Data Sheets: For Hfc/Hfo/Hcfc Refrigerants Standard and Ecoinside Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

B1.5-10.

1Y
Data sheets
For HFC/HFO/HCFC refrigerants > Standard and ECOinside series

Technical data:
Cylinders # 2
Displacement @ 50 Hz m3/h [50Hz] 9.88
Displacement @ 60 Hz m3/h [60Hz] 11.86
Motor version[1] 2
Nominal Motor power (HP) 1.5
Nominal Motor power (kW) 1.1
Motor voltage at 50 Hz[2] V/ph/Hz 220-240V - 380-420V/3/50Hz DOL
Motor voltage at 60 Hz[2] V/ph/Hz 265-290V - 440-480V/3/60Hz DOL
MRA, maximum operating current at 230V/50Hz and A 9.5
MRA, maximum operating current at 400V/50Hz and A 5.5
LRA, maximum starting current at 230V/50Hz and A 46.6
LRA, max starting current at 400V/50Hz and 460V/60Hz, A 26.8
Frequency min Hz 30
Frequency max[3] Hz 87
Control and protection device INT69®
Electric terminal box class protection IP56
Maximum pressure HP bar 30
Maximum pressure LP bar 20.5
Oil type[4] POE32
Oil charge (3/4 of sight glass) l 1
Lubrication type Centrifugal
Suction valve (SV) inch ⅝
Discharge valve (DV) inch ½
Net weight kg 38
Max Length mm 329
Max Width mm 237
Max Height mm 292
Rubber mounts diameter[2] mm 30
Rubber mounts height mm 30
Rubber mounts shore sh 45
Sound power level (-10/45, R404A)[5] dB(A) 65.5
Sound pressure level @ 1m (-10/45, R404A)[5] dB(A) 57.5
Compressor body material Cast Iron
Motor protection PTC
Oil level sight glass # 1

Motor version: 1 = high and mid temperature, all refrigerants; 2 = low and mid temperature, all refrigerants; 3 = ECOinside, low
[1]
temperature, R134a and R1234ze only
[2] Others available on request
[3] Maximum frequency depends on the working condition: see FSS3 (Frascold selection software)
[4] Different kind of oil available on request

FRASCOLD SPA via Barbara Melzi 103/105, IT 20027 Rescaldina MI - ++39-0331-742201 email [email protected] web www.frascold.it
B1.5-10.1Y
Data sheets
For HFC/HFO/HCFC refrigerants > Standard and ECOinside series

Accessories:
Water cooled head T00SK50030
Electronic control module - INT 69 Diagnose (230/110V) T00EC01D-RIC
Oil heater (230V-50W) T00CH13-RIC
Head cooling fan - 230V/1/50-60Hz SZ-FM1
Electronic oil level regulator T00EC1900
Kit adapters for oil equalization line - 1" ROT 5/8" ODS T00SK170200
Kit adapters for oil equalization line - 1"1/4 ROT 1"1/8 ODS T00SK170300
DP Modbus Gateway T00EC59
Connection cable Modbus Gateway - INT69 T00EC64

FRASCOLD SPA via Barbara Melzi 103/105, IT 20027 Rescaldina MI - ++39-0331-742201 email [email protected] web www.frascold.it
B1.5-10.1Y
Data sheets
For HFC/HFO/HCFC refrigerants > Standard and ECOinside series

Dimensional drawing: 2 Low pressure plug 1/8" NPT


SV Suction valve mm 15.8 3 Oil charge plug 1/4" GAS
DV Discharge valve mm 12.7 4 Oil level sight glass -
SV Suction valve inch ⅝ 5 Crankcase heater -
DV Discharge valve inch ½ 6 Oil drain plug M8 x 22
A Length mm 329 12 Oil return plug 1/8" NPT
B Width mm 237 NP Name Plate -
C Height mm 292 DV Discharge valve -
D Base mounting mm 234 SV Suction valve -
E Base mounting mm 194
F Suction valve mm 150
G Suction valve mm 209
H Suction valve mm 29
L Discharge valve mm 97
M Discharge valve mm 167
N Discharge valve mm 18
1 High pressure plug 1/8" NPT

FRASCOLD SPA via Barbara Melzi 103/105, IT 20027 Rescaldina MI - ++39-0331-742201 email [email protected] web www.frascold.it
Powered by TCPDF (www.tcpdf.org)

You might also like