1 Hz) – auto
Output Frequency
frequency selection
1 μF @ 0.1 Hz @ 44 kV RMS
5.0 μF @ 0.01 @ 44 kV RMS
Output Load
10.0 μF max capacitance (at lower frequency
and Voltage)
Output Modes
VLF AC Sinewave
VLF AC Squarewave
DC (positive or negative polarity)
Vacuum Bottle Test Mode (DC)
Cable Jacket / Sheath Testing
Sheath Fault Location
Breakdown Mode
Fault Condition Mode
Fault Trip Mode
Metering
Voltage and Current True RMS and / or peak
Capacitance 0.1 nF to 20 μF Range
Resistance 0.1 MΩ to 20 GΩ
Real time oscilloscope display of actual
Waveform
output voltage waveform
50 / 60 Hz – 12 kV Feedback Protection /
Safety
Dual Discharge Device (internal)
Duty Cycle Continuous
Computer Interfaces USB, RS-485
Display Color touchscreen TFT 5.7 “ (115 × 86 mm)
Input Voltage (110 to 240) V AC ±10 %, 50 / 60 Hz
Consumption Power 1.2 kVA
Dimensions (H × W × D) 530 × 580 × 410 mm
Weight 60 kg
HVTS-70/50 HVT-70/50
Application
High-voltage testing system HVT and HVTS perform DC unit. High-voltage units of both HVT and HTVS can be
high-voltage testing of power cables (IEC 60502-2), power supplied with either transformer oil as an insulating material
cables accessories (IEC 61442) as well as AC high-voltage (HVU-L) or with sulfur hexafluoride as an insulating material
testing of switchgear, reclosers, dielectric insulators, high- (HVU-G). Thus, there are four modifications offered: HVTS +
voltage dischargers (arresters), busbars and other dielectric HVU-G, HVTS + HVU-L, HVT + HVU-L and HVT + HVU-G. We
materials with relatively low electric capacitance. recommend using either HVTS + HVU-G or HVT + HVU-L.
Both devices consist of a control unit and a high-voltage
Technical specifications
Value
Parameter HVTS-70/50 HVT-70/50
DC AC DC AC
Output voltage, kV, max 70 50 70 50
Output current, mA, max 25 25 (40*) 15 25 (40*)
Output voltage measuring range, kV 3 – 70 3 – 50 0 – 70 0 – 50
Output current measuring range, mA 1 – 25 1 – 40 0 – 15 0 – 40
Measurement uncertainty 3 % of reading 3 % of FS
Voltage raising rate, kV/s manual / 0.5 – 4 manual
Timer value, minutes, max 60
Bluetooth data transfering (optional)
Input voltage, V 230 ± 10 %
Frequency, Hz 50 ± 1
Power consumption, kVA, max 3.0
Control unit dimensions (W × H × D), mm 349 × 256 × 240
HVU dimensions** (W × H × D), mm 322 × 356 × 355 360 × 500 × 310
Control unit net weight, kg 14
HVU net weight**, kg 23 35
* - In a short duration mode (1 minute ON, 5 minutes OFF).
** - For HVTS-70/50 given size and weight HVU-G, for HVT-70/50 given size and weight HVU-L.
Technical data is an object to change without prior notification.
Functional features
Control unit features HVTS HVT
High resistance to external environmental influences. Casing with firmly closing cover which prevents
penetration of dust and moisture during the transportation and storage
Mobility. Supplied with a belt for easy transportation by a single person
Advanced protection and safety features. Emergency Stop button and grounding terminal on a front
panel. Indication of the actual voltage on the output HV terminal
Analog indicators. Control panel with two analog indicators for voltage and current measurement *
Overcurrent protection. Blocks output circuit if current exceeds the limit
Overvoltage protection. Blocks output circuit if voltage exceeds the limit
CE Compliant. Conforms to the EU Directives 2006/95/EC (LVD) and 2004/108/EC (EMC), which is proven
by independent tests at TRaC laboratories, UK
Improved precision. Ability to measure RMS values of both AC voltage and current irrespectively to the
crest-factor (True-RMS) thus greatly reducing the crest factor errors
High-contrast graphical display. Ability to control and adjust the unit using a context menu which an
operator can navigate by pressing keys located on both sides of display and reading the results on the
display. Display indicates measurement and auxiliary information during test procedure
Automatic testing mode. Automatic and manual testing modes. In AUTO mode the unit raises the voltage
at a pre‑set rate to a pre‑set voltage value, keeps the voltage on an object under test (OUT) for a certain time
and then drops the voltage slowly down to zero
Internal memory for test results storage. Ability to save up to eight presets for the most frequently used
test procedures. Ability to save measurement data history
Auxiliary protection. Blocking HVU-G output if insulating gas pressure is low or its temperature is high
You can also try to use it virtually from our web-site (Adobe Flash Player
required)
Application
The High-power high-voltage testers of HVTS-
HP series are designed for testing an insulation of
high-voltage cables and other non-liquid dielectric
materials with both AC and DC voltage up to 140 kV.
Typically this series includes testers which have
a test voltage 70 kV DC/50 kV AC 50 Hz and 100
kV DC/100 kV AC 50Hz. There are two common
modifications for each model mentioned above
which can bring output power value of 7.5 kVA and
17.5 kVA.
Any other special models, which have test
voltages up to 250 kV with a power of up to 40 kVA
are available on customer’s request.
Technical specifications
HVTS-HP HVTS-HP HVTS-HP HVTS-HP
Parameter
70/55-7.5 (17.5) 70/100-7.5 (17.5) 100/100-7.5 (17.5) 140/100-7,5 (17.5)
Output AC voltage, kV, max 55 100
Output DC voltage, kV, max 70 100 140
Output AC current, mA, max 130* (300*) 75* (175*)
Output DC current, mA, max 90 (200) 30 (65) 40 (90) 55 (125)
Output AC voltage measuring range, kV 3 – 55 3 – 100
Output DC voltage measuring range, kV 3 – 70 3 – 100 3 – 140
Output AC current measuring range, mA 1 – 130 (3 – 300) 1 – 75 (1 – 175)
Output DC current measuring range, mA 1 – 90 (3 – 200) 1 – 30 (1 – 65) 1 – 40 (1 – 90) 1 – 55 (1 – 125)
Measuring uncertainty, % 3 of reading
Interface languages Russian, English, (Turkish, Polish and other – on request)
Input voltage, V 230 ± 10 %
Frequency, Hz 50 ± 1 (60 – on request)
Output power, kVA, max 7.5 (17.5)
Parameters for a 17.5 kVA model of HVTS-HP are given in parenthesis.
The connectors for control unit connection Transporting position Operating position
Application
Automatic circuit breaker testers UPA are intended for automatic circuit breaker under the test. Power regulation
automatic AC current circuit breakers testing. The devices could be done either through an external voltage regulator
allow registering the values of the supplied current and timing (RNO or VR) or through a built-in thyristor controller.
the automatic circuit breaker switching interval. All metrological characteristics (current and time
UPA operate on the principle of varying the power in measurement) are valid if RNO is used, i.e. if the exit signal
the primary circuit of the matching power transformer and, waveform is stable (just as in other analogs).
respectively, varying the output current, flowing through the
UPA-10
UPA-3 (UPA-6)
(UPA-1) RNO-VT-80*
RNO-VT-20*
Current source 3 kА
(1 kА)
AC voltage regulators
from 20 A to 120 A are available
upon request
• RNO-VT-20 20A
• RNO-VT-40 40A
• RNO-VT-80 80A
• RNO-VT-120 120A
RNO-VT-40 RNO-VT-20
* - recommended voltage regulator for current UPA models (optional)
Technical specifications
Value
Parameter
UPA-1 UPA-3 UPA-6 UPA-10 UPA-16 UPA-20
one turn 0.1 – 1 1–3 1–6 1 – 9.99 3 – 16 3 – 20
two turns 0.05 – 0.5 0.5 – 1.5 – – 1.5 – 8 1.5 – 10
Output current measuring
three turns 0.03 – 0.33 0.33 – 1 – – 1 – 5.33 1 – 6.67
range in mode “kA” (RMS), kA
four turns 0.025 – 0.25 0.25 – 0.75 – – 0.75 – 4 0.75 – 5
five turns 0.02 – 0.2 0.2 – 0.6 – – 0.6 – 3.2 0.6 – 4
one turn 10 – 100 100 – 1000 100 – 999 200 – 4000
two turns 5 – 50 50 – 500 – – 100 – 2000
Output current measuring
three turns 3.3 – 33 33 – 330 – – 66.7 – 1333
range in mode “A” (RMS), A
four turns 2.5 – 25 25 – 250 – – 50 – 1000
five turns 2 – 20 20 – 200 – – 40 – 800
Measurement uncertainty (for A and kA), % 3 of FS
Circuit breaker switch off time 50 ms – 990 ms, ms ± 20
measuring uncertainty*: 1 s – 7200 s** , % 3 of reading
Max. time of uninterrupted work at max. current, s 10
Input voltage, V 230 ± 10 % 230 V / 400 V ± 10 %
Frequency, Hz 50 ± 1
Power consumption, kVA, max 5.5 33 55 55
Control unit dimensions (W × H × D), mm 347 × 140 × 210 660 × 985 × 480
542 × 360 × 200
Current source dimensions (W × H × D), mm 110 × 212 × 253 185 × 305 × 360
Control unit net weight, kg 3 110
47
Current source net weight, kg 16.7 56
* The given measurement uncertainty are true when operating a UPA with VR.
** The measurement of current feed duration over 10 s should be done at the current of not more than 1000 A. UPA-6, UPA-10
have 1 s - 990 s range.
UPA-16
(UPA-20)
RNO-VT-120*
OLT-80A OLT-80M
(OLT-90A) (OLT-90M)
(OLT-100A) (OLT-100M)
Online
Simulator
A-Series M-Series
Application
Oil testers are used for testing dielectric liquids with their breakdown voltage measuring. A-series of oil testers
works automatically, according with selected standard, which are preloaded.
Description
Both A and M series of oil testers bring out accurate and repeatable results of measured breakdown voltage. Fast
high-voltage switch off time makes it possible to carry out test of dielectric liquids, which are easily destroyed under
such influences.
The internal design of oil testers combined with a use of automatic high voltage breakers, cutting off supplied
voltage if tester’s lid has been opened during the test, provide operator with high level of safety.
Testers are fully equipped and are ready for operation right after unpacking. They come with a test vessel (IEC 60156
– basic configuration) with VDE 0370 mushroom-shape electrodes. A gap between electrodes is easily regulated with
a use of pass-no pass gauge, which comes in pack.
A-series provides with fully automatic test procedure according to selected standard (basically IEC 60156 and
GOST 6581 settings are preloaded). It has a built-in printer which is able to print a test report after procedure is done.
Test results are saved into non-volatile memory of oil tester. A PC-connectivity makes it easy to collect data from oil
tester, save and store them as well as print a fulfilled report. Test voltage is being measured directly on electrodes. This
fact combined with a true sine voltage shape (independent from supply voltage shape), increases repeatability and
accuracy of measurements.
M-series provides operator with ultra-simplicity of operation. It doesn’t require any presets. All you need is pressing
start button after a test vessel is loaded. Tester will show a breakdown voltage result immediately after breakdown
occurs.
Test vessel for this series goes with magnetic stirrer, which stirs a liquid between two measurements.
Technical specifications
Package contents
Quantity
Component
A-series M-series
OLT oil tester 1 1
Test vessel* IEC 60156 with electrodes
1 1
and cover
Go/No-Go gauge 1 1
Magnetic stirrer 1 N/A A-Series built-in printer
Lifting stick for magnetic stirrer 1 N/A
USB cable (A-B type) 1 N/A
Power cord (C-type plug.) 1 1
Stirrer
Grounding cable 1 1
Software on USB flash-drive 1 N/A
Fuses (250V/3A) 2 2
Paper roll (inside the printer) 1 N/A
Go/No-Go gauge
User’s manual 1 1
ISO/IEC 17025 calibration certificate
1 1
(optional, on Customer’s request)
C-80 (C-100) calibration kit (optional) 1 1
Lifting stick
* - Addititional test vessels are avaible on request
Application
The reference measuring cell C-80 (C-100)
is intended for AC voltage measurement on the
balanced transformers with the grounded midpoint
high-voltage terminals, which are used in OLT-series
oil testers.
The sell made as a mobile device with a built-in
battery.
Technical specifications
You can also try to use it
Value
Parameter virtually from our web-site
C-80 C-100 (Adobe Flash Player required)
Measured voltage, kV, RMS 10 to 80 10 to 100
Measurement uncertainty, % 1.0 of reading
Measured frequency, Hz 45 – 65
Voltage resolution, kV 0.01
Peak factor resolution, kV 0.01
Frequency resolution, Hz 0.01
Inter-electrode gap, mm 221 273
Input resistance, MΩ, min 600 700
Internal battery LiPO 3.7V
Charging supply voltage, V 9 – 12
Continuous run time on full charge,
4
hours
Consumption supply current, mA, max 50
Dimensions (W × H × D), mm, max 280 × 90 × 50 327 × 91 × 80
Net weight, kg, max 1.5
Application
A digital automatic dissipation factor
measurement apparatus Tangens-3M is
intended for taking measurements of the
transformer oil dielectric dissipation factor
according to IEC 60247 at 50 Hz frequency.
Technical specifications
Parameter Value
0.0001 − 1.0000
Dissipation factor (DF) measuring range
(0.01% − 100 %)
DF measuring accuracy ± (0.03 DF + 0.0002)
Resolution 0.00001
Output AC voltage, V RMS 1940 – 2060
Measuring uncertainty, % 2.5 of reading
Capacitance measuring range, pF 5 − 30
Testing temperature, °С 90
Temperature measuring accuracy, °С ±1
Measuring time for "Program 1"
35
(measuring at 70 °С and 90 °С), minutes
Measuring time for "Program 2"
(measuring at 70 °С, 80 °С and 90 °С on increasing
85
temperature and measuring at 90 °С, 80 °С and
70 °С on decreasing temperature), minutes
Input voltage, V 230 ± 10 %
Frequency, Hz 50 ± 1
Power consumption, kVA, max 0.3
Dimensions (W × H × D), mm 405 × 260 × 90
Weight (incl. package), kg, max 10
YAPI-3
Application
Resonance testers UIG are designed for testing The first option has a decreased initial value of
high voltage objects such as generator stator inductance due to mechanical changes to the
windings, busbars, cables insulation, etc. with an AC magnetic gap reactor. In the second option is based
voltage of an industrial frequency or with a rectified on changing the inductance of the bias magnetic
current voltage in semi-automatic and automatic DC reactor.
modes. Using the current resonance effect enables
UIG testers are developed based on the principle a significant reduction of a power consumption
of parallel resonance in an electrical circuit in (usually 40 times and more). Thus, it reduces voltage
which an object under the test acts as an electrical regulator power, a step-up transformer rated power
capacitance (the stator winding of the generator, as well allows for a smaller cross-section of cables.
track, etc.), and where an automatic inductance The resonance testers UIG support performing
changing is used for supporting the current full set of high-voltage tests for the high-power
resonance. For all voltage ranges, the resonance is generators.
maintained automatically. UIG testers are bespoke devices produced
Inductance change is done using a resonance according to the individually client's requirements.
reactor, which can have two structural variations.
Generalized specifications
Parameter Value
Output AC voltage in stator winding test mode, kV, max 30 – 501
Output AC voltage in bus test mode, kV, max 60 – 100
Output DC voltage in leakage current test mode, kV 85 – 140
Output AC/DC current, A, max 6 – 45
Measurement uncertainty (specified from 10 % of range to UIG-50-500
3
100 % of range), %
Output power, kVA, max 200 – 1500
Test object capacitance, µF, max 0.5 – 4
Duty cycle at full load (test / idle), minutes 20 / 40
Output test voltage rising speed (adjustible), kV/s 1
Input AC current, A 80 – 120
Input voltage, V 400 ± 10 %2 UIG-35/400
Frequency, Hz 50 ± 1
Power consumption, kVA 30 – 50
Typical dimensions (W × H × D), mm 1800 × 2200 × 1900
Weight, kg 1200 – 3500
1
- there are possible modifications with increased output voltage (up to 330 kV);
2
- for low-power apparatus It is possible to have mains voltage 230 V ± 10 %;
UI-25/50/70-180
UIG-35/70/100-300
UIG-35/70/100-300 UIG-35/70/100-300
40 www.kep.ua
high voltage
testing equipment
www.kep.ua 41
high voltage
testing equipment
DEALERS
CHINA
PD Technologies Limited
+852-3695-0998 www.pdtech.com.hk
Hong Kong , Block 1, Flat F, 16F., Kin Ho +852-3695-0999 [email protected]
Industrial Bldg., 14 Au Pui Wan Street, Shatin
EGYPT
Engineering Trade Office
www.electroeto.com
Cairo, 6 Abd El Kawy Ahmed street - El +2 (02) 3384-7711
[email protected]
Mohandseen - 12411
INDIA
MTekpro Technologies Private Limited
www.mtekpro.com
New Delhi - 110048, B-229, LGF, Greater +91 (11) 4152-12-45
[email protected]
Kailash Part-1
INDONESIA
Pt. Sinergi Sinar Abadi
+62 (813) 802-84622
Jakarta, Jl. Pancoran Timur III No.6 Perdatam [email protected]
+62 (821) 227-06844
Jakarta Selatan 12780
IRAK
Al Zaitoon Group Companies
+ 00 (964)-790-333-0-354 [email protected]
Irak, Basra, Al Jazair Street
IRAN
Niroonamad Khorasan Company
Mashhad, on the corner of 5th Kooshesh, +98 (51) 324-00-761 www.niroonamad.com
down of 11th Sanat, High Technologies
Industrial State
K AZAKHSTAN
TOO "Technosila-Kazakhstan"
(GK Energoskan) +7 (7172)-78-34-27 [email protected]
Astana, str. Beybitshilik 14, office 402
RUSSIAN FEDERATION
ALFA-ENERGY Ltd. www.alfaen.ru
+7 (495) 505-76-70
Moscow, str. 1-st Radiatorskaya, 3 [email protected]
Energoskan Ltd.
Moscow, str. Akademika Koroleva, 13, office +7 (495) 268-02-90 [email protected]
839
42 www.kep.ua
high voltage
DEALERS testing equipment
SOUTH AFRICA
NERM Applications and
Testing (Pty) Ltd. www.nerma.co.za
+27 (11) 894-23-26
Boksburg, 187 Dr Vosloo Road, N12 Business Park, [email protected]
Gauteng, 1460
SOUTH KOREA
Altus Corporation
+82 (0) 32-321-5075 www.altus.or.kr
Gyeonggi-do, RM 801-B, Richtown, 1080-1, Jung- +82 (0) 32-321-5076 [email protected]
dong, Wonmi-gu Bucheon-city
Sam-Young Tech
Gyeonggi-do, 505 (Bugun Plaza, Sang-dong), +82 (0) 32-324-2231 [email protected]
Giljuro77 beongil 61, Wonmi-gu, Bucheon-si
TURKEY
ELZ Enerji Elektrik Elektronik İnş. Malz. İth.
San. ve Tic. Ltd. Şti +90 (312) 354-7030 [email protected]
Ankara, Saray Mah. 213. Sok. No: 3/A Kazan 06980
UZBEKISTAN
"Vodiy ulgurji sanoat" Ltd. +998 (91) 342-92-09
[email protected]
Namangan, str. Navoi, 7 +998 (93) 499-00-55
VIE TNAM
Ha Long Inspection And Technical
Service J.S.C. www.haintec.com
+84 (4) 3537-8919
Hanoi, No.2, Quarter 46, Quan Hoa Ward, [email protected]
Cau Giay District
Measuring And Testing Equipment Co., Ltd. +84 (4) 3719-8669 www.mtcequipment.com.vn
Hanoi, 88 Au Co Street, Tay Ho Dist +84 (4) 3719-8659 [email protected]
www.kep.ua 43