Manual de Comissionamento REC650 Iec

Download as pdf or txt
Download as pdf or txt
You are on page 1of 116

Relion® 650 SERIES

Bay control REC650


Version 1.3 IEC
Commissioning manual
Document ID: 1MRK 511 288-UEN
Issued: November 2019
Revision: B
Product version: 1.3

© Copyright 2013 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license and may
be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in the OpenSSL
Toolkit. (http://www.openssl.org/)

This product includes cryptographic software written/developed by: Eric Young


([email protected]) and Tim Hudson ([email protected]).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

ABB AB
Grid Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/protection-control
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified
voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests
conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for
the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international standards of
the IEC 60255 series.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that
each intended application is suitable and acceptable, including that any applicable safety or
other operational requirements are complied with. In particular, any risks in applications where
a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby requested to
ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be completely ruled
out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall ABB be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
Table of contents

Table of contents

Section 1 Introduction.................................................................................................... 7
1.1 This manual.................................................................................................................................... 7
1.2 Intended audience........................................................................................................................ 7
1.3 Product documentation..............................................................................................................8
1.3.1 Product documentation set..................................................................................................... 8
1.3.2 Document revision history....................................................................................................... 9
1.3.3 Related documents.................................................................................................................... 9
1.4 Symbols and conventions......................................................................................................... 10
1.4.1 Symbols...................................................................................................................................... 10
1.4.2 Document conventions........................................................................................................... 10

Section 2 Safety information....................................................................................... 11


2.1 Symbols on the product.............................................................................................................11
2.2 Warnings....................................................................................................................................... 11
2.3 Caution signs............................................................................................................................... 12
2.4 Note signs.................................................................................................................................... 13

Section 3 Available functions....................................................................................... 15


3.1 Back-up protection functions.................................................................................................. 15
3.2 Control and monitoring functions.......................................................................................... 16
3.3 Station communication.............................................................................................................19
3.4 Basic IED functions.....................................................................................................................21

Section 4 Starting up.....................................................................................................23


4.1 Factory and site acceptance testing...................................................................................... 23
4.2 Commissioning checklist.......................................................................................................... 23
4.3 Checking the power supply...................................................................................................... 24
4.4 Energizing the IED...................................................................................................................... 24
4.4.1 Checking the IED operation................................................................................................... 24
4.4.2 IED start-up sequence.............................................................................................................24
4.5 Setting up communication between PCM600 and the IED............................................... 25
4.6 Writing an application configuration to the IED..................................................................30
4.7 Checking CT circuits...................................................................................................................31
4.8 Checking VT circuits................................................................................................................... 31
4.9 Using the RTXP test switch...................................................................................................... 32
4.10 Checking binary input and output circuits............................................................................32
4.10.1 Binary input circuits................................................................................................................. 32
4.10.2 Binary output circuits.............................................................................................................. 33
4.11 Checking optical connections..................................................................................................33

Section 5 Establishing connection and verifying the IEC 61850 station


communication............................................................................................. 35

Bay control REC650 1


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Table of contents

5.1 Setting the station communication....................................................................................... 35


5.2 Verifying the station communication.................................................................................... 35

Section 6 Testing IED operation.................................................................................. 37


6.1 Preparing the IED to verify settings........................................................................................37
6.2 Activating the test mode.......................................................................................................... 38
6.3 Preparing the connection to the test equipment................................................................ 39
6.4 Connecting the test equipment to the IED........................................................................... 39
6.5 Releasing the function to be tested.......................................................................................40
6.6 Verifying analog primary and secondary measurement.....................................................41
6.7 Testing the protection functionality...................................................................................... 42

Section 7 Testing functionality................................................................................... 43


7.1 Testing disturbance report...................................................................................................... 43
7.1.1 Introduction.............................................................................................................................. 43
7.1.2 Disturbance report settings.................................................................................................. 43
7.2 Identifying the function to test in the technical reference manual ................................ 43
7.3 Testing current protection functions.................................................................................... 43
7.3.1 Instantaneous phase overcurrent protection 3-phase output PHPIOC .......................43
7.3.1.1 Measuring the operate limit of set values.....................................................................44
7.3.1.2 Completing the test...........................................................................................................44
7.3.2 Four step phase overcurrent protection 3-phase output OC4PTOC............................ 44
7.3.2.1 Verifying the settings........................................................................................................ 44
7.3.2.2 Completing the test........................................................................................................... 45
7.3.3 Instantaneous residual overcurrent protection EFPIOC ................................................. 45
7.3.3.1 Measuring the operate limit of set values.....................................................................45
7.3.3.2 Completing the test...........................................................................................................46
7.3.4 Four step residual overcurrent protection, zero or negative sequence
direction EF4PTOC ................................................................................................................. 46
7.3.4.1 Four step directional residual overcurrent protection .............................................. 46
7.3.4.2 Four step non-directional residual overcurrent protection....................................... 47
7.3.4.3 Completing the test........................................................................................................... 47
7.3.5 Sensitive directional residual overcurrent and power protection SDEPSDE .............. 47
7.3.5.1 Measuring the operate and time limit for set values.................................................. 47
7.3.5.2 Completing the test........................................................................................................... 51
7.3.6 Thermal overload protection, one time constant, Celsius/Fahrenheit LCPTTR/
LFPTTR........................................................................................................................................ 51
7.3.6.1 Testing the protection without external temperature compensation
(NonComp)........................................................................................................................... 51
7.3.6.2 Completing the test........................................................................................................... 52
7.3.7 Breaker failure protection, phase segregated activation and output CCRBRF...........52
7.3.7.1 Checking the phase current operate value, IP>............................................................ 52
7.3.7.2 Checking the residual (earth fault) current operate value IN> set below IP>.........53
7.3.7.3 Checking the re-trip and back-up times........................................................................ 53
7.3.7.4 Verifying the re-trip mode................................................................................................ 53
7.3.7.5 Verifying the back-up trip mode..................................................................................... 54
7.3.7.6 Verifying the case RetripMode = Contact......................................................................54

2 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Table of contents

7.3.7.7 Verifying the function mode Current&Contact............................................................ 55


7.3.7.8 Completing the test........................................................................................................... 55
7.3.8 Stub protection STBPTOC......................................................................................................55
7.3.8.1 Measuring the operate limit of set values.....................................................................56
7.3.8.2 Completing the test........................................................................................................... 56
7.3.9 Pole discordance protection CCRPLD..................................................................................56
7.3.9.1 Verifying the settings........................................................................................................ 56
7.3.9.2 Completing the test........................................................................................................... 57
7.3.10 Broken conductor check BRCPTOC ......................................................................................57
7.3.10.1 Measuring the operate and time limit of set values.................................................... 57
7.3.10.2 Completing the test........................................................................................................... 58
7.3.11 Directional underpower protection GUPPDUP ................................................................. 58
7.3.11.1 Verifying the settings........................................................................................................ 58
7.3.11.2 Completing the test........................................................................................................... 59
7.3.12 Directional overpower protection GOPPDOP ....................................................................59
7.3.12.1 Verifying the settings........................................................................................................ 60
7.3.12.2 Completing the test...........................................................................................................60
7.4 Testing voltage protection functions....................................................................................60
7.4.1 Two step undervoltage protection UV2PTUV ................................................................... 60
7.4.1.1 Verifying the setting.......................................................................................................... 60
7.4.1.2 Completing the test........................................................................................................... 62
7.4.2 Two step overvoltage protection OV2PTOV ......................................................................62
7.4.2.1 Verification of single-phase voltage and time delay to operate for Step 1............ 62
7.4.2.2 Completing the test........................................................................................................... 63
7.4.3 Two step residual overvoltage protection ROV2PTOV ....................................................63
7.4.3.1 Verifying the settings........................................................................................................ 63
7.4.3.2 Completing the test...........................................................................................................64
7.4.4 Loss of voltage check LOVPTUV .......................................................................................... 64
7.4.4.1 Measuring the operate limit of set values.....................................................................64
7.4.4.2 Completing the test........................................................................................................... 65
7.5 Testing frequency protection functions............................................................................... 65
7.5.1 Underfrequency protection SAPTUF ................................................................................... 65
7.5.1.1 Verifying the settings........................................................................................................ 65
7.5.1.2 Completing the test...........................................................................................................66
7.5.2 Overfrequency protection SAPTOF ..................................................................................... 66
7.5.2.1 Verifying the settings........................................................................................................ 67
7.5.2.2 Completing the test...........................................................................................................68
7.5.3 Rate-of-change frequency protection SAPFRC .................................................................68
7.5.3.1 Verifying the settings........................................................................................................ 68
7.5.3.2 Completing the test...........................................................................................................68
7.6 Testing secondary system supervision functions...............................................................69
7.6.1 Current circuit supervision CCSRDIF ...................................................................................69
7.6.1.1 Verifying the settings........................................................................................................ 69
7.6.1.2 Completing the test...........................................................................................................69
7.6.2 Fuse failure supervision SDDRFUF....................................................................................... 69
7.6.2.1 Checking that the binary inputs and outputs operate as expected ....................... 69

Bay control REC650 3


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Table of contents

7.6.2.2 Measuring the operate value for the negative sequence function ..........................70
7.6.2.3 Measuring the operate value for the zero-sequence function .................................. 71
7.6.2.4 Checking the operation of the du/dt and di/dt based function ..............................71
7.6.2.5 Completing the test........................................................................................................... 72
7.7 Testing control functions..........................................................................................................72
7.7.1 Synchrocheck, energizing check, and synchronizing SESRSYN...................................... 72
7.7.1.1 Testing the synchronizing function................................................................................ 74
7.7.1.2 Testing the synchrocheck check......................................................................................75
7.7.1.3 Testing the energizing check........................................................................................... 78
7.7.1.4 Testing the voltage selection........................................................................................... 79
7.7.1.5 Completing the test........................................................................................................... 79
7.7.2 Autorecloser for 3-phase operation SMBRREC ................................................................. 79
7.7.2.1 Preparation of the verification ........................................................................................ 81
7.7.2.2 Switching the autorecloser for 3-phase operation function to On and Off........... 81
7.7.2.3 Verifying the autorecloser for 3-phase operation function SMBRREC ................... 82
7.7.2.4 Checking the reclosing conditions .................................................................................82
7.7.2.5 Completing the test........................................................................................................... 83
7.7.3 Interlocking................................................................................................................................83
7.7.4 Apparatus control APC............................................................................................................84
7.8 Testing scheme communication functions.......................................................................... 84
7.9 Testing logic functions............................................................................................................. 84
7.9.1 Tripping logic, common 3-phase output SMPPTRC .........................................................84
7.9.1.1 Three-phase operating mode.......................................................................................... 84
7.9.1.2 Circuit breaker lockout......................................................................................................84
7.9.1.3 Completing the test........................................................................................................... 85
7.10 Testing monitoring functions..................................................................................................85
7.10.1 Event counter CNTGGIO......................................................................................................... 85
7.10.2 Limit counter L4UFCNT.......................................................................................................... 85
7.10.2.1 Completing the test........................................................................................................... 85
7.10.3 Fault locator LMBRFLO........................................................................................................... 86
7.10.3.1 Measuring the operate limit.............................................................................................86
7.10.3.2 Completing the test........................................................................................................... 87
7.11 Testing metering functions......................................................................................................87
7.11.1 Pulse counter PCGGIO............................................................................................................. 87
7.12 Testing station communication.............................................................................................. 87
7.12.1 Establishing connection and verifying the IEC 61850 communication.........................87
7.12.1.1 Overview...............................................................................................................................88
7.12.1.2 Setting the station communication............................................................................... 88
7.12.1.3 Verifying the station communication............................................................................ 89
7.13 Exit test mode.............................................................................................................................89

Section 8 Commissioning and maintenance of the fault clearing system.............91


8.1 Commissioning and maintenance of the fault clearing system....................................... 91
8.1.1 Commissioning tests...............................................................................................................91
8.1.2 Periodic maintenance tests....................................................................................................91
8.1.2.1 Visual inspection.................................................................................................................92

4 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Table of contents

8.1.2.2 Maintenance tests.............................................................................................................. 92

Section 9 Troubleshooting .......................................................................................... 95


9.1 Fault tracing................................................................................................................................ 95
9.1.1 Identifying hardware errors................................................................................................... 95
9.1.2 Identifying runtime errors......................................................................................................95
9.1.3 Identifying communication errors........................................................................................95
9.1.3.1 Checking the communication link operation................................................................95
9.1.3.2 Checking the time synchronization................................................................................ 96
9.1.4 Running the display test.........................................................................................................96
9.2 Indication messages..................................................................................................................96
9.2.1 Internal faults............................................................................................................................96
9.2.2 Warnings.................................................................................................................................... 97
9.2.3 Additional indications............................................................................................................. 97
9.3 Correction procedures.............................................................................................................. 98
9.3.1 Changing and setting the password....................................................................................98
9.3.2 Identifying IED application problems.................................................................................. 98
9.3.2.1 Inspecting the wiring.........................................................................................................98

Section 10 Glossary....................................................................................................... 103

Bay control REC650 5


Commissioning manual
© Copyright 2013 ABB. All rights reserved
6
1MRK 511 288-UEN B Section 1
Introduction

Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v14

The commissioning manual contains instructions on how to commission the IED. The manual
can also be used by system engineers and maintenance personnel for assistance during the
testing phase. The manual provides procedures for the checking of external circuitry and
energizing the IED, parameter setting and configuration as well as verifying settings by
secondary injection. The manual describes the process of testing an IED in a substation which
is not in service. The chapters are organized in the chronological order in which the IED should
be commissioned. The relevant procedures may be followed also during the service and
maintenance activities.

1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v9

This manual addresses the personnel responsible for commissioning, maintenance and taking
the IED in and out of normal service.

The commissioning personnel must have a basic knowledge of handling electronic equipment.
The commissioning and maintenance personnel must be well experienced in using protection
equipment, test equipment, protection functions and the configured functional logics in the
IED.

Bay control REC650 7


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 1 1MRK 511 288-UEN B
Introduction

1.3 Product documentation

1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v12

Deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual

Application manual

Technical manual
Communication
protocol manual

IEC07000220-3-en.vsd
IEC07000220 V3 EN-US

Figure 1: The intended use of manuals throughout the product lifecycle


The engineering manual contains instructions on how to engineer the IEDs using the various
tools available within the PCM600 software. The manual provides instructions on how to set
up a PCM600 project and insert IEDs to the project structure. The manual also recommends a
sequence for the engineering of protection and control functions, LHMI functions as well as
communication engineering for IEC 60870-5-103, IEC 61850 and DNP 3.0.

The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the
chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. The manual
can also be used by system engineers and maintenance personnel for assistance during the
testing phase. The manual provides procedures for the checking of external circuitry and
energizing the IED, parameter setting and configuration as well as verifying settings by
secondary injection. The manual describes the process of testing an IED in a substation which
is not in service. The chapters are organized in the chronological order in which the IED should
be commissioned. The relevant procedures may be followed also during the service and
maintenance activities.

The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of
the IED. The manual also describes how to identify disturbances and how to view calculated
and measured power grid data to determine the cause of a fault.

8 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 1
Introduction

The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical protection
function can be used. The manual can also provides assistance for calculating settings.

The technical manual contains application and functionality descriptions and lists function
blocks, logic diagrams, input and output signals, setting parameters and technical data,
sorted per function. The manual can be used as a technical reference during the engineering
phase, installation and commissioning phase, and during normal service.

The communication protocol manual describes the communication protocols supported by


the IED. The manual concentrates on the vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific to the
IED. The manual should be used in conjunction with the corresponding communication
protocol manual.

1.3.2 Document revision history GUID-52A4699C-F83B-48F8-BF4E-D853043AB731 v5.1.1.1.1

Document revision/date History


-/March 2013 First release
A/October 2016 Minor corrections made
B/November 2019 Maintenance release - Updated safety information and bug corrections

1.3.3 Related documents GUID-DEA16B32-29D9-40B2-BC9F-12F3AEA90245 v7

Documents related to REC650 Identity number


Application manual 1MRK 511 286-UEN
Technical manual 1MRK 511 287-UEN
Commissioning manual 1MRK 511 288-UEN
Product Guide 1MRK 511 289-BEN
Type test certificate 1MRK 511 289-TEN

650 series manuals Identity number


Communication protocol manual, DNP 3.0 1MRK 511 280-UEN
Communication protocol manual, IEC 61850–8–1 1MRK 511 281-UEN
Communication protocol manual, IEC 60870-5-103 1MRK 511 282-UEN
Cyber Security deployment guidelines 1MRK 511 285-UEN
Point list manual, DNP 3.0 1MRK 511 283-UEN
Engineering manual 1MRK 511 284-UEN
Operation manual 1MRK 500 096-UEN
Installation manual 1MRK 514 016-UEN
Accessories, 650 series 1MRK 513 023-BEN
MICS 1MRG 010 656
PICS 1MRG 010 660
PIXIT 1MRG 010 658

Bay control REC650 9


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 1 1MRK 511 288-UEN B
Introduction

1.4 Symbols and conventions

1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v9

The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.

The warning icon indicates the presence of a hazard which could result in
personal injury.

The caution icon indicates important information or warning related to the


concept discussed in the text. It might indicate the presence of a hazard which
could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or
how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. It is important that the
user fully complies with all warning and cautionary notices.

1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v2

• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary
also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button
icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal
name may be customized using the PCM600 software.
• the character * after an input/output signal name indicates that the signal must be
connected to another function block in the application configuration to achieve a
valid application configuration.

10 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 2
Safety information

Section 2 Safety information


2.1 Symbols on the product GUID-E48F2EC3-6AB8-4ECF-A77E-F16CE45CA5FD v4

All warnings must be observed.

Read the entire manual before doing installation or any maintenance work on
the product.

Class 1 Laser product. Take adequate measures to protect your eyes and do not
view directly with optical instruments.

2.2 Warnings IP1504-1 v2

Observe the warnings during all types of work related to the product.
GUID-C9B6638A-57E7-4E05-9A33-A60E359C54AF v1

Only electrically skilled persons with the proper authorization and knowledge of
any safety hazards are allowed to carry out the electrical installation.

M2366-2 v2

National and local electrical safety regulations must always be followed.


Working in a high voltage environment requires serious approach to avoid
human injuries and damage to equipment.

M2362-2 v1

Do not touch circuitry during operation. Potentially lethal voltages and currents
are present.

M2364-2 v1

Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.

M2370-2 v1

Never connect or disconnect a wire and/or a connector to or from a IED during


normal operation. Hazardous voltages and currents are present that may be
lethal. Operation may be disrupted and IED and measuring circuitry may be
damaged.

Bay control REC650 11


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 2 1MRK 511 288-UEN B
Safety information

GUID-BEDD698E-356C-4CF9-9DAE-64DB3CEADEAD v1

Dangerous voltages can occur on the connectors, even though the auxiliary
voltage has been disconnected.

M2369-2 v3

Always connect the IED to protective earth, regardless of the operating


conditions. This also applies to special occasions such as bench testing,
demonstrations and off-site configuration. This is class 1 equipment that shall
be earthed.

M2372-2 v1

Never remove any screw from a powered IED or from a IED connected to
powered circuitry. Potentially lethal voltages and currents are present.

SEMOD168311-3 v1

Take adequate measures to protect the eyes. Never look into the laser beam.

GUID-11CCF92B-E9E7-409C-84D0-DFDEA1DCBE85 v2

2.3 Caution signs IP1503-1 v1

GUID-5D1412B8-8F9D-4D39-B6D1-60FB35797FD0 v2

Whenever changes are made in the IED, measures should be taken to avoid
inadvertent tripping.

GUID-F2A7BD77-80FB-48F0-AAE5-BE73DE520CC2 v1

The IED contains components which are sensitive to electrostatic discharge.


ESD precautions shall always be observed prior to touching components.

M2695-2 v2

Always transport PCBs (modules) using certified conductive bags.

M2696-2 v1

Do not connect live wires to the IED. Internal circuitry may be damaged

M2697-2 v2

Always use a conductive wrist strap connected to protective earth when


replacing modules. Electrostatic discharge (ESD) may damage the module and
IED circuitry.

M2698-2 v2

Take care to avoid electrical shock during installation and commissioning.

12 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 2
Safety information

M2693-2 v1

Changing the active setting group will inevitably change the IEDs operation. Be
careful and check regulations before making the change.

2.4 Note signs IP1497-1 v1

M19-2 v3.1.1

Observe the maximum allowed continuous current for the different current
transformer inputs of the IED. See technical data.

Bay control REC650 13


Commissioning manual
© Copyright 2013 ABB. All rights reserved
14
1MRK 511 288-UEN B Section 3
Available functions

Section 3 Available functions


GUID-6A17ECFA-FE08-4F72-932E-635865410F5C v1

Note that not all functions included in the tables below have commissioning
information available.

3.1 Back-up protection functions GUID-47D5EAC9-5F4A-4A3D-B813-4E50A2BCCDC3 v7.1.1

IEC 61850 or ANSI Function description Bay


Function name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
REC650

3Ph/1CBA

BCAB
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection, 0–1 1 1 1
3–phase output
OC4PTOC 51/67 Four step phase overcurrent protection, 3- 0–1 1 1 1
phase output
EFPIOC 50N Instantaneous residual overcurrent 0–1 1 1 1
protection
EF4PTOC 51N/67 Four step residual overcurrent protection, 0–1 1 1 1
N zero/negative sequence direction
SDEPSDE 67N Sensitive directional residual overcurrent and 0–1 1 1 1
power protection
LCPTTR 26 Thermal overload protection, one time 0–1 1 1 1
constant, Celsius
LFPTTR 26 Thermal overload protection, one time 0–1 1 1 1
constant, Fahrenheit
CCRBRF 50BF Breaker failure protection, 3–phase activation 0–1 1 1 1
and output
STBPTOC 50STB Stub protection 0–1 1 1 1
CCRPLD 52PD Pole discordance protection 0–1 1 1 1
BRCPTOC 46 Broken conductor check 0–1 1 1 1
GUPPDUP 37 Directional underpower protection 0–1 1 1 1
GOPPDOP 32 Directional overpower protection 0–1 1 1 1
DNSPTOC 46 Negative sequence based overcurrent 0–1 1 1 1
function
Voltage protection
UV2PTUV 27 Two step undervoltage protection 0–1 1 1 1
OV2PTOV 59 Two step overvoltage protection 0–1 1 1 1
ROV2PTOV 59N Two step residual overvoltage protection 0–1 1 1 1
LOVPTUV 27 Loss of voltage check 0–1 1 1 1
Frequency protection
Table continues on next page

Bay control REC650 15


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 3 1MRK 511 288-UEN B
Available functions

IEC 61850 or ANSI Function description Bay


Function name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
REC650

3Ph/1CBA

BCAB
SAPTUF 81 Underfrequency function 0–2 2 2 2
SAPTOF 81 Overfrequency function 0–2 2 2 2
SAPFRC 81 Rate-of-change frequency protection 0–2 2 2 2

3.2 Control and monitoring functions GUID-C4EC0541-2883-4185-90AB-BAEB25A5E249 v7

IEC 61850 or ANSI Function description Bay


Function name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
REC650

3Ph/1CBA

BCAB
Control
SESRSYN 25 Synchrocheck, energizing check, and 0–1 1 1 1
synchronizing
SMBRREC 79 Autorecloser for 3–phase operation 0–1 1 1 1
SLGGIO Logic Rotating Switch for function 15 15 15 15
selection and LHMI presentation
VSGGIO Selector mini switch 20 20 20 20
DPGGIO IEC 61850 generic communication I/O 16 16 16 16
functions double point
SPC8GGIO Single point generic control 8 signals 5 5 5 5
AUTOBITS AutomationBits, command function for 3 3 3 3
DNP3.0
I103CMD Function commands for IEC60870-5-103 1 1 1 1
I103IEDCMD IED commands for IEC60870-5-103 1 1 1 1
I103USRCMD Function commands user defined for 4 4 4 4
IEC60870-5-103
I103GENCMD Function commands generic for 50 50 50 50
IEC60870-5-103
I103POSCMD IED commands with position and select 50 50 50 50
for IEC60870-5-103
Apparatus control and Interlocking
APC8 Apparatus control for single bay, max 8 1 1 1 1
app. (1CB) incl. interlocking
SCILO 3 Logical node for interlocking 8 8 8 8
BB_ES 3 Interlocking for busbar earthing switch 3 3 3 3
A1A2_BS 3 Interlocking for bus-section breaker 2 2 2 2
A1A2_DC 3 Interlocking for bus-section disconnector 3 3 3 3
ABC_BC 3 Interlocking for bus-coupler bay 1 1 1 1
BH_CONN 3 Interlocking for 1 1/2 breaker diameter 1 1 1 1
Table continues on next page

16 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 3
Available functions

IEC 61850 or ANSI Function description Bay


Function name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
REC650

3Ph/1CBA

BCAB
BH_LINE_A 3 Interlocking for 1 1/2 breaker diameter 1 1 1 1
BH_LINE_B 3 Interlocking for 1 1/2 breaker diameter 1 1 1 1
DB_BUS_A 3 Interlocking for double CB bay 1 1 1 1
DB_BUS_B 3 Interlocking for double CB bay 1 1 1 1
DB_LINE 3 Interlocking for double CB bay 1 1 1 1
ABC_LINE 3 Interlocking for line bay 1 1 1 1
AB_TRAFO 3 Interlocking for transformer bay 1 1 1 1
SCSWI Switch controller 8 8 8 8
SXCBR Circuit breaker 3 3 3 3
SXSWI Circuit switch 7 7 7 7
POS_EVAL Evaluation of position indication 8 8 8 8
SELGGIO Select release 1 1 1 1
QCBAY Bay control 1 1 1 1
LOCREM Handling of LR-switch positions 1 1 1 1
LOCREMCTRL LHMI control of Permitted Source To 1 1 1 1
Operate (PSTO)
Secondary system supervision
CCSRDIF 87 Current circuit supervision 0–1 1 1 1
SDDRFUF Fuse failure supervision 0–1 1 1 1
TCSSCBR Breaker close/trip circuit monitoring 3 3 3 3
Logic
SMPPTRC 94 Tripping logic, common 3–phase output 1 1 1 1
TMAGGIO Trip matrix logic 12 12 12 12
OR Configurable logic blocks 283 283 283 283
INVERTER Configurable logic blocks 140 140 140 140
PULSETIMER Configurable logic blocks 40 40 40 40
GATE Configurable logic blocks 40 40 40 40
XOR Configurable logic blocks 40 40 40 40
LOOPDELAY Configurable logic blocks 40 40 40 40
TIMERSET Configurable logic blocks 40 40 40 40
AND Configurable logic blocks 280 280 280 280
SRMEMORY Configurable logic blocks 40 40 40 40
RSMEMORY Configurable logic blocks 40 40 40 40
Q/T Configurable logic blocks Q/T 0–1
ANDQT Configurable logic blocks Q/T 0–120 120 120 120
ORQT Configurable logic blocks Q/T 0–120 120 120 120
INVERTERQT Configurable logic blocks Q/T 0–120 120 120 120
XORQT Configurable logic blocks Q/T 0–40 40 40 40
Table continues on next page

Bay control REC650 17


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 3 1MRK 511 288-UEN B
Available functions

IEC 61850 or ANSI Function description Bay


Function name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
REC650

3Ph/1CBA

BCAB
SRMEMORYQT Configurable logic blocks Q/T 0–40 40 40 40
RSMEMORYQT Configurable logic blocks Q/T 0–40 40 40 40
TIMERSETQT Configurable logic blocks Q/T 0–40 40 40 40
PULSETIMERQT Configurable logic blocks Q/T 0–40 40 40 40
INVALIDQT Configurable logic blocks Q/T 0–12 12 12 12
INDCOMBSPQT Configurable logic blocks Q/T 0–20 20 20 20
INDEXTSPQT Configurable logic blocks Q/T 0–20 20 20 20
FXDSIGN Fixed signal function block 1 1 1 1
B16I Boolean 16 to Integer conversion 16 16 16 16
B16IFCVI Boolean 16 to Integer conversion with 16 16 16 16
logic node representation
IB16A Integer to Boolean 16 conversion 16 16 16 16
IB16FCVB Integer to Boolean 16 conversion with 16 16 16 16
logic node representation
TEIGGIO Elapsed time integrator with limit 12 12 12 12
transgression and overflow supervision
Monitoring
CVMMXN Measurements 6 6 6 6
CMMXU Phase current measurement 10 10 10 10
VMMXU Phase-phase voltage measurement 6 6 6 6
CMSQI Current sequence component 6 6 6 6
measurement
VMSQI Voltage sequence measurement 6 6 6 6
VNMMXU Phase-neutral voltage measurement 6 6 6 6
AISVBAS Function block for service values 1 1 1 1
presentation of the analog inputs
TM_P_P2 Function block for service values 1 1 1 1
presentation of primary analog inputs
600TRM
AM_P_P4 Function block for service values 1 1 1 1
presentation of primary analog inputs
600AIM
TM_S_P2 Function block for service values 1 1 1 1
presentation of secondary analog inputs
600TRM
AM_S_P4 Function block for service values 1 1 1 1
presentation of secondary analog inputs
600AIM
CNTGGIO Event counter 5 5 5 5
L4UFCNT Event counter with limit supervision 12 12 12 12
DRPRDRE Disturbance report 1 1 1 1
AnRADR Analog input signals 4 4 4 4
BnRBDR Binary input signals 6 6 6 6
Table continues on next page

18 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 3
Available functions

IEC 61850 or ANSI Function description Bay


Function name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
REC650

3Ph/1CBA

BCAB
SPGGIO IEC 61850 generic communication I/O 64 64 64 64
functions
SP16GGIO IEC 61850 generic communication I/O 16 16 16 16
functions 16 inputs
MVGGIO IEC 61850 generic communication I/O 16 16 16 16
functions
MVEXP Measured value expander block 66 66 66 66
LMBRFLO Fault locator 0–1 1 1
SPVNZBAT Station battery supervision 0–1 1 1 1
SSIMG 63 Insulation gas monitoring function 0–1 1 1 1
SSIML 71 Insulation liquid monitoring function 0–1 1 1 1
SSCBR Circuit breaker condition monitoring 0–1 1 1 1
I103MEAS Measurands for IEC60870-5-103 1 1 1 1
I103MEASUSR Measurands user defined signals for 3 3 3 3
IEC60870-5-103
I103AR Function status auto-recloser for 1 1 1 1
IEC60870-5-103
I103EF Function status earth-fault for 1 1 1 1
IEC60870-5-103
I103FLTPROT Function status fault protection for 1 1 1 1
IEC60870-5-103
I103IED IED status for IEC60870-5-103 1 1 1 1
I103SUPERV Supervison status for IEC60870-5-103 1 1 1 1
I103USRDEF Status for user defined signals for 20 20 20 20
IEC60870-5-103
Metering
PCGGIO Pulse counter 16 16 16 16
ETPMMTR Function for energy calculation and 3 3 3 3
demand handling

3.3 Station communication GUID-22F345AB-6250-40E7-9B80-36EA4D8EDA62 v6

IEC 61850 or Function ANSI Function description Bay


name
REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
3Ph/1CBA
REC650

BCAB

Station communication
IEC61850-8-1 IEC 61850 communication protocol 1 1 1 1
DNPGEN DNP3.0 communication general 1 1 1 1
protocol
Table continues on next page

Bay control REC650 19


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 3 1MRK 511 288-UEN B
Available functions

IEC 61850 or Function ANSI Function description Bay


name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
3Ph/1CBA
REC650

BCAB
RS485DNP DNP3.0 for RS-485 communication 1 1 1 1
protocol
CH1TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
CH2TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
CH3TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
CH4TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
OPTICALDNP DNP3.0 for optical RS-232 1 1 1 1
communication protocol
MSTSERIAL DNP3.0 for serial communication 1 1 1 1
protocol
MST1TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
MST2TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
MST3TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
MST4TCP DNP3.0 for TCP/IP communication 1 1 1 1
protocol
RS485GEN RS485 1 1 1 1
OPTICALPROT Operation selection for optical serial 1 1 1 1
RS485PROT Operation selection for RS485 1 1 1 1
DNPFREC DNP3.0 fault records for TCP/IP 1 1 1 1
communication protocol
OPTICAL103 IEC60870-5-103 Optical serial 1 1 1 1
communication
RS485103 IEC60870-5-103 serial communication 1 1 1 1
for RS485
GOOSEINTLKRCV Horizontal communication via GOOSE 59 59 59 59
for interlocking
GOOSEBINRCV GOOSE binary receive 4 4 4 4
ETHFRNT Ethernet configuration of front port, 1 1 1 1
ETHLAN1 LAN1 port and gateway
GATEWAY
ETHLAN1_AB Ethernet configuration of LAN1 port 1
PRPSTATUS System component for parallell 1
redundancy protocol
CONFPROT IED Configuration Protocol 1 1 1 1
ACTIVLOG Activity logging parameters 1 1 1 1
SECALARM Component for mapping security 1 1 1 1
events on protocols such as DNP3 and
IEC103
Table continues on next page

20 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 3
Available functions

IEC 61850 or Function ANSI Function description Bay


name

REC650 (A02)

REC650 (A07)
REC650 (A01)

3Ph/1CBAB
3Ph/1CBA
REC650

BCAB
AGSAL Generic security application 1 1 1 1
component
GOOSEDPRCV GOOSE function block to receive a 32 32 32 32
double point value
GOOSEINTRCV GOOSE function block to receive an 32 32 32 32
integer value
GOOSEMVRCV GOOSE function block to receive a 16 16 16 16
measurand value
GOOSESPRCV GOOSE function block to receive a 64 64 64 64
single point value

3.4 Basic IED functions GUID-1DA8FC6E-D726-407B-84D3-0796B00D636F v5

IEC 61850/Function Function description


block name
Basic functions included in all products
INTERRSIG Self supervision with internal event list 1
SELFSUPEVLST Self supervision with internal event list 1
TIMESYNCHGEN Time synchronization 1
SNTP Time synchronization 1
DTSBEGIN, DTSEND, Time synchronization, daylight saving 1
TIMEZONE
IRIG-B Time synchronization 1
SETGRPS Setting group handling 1
ACTVGRP Parameter setting groups 1
TESTMODE Test mode functionality 1
CHNGLCK Change lock function 1
PRIMVAL Primary system values 1
SMAI_20_1 - Signal matrix for analog inputs 2
SMAI_20_12
3PHSUM Summation block 3 phase 12
GBASVAL Global base values for settings 6
ATHSTAT Authority status 1
ATHCHCK Authority check 1
AUTHMAN Authority management 1
FTPACCS FTPS access with password 1
DOSFRNT Denial of service, frame rate control for front port 1
DOSLAN1 Denial of service, frame rate control for LAN1A and LAN1B ports 1
DOSSCKT Denial of service, socket flow control 1

Bay control REC650 21


Commissioning manual
© Copyright 2013 ABB. All rights reserved
22
1MRK 511 288-UEN B Section 4
Starting up

Section 4 Starting up
4.1 Factory and site acceptance testing GUID-38C2B5FA-9210-4D85-BA21-39CE98A1A84A v2

Testing the proper IED operation is carried out at different occasions, for example:

• Acceptance testing
• Commissioning testing
• Maintenance testing

This manual describes the workflow and the steps to carry out the commissioning testing.

Factory acceptance testing (FAT) is typically done to verify that the IED and its corresponding
configuration meet the requirements of the utility or industry. This test is the most complex
and in depth, as it is done to familiarize the user with a new product or to verify a new
configuration. The complexity of this testing depends on several factors, such as:

• New IED type


• New configuration
• Modified configuration

Site acceptance testing (SAT or commissioning testing) is typically done to verify that the
installed IED is correctly set and connected to the power system. SAT requires that the
acceptance testing has been performed and that the application configuration is verified.

Maintenance testing is a periodic verification that the IED is healthy and has correct settings,
depending on changes in the power system. There are also other types of maintenance
testing.

4.2 Commissioning checklist GUID-93D14E4E-5DDE-4D37-84A6-2DF0656AB73D v3

Before starting up commissioning at site, check that the following items are available.

• Single line diagram


• Protection block diagram
• Circuit diagram
• Setting list and configuration
• RJ-45 Ethernet cable (CAT 5)
• Three-phase test kit or other test equipment depending on the complexity of the
configuration and functions to be tested.
• PC with PCM600 installed along with the connectivity packages corresponding to the IEDs
to be tested.
• Administration rights on the PC, to set up IP addresses
• Product documentation (engineering manual, installation manual, commissioning manual,
operation manual, technical manual and communication protocol manual)

Bay control REC650 23


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 4 1MRK 511 288-UEN B
Starting up

4.3 Checking the power supply M11725-2 v4.1.1

Insert only the corresponding male connector to the female connector.


Inserting anything else (such as a measurement probe) may violate the female
connector and prevent a proper electrical contact between the printed circuit
board and the external wiring connected to the screw terminal block.

Check that the auxiliary supply voltage remains within the permissible input voltage range
under all operating conditions. Check that the polarity is correct before powering the IED.

Table 1: Supervision Power Supply


Battery Supervision BATS Logic Led Battery VS+ (output voltage)
Station Battery Output Ready VS+ Supervision VS+ Output
Active Active 1 On > 15.1 V > 33.5 V
Active 0 Off < 14.6 V > 33.5 V
Active 0 On > 15.1 V < 32.9 V
0 Off < 14.6 V < 32.9 V

4.4 Energizing the IED

4.4.1 Checking the IED operation M11726-2 v6

Check all connections to external circuitry to ensure correct installation, before energizing the
IED and carrying out the commissioning procedures.

Energize the power supply of the IED to start it up. This could be done in a number of ways,
from energizing a whole cubicle to energizing a single IED. Set the IED time if no time
synchronization source is configured. Check the self-supervision function in Main menu/
Diagnostics/Internal events or Main menu/Diagnostics/IED status/General menu in local
HMI to verify that the IED is functioning properly.

4.4.2 IED start-up sequence M11727-3 v9

The following sequence is expected when the IED is energized.

• The green Ready LED starts flashing instantly and the ABB logo is shown on the LCD.
• After approximately 30 seconds, "Starting" is shown on the LCD.
• Within 90 seconds, the main menu is shown on the LCD and the green Ready LED shows a
steady light, which indicates a successful startup.

The startup time depends on the size of the application configuration.


Application configurations with less functionality have shorter startup times.

If the green Ready LED continues to flash after startup, the IED has detected an internal error.
Navigate via Main menu/Diagnostics/IED status/General to investigate the error description.

24 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 4
Starting up

4.5 Setting up communication between PCM600 and the


IED SEMOD58570-5 v9

The communication between the IED and PCM600 is independent of the communication
protocol used within the substation or to the NCC.

The communication media is always Ethernet and the used protocol is TCP/IP.

Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connector
shall be used for communication with PCM600..

When an Ethernet-based station protocol is used, PCM600 communication can use the same
Ethernet port and IP address.

To connect PCM600 to the IED, two basic variants must be considered.

• Direct point-to-point link between PCM600 and the IED front port.
• Indirect link via a station LAN or from remote via a network.

The physical connection and the IP address must be configured in both cases to enable
communication.

The communication procedures are the same in both cases.

1. If needed, set the IP address for the IEDs.


2. Set up the PC or workstation for a direct link (point-to-point), or
3. Connect the PC or workstation to the LAN/WAN network.
4. Configure the IED IP addresses in the PCM600 project for each IED to match the IP
addresses of the physical IEDs.

Setting up IP addresses
The IP address and the corresponding mask must be set via the LHMI for each available
Ethernet interface in the IED. Each Ethernet interface has a default factory IP address when the
IED is delivered. This is not given when an additional Ethernet interface is installed or an
interface is replaced.

• The default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.255.0, which can be set via the local HMI path Main menu/
Configuration/Communication/TCP-IP configuration/ETHFRNT:1.

Setting up the PC or workstation for point-to-point access to IEDs front


port
A special cable is needed to connect two physical Ethernet interfaces together without a hub,
router, bridge or switch in between. The Tx and Rx signal wires must be crossed in the cable to
connect Tx with Rx on the other side and vice versa. These cables are known as cross over
cables. The maximum length is 2 m. The connector type is RJ-45.

Bay control REC650 25


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 4 1MRK 511 288-UEN B
Starting up

IED RJ-45
PCM600

Tx Tx
Rx Rx
IEC09000096-2-en.vsd
IEC09000096 V2 EN-US

Figure 2: Point-to-point link between IED and PCM600 using a null-modem cable
The following description is an example valid for standard PCs using Microsoft Windows
operating system. The example is taken from a Laptop with one Ethernet interface.

Administrator rights are required to change the PC communication setup.


Some PCs have the feature to automatically detect that Tx signals from the IED
are received on the Tx pin on the PC. Thus, a straight (standard) Ethernet cable
can be used.

When a PC is connected to the IED and the setting DHCPServer is set to On via the local HMI
path Main menu/Configuration/Communication/TCP-IP configuration/ETHFRNT:1/
DHCPServer, the IEDs DHCP server for the front port assigns an IP address for the PC. The PC
must be configured to obtain its IP address automatically as described in the following
procedure.

1. Select Search programs and files in the Start menu in Windows.

26 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 4
Starting up

IEC13000057-1-en.vsd
IEC13000057 V1 EN-US

Figure 3: Select: Search programs and files


2. Type View network connections and click on the View network connections icon.

Bay control REC650 27


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 4 1MRK 511 288-UEN B
Starting up

IEC13000058-1-en.vsd
IEC13000058 V1 EN-US

Figure 4: Click View network connections


3. Right-click and select Properties.

IEC13000059-1-en.vsd
IEC13000059 V1 EN-US

Figure 5: Right-click Local Area Connection and select Properties


4. Select the TCP/IPv4 protocol from the list of configured components using this
connection and click Properties.

28 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 4
Starting up

IEC13000060-1-en.vsd
IEC13000060 V1 EN-US

Figure 6: Select the TCP/IPv4 protocol and open Properties


5. Select Obtain an IP address automatically if the parameter DHCPServer is set to On in the
IED.

IEC13000061-1-en.vsd
IEC13000061 V1 EN-US

Figure 7: Select: Obtain an IP address automatically


6. Select Use the following IP address and define IP address and Subnet mask if the front
port is used and if the IP address is not set to be obtained automatically by the IED, see
Figure 8. The IP address must be different from the IP address chosen for the IED.

Bay control REC650 29


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 4 1MRK 511 288-UEN B
Starting up

IEC13000062-1-en.vsd
IEC13000062 V1 EN-US

Figure 8: Select: Use the following IP address


7. Close all open windows and start PCM600.

Setting up the PC to access the IED via a network


This task depends on the used LAN/WAN network.

The PC and IED must belong to the same subnetwork for this set-up to work.

4.6 Writing an application configuration to the IED M11734-2 v5

Ensure that the IED includes the correct application configuration according to
project specifications.

The application configuration is created using PCM600 and then written to the IED. Establish a
connection between PCM600 and the IED when an application configuration must be written
to the IED.

After writing an application configuration to the IED, the IED makes an application restart or a
complete IED restart, when necessary.

The IED does not restart after reconfiguring IEC61850 (regardless of whether
the protocol is enabled or disabled).

Be sure to set the correct technical key in both the IED and PCM600 to prevent
writing an application configuration to a wrong IED.

30 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 4
Starting up

See the engineering manual for information on how to create or modify an


application configuration and how to write to the IED.

4.7 Checking CT circuits M12182-2 v13

Check that the wiring is in strict accordance with the supplied connection
diagram.

• Primary injection test to verify the current ratio of the CT, the correct wiring up to the
protection IED and correct phase sequence connection (that is L1, L2, L3.)
• CT secondary loop resistance measurement to confirm that the current transformer
secondary loop DC resistance is within specification and that there are no high resistance
joints in the CT winding or wiring.
• Earthing check of the individual CT secondary circuits to verify that each three-phase set
of main CTs is properly connected to the station earth and only at one electrical point.
• Insulation resistance check.

CT and VT connectors are pre-coded, and the CT and VT connector markings


are different. For more information, see the installation manual.

Both the primary and the secondary sides must be disconnected from the line
and the IED when plotting the excitation characteristics.

4.8 Checking VT circuits M11724-2 v8

Check that the wiring is in strict accordance with the supplied connection diagram.

Correct possible errors before continuing to test the circuitry.

Test the circuitry.

• Polarity check
• VT circuit voltage measurement (primary injection test)
• Earthing check
• Phase relationship
• Insulation resistance check

The polarity check verifies the integrity of circuits and the phase relationships. The check must
be performed as close to the IED as possible.

The primary injection test verifies the VT ratio and the wiring all the way from the primary
system to the IED. Injection must be performed for each phase-to-neutral circuit and each
phase-to-phase pair. In each case, voltages in all phases and neutral are measured.

Bay control REC650 31


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 4 1MRK 511 288-UEN B
Starting up

4.9 Using the RTXP test switch GUID-F1E29C06-7FE8-44D8-AD5A-EE8990A2AA41 v3

The RTXP test switch is designed to provide the means of safe testing of the IED. This is
achieved by the electromechanical design of the test switch and test plug handle. When the
test plug handle is inserted, it first blocks the trip and alarm circuits then it short circuits the
CT secondary circuit and opens the VT secondary circuits making the IED available for
secondary injection.

When pulled out, the test handle is mechanically stopped in half withdrawn position. In this
position, the current and voltage enter the protection, but the alarm and trip circuits are still
isolated. Before removing the test handle, check that no trip or alarms are present in the IED.

Not until the test handle is completely removed, the trip and alarm circuits are restored for
operation.

Verify that the contact sockets have been crimped correctly and that they are
fully inserted by tugging on the wires. Never do this with current circuits in
service.

Current circuit

1. Verify that the contacts are of current circuit type.


2. Verify that the short circuit jumpers are located in the correct slots.

Voltage circuit

1. Verify that the contacts are of voltage circuit type.


2. Check that no short circuit jumpers are located in the slots dedicated for voltage.

Trip and alarm circuits

1. Check that the correct types of contacts are used.

4.10 Checking binary input and output circuits


GUID-231F80F2-B09C-47B0-BB25-7DF412B7A2E5 v1

Insert only the corresponding male connector to the female connector.


Inserting anything else (such as a measurement probe) may violate the female
connector and prevent a proper electrical contact between the printed circuit
board and the external wiring connected to the screw terminal block.

4.10.1 Binary input circuits M11722-4 v3

Preferably, disconnect the binary input connector from the binary input cards. Check all
connected signals so that both input level and polarity are in accordance with the IED
specifications.

32 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 4
Starting up

4.10.2 Binary output circuits M11722-8 v3

Preferably, disconnect the binary output connector from the binary output cards. Check all
connected signals so that both load and polarity are in accordance with IED specifications.

4.11 Checking optical connections M16022-2 v6

Check that the Tx and Rx optical connections are correct.

An IED equipped with optical connections requires a minimum depth of 180


mm for plastic fiber cables and 275 mm for glass fiber cables. Check the
allowed minimum bending radius from the optical cable manufacturer.

Bay control REC650 33


Commissioning manual
© Copyright 2013 ABB. All rights reserved
34
1MRK 511 288-UEN B Section 5
Establishing connection and verifying the IEC 61850 station communication

Section 5 Establishing connection and


verifying the IEC 61850 station
communication
5.1 Setting the station communication SEMOD172108-3 v7

To enable IEC 61850 station communication:

• The IEC 61850-8-1 station communication functionality must be on in the local HMI.
Navigate to Main menu/Configuration/Communication/Station communication/
IEC61850-8-1:1 and set the Operation parameter to On.
• To enable GOOSE communication the Operation parameter for the corresponding GOOSE
function blocks (GOOSEBINRCV and GOOSEINTLKRCV) must be set to On in the
application configuration.
• To enable GOOSE communication via the front port the parameter PortSelGOOSE in Main
menu/Configuration/Communication/Station communication/IEC61850-8-1:1 must be
set to Front. To enable GOOSE communication via rear port the parameter PortSelGOOSE
must be set to LAN1.
• To enable MMS communication via the rear port the parameter PortSelMMS in Main
menu/Configuration/Communication/Station communication/IEC61850-8-1:1 must be
set to LAN1.

5.2 Verifying the station communication SEMOD172108-24 v7

Connect your PC to the substation network and ping the connected IED and the Substation
Master PC, to verify that the communication is working (up to the transport layer).

The best way to verify the communication up to the application layer is to use protocol
analyzer connected to the substation bus, and monitor the communication.

Bay control REC650 35


Commissioning manual
© Copyright 2013 ABB. All rights reserved
36
1MRK 511 288-UEN B Section 6
Testing IED operation

Section 6 Testing IED operation


6.1 Preparing the IED to verify settings M11741-2 v9

If a test switch is included, start preparation by making the necessary connections to the test
switch. This means connecting the test equipment according to a specific and designated IED
terminal diagram.

Put the IED into the test mode to facilitate the test of individual functions and prevent
unwanted operation caused by other functions. The busbar differential protection is not
included in the test mode and is not prevented to operate during the test operations. The test
switch should then be connected to the IED.

Verify that analog input signals from the analog input module are measured and recorded
correctly by injecting currents and voltages required by the specific IED.

To make testing even more effective, use PCM600. PCM600 includes the Signal monitoring
tool, which is useful in reading the individual currents and voltages, their amplitudes and
phase angles. In addition, PCM600 contains the Disturbance handling tool. The content of
reports generated by the Disturbance handling tool can be configured which makes the work
more efficient. For example, the tool may be configured to only show time tagged events and
to exclude analog information and so on.

Check the disturbance report settings to ensure that the indications are correct.

For test functions and test and signal parameter names, see the technical manual. The correct
initiation of the disturbance recorder is made on start and/or release or trip from a function.
Also check that the wanted recordings of analog (real and calculated) and binary signals are
achieved.

The IEDs in the 650 series can have between 1 and 4 individual parameter setting groups
prepared with full sets of different parameters for all functions. The purpose of these groups
is to be able to handle different power system load conditions to optimize the parameters
settings of the different functions for these different power systems conditions (for example
summer/winter and day/night).

Parameters can be entered into different setting groups. Make sure to test
functions for the same parameter setting group. If needed, repeat the tests for
all different setting groups used. The difference between testing the first
parameter setting group and the remaining is that there is no need for testing
the connections.

During testing, observe that the right testing method, that corresponds to the actual
parameters set in the activated parameter setting group, is used.

In the local HMI the sensitive directional earth fault protection SDEPSDE parameter group 4 is
active indicated by the * next to #4 and the test of the SDEPSDE must be performed according
to the instructions given for the setting OpMode and setting value 3I03U0cosfi.

Set and configure the function(s) before testing. Most functions are highly flexible and permit
a choice of functional and tripping modes. The various modes are checked at the factory as
part of the design verification. In certain cases, only modes with a high probability of coming
into operation need to be checked when commissioned to verify the configuration and
settings.

Requirements for testing the function.

Bay control REC650 37


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 6 1MRK 511 288-UEN B
Testing IED operation

• Calculated settings
• Valid configuration diagram for the IED
• Valid terminal diagram for the IED
• Technical manual
• Three-phase test equipment

Content of the technical manual.

• Application and functionality summaries


• Function blocks
• Logic diagrams
• Input and output signals
• A list of setting parameters
• Technical data for the function

The test equipment should be able to provide a three-phase supply of currents and three-
phase voltage. The magnitude and angle of currents (and voltages) should be possible to vary.
Check that the IED is prepared for test before starting the test session. Consider the logic
diagram of the function when performing the test.

The response from a test can be viewed in different ways.

• Binary output signals


• Service values in the local HMI (logical signal or phasors)
• Using the online mode in the PCM600 configuration software

Do not switch off the auxiliary power supply to the IED before changes, for
example, setting parameter or local/remote control state changes are saved.

A mechanism for limiting the number of writings per time period is included in the IED to
prevent the flash memory to be worn out due to too many writings. As a consequence it may
take up to an hour to save changes. If the auxiliary power is interrupted before a change is
saved, that change is lost.

6.2 Activating the test mode M11412-2 v10

Put the IED into the test mode before testing. The test mode blocks all protection functions
and some of the control functions in the IED, and the individual functions to be tested can be
unblocked to prevent unwanted operation caused by other functions. In this way, it is possible
to test slower back-up measuring functions without the interference from faster measuring
functions. The busbar differential protection is not included in the test mode and is not
prevented to operate during the test operations. The test switch should then be connected to
the IED.Test mode is indicated when the yellow StartLED flashes. The control functions not
blocked when the IED enters test mode are listed in the following table:

Function Function Name Description


Group
Control DPGGIO IEC 61850 generic communication I/O functions double point
Control QCBAY Bay control
Control QCRSV Bay reserve
Control SCILO Logical node for interlocking
Control SCSWI Switch controller
Table continues on next page

38 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 6
Testing IED operation

Function Function Name Description


Group
Control SELGGIO Select release
Control SXCBR Circuit breaker
Control SXSWI Circuit switch
Control TCMYLTC Tap changer control and supervision, 6 binary inputs
Control VCTRRCV Voltage control receiving block for GOOSE

1. Select Main menu/Tests/IED test mode/TESTMODE:1


2. Set parameter TestMode to On.
3. Save the changes.
As a consequence, the yellow startLED starts flashing as a reminder and remains flashing
until the test mode is switched off.

6.3 Preparing the connection to the test equipment M11743-2 v7

The IED can be equipped with a test switch of type RTXP8, RTXP18 or RTXP24. The test switch
and its associated test plug handle (RTXH8, RTXH18 or RTXH24) are a part of the COMBITEST
system, which provides secure and convenient testing of the IED.

When using the COMBITEST, preparations for testing are automatically carried out in the
proper sequence, that is, for example, blocking of tripping circuits, short circuiting of CT’s,
opening of voltage circuits, making IED terminals available for secondary injection. Terminals 1
and 8, 1 and 18 as well as 1 and 12 of the test switches RTXP8, RTXP18 and RTXP24 respectively
are not disconnected as they supply DC power to the protection IED.

The RTXH test-plug handle leads may be connected to any type of test equipment or
instrument. When a number of protection IEDs of the same type are tested, the test-plug
handle only needs to be moved from the test switch of one protection IED to the test switch of
the other, without altering the previous connections.

Use COMBITEST test system to prevent unwanted tripping when the handle is withdrawn,
since latches on the handle secure it in the half withdrawn position. In this position, all
voltages and currents are restored and any re-energizing transients are given a chance to
decay before the trip circuits are restored. When the latches are released, the handle can be
completely withdrawn from the test switch, restoring the trip circuits to the protection IED.

If a test switch is not used, perform measurement according to the provided circuit diagrams.

Never disconnect the secondary connection of a current transformer circuit


without first short-circuiting the transformer's secondary winding. Operating a
current transformer with the secondary winding open will cause a massive
potential build up that may damage the transformer and cause personal injury.

6.4 Connecting the test equipment to the IED M11744-2 v7

Connect the test equipment according to the IED specific connection diagram and the needed
input and output signals for the function under test. An example of a connection is shown in
figure 9.

Bay control REC650 39


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 6 1MRK 511 288-UEN B
Testing IED operation

Connect the current and voltage terminals. Pay attention to the current polarity. Make sure
that the connection of input and output current terminals and the connection of the residual
current conductor is correct. Check that the input and output logical signals in the logic
diagram for the function under test are connected to the corresponding binary inputs and
outputs of the IED under test.

To ensure correct results, make sure that the IED as well as the test equipment
are properly earthed before testing.

IL1 IL1
IL2 IL2
IL3 IL3
IN IN
Test equipment

UL1 UL1
UL2

IED
UL2
UL3 UL3
N N
UN
TRIP

IEC 61850
IEC09000643-1-en.vsd
IEC09000643 V1 EN-US

Figure 9: Connection example of the test equipment to the IED when test equipment is
connected to the transformer input module

6.5 Releasing the function to be tested M11413-2 v6

Release or unblock the function to be tested. This is done to ensure that only the function or
the chain of functions to be tested are in operation and that other functions are prevented
from operating. Release the tested function(s) by setting the corresponding Blocked
parameter under Function test modes to No in the local HMI.

When testing a function in this blocking feature, remember that not only the actual function
must be activated, but the whole sequence of interconnected functions (from measuring
inputs to binary output contacts), including logic must be activated. Before starting a new test
mode session, scroll through every function to ensure that only the function to be tested (and
the interconnected ones) have the parameters Blocked and eventually EvDisable set to No and
Yes respectively. Remember that a function is also blocked if the BLOCK input signal on the
corresponding function block is active, which depends on the configuration. Ensure that the
logical status of the BLOCK input signal is equal to 0 for the function to be tested. Event
function blocks can also be individually blocked to ensure that no events are reported to a
remote station during the test. This is done by setting the parameter EvDisable to Yes.

40 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 6
Testing IED operation

Any function is blocked if the corresponding setting in the local HMI under Main
menu/Tests/Function test modes menu remains On, that is, the parameter
Blocked is set to Yes and the parameter TestMode under Main menu/
Tests/IED test mode remains active. All functions that were blocked or
released in a previous test mode session, that is, the parameter Test mode is
set to On, are reset when a new test mode session is started.

Procedure

1. Click the Function test modes menu.


The Function test modes menu is located in the local HMI under Main menu/Tests/
Function test modes.
2. Browse to the function instance that needs to be released.
3. Set parameter Blocked for the selected function to No.

6.6 Verifying analog primary and secondary measurement M11745-2 v10

Verify that the connections are correct and that measuring and scaling is done correctly. This
is done by injecting current and voltage to the IED.

Apply input signals as needed according to the actual hardware and the
application configuration.

1. Inject a symmetrical three-phase voltage and current at rated value.


2. Compare the injected value with the measured values.
The voltage and current phasor menu in the local HMI is located under Main menu/
Measurements/Analog primary values and Main menu/Measurements/Analog
secondary values.
3. Compare the frequency reading with the set frequency and the direction of the power.
The frequency and active power are located under Main menu/Tests/Function status/
Monitoring/CVMMXN/CVMMXN:1/Outputs. Then navigate to the bottom of the list to
find the frequency.

Check both analog primary and secondary values, because then the CT
and VT ratios entered into the IED are also checked.

These checks shall be repeated for Analog primary values.


4. Inject an unsymmetrical three-phase voltage and current, to verify that phases are
correctly connected.

If some setting deviates, check the analog input settings under

Main menu/Configuration/Analog modules

Measured values such as current and voltages as well as active, reactive and apparent power,
power factor phase angles as well as positive and negative and zero sequence currents and
voltages are available in the local HMI under Main menu/Tests/Function status/Monitoring.

Navigate to the measurement function that contains the quantity to be checked.

Bay control REC650 41


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 6 1MRK 511 288-UEN B
Testing IED operation

Table 2: Measurement functions


Function Quantity Description
CMMXU IL1 to IL3 amplitude, range and angle
CMSQI 3I0; I1 and I2 amplitude, range and angle

CVMMXN S; P; Q; PF; Ilag; Ilead; U; I and f amplitude, range and angle


VMMXU UL12 to UL31 i.e. phase-to-phase amplitude, range and angle
VMSQI 3U0; U1 and U2 amplitude, range and angle

VNMMXU UL1 to UL3 i.e. phase-to-neutral amplitude, range and angle

Also the Signal Monitoring tool in PCM600 can be used to read the measured values. In many
cases it is more convenient to use PCM600 since, among many things, reports on measured
values can be exported from the Signal Monitoring tool to other tools (for example, MS Excel)
for further analysis.

6.7 Testing the protection functionality GUID-125B6F28-D3E5-4535-9CD6-6C056B79F496 v2

Each protection function must be tested individually by secondary injection.

• Verify operating levels (trip) and timers.


• Verify alarm and blocking signals.
• Use the disturbance handling tool in PCM600 to evaluate that the protection function has
received the correct data and responded correctly (signaling and timing).
• Use the event viewer tool in PCM600 to check that only expected events have occurred.

42 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Section 7 Testing functionality


7.1 Testing disturbance report

7.1.1 Introduction M17101-2 v5

The following sub-functions are included in the disturbance report function:

• Disturbance recorder
• Event list
• Event recorder
• Trip value recorder
• Indications

If the disturbance report is set on, then its sub-functions are also set up and so it is not
possible to only switch these sub-functions off. The disturbance report function is switched
off (parameter Operation = Off) in PCM600 or the local HMI under Main menu/Settings/IED
Settings/Monitoring/Disturbance report/DRPRDRE:1.

7.1.2 Disturbance report settings M11746-2 v5

When the IED is in test mode, the disturbance report can be made active or inactive. If the
disturbance recorder is turned on during test mode, recordings will be made. When test mode
is switched off all recordings made during the test session are cleared.

Setting OpModeTest for the control of the disturbance recorder during test mode are located
on the local HMI under Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DRPRDRE:1.

7.2 Identifying the function to test in the technical


reference manual M11748-2 v3

Use the technical manual to identify function blocks, logic diagrams, input and output signals,
setting parameters and technical data.

7.3 Testing current protection functions

7.3.1 Instantaneous phase overcurrent protection 3-phase output


PHPIOC M11754-3 v7.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for PHPIOC are available on the local HMI under Main menu/
Tests/Function status/Current/PHPIOC(50,I>>)/PHPIOC:1. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.

To verify the settings the following fault type should be tested:

• Phase-to-earth fault

Bay control REC650 43


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

Ensure that the maximum continuous current, supplied from the current source used for the
test of the IED, does not exceed four times the rated current value of the IED.

7.3.1.1 Measuring the operate limit of set values M11754-11 v4

1. Inject a phase current into the IED with an initial value below that of the setting.
2. Increase the injected current until the TRIP signal appears.
3. Switch the fault current off.

Observe: Do not exceed the maximum permitted overloading of the


current circuits in the IED.

4. Compare the measured operating current with the set value.

7.3.1.2 Completing the test M11754-24 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
PHPIOC(50,I>>)/PHPIOC:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.3.2 Four step phase overcurrent protection 3-phase output


OC4PTOC SEMOD56287-67 v6.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for OC4PTOC are available on the local HMI under Main menu/
Tests/Function status/Current/OC4PTOC(51_67,4I>)/OC4PTOC:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.3.2.1 Verifying the settings SEMOD56287-72 v5

1. Connect the test set for current injection to the appropriate IED phases.
If there is any configuration logic that is used to enable or block any of the four available
overcurrent steps, make sure that the step under test is enabled (for example, end fault
protection).
Connect the symmetrical three-phase injection current into phases L1, L2 and L3.
2. Connect the test set for the appropriate three-phase voltage injection to the IED phases
L1, L2 and L3. The protection shall be fed with a symmetrical three-phase voltage.
3. Set the injected polarizing voltage slightly larger than the set minimum polarizing voltage
(default is 5% of UBase) and set the injection current to lag the appropriate voltage by an
angle of 55° if forward directional function is selected.
If 1 out of 3 currents for operation is chosen: The voltage angle of phase L1 is the
reference.
If reverse directional function is selected, set the injection current to lag the polarizing
voltage by an angle equal to 235° (equal to 55° + 180°).
4. Increase the injected current and note the operate value of the tested step of the
function.
5. Decrease the current slowly and note the reset value.

44 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

6. If the test has been performed by injection of current in phase L1, repeat the test,
injecting current into phases L2 and L3 with polarizing voltage connected to phases L2,
respectively L3 (1 out of 3 currents for operation).
7. If the test has been performed by injection of current in phases L1 – L2, repeat the test,
injecting current into phases L2 – L3 and L3 – L1 with the appropriate phase angle of
injected currents.
8. Block higher set stages when testing lower set stages by following the procedure
described below.
9. Connect a trip output contact to a timer.
10. Set the injected current to 200% of the operate level of the tested stage, switch on the
current and check the time delay.
For inverse time curves, check the operate time at a current equal to 110% of the operate
current for txMin.
11. Check that all trip and start contacts operate according to the configuration (signal
matrixes)
12. Reverse the direction of the injected current and check that the protection does not
operate.
13. Repeat the above described tests for the higher set stages.
14. Finally check that start and trip information is stored in the event menu.

Verification of the non-directional phase overcurrent function is done as


instructed above, without applying any polarizing voltage.

7.3.2.2 Completing the test SEMOD56287-118 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
OC4PTOC(51_67,4I>)/OC4PTOC:1 for the function, or for each individual function in a chain, to
be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.3.3 Instantaneous residual overcurrent protection EFPIOC SEMOD52967-3 v6.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for EFPIOC are available on the local HMI under Main menu/Tests/
Function status/Current/EFPIOC(50N,IN>>)/EFPIOC:1. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.

To verify the settings the following fault type should be tested:

• Phase-to-earth fault

Ensure that the maximum continuous current, supplied from the current source used for the
test of the IED, does not exceed four times the rated current value of the IED.

7.3.3.1 Measuring the operate limit of set values SEMOD52967-11 v5

Bay control REC650 45


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

1. Inject a phase current into the IED with an initial value below that of the setting.
2. Increase the injected current in the Ln or in the neutral (summated current input) phase
until the TRIP signal appears.
3. Switch the fault current off.
Observe to not exceed the maximum permitted overloading of the current circuits in the
IED
4. Compare the measured operating current with the set value.

7.3.3.2 Completing the test SEMOD52967-24 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
EFPIOC(50N,IN>>)/EFPIOC:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.3.4 Four step residual overcurrent protection, zero or negative


sequence direction EF4PTOC SEMOD53296-3 v7.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for EF4PTOC are available on the local HMI under Main menu/
Tests/Function status/Current/EF4PTOC(51N67N,4IN>)/EF4PTOC:X. The Signal Monitoring
in PCM600 shows the same signals that are available on the local HMI.

7.3.4.1 Four step directional residual overcurrent protection SEMOD53296-208 v5

1. Connect the test set for single current injection to the appropriate IED terminals.
Connect the injection current and voltage to terminals L1 and neutral.
2. Set the injected polarizing voltage slightly larger than the set minimum polarizing voltage
(default 1% of Ur) and set the injection current to lag the voltage by an angle equal to the
set reference characteristic angle (AngleRCA), if the forward directional function is
selected.
If reverse directional function is selected, set the injection current to lag the polarizing
voltage by an angle equal to RCA+ 180°.
3. Increase the injected current and note the value at which the studied step of the function
operates.
4. Decrease the current slowly and note the reset value.
5. If the test has been performed by injection of current in phase L1, repeat the test,
injecting current into terminals L2 and L3 with a polarizing voltage connected to
terminals L2, respectively L3.
6. Block lower set steps when testing higher set steps according to the instructions that
follow.
7. Connect a trip output contact to a timer.
8. Set the injected current to 200% of the operate level of the tested step, switch on the
current and check the time delay.
For inverse time curves, check the operate time at a current equal to 110% of the operate
current for txMin.
9. Check that all trip and start contacts operate according to the configuration (signal
matrixes)
10. Reverse the direction of the injected current and check that the step does not operate.

46 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

11. Check that the protection does not operate when the polarizing voltage is zero.
12. Repeat the above described tests for the higher set steps.
13. Finally, check that start and trip information is stored in the event menu.

7.3.4.2 Four step non-directional residual overcurrent protection SEMOD53296-202 v4

1. Do as described in "Four step directional residual overcurrent protection", but without


applying any polarizing voltage.

7.3.4.3 Completing the test SEMOD53296-122 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
EF4PTOC(51N67N,4IN>)/EF4PTOC:X for the function, or for each individual function in a chain,
to be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.3.5 Sensitive directional residual overcurrent and power


protection SDEPSDE SEMOD175060-3 v5.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for SDEPSDE are available on the local HMI under Main menu/
Tests/Function status/Current/SDEPSDE(67N,IN<->)/SDEPSDE:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.3.5.1 Measuring the operate and time limit for set values

Operation mode 3I0 · cosφ


SEMOD175060-34 v6
Procedure

1. Set the polarizing voltage to 1.2 · UNRel> and the phase angle between voltage and
current to the set characteristic angle (RCADir), the current lagging the voltage.
Take setting RCAComp into consideration if not equal to 0.
2. Measure that the operate current of the set directional element is equal to the INcosPhi>
setting.
The I Dir (I0 cos(Angle)) function activates the START and STDIRIN output.
3. Measure with angles j = RCADir +/- 45° that the measuring element operates when I0 cos
(RCADir - j) = I0cos(+/-45) = INcosPhi>.
4. Compare the result with the set value.
Take the set characteristic into consideration, see figure 10 and figure 11.
5. Measure the operate time of the timer by injecting a current two times the set INcosPhi>
value and the polarizing voltage 1.2 · UNRel>.

Tinv = kSN × Sref / 3 I 0 test × cos (j )


IECEQUATION2402 V1 EN-US (Equation 1)

6. Compare the result with the expected value.

Bay control REC650 47


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

The expected value depends on whether definite or inverse time was selected.
7. Set the polarizing voltage to zero and increase until the boolean output signal UNREL is
activated, which is visible in the Application Configuration in PCM600 when the IED is in
online mode. Compare the voltage with the set value UNRel>.
8. Continue to test another function or complete the test by setting the test mode to Off.

RCADir = 0o

3I0
Operate area

j
-3U0 = Uref
3I0 × cos j

ROADir

IEC06000650_2_en.vsd
IEC06000650 V2 EN-US

Figure 10: Characteristic with ROADir restriction

48 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

RCADir = 0º

Operate area

-3U0 =Uref

Instrument
transformer a
RCAcomp
angle error
Characteristic after
angle compensation

3I0 (to prot)


3I0 (prim)

en06000651.vsd
IEC06000651 V2 EN-US

Figure 11: Explanation of RCAcomp

Operation mode 3I0 · 3U0 · cosφ


SEMOD175060-76 v6

1. Set the polarizing voltage to 1.2 · UNRel> and the phase angle between voltage and
current to the set characteristic angle (RCADir), the current lagging the voltage.
2. Measure that the operate power is equal to the SN> setting for the set directional
element.
Note that for operation, both the injected current and voltage must be greater than the
set values INRel> and UNRel> respectively.
The function activates the START and STDIRIN outputs.
3. Measure with angles j = RCADir +/- 45° that the measuring element operates when 3I0 ·
3U0 · cos (RCADir - j) = 3I0 · 3U0 · cos(+/-45) = SN>.
4. Compare the result with the set value. Take the set characteristic into consideration, see
figure 10 and figure 11.
5. Measure the operate time of the timer by injecting 1.2 · UNRel> and a current to get two
times the set SN> operate value.

Tinv = kSN × Sref / 3 I 0 test × 3U 0 test × cos (j )


IECEQUATION2403 V1 EN-US (Equation 2)

6. Compare the result with the expected value.


The expected value depends on whether definite or inverse time was selected.
7. Continue to test another function or complete the test by setting the test mode to Off.

Operation mode 3I0 and φ


SEMOD175060-87 v6

Bay control REC650 49


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

1. Set the polarizing voltage to 1.2 · UNRel> and the phase angle between voltage and
current to the set characteristic angle (RCADir), the current lagging the voltage.
2. Measure that the operate power is equal to the INDir> setting for the set directional
element.

Note that for operation, both the injected current and voltage must be
greater than the set values INRel> and UNRel> respectively.

The function activates the START and STDIRIN output.


3. Measure with angles j around RCADir +/- ROADir.
4. Compare the result with the set values, refer to figure 12 for example characteristic.
5. Measure the operate time of the timer by injecting a current to get two times the set
SN_> operate value.

Tinv = kSN × Sref / 3 I 0 test × 3U 0 test × cos (j )


IECEQUATION2403 V1 EN-US (Equation 3)

6. Compare the result with the expected value.


The expected value depends on whether definite or inverse time was selected.
7. Continue to test another function or complete the test by setting the test mode to Off.
RCADir = 0º

ROADir = 80º

Operate area

3I0

-3U0

IEC06000652-3-en.vsd
IEC06000652 V3 EN-US

Figure 12: Example characteristic

Non-directional earth fault current protection SEMOD175060-117 v7


Procedure

1. Measure that the operate current is equal to the INNonDir> setting.


The function activates the START and STDIRIN output.
2. Measure the operate time of the timer by injecting a current of 200% of the operate
value.
3. Compare the result with the expected value.
The expected value depends on whether definite time tINNonDir or inverse time was
selected.
4. Continue to test another function or complete the test by setting the test mode to Off.

50 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Residual overvoltage release and protection SEMOD175060-131 v4


Procedure

1. Measure that the operate voltage is equal to the UN> setting.


The function activates the START and STUN signals.
2. Measure the operate time by injecting a voltage 1.2 timers set UN> operate value.
3. Compare the result with the set tUN operate value.
4. Inject a voltage 0.8 · UNRel> and a current high enough to operate the directional
function at the chosen angle.
5. Increase the voltage until the directional function is released.
6. Compare the measured value with the set UNRel> operate value.

7.3.5.2 Completing the test SEMOD175060-148 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
SDEPSDE(67N,IN<->)/SDEPSDE:1 for the function, or for each individual function in a chain, to
be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.3.6 Thermal overload protection, one time constant, Celsius/


Fahrenheit LCPTTR/LFPTTR M14950-2 v7.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for LCPTTR/LFPTTR are available on the local HMI under , Main
menu/Tests/Function status/Current/LCPTTR(26,T>)/LCPTTR:1, Main menu/Tests/
Function status/Current/LFPTTR(26,T>)/LFPTTR:1. The Signal Monitoring in PCM600 shows
the same signals that are available on the local HMI.

Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical
signal TRIP, START and ALARM are equal to logical zero.

7.3.6.1 Testing the protection without external temperature compensation


(NonComp) M14950-10 v7

1. Quickly set the measured current (fault current) in one phase to about 300% of IRef (to
minimise the trip time), and switch the current off.
2. Reset the thermal memory on the local HMI under Main menu/Clear/Clear temperature
constant/LFPTTR(26,8>)/LFPTTR:1, Main menu/Clear/Clear temperature constant/
LCPTTR(26,8>)/LCPTTR:1
3. Switch the fault current on and take note of the temperature, available on the local HMI
under Main menu/Tests/Function status/Current/LFPTTR(26,8>)/LFPTTR:1/Outputs/
TEMP, Main menu/Tests/Function status/Current/LCPTTR(26,8>)/LCPTTR:1/Outputs/
TEMP
4. Check the time until the alarm limit has reached the AlarmTemp level during injection.
Monitor the signal ALARM until it appears on the corresponding binary output or on the
local HMI.
5. Compare the measured temperature with the setting.
6. Measure the LCPTTR/LFPTTRprotection trip time.
Use the TRIP signal from the configured binary output to stop the timer.
7. Take the TEMP readings.
Compare with the setting of TripTemp.

Bay control REC650 51


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

8. Activate the BLOCK binary input.


The signals ALARM, START and TRIP should disappear.
9. Reset the BLOCK binary input.
10. Check the reset limit (TdReset).
Monitor the signal START until it disappears on the corresponding binary output or on
the local HMI, take the TEMP readings and compare with the setting of ReclTemp.
11. Compare the measured trip time with the setting according to the formula.
12. Reset the thermal memory.
13. Continue to test another function or end the test by changing the test mode setting to
Off.

7.3.6.2 Completing the test M14950-48 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
LCPTTR(26,T>)/LCPTTR:1, Main menu/Tests/Function test modes/Current/LFPTTR(26,T>)/
LFPTTR:1 for the function, or for each individual function in a chain, to be tested next.
Remember to set the parameter Blocked to Yes, for each individual function that has been
tested.

7.3.7 Breaker failure protection, phase segregated activation and


output CCRBRF M12104-2 v9.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for CCRBRF are available on the local HMI under Main menu/
Tests/Function status/Current/CCRBRF(50BF)/CCRBRF:1. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.

The Breaker failure protection, 3-phase activation and output function CCRBRF should
normally be tested in conjunction with some other function that provides a start signal. An
external START signal can also be used.

To verify the settings in the most common back-up trip mode 1 out of 3, it is sufficient to test
phase-to-earth faults.

At mode 2 out of 4 the phase current setting, IP> can be checked by single-phase injection
where the return current is connected to the summated current input. The value of residual
(earth fault) current IN set lower than IP> is easiest checked in back-up trip mode 1 out of 4.

7.3.7.1 Checking the phase current operate value, IP> M12104-23 v7

Check the current level IP> where setting FunctionMode=Current and setting BuTripMode=1
out of 3 or 2 out of 4 as set under Main menu/Settings/IED Settings/Current/
CCRBRF(50BF)/CCRBRF:1.

1. Apply the fault condition, including START of CCRBRF, with a current below set IP>.
2. Repeat the fault condition and increase the current in steps until a trip occurs.
3. Compare the result with the set IP>.
4. Disconnect AC and START input signals.

52 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Note! If NoI>check or Retrip off is set, only back-up trip can be used to
check set IP>.

7.3.7.2 Checking the residual (earth fault) current operate value IN> set below
IP> M12104-80 v7

Check the low set IN> current where setting FunctionMode = Current and setting BuTripMode
= 1 out of 4 as set under Main menu/Settings/IED Settings/Current/CCRBRF(50BF)/
CCRBRF:1.

1. Apply the fault condition, including START of CCRBRF, with a current just below set
IN>Pickup_N.
2. Repeat the fault condition and increase the current in steps until trip appears.
3. Compare the result with the set IN>.
4. Disconnect AC and START input signals.

7.3.7.3 Checking the re-trip and back-up times M12104-93 v6

The check of the set times can be made in connection with the check of operate values above.

Choose the applicable function and trip mode, such as FunctionMode = Current and setting
RetripMode = No CBPos. Check as set under Main menu/Settings/IED Settings/Current/
CCRBRF(50BF)/CCRBRF:1.

1. Apply the fault condition, including start of CCRBRF, well above the set current value.
Measure time from START of CCRBRF.
2. Check the re-trip t1 and back-up trip times t2.
3. Disconnect AC and START input signals.

7.3.7.4 Verifying the re-trip mode M12104-36 v6

Choose the mode below, which corresponds to the actual case.

In the cases below it is assumed that FunctionMode = Current as set under Main menu/
Settings/IED Settings/Current/CCRBRF(50BF)/CCRBRF:1.

Checking the case without re-trip, RetripMode = Retrip Off M12104-107 v4

1. Set RetripMode = Retrip Off.


2. Apply the fault condition, including start of CCRBRF, well above the set current value.
3. Verify that no re-trip, but back-up trip is achieved after set time.
4. Disconnect AC and START input signals.

Checking the re-trip with current check, RetripMode = CB Pos Check M12104-48 v4

1. Set RetripMode = CB Pos Check.


2. Apply the fault condition, including start of CCRBRF, well above the set current value.
3. Verify that re-trip is achieved after set time t1 and back-up trip after time t2
4. Apply the fault condition, including start of CCRBRF, with current below set current value.
5. Verify that no re-trip, and no back-up trip is obtained.
6. Disconnect AC and START input signals.

Checking re-trip without current check, RetripMode = No CBPos Check M12104-58 v6

Bay control REC650 53


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

1. Set RetripMode = No CBPos Check.


2. Apply the fault condition, including start of CCRBRF, without any current.
3. Verify that re-trip is achieved after set time t1, and back-up trip after time t2.
4. Apply the fault condition, including start of CCRBRF, with current below set current value.
5. Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
6. Disconnect AC and START input signals.

7.3.7.5 Verifying the back-up trip mode M12104-146 v4

In the cases below it is assumed that FunctionMode = Current is selected.

Checking that back-up tripping is not achieved at normal CB tripping M12104-150 v5


Use the actual tripping modes. The case below applies to re-trip with current check.

1. Apply the fault condition, including start of CCRBRF, with phase current well above set
value IP.
2. Interrupt the current, with a margin before back-up trip time, t2. It may be made at issue
of re-trip command.
3. Check that re-trip is achieved, if selected, but no back-up trip is obtained.
4. Disconnect AC and START input signals.

The normal mode BuTripMode = 1 out of 3 should have been verified in the tests above. In
applicable cases the modes 1 out of 4 and 2 out of 4 can be checked. Choose the mode below,
which corresponds to the actual case.

Checking the case BuTripMode = 1 out of 4 M12104-165 v5


It is assumed that the earth-fault current setting IN> is below phase current setting IP>.

1. Set BuTripMode = 1 out of 4.


2. Apply the fault condition, including start of CCRBRF, with one-phase current below set
IP> but above IN>. The residual earth-fault should then be above set IN>.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
4. Disconnect AC and START input signals.

Checking the case BuTripMode = 2 out of 4 M12104-179 v6


The earth-fault current setting IN> may be equal to or below phase-current setting IP>.

1. Set BuTripMode = 2 out of 4.


2. Apply the fault condition, including start of CCRBRF, with one-phase current above set
IP> and residual (earth fault) above set IN>.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
4. Apply the fault condition, including start of CCRBRF, with at least one-phase current
below set IP> and residual (earth fault) above set IN>. The current may be arranged by
feeding three- (or two-) phase currents with equal phase angle (I0-component) below IP>,
but of such value that the residual (earth fault) current (3I0) will be above set value IN>.
5. Verify that back-up trip is not achieved.
6. Disconnect AC and START input signals.

7.3.7.6 Verifying the case RetripMode = Contact M12104-213 v7

It is assumed that re-trip without current check is selected, RetripMode = Contact.

1. Set FunctionMode = Contact


2. Apply input signal for CB closed to input CBCLDL1, CBCLD2 or CBCDL3.
3. Apply input signal, for start of CCRBRF.

54 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

4. Verify that phase selection re-trip and back-up trip are achieved after set times.
5. Disconnect the start signal. Keep the CB closed signal.
6. Apply input signal, for start of CCRBRF.
7. Arrange disconnection of CB closed signal well before set back-up trip time t2.
8. Verify that back-up trip is not achieved.
9. Disconnect injected AC and START input signals.

7.3.7.7 Verifying the function mode Current&Contact M12104-237 v4

To be made only when FunctionMode = Current&Contact is selected.

Checking the case with fault current above set value IP> M12104-241 v4
The operation shall be as in FunctionMode = Current.

1. Set FunctionMode = Current&Contact.


2. Leave the inputs for CB close inactivated. These signals should not influence.
3. Apply the fault condition, including start of CCRBRF, with current above the set IP> value.
4. Check that the re-trip, if selected, and back-up trip commands are achieved.
5. Disconnect injected AC and START input signals.

Checking the case with fault current below set value I>BlkCont M12104-281 v7
The case shall simulate a case where the fault current is very low and operation will depend on
CB position signal from CB auxiliary contact. It is suggested that re-trip without current check
is used, setting RetripMode = No CBPos Check.

1. Set FunctionMode = Current&Contact.


2. Apply input signal for CB closed to relevant input or inputs CBCLDL1 (2 or 3)
3. Apply the fault condition with input signal(s) for start of CCRBRF. The value of current
should be below the set value I>BlkCont
4. Verify that phase selection re-trip (if selected) and back-up trip are achieved after set
times. Failure to trip is simulated by keeping the signal(s) CB closed activated.
5. Disconnect the AC and the START signal(s). Keep the CB closed signal(s).
6. Apply the fault and the start again. The value of current should be below the set value
I>BlkCont.
7. Arrange disconnection of BC closed signal(s) well before set back-up trip time t2. It
simulates a correct CB tripping.
8. Verify that back-up trip is not achieved. Re-trip can appear for example, due to selection
“Re-trip without current check”.
9. Disconnect injected AC and START input signals.

7.3.7.8 Completing the test M12104-72 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
CCRBRF(50BF)/CCRBRF:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.3.8 Stub protection STBPTOC M14922-2 v7.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Logical signals for STBPTOC protection are available on the local HMI underMain menu/Tests/
Function status/Current/STBPTOC(50STB)/STBPTOC:1/Inputs or Outputs

Bay control REC650 55


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

Values of the logical signals for STBPTOC are available on the local HMI under Main menu/
Tests/Function status/Current/STBPTOC(50STB,I>)/STBPTOC:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.3.8.1 Measuring the operate limit of set values M14922-6 v7

1. Check that the input logical signals BLOCK and RELEASE and the output logical signal
TRIP are all logical zero.
2. Activate the input RELEASE on the STBPTOC function block
3. For a short while inject a current (fault current) in one phase to about 110% of the set
operating current, and switch the current off.
Observe to not exceed the maximum permitted overloading of the current circuits in the
IED.
4. Switch the fault current on and measure the operating time of STBPTOC.
Use the TRIP signal from the configured binary output to stop the timer. The operation
should be instantaneously.
5. Activate the input BLOCK on the STBPTOC function block.
6. Switch on the fault current (110% of the setting).
No TRIP signal should appear.
7. Switch off the fault current.
8. For a short while inject a current (fault current) in same phase to about 90% of the set
operating current, and switch the current off.
9. Switch the fault current on.
No TRIP signal should appear.
10. Switch off the fault current.
11. Reset the RELEASE binary input.
12. Switch the fault current on.
No TRIP signal should appear.
13. Switch the fault current off.

7.3.8.2 Completing the test M14922-50 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
STBPTOC(50STB,I>)/STBPTOC:1 for the function, or for each individual function in a chain, to
be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.3.9 Pole discordance protection CCRPLD SEMOD55625-59 v5.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for CCRPLD are available on the local HMI under Main menu/
Tests/Function status/Current/CCRPLD(52PD)/CCRPLD:X. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.

7.3.9.1 Verifying the settings SEMOD55625-63 v6

1. When CCRPLD is set for external, set setting ContSel to On under Main menu/
Settings/IED Settings/Current/CCRPLD/CCRPLD:1 to activate the logic that detects

56 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

pole discordance when external pole discordance signaling is used (input EXTPDIND) in
the application configuration.
2. Activate the input EXTPDIND on CCRPLD function block, and measure the operating time
of CCRPLD.
3. Compare the measured time with the set value tTrip.
4. Reset the EXTPDIND input.
5. When CCRPLD is set for unsymmetrical current detection with CB monitoring, set setting
CurrSel under Main menu/Settings/IED Settings/Current/CCRPLD/CCRPLD:1 to On.
Use the TRIP signal from the configured binary output to stop the timer.
6. Repeat point 4 and 5 using OPENCMD instead of CLOSECMD. Set all three currents to
110% of CurrRelLevel. Activate CLOSECMD.
NO TRIP signal should appear due to symmetrical condition.

7.3.9.2 Completing the test SEMOD55625-106 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
CCRPLD(52PD)/CCRPLD:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.3.10 Broken conductor check BRCPTOC SEMOD175021-3 v5.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for BRCPTOC are available on the local HMI under Main menu/
Tests/Function status/Current/BRCPTOC(46,lub)/BRCPTOC:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.3.10.1 Measuring the operate and time limit of set values SEMOD175021-7 v4

1. Check that the input logical signal BLOCK to the BRCPTOC function block is logical zero
and note on the local HMI that the output signal TRIP from the BRCPTOC function block is
equal to the logical 0.
2. Set the measured current (fault current) in one phase to about 110% of the set operating
current IP>.
Observe to not exceed the maximum permitted overloading of the current circuits in the
terminal.
3. Switch on the fault current and measure the operating time of BRCPTOC.
TRIP is controlled by Gate 13 in the configuration.
Use the TRIP signal from the configured binary output to stop the timer.
4. Compare the measured time with the set value tOper.
5. Activate the BLOCK binary input.
6. Switch on the fault current (110% of the setting) and wait longer than the set value tOper.
No TRIP signal should appear.
7. Switch off the fault current.
8. Set the measured current (fault current) in same phase to about 90% of the set operating
current IP>. Switch off the current.
9. Switch on the fault current and wait longer than the set value tOper.
No TRIP signal should appear.
10. Switch off the fault current.

Bay control REC650 57


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

7.3.10.2 Completing the test SEMOD175021-42 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
BRCPTOC(46,lub)/BRCPTOC:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.3.11 Directional underpower protection GUPPDUP SEMOD175027-3 v5.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for GUPPDUP are available on the local HMI under Main menu/
Tests/Function status/Current/GUPPDUP(37,P<)/GUPPDUP:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.3.11.1 Verifying the settings SEMOD175027-7 v7

The underpower protection shall be set to values according to the real set values to be used.

The test is made by means of injection of voltage and current where the amplitude of both
current and voltage and the phase angle between the voltage and current can be controlled.
During the test, the analog outputs of active and reactive power shall be monitored.

1. Connect the test set for injection of voltage and current corresponding to the mode to
be used in the application. If a three-phase test set is available this could be used for all
the modes. If a single-phase current/voltage test set is available the test set should be
connected to a selected input for one-phase current and voltage.
Use the formulas stated in Table 3 for the different calculation modes used. The set
mode Mode can be found on the local HMI under Main menu/Settings/IED Settings/
Current/GUPPDUP(37,P<)/GUPPDUP:1/General.

Table 3: Calculation modes


Set value: Mode Formula used for complex power calculation
L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN-US (Equation 4)

Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN-US (Equation 5)

PosSeq
S = 3 × U PosSeq × I PosSeq*
EQUATION1699 V1 EN-US (Equation 6)

L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN-US (Equation 7)

Table continues on next page

58 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Set value: Mode Formula used for complex power calculation


L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN-US (Equation 8)

L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN-US (Equation 9)

L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN-US (Equation 10)

L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN-US (Equation 11)

L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN-US (Equation 12)

2. Adjust the injected current and voltage to the set values in % of IBase and UBase
(converted to secondary current and voltage). The angle between the injected current
and voltage shall be set equal to the set direction Angle1, angle for stage 1 (equal to 0° for
low forward power protection and equal to 180° for reverse power protection). Check
that the monitored active power is equal to 100% of rated power and that the reactive
power is equal to 0% of rated power.
3. Change the angle between the injected current and voltage to Angle1 + 90°. Check that
the monitored active power is equal to 0% of rated power and that the reactive power is
equal to 100% of rated power.
4. Change the angle between the injected current and voltage back to 0°. Decrease the
current slowly until the START1 signal, start of stage 1, is activated.
5. Increase the current to 100% of IBase.
6. Switch the current off and measure the time for activation of TRIP1, trip of stage 1.
7. If a second stage is used, repeat steps 2 to 6 for the second stage.

7.3.11.2 Completing the test SEMOD175027-15 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
GUPPDUP(37,P<)/GUPPDUP:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.3.12 Directional overpower protection GOPPDOP SEMOD175058-3 v5.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for GOPPDOP are available on the local HMI under Main menu/
Tests/Function status/Current/GOPPDOP(32,P>)/GOPPDOP:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

Bay control REC650 59


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

7.3.12.1 Verifying the settings SEMOD175058-7 v6

The overpower protection shall be set to values according to the real set values to be used. The
test is made by means of injection of voltage and current where the amplitude of both current
and voltage and the phase angle between the voltage and current can be controlled. During the
test the analog outputs of active and reactive power shall be monitored.

1. Connect the test set for injection of voltage and current corresponding to the mode to
be used in the application. If a three phase test set is available this could be used for all
the modes. If a single phase current/voltage test set is available the test set should be
connected to a selected input for one phase current and voltage.
Use the formulas stated in Table 3 for the different calculation modes used. The set
mode Mode can be found under Main menu/Settings/IED Settings/Current/
GOPPDOP(32,P>)/GOPPDOP:1/General.
2. Adjust the injected current and voltage to the set rated values in % of IBase and UBase
(converted to secondary current and voltage). The angle between the injected current
and voltage shall be set equal to the set direction Angle1, angle for stage 1 (equal to 0° for
low forward power protection and equal to 180° for reverse power protection). Check
that the monitored active power is equal to 100% of rated power and that the reactive
power is equal to 0% of rated power.
3. Change the angle between the injected current and voltage to Angle1 + 90°. Check that
the monitored active power is equal to 0% of rated power and that the reactive power is
equal to 100% of rated power.
4. Change the angle between the injected current and voltage back to Angle1 value. Increase
the current slowly from 0 until the START1 signal, start of stage 1, is activated. Check the
injected power and compare it to the set value Power1, power setting for stage 1 in % of
Sbase.
5. Increase the current to 100% of IBase and switch the current off.
6. Switch the current on and measure the time for activation of TRIP1, trip of stage 1.
7. If a second stage is used, repeat steps 2 to 6 for the second stage.

7.3.12.2 Completing the test SEMOD175058-66 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Current/
GOPPDOP(32,P>)/GOPPDOP:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.4 Testing voltage protection functions

7.4.1 Two step undervoltage protection UV2PTUV M13796-2 v6.1.1

Prepare the IED for verification of settings as outlined in the section "Preparing the IED to
verify settings".

Values of the logical signals for UV2PTUV are available on the local HMI under Main menu/
Tests/Function status/Voltage/UV2PTUV(27,2U<)/UV2PTUV:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.4.1.1 Verifying the setting

Verification of START value and time delay to operate for Step 1 M13796-29 v6

60 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

1. Check that the IED settings are appropriate, especially the START value, the definite time
delay and the 1 out of 3 operation mode.
2. Supply the IED with three-phase voltages at their rated values.
3. Slowly decrease the voltage in one of the phases, until the START signal appears.
4. Note the operate value and compare it with the set value.

The operate value in secondary volts is calculated according to the


following equations:

For phase-to-ground measurement:

U1 < UBase VT sec


× ×
100 3 VTprim
IECEQUATION2430 V1 EN-US (Equation 13)

For phase-to-phase measurement:

U1 < VT sec
× UBase ×
100 VTprim
IECEQUATION2431 V1 EN-US (Equation 14)
5. Increase the measured voltage to rated load conditions.
6. Check that the START signal resets.
7. Instantaneously decrease the voltage in one phase to a value about 20% lower than the
measured operate value.
8. Measure the time delay for the TRIP signal, and compare it with the set value.
9. Check the inverse time delay by injecting a voltage corresponding to 0.8 × U1<.

For example, if the inverse time curve A is selected, the trip signals TR1
and TRIP operate after a time corresponding to the equation:

k1
t (s ) =
 U 
 1 − U1 < 
 
IECEQUATION2428 V1 EN-US (Equation 15)

where:
t(s) Operate time in seconds
k1 Settable time multiplier of the function for step 1
U Measured voltage
U1< Set start voltage for step 1

For example, if the measured voltage jumps from the rated value to 0.8 times the set
start voltage level and time multiplier k1 is set to 0.05 s (default value), then the TR1 and
TRIP signals operate at a time equal to 0.250 s ± tolerance.
10. The test above can be repeated to check the inverse time characteristic at different
voltage levels.
11. Repeat the above-described steps for step 2.

Extended testing M13796-35 v6

1. The tests above can be repeated for 2 out of 3 and for 3 out of 3 operation mode.

Bay control REC650 61


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

7.4.1.2 Completing the test M13796-25 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Voltage/
UV2PTUV(27,2U<)/UV2PTUV:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.4.2 Two step overvoltage protection OV2PTOV M13806-2 v6.1.1

Prepare the IED for verification of settings as outlined in the section "Preparing the IED to
verify settings".

Values of the logical signals for OV2PTOV are available on the local HMI under Main menu/
Tests/Function status/Voltage/OV2PTOV(59,2U>)/OV2PTOV:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.4.2.1 Verification of single-phase voltage and time delay to operate for Step 1 M13806-50 v5

1. Apply single-phase voltage below the set value U1>.


2. Slowly increase the voltage until the ST1 signal appears.
3. Note the operate value and compare it with the set value.

The operate value in secondary volts is calculated according to the


following equations:

For phase-to-ground measurement:

U1 > UBase VT sec


× ×
100 3 VTprim
IECEQUATION2426 V1 EN-US (Equation 16)

For phase-to-phase measurement:

U1 > VT sec
× UBase ×
100 VTprim
IECEQUATION2427 V1 EN-US (Equation 17)
4. Decrease the voltage slowly and note the reset value.
5. Set and apply about 20% higher voltage than the measured operate value for one phase.
6. Measure the time delay for the TR1 signal and compare it with the set value.
7. Check the inverse time delay by injecting a voltage corresponding to 1.2 × U1>.

For example, if the inverse time curve A is selected, the trip signals TR1
and TRIP operate after a time corresponding to the equation:

k1
t (s ) =
 U 
 U1 > − 1
 
IECEQUATION2429 V1 EN-US (Equation 18)

where:

62 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

t(s) Operate time in seconds


k1 Settable time multiplier of the function for step 1
U Measured voltage
U1> Set start voltage for step 1

For example, if the measured voltage jumps from 0 to 1.2 times the set start voltage level
and time multiplier k1 is set to 0.05 s (default value), then the TR1 and TRIP signals
operate at a time equal to 0.250 s ± tolerance.
8. The test above can be repeated to check the inverse time characteristic at different
voltage levels.
9. Repeat the above-described steps for step 2.

7.4.2.2 Completing the test M13806-43 v6

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Voltage/
OV2PTOV(59,2U>)/OV2PTOV:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.4.3 Two step residual overvoltage protection ROV2PTOV SEMOD54358-3 v6.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for ROV2PTOV are available on the local HMI under Main menu/
Tests/Function status/Voltage/ROV2PTOV(59N,2UN>)/ROV2PTOV:1. The Signal Monitoring
in PCM600 shows the same signals that are available on the local HMI.

7.4.3.1 Verifying the settings SEMOD54358-35 v7

1. Apply the single-phase voltage either to a single-phase voltage input or to a residual


voltage input with the start value below the set value U1>.
2. Slowly increase the value until ST1 appears.
3. Note the operate value and compare it with the set value.
4. Decrease the voltage slowly and note the reset value.
5. Set and apply about 20% higher voltage than the measured operate value for one phase.
6. Measure the time delay for the TR1 signal and compare it with the set value.
7. Check the inverse time delay by injecting a voltage corresponding to 1.2 × U1>.

For example, if the inverse time curve A is selected, the trip signals TR1
and TRIP operate after a time corresponding to the equation:

k1
t (s ) =
 U 
 U1 > − 1
 
IECEQUATION2429 V1 EN-US (Equation 19)

Bay control REC650 63


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

where:
t(s) Operate time in seconds
k1 Settable time multiplier of the function for step 1
U Measured voltage
U1> Set start voltage for step 1

For example, if the measured voltage jumps from 0 to 1.2 times the set start voltage level
and time multiplier k1 is set to 0.05 s (default value), then the TR1 and TRIP signals
operate at a time equal to 0.250 s ± tolerance.
8. Repeat the test for step 2.

7.4.3.2 Completing the test SEMOD54358-38 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Voltage/
ROV2PTOV(59N,2UN>)/ROV2PTOV:1 for the function, or for each individual function in a chain,
to be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.4.4 Loss of voltage check LOVPTUV SEMOD175023-3 v5.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for LOVPTUV are available on the local HMI under Main menu/
Tests/Function status/Voltage/LOVPTUV(27,U<)/LOVPTUV:1. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.4.4.1 Measuring the operate limit of set values SEMOD175023-7 v6

1. Check that the input logical signals BLOCK, CBOPEN and VTSU are logical zero.
2. Supply a three-phase rated voltage in all three phases and note on the local HMI that the
TRIP logical signal is equal to the logical 0.
3. Switch off the voltage in all three phases.
After set tTrip time a TRIP signal appears on the corresponding binary output or on the
local HMI.

Note that TRIP at this time is a pulse signal, duration should be according
to set tPulse.

4. Inject the measured voltages at rated values for at least set tRestore time.
5. Activate the CBOPEN binary input.
6. Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
7. Inject the measured voltages at rated values for at least set tRestore time.
8. Activate the VTSU binary input.
9. Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
10. Reset the VTSU binary input.
11. Inject the measured voltages at rated values for at least set tRestore time.

64 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

12. Activate the BLOCK binary input.


13. Simultaneously disconnect all the three-phase voltages from the IED.
No TRIP signal should appear.
14. Reset the BLOCK binary input.

7.4.4.2 Completing the test SEMOD175023-47 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Voltage/
LOVPTUV(27,U<)/LOVPTUV:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.5 Testing frequency protection functions

7.5.1 Underfrequency protection SAPTUF M16289-2 v7.2.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for SAPTUF are available on the local HMI under Main menu/
Tests/Function status/Frequency/SAPTUF(81,f<)/SAPTUF:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.5.1.1 Verifying the settings

Verification of START value and time delay to operate M16289-17 v4.1.1

1. Check that the IED settings are appropriate, for example the start value and the time
delay.
2. Supply the IED with three-phase voltages at their rated values and initial frequency.
The initial frequency is calculated using Equation 20.

StartFrequency  0.02  floor  f r  StartFrequency / 0.04  0.04


IECEQUATION16059 V1 EN-US (Equation 20)
[1]

3. Slowly decrease the voltage frequency by steps of 40 mHz until the START signal
appears; during each step apply the voltage signal for a time that is either at least 10%
longer than (tDelay+100 ms) or a suitable time to monitor the function.
4. Note the frequency value at which the START signal appears and compare it with the set
value StartFrequency.
5. Increase the frequency until its rated value is reached.
6. Check that the START signal resets.
7. Supply the IED with three-phase voltages at their rated values and frequency 20 mHz over
the set value StartFrequency.
8. Decrease the frequency with a 40 mHz step, applying it for a time that is at least 10%
longer than (tDelay+100 ms).
9. Measure the time delay of the TRIP signal, and compare it with the set value tDelay. Note
that the measured time consists of the set value of the time delay plus the minimum
operate time of the function (80 - 90 ms).

Extended testing M16289-31 v5.1.1

[1] floor[x] is the largest integer less than or equal to x

Bay control REC650 65


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

1. Check that the IED settings are appropriate, for example the start value and the time
delay.
2. Supply the IED with three-phase voltages at their rated values and frequency 20 mHz
under the set value StartFrequency, applying it for a time that is at least 10% longer than
(tDelay+100 ms).
3. Verify that the TRIP signal is active.
4. Increase the frequency with a 40 mHz step, applying it until the TRIP signal resets.
5. Measure the reset time of the TRIP signal, and compare it with the technical data of the
function.

Verification of the low voltage magnitude blocking M16289-39 v5.1.1

1. Check that the IED settings are appropriate, especially the StartFrequency and the tDelay
in SAPTUF, and the GlobalBaseSel and the MinValFreqMeas in the SMAI preprocessing
function.
2. Supply the IED with three-phase voltages at rated values.
3. Slowly decrease the magnitude of the applied voltage until the BLKDMAGN signal
appears.
4. Note the voltage magnitude value and compare it with the value MinValFreqMeas x
UBase / 100.
Where:
• MinValFreqMeas is a set value of the SMAI.
• UBase is the value in the GBASVAL group identified by the setting GlobalBaseSel.
5. Slowly decrease the frequency of the applied voltage, to a value below StartFrequency as
explained in Section "Verification of START value and time delay to operate".
6. Check that the START signal does not appear.
7. Wait for a time corresponding to (tDelay+100 ms), and check that the TRIP signal does
not appear.
8. Slowly increase the magnitude of the applied voltages until the BLKDMAGN signal resets.
9. Verify that the signal START appears and wait for a time at least equal to (tDelay+100 ms)
to verify that also the signal TRIP becomes active.

7.5.1.2 Completing the test M16289-57 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Frequency/
SAPTUF(81,f<)/SAPTUF:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.5.2 Overfrequency protection SAPTOF M16290-2 v7.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for SAPTOF are available on the local HMI under Main menu/
Tests/Function status/Frequency/SAPTOF(81,f>)/SAPTOF:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

66 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

7.5.2.1 Verifying the settings

Verification of START value and time delay to operate M16290-14 v4.1.1

1. Check that the IED settings are appropriate, for example the start value and the time
delay.
2. Supply the IED with three-phase voltages at their rated values and initial frequency.
The initial frequency is calculated using Equation 21.

StartFrequency  0.02  floor  f r  StartFrequency / 0.04  0.04


IECEQUATION16061 V1 EN-US (Equation 21)
[2]

3. Slowly increase the voltage frequency by steps of 40 mHz until the START signal appears;
during each step apply the voltage signal for a time that is either at least 10% longer than
(tDelay+100 ms) or a suitable time to monitor the function.
4. Note the frequency value at which the START signal appears and compare it with the set
value StartFrequency.
5. Decrease the frequency until its rated value is reached.
6. Check that the START signal resets.
7. Supply the IED with three-phase voltages at their rated values and frequency 20 mHz
under the set value StartFrequency.
8. Increase the frequency with a 40 mHz step, applying it for a time that is at least 10%
longer than (tDelay+100 ms).
9. Measure the time delay of the TRIP signal, and compare it with the set value tDelay. Note
that the measured time consists of the set value of the time delay plus the minimum
operate time of the function (80 - 90 ms).

Extended testing M16290-28 v4.1.1

1. Check that the IED settings are appropriate, for example the start value and the time
delay.
2. Supply the IED with three-phase voltages at their rated values and frequency 20 mHz over
the set value StartFrequency, applying it for a time that is at least 10% longer than
(tDelay+100 ms).
3. Verify that the TRIP signal is active.
4. Decrease the frequency with a 40 mHz step, applying it until the TRIP signal resets.
5. Measure the reset time of the TRIP signal, and compare it with the technical data of the
function.

Verification of the low voltage magnitude blocking M16290-34 v4.1.1

1. Check that the IED settings are appropriate, especially the StartFrequency and the tDelay
in SAPTOF, and the GlobalBaseSel and the MinValFreqMeas in the SMAI preprocessing
function.
2. Supply the IED with three-phase voltages at rated values.
3. Slowly decrease the magnitude of the applied voltage until the BLKDMAGN signal
appears.
4. Note the voltage magnitude value and compare it with the value MinValFreqMeas x
UBase / 100.
Where:
• MinValFreqMeas is a set value of the SMAI.
• UBase is the value in the GBASVAL group identified by the setting GlobalBaseSel.
5. Slowly increase the frequency of the applied voltage, to a value above StartFrequency as
explained in Section Verification of START value and time delay to operate.
6. Check that the START signal does not appear.

[2] floor[x] is the largest integer less than or equal to x

Bay control REC650 67


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

7. Wait for a time corresponding to (tDelay+100 ms), and check that the TRIP signal does
not appear.
8. Slowly increase the magnitude of the applied voltages until the BLKDMAGN signal resets.
9. Verify that the signal START appears and wait for a time at least equal to (tDelay+100 ms)
to verify that also the signal TRIP becomes active.

7.5.2.2 Completing the test M16290-52 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Frequency/
SAPTOF(81,f>)/SAPTOF:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

7.5.3 Rate-of-change frequency protection SAPFRC M16256-2 v6.1.1

Prepare the IED for verification of settings as outlined in section "Preparing the IED to verify
settings".

Values of the logical signals for SAPFRC are available on the local HMI under Main menu/
Tests/Function status/Frequency/SAPFRC(81,df/dt)/SAPFRC:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

7.5.3.1 Verifying the settings

Verification of START value and time delay to operate M16256-10 v4

1. Check that the appropriate settings are available in the IED, especially the START value
and the definite time delay. Set StartFreqGrad, to a rather small negative value.
2. Supply the IED with three-phase voltages at their rated values.
3. Slowly decrease the frequency of the applied voltage, with an increasing rate-of-change
that finally exceeds the setting of StartFreqGrad, and check that the START signal
appears.
4. Note the operate value and compare it with the set value.
5. Increase the frequency to rated operating conditions, and zero rate-of-change.
6. Check that the START signal resets.
7. Instantaneously decrease the frequency of the applied voltage to a value about 20%
lower than the nominal value.
8. Measure the time delay for the TRIP signal, and compare it with the set value.

Extended testing M16256-29 v4

1. The test above can be repeated to check a positive setting of StartFreqGrad.


2. The tests above can be repeated to test the RESTORE signal, when the frequency
recovers from a low value.

7.5.3.2 Completing the test M16256-39 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Frequency/
SAPFRC(81,df/dt)/SAPFRC:X for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter Blocked to Yes, for each individual function that
has been tested.

68 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

7.6 Testing secondary system supervision functions

7.6.1 Current circuit supervision CCSRDIF M12917-25 v4.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for CCSRDIF are available on the local HMI under Main menu/
Tests/Function status/Secondary system supervision/CCSRDIF(87,INd)/CCSRDIF:X. The
Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.

The Current circuit supervision function CCSRDIF is conveniently tested with the same three-
phase test set as used when testing the measuring functions in the IED.

The condition for this procedure is that the setting of IMinOp is lower than the setting of
Ip>Block.

7.6.1.1 Verifying the settings M12917-31 v4

1. Check the input circuits and the operate value of the IMinOp current level detector by
injecting current, one phase at a time.
2. Check the phase current blocking function for all three phases by injecting current, one
phase at a time. The output signals shall reset with a delay of 1 second when the current
exceeds 1.5 · IBase.
3. Inject a current 0.1 · IBase to the reference current input IREFSMPL.
4. Increase slowly the current in one of the phases current input and check that FAIL output
is obtained when the current is about 0.9 · IBase.

7.6.1.2 Completing the test M12917-43 v4

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Secondary
system supervision/CCSRDIF(87,INd)/CCSRDIF:X for the function, or for each individual
function in a chain, to be tested next. Remember to set the parameter Blocked to Yes, for each
individual function that has been tested.

7.6.2 Fuse failure supervision SDDRFUF M1405-2 v6.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for SDDRFUF are available on the local HMI under Main menu/
Tests/Function status/Secondary system supervision/SDDRFUF/SDDRFUF:1. The Signal
Monitoring in PCM600 shows the same signals that are available on the local HMI.

The verification is divided in two main parts. The first part is common to all fuse failure
supervision options, and checks that binary inputs and outputs operate as expected according
to actual configuration. In the second part the relevant set operate values are measured.

7.6.2.1 Checking that the binary inputs and outputs operate as expected M1405-9 v6

Bay control REC650 69


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

1. Simulate normal operating conditions with the three-phase currents in phase with their
corresponding phase voltages and with all of them equal to their rated values.
2. Connect the nominal dc voltage to the DISCPOS binary input.
• The signal BLKU should appear with almost no time delay.
• No signals BLKZ and 3PH should appear on the IED.
• Only the distance protection function can operate.
• Undervoltage-dependent functions must not operate.
3. Disconnect the dc voltage from the DISCPOS binary input terminal.
4. Connect the nominal dc voltage to the MCBOP binary input.
• The BLKU and BLKZ signals should appear without any time delay.
• All undervoltage-dependent functions must be blocked.
5. Disconnect the dc voltage from the MCBOP binary input terminal.
6. Disconnect one of the phase voltages and observe the logical output signals on the
binary outputs of the IED.
BLKU and BLKZ signals should appear simultaneously wether the BLKU and BLKZ reset
depends on the setting SealIn “on” or “off”. If “on” no reset, if “off” reset.
7. After more than 5 seconds disconnect the remaining two-phase voltages and all three
currents.
• There should be no change in the high status of the output signals BLKU and BLKZ.
• The signal 3PH will appear.
8. Establish normal voltage and current operating conditions simultaneously and observe
the corresponding output signals.
They should change to logical 0 as follows:
• Signal 3PH after about 25ms
• Signal BLKU after about 50ms
• Signal BLKZ after about 200ms

7.6.2.2 Measuring the operate value for the negative sequence function M1405-46 v8

1. Simulate normal operating conditions with the three-phase currents in phase with their
corresponding phase voltages and with all of them equal to their rated values.
2. Slowly decrease the measured voltage in one phase until the BLKU signal appears.
3. Record the measured voltage and calculate the corresponding negative-sequence voltage
according to the equation.
Observe that the voltages in the equation are phasors.
2
3 × U 2 = UL 1 + a × U L 2 + a × U L3
EQUATION707 V1 EN-US (Equation 22)

Where:

UL1 , U L 2 and U L3
= the measured phase voltages
IEC00000275 V1 EN-US

2 ×p
j 3
a = 1× e 3
= -0, 5 + j
2
IECEQUATION00022 V1 EN-US

4. Compare the result with the set value (consider that the set value 3U2> is in percentage
of the base voltage UBase) of the negative-sequence operating voltage.
5. Repeat steps 1 and 2. Then slowly increase the measured current in one phase until the
BLKU signal disappears.
6. Record the measured current and calculate the corresponding negative-sequence current
according to the equation.
Observe that the currents in the equation are phasors.

70 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

3 × I 2 = I L1 + a × I L 2 + a × I L 3
2

IECEQUATION00021 V1 EN-US (Equation 25)

Where:
= the measured phase currents
I L1 , I L 2 and I L 3
IECEQUATION00020 V1 EN-US

2 ×p
j 3
a = 1× e 3
= -0, 5 + j
2
IECEQUATION00022 V1 EN-US

7. Compare the result with the set value of the negative-sequence operating current.
Consider that the set value 3I2< is in percentage of the base current IBase.

7.6.2.3 Measuring the operate value for the zero-sequence function M1405-72 v7

1. Simulate normal operating conditions with the three-phase currents in phase with their
corresponding phase voltages and with all of them equal to their rated values.
2. Slowly decrease the measured voltage in one phase until the BLKU signal appears.
3. Record the measured voltage and calculate the corresponding zero-sequence voltage
according to the equation.
Observe that the voltages in the equation are phasors.

3 × U0 = U L1 + UL2 + U L3
IEC00000276 V1 EN-US (Equation 28)

Where:

UL1 , U L 2 and U L3
= the measured phase voltages
IEC00000275 V1 EN-US

4. Compare the result with the set value (consider that the set value 3U0> is in percentage
of the base voltage of the zero-sequence operating voltage.
5. Repeat steps 1 and 2. Then slowly increase the measured current in one phase until the
BLKU signal disappears.
6. Record the measured current and calculate the corresponding zero-sequence current
according to the equation.
Observe that the currents in the equation are phasors.

3 × I 0 = I L1 + I L2 + I L3
IECEQUATION00019 V1 EN-US (Equation 30)

Where:
= the measured phase currents
I L1 , I L 2 and I L 3
IECEQUATION00020 V1 EN-US

7. Compare the result with the set value of the zero-sequence operating current. Consider
that the set value 3I0< is in percentage of the base current IBase.

7.6.2.4 Checking the operation of the du/dt and di/dt based function M1405-96 v8

Bay control REC650 71


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

1. Simulate normal operating conditions with the three-phase currents in phase with their
corresponding phase voltages and with all of them equal to their rated values.
2. Change the voltages and currents in all three phases simultaneously.
The voltage change must be greater than the set value for DU> and the current change
must be less than the set value for DI<.
• The BLKU and BLKZ signals appear without any time delay. The BLKZ signal will be
activated only if the internal deadline detection is not activated at the same time.
• 3PH should appear after 5 seconds, if the remaining voltage levels are lower than
the set UDLD< of the DLD function.
3. Apply normal conditions as in step 1.
The BLKU, BLKZ and 3PH signals should reset, if activated, see step 1 and 2.
4. Change the voltages and currents in all three phases simultaneously.
The voltage change must be greater than the set value for DU> and the current change
must be more than the set value for DI<.
The BLKU, BLKZ and 3PH signals should not appear.
5. Repeat step 2.
6. Connect the nominal voltages in all three phases and feed a current below the operate
level in all three phases.
7. Keep the current constant. Disconnect the voltage in all three phases simultaneously.
The BLKU, BLKZ and 3PH signals should not appear.
8. Change the magnitude of the voltage and current for phase 1 to a value greater than the
set value for DU> and DI<.
9. Check that the start output signals STDUL1 and STDIL1 and the general start signals
STDU or STDI are activated.
10. Check that the start output signals for the current and voltage phases 2 and 3 are
activated by changing the magnitude of the voltage and current for phases 2 and 3.

7.6.2.5 Completing the test M1405-130 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Secondary
system supervision/SDDRFUF/SDDRFUF:1 for the function, or for each individual function in a
chain, to be tested next. Remember to set the parameter Blocked to Yes, for each individual
function that has been tested.

7.7 Testing control functions


GUID-9B5BDD59-F6F5-41C6-913B-0AFEB0779290 v3

During periods of frequent counter state/value changes, if the auxiliary power


to the IED is interrupted, it is possible that this information will be lost.

7.7.1 Synchrocheck, energizing check, and synchronizing SESRSYN M2377-3 v9.1.1

This section contains instructions on how to test the synchrocheck, energizing check, and
synchronizing function SESRSYN for single, double and 1½ breaker arrangements.

This section contains instructions on how to test the synchrocheck and energizing check for
single CB with or without the synchronizing function.

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

72 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Values of the logical signals for SESRSYN are available on the local HMI under Main menu/
Tests/Function status/Control/SESRSYN(25,SYNC)/SESRSYN:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

At commissioning and periodical checks, the functions shall be tested with the used settings.
To test a specific function, it might be necessary to change some setting parameters, for
example:

• AutoEnerg = Off/DLLB/DBLL/Both
• ManEnerg = Off
• Operation = Off/On
• Activation of the voltage selection function if applicable

The tests explained in the test procedures below describe the settings, which can be used as
references during testing before the final settings are specified. After testing, restore the
equipment to the normal or desired settings.

A secondary injection test set with the possibility to alter the phase angle and amplitude of
the voltage is needed. The test set must also be able to generate different frequencies on
different outputs.

The description below applies for a system with a nominal frequency of 50 Hz


but can be directly applicable to 60 Hz. SESRSYN can be set to use different
phases, phase to earth or phase to phase. Use the set voltages instead of what
is indicated below.

Figure 13 shows the general test connection principle, which can be used during testing. This
description describes the test of the version intended for one bay.

Figure 14 shows the general test connection for a 1½ breaker diameter with one-phase voltage
connected to the line side.

IED
Test
U-Bus U-Bus
equipment

N UMeasure
Ph/N
U-Line Ph/Ph
UL1 Input Phase
UL2 L1,L2,L3
UL3 L12,L23,L31
N N

en08000027.vsd
IEC08000027 V1 EN-US

Figure 13: General test connection with three-phase voltage connected to the line side

Bay control REC650 73


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

IED

Test U-Bus1
equipment U-Bus1

U-Bus2
U-Bus2

U-Line2
U-Line2

U-Line1
U-Line1
UMeasure
Ph/N
Ph/Ph

N N

IEC11000273-2-en.vsd
IEC11000273 V2 EN-US

Figure 14: General test connection for a 1½ breaker diameter with one-phase voltage
connected to the line side

7.7.1.1 Testing the synchronizing function M2377-21 v6

This section is applicable only if the synchronizing function is included.

The voltage inputs used are:

U-Line UL1, UL2 or UL3 line 1 voltage inputs on the IED


U-Bus Bus voltage input on the IED

Testing the frequency difference M2377-116 v7


The frequency difference is in the example set at 0.20 Hz on the local HMI, and the test should
verify that operation is achieved when the FreqDiffMax frequency difference is lower than 0.20
Hz. The test procedure below will depend on the settings used. Input STARTSYN must be
activated during the test.

1. Apply voltages
1.1. U-Line = 100% GblBaseSelLine and f-Line = 50.0 Hz
1.2. U-Bus = 100% GblBaseSelBus and f-Bus = 50.2Hz
2. Check that a closing pulse is submitted at a closing angle less than 2 degrees from phase
equality. Modern test sets will evaluate this automatically.
3. Repeat with
3.1. U-Bus = 80% GblBaseSelBus and f-Bus = 50.25 Hz, to verify that the function does
not operate when frequency difference is above limit.
4. Repeat with different frequency differences for example, 100 mHz with f-Bus nominal and
line leading and for example 20 mHz (or just above FreqDiffMin) to verify that
independent of frequency difference the closing pulse occurs within 2 degrees.
5. Verify that the closing command is not issued when the frequency difference is less than
the set value FreqDiffMin.

74 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

7.7.1.2 Testing the synchrocheck check M2377-132 v7

During the test of SESRSYN for a single bay arrangement, these voltage inputs are used:

U-Line UL1, UL2 or UL3 line 1 voltage inputs on the IED


U-Bus Bus voltage input on the IED

Testing the voltage selection for single 1 1/2 CB arrangements GUID-12E7DA63-FE04-4C83-9BA6-34818C510DB8 v2


At test of the SESRSYN function for a 1½ CB diameter the following alternative voltage inputs
can be used for the three SESRSYN (SESRSYN 1, SESRSYN 2, SESRSYN 3) functions. These three
SESRSYN functions can either be in one, two or three different IEDs. Table 4 describes the
scenario when SESRSYN 1, SESRSYN 2 and SESRSYN 3 all are in the same IED. If SESRSYN 3 is in
another IED, Bus1 will be considered as Bus2 and Line2 as Line1. The voltage is selected by
activation of different inputs in the voltage selection logic as shown in table 4 and figure 15.

Table 4: Voltage selection logic


SESRSYN CBConfig Section to Activated Activated Activated Activated Indication
setting be B1QCLD B2QCLD LN1QCLD LN2QCLD from
synchroniz input on input on input on input on SESRSYN
ed IED from IED from IED from IED from on IED
SESRSYN 1 1 ½ bus CB Bus1 – LN1QB9 B1SEL,
(Operates on Line1 LN1SEL
CB1QA1)
Bus1 – CB2QA1 LN2QB9 B1SEL,
Line2 LN2SEL
Bus1 – CB2QA1 CB3QA1 B1SEL,
Bus2 B2SEL
SESRSYN 2 Tie CB Line1 – LN1QB9 LN2QB9 LN1SEL,
(Operates on Line2 LN2SEL
CB2QA1)
Bus1 – CB1QA1 LN2QB9 B1SEL,
Line2 LN2SEL
Bus2 – CB3QA1 LN1QB9 B2SEL,
Line1 LN1SEL
Bus1 – CB1QA1 CB3QA1 B1SEL,
Bus2 B2SEL
SESRSYN 3 1 ½ bus Bus2 – LN2QB9 B2SEL,
(Operates on alt. CB Line2 LN2SEL
CB3QA1) (mirrored)
Bus2 – CB2QA1 LN1QB9 B2SEL,
Line1 LN1SEL
Bus2 – CB2QA1 CB1QA1 B1SEL,
Bus1 B2SEL

Bay control REC650 75


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

Bus 1

Bus 2

CB1QA1 CB3QA1
(SESRSYN 1) (SESRSYN 3)

CB2QA1
(SESRSYN 2)

LN1QB9 LN2QB9

Line 1 Line 2

IEC11000274-2-en.vsd
IEC11000274 V2 EN-US

Figure 15: Objects used in the voltage selection logic

Testing the voltage difference M2377-194 v6


Set the voltage difference to 0.15 p.u. on the local HMI, and the test should check that
operation is achieved when the voltage difference UDiffSC is lower than 0.15 p.u.

The settings used in the test shall be final settings. The test shall be adapted to site setting
values instead of values in the example below.

Test with no voltage difference between the inputs.

Test with a voltage difference higher than the set UDiffSC.

1. Apply voltages U-Line (for example) = 80% GblBaseSelLine and U-Bus = 80%
GblBaseSelBus
2. Check that the AUTOSYOK and MANSYOK outputs are activated.
3. The test can be repeated with different voltage values to verify that the function
operates within the set UDiffSC. Check with both U-Line and U-Bus respectively lower
than the other.
4. Increase the U-Bus to 110% GblBaseSelBus, and the U-Line = 90% GblBaseSelLine and
also the opposite condition.
5. Check that the two outputs for manual and auto synchronism are not activated.

Testing the phase angle difference M2377-215 v6


The phase angle differences PhaseDiffM and PhaseDiffA respectively are set to their final
settings and the test should verify that operation is achieved when the phase angle difference
is lower than this value both leading and lagging.

Test with no voltage difference.

76 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

1. Apply voltages U-Line (for example) = 100% GblBaseSelLine and U-Bus = 100%
GblBaseSelBus, with a phase difference equal to 0 degrees and a frequency difference
lower than FreqDiffA and FreqDiffM.
2. Check that the AUTOSYOK and MANSYOK outputs are activated.
The test can be repeated with other phase difference values to verify that the function
operates for values lower than the set ones, PhaseDiffM and PhaseDiffA. By changing the
phase angle on the voltage connected to U-Bus, between ± dφ degrees, the user can
check that the two outputs are activated for a phase difference lower than the set value.
It should not operate for other values. See figure 16.

U-Bus

No operation
+dj
U-Line operation
-dj

U-Bus

en05000551.vsd
IEC05000551 V1 EN-US

Figure 16: Test of phase difference


3. Change the phase angle between +dφ and -dφ and verify that the two outputs are
activated for phase differences between these values but not for phase differences
outside, see figure 16.

Testing the frequency difference M2377-232 v6


The frequency difference test should verify that operation is achieved when the FreqDiffA and
FreqDiffM frequency difference is lower than the set value for manual and auto synchronizing
check, FreqDiffA and FreqDiffM respectively and that operation is blocked when the frequency
difference is greater.

Test with frequency difference = 0 mHz

Test with a frequency difference outside the set limits for manual and auto synchronizing
check respectively.

1. Apply voltages U-Line equal to 100% GblBaseSelLine and U-Bus equal to 100%
GblBaseSelBus, with a frequency difference equal to 0 mHz and a phase difference lower
than the set value.
2. Check that the AUTOSYOK and MANSYOK outputs are activated.
3. Apply voltage to the U-Line equal to 100% GblBaseSelLine with a frequency equal to 50
Hz and voltage U-Bus equal to 100% GblBaseSelBus, with a frequency outside the set
limit.
4. Check that the two outputs are not activated. The test can be repeated with different
frequency values to verify that the function operates for values lower than the set ones. If
a modern test set is used, the frequency can be changed continuously.

Testing the reference voltage M2377-249 v5

1. Use the same basic test connection as in figure 13.

Bay control REC650 77


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

The voltage difference between the voltage connected to U-Bus and U-Line should be 0%,
so that the AUTOSYOK and MANSYOK outputs are activated first.
2. Change the U-Line voltage connection to U-Line2 without changing the setting on the
local HMI. Check that the two outputs are not activated.

7.7.1.3 Testing the energizing check M2377-262 v5

During the test of the energizing check function for a single bay arrangement, these voltage
inputs are used:

U-Line UL1, UL2 or UL3 line1 voltage inputs on the IED


U-Bus Bus voltage input on the IED

General M2377-271 v5
When testing the energizing check function for the applicable bus, arrangement shall be done
for the energizing check functions. The voltage is selected by activation of different inputs in
the voltage selection logic.

Live voltage level is fixed to 80% UBase and dead voltage level to fixed 40% UBase.

The test shall be performed according to the settings for the station. Test the alternatives
below that are applicable.

Testing the dead line live bus (DLLB) M2377-276 v5


The test should verify that the energizing check function operates for a low voltage on the U-
Line and for a high voltage on the U-Bus. This corresponds to the energizing of a dead line to a
live bus.

1. Apply a single-phase voltage 100% GblBaseSelBus to the U-Bus, and a single-phase


voltage 30% GblBaseSelLine to the U-Line.
2. Check that the AUTOENOK and MANENOK outputs are activated after set tAutoEnerg
respectively tManEnerg.
3. Increase the U-Line to 60% GblBaseSelLine and U-Bus to be equal to 100%
GblBaseSelBus. The outputs should not be activated.
4. The test can be repeated with different values on the U-Bus and the U-Line.

Testing the dead bus live line (DBLL) M2377-289 v6


The test should verify that the energizing check function operates for a low voltage on the U-
Bus and for a high voltage on the U-Line. This corresponds to an energizing of a dead bus to a
live line.

1. Verify the settings AutoEnerg or ManEnerg to be DBLL.


2. Apply a single-phase voltage of 30% GblBaseSelBus to the U-Bus and a single-phase
voltage of 100% GblBaseSelLine to the U-Line.
3. Check that the AUTOENOK and MANENOK outputs are activated after set tAutoEnerg
respectively tManEnerg.
4. Decrease the U-Line to 60% GblBaseSelLine and keep the U-Bus equal to 30%
GblBaseSelBus. The outputs should not be activated.
5. The test can be repeated with different values on the U-Bus and the U-Line.

Testing both directions (DLLB or DBLL) M2377-306 v6

78 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

1. Verify the local HMI settings AutoEnerg or ManEnerg to be Both.


2. Apply a single-phase voltage of 30% GblBaseSelLine to the U-Line and a single-phase
voltage of 100% GblBaseSelBus to the U-Bus.
3. Check that the AUTOENOK and MANENOK outputs are activated after set tAutoEnerg
respectively tManEnerg.
4. Change the connection so that the U-Line is equal to100% GblBaseSelLine and the U-Bus
is equal to 30% GblBaseSelBus. The outputs should still be activated.
5. The test can be repeated with different values on the U-Bus and the U-Line.

Testing the dead bus dead line (DBDL) M2377-323 v6


The test should verify that the energizing check function operates for a low voltage on both
the U-Bus and the U-Line, that is, closing of the breaker in a non-energized system. Test is valid
only when this function is used.

1. Verify the local HMI setting AutoEnerg to be Off and ManEnerg to be DBLL.
2. Set the parameter ManEnergDBDL to On.
3. Apply a single-phase voltage of 30% GblBaseSelBus to the U-Bus and a single-phase
voltage of 30% GblBaseSelLine to the U-Line.
4. Check that the MANENOK output is activated after set tManEnerg.
5. Increase the U-Bus to 80% GblBaseSelBus and keep the U-Line equal to 30%
GblBaseSelLine. The outputs should not be activated.
6. Repeat the test with ManEnerg set to DLLB with different values on the U-Bus and the U-
Line voltage.

7.7.1.4 Testing the voltage selection M2377-342 v2

Testing the voltage selection for single CB arrangements M2377-473 v6


This test should verify that the correct voltage is selected for the measurement in the
SESRSYN function used in a double-bus arrangement. Apply a single-phase voltage of 30%
GblBaseSelLine to the U-Line and a single-phase voltage of 100% GblBaseSelBus to the U-Bus.

If the UB1OK or UB2OK inputs for the fuse failure are used, they must be activated, during
tests below. Also verify that deactivation prevents operation and gives an alarm.

1. Connect the signals above to binary inputs and binary outputs.


2. Connect the voltage inputs to the analog inputs used for each bus or line depending of
the type of busbar arrangement and verify that correct output signals are generated.

7.7.1.5 Completing the test M2377-1042 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Control/
SESRSYN(25,SYNC)/SESRSYN:X for the function, or for each individual function in a chain, to
be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.7.2 Autorecloser for 3-phase operation SMBRREC M12400-2 v8.1.1

Verification of the Autorecloser for 3-phase operation function SMBRREC for three-phase
reclosing attempts can be considered to consist of two parts.

Bay control REC650 79


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

• One part to verify the internal logic and timing of the function
• One part to verify its interaction with the protection system

This section deals with verification of SMBRREC itself. However, it is practical to start
SMBRREC by activating a protection function, for example, by secondary injection tests.

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for SMBRREC are available on the local HMI under Main menu/
Tests/Function status/Control/SMBRREC(79,0->1)/SMBRREC:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

The purpose of verification before commissioning is to check that entered selections, setting
parameters and configuration render the intended result. The function is flexible with many
options and facilities. At commissioning only the selections and settings intended for use are
verified. If one chooses to reduce some time settings in order to speed up verification, be
careful to set the parameters at intended operational values at the end of the verification
procedure. One such parameter is the tReclaim time that must be timed out before a new test
sequence can be performed.

The verification test is performed together with protection and trip functions. Figure 17
illustrates a suggested testing arrangement, where the circuit-breaker (CB) is simulated by an
external bi-stable relay (BR), for example a relay type RXMVB2 or RXMD or Breaker Simulator of
ABB. The following manual switches are used:

• Switch or push-button to close (SC)


• Switch or push-button to trip (ST)
• Switch for CB ready condition (SRY)

If no bi-stable relay or breaker simulator is available, replace it with two self-reset auxiliary
relays and use a self-holding connection.

Use a secondary injection IED test set to operate the protection function. The test set shall be
switched off when a trip signal is given or when the BR comes to open position to simulate real
conditions.

The CB simulation can be made more elaborate, including simulation of the operating gear
condition, CBREADY of either the type ready for a Close-Open (CO) cycle, or the type ready for
an Open-Close -Open (OCO) cycle.

The CB condition CBREADY of a type, CO, shall be high (true) until a closing operation is
performed. It then goes low (false) for a recharging time of about 5 - 10s. After that it is high
again.

A CB condition CBREADY of a type, OCO shall be high (true) before and during tripping (Start
reclosing). During tripping it goes low for a recharging time, for example, 10s. It may thus be
low at the instant of reclosing. After each Open or Close operation it may need a recharging
period before it goes high again.

In the example of CB simulation arrangement, the CBREADY condition is simulated by a


manual switch, SRY.

Information and material for the verification:

• Protection or control unit, IED, configured and with settings entered.


• Configuration diagram for the IED
• Terminal diagram for the IED, or plant circuit diagram including the IED
• Technical reference manual for the IED
• IED test set for secondary injection

80 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

• Means to indicate, measure and record operation and times, for example an event
recording facility
• A bi-stable relay (BR) or two auxiliary relays to simulate a CB
• Two push-buttons (SC, ST) to operate the BR and a change-over switch (SRY) to simulate
CBREADY
• Possibly a switch simulation the synchronizing check SESRSYN condition

IED

SMBRREC - CLOSECB

BR

SC
Trip

ST

SMBRREC - CBPOS

SRY
SMBRREC - CBREADY

To test
set

+ -
IEC09000206_1_en.vsd
EN09000206 V1 EN-US

Figure 17: Simulating the CB operation by a bi-stable relay/breaker simulator and


manual switches

7.7.2.1 Preparation of the verification M12400-40 v6

1. Check the function settings on the local HMI under Main menu/Settings/IED Settings/
Control/SMBRREC(79,0->1)/SMBRREC:1
If any timer settings are reduced to speed up or facilitate the testing, they shall be set to
normal after testing. A temporary label on the IED can be a reminder to restore normal
settings after which a verification test should be performed.
2. Decide if a synchronizing check function SESRSYN shall be included in the test.
If SESRSYN as an internal function or external device is not operated by the injection,
input signal SYNC must be connected as a permanent high signal or controlled by a
switch.
3. Read and make notes of the reclosing operation counters on the local HMI under Main
menu/Tests/Function status/Control/SMBRREC(79,0->1)/SMBRREC:1
Possibly reset the counters to Zero. Counters are reset in the reset menu.
4. Make arrangements for the simulation of the CB, for example as in figure 17.
5. Make arrangements for indication, recording and time measurements.
The signals for CBPOS, START, CLOSECB, READY and other relevant signals should
preferably be arranged for event recording with time tagging. If that is not possible,
other means of time measurement and recording should be arranged.

7.7.2.2 Switching the autorecloser for 3-phase operation function to On and Off M12400-79 v5

1. Set the Operation setting to Off and check the state.


2. Set the Operation setting to On and check the state, including SETON and READY.

Bay control REC650 81


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

The CB should be closed and ready.


3. If external control Off/On is connected, check that it works.
Set Operation to ExternalCtrl and use that control to switch On and Off, and check the
state of the function.

7.7.2.3 Verifying the autorecloser for 3-phase operation function SMBRREC M12400-91 v9

Select the test cases to be run according to what is applicable to the particular application. It
can be, for example, three-phase single-shot reclosing or two-shot reclosing. Below, a case
with three-phase single-shot reclosing is described.

1. Set Operation = On.


2. If the autorecloser for 3-phase operation function SMBRREC is not to be operated, ensure
that the SMBRREC input is activated. If SMBRRECis to be included, ensure that it is
supplied with the appropriate AC quantities.
3. Simulate CB closed position by closing switch SC to make the BR relay start.
4. Simulate CBREADY by closing the switch SRY, and leave it closed.
5. Inject AC quantities to give a trip to the BR and to the START input.
Observe and preferably record the operation. The BR relay shall trip and reclose (start).
After reclosing, the SRY switch can be opened for about 5s and then closed again.
The autoreclosing open time and the sequence should be checked, for example in the
event recording. Check also the operation indications (disturbance report) and the
operation counters on the local HMI under Main menu/Tests/Function status/
SMBRREC(79,0->1)/SMBRREC:1
Should the operation not be as expected, this should be investigated. It could be caused
by an inappropriate setting or missing condition such as CBREADY.
6. Repeat the sequence by simulating a permanent fault.
Shortly after the reclosing shot, a new fault is applied. If a single-shot reclosing program
is selected, there shall be one reclosing operation and then blocking of SMBRREC for the
set Reclaim time.
Before a new reclosing sequence can be run, the CBREADY and CBPOS (CB closed) must
be set manually.

7.7.2.4 Checking the reclosing conditions M12400-123 v4

When checking the influence of a releasing condition it is suggested to first run a sequence
with the condition fulfilled. When the condition signal is removed, and a new sequence is run, it
indicates that the result was due to the changed condition. In case of a blocking signal the
procedure should be similar. Start without the blocking or inhibit signal, and then run a
sequence with the blocking or inhibit signal added.

Checking the influence of the INHIBIT signal M12400-129 v4

1. Check that the autorecloser function SMBRREC is operative, for example, by making a
reclosing shot without the INHIBIT signal.
2. Apply a fault and thereby a START signal. At the same time, or during the open time,
apply a signal to the input INHIBIT.
3. Check that the reclosing sequence is interrupted and no reclosing takes place.

Check closing onto a fault M12400-137 v4

1. Check that the autorecloser function SMBRREC is operative, for example by making a
reclosing shot.

82 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Keep the CBREADY signal high.


2. Set the breaker simulating relay BR in Open position.
3. Close the BR relay and apply immediately a fault and thereby a START signal.
4. Check that no reclosing takes place.

Checking the influence of CB not ready for reclosing M12400-149 v4

1. Check that the autorecloser function SMBRREC is operative, for example by making a
reclosing shot.
Keep the CB simulator BR closed. Remove the CBREADY signal by opening SRY.
2. Apply a fault and thereby a START signal.
3. Check that no reclosing takes place.

Checking the influence of synchronizing check (at three-phase reclosing) M12400-161 v7

1. Check that the autorecloser for 3-phase operation function SMBRREC is operative, for
example, by making a three-phase reclosing shot with the synchronizing check condition.
Remove the SMBRREC signal.
2. Apply a fault causing three-phase trip and thereby a START signal.
3. Wait for the tSync time out limit.
Check that no reclosing is made.

Restoring equipment M12400-190 v4


After the tests, restore the equipment to normal or desired state. Check the following items in
particular:

1. Check the operation counters.


Reset the counters to zero, if that is the user's preference. The counter reset function is
found on the local HMI under Main menu/Clear/Clear counters/SMBRREC(79,0->1)
2. Restore settings that may have been modified for the tests back to normal.
3. Disconnect the test switch, CB simulating arrangement and test circuits.
Reconnect any links or connection terminals, which may have been opened for the tests.
4. Reset indications, alarms and disturbance recordings.
Clearing of the disturbance report must be done via the Disturbance Handling in
PCM600.

7.7.2.5 Completing the test M12400-218 v5

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Control/
SMBRREC(79,0->1)/SMBRREC:X for the function, or for each individual function in a chain, to
be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.7.3 Interlocking M11755-2 v6.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals are available on the local HMI under Main menu/Tests/Function
status/Control/<Function>/<Function:1>. The Signal Monitoring in PCM600 shows the same
signals that are available on the local HMI.

The interlocking function consists of a bay-level part and a station-level part. The interlocking
is delivery specific and is realized by bay-to-bay communication over the station bus. For that

Bay control REC650 83


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

reason, test the function in a system, that is, either in a complete delivery system as an
acceptance test (FAT/SAT) or as parts of that system.

7.7.4 Apparatus control APC M13385-2 v4

The apparatus control function consists of four types of function blocks, which are connected
in a delivery-specific way between bays and to the station level. For that reason, test the total
function in a system, that is, either in a complete delivery system as an acceptance test (FAT/
SAT) or as parts of that system.

If a block/unblock command is sent from remote to function, while the IED is


shut down, this command will not be recognized after the start up, thus the
command that was sent prior to the shut down is used. In such cases, where
there is a mismatch, the user is advised to make a complete cycle of block/
unblock operations to align the statuses.

7.8 Testing scheme communication functions

7.9 Testing logic functions

7.9.1 Tripping logic, common 3-phase output SMPPTRC SEMOD54375-102 v8.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for SMPPTRC are available on the local HMI under Main menu/
Tests/Function status/Logic/SMPPTRC(94,1->0)/SMPPTRC:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.

This function is functionality tested together with other protection functions (earth-fault
overcurrent protection, and so on) within the IED. It is recommended that the function is
tested together with the autorecloser function, regardless of whether the autorecloser
function is integrated or external.

7.9.1.1 Three-phase operating mode SEMOD54375-106 v8

1. Check that AutoLock and TripLockout are both set to Off.


2. Initiate a three-phase fault.
An adequate time interval between the faults should be considered, to overcome a
reclaim time caused by the possible activation of the Autorecloser function, SMBRREC.
The function must issue a three-phase trip in all cases, when a trip is initiated by any
protection function, either integrated or external. The functional TRIP output signal must
always appear.

7.9.1.2 Circuit breaker lockout SEMOD54375-170 v9

The following tests should be carried out when the built-in lockout function is used in addition
to possible other tests, which depends on the complete configuration of an IED.

84 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

1. Check that AutoLock and TripLockout are both set to Off.


2. Initiate a three-phase fault.
The functional output TRIP should be active at each fault. The output CLLKOUT must not
be activated.
3. Activate the automatic lockout function, set AutoLock = On and repeat.
Besides the TRIP outputs, CLLKOUT should be set.
4. Reset the lockout signal by activating the reset lockout (RSTLKOUT) signal.
5. Activate the TRIP signal lockout function, set TripLockout = On and repeat.
The output TRIP must be active and stay active after each fault. CLLKOUT must be
activated.
6. Reset the lockout.
All functional outputs should reset.
7. Deactivate the TRIP signal lockout function, set TripLockout = Off and the automatic
lockout function, set AutoLock = Off if not used.

7.9.1.3 Completing the test SEMOD54375-203 v6

Continue to test another function or end the testing by setting the parameter TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter Blocked to No under Main menu/Tests/Function test modes/Logic/
SMPPTRC(94,1->0)/SMPPTRC:X for the function, or for each individual function in a chain, to
be tested next. Remember to set the parameter Blocked to Yes, for each individual function
that has been tested.

7.10 Testing monitoring functions

7.10.1 Event counter CNTGGIO M13419-2 v4

The event counter function CNTGGIO can be tested by connecting a binary input to the counter
under test and applying pulses to the counter. The speed of pulses must not exceed 10 per
second. Normally the counter will be tested in connection with tests on the function that the
counter is connected to, such as trip logic. When configured, test it together with the function
that operates it. Trig the function and check that the counter result corresponds with the
number of operations.

7.10.2 Limit counter L4UFCNT GUID-E35C0EBD-081E-4EC2-9DE9-D276DBA8354A v1

The Limit counter function L4UFCNT can be tested by connecting a binary input to the counter
and applying pulses to the counter. The speed of the pulses must not exceed the cycle time of
the function. Normally the counter will be tested when testing the function that the counter is
connected to, such as the trip function. When the function is configured, test it together with
the function that operates it. Trig the function and check that the counter result corresponds
to the number of operations.

7.10.2.1 Completing the test GUID-8E1A0F3F-0611-4AF4-9FE4-63E750AE90C3 v1

Continue to test another function or end the test by changing the Test mode setting to Off.
Restore connections and settings to their original values, if they were changed for testing
purposes.

Bay control REC650 85


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

7.10.3 Fault locator LMBRFLO M14955-2 v7.1.1

Prepare the IED for verification of settings as outlined in section Preparing the IED to verify
settings.

Values of the logical signals for LMBRFLO are available on the local HMI under Main menu/
Tests/Function status/Monitoring/LMBRFLO/LMBRFLO:1. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.

The Fault locator function LMBRFLO depends on other functions to work properly, that is,
phase selection information from distance protection function and analog information
supplied by the trip value recorder function. Check that proper binary start and phase
selection signals are connected and voltage and current signals are configured (parameter
settings).

The fault locator LMBRFLO function, supports kilometer and mile for the line
length unit. The fault distance will be presented with the same unit as the line
length and is mapped to IEC61850 -8-1 communication protocol, where the
fault distance is supposed to be in kilometer (km). Select the line length unit to
kilometer for compliance with IEC61850.

The result is displayed on the local HMI or via PCM600. Distances to faults for the last 100
recorded disturbances can be found on the local HMI under Main menu/Tests/Function
status/Monitoring/LMBRFLO/LMBRFLO:1/Outputs

If PCM600 is used, the result is displayed on the recording list after upload, including loop
selection information.

Table 5: Test settings


Parameter Condition
I Higher than 30% Ir

Healthy conditions U = 63,5 V, I = 0 A & ZF = 0°


Impedance |Z| Test point
Note:

• Zx£ (X0 + 2 · X1)/3 For single-phase faults


• Zx£ X1 For three and two phase faults
• Zx£ (X0 + 2 · X1 XM)/3 For single-phase fault with mutual zero-
sequence current

Impedance angle ZF Test angle

• ZF arctan[(X0 + 2 · X1) / (R0 + 2R1)] For single-phase faults


• ZF arctan(X1/R1) For two-phase faults

7.10.3.1 Measuring the operate limit M14955-48 v5

1. Set the test point (|Z| fault impedance and ZF impedance phase angle ) for a condition
that meets the requirements in table 5.
2. Subject the IED to healthy normal load conditions for at least two seconds.
3. Apply a fault condition.
Check that the distance-to-fault value displayed on the HMI complies with equations 32,
33 and 34

86 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Z
p = ------x- × 100
X1
EQUATION123 V1 EN-US (Equation 32)

in % for two- and three-phase faults

3 × Zx
p= × 100
X0 + 2 × X1
EQUATION124 V1 EN-US (Equation 33)

in % for single-phase-to-earth faults

3 × Zx
p = --------------------------------------------- × 100
X0 + 2 × X1 ± XM
EQUATION125 V1 EN-US (Equation 34)

in % for single-phase-to-earth faults with mutual zero sequence current.

Where:
p = the expected value of a distance to fault in percent
Zx = set test point on the test set

X0 = set zero-sequence reactance of a line


X1 = set positive-sequence reactance of a line
XM = set mutual zero-sequence impedance of a line

7.10.3.2 Completing the test M14955-84 v6

7.11 Testing metering functions

7.11.1 Pulse counter PCGGIO M13405-2 v6

The test of the Pulse counter function PCGGIO requires the Parameter Setting tool in PCM600
or an appropriate connection to the local HMI with the necessary functionality. A known
number of pulses with different frequencies are connected to the pulse counter input. The test
should be performed with settings Operation = On or Operation = Off and the function
blocked or unblocked. The pulse counter value is then checked in PCM600 or on the local HMI.

7.12 Testing station communication

7.12.1 Establishing connection and verifying the IEC 61850


communication GUID-0EEBE65F-5A84-4D2E-A358-BF5283E948D6 v1

About this chapter


This chapter contains instructions on how to establish connection and verify that the IEC
61850 communication operates as intended, when the IED is connected to an Ethernet
network via the optical ports of the COM module.

Bay control REC650 87


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 7 1MRK 511 288-UEN B
Testing functionality

7.12.1.1 Overview GUID-F8AA9CC0-E9DC-4656-B209-879B18243189 v1

The COM03 ports are used for substation bus (IEC 61850-8-1) communication as well as
redundant communication.

The COM05 ports are also used for communication but not redundant communication.

For IEC 61850-8-1 redundant communication according to IEC62439–3 Edition 2, port LAN_1A
and LAN_1B is utilized.

Redundant communication according to IEC62439–3 Edition 1 and IEC 61850–


9–2LE process bus communication are not supported in the 650 Ver 1.3 series
IEDs.

7.12.1.2 Setting the station communication GUID-B77A38F2-1895-4CB3-AB16-961E8A73DAD5 v1

To enable the IEC 61850 communication, the corresponding COM03 ports must be activated.
Port LAN1 A and LAN1 B are used for redundancy.

If COM03 is used; the following below apply. If COM05 is used; there is no redundancy and the
port is named LAN1 or (FRONT)

To enable IEC 61850 station communication:

• The IEC 61850-8-1 station communication functionality must be configured in the local
HMI. Navigate to Main Menu/Configuration/Communication/TCP-IP configuation/
ETHLAN1_AB and set the OperationMode parameter to NonRedundant(A) or, for
redundant communication, to PRP(A+B).
• To enable GOOSE communication, the Operation parameter for the corresponding GOOSE
function blocks (GOOSEBINRCV and GOOSEINTLKRCV) must be set to On in the
application configuration.
• To enable GOOSE communication via the front port the parameter GOOSE in Main menu/
Configuration/Communication/Station communication/IEC61850-8-1/PortSelGOOSE
must be set to Front. To enable GOOSE communication via rear port the parameter
PortSelGOOSE must be set to LAN1.

To enable IEC 61850 station communication:

1. Enable IEC 61850-8-1 (substation bus) communication for port A and B.


1.1. Set values for ETHLAN1_AB.
Navigate to Main Menu/Configuration/TCP-IP configuation/ETHLAN1_AB.
Set values for OperationMode, IPAddress and IPMask. OperationMode must be set
to NonRedundantA.
Check that the correct IP address is assigned to the port.
1.2. Enable IEC 61850-8-1 communication.
Navigate to Main menu/Settings/General settings/Communication/Station
communication/IEC 61850-8-1.
Set Operation to On and PortSelGOOSE to the port used.
2. Enable redundant IEC 61850-8-1 communication for port A and B.
2.1. Enable redundant communication.
Navigate to Main Menu/Configuration/TCP-IP configuation/ETHLAN1_AB.
Set values for OperationMode, IPAddress and IPMask. OperationMode must be set
to PRP(A+B).

88 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 7
Testing functionality

Make sure that the optical fibres are connected correctly.

7.12.1.3 Verifying the station communication GUID-0B7E64BC-3346-4105-90C0-2EA5A5BB74DE v1

Connect a PC to the substation network and ping the connected IED and the Substation
Master PC to verify that the communication is working up to the transport layer.

The best way to verify the communication up to the application layer is to use a protocol
analyzer connected to the substation or process bus and monitor the communication.

Verifying redundant IEC 61850-8-1 communication


Ensure that the IED receives IEC 61850-8-1 data on both ports A and B. In the local HMI
navigate to Main menu/Tests/Function status/Communication/PRP Status/LAN1–A / LAN1–
B and check that both signals LAN1-A and LAN1-B are shown as Ok. Remove the optical
connection to one of the ports A or B. Verify that either signal LAN1-A or LAN1-B (depending on
which connection that was removed) are shown as Error and that the other signal is shown as
Ok. Be sure to re-connect the removed connection after completed verification.

7.13 Exit test mode SEMOD53244-3 v4

The following procedure is used to return to normal operation.

1. Navigate to the test mode folder.


2. Change the On setting to Off. Press the 'E' key and the left arrow key.
3. Answer YES, press the 'E' key and exit the menus.

Bay control REC650 89


Commissioning manual
© Copyright 2013 ABB. All rights reserved
90
1MRK 511 288-UEN B Section 8
Commissioning and maintenance of the fault clearing system

Section 8 Commissioning and maintenance of


the fault clearing system
8.1 Commissioning and maintenance of the fault clearing
system SEMOD56497 v1

About this chapter


This chapter discusses maintenance tests and other periodic maintenance measures.

8.1.1 Commissioning tests SEMOD56513-5 v4

During commissioning all protection functions shall be verified with the setting values used at
each plant. The commissioning tests must include verification of all circuits by green-lining the
circuit diagrams and the configuration diagrams for the used functions.

Further, the settings for protection functions are tested and recorded carefully as outlined for
the future periodic maintenance tests.

The final testing includes primary verification of all directional functions where load currents is
checked on the local HMI and in PCM600. The amplitudes and angles of all currents and
voltages should be checked and the symmetry verified.

Directional functions have information about the measured direction and, for example,
measured impedance. These values must be checked and verified as correct with the export or
import of power available.

Finally, final trip tests must be performed. This involves activation of protection functions or
tripping outputs with the circuit breaker closed and the tripping of the breaker verified. When
several breakers are involved, each breaker must be checked individually and it must be
verified that the other involved breakers are not tripped at the same time.

8.1.2 Periodic maintenance tests SEMOD56517-1 v1

SEMOD56520-5 v4
The periodicity of all tests depends on several factors, for example the importance of the
installation, environmental conditions, simple or complex equipment, static or
electromechanical IEDs, and so on.

The normal maintenance praxis of the user should be followed. However, ABB's
recommendation is as follows:

Every second to third year

• Visual inspection of all equipment.


• Removal of dust on ventilation louvres and IEDs if necessary.
• Periodic maintenance test for protection IEDs of object where no redundant protections
are provided.

Every four to six years

• Periodic maintenance test for protection IEDs of objects with redundant protection
system.

Bay control REC650 91


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 8 1MRK 511 288-UEN B
Commissioning and maintenance of the fault clearing system

First maintenance test should always be carried out after the first half year of
service.

When protection IEDs are combined with built-in control, the test interval can
be increased drastically, up to for instance 15 years, because the IED
continuously reads service values, operates the breakers, and so on.

8.1.2.1 Visual inspection SEMOD56525-5 v2

Prior to testing, the protection IEDs should be inspected to detect any visible damage that
may have occurred (for example, dirt or moisture deposits, overheating). Should burned
contacts be observed when inspecting the IEDs, a diamond file or an extremely fine file can be
used to polish the contacts. Emery cloth or similar products must not be used as insulating
grains of abrasive may be deposited on the contact surfaces and cause failure.

Make sure that all IEDs are equipped with covers.

8.1.2.2 Maintenance tests SEMOD56534-1 v1

SEMOD56528-5 v4
To be made after the first half year of service, then with the cycle as proposed above and after
any suspected maloperation or change of the IED setting.

Testing of protection IEDs shall preferably be made with the primary circuit de-energized. The
IED cannot protect the circuit during testing. Trained personnel may test one IED at a time on
live circuits where redundant protection is installed and de-energization of the primary circuit
is not allowed.

ABB protection IEDs are preferably tested by aid of components from the COMBITEST testing
system described in information B03-9510 E. Main components are RTXP 8/18/24 test switch
located to the left in each protection IED and RTXH 8/18/24 test handle, which is inserted in
test switch at secondary testing. All necessary operations such as opening of trip circuits,
short-circuiting of current circuits and opening of voltage circuits are automatically performed
in the right order to allow for simple and safe secondary testing even with the object in
service.

Preparation SEMOD56528-10 v2
Before starting maintenance testing, the test engineers should scrutinize applicable circuit
diagrams and have the following documentation available:

• Test instructions for protection IEDs to be tested


• Test records from previous commissioning and maintenance tests
• List of valid settings
• Blank test records to fill in measured values

Recording SEMOD56528-14 v2
It is of utmost importance to carefully record the test results. Special test sheets covering the
frequency of test, date of test and achieved test values should be used. IED setting list and
protocols from previous tests should be available and all results should be compared for
differences. At component failures, spare equipment is used and set to the requested value. A
note of the exchange is made and the new measured values are recorded. Test records for
several years of testing should be stored in a common file for a station, or a part of a station,
to give a simple overview of the period of testing and achieved test values. These test records
are valuable when analysis of service disturbances shall be done.

92 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 8
Commissioning and maintenance of the fault clearing system

Secondary injection SEMOD56528-17 v2


The periodic maintenance test is done by secondary injection from a portable test set. Each
protection shall be tested according to the secondary injection test information for the
specific protection IED. Only the setting values adopted shall be checked for each protection
function. If the discrepancy between obtained value and requested set value is too big the
setting should be adjusted, the new value recorded and a note should be made in the test
record.

Alarm test SEMOD56528-20 v4


When inserting the test handle the alarm and event signalling is normally blocked. This is done
in the IED by setting the event reporting to Off during the test. This can be done when the test
handle is inserted or the IED is set to test mode from the local HMI. At the end of the
secondary injection test it should be checked that the event and alarm signalling is correct by
activating the events and performing some selected tests.

Self supervision check SEMOD56528-23 v4


Once secondary testing has been completed, it should be checked that no self-supervision
signals are activated continuously or sporadically. Especially check the time synchronization
system, GPS or other, and communication signals, both station communication and remote
communication.

Trip circuit check SEMOD56528-26 v4


When the protection IED undergoes an operational check, a tripping pulse is normally obtained
on one or more of the output contacts and preferably on the test switch. The healthy circuit is
of utmost importance for the protection operation. If the circuit is not provided with a
continuous trip-circuit supervision, it is possible to check that circuit is really closed when the
test-plug handle has been removed by using a high-ohmic voltmeter and measuring between
the plus and the trip output on the panel. The measurement is then done through the tripping
magnet of the circuit breaker and therefore the complete tripping circuit is checked.

Note that the breaker must be closed.

Please observe that the test system does not provide built-in security during
this test. If the instrument should be set on Amp instead of Volts, the circuit
breaker naturally is tripped, therefore, great care is necessary.

Trip circuit from trip IEDs to circuit breaker is often supervised by trip-circuit supervision. It
can then be checked that a circuit is healthy by opening tripping output terminals in the
cubicle. When the terminal is opened, an alarm shall be achieved on the signal system after a
delay of some seconds.

Remember to close the circuit directly after the test and tighten the terminal
carefully.

Measurement of service currents SEMOD56528-30 v4


After a maintenance test it is recommended to measure the service currents and service
voltages recorded by the protection IED. The service values are checked on the local HMI or in
PCM600. Ensure that the correct values and angles between voltages and currents are
recorded. Also check the direction of directional functions such as Distance and directional
overcurrent functions.

Bay control REC650 93


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 8 1MRK 511 288-UEN B
Commissioning and maintenance of the fault clearing system

For transformer differential protection, the achieved differential current value is dependent on
the tap changer position and can vary between less than 1% up to perhaps 10% of rated
current. For line differential functions, the capacitive charging currents can normally be
recorded as a differential current.

The zero-sequence current to earth-fault protection IEDs should be measured. The current
amounts normally very small but normally it is possible to see if the current circuit is "alive".

The neutral-point voltage to an earth-fault protection IED is checked. The voltage is normally
0.1 to 1V secondary. However, voltage can be considerably higher due to harmonics. Normally a
CVT secondary can have around 2.5 - 3% third-harmonic voltage.

Restoring SEMOD56528-36 v2
Maintenance is very important to improve the availability of the protection system by
detecting failures before the protection is required to operate. There is however little point in
testing healthy equipment and then putting it back into service with an open terminal, with a
removed fuse or open miniature circuit breaker with an open connection, wrong setting, and
so on.

Thus a list should be prepared of all items disturbed during test so that all can be put back into
service quickly and without overlooking something. It should be put back into service item by
item and signed by the responsible engineer.

94 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 9
Troubleshooting

Section 9 Troubleshooting
9.1 Fault tracing

9.1.1 Identifying hardware errors GUID-0F0FF99B-E3EF-4D44-ABB4-19041BA9FBF1 v6

1. Check the module with an error.


• Check the general IED status in Main menu/Diagnostics/IED status/General for a
faulty hardware module.
• Check the history of changes in internal event list in Main menu/Diagnostics/
Internal Events.
2. Inspect the IED visually.
• Inspect the IED visually to find any physical error causes.
• If you can find some obvious physical damage, contact ABB for repair or
replacement actions.
3. Check whether the error is external or internal.
• Check that the error is not caused by external origins.
• Remove the wiring from the IED and test the input and output operation with an
external test device.
• If the problem remains, contact ABB for repair or replacement actions.

9.1.2 Identifying runtime errors GUID-105A9FFE-75F3-4E65-BFF7-F31268CD7DCE v6

1. Check the error origin from IED's internal event list Main menu/Diagnostics/IED status/
General.
2. Reboot the IED and recheck the supervision events to see if the fault has cleared.
3. In case of persistent faults, contact ABB for corrective actions.

9.1.3 Identifying communication errors GUID-4C589FC4-B122-4F12-8E3D-1B05B4FC5FCE v6

Communication errors are normally communication interruptions or synchronization message


errors due to communication link breakdown.

• Check the IEC61850 and DNP3 communication status in internal event list in Main menu/
Diagnostics/IED Status/General.
• In case of persistent faults originating from IED's internal faults such as component
breakdown, contact ABB for repair or replacement actions.

9.1.3.1 Checking the communication link operation GUID-A1815C16-1AB7-4DEE-8E9B-0BF91DDEE72C v4

There are several different communication links on the product. First check that all
communication ports that are used for communication are turned on.

1. Check the front communication port RJ-45.


1.1. Check that the uplink LED is lit with a steady green light.

Bay control REC650 95


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 9 1MRK 511 288-UEN B
Troubleshooting

The uplink LED is located on the LHMI above the RJ-45 communication port on the
left. The port is used for direct electrical communication to a PC connected via a
crossed-over Ethernet cable.
1.2. Check the communication status of the front port via the LHMI in Main menu/Test/
Function status/Communication/DOSFRNT:1/Outputs.
Check that the LINKUP value is 1, that is, the communication is working. When the
value is 0, there is no communication link.
2. Check the communication status of the rear port X1 via the LHMI in Main menu/Tests/
Function status/Communication/DOSLAN1:1/Outputs.
The X1 communication port on the rear side of the IED is for optical Ethernet via LC
connector.
• Check that the LINKUP value is 1, that is, the communication is working. When the
value is 0, there is no communication link.

9.1.3.2 Checking the time synchronization GUID-CE54512E-06E3-4255-823C-1ACA122CC67E v5

• Select Main menu/Diagnostics/IED status/General and check the status of the time
synchronization on Time Synch.
The Time synch value is Ready when the synchronization is in order.

Note that the time synchronization source has to be activated. Otherwise


the value is always Ready.

9.1.4 Running the display test AMU0600411 v6

To run the display test, either use the push buttons or start the test via the menu.

• Select Main menu/Tests/LED test.


• Press or simultaneously and .
All the LEDs are tested by turning them on simultaneously. The display shows a set of
patterns so that all the pixels are activated. After the test, the display returns to normal
state.

9.2 Indication messages

9.2.1 Internal faults GUID-2ACAE73F-9CDD-4C33-AFED-6BACC8990F37 v4

When the Ready LED indicates an internal fault by flashing, the message associated with the
fault is found in the internal event list in the LHMI menu Main menu/Diagnostics/Internal
events. The message includes the date, time, description and signal state for the fault. The
internal event list is not updated dynamically. The list is updated by leaving the Internal events
menu and then selecting it again. The current status of the internal fault signals can also be
checked via the LHMI in Main menu/Diagnostics/IED status.

Different actions are taken depending on the severity of the fault. If the fault is found to be
permanent, the IED stays in internal fault mode. The IED continues to perform internal tests
during the fault situation.

When a fault appears, the fault indication message is to be recorded and stated when
requesting support or service.

96 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 9
Troubleshooting

Table 6: Internal fault indications


Fault indication Additional information
Internal Fault Hardware error with the real time
Real Time Clock Error clock.
Internal Fault One or more of the application
Runtime Exec. Error threads are not working properly.
Internal Fault This signal will be activated when
SW Watchdog Error the terminal has been under too
heavy load for at least 5 minutes.
Internal Fault One or more of the application
Runtime App Error threads are not in an expected
state.
Internal Fault A file system error has occurred.
File System Error
Internal Fault A TRM card error has occurred. The
TRM-Error instance number is displayed at the
end of the fault indication.
Internal Fault A COM card error has occurred. The
COM-Error instance number is displayed at the
end of the fault indication.
Internal Fault A PSM card error has occurred. The
PSM-Error instance number is displayed at the
end of the fault indication.

9.2.2 Warnings GUID-7BAFA38E-5163-4E01-A7C3-6489B42233C7 v2

The warning message associated with the fault is found in the internal event list in the LHMI
menu Main menu/Diagnostics/Internal events. The message includes the date, time,
description and signal state for the fault. The current status of the internal fault signals can
also be checked via the LHMI in Main menu/Diagnostics/IED status/General.

When a fault appears, record the fault indication message and state it when ordering service.

Table 7: Warning indications


Warning indication Additional information
Warning IEC 61850 has not
IEC 61850 Error succeeded in some actions
such as reading the
configuration file, startup
etc.
Warning Error in DNP3
DNP3 Error communication.

9.2.3 Additional indications GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3.1.1

The additional indication messages do not activate internal fault or warning.

The messages are listed in the LHMI menu under the event list. The signal status data is found
under the IED status and in the internal event list.

Bay control REC650 97


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 9 1MRK 511 288-UEN B
Troubleshooting

Table 8: Additional indications


Warning indication Additional information
Time Synch Error Source of the time synchronization is lost or time
system has made a time reset.
Settings Changed Settings have been changed.
Setting Groups Changed Setting group has been changed.

9.3 Correction procedures

9.3.1 Changing and setting the password GUID-D3FA85BA-1E36-4F8B-BD71-85C7AC46A0B4 v1

The password can only be set with PCM600.

For more information, see PCM600 documentation.

9.3.2 Identifying IED application problems GUID-D8E1AECF-1FD8-4996-A447-948B52EAD0C2 v5

Navigate to the appropriate menu in the LHMI to identify possible problems.

• Check that the function is on.


• Check that the correct setting group (1 to 4) is activated.
• Check the blocking.
• Check the mode.
• Check the measurement value.
• Check the connection to trip and disturbance recorder functions.
• Check the channel settings.

9.3.2.1 Inspecting the wiring GUID-665B75A6-A074-4A03-ADF1-3D0FAD198E61 v5

The physical inspection of wiring connections often reveals the wrong connection for phase
currents or voltages. However, even though the phase current or voltage connections to IED
terminals might be correct, wrong polarity of one or more measurement transformers can
cause problems.

• Check the current or voltage measurements and their phase information from Main
menu/Measurements/Analog primary values or Analog secondary values.
• Check that the phase information and phase shift between phases is correct.
• Correct the wiring if needed.
• Change the parameter Negation in Configuration/Analog modules/
3PhaseAnalogGroup/SMAI_20_n:1 (n= the number of the SMAI used).

Changing the Negation parameter is not recommended without


special skills.

• In PCM600, change the parameter CTStarPointn (n= the number on the current
input) under the parameter settings for each current input.
• Check the actual state of the connected binary inputs.

98 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 9
Troubleshooting

• In LHMI, select Main menu/Tests/I/O modules. Then navigate to the board with the
actual binary input to be checked.
• With PCM600, right-click the product and select Signal Monitoring. Then navigate to
the actual I/O board and to the binary input in question. The activated input signal is
indicated with a yellow-lit diode.

• Measure output contacts using the voltage drop method of applying at least the minimum
contact load given for the output relays in the technical data, for example 100 mA at 24 V
AC/DC.

Output relays, especially power output relays, are designed for breaking
high currents. Due to this, layers of high resistance may appear on the
surface of the contacts. Do not determine proper functionality of
connectivity or contact resistance by measuring with a regular hand-held
ohm meter.

V 2

A 1 3

4
GUID-BBAEAF55-8D01-4711-A71D-BBC76B60BA3D V1 EN-US

Figure 18: Testing output contacts using the voltage drop method

1 Contact current
2 Contact voltage drop
3 Load
4 Supply voltage

Bay control REC650 99


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 9 1MRK 511 288-UEN B
Troubleshooting

1 V

GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN-US

Figure 19: Testing a trip contact

1 Trip contact under test


2 Current limiting resistor

• To check the status of the output circuits driving the output relay via the LHMI, select
Main menu/Tests/I/O modules and then navigate to the board with the actual binary
output to be checked.
• Test and change the relay state manually.
1. To set the IED to test mode, select Main menu/Tests/IED test mode/TESTMODE:1
and set the parameter to On.
2. To operate or force the output relay to operate, select and then navigate to the
board with the actual binary output relay to be operated/forced.
3. Select the BOn_PO to be operated/forced and use and or to operate the
actual output relay.
In PCM600, only the result of these operations can be checked by right-clicking the
product and selecting Signal Monitoring tool and then navigating to the actual I/O-
board and the binary input in question. The activated output signal is indicated with
a yellow-lit diode. Each BOn_PO is represented by two signals. The first signal in
LHMI is the actual value 1 or 0 of the output, and in PCM600 a lit or dimmed diode.
The second signal is the status Normal or Forced. Forced status is only achieved
when the BO is set to Forced or operated on the LHMI.

100 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 9
Troubleshooting

Set the parameter TestMode to Off after completing these tests. The
Start LED stops flashing when the relay is no longer in test mode.

An initially high contact resistance does not cause problems as it is reduced quickly by the
electrical cleaning effect of fritting and thermal destruction of layers, bringing the contact
resistance back to the mOhm range. As a result, practically the full voltage is available at the
load.

Bay control REC650 101


Commissioning manual
© Copyright 2013 ABB. All rights reserved
102
1MRK 511 288-UEN B Section 10
Glossary

Section 10 Glossary
M14893-1 v11.1.1

AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fibre optic connector
BFP Breaker failure protection
BI Binary input
BOS Binary outputs status
BR External bistable relay
BS British Standards
CB Circuit breaker
CCITT Consultative Committee for International Telegraph and Telephony. A
United Nations-sponsored standards body within the International
Telecommunications Union.
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600
CO cycle Close-open cycle
COMTRADE Standard format according to IEC 60255-24
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT Capacitive voltage transformer

Bay control REC650 103


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 10 1MRK 511 288-UEN B
Glossary

DAR Delayed autoreclosing


DARPA Defense Advanced Research Projects Agency (The US developer of the
TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFC Data flow control
DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DTT Direct transfer trip scheme
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility
EMF Electromotive force
EMI Electromagnetic interference
EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fibre connector
FAN Fault number
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech, data and
protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission of up to seven
duplex channels of digital data over optical fibers
FTP File Transfer Protocal
FUN Function type
GCM Communication interface module with carrier of GPS receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application

104 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 10
Glossary

GSE Generic substation event


HDLC protocol High-level data link control, protocol based on the HDLC standard
HFBR connector type Plastic fiber connector
HMI Human-machine interface
HSAR High speed autoreclosing
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 61869-2 IEC Standard, Instrument transformers
IEC 60870-5-103 Communication standard for protective equipment. A serial master/
slave protocol for point-to-point communication
IEC 61850 Substation automation communication standard
IEC 61850–8–1 Communication protocol standard
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-
pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules. References
the CMC (IEEE P1386, also known as Common Mezzanine Card)
standard for the mechanics and the PCI specifications from the PCI SIG
(Special Interest Group) for the electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber
Security Capabilities
IED Intelligent electronic device
I-GIS Intelligent gas-insulated switchgear
Instance When several occurrences of the same function are available in the IED,
they are referred to as instances of that function. One instance of a
function is identical to another of the same kind but has a different
number in the IED user interfaces. The word "instance" is sometimes
defined as an item of information that is representative of a type. In
the same way an instance of a function in the IED is representative of a
type of function.
IP 1. Internet protocol. The network layer for the TCP/IP protocol suite
widely used on Ethernet networks. IP is a connectionless, best-effort
packet-switching protocol. It provides packet routing, fragmentation
and reassembly through the data link layer.
2. Ingression protection, according to IEC standard
IP 20 Ingression protection, according to IEC standard, level 20
IP 40 Ingression protection, according to IEC standard, level 40
IP 54 Ingression protection, according to IEC standard, level 54
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B, standard 200
ITU International Telecommunications Union
LAN Local area network
LCD Liquid crystal display
LDD Local detection device

Bay control REC650 105


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 10 1MRK 511 288-UEN B
Glossary

LED Light-emitting diode


LNT LON network tool
MCB Miniature circuit breaker
MVAL Value of measurement
NCC National Control Centre
NOF Number of grid faults
NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event than start/pick-up
OV Over-voltage
Overreach A term used to describe how the relay behaves during a fault condition.
For example, a distance relay is overreaching when the impedance
presented to it is smaller than the apparent impedance to the fault
applied to the balance point, that is, the set reach. The relay “sees” the
fault but perhaps it should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near proximity to the
measured and/or controlled components
PSM Power supply module
PST Parameter setting tool within PCM600
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital data in point-
to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close
SCL Short circuit location
SCS Station control system
SCADA Supervision, control and data acquisition

106 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
1MRK 511 288-UEN B Section 10
Glossary

SCT System configuration tool according to standard IEC 61850


SDU Service data unit
SMA connector Subminiature version A, A threaded connector with constant
impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize computer clocks
on local area networks. This reduces the requirement to have accurate
hardware clocks in every embedded system in a network. Each
embedded node can instead synchronize with a remote clock,
providing the required accuracy.
SOF Status of fault
SPA Strömberg protection acquisition, a serial master/slave protocol for
point-to-point communication
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport layer
protocol used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The de facto
standard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP
was developed by DARPA for Internet working and encompasses both
network layer and transport layer protocols. While TCP and IP specify
two protocols at specific protocol layers, TCP/IP is often used to refer
to the entire US Department of Defense protocol suite based upon
these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)
TNC connector Threaded Neill-Concelman, a threaded constant impedance version of a
BNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents and voltages
taken from the process into levels suitable for further signal
processing.
TYP Type identification
UMT User management tool
Underreach A term used to describe how the relay behaves during a fault condition.
For example, a distance relay is underreaching when the impedance
presented to it is greater than the apparent impedance to the fault
applied to the balance point, that is, the set reach. The relay does not
“see” the fault but perhaps it should have seen it. See also Overreach.

Bay control REC650 107


Commissioning manual
© Copyright 2013 ABB. All rights reserved
Section 10 1MRK 511 288-UEN B
Glossary

UTC Coordinated Universal Time. A coordinated time scale, maintained by


the Bureau International des Poids et Mesures (BIPM), which forms the
basis of a coordinated dissemination of standard frequencies and time
signals. UTC is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize it with
Universal Time 1 (UT1), thus allowing for the eccentricity of the Earth's
orbit, the rotational axis tilt (23.5 degrees), but still showing the Earth's
irregular rotation, on which UT1 is based. The Coordinated Universal
Time is expressed using a 24-hour clock, and uses the Gregorian
calendar. It is used for aeroplane and ship navigation, where it is also
sometimes known by the military name, "Zulu time." "Zulu" in the
phonetic alphabet stands for "Z", which stands for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
3IO Three times zero-sequence current. Often referred to as the residual or
the earth-fault current
3UO Three times the zero sequence voltage. Often referred to as the
residual voltage or the neutral point voltage

108 Bay control REC650


Commissioning manual
© Copyright 2013 ABB. All rights reserved
109
ABB AB
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Scan this QR code to visit our website

www.abb.com/protection-control
1MRK 511 288-UEN

© Copyright 2013 ABB.


All rights reserved.

You might also like