Selection of Fired Process Heaters
Selection of Fired Process Heaters
Selection of Fired Process Heaters
Changes shown by
CONTENTS
Section Page
SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Design Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
International Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Other Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
BACKGROUND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Process Fired Heaters (Conventional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pyrolysis Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Types of Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TYPES OF FIRED HEATERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Vertical-Cylindrical Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Horizontal Tube Cabin Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hoop-Tube Cabin Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Vertical Tube Box Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Tube Box Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
FIRED HEATER SELECTION AND DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fired Heater Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Return on Incremental Investment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Factors Affecting Fired Heater Selection and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Stack Temperature (Ts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
OPERATING CONDITIONS AND FLUID CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fired Heaters in All-Liquid or Vaporizing Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fired Heaters in All-Vapor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Multi-Service Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
High-Pressure Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
COMPUTER PROGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
TABLES
Table 1 Checklist of Items Normally Covered in Process Fired Heater Design Specifications . . . . . . . . . . . . 14
Table 2 Checklist of Items Normally Covered in Fired Heater Duty Specifications . . . . . . . . . . . . . . . . . . . . . . 16
Table 3 Factors Affecting Fired Heater Selection and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
FIGURES
Figure 1 Vertical-Cylindrical Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 2 Vertical-Cylindrical Fired Heater with Horizontal Convection Section . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 3 Horizontal Tube Cabin Fired Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 4 Variations of Cabin Fired Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 5 Vertical Tube Box Fired Heater Proprietary Exxon High Intensity Fired Heater . . . . . . . . . . . . . . . . . . 22
Figure 6 Single Wing Horizontal Tube Box Fired Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 7 Fired Heater Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Revision Memo
SCOPE
This subsection describes the different types of fired process heaters which are available and gives guidelines for selecting and
specifying the fired heater for a specific service. Fired heater design is covered in other subsections.
REFERENCES
INTERNATIONAL PRACTICES
IP 3-4-1 Piping for Fired Equipment
IP 18-3-2 Statically Cast Steel and Alloy Pressure Containing Parts, and Tube Supports for Fired Heaters
IP 18-3-3 Centrifugally Cast High Alloy Tubes for Fired Heaters other than Steam Cracking Reactors
OTHER LITERATURE
API 560, Fired Heaters for General Refinery Services
API 530, Recommended Practice for Calculation of Heater Tube Thickness in Petroleum Refineries
Guide to Boiler and Fired Heater Turndown and Excess Air Reduction
BACKGROUND
The heating of a process fluid in a fired heater is accomplished through a combination of radiation and convection heat transfer.
The usual flow pattern of the process fluid is countercurrent to the flue gas; i.e., the process fluid passes first through the convection
section and then through the radiant section of the fired heater, whereas the flue gas travels in the other direction. This arrangement
yields a higher fired heater efficiency (lower stack gas temperature) than would be the case with concurrent flow.
BACKGROUND (Cont)
In the radiant section, heat is transferred to the process fluid mainly by radiation from high-temperature flue gas which results from
combustion of fuel in the fire box. Some heat is also transferred here by convection. As the flue gas in the radiant section gives up
its heat and becomes cooler, heat transfer by radiation requires progressively more tube area, therefore becoming progressively
less economical. For this reason, the transition to the convection section is made while the flue gas is still relatively hot.
In the convection section, heat transfer is mainly by convection, although a small amount of radiant heat transfer occurs here also.
After all of the heat which can be economically recovered has been transferred to the process fluid, the flue gas leaves the fired
heater and passes through a stack to the atmosphere.
Fired heaters fall into two main categories: process and pyrolysis fired heaters.
Some fired heaters such as visbreakers and thermal crackers, are considered to be process heaters even though they
have chemical reactions taking place inside the tubes. Their temperatures are low, compared to those of pyrolysis heaters, and
apart from the cracking calculations (consult the Heat Transfer Equipment Section of EETD), the designs closely resemble those
for process heaters.
TYPES OF SPECIFICATIONS
Two types of documents are used for specifying fired heaters: design specifications or duty specifications. In a design specification,
all of the major variables which affect performance have been determined by the designer and are specified. The fired heater vendor
must then provide the detailed mechanical design. In a duty specification, only the service requirements (e.g., heat duty and inlet
and outlet conditions) of the equipment are given. The vendor then provides both the process and mechanical designs.
Items covered in each type of specification are given in Tables 1 and 2. Fired Heater Data Sheets, ER&E developed or API 560,
may be used to present the information required by either type of specification. Most of the fired heaters specified by Exxon
Engineering are covered by a design specification. TO PROTECT PROPRIETARY TECHNOLOGY, PROCESS INFORMATION
FOR FIRED HEATERS COVERED BY DESIGN SPECIFICATIONS SHALL NOT BE DIVULGED TO THE FIRED HEATER
VENDOR BEFORE THE APPROPRIATE SECRECY AGREEMENTS HAVE BEEN EXECUTED.
DEFINITIONS
(SEE ALSO FIGURES 1 THROUGH 6)
Air Preheater. A heat exchanger which heats the air required for combustion by exchanging heat with the flue gases leaving the
convection section.
Arch. The overhead (usually flat) portion of the radiant section, supported from above.
Box. The burners and tubes are enclosed in the fire box, which consists of a structure, refractory lining and tube supports.
Breeching. The hood which collects the flue gas at the convection section exit, for transmission to the stack.
Bridgewall Temperature. The temperature of the flue gas leaving the radiant section. The term comes from the old horizontal box
heaters, where a bridgewall physically separated the radiant and convection sections.
Bulk Temperature. The average temperature of the process fluid at any tube cross-section.
DEFINITIONS (Cont)
(SEE ALSO FIGURES 1 THROUGH 6)
Casing. A steel sheathing which encloses the heater box and makes it essentially air-tight.
Cell. A portion of the radiant section, separated from other cells by tubes or a refractory wall. Also called a “zone”.
Center Wall. A refractory wall in the radiant section, which divides it into two separate cells.
Coil. A series of straight tube lengths connected by 180_ return bends, forming a continuous path through which the process fluid
passes and is heated.
Convection Section. The portion of a heater, consisting of a bank of tubes, which receives heat from the hot flue gases, mainly
by convection.
Conversion. The fraction of feed converted into a desired product, usually expressed as LV%. Applied mainly to Visbreaker and
Thermal Cracker Fired Heaters.
Corbelling. Narrow ledges extending from the convection section side walls to prevent flue gas from flowing preferentially up the
side of the convection section, between the wall and the nearest tubes, thereby bypassing the tube bank.
Critical Velocity. A fluid velocity equal to the velocity of sound through the fluid at its temperature and pressure. Also called
“sonic velocity”.
Crossover. Piping which transfers the process fluid either externally or internally from one section of the heater to another.
Damper. A device to regulate flow of gas through a stack or duct and to control draft in a heater. A typical damper consists of one
or more flat plates connected to a shaft(s) which can be rotated.
Draft. The negative pressure (vacuum) at a given point inside the heater, usually expressed in inches of water.
Excess Air. The percentage of air in the heater in excess of the stoichiometric amount required for combustion.
Extended Surface. Surface added to the outside of bare tubes in the convection section to provide more heat transfer area. This
may consist of cylindrical studs butt-welded to the tube or fins continuously wound around and welded to the tube.
Film. A thin fluid layer adjacent to a pipe wall which remains in laminar flow, even when the bulk flow is turbulent. The velocity profile
in the film is approximately linear, with zero velocity existing at the wall.
Film Temperature. The maximum temperature in the film, at the tube wall.
Fire Box. A term used to describe the structure which surrounds the radiant coils and into which the burners protrude.
Flue Gas. A mixture of gaseous products resulting from combustion of the fuel.
Fouling. The building up of a film of dirt, ash, soot or coke on heat transfer surfaces, resulting in increased resistance to heat flow.
Forced Draft. Use of a fan to supply combustion air to the burners and to overcome the pressure drop through the burners. This
is in contrast to natural draft, where the buoyancy of the column of hot flue gas in the stack and heater provides the “suction” to pull
combustion air into the burners.
Fired Heater Efficiency. The ratio of heat absorbed to heat fired, on a lower heating value basis.
Gross Fuel. The total fuel fired in the heater, including all losses (usually expressed in lb/hr or kg / hr).
Header. The fitting which connects two tubes in a coil. In common usage, “header” refers to cast or forged 180_ “U-bends” (“return bends”).
DEFINITIONS (Cont)
(SEE ALSO FIGURES 1 THROUGH 6)
Header Box. The compartment at the end of the convection section where the headers are located. There is no flue gas flow in
the header box, since it is separated from the inside of the heater by an insulated tube sheet. Header boxes are sometimes also
used in the radiant section.
Heat Available. The heat absorbed from the products of combustion (flue gas) as they are cooled from the flame temperature to
a given flue gas temperature.
Heat Density. The rate of heat transfer per unit area to a tube, usually based on total outside surface area. Typical units are
Btu/hr-sq. ft (w/m2). Also called “heat flux”.
Heat Duty. The total heat absorbed by the process fluid, usually expressed in MBtu/hr (MW). Total fired heater duty is the sum of
heat transferred to all process streams, including auxiliary services such as steam superheaters and drier coils.
Heat Fired. The total heat released in the heater, equal to gross fuel times lower heating value (LHV) of the fuel. Usually expressed
in MBtu/hr (MW).
Higher Heating Value (HHV). The theoretical heat of combustion of a fuel, when the water formed is considered as a liquid (credit
taken for its heat of condensation). Also called “gross heating value”.
Hip Section. The transition zone at the top of the radiant section in cabin type heaters. The wall of this section is usually at a
45 degree angle.
Induced Draft. Use of a fan to provide the additional draft required over that supplied by the stack, to draw the flue gas through the
convection section, and any downstream heat recovery equipment (i.e., air preheater).
Inspection Doors. Openings in the convection section sidewalls to allow inspection of tubes, extended surfaces and supports,
when the heater is out of service.
Lower Heating Value (LHV). The theoretical heat of combustion of a fuel, when no credit is taken for the heat of condensation of
water in the flue gas. Also called “net heating value”. Usually expressed in Btu/lb (kJ/kg).
Manifold. A pipe connected to several parallel passes and used to distribute or collect fluid from these passes.
Mass Velocity. The mass flow rate per unit of flow area through the coil. Typical units are lb/s-sq. ft (kg/s-m2).
Natural Draft. System in which the draft required to move combustion air into the heater and flue gas through the heater and out
the stack is provided by stack effect alone.
Net Fuel. The fuel which would be required in the heater if there were no radiation losses. Usually expressed in lb/hr (kg/hr).
Observation Doors. Openings in the radiant section floor and at selected points along the walls, to permit viewing of tubes,
supports, and burners.
One-Side Fired Tubes. Radiant section tubes located adjacent to a heater wall have only one side directly exposed to a burner
flame. Radiation to the back side of the tubes is by reflection/reradiation from the refractory wall.
Pass. A coil which transports the process fluid from fired heater inlet to outlet. The total process fluid can be transported through
the heater by one or more parallel passes.
Peepholes. Small observation ports usually placed in the radiant section floor and/or arch to permit viewing of tubes, supports and
burners. They are usually glass covered.
Radiant Section. The section of the fired heater in which heat is transferred to the heater tubes primarily by radiation from
high-temperature flue gas.
Service Factor. A measure of the continuity of operation, generally expressed as the ratio of total running days for a given time
period to the total calendar days in the period.
DEFINITIONS (Cont)
(SEE ALSO FIGURES 1 THROUGH 6)
Shield Section. The first two tube rows of the convection section. These tubes are exposed to direct radiation from the radiant
section and usually receive about half of their heat in this manner. They are usually made of more resistant material than the rest
of the tubes in the convection section. Extended surfaces are not used in this section.
Sootblower. A steam lance (usually movable) in the convection section for blowing soot and ash from the tubes using
high-pressure steam.
Stack. A cylindrical steel, concrete or brick shell which carries flue gas to the atmosphere and provides necessary draft.
Stack Effect. The difference (buoyancy) between the weight of a column of high-temperature gases inside the heater and/or stack
and the weight of an equivalent column of external air, usually expressed in inches of water per foot of height.
Stack Temperature. The temperature of the flue gas as it leaves the convection section, or air preheater directly upstream of the stack.
Transfer Line. Piping used to connect the fired heater outlet to downstream processing equipment (tower, reactor, etc.).
Tube Sheet. A large tube support plate located in the convection section and supporting a number of tubes. The end supports are
usually carbon steel or low-alloy steel and make up one side of the header box. The inside of the end supports, which is exposed
to the flue gas, is insulated. Intermediate supports are exposed to flue gas on both sides and are fabricated of a suitable alloy
material, usually castings.
Tube Support. A metal part which supports the weight of the tube.
Turndown. Reduced operating conditions compared to design conditions. This usually refers to reduced heat duty, which may be
the result of reduced throughput and/or reduced enthalpy requirements.
Two-Side Fired Tubes. Radiant section tubes which are exposed on both sides to direct radiation from the burners.
Many fired heater types, or arrangements, are available and have been used over the years. These heaters are all made up of four
basic components: box, burners, coil and stack. The fired process heaters described below are currently the types most commonly
found in Exxon refineries and chemical plants.
Vertical-cylindrical heaters are designed both with and without a convection section. The all-radiant heater (Figure 1A) is
inexpensive, but since the temperature of flue gases leaving the heater is high, 1500 – 1800_F (815 – 980_C), it has a very low
efficiency. A convection section can usually be justified, except for the very smallest heaters less than about 5 MBtu/hr (1.5 MW),
heaters infrequently operated, or in locations where fuel costs are extremely low.
Most vertical-cylindrical fired heaters now built have a horizontal convection section located above the radiant section (Figure 2).
Flue gases flow upwards through the convection bank and then to the stack. The shield section consists of the bottom two rows
of tubes in the convection section.
Some older vertical-cylindrical fired heaters have vertical convection sections (Figure 1B). Often the same tube is used for both
radiant and convection service (integral convection section). The convection portion of the tube usually has some form of extended
surface to increase the convection heat transfer rate. Only gas or distillate fuels should be fired in this type heater, since the
convection section is almost impossible to clean. This type of fired heater has not been built since the mid-1960’s.
Horizontal tube cabin fired heaters have been built in sizes up to about 500 MBtu/hr (145 MW) heat absorbed. However, in small sizes
under about 120 MBtu/hr (35 MW), vertical cylindrical fired heaters are usually more economical, and in sizes larger than about
150 MBtu/hr (45 MW), the vertical tube box fired heater is generally more economical. Also, both vertical tube type fired heaters require
less plot area. Therefore, except in special cases, horizontal tube cabin fired heaters are no longer being designed by Exxon Engineering.
Variations of the cabin fired heater arrangements are made for certain applications, as illustrated in Figure 4. Cabin fired heaters
with a center wall (Figures 4A and B) can be used for the following services:
1. For large fired heaters, the use of an air-cooled center wall permits about twice the surface for a given tube length. This configuration
is usually used when tubes in a single radiant zone would be over about 80 ft (24 m) long, or the radiant zone over 40 ft (12 m) high.
2. Where two separate heating zones (i.e., two or more separately controlled services) are required in the radiant section.
Depending upon the heater size, the center wall may or may not be covered with tubes. The different services must be
compatible, since to some extent the firing in one section will affect heater transfer in the other section. The maximum turndown
of one service is to about 75% of design with the other service at full capacity, if both services use the convection section
(or to about 50% of design if one is in all-radiant service). If one service is taken off stream, the heater must be completely shut
down or some other fluid circulated through the off-stream section to prevent tube burnout.
HOOP-TUBE CABIN FIRED HEATERS
In all-vapor flow, non-coking services where low coil pressure drop is desired (such as POWERFORMING units), cabin fired heaters
with vertically oriented, bent, or “hoop”, tubes offer considerable savings in investment (Figures 4C and D). This arrangement
permits a low process mass velocity to be used, because of the many parallel flow passes, without maldistribution of flow.
For POWERFORMING heaters, the radiant section consists of separate zones for preheat and for each reheat duty. These zones
are separated by free-standing brick walls. Flue gases from all of the radiant zones pass through a common convection section,
which in the past has been utilized for preheat service only. In such a heater, variations in operating conditions of the individual
services should be carefully considered, since the reheat zones are also providing heat to the preheat convection coil. More recently,
with low pressure POWERFORMING, the entire process duty will be absorbed in the radiant section and the convection section
used for a separate service(s). This is due to the relatively high/costly pressure drop of the convection coil. POWERFORMING
heaters of the hoop tube type have been built in sizes from about 70 to 400 MBtu/hr (20 to 120 MW) total heat absorbed.
Figure 5 shows a typical vertical tube box fired heater. In the radiant section, tubes stand vertically along all four walls. These tubes
are fired from one side, the same as in vertical-cylindrical and cabin fired heaters. In addition, rows of standing vertical tubes running
across the box are fired on both sides by the floor-mounted burners. These two-side fired tubes have a 50% greater heat input than
the wall tubes, although the peak heat density is the same as for the wall tubes.
The addition of the two-side fired tubes shortens the radiant coil and results in a significant decrease in radiant box volume,
compared to horizontal tube cabin heaters. Each tube pass has an equal number of both wall and center tubes, so that heat
distribution between passes is uniform. This heater is particularly well suited for the large forced-draft burners now in general usage.
Two to four burners provide the required heat input to each cell and usually set the box dimensions. A horizontal convection section
running the entire length of the heater is located above the radiant section.
Variations of the vertical tube box fired heater arrangement are occasionally used. The most common variation consists of installing
only the two-side fired center tubes. These tubes are usually installed in a number of rows across the box, normal to the convection
section. They may also be installed in two rows parallel to the convection section, extending the entire length of the heater. The latter
arrangement is like that used in steam reformer fired heaters.
For a given heat duty, the use of all two-side fired radiant tubes requires less tube surface (and a shorter coil length) than in a
conventional heater. As mentioned above, the two-side fired tubes pick up 50% more heat than the one-side fired wall tubes.
However, the advantage of a shorter coil is offset by the need for a larger radiant section box. The use of two-side fired tubes only
is advantageous in the following cases:
1. Where tube materials are very expensive; e.g., thick-wall stainless steel tubes.
2. Where short residence time is required.
3. Where allowable coil pressure drop is low.
4. Where preinvestment for future increased capacity is required. (Wall tubes can be added later.)
HORIZONTAL TUBE BOX FIRED HEATERS
Figure 6 shows the side view of a typical horizontal tube box fired heater. The radiant and convection sections are separated by
a wall called the bridge wall. Larger box heaters have two radiant sections, with a common convection section located between
them. Although these heaters were commonly built until about 1955, they are now obsolete because of their high initial cost.
1. Operability – The ability of the fired heater to safely meet the process requirements with an acceptable service factor is
undoubtedly the most important single measure of performance.
2. Maintenance – Costs and manpower required to maintain the fired heater in a condition to meet process requirements must
be considered. Incremental investment to reduce maintenance costs must be judged against these savings. In most cases, this
is largely based on judgment, refinery experience and project investment philosophy.
RETURN ON INCREMENTAL INVESTMENT
This factor affects mainly the fired heater tube area; i.e., adding heat transfer surface to increase efficiency and save fuel. This is
probably the only type of fired heater investment that can be readily broken out and evaluated on its own.
Heat Duty andType of Service – The main considerations in selecting the specific fired heater type are the heat duty and the type
of fluid flow (all-liquid or vaporizing flow vs. all-vapor flow). Since the radiant heat density (flux rate) is largely fixed for any given
service, the physical size of the heater is proportional to duty. Thus, except for borderline cases, the selection of the best heater
type is usually clear-cut. A fired heater selection guide is given in Figure 7. Note that in some cases requiring very small fired heaters
(duties < 25 MBtu/hr or 7.5 MW), commercially available packages may be appropriate and can result in significant investment
savings vs. a custom designed fired heater.
Type of Fuel – The fuel to be fired in a fired heater has a marked effect on the design. It is therefore extremely important to decide
what fuel or fuels are to be fired before beginning any detailed design work. Factors affected by the type of fuel are:
1. Fired Heater Efficiency – Fuel value will affect the incremental heater investment that can be justified to increase efficiency.
2. Fired Heater Cost – In general, a heater designed to fire heavy liquid fuel requires 10 to 20% greater investment than for the
same duty heater designed to fire only gas. This is due largely to sootblower investment.
3. Type of Convection Section Extended Surface – Tubes with thin, closely spaced fins are easily fouled and therefore
should be used only with gas firing (or very light liquid fuels). Thick finned or studded tubes must be used if the fuel is heavier
than 25_ API.
' 4. Convection Section Cleaning – If the fuel oil contains more than 0.01 wt% ash, sootblowers must be provided to keep the
convection tubes clean. This is nearly always the case with heavy liquid fuels. Sootblowers should also be provided for dirty
gaseous fuels producing more than 5 wppm (5 mg/kg) particulates in the flue gas.
5. Type of Burners – Gas firing is usually done with natural-draft burners of the raw gas or inspirating type. These burners are
easy to operate and maintain, combustion is good and noise attenuation is easily accomplished by primary mufflers and plenum
chambers.
Oil firing is more difficult than gas firing due to plugging of oil guns by solids in the fuel. Natural-draft oil burners require higher
operating and maintenance attention. Noise attenuation is accomplished by plenum chambers, but oil dripping back into these
plenums may cause a serious maintenance problem.
To reduce these problems, forced-draft burners are often used for oil firing. Combustion is better than in natural-draft burners
due to better fuel and air mixing, maintenance and operator attention are reduced and noise in the forced-draft system is easily
attenuated. The forced-draft system provides an efficiency credit when either fuel oil or a combination of gas and oil is fired, due
to lower excess air requirements, and is also readily adaptable to computer control.
Forced draft burners or natural draft burners, adapted for forced draft service, are usually required for fired heaters equipped
with air preheaters.
6. Radiant and Convection Section Layout – Greater clearances between burners and tubes are usually required for firing of
oil fuels, compared to gaseous fuels, because of the larger flames produced from oil firing. When heater stack height is
determined by draft requirements, flue gas mass velocities in the convection section should be designed lower for oil firing than
for gas firing, because of the greater fouling potential of oil fuels. When stack height is set by environmental/pollution
considerations or when induced draft systems are employed, sufficient draft may be available to overcome pressure losses in
fouled convection sections. Higher design mass velocities may then be used for oil firing installations. These higher mass
velocities increase convection heat transfer coefficients and therefore, may reduce the amount of convection surface required.
7. Design Excess Air – A higher combustion air rate is necessary than that theoretically required for complete combustion of the
fuel. This is caused by variations in the distribution of air and fuel to the individual burners, as well as by imperfect mixing of air
and fuel in the burner and the flame. Consequently, extra air must be supplied to obtain satisfactory combustion. However, no
more excess air should be furnished than that actually required, since any additional air must be heated up to the stack exit
temperature, wasting fuel.
All fired heaters designed for forced-draft firing (regardless of fuel) or for natural draft firing of gas fuel should be based on 15%
excess air. Heaters designed for natural draft fuel oil firing, or combination gas/oil firing, encounter greater mixing difficulties and
should be designed for 20% excess air.
8. Corrosive Materials – Special construction materials may be required for refractory and tube supports if the fuel contains high
concentrations of corrosive materials, such as vanadium, sodium or sulfur. See IP 7-1-1.
Design tube metal temperature should be kept below 1200_F if the fuel contains more than about 150 ppm vanadium plus sodium.
9. “Cold-End” Corrosion – Special consideration should be given to services with tube metal temperatures, or coil inlet
temperatures, below about 250 to 300_F (120_C to 150_C) to avoid “cold-end” corrosion. When fuels containing sulfur are
burned, part of the sulfur is converted to sulfur trioxide (SO3), which combines with water vapor to form sulfuric acid. This sulfuric
acid remains in the vapor state as long as the temperature is above the dew point of the gas, but condenses out on relatively
cool surfaces, below about 250 to 300_F (120_C to 150_C) and causes metal corrosion. The surfaces most likely to be affected
are the last rows of convection section tubes, and the cold end of air preheaters where metal temperatures are close to the flue
gas dew point temperature.
Flue gas dew points can be determined from the Exxon Refinery Construction Materials Manual.
STACK TEMPERATURE (T S)
The economical stack temperature is a function of fuel value, process inlet temperature, cost of incremental convection section or
air preheater capacity and the required rate of return on incremental investment. For heaters that include air preheat facilities the
economical stack temperature is normally set by cold end corrosion considerations and is discussed more fully in Subsection VIII-K
on Air Preheaters. For heaters without air preheat, an approach temperature of 25 – 50_F (15 – 30_C) between stack temperature
and inlet process stream temperature can visually be justified. The situation where this would not be true will usually have one or
more of the following characteristics:
= C
S
0.12 100
When calculating investment for convection section surface, care must be taken to consider step changes which are occasionally
necessary. For example, the return on incremental investment for the last two or three rows of tubes would be much lower if an
additional row of sootblowers is required than if it were not.
Another factor which will enter into the calculation of incremental investment is the change in the radiant section investment due
to the increased heat transferred in the convection section. The increased investment in the convection section and stack is
sometimes partly offset by a reduction in investment in the radiant section. For heaters in which the radiant heat duty is essentially
constant (steam crackers and steam reformers), the savings due to increased convection heat duty will take the form of reduced
investment or fuel savings for other equipment such as offsite steam generation.
Typically, in process heaters designed for non-cracking services such as atmospheric and vacuum pipestills, incipient coke begins
to form at a film temperature above about 660_F (350_C), usually equivalent to a bulk fluid temperature of about 600_F (315_C).
In other services such as Visbreaking and Thermal Cracking, where fluid cracking is an inherent characteristic of the process,
acceptable coke formation and run length can usually be attained if film temperatures do not exceed 910_F (490_C), equivalent
to a bulk fluid temperature of about 880_F (470_C).
In order to directionally mitigate the formation of coke, a high inside film coefficient is necessary to minimize the difference between
bulk fluid and film temperature. This high film coefficient is obtained largely by maintaining adequately turbulent flow conditions
inside the tube. The higher the mass velocity the better the heat transfer coefficient will be.
However, too high a mass velocity will cause a high coil pressure drop, resulting in high pumping costs, increased design pressure
of upstream equipment, and sometimes, erosion of return bends. Therefore, the design mass velocity is usually kept in a range of
250 to 300 lb/s ft2 (1220 to 1465 kg/s-m2) for most conventional, non-cracking liquid or vaporizing hydrocarbon services. For
cracking services, such as Visbreaking and Thermal Cracking, mass velocities in a range of 550 – 600 lb/s ft2 (2700 – 2930 kg/s-m2)
are usually used. These target velocities have been found satisfactory for either horizontal or vertical flow tubes. More specific
recommendations for mass velocity in different services are given in Subsection VIII-B.
In addition to these mass velocity criteria, special services such as lube plant vacuum pipestill fired heaters must also meet
residence time/temperature criteria to avoid color degradation of the lube product. These special requirements are frequently
provided by the Process Designer in the Design Basis memorandum covering the heater or may be discussed with fired heater
design specialists in the Heat Transfer Equipment Section of EETD.
During the design of fired heaters consideration must be given to unit performance during anticipated turndown operations. Earlier
Design Practices guidelines required that mass velocity during maximum turndown should not be permitted to drop below
150 – 180 lb/s ft2 (730 – 880 kg/s-m2). However, more recent information, based on simulation studies and extensive field data,
strongly support the position that most fired heaters in non-cracking services can be satisfactorily operated at substantially lower
mass velocity during turndown. Also, the bases for establishing permissible turndown criteria must account for changes in other
parameters such as coil inlet temperature, firing patterns, air preheat and excess air levels and radiant vs. convection section duty
shifts. The inter-relationships of these parameters are discussed in considerable detail in Report EE.70E.75, Pipestill Furnace
Turndown, dated August, 1975; and, in a more comprehensive manual, Guide to Boiler and Fired Heater Turndown and Excess
Air Reduction. The substantive conclusion of these studies is that most conventional all liquid and vaporizing service fired heaters
will be more tolerant of turndown operations than once considered prudent.
Even at full design throughput conditions a high film coefficient by itself will not necessarily guarantee a satisfactory design. If the
rate of heat transfer to any point is too great, vaporization on the surface will be so rapid that the area will become vapor-blanketed.
The surface is then essentially covered with vapor bubbles and liquid cannot move in to replace the bubbles. Thus, the effective
film coefficient becomes very low, resulting in excessive tube and film temperatures and rapid coke buildup. For typical vaporizing
hydrocarbon services, about 35,000 Btu/hr-sq. ft (110 kW/m2) is the maximum possible heat transfer rate before a “burn-out”
condition is encountered (assuming adequate mass velocities as discussed above).
The rate of heat transfer is not uniform to all radiant tube surfaces. For typical one-side fired tubes the overall average heat density
is only about 40 to 50% of the maximum point heat flux. For two-side fired tubes this average is improved to about 60 to 75% of
maximum. Therefore, the heater design and operation must be based on average heat densities low enough to assure a satisfactory
maximum density. Detailed recommendations for average radiant heat densities are listed in Subsection VIII-B. Following these
recommendations, as well as all other recommended heater design criteria, will insure that the maximum radiant heat density will
be satisfactory.
One condition that must usually be avoided is going through the dry point in the coil, since this may cause a coking or fouling problem.
Material that does not vaporize may plate out on the tube at the dry point and cause a heavy buildup. This may be a foreign material,
such as corrosion products, or a polymer that was formed in tankage. Such heaters should be designed to get the dry point out of
the heated zone. Maximum vaporization in the coil should be limited to about 80 wt%.
On the other hand, when a distillate, such as a pipestill sidestream, is fed directly into a fired heater (with no intermediate storage),
the risk associated with going through the dry point is minimal, since the distillate has just been completely vaporized and
condensed.
The normal design criteria for vaporizing services may not be applicable to single-component fluids in horizontal tubes. Stratified
flow, leading to excessive tube metal temperatures, has been found in heaters operating near the interface between slug flow and
bubble or froth flow (see Section XIV-C). In such cases, the Heat Transfer Equipment Section of EETD should be consulted.
COMPUTER PROGRAMS
Program 3558, the Fired Heater Simulation Program, is available to aid engineers design new heaters and simulate existing ones.
Program 3660, the Fired Heater Pressure Drop Program, is available for the calculation of pressure drop in fired heater coils and
transfer lines. The program can be used to calculate pressure drops for single phase liquid or vapor processes, as well as mixed
phase processes.
For an up-to-date listing and description of heat transfer programs, personnel should access the Application Technology Set Catalog
(ATS CAT) maintained by ER&E.
TABLE 1
CHECKLIST OF ITEMS NORMALLY COVERED IN PROCESS FIRED HEATER DESIGN SPECIFICATIONS
Notes Notes
TABLE 1 (Cont)
CHECKLIST OF ITEMS NORMALLY COVERED IN PROCESS FIRED HEATER DESIGN SPECIFICATIONS
Notes Notes
Notes:
(1) Items normally shown on fired heater sketch.
(2) Normally covered in utility section of Design Specification.
(3) Normally covered in flow plan section of Design Specification.
(4) Information required by IP 7-1-1.
(5) Instruments are normally shown on the flow plan. They are usually located on the fired heater sketch so that the proper
connections may be provided.
TABLE 2
CHECKLIST OF ITEMS NORMALLY COVERED IN FIRED HEATER DUTY SPECIFICATIONS
TABLE 3
FACTORS AFFECTING FIRED HEATER SELECTION AND DESIGN
DESIGN CONSIDERATION REMARKS
Type of Service (Fluid being heated)
1. All-Liquid
2. Vaporizing Requires adequate mass velocity to minimize coking/fouling.
3. All-Vapor Usually not coking; lower mass velocity to minimize P.
Heat Duty Determines type of fired heater.
Operating Conditions:
1. Feed Rate Affects tube size and number of passes.
2. Process Conditions:
a. Properties
b. Temperature
c. Pressure High pressure ( 1000 psig), requires special considerations.
d. Vaporization Maximum vaporization in the coil should be limited to about 80 wt%.
Minimize vapor at inlet of multi-pass fired heaters.
e. Composition Single-component fluids require special considerations in
vaporizing services.
3. Flue Gas Conditions:
a. Stack Temperature 1. High temperatures increase incentives for air
preheaters/additional waste heat recovery.
b. Composition 2. Low temperatures may result in acid dew point problems.
Fluid Characteristics:
1. Coking Residence time/temperature important.
2. Color Stability
3. Corrosivity
4. H2 / H2S Content Affects tube materials required.
5. Viscosity High viscosity gives poor film coefficient.
Fuels
1. Gas and/or Liquids Affects convection section extended surface, convection section
cleaning, type of burners.
2. Corrosive Compounds Affects tube supports, refractory materials.
3. Cost 1. Affects design fired heater efficiency.
2. Affects air preheater justification.
Special Requirements:
1. High Turndown Fired heater geometry, mass velocity, P.
2. Pre-Investment Two sets of conditions to be covered.
3. Space Limitations Type of fired heater.
4. Special Refinery Requirements Maintenance and operating experience.
5. Air Pollution, SO2 Ground Level Concentration Stack height.
6. Noise Mufflers, forced-draft burners.
7. NOx Low NOx burners.
FIGURE 1
VERTICAL-CYLINDRICAL FIRED HEATERS
Draft Gage
Top Headers
Top Header
Draft Gage Box
Reradiating
Cone
Radiant
Section
Radiant
Radiant Tubes
Section Combustion
Zone
Draft Gage
Draft Gage
FIGURE 2
VERTICAL-CYLINDRICAL FIRED HEATER WITH HORIZONTAL CONVECTION SECTION
ÉÉ É
ÉÉ É
Breeching
Coil Inlet
Convection
ÉÉ É
ÉÉ É
Section
Draft Gage
SIDE VIEW
Radiant
Section
ÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉ
ÇÇÇÇÇÇÇÇÇ
ÉÉÉÉÉÉÉÉÉ
ÇÇÇÇÇÇÇÇÇ
ÉÉÉÉÉÉÉÉÉ
ÇÇÇÇÇÇÇÇÇ
Radiant
ÉÉÉÉÉÉÉÉÉ
ÇÇÇÇÇÇÇÇÇ
ÉÉÉÉÉÉÉÉÉ
Tubes
Draft Gage
ÏÏÏ ÇÇÇÇÇÇÇÇÇ
ÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉ
Burners
Coil Outlet
ÉÉÉÉÉÉÉÉÉ
Radiant Tube Circle
ELEVATION PLAN VIEW
FIGURE 3
HORIZONTAL TUBE CABIN FIRED HEATER
Header Box
+
Breeching
+
+
SIDE VIEW
+
+
Sootblower
Tube Supports
Locations
+
Convection
Radiant
Section
Section
Stack TI
Damper
END VIEW
Draft Gage
Burners
Draft Gages
Shield Tubes
Corbelling
Stack
Coil Inlet
Draft Gage
Outlet
Coil
FIGURE 4
VARIATIONS OF CABIN FIRED HEATERS
FIGURE 5
VERTICAL TUBE BOX FIRED HEATER
PROPRIETARY EXXON HIGH INTENSITY FIRED HEATER
To Stack
1-Side Fired
Wall Tubes
2-Side Fired
Center Tubes
Burners
Forced Air
Supply Duct
FIGURE 6
SINGLE WING HORIZONTAL TUBE BOX FIRED HEATER
Stack
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ Coil Outlet
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
Corbelling
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ Convection
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
Section
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
Shield Tubes
Radiant Section
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
Burners
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
Self-Supporting
Bridge wall
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
Draft Gage Draft Gage
ÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌÌ
FIGURE 7
FIRED HEATER SELECTION GUIDE
Vertical Cylindrical
Horizontal Cabin
ALL-VAPOR SERVICES
Heat Duty Absorbed, MW
20 40 60 80 100 120 140 160
Vertical Cylinder
Multiservice V.C.