Model LT56 Series Special Sprinklers: Model FV Escutcheon Model FP Escutcheon

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Bulletin 058 November 2021

Model LT56 Series Special Sprinklers


Designed specifically for corridors and hallway
K5.6 (80 Metric)
UL Listed

Features
• 28 ft x 10 ft (8.5 m x 3 m) max. coverage area

• UL Listed for Light Hazard occupancies

• Increased spacing and reduced water demand


in corridors compared with traditional extended
coverage sprinklers Models LT56 & LT56-300 Models LT56L & LT56L-300

Product Description
Model LT56 series sprinklers are UL Listed Specific Application
sprinklers designed for installation in accordance with NFPA
13. The sprinklers produce a spray pattern that is specifically
designed to cover long narrow spaces, such as corridors and
hallways, with fewer sprinklers and less water demand compared
with traditional extended coverage sprinklers. Model FV Escutcheon Model FP Escutcheon

Model LT56 series sprinklers are quick-response sprinklers for


use in Light Hazard occupancies only. Model LT56 and Model
LT56-300 sprinklers have a glass bulb operating element.
Model LT56L, LT56L-300, and LT56C sprinklers have a fusible
link operating element. Model LT56, LT56-300, LT56L, and
LT56L-300 sprinklers are available with Model FV recessed
escutcheons, Model FP recessed escutcheons, or Model CCP
concealed cover plates. Model LT56C sprinklers require a Model
G4/G5 flat concealed cover plate. Model G4/G5 Flat Cover Plate Model CCP Cover Plate

Model LT56C Sprinkler

Table A
Max. Working Sprinkler
Operating Coverage
Sprinkler Model Pressure Styles Identification
Element Areas
psi (bar) Number (SIN)
LT56 Glass Bulb 250 (17.2) Table B RA5814
LT56L Fusible Link 250 (17.2) Pendent, Recessed Pendent or Table C R5814
LT56-300 Glass Bulb 300 (21) Conical Concealed Pendent Table D RA5914
LT56L-300 Fusible Link 300 (21) Table E R5914
LT56C Fusible Link 175 (12) Flat Concealed Table F RA5994

www.reliablesprinkler.com
Model LT56 Specific Application Sprinkler SIN RA5814
Technical Specifications Sprinkler Finishes
Style: Pendent, Recessed Pendent, or (See Table H)
Conical Concealed
Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity
Nominal K-Factor: 5.6 (80 metric) Quick-response
Max. Working Pressure: 250 psi (17.2 bar)
Min. Spacing: 14 ft. (4.3 m) Temperature Ratings
155°F (68°C)
Material Specifications 200°F (93°C)
Thermal Sensor: 3 mm glass-bulb
Sprinkler Frame: Brass Alloy Recessed Escutcheons/Cover Plates
Button: Copper Alloy Model FV recessed escutcheon
Sealing Assembly: Nickel Alloy with PTFE Model FP recessed escutcheon
Load Screw: Bronze Alloy Model CCP cover plate
Deflector: Bronze Alloy
Sprinkler Wrenches
Model W2 (pendent)
Model W4 (recessed and concealed)

Listings and Approvals


UL Listed

Model LT56 Sprinkler Components and Dimensions Figure 1

Model LT56 Sprinkler Hydraulic Design Criteria Table B


Minimum Flow and Residual Pressure
Max. Coverage Area Flow Pressure
ft. x ft. gpm psi
(m x m) (l/min) (bar)
28 x 8 23 16.9
(8.5 x 2.4) (87) (1.17)
28 x 10 28 25.0
(8.5 x 3.0) (106) (1.72)
Note: For coverage area dimensions less than or between those listed above, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.

Bulletin 058 Page 2 of 10


November 2021 www.reliablesprinkler.com
Model LT56L Specific Application Sprinkler SIN R5814
Technical Specifications Sprinkler Finishes
Style: Pendent, Recessed Pendent, or (See Table H)
Conical Concealed
Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity
Nominal K-Factor: 5.6 (80 metric) Quick-response
Max. Working Pressure: 250 psi (17.2 bar)
Min. Spacing: 14 ft. (4.3 m) Temperature Ratings
165°F (74°C)
Material Specifications 212°F (100°C)
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Frame: Brass Alloy Recessed Escutcheons/Cover Plates
Button: Copper Alloy Model FV recessed escutcheon
Sealing Assembly: Nickel Alloy with PTFE Model FP recessed escutcheon
Load Screw: Bronze Alloy Model CCP cover plate
Deflector: Bronze Alloy
Sprinkler Wrenches
Model W2 (pendent)
Model W4 (recessed and concealed)

Listings and Approvals


UL Listed

Model LT56L Sprinkler Components and Dimensions Figure 2

Model LT56L Sprinkler Hydraulic Design Criteria Table C


Minimum Flow and Residual Pressure
Max. Coverage Area Flow Pressure
ft. x ft. gpm psi
(m x m) (l/min) (bar)
28 x 8 23 16.9
(8.5 x 2.4) (87) (1.17)
28 x 10 28 25.0
(8.5 x 3.0) (106) (1.72)
Note: For coverage area dimensions less than or between those listed above, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.

Bulletin 058 Page 3 of 10


November 2021 www.reliablesprinkler.com
Model LT56-300 Specific Application Sprinkler SIN RA5914
Technical Specifications Sprinkler Finishes
Style: Pendent, Recessed Pendent, or (See Table H)
Conical Concealed
Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity
Nominal K-Factor: 5.6 (80 metric) Quick-response
Max. Working Pressure: 300 psi (21 bar)
Min. Spacing: 14 ft. (4.3 m) Temperature Ratings
155°F (68°C)
Material Specifications 200°F (93°C)
Thermal Sensor: 3 mm glass-bulb
Sprinkler Frame: Brass Alloy Recessed Escutcheons/Cover Plates
Button: Copper Alloy Model FV recessed escutcheon
Sealing Assembly: Nickel Alloy with PTFE Model FP recessed escutcheon
Load Screw: Bronze Alloy Model CCP cover plate
Deflector: Bronze Alloy
Sprinkler Wrenches
Model W2 (pendent)
Model W4 (recessed and concealed)

Listings and Approvals


UL Listed

Model LT56-300 Sprinkler Components and Dimensions Figure 3

Model LT56-300 Sprinkler Hydraulic Design Criteria Table D


Minimum Flow and Residual Pressure
Max. Coverage Area Flow Pressure
ft. x ft. gpm psi
(m x m) (l/min) (bar)
28 x 8 23 16.9
(8.5 x 2.4) (87) (1.17)
28 x 10 28 25.0
(8.5 x 3.0) (106) (1.72)
Note: For coverage area dimensions less than or between those listed above, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.

Bulletin 058 Page 4 of 10


November 2021 www.reliablesprinkler.com
Model LT56L-300 Specific Application Sprinkler SIN R5914
Technical Specifications Sprinkler Finishes
Style: Pendent, Recessed Pendent, or (See Table H)
Conical Concealed
Threads: 1/2” NPT or ISO 7-1 R1/2 Sensitivity
Nominal K-Factor: 5.6 (80 metric) Quick-response
Max. Working Pressure: 300 psi (21 bar)
Min. Spacing: 14 ft. (4.3 m) Temperature Ratings
165°F (74°C)
Material Specifications 212°F (100°C)
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Frame: Brass Alloy Recessed Escutcheons/Cover Plates
Button: Copper Alloy Model FV recessed escutcheon
Sealing Assembly: Nickel Alloy with PTFE Model FP recessed escutcheon
Load Screw: Bronze Alloy Model CCP cover plate
Deflector: Bronze Alloy
Sprinkler Wrenches
Model W2 (pendent)
Model W4 (recessed and concealed)

Listings and Approvals


UL Listed

Model LT56L-300 Sprinkler Components and Dimensions Figure 4

Model LT56L-300 Sprinkler Hydraulic Design Criteria Table E


Minimum Flow and Residual Pressure
Max. Coverage Area Flow Pressure
ft. x ft. gpm psi
(m x m) (l/min) (bar)
28 x 8 23 16.9
(8.5 x 2.4) (87) (1.17)
28 x 10 28 25.0
(8.5 x 3.0) (106) (1.72)
Note: For coverage area dimensions less than or between those listed above, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.

Bulletin 058 Page 5 of 10


November 2021 www.reliablesprinkler.com
Model LT56C Specific Application Sprinkler SIN RA5994
Technical Specifications Sprinkler Finishes
Style: Flat Cover Plate Concealed Pendent (See Table H)
Threads: 1/2” NPT or ISO 7-1 R1/2
Nominal K-Factor: 5.6 (80 metric) Sensitivity
Max. Working Pressure: 175 psi (12 bar) Quick-response
Min. Spacing: 14 ft. (4.3 m)
Temperature Ratings
Material Specifications 165°F (74°C)
Thermal Sensor: Nickel Alloy Solder Link 212°F (100°C)
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy Cover Plate
Yoke: Brass Alloy Model G4/G5
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy Sprinkler Wrench
Towers: Copper Alloy Model FC (without wrench-able cap)
Pins: Stainless Steel Model W3 (with wrench-able cap)
Deflector: Bronze Alloy
Cup: Steel Listings and Approvals
UL Listed

Model LT56C Sprinkler Components and Dimensions Figure 5

Model LT56C Sprinkler Hydraulic Design Criteria Table F


Minimum Flow and Residual Pressure
Max. Coverage Area Flow Pressure
ft. x ft. gpm psi
(m x m) (l/min) (bar)
28 x 8 24 18.4
(8.5 x 2.4) (91) (1.27)
28 x 10 28 25.0
(8.5 x 3.0) (106) (1.72)
Note: For coverage area dimensions less than or between those listed above, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.

Bulletin 058 Page 6 of 10


November 2021 www.reliablesprinkler.com
Recessed Escutcheon and Conical Concealed Cover Plate Dimensions Table G

Maximum Face of Minimum Face of Maximum Minimum


Cover Plate
Adjustment Fitting to Fitting to Deflector Deflector
Temperature
Type Inch Ceiling(1) Ceiling(1) Distance Below Distance Below
°F
(mm) Inch Inch Ceiling Inch Ceiling Inch
(°C)
(mm) (mm) (mm) (mm)

1/2 7/8 3/8 1-3/4 1-1/4


FV N/A
(12) (22) (10) (44) (32)
1/2 1-1/2 1 1 1/2
FP N/A
(12) (38) (25) (25) (12)
CCP 1/2 1-1/2 1 1 1/2 135°F(2)
135 (12) (38) (25) (25) (12) (57°C)
CCP 1/2 1-1/2 1 1 1/2 165°F(3)
165 (12) (38) (25) (25) (12) (74°C)
G4/G5 3/4 2-1/4 1-1/2 1 1/4 135°F(2)
135 (19) (57) (38) (25) (6) (57°C)
G4/G5 3/4 2-1/4 1-1/2 1 1/4 165°F(3)
165 (19) (57) (38) (25) (6) (74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on nominal thread make up. Verify dimensions based on fitting and thread sealing method
prior to installation.
2. For use with 155°F (68°C) and 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed
100°F (38°C).
3. For use with 200°F (93°C) and 212°F (100°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed
150°F (66°C).

Recessed Escutcheon and Concealed Cover Plate Diagrams Figure 6

Bulletin 058 Page 7 of 10


November 2021 www.reliablesprinkler.com
Application Model LT56C series sprinklers can be installed without removing
the wrench-able protective cap using the Model W3 wrench.
Model LT56 series sprinklers are UL Listed Specific Application Alternatively, Model LT56C series sprinklers can be installed
sprinklers for use in Light Hazard corridors and hallways in using the Model FC wrench by temporarily removing the
accordance with NFPA 13. The sprinklers are classified as protective cap during installation of the sprinkler. The use of any
Special Sprinklers based on the maximum and minimum other wrench to installed Model LT56C series sprinklers is not
allowable spacing, but shall otherwise be designed in accordance permitted and may damage the sprinkler. Fully insert the Model
with the requirements of NFPA 13 for Extended Coverage W3 wrench over the cap until it reaches the bottom of the cup,
Pendent Spray sprinklers. Model LT56 series sprinklers are quick- or the Model FC wrench over the sprinkler until the wrench
response sprinklers for use in Light Hazard occupancies only. engages the body. Do not wrench any other part of the sprinkler/
cup assembly. The Model W3 and FC wrenches are designed to
The sprinklers must be hydraulically designed using the minimum be turned with a standard 1/2” square drive. Tighten the sprinkler
flow and pressure specified in the Hydraulic Design Criteria tables into the fitting after applying a PTFE based thread sealant to the
in this Bulletin. Figure 7 outlines the maximum coverage area of sprinkler’s threads. Recommended installation torque is 8 to 18
Model LT56 series sprinklers. Figure 8 identifies the sprinklers ft-lbs (11 to 24 N-m) for 1/2” thread sprinklers and 14 to 20 ft-lbs
that can be located adjacent to Model LT56 series sprinklers; (19 to 27 N-m) for 3/4” thread sprinklers.
note that LT56 series sprinkler are not permitted to be installed
with the short coverage length oriented towards the short Model LT56 series sprinklers must be installed with the frame
coverage length of an adjacent LT56 series sprinkler. An example arms or towers perpendicular to the length of the corridor or
hallway. The deflector is marked with “<-28 FT->” to indicate the
layout of Model LT56 series sprinklers is illustrated in Figure 9.
direction of the 28 ft. (8.5 m) coverage length. Model LT56 series
sprinklers need not be installed with the frame arms or towers
Listings and Approvals parallel to the sprinkler pipe.

Listed by Underwriters Laboratories, Inc. Caution: The protective cap provided with the Model LT56C
concealed sprinkler must be removed temporarily to verify
UL Listing Category alignment at the time of sprinkler rough-in. Replace protective
cap following alignment and leave in place until cover plate is
Sprinklers, Automatic and Open installed.

UL Guide Number Recommended installation torque is 8-18 ft-lbs (11 – 24 N-m). Do


not tighten sprinklers over the maximum recommended torque.
VNIV Exceeding the maximum recommended torque may cause
leakage or impairment of the sprinklers.
Installation
Do not install any glass bulb sprinklers where the bulb is cracked
Model LT56 series sprinklers must be installed in accordance with or there is a loss of liquid from the bulb.
the requirements of the NFPA 13 for pendent sprinklers and may
also be installed as a recessed sprinkler or concealed sprinkler as Glass bulb sprinklers have orange bulb protectors to minimize
shown in Figure 6. The Model FV and FP recessed escutcheons, bulb damage during shipping, handling and installation. Remove
and Model CCP cover plate, are the only recessed escutcheons the bulb protector at the time the sprinkler system is placed in
and concealed cover plate to be used with Model LT56, LT56L, service for fire protection. Removal of the bulb protectors before
LT56-300 and LT56L-300 sprinklers. The Model G4/G5 cover this time may leave the bulb vulnerable to damage. The required
plate is the only concealed cover plate permitted for use with the sprinkler wrenches are designed to install sprinklers with bulb
Model LT56C sprinkler. Use of any other recessed escutcheon protectors in place. Remove bulb protectors by undoing the clasp
or cover plate will void all approvals and warranties. Do not install by hand. Do not use tools to remove the bulb protectors.
Model FV and FP escutcheons or Model CCP and G4/G5 cover
plates in ceilings that are positively pressurized with respect to
the occupied space below.

When installing Model LT56, LT56L, LT56-300, and LT56L-300


sprinklers use only the Model W2 wrench for pendent installations
and the Model W4 wrench for recessed pendent and concealed
installation. The Model LT56C sprinkler must be installed with
the W3 or FC wrench only. Use of wrenches other than those
specified may damage these sprinklers.

Bulletin 058 Page 8 of 10


November 2021 www.reliablesprinkler.com
Coverage Area Figure 7

Adjacent Sprinklers Figure 8

Example Sprinkler Layout Figure 9

Bulletin 058 Page 9 of 10


November 2021 www.reliablesprinkler.com
Wrench

Model FC
For use with Model LT56C Series sprinklers Model W3
without wrench-able cap installed For use with Model LT56C Series
sprinklers with wrench-able cap installed

Sprinkler, Escutcheon, & Cover Plate Finishes(2) Table H


Standard Finishes Special Application Finishes
FV, FP(4) CCP, G4/G5 CCP, G4/G5
Sprinkler(1) Sprinkler FV, FP(3) Escutcheons
Escutcheons Cover Plate Cover Plate
Bronze Brass Bright Brass Bright Brass Bright Brass
Chrome Plated Chrome Plated Chrome Plated Satin Chrome Satin Chrome Satin Chrome
White Polyester (3)
White Polyester White Paint Black Polyester (3)
Black Polyester Black Paint
Custom Color Polyester Custom Color Polyester Custom Color Paint
Notes:
1. Model LT56, LT56L, LT56-300, and LT56L-300 only.
2. Paint or any other coating applied over the factory finish will void all approvals and warranties.
3. UL Listed Corrosion Resistant, Models LT56 (RA5814) and LT56-300 (RA5914) only.
4. The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring.

Maintenance Guarantee
Reliable Model LT56 series sprinklers should be inspected and For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
the sprinkler system maintained in accordance with NFPA 25, as and conditions, visit www.reliablesprinkler.com.
well as the requirements of any Authorities Having Jurisdiction.
Patents
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential Patent Pending
for damage to sprinklers that could cause improper operation or
non-operation.
Ordering Information
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming Specify the following when ordering:
without touching the sprinkler. Sprinkler
• Model (LT56, LT56L, LT56-300, LT56L-300, LT56C)
Replace any sprinkler which has been painted (other than • Temperature Rating
factory applied). Properly installed Model CCP and Model G4/ • Threads (1/2” NPT or ISO 7-1 R1/2)
G5 cover plates will have an air gap that is required for proper • Finish (See Table H)
operation, do not seal the gap or paint the cover plates. Model Escutcheon or Cover Plate
FV and FP escutcheons as well as Model CCP and Model G4/ • Type (None, FV, FP, CCP, G4/G5)
G5 cover plates have holes in the ring or cup that must remain • Finish (See Table H)
unobstructed. Sprinkler Wrench
• Pendent: Model W2 Wrench
Replace any sprinkler which has been damaged, cracked the • Recessed Pendent & Conical Concealed: Model
glass bulb, or has lost liquid from the glass bulb. A stock of spare W4 Wrench
sprinklers should be maintained to allow quick replacement of • Flat Concealed Pendent:
damaged or operated sprinklers. Failure to properly maintain - Model W3 Wrench (with wrench-able cap)
P/N 9999970493

sprinklers may result in inadvertent operation or non-operation - Model FC Wrench (without wrench-able cap)
during a fire event.

Bulletin 058 Page 10 of 10


November 2021 www.reliablesprinkler.com

You might also like