Conduit Installation Manhours Per Linear Meter

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

CONDUIT INSTALLATION MANHOURS PER LINEAR METER

Sizes RSC PVC Pipes EMT / IMC

Concealed Exposed Concealed Exposed Installation Concealed


Installation Installation Installation Installation

1-Feb 0.217 0.188 0.195 0.169 0.182


3-Apr 0.266 0.23 0.239 0.207 0.218
1 0.272 0.236 0.245 0.212 0.231
l-1/4 0.273 0.2371 0.246 0.213 0.232
1/1/2002 0.326 0.282 0.261 0.225 0.238
2 0.435 0.376 0.326 0.282 0.296
2·1/2 0.607 0.526 0.547 0.473 0.358
3 0.802 0.695 0.602 0.521 0.474
3·1/2 0.851 0.737 0.638 0.553 0.476
4 1.155 1 0.866 0.75 0.647
5 1.579 1.367 1.184 1.025
6 2.041 1.766 1.53 1.324
MC Flexible Steel Conduit

Exposed Installation Concealed Installation Exposed


Installation

0.158 0.11 0.155


0.188 0.142 0.177
0.2 0.184 0.23
0.201 0.188 0.236
0.206 0.231 0.289
0.256 0.288 0.36
0.31 0.435 0.544
0.41 0.608 0.759
0.412 0.895 1.119
0.559
WIRE INSTALLATION MANHOURS PER LINEAR METER

AWG Metric Size Number of Core/Conducter per Cable


Size
2 3 4
16 1.0 mm2 0.039 0.052 0.072

14 2 mm2 0.043 0.056 0.079


12 3.5 mm2 0.049 0.066 0.089

10 5.5 mm2 0.072 0.089 0.105

8 8 mm2 0.085 0.102 0.118


6 14 mm2 0.095 0.108 0.131
4 22 mm2 0.115 0.131 0.157
2 30 mm2 0.121 0.141 0.167
1 38 mm2 0.138 0.157 0.164
1/0 50 mm2 0.174 0.2 0.239
2/0 60 mm2 0.203 0.233 0.282
3/0 80 mm2 0.236 0.272 0.325
4/0 100 mm2 0.276 0.318 0.38

250 MCM 125 mm2 0.295 0.341 0.407

300 MCM 150 mm2 0.312 0.358 0.43

350 MCM 175 mm2 0.328 0.377 0.453

400 MCM 200 mm2 0.361 0.417 0.499

500 MCM 250 mm2 0.384 0.443 0.528

750 MCM 400 mm2 0.518 0.597 0.715

1000 MCM 500 mm2 0.623 0.718 0.859


6
0.102

0.108
0.125

0.141

0.161
0.171
0.207
0.216
0.246
0.312
0.364
0.423
0.495

0.528

0.558

0.587

0.646

0.689

0.928

1.118