Alter TTB Drive For DC Motors With Field Control
Alter TTB Drive For DC Motors With Field Control
Alter TTB Drive For DC Motors With Field Control
THYRISTORS
THREE-PHASE CONVERTER
MODEL
TTB-M00
TTU-M00
Instruction book 91/094 – Revision 00 – Edition 02 – Date 25/05/2007
INDEX
1 SAFETY AND STANDARDS.................................................................................................................................3
1.1 Recall to the safety standards............................................................................................................................3
1.2 Safety general standards....................................................................................................................................3
1.2.1 Preliminary advice.......................................................................................................................................3
1.2.2 Operations of installation, startup and maintenance...................................................................................3
1.2.3 Power-supply sectioning device ..................................................................................................................3
1.2.4 Stop Function...............................................................................................................................................3
1.2.5 Emergency Stop............................................................................................................................................4
1.2.6 Unintentional starting and uncontrolled running........................................................................................4
1.3 Reference documents and standards.................................................................................................................4
1.4 Conformity to the CEE directives and CE marking.........................................................................................5
1.4.1 Advice...........................................................................................................................................................5
1.4.2 Declaration of conformity and marking......................................................................................................5
1.4.3 Application of other CEE directives............................................................................................................5
1.4.4 Declaration of the manufacturer..................................................................................................................5
1.5 Rating Plate and information for the technical support .................................................................................6
1.5.1 Rating plate of the converter........................................................................................................................6
1.5.2 Informative notes..........................................................................................................................................7
2 GUIDE FOR THE INSTALLATION....................................................................................................................8
2.1 Purpose and destination ....................................................................................................................................8
2.2 Recall of some definitions..................................................................................................................................8
2.3 Indications for the installation ........................................................................................................................9
2.3.1 General indications......................................................................................................................................9
2.3.2 Installation of the converter inside the electrical cabinet............................................................................9
2.3.3 Complete electric plant..............................................................................................................................10
2.3.4 Specific indications for the drives type TTB and TTU...............................................................................10
1CHARACTERISTICS OF THE DRIVES TYPE TTB AND TTU....................................................................13
3.1 Generality.........................................................................................................................................................13
3.2 Modes and limits of operation of the converters.............................................................................................13
3.2.1 Speed Control by Analog Tachogenerator.................................................................................................13
3.2.2 Speed Control by Armature Voltage..........................................................................................................14
3.2.3 Torque Control by the Armature Current..................................................................................................14
3.2.4 Master - Slave Interlocking........................................................................................................................15
3.3 Technical data..................................................................................................................................................16
3.3.1 General technical characteristics..............................................................................................................16
3.3.2 Supply.........................................................................................................................................................17
3.4 Commands, signaling, inputs and outputs (I/O).............................................................................................20
3.4.1 Switch (SW1)..............................................................................................................................................20
3.4.2 Signaling LED (green)...............................................................................................................................20
3.4.3 Alarm LED (red)........................................................................................................................................21
3.4.4 Test point of measure (T.P.).......................................................................................................................22
3.4.5 Regulation Trimmers..................................................................................................................................23
3.4.6 Analog inputs.............................................................................................................................................24
3.4.7 Analog outputs...........................................................................................................................................25
3.4.8 Common digital I/O...................................................................................................................................26
3.4.9 Digital inputs..............................................................................................................................................26
3.4.10 Digital outputs .........................................................................................................................................27
4 RUNNING SEQUENCES OF THE CONVERTER AND STARTUP..............................................................28
4.1 Starting Sequence ............................................................................................................................................28
4.2 Shutdown Sequence.........................................................................................................................................28
4.3 Startup..............................................................................................................................................................29
4.3.1 Synoptic picture of the operations.............................................................................................................29
4.3.2 Preliminary operations..............................................................................................................................29
4.3.3 Setting.........................................................................................................................................................30
4.3.4 Starting.......................................................................................................................................................30
4.3.5 Motor Running...........................................................................................................................................31
4.3.5.1 SPEED CONTROL BY TACHOGENERATOR...................................................................................31
4.3.5.2 SPEED CONTROL BY THE ARMATURE VOLTAGE.......................................................................32
WARNING! This symbol recalls the attention to a situation of danger that could also bring to serious
damages to the people (also potentially lethal) or to irreparable breakdowns to the
equipment or to the operated system. This is the level of more important alarm. It's
absolutely necessary to follow the instructions underlined with the symbols under brought.
Dangerous voltage: it signals the situations of danger owed from electric voltages.
WARNING!
Generic danger: it signals the situations of danger owed to different causes from the
electric voltage.
WARNING!
WARNING!
This personnel has to own the special documentation furnished by ALTER, particularly this instruction book.
For any reason the unqualified operator has to operate on the terminal block of the converter. Besides it is
necessary that the converter be preventively disconnected from mains, as specified on the point 2.3.4.5.
1.2.3 Power-supply sectioning device
Since the converter has built for being embedded on an electrical cabinet, containing
eventually also other equipments, the sectioning device for the command manual
feeding, required by EN 60204-1 §s 5.3.1, can be that common to the whole
electrical cabinet and it owes - in every case - must be inserts at the builder of the
WARNING! machine.
1.2.4 Stop Function
The stop functions, as prescribed on EN 60204-1 §s 9.2.2, particularly the 0
category stop, must be realized by the builder of the machine, in how much
inherent to the logic of machine, that obviously differs according to the type of
machine and following the instructions contained in this instruction book.
WARNING!
WARNING!
1.2.6 Unintentional starting and uncontrolled running
The motor connected to a drive type TTB and TTU can be started and stopped
utilizing the commands performed by the operator (please to see point 3.4). If it is
necessary to manually act on a mover controlled by the motor, to satisfy the
safety conditions for the operator, it is necessary not only to stop the motor by the
WARNING! command of the converter, but also to insulate the converter from the feeder line.
In fact the motor can to run without any command but only by cause of fault of the
electronic components or other accidental causes (breakdown on mains or on the
cables e/o connections, etc.). For the same causes, during the normal operation the
converter would be able not to run as described in this instruction book and could be
happen that the motor is fed by electric quantity not checked and therefore also the
speed and the direction of rotation of the motor are uncontrolled. The user owes
therefore to predispose additional protection e/o safety systems suitable to
prevent damages to people or things.
1.4.1 Advice
The converters model TTB and TTU are CDM (please to see the point 2.2.2) and therefore they are utilized
together with a D.C. motor to constitute a drive (PDS). The PDS is, in turn, integrated in the electric equipment.
The phenomenon EMCs are particularly sensitive to the conditions of the plant, what length of the connections,
shielding and connections to the PE and to the earth.
The conformity of the converters model TTB and TTU, listed on the Chart 1 and on the Chart 2 of the Chapter 3
and the relative CE marking, placed on the converters, for how much it concern to the EMCs directive, of which to
the documents [1], [2], and [3] mentioned on the paragraph 1.3, ago reference to the standards [8], with the
following precise statements:
1.4.1.1
The drives type TTB and TTU, since are CDM, they are commercialized in condition of narrow distribution
(please to see the point 2.2.4); this implies that the builder of the drive, and/or the electrical cabinet and/or the
installer and/or the builder of the machine and/or the final user they are competent people about EMC.
1.4.1.2
The drives type TTB and TTU can be applied both in "first environment" that in "second environment" (please
to see the points 2.2.5 and 2.2.6). In the case of application in first environment it is necessary to install a filter to
the three-phase supply of the converter, as specified on Chart 1 on page 19 of the chapter 3.
1.4.1.3
The drives type TTB and TTU, since they are components of a PDS, they are sold to be included as a part of an
apparatus or system or installed system; therefore the operational conditions of the CDM inside the PDS, and
therefore of an apparatus, system or installed system, they have to follow, in subject of EMC, how much
prescribed and/or recommended on this instruction book, particularly on the Chapter 2.
1.4.1.4
For how much required by the directives "Low Voltage", according to the documents [4], [5] and [6], the drives
type TTB and TTU, make reference to the standards [7], [10] and [11], however applicable.
1. Mains frequency.
2. Rated voltage of three-phase supply.
3. Rated voltage of single-phase supply.
4. Model converter (TTB or TTU).
5. Type of the Converter (02/xxx).
6. Serial Number
7. Data of registration (month/year).
8. Rated single-phase service supply.
9. Maximum field supply.
10. Maximum armature supply.
For commercial information, technical and application advice are available the followings address:
E MAIL: [email protected]
On the site Internet http://www.alterelettronica.it are available all the information about the products and the
update editions of the instruction manuals.
The specifications of product and the content of this instruction book can be changed without notice, we
recommends therefore to check on the special sections of the internet site the possible variations of specifications
and the updating of this instruction book.
The ALTER Elettronica S.r.l. it declines every responsibility for inaccuracies or mistakes brought on this
instruction book.
2.1.2
Purpose of this guide is that to furnish to the technician, to the builder of the machine and to the final user of the
drives type TTB and TTU information as required by the CEE Directives in vigor in subject of Electromagnetic
and Safety Compatibility for the so-called Low Voltage materials. Particularly prescriptions and indications are
recalled regarding the EMC to the various operators that utilize the drives type TTB and TTU to realize
installations including speed varying drives by d.c. motor. With reference to this, we recall the attention on the fact
that is necessary, for the performer of the drive, to coordinate the content of this guide with the EMC guide of
the builder of the d.c. motor, that is joined to TTB and TTU drive type.
2.2.2
ELECTRIC DRIVE (PDS): an electric drive is systems that convert electric energy into mechanics, by power
electronic equipments, according to a command function (and according to an established program).
A drive consist of:
- A POWER SUPPLY, CONVERSION AND CONTROL MODULE, (CDM) that it includes the whole
drive with the exception of the motor and the sensors placed on the motor; particularly it includes a
CONVERSION AND CONTROL MODULE (BDM) and its possible extensions as the supply module
or some auxiliary ones (for example: fan). The BDM includes the functions of conversion, control and
self-protection. In the practice the CDM has often called, shortly, CONVERTER.
- A MOTOR UNIT.
2.2.3
NOT NARROW DISTRIBUTION: marketing modality in which the supply of the equipments doesn't depend from
the competence of the client or of the user about EMC for the utilization of drives. This involves restrictive limits
of emission according to the essential requirements of EMC protection.
2.2.4
NARROW DISTRIBUTION: marketing modality in which the builder limits the supply of the equipments to
suppliers, clients or users that, separately or jointly have technical competence of the requisite regarding the EMC
for the application of drives. For economic motives, the interested parts should guarantee the essential requisite of
EMC protection, for the specific installation, choosing suitable categories of emission, through measurement "on
site" at the real conditions to the contour and through exchange of exchange of technical specifications.
2.2.5
FIRST ENVIRONMENT: environment that include the home purposes. It directly includes also the connected
industrial uses, without input transformers, to low voltage mains that feed buildings assigned to home purposes.
2.2.6
SECOND ENVIRONMENT: environment that includes all the different industrial purposes, not those connected to
low voltage mains that feed buildings assigned to home purposes.
2.3.1.2
Very particular cases accepted, the converters TTB and TTU are placed inside a metallic cabinet (so-called
electrical cabinet), that contains also electric equipments of various type (other electronic power converters,
contactors, transformers, inductors, etc.)
The motor or, better, the motor unit (because they can also exist other accessories what a tachogenerator, an
electric fan, a brake, etc.) it is located on the machine, to a certain distance from the electrical cabinet.
They exist therefore, in reality, two separate types of plant: what refers to the wiring of the electrical cabinet and
the real definitive plant that the technician realizes at the final client.
2.3.2 Installation of the converter inside the electrical cabinet
2.3.2.1
The drives type TTB and TTU, have IP20 degree of protection (please to see the point 3.3.1). To comply with how
much prescribed on the § 4.4.6 "Contaminating" of the EN 60204-1 (1998) standards it is necessary, that they be
situated, by the builder of the machine, in a suitable case, according to the required protection degree. Of rule they
will have placed therefore inside a cabinet; to satisfy EMC standards the cabinet has to be metallic made by
iron plate having thickness at least 1 mm.
It is important that inside the electric cabinet all the panels are connected among them by mechanical connections
that introduce low electric impedance at high frequencies. This can be made, for example, adding fastening screws,
using galvanized surface panels or cadmium plated rather than painted or removing the paint under the connection
points, using special metallic EMC gaskets.
2.3.2.2
The components' layout inside the electrical cabinet, both in terms of positioning and in terms of distances, must
be performs with the criterion to minimize the mutual influences regarding the electromagnetic noises of the
equipments. Generally the transformers, the inductors, the contactors, because of their coils, they can produce high
electric field at close distance.
2.3.2.3
The wiring of the power circuits must be physically separated from the wiring of the control circuits (signal
circuits); the power circuits must carefully be shielded from the signal circuits; this is made utilizing some metallic
raceways inside the electrical cabinet, metallic sheath or shielded cables, also for power connection.
2.3.2.4
Particular attention must be put on the wiring of the signal circuits, for motives about electromagnetic immunity.
Is necessary therefore that the connections of the signal circuits of the converter, both input and output, are made
using twisted pair cables and carefully shielded. The shield must be connected to ground on the converter side,
as illustrated on the page 45 of this instruction book and, where it is necessary, also to the ground connection of the
interested peripheral.
2.3.2.5
All the equipments, for which additional devices are prescribed to conform them to the EMC standards, must be
provided of such devices, placed according to the prescriptions of the manufacturer; particularly the good rules
recalls to place the spikes limiting devices in parallel to the a.c. coils of the contactors, the diodes in parallel to the
d.c. coils of relay or contactors, the filters against the conducted H.F. electrical noises placed on the three-phases
power input of some converters, when is prescribed.
2.3.2.6
The shielding of the cables have to finish the nearest possible to the terminal block; if the connection of the shield
is prescribed to ground or, in some cases, to the earth, it must possibly be made by some special cable-head that let
a 360° contact between the shield and the ground, in absence of this, by connections as short as possible and having
2.3.2.7
To disconnect the converter from the circuit under electric test, before making
resistance or isolation tests and/or applied voltage test.
The not compliance of this prescription can seriously damage the converter.
WARNING!
2.3.3.2
The three-phase transformer MV/LV of the feeder line to which some converters of electric drives are connected
must have an apparent power suitable to the loads, keeping in mind the power factor and the distortion factor. For
the converters TTB and TTU please to see Chart 1 on page 19.
2.3.3.3
The copper cross section area of the feeder line connected to the terminal block of the converter (see the
schemes "external Connections for converters" Figure 10 and Figure 11) must be suitable to the rated current of
every converter. The design must be made in such way to avoid voltage drops that can bring the supply voltage
values out of the contractual tolerance.
Moreover it is necessary to carefully study the runs to minimize the cables length.
2.3.3.4
All the metallic raceways, the metallic sheaths and, all the shielding, if not otherwise specified, must generally to
be connected to the PE both on the electrical cabinet both on the motor; these connections must to be very short and
have a wide cross section area.
2.3.4 Specific indications for the drives type TTB and TTU
2.3.4.1
The drives type TTB and TTU don't require, generally, particular modality for placing and installation over the
normal professionalism and knowledge of the rules of the art of the electric and electronic planting sector.
In every case, it is necessary to follow how much prescribed or recommended on this instruction book.
Following some specific indications are brought for the installation of the converters TTB and TTU, as it regards
the EMC and Low Voltage directive.
2.3.4.2
The connection schemes of the converters with built-in armature bridge (please to see Figure 10) and those with
external armature bridge (please to see Figure 11) they have to be integrated by the connection scheme brought
on Figure 12. Such scheme contains some important practical instructions about wiring to respect the EMC
standards, and about the shields connections to the drives type TTB and TTU.
When the drives type TTB and TTU are utilized in first environment, with reference to how much brought on the
point 1.4.1.2 it is necessary to install a filter on the three-phase supply of the converter; also the connections of
such filters are suitable on the figure above pointed.
On the Chart 1 on page 19 of the Chapter 3 are brought the types of the three-phase filters to utilize when is used
the scheme at Figure 12.
Making the connections brought on the pointed scheme must be observed the following rules.
The location of the filter is very important: it must be placed, inside the electrical cabinet, the nearest possible
to the component connected to her output. On the Figure 12 such component is named Z inductor.
The length of the connections between the filter output and the input of the component connected to its output
should not overcome 0,3 m and must be made by conductors, having a suitable cross section area, shielded as
far as possible. It is evident that, in certain cases, is not be possible to shield components as fuses and
contactors; for this reason it is necessary that the runs of the connections are the shortest possible.
WARNING! The input and the output of the filter cannot be exchanged!
Many ground connections are available on the converter to make easier the wiring;
Different ground points of the converter are marked by the symbol “ ”. (Please to see the schemes to Figure
13 the pointed out connections "E1" and "E2").
E1 (Figure 13), made by 2 M5 screws. It is the main ground and must to be connected
to the PE and therefore to the earth of the plant, by a conductor having a cross section
area not less then that of the three-phase supply conductors. This connection is
essential to the protection compliance and not only to the EMC compliance.
WARNING! E2 it is the connecting point of the shields of the signal cables, that they are brought
on Figure 8.
The ground terminal of the metallic frame of the filter, must to be connected as suitable on Figure 12.
2.3.4.3
You have seen, on the point 2.3.3.2 that the three-phase MV/LV transformer must have a suitable apparent power
(kVA).
In this session it is important to note however that in addition to the transformer, also the filter must have a power
suitable to that of the converter (or of the converters); it is also necessary that the voltage drop of the transformer,
to full load, it must be less them 3%.
2.3.4.4
To comply with how much prescribed on the Low Voltage directive and on the standards that can make reference
to it, we recall, as follow, some connected general safety dispositions with specific references to the drives type
TTB and TTU.
2.3.4.5
For any reason, safe during the operations of which to the point 2.3.4.6, are had to enter
inside the converter when it is fed. To enter must surely be disconnected: the three-
phase supply (terminals L1, L2, L3), the single-phase supply (terminals FL1, FL2),
the service supply (terminals 230V, 230V) and every other supply having a voltage
WARNING! value more them 50Va.c. and 75Vd.c., eventually existing on the connectors. Inside the
converter, when it is fed, there are some voltages potentially dangerous for the
safety of the operator!
2.3.4.6
Only during the startup operations, that must be carry out by qualified personal, it is allowed to provisionally
remove the protection panel to have only access to the Tests Point and to the Trimmers placed on the frontal plate.
After the startup to reassemble the panel.
2.3.4.7
To observance the instructions contained on this instruction book, from the point of
view of the safety, it is important to follow the prescriptions regarding the value
and the type of protections (fuses) prescribed (please to see Chart 2 on page 19).
WARNING!
2.3.4.9
All the connections to the common ground of the electrical cabinet has to be short and
have a suitable cross section area; the PE of the electrical cabinet must to be connected
to a good heart. Also the ground of the motor must be connected to a good heart, as
suggested on Figure 12.
WARNING!
This condition can never be reached, even if the resistance of the windings will be reduced remarkably to the
increase of the rated power of the motor.
To control the armature voltage to indirectly control the motor speed is advised against therefore in the most
greater part of the cases, since of the insufficient obtainable speed precision specially to the low speeds and
utilizing such small power motor.
In this mode it is not possible the motor operation in maximum constant power mode.
The set for this mode of operation is made by SWITCH.
The converter, not having the speed signal of the motor supplied by the T.G., it uses the armature voltage for all the
auxiliary functions joined to the speed. In the use of these auxiliary functions it is to keep in mind that to identify
the motor speed with his armature voltage especially causes remarkable inaccuracies to the low values.
Measuring the armature voltage and using the data of motor rating plate, it is possible to calculate, in approximate
way, the speed of the motor shaft by the following formula:
A converter running in this mode imposes that the current in the motor armature follows the reference.
This happen to condition that the current doesn't exceed the set limit and the armature voltage don't exceed the
maximum voltage allowed by the a.c. feeder line of the thyristors bridge.
If the torque of the load is not equal to that provided by the motor, the motor speed it reaches the maximum value
allowed by the a.c. feeder line.
It is not therefore possible to determine the operation speed of a single group converter + motor. The control of the
motor torque can be used only in a system in which the operation speed is imposed by another motor.
The most important characteristic of this type of control is the quickness of answer of the motor obtained by
exclusion from the operation of the speed control loop / armature voltage loop of the converter.
The current reference, supplied by the speed loop, is replaced by the external reference and it is forwarded to the
armature current loop control.
The digital command CME (Current Mode Enable) it enables this mode of operation and it excludes the speed loop
of the converter. Without such command the converter controls the motor speed.
The same converter can run then in the two operating modes.
For the operation it needs nevertheless to also predispose the converter for the speed control by T.G. or by
ARMATURE VOLTAGE.
The operation on maximum constant power mode it is possible only if the speed control is made by T.G.; by
armature voltage it is not possible.
In this mode of operation are available only the followings auxiliary functions:
- Motor standstill
- Speed over threshold
- Speed monitor
- Limit of the armature current dependent from the motor speed
In the use of these auxiliary functions you must make reference to that written for the 3.2.1 Speed Control by
Analog Tachogenerator or ARMATURE VOLTAGE.
The armature current reference must be applies to the analog input CRI (Current Reference Input).
Without the digital command CME this reference, even if it exist, it doesn't produce regulation effects on the
armature current. If the command CME it exist, the speed reference existing on the input don't produce regulation
effects of the speed or of the armature voltage.
3.2.4 Master - Slave Interlocking
If two or more electric motors are mechanically connected to the same transmission shaft it is possible to divide on
the different motors the total torque transmitted to the shaft.
To get this so many converters are needed how many the motors are.
The system is composed by a Master converter, that control the speed of the system and it determines the necessary
total current, and by one or more SLAVES converters, that receives the current reference from the Master and they
supplies each a part of the total current.
The current supplied by the Master added to the currents supplied by the SLAVES it is the current necessary to run.
The Master converter must to run as speed control mode by T.G. or by Armature Voltage.
The Slaves converters must run as Torque Control by the Armature Current.
The mode and the operation limits of the SLAVES are the same of the Torque Control by the Armature
Current.
The digital command CME (Current Mode Enable) it enables this operating mode and it disables the motor speed
control.
Without the digital command CME the converter controls the motor speed.
The same converter can run then in the two modes MASTER and SLAVE.
The analog input CRI (Current Reference Input) of the SLAVES it must to be connected to the armature current
reference that is supplied by the analog output CRO (Current Reference Output) of the Master.
SERVICES
Supply: single-phase 230Va.c. ±10% - 500mA max. (Terminals: 230V)
Cross section area of the connection cables: 1,5 mm2
Supply Protection by N°2 fuses having rated current 1A
FIELD
The single-phase supply voltage of the converter VFL (terminals FL1-FL2) it is calculated by the following
formula:
VFL = 1,2 x Maximum voltage of the motor field
The maximum input current of the converter IFL (terminals FL1-FL2) it is calculated by the following formula:
ARMATURE
The converter must be connected to a three-phase mains having grounded neutral and rating voltage: 400/230Va.c.
±10% 50/60Hz. (the selection of the voltage and of the frequency are described on page 30 paragraph 4.3.3). To
insert between the three-phase mains and the converter a three-phase inductor having an inductance of at least 100µ
Η, that must to be designed for the current supplied to the converter and having a saturation current at least the
double one of the designing current.
To use some transformer having connections ∆/Y with center tap connected to ground or some autotransformer
(Y/Y) to fit mains.
To protect the converter bridge by N°3 ultra-fast fuses as suitable on the Chart 2.
The rating of the converters are brought on Chart 1 and Chart 2 on page 19.
CONVERTER
TYPE OUTPUT ABSORBED APPARENT
FILTER INDUCTANCE
CURRENT SIZE POWER
TTB TTU
Rated/Peak Rated/Peak
(1) [A] (2) (3) [KVA] (4) TYPE TYPE
02/211 02/231 15 / 20 1 8,5 / 11,4 23/001 17/001
02/212 02/232 30 / 40 1 17 / 22,7 23/002 17/001
02/213 02/233 60 / 80 1 34 / 45,4 23/003 17/003
02/214 02/234 90 / 120 1 51,1 / 68,1 23/004 17/004
02/215 02/235 120 / 160 1 68,1 / 90,9 23/005 17/005
02/216 02/236 180 / 240 2 102,2 / 136,3 23/007 17/007
02/217 02/237 240 / 320 2 136,3 / 181,8 23/008 17/008
02/218 02/238 300 / 400 3 170,4 / 227,2 23/010 17/009
02/219 02/239 400 / 530 3 227,2 / 301 23/010 17/010
02/220 02/240 500 / 660 3 284 / 375 23/010 ----
-- -- >500 1 (5) Driving Unity of external bridge
Chart 1
NOTE:
The Rated / Peak apparent power is absorbed from mains, when the converter deliver the Rated / Peak current.
THREE-PHASE SUPPLY
CONVERTER CONNECTION
FUSES
TYPE OUTPUT
RATED Max. I2t at SUPPLY MOTOR
CURRENT
TTB TTU CURRENT 10ms L1-L2-L3 A-B
Rated/Peak
(1) [A] [A] [A2s] (6) [mm2] [mm2]
02/211 02/231 15/20 32 1.100 4 4
02/212 02/232 30/40 50 1.100 10 10
02/213 02/233 60/80 100 3.500 16 16
02/214 02/234 90/120 160 15.000 35 35
02/215 02/235 120/160 200 18.000 70 70
02/216 02/236 180/240 250 18.000 BAR BAR
02/217 02/237 240/320 400 125.000 BAR BAR
02/218 02/238 300/400 500 125.000 BAR BAR
02/219 02/239 400/530 630 320.000 BAR BAR
02/220 02/240 500/660 700 320.000 BAR BAR
-- -- >500 (5) Driving Unity of external bridge
Chart 2
NOTE
(1) Inside temperature of the electrical cabinet, inside which the converter is placed, from 0 to 40°C.
4% of current derating for every °C over 40°C.
(2) Outline dimensions and weights on the Figure 13.
(3) Power calculated with 400Va.c. three-phase mains.
(4) The filter is necessary when the drives type TTB and TTU are utilized in first environment, to satisfy the
requisite regarding the EMC compatibility (please to see the point 2.3.4.2).
(5) The Driving unity of external bridge (please to see the Figure 11) it is available to drive:
- An already existing bridge;
- A bridge for current >500A.
Inside the frame they are placed: the bridge for the field supplying and the relative terminals block, the terminal
block for the connections to the external bridge.
The three-phase supply fuses size and the cross sections area of the cables is dependent from the current.
(6) Input a.c. current = 0,82 x Armature Current
NOTES:
(*) With this alarm the armature bridge is disabled, the led DOK is out and the digital output DOK is OFF.
(* *) With this alarm the armature bridge is disabled, the led DOK is out and the digital output DOK is OFF
only if the enabling commands of the corresponding bridge are existing (ABE and/or FBE).
The reset of the memorized alarms happens by the digital command ALR.
(*) Please replace Speed with Armature Voltage if the control is by Armature Voltage.
(*) Please replace Speed with Armature Voltage if the control is by Armature Voltage.
(*) Please replace Speed with Armature Voltage if the control is by Armature Voltage.
NOTES:
- To eliminate the points 1 - 2 - 9 - 10 if the d.c. motor is a permanent magnets type.
- The commands of which points 1 - 2 can be simultaneous.
- The commands of which points 7 - 8 - 9 - 10 can be simultaneous.
- To apply the three-phase voltage to supply the motor armature (point 3) only if the digital output DOK is found
in the ON state.
- If the commands of which points 3 and 4 are simultaneous, the enabling of the armature supply bridge it
happens 100 msec after the three-phase voltage is applying.
- After the enabling of the bridge to supply the motor field, (with the single-phase voltage to supply the motor
field applied) to wait at least 1 sec before to enable the armature bridge (point 4) to let the field current to reach
the steady value.
- When the motor is not running, can be useful to stop the fan of the motor and to also disable the bridge to
supply the motor field not to overheat the motor in absence of ventilation. To also remove the three-phase
voltage supply and the enabling of the armature bridge.
- To immediately remove the three-phase voltage supplies to the armature bridge if the digital output DOK go in
the OFF state.
To always observe the starting and the shutdown sequences.
4.3 Startup
Setting
(to see pag.30)
Starting
(to see pag.30)
Motor running
Auxiliary functions
setting
Armature current limit
depend from the speed Steady speed
(to see pag.34) (to see pag. 35)
END
4.3.4 Starting
- NOTES:
- The regulations are described in the sequence in which they must be made.
- The clockwise rotation of the trimmer’s regulation screw corresponds to an Increase of the corresponding
greatness.
- To connect to the T.P. A0V or to the metallic frame of the converter the negative prod of the voltmeter and the
ground of the probe of the oscilloscope.
- Make use of insulated screwdriver to regulate the trimmers.
- The trimmer’s regulation screw sealed by enamel must not be turned.
- The motor speed is calculable by the following formula:
VT .G . (read on terminal 2)
Motor Speed =
KT .G. (read on T .G.)
1 To supply only the services and to verify that: the fan (if built-in) is running, the lighting of the following led:
DOK STS SUP ZES
NOTE: Any red LED must be lighted.
To calculate the voltage corresponding to the rated field current by the following formula:
To apply the single-phase voltage, that supply the field bridge, and to enable the field control (digital Input FBE).
To adjust by the trimmer RFC the voltage on the T.P. FLC to get the calculated value.
NOTE: The supply voltage of the field is not significant, to verify only that it is not more than the rated value
indicated on the rating plate of the motor.
The converter also control the motor speed in one of the two modes: by T.G. or by ARMATURE VOLTAGE,
then it is necessary also to make the motor running for the corresponding operation mode (please to see on
page 31 or on page 32).
To apply the digital command CME that enables this operation mode.
To apply a current reference on the input CRI (terminal 34) (less than 1V on the T.P. ACR) and to verify that the
torque direction on the motor shaft be right.
NOTES:
If the sign of the torque is wrong it is necessary to reverse the sign of the current reference on the input ACR
or to reverse the connections of the armature or of the field of the motor after having removed the commands
ABE, FBE and all the supplies.
To apply therefore the supplies and then to repeat the MOTOR RUNNING.
4.3.5.4 MASTER - SLAVE INTERLOCKING
Before beginning to carefully read the paragraph 3.2 (page 13).
- To execute the startup of the MASTER converter.
- To execute the startup of the SLAVE converter in the operation mode "Torque Control by the Armature
Current" (please to see on page33).
NOTES:
You must connect the current reference output of the MASTER converter (CRO output terminal 32) to the
current reference input of the SLAVE converter (CRI input terminal 34).
NOTE: The rise and the fall times of the speed ramp are equal.
To enable the RAMP function by the digital input SRE.
To select the range of rise / fall time of the ramp by SW1-1.
If SW1.1 = OFF the time is adjustable from 0,5 to 5 sec.
If SW1.1 = ON the time is adjustable from 5 to 50 sec. To have time greater than 50 sec. it is necessary to
place a capacitor in C20 position (please to see the scheme on page 36). The capacity is calculated by the
following formula:
T − 50
C 20 = [µF]
50
T = Maximum approximate rise / fall time [sec.].
These times are gotten with 10V speed reference amplitude. If the amplitude is less than 10V the times are
proportionally shortest.
Adjust, by the trimmer SRT, the rise / fall time corresponding to the maximum speed reference on the inputs
SI1÷6 and check the time, by the oscilloscope, on the T.P. SPR.
Figure 1
DIAGRAM OF THE ARMATURE CURRENT LIMIT DEPENDENT FROM THE SPEED
NOTES: This setting must be made if required by the builder of the motor (please to see data on the rating
plate of the motor) or by the application.
Before making this setting you have to verify the set limit of the armature current I1 (please to see on page 30).
If SW1.7 = OFF the setting is disabled (limit of the current is constant = I1).
If SW1.7 = ON the setting is enabled.
Setting:
- To carry the trimmers CP1 and CP2 to clockwise limit stop position and the trimmer CDE to counterclockwise
limit stop position.
- To carry the motor to the speed ω1.
- To adjust, by the trimmer CP1, the voltage on the TP CP1 to be equal to that measured on the T.P. SPR
(eliminating the sign).
- To slowly carry the motor to the speed ω2 and to adjust, by the trimmer CP2, the voltage on the TP CP2 to be
equal to that measured on the T.P. SPR.
- To adjust, by the trimmer CDE, the voltage on the TP ACL to have a value corresponding to the current I2
calculated by the following formula:
I2 I2 = Armature current indicated on the rating plate of the
VT . P. ACL = 5 • motor, corresponding to the speed ω2 (the ω2 can be that
Converter Nom. Current
suitable on the plate of the motor or that of maximum
use if it is inferior).
4.3.6.4 MAXIMUM ALLOWABLE SPEED ERROR FOR THE STEADY SPEED SIGNALING
(Digital output “STS”) (Terminal 26).
This setting must be execute only to make use of the digital output STS.
To set by the trimmer SEL on the T.P. SEL the voltage calculated by the following formula:
∆ω
VT . P .SEL = • V R max . [V]
ω MAX
∆ω = Maximum speed error (constant at all the speeds) [RPM].
ωMAX = Maximum motor speed (corresponding to the Maximum speed reference) [RPM].
VRmax = Maximum speed reference (voltage on the T.P SPR) [V].
ATTACHMENTS
VARIOUS SCHEMES OF CIRCUIT
Figure 2
Figure 3
Figure 4
Figure 5
COMPONENT LAYOUT
Figure 6
ALTER Elettronica S.r.l. - 38 - Instruction book 91/094 Rev. 00 Edit. 02
Chapter 5 Attachments
GENERAL LAYOUT
Figure 7
EXTERNAL LINKS
ANALOG I/O
Figure 8
Figure 9
If the necessary total current overcomes 300mA, it is not possible to use the 24V output of the converter; it needs
therefore to have a 24V stand-alone power supply.
Figure 10
* For further information about the motor field connections please to see on page 17 paragraph “FIELD”
Figure 11
* For further information about the motor field connections please to see on page 17 paragraph “FIELD”.
Figure 12
MECHANICAL FEATURES
Figure 13
DIMENSION ON mm
SIZE A B C D MASS
1 194 390 157 372 Kg 13,5
2 288 430 228 412 Kg 20
3 288 587 228 412 --
http://www.alterelettronica.it
| [email protected]