2016 108 Cu. In. Nitrogen Pilot Cylinder and Bracket

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Kidde Fire Suppression System

Component Description

108 cu. inch Nitrogen Pilot Cylinder and Bracket Effective: August 2016
K-85-5051

FEATURES
• Safety: Safety Burst Disc Assembly • Pressure Gauge
• Actuation Port Safety Cap • Quick Disconnect Bracket
• RoHS Compliant • See Compatibility Table for Corresponding Manual P/N

DESCRIPTION
The Kidde Fire Suppression Systems 108 cu. in. capacity
Nitrogen Pilot Cylinder is factory charged to 1800 PSIG
(124 bar) with dry nitrogen and is designed for use as a
pilot cylinder. The cylinder valve is a 5/8-inch bore design
and is fitted with a contents pressure gauge. The valve is
designed to accept the full range of Kidde Systems con-
trol heads (excluding the stackable electric control head,
P/N 81-486500-010).
OPERATION
Either electrical, pneumatic, pressure or mechanical
inputs may operate the 108 cu in cylinder. The suite of
Kidde Systems control heads can provide these inputs,
again excluding control head part number
81-486500-010.
INSTALLATION

Nitrogen cylinders must not be moved


unless the discharge and control
heads have been removed and the pro-
tection caps are installed. Failure to do
so could result in inadvertent dis-
WARNING
charge which could cause serious
bodily injury, death or property dam- MAINTENANCE
age. The pressure of the nitrogen cylinder should be checked
daily, and the cylinder should be visually inspected during
The 108 cuin cylinder is fitted to a wall bracket attached periodic maintenance. The cylinder should be hydro-
to an appropriate mounting location. Rotate the cylinder tested (or be subject to a full external visual inspection)
to the correct orientation before completely tightening the every five years in accordance with DOT CFR 49 and
bracket. Upon securing the cylinder, attach the appropri- CGA (Compressed Gas Association) Pamphlet C-6.
ate control head style. Ensure the cylinder pressure
gauge remains sufficiently visible to facilitate periodic
inspection requirements.
Remove the supplied pipe plug and attach a suitable
1/8-in. NPT fitting to the cylinder outlet port. Kidde Fire
Systems provides 1/8-in. x 5/16-in. flare connections (see
accessories table). Either tubing or 1/4-in. flexible actua-
tion hoses may be attached to these connections. Refer
to the applicable Kidde design manual for allowable tub-
ing material, diameters and lengths. Fittings should be
rated for a maximum working pressure of no less than
3000 PSI (207 bar). Refer to the Electrical Contact table
for additional information.

1
DIMENSIONS
GAUGE PLUG OUTLET PORT - 1/8 in. (FEMALE)
ATTACH ADAPTER HERE

5/16 in. TUBING (MALE)

1/8 in. NPT (MALE) ADAPTER


P/N: WK-699205-010
1-1/4 in. -18 NF-3
FOR CONTROL HEAD CONNECTION
SAFETY OUTLET
CYLINDER

BRACKET P/N WK-877845-000

16 in.
(406 mm)

3.56 in.
(90 mm)
Figure 1. 108 cu. in. Nitrogen Pilot Cylinder

3-13/16 in.
(96.8 mm)
3-13/16 in. 1 in.
(96.8 mm) (25.4 mm)

9/16 in.
(14.2 mm)

8-3/4 in.
(22.3 mm)
2 Mounting holes
(Use 5/16 in. flat-head
hardware)
12-1/16 in.
(307.8 mm)

4-3/4 in.
(111.3 mm)

2-13/16 in.
(71.3 mm)

2 in.
(50.8)

Figure 2. 108 cu. in. Nitrogen Pilot Cylinder Bracket

2 K-85-5051

Effective: August 2016


SPECIFICATIONS
Charge Pressure: 1800 PSIG @ 70°F
(124 bar @ 21°C)
Contents: Nitrogen (BB-n-411 Grade A, Type I)
Safety Relief: Bust Disc 2650-3000 PSI (183-207 BAR) at 70F (20C)
Cylinder Volume: 108 cu. in. (1.77 L)
Empty Weight: 5.57 lb. (2.53 kg)
Charged Weight: 6.80 lb. (3.10 kg)
Bracket Weight: 1.50 lb. (0.68 kg)
Cylinder Type: Seamless, DOT3AA-1800
Cylinder Finish: Black, Painted
Materials:
Valve– Forged Brass
Siphon Tube– None Fitted
Cylinder– Chrome, Moly Steel
Bracket– Steel, Stainless Steel
Operating Temperature
Range: -40°F to 130°F
(-40°C to 54°C)
Height (including
protection cap): 16 in. (406 mm)
Transport Information: Class 2.2, I.D.#UN1066

ORDERING INFORMATION

Factory
Part Number Comments
Charged

WK-877940-000 Yes Standard Pressure Gauge Only

WK-877940-001 No Standard Pressure Gauge Only

WK-877940-200 Yes Fitted with En-Gauge

06-129773-001 Yes Fitted with NC Pressure Switch

06-129773-002 Yes Fitted with NO Pressure Switch

06-129773-003 No Fitted with NC Pressure Switch

06-129773-004 No Fitted with NO Pressure Switch

K-85-5051 3
Effective: August 2016
ACCESSORIES

Part Number Description Comments

WK-877845-000 Mounting Bracket, Nitrogen Pilot Cylinder Steel Material

WK-699205-010 Male Connector, 5/6-in. Flare x 1/8-in. NPT See Data Sheet K-90-5040

WK-699205-030 Male Elbow, 5/16-in. Flare x 1/8-in. NPT See Data Sheet K-90-5040

WK-699205-050 Male Branch Tee, 5/16-in. Flare x 1/8-in. NPT See Data Sheet K-90-5040

WK-264987-000 Actuation Hose, 22-in. See Data Sheet K-90-5070

WK-264986-000 Actuation Hose, 30-in. See Data Sheet K-90-5070

WK-264985-000 Check Valve, 1/4-in. See Data Sheet K-90-5090

WK-933537-000 Adapter, Recharging See Data Sheet K-90-9110

ELECTRICAL CONTACT INFORMATION

Cylinder Contact Status


Set Point Dead Band
Assembly Part Comments
PSIG PSIG
Number Ambient 1800 PSI

WK-877940-200 - - - - See Data Sheet K-90-116


06-129773-001 Closed Open 1350 +/- 50 200 Max 48 Inch x 18 AWG Stranded Leads
06-129773-002 Open Closed 1350 +/- 50 200 Max 48 Inch x 18 AWG Stranded Leads
06-129773-003 Closed Open 1350 +/- 50 200 Max 48 Inch x 18 AWG Stranded Leads
06-129773-004 Open Closed 1350 +/- 50 200 Max 48 Inch x 18 AWG Stranded Leads

COMPATIBILITY

For Use
Series Land DIOM Manual P/N Marine DIOM Manual P/N
With

Kidde ECS with HFC-227ea Agent X 06-236115-001 06-236225-001

Kidde Advanced Delivery with FM-200® Agent X 06-235068-001 06-236595-001

Kidde ECS with 3M™ Novec™ X 06-236553-001 06-236559-001


1230 Fire Protection Fluid

Kidde Advanced Delivery with 3M™ Novec™ X 06-237256-001 06-237257-001


1230 Fire Protection Fluid

Jurisdiction: EAR
Classification: EAR99
This document contains technical data subject to the
All trademarks are the property of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact Kidde-Fenwal Inc.

Kidde Fire Systems


400 Main Street
Ashland, MA 01721
K-85-5051 Rev AA Ph: 508.881.2000
Fax: 508.881.8920
©2016 Kidde-Fenwal, Inc. www.kiddefiresystems.com