CPWD Elctrical

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

ELECTRICAL FORMULAE

OHMSLAW

1 2 3

2 2
POWER P=VxI V/R I XR
FORMULAS

4 5 6

2 2
RESISTANCE R = V /I V/P, P/I
FORMULAS

7 8 9

CURRENT I=V/R, P/V P/R


FORMULAS

10 11 12

VOLATGE V=IxR, P/I, PxR


FORMULAS

1 R.SRIDHAR CPWD,MADURAI
HP FORMULA FOR MOTOR PUMP

13 HP FOR PUMP MOTOR = GPM x HEAD(FT) x SPECFIC GRAVITY


3960 x %EFFICIENCY OF PUMP MOTOR

HP FORMULA FOR FAN MOTOR

14 P = (Q x Pw ) / 6356 x U )

15 P = (Q x p) / 229 x U )

16 P = (Q x PF ) / 33000 x U )

where

P = Power, hp

Q = Flow rate, cfm


2
p = Pressure, lb/inch
2
Pf = Pressure, lb/ft
Pw = Water Gauge, Inches
U = efficiency coefficient

17 FIND AMPHERE HOUR OF INVERTER AND BATTERY


( TIME X WATTS ) / ( VOLTAGE X POWER FACTOR ) = AH

BACK UP TIME OF BATTERY

18 ( AH X VOLTS X P.F ) / WATTS = BACK UP HOURS

2 R.SRIDHAR CPWD,MADURAI
FORMULAS FOR FINDING HP, KVA,KW

DIRECT CURRENT AC SINGLE PHASE

19 20

WHEN HP KNOWN HP x 746 HP x 746


CURRENT REQUIRED? V x %EFF V x P.F x %EFF

AC TWO PHASE AC THREE PHASE

21 22 HP x 746
HP x 746
V x P.F x 2 x %EFF V x p.f x 3 x %EFF

DIRECT CURRENT AC SINGLE PHASE

23 24

WHEN KW KNOWN KW X 1000 KW X 1000


CURRENT REQUIRED? V x %EFF V x P.F x %EFF

AC TWO PHASE AC THREE PHASE

25 26
KW X 1000 KW X 1000
V x P.F x 2 x %EFF V x P.F x 3 x %EFF

3 R.SRIDHAR CPWD,MADURAI
WHEN KVA KNOWN
CURRENT REQUIRED

AC SINGLE PHASE AC TWO PHASE

27 KVA X 1000 28 KVA X 1000


V x %EFF V x 2 x %EFF

AC THREE PHASE

29 KVA X 1000
V x 3 x %EFF

HP OUTPUT FORMULAE

DIRECT CURRENT AC SINGLE PHASE

30 31
V x %EFF x I V x P.F x %EFF x I
746 746

AC TWO PHASE AC THREE PHASE

32 33

V x P.F x 2 x %EFF x I V x P.F x 3 x %EFF x I


746 746

4 R.SRIDHAR CPWD,MADURAI
KW FORMULAS

DIRECT CURRENT AC SINGLE PHASE

34 35

VxI V x P.F x I
1000 1000

AC THREE PHASE
AC TWO PHASE

36 37

V x P.F x 2 x I V x P.F x 3 x I
1000 1000

KVA FORMULAS

AC SINGLE PHASE AC TWO PHASE

38 39
VxI Vx2xI
1000
1000

AC THREE PHASE

40
Vx3xI
1000

5 R.SRIDHAR CPWD,MADURAI
41 KILOWATT HOUR(AC) V x P.F x 3 x I x HOURS
1000

42 KILOWATT HOUR(DC) V x 3 x I x HOURS


1000

1
43 CAPACITANCE =
2 FC

POWERFACTOR = KILOWATT
44
KILOVOLT AMPERE

45 INDUCTANCE = 2 XL

46 SLIP TORQE = NS - NR X 100%


NS

47 SPEED NS = 120 X FREQUENCY


POLES

2 2
48 IMPEDENCE Z = R +XL

49 POWER = V x I x P.F x 3

6 R.SRIDHAR CPWD,MADURAI
ILLUMINATION CALCULATION AND CONVERSION FORMULAS

50 LUMENS TO LUX = 10.76391 x LUMENS / AREA IN FT 2

2
51 LUX TO LUMENS = 0.09290304 x LUX x AREA IN FT

52 LUMENS TO WATTS = LUMENS/LUMENS/WATTS

53 WATTS TO LUMENS = WATTS x LUMENS/WATTS

2
54 WATTS TO LUX = 10.76391 x WATTS x AREA IN FT / (LUMENS/WATTS)

55 LUX TO WATTS = 0.09290304 x LUX x (LUMENS/WATTS) / AREA IN FT2

56 CANDELA TO LUX = 10.76391 x CANDELA / DISTANCE IN FT 2

57 LUX TO CANDELA = 0.09290303 x LUX x DISTANCE IN FT 2

58 LUMENS TO CANDELA = (LUMENS/2 (1-COS(0/2)))

59 CANDELA TO LUMENS = ( CANDELA x 2 (1-COS(0/2)))

60 FOOTCANDELA TO LUX = Fc ev x 10.76391

61 LUX TO FOOTCANDELA = Fc ev / 0.09290304

7 R.SRIDHAR CPWD,MADURAI
TRANSFORMER FORMULAS

62 TRANSFORMER EFFICIENCY = OUTPUTPOWER X 100%


INPUTPOWER

63 TRANSFORMER VOLTAGE TRANSMISSION RATIO = SECONDRY N d0


PRIMARY dt

64 TRANSFORMER CURRENT TRANSMISSION RATIO = PRIMARY


SECOUNDRY

2
65 TRANSFORMER VOLTAGE TRANSMISSION RATIO = SECOUNDRY
PRIMARY

2
66 TRANSFORMER INDUCTANCE TRANSMISSION RATIO = SECOUNDRY
PRIMARY

67 STEPUP TRANSFORMER = ES > EP, IS < IP

68 STEPDWON TRANFORMER = EP > ES , IS > IP

69 % Voltage Drop (VD) = ( 2 x L x A x R) / 1000

L = LENGTH OF THE CABLE


A = CROSS SECTIONAL AREA OF CABLE

R= RESISTANCE OF THE CABLE

2 2
70 KVAR = KVA - KW

8 R.SRIDHAR CPWD,MADURAI
71 HP TO KW = (HP X 746) / 1000

72 KW TO HP = KW/0.746

73 KVA TO HP = (KVA x PF x % EFF)/0. 746

74 HP TO KVA = (HP x 0.746)/(P.F x %EFF)

75 KW TO KVA = KW/PF

76 KVA TO KW = KVA x PF

77 HP TO AMPS = (HP x 746) / VOLTS

78 AMPS TO HP = (I x V x %EFF ) / 746

79 AMPS TO VOLT (I) = V/R

80 VOLT TO AMPS (V) = I x R

9 R.SRIDHAR CPWD,MADURAI
81 OHMS TO AMPS (R) = V / I

82 WATTS TO AMPS (P) = V x I

83 KW TO AMPS = KW x1000/VOLT

84 AMPS TO KW = I x V / 1000

85 KVA TO AMPS = KVA x 1000 / VOLT

86 AMPS TO KVA = I x V /1000

87 VA TO KW = VA x PF / 1000

88 KW TO VA = KW x 1000 / PF

89 KW TO KWH = KW x T (HR)

90 KWH TO KW = KWH / T (HR)

91 VA TO KVA = VA / 1000

92 KVA TO VA = KVA x 1000

93 VA TO AMPS = VA / V

94 AMPS TO VA = I x V

95 KVA TO VA = KVA x 1000

96 VA TO KVA = VA / 1000

97 AH TO WH = AH x V

98 WH TO AH = WH / V

10 R.SRIDHAR CPWD,MADURAI
99 WATTS TO VA = WATT / PF

100 VA TO WATTS = VA x PF

101 (DC) KW TO VOLT = KW x 1000 / I (AMPS)

102 (AC10) KW TO VOLT = KW x 1000/ (PF x I)

103 (AC20) KW TO VOLT = KW x 1000/ (PF x I x 2)

104 (AC30) KW TO VOLT = KW x 1000/ ( 3 x PF x I )

105 (DC) VOLT TO KW = I x V / 1000

106 (AC 10) VOLT TO KW = I x V x PF / 1000

107 (AC 20) VOLT TO KW = I x V x 2 x PF / 1000

108 (AC30) VOLT TO KW = 3 xI x PF x V / 1000


L-L(V)

109 KVA TO WATTS = (KVA x 1000 x PF)

110 WATTS TO KVA = WATT /(1000 x PF)

11 R.SRIDHAR CPWD,MADURAI
111 MAH TO WH = MAH x VOLT / 1000

112 WH TO MAH = WH x 1000 / VOLT

113 WATTS TO KWH = (WATT x TIME (HR)) /1000

114 KWH TO WATTS = (KWH x 1000) / TIME (HR)

115 AH TO MAH = AH x 1000

116 MAH TO AH = MAH /1000

117 AMPS TO MILLIAMP = AMPS x 1000

118 MILLIAMPS TO AMPS = MILLIAMPS / 1000

119 JOULE TO VOLT = EJ/QC

120 VOLT TO JOULE = VOLT x COLUMB

121 JOULE TO WATT = JOULE/TIME(SEC)

122 WATT TO JOULE = WATT x TIME (SEC)

123 JOULE TO KILOJOULE = JOULE /1000

124 KILOJOULE TO JOULE = KILOJOULE x 1000

12 R.SRIDHAR CPWD,MADURAI
125 RT(TON) TO KW = RT x 3.5168

126 KW TO RT = RT/3.5168

127 JOULE TO CALORIE = JOULE / 4.184 CALORIE

128 CALORIE TO JOULE = JOULE X 4.184 CALORIE

129 CALORIE TO KILOCALORIE = CALORIE X 0.0001 (KCAL)

130 KILOCALORIE TO CALORIE =1000 x KILOCALORIE

1 BTU/HR = 0.00029307 WATTS


131

132 1 HP = 746 WATTS

133 1 KW = 1000 WATTS

134 1 VA = 0.0001 KW

13 R.SRIDHAR CPWD,MADURAI
135 1 AH = 3600 COLUMB

136 1 LUX = 1 SQUARE METER/LUMEN

137 1 KWH = 860 KCAL

-4
138 1 COLUMB = 2.7778 .10

139 1 UNIT OF ILLUMINATION =

0.09290304 FOOTCANDELA

4
140 1KWH = 36 x 10 JOULES

141 1 BTU TO JOULES = 1055.0558 JOULES

142 JOULES TO ELECTROVOLT = 6.24150 ELECTROVOLT

143 VOLT TO ELECTRO VOLT = ELECTROVOLT


ELEMENTRY CHARGES

144 ELECTRO VOLT TO VOLT

= VOLT x ELEMENTRY CHARGES

14 R.SRIDHAR CPWD,MADURAI
10
145 DECIBAL TO MILLIWATTS = 10 x LOG (m/w/Imw)

146 1 TON = 85 SQFEET

147 1 TON = 1200 BTU

148 1 FARAD = 1 COLUMB / 1 VOLT

149 WATTS TO KW = WATTS x 1000

150 KW TO WATTS= WATTS /1000

151 LUMINIOUS FLUX = 1 LUMEN FALLING PERPENDICULAR 1 SQ METER

9
152 GEGAVOLT TO ELECTROVOLT = GEV- 10 EV

153 WATT = JOULE / SECOUND

154 CAPACITANCE = COLUMB/VOLT

155 RESISTANCE R = L
A

15 R.SRIDHAR CPWD,MADURAI
156 1 AMPS = 1COLUMB / 1 SECOUND

157 1 HENDRY = 1WBER /1 AMPS

158 1 HERTZ = 1 CYCLE / SECOUND

2
159 1 JOULE = 1 KG x M / SEC

160 1 KWH =1000 WH

161 1 AH = 1 AMPS x HOUR

162 1 SIEMENS = 1/1 OHM

2
163 1 TESELA = 1 WB / 1 METER

164 CAPACITANCE (C) = Q/V

165 INDUCTANCE (VL) = - L (Di/Dt)

16 R.SRIDHAR CPWD,MADURAI
166 CHARGE (Q) = COLUMB x VOLT

167 FREQUENCY (F) = 1 / TIME

168 PERIOD (S) TIME =1 / FREQENCE

169 CONDUCTANCE (G) = 1 / RESISTENCE

170 1 AH = 1 AMPS x 1HOUR

171 1 SIEMENS = 1 / 1 OHM

172 1 TESELA = 1WB /1 MHO

TRANSFORMER VOLTAGE CURRENT CALCULATION

173 V = (K x 1000) / (Ph x I)

174 I = (K x 1000) / (Ph x V)

175 I = (K X I x V ) / 1000

K = KVA , I = CURRENT , V = VOLTAGE , PH = 3

17 R.SRIDHAR CPWD,MADURAI
STAR TO DELTA

176 Ra = R1R2 + R1R3 + R2R3 B Y

R1

177 Rb = R1R2 + R1R3 + R2R3


B
R
R2

178 Rc = R1R2 + R1R3 + R2R3


R3

DELTA TO STAR

B
R
179 R1 = RB RC
RA+RB+RC
Y

180 R2 = RA RC
RA+RB+RC
R

181 R3 = RA RB
B Y
RA+RB+RC

STAR CONNECTION

182 LINE CURRENT =PHASE CURRENT

183 LINE VOLATAGE = 3 PHASE VOLTAGE

18 R.SRIDHAR CPWD,MADURAI
DELTA CONNECTION

184 LINE CURRENT = 3 PHASE CURRENT

185 LINE VOLTAGE = PHASE VOLTAGE

186 PHASE CURRENT = PHASE POWER/PHASE VOLTAGE

187 LINE CURRENT = LINE POWER/LINE VOLT x 3

IMPEDANCE FORMULA

2 2
188 ZRX = R + XL

2 2
189 ZRC = R + XC

190 ZXL = (XL -XC) 2

IMPEDANCE SERIOUS CIRCUITS

2
191 ZRLC = R2+ (XL - XC)

IMPEDANCE PARALLEL CIRCUITS

RX
192 2
R2+ XL

19 R.SRIDHAR CPWD,MADURAI
REACTANCE FORMULA

193 C = 1/2 FC 194 L = XL / 2 FL

195 XC = 1/2 FC 196 XL = 2 FL

REACTANCE FREQUENCY FORMULA

197 F = 1/2 LC FHz = 159.2 / L C

2 2
198 L = 1/4 FL L mirohendry =25.330/F c

2 2
199 C = 1/4 FC C mirofarads =25.330/F c

RELATION BETWEEN HP, TORQUE AND SPEED

200 HP = T x N
5250 T = TORQUE

201 T =HP x 5250 NS = SPEED


NS

202 NS = HP X 5250
T

20 R.SRIDHAR CPWD,MADURAI
RELATION BETWEEN SPEED, FREQUENCY AND NO POLES

203 NS = 120 x F NS = SYN SPEED


P

204 F = PxN F = FREQUENCY


120

205 P = 120 x F P = POLES


NS

CAPACITOR, INDUCTOR, RESISTOR FORMULAS

206 CAPACITOR I SERIOUS = 1/CEQ = 1/C1 + 1/C2 +.......+ 1/NC

207 CAPACITOR PARALLEL = CEQ = C1 + C2 +.........+ CN

208 RESISTOR IN SERIOUS = REQ= R1 + R2 +......+ RN

209 RESISTOR IN PARALEL EQUAL = 1/REQ = R/N

210 RESISTOR IN PARALEL UN EQUAL = 1/REQ = 1/R1 +1/R 2 +......+ 1/RN

211 INDUCTOR IN SERIOUS = LEQ = L1 + L2 +..........+LN

212 INDUCTOR IN PARALLEL = 1/LEQ = 1/L1 + 1/L2+.....1/L3

21 R.SRIDHAR CPWD,MADURAI
POWER FACTOR SINGLE PHASE & THREE PHASE FORMULA

213 SINGLE PHASE PF = KW x 1000 / (I x V)

214 THREE PHASE PF = KW x 1000 / ( 3 x V x I)


L-L(V)

215 THREE PHASE PF = kW x 1000 / ( 3xV x I)


L-N(V)

CAPACITOR CAPACITANCE SINLE & THREE PHASE FORMULA

2
216 SINGLE PHASE CF =KVAR x 1000 / (2 FC x V )

217 THREE PHASE CF = KVAR x 1000 / ( 3x2 FC x V 2 )


L- L(V)

218 THREE PHASE CF = KVAR x 1000 / ( 3x2 FC x V 2)


L - N(V)

KW TO AMPS CONVENTION SINGLE & THREE PHASE

219 AC SINGLE Ph TO KW TO AMPS = 1000 X KW /(PF X V)

220 AC THREE Ph TO KW TO AMPS = 1000 X KW /( 3 x PF x V )


L-L(V)

221 AC THREE Ph TO KW TO AMPS = 1000 X KW /( 3 x PF x V L - N(V) )

AMPHERE TO KW CONVENTION SINGLE & THREE PHASE

222 AC SINGLE Ph TO AMPS TO KW = (PF x I x V)/1000

223 AC THREE Ph TO AMPS TO KW = ( 3 x P.F x I x VL- L(V) ) / 1000

224 AC THREE Ph TO AMPS TO KW = ( 3 x P.F x I x V ) / 1000


L- N(V)

22 R.SRIDHAR CPWD,MADURAI
AMPS TO KVA CONVERSION SINGLE PHASE & THREE PHASE

225 AC SINGLE Ph TO AMPS TO KVA = I x V / 1000

226 AC TWO Ph TO AMPS TO KVA = I x VL - N(V) x 2 / 1000

227 AC THREE Ph TO AMPS TO KVA = I x 3 x VL - L(V) /1000

228 AC THREE Ph TO AMPS TO KVA = I x 3 x V N(V) /1000


L-

HP TO AMPS CONVENTION SINGLE & THREE PHASE

229 DC HP TO AMPS = HP x 746 / (V x %EFF)

230 AC SINGLE Ph TO HP TO AMPS = HP x 746 / (VL - N(V) x %EFF x PF)

231 AC TWO Ph TO HP TO AMPS = HP x 746 / ( VL - N(V) x %EFF x PF x 2)

232
AC THREE Ph TO HP TO AMPS = HP x 746 / ( V x %EFF x PF x 3 VL - L(V) )

233 AC THREE Ph TO HP TO AMPS = HP x 746 / ( V x %EFF x PF x 3 VL - N(V) )

KVA TO AMPS CONVENTION SINGLE & THREE PHASE

234 AC SINGLE Ph TO KVA TO AMPS = KVA x 1000/ V

235 TWO Ph TO KVA TO AMPS = KVA x 1000/ VL - N(V) x 2

236 AC THREE Ph TO KVA TO AMPS = KVA x 1000/( 3 x VL - L(V) )

237 AC THREE Ph TO KVA TO AMPS = KVA x 1000/( 3 x VL - N(V) )

23 R.SRIDHAR CPWD,MADURAI
AMPHERE TO HP CONVERSION SINGLE PHASE & THREE PHASE

238 DC AMPS TO HP AMPS = ( I x %EFF x V ) / 746

239 AC SINGLE Ph TO HP TO AMPS = ( I x %EFF x VL - N(V) x PF) / 746


240 AC TWO Ph TO HP TO AMPS = ( I x %EFF x PF x V x 2) / 746
L - N(V)
241 AC THREE Ph TO HP TO AMPS = ( I x %EFF x PF x 3 VL - L(V) / 746

242 AC THREE Ph TO HP TO AMPS = ( I x %EFF x PF x 3 VL - N(V) / 746

243 PRESSURE (PSI) = HEAD(FT) x SPECFIC GRAVITY/2.381

244 HEAD (FT) = PRESSURE X 2.381 / SPECFIC GRAVITY

245 PUMP EFFICIENCY = ((HP x WATER) / (HP x BRAKE)) x 100%

CABLE SPAN AND SAG FORMULA


2
246 LENGTH = ( S + ( 8 x d ) / ( (S x 3)
d = SAG, S = SPAN

247 BATTERY MAH CALCULATION


2
E = (V x C)/2 T=RxC

248 RESONANCE FREQUENCY


1/2 K/M SPRING CONSTAND
M = SPRING MASS

24 R.SRIDHAR CPWD,MADURAI
249 TWO WATT METER METHOD
( I2 x V2 x COS 0 (30 + 0 ) + (I3 x V3x COS 0 (30 + 0 )

WHERE I2 , I3 ARE CURRENT AND V2, V3 ARE VOLTAGE


0 = ANGLE DISPALCEMENT

250 THE EMF EQUATION OF DC MOTOR


E = PN 0Z
60A

251 FLUX = MAGANETO MOTIVE FORCE


RELECTANCE

252 CURRENT = ELECTROMOTIVE FORCE


RESISTANCE

253 PERMEANCE = 1
RELECTANCE

254 CONDUCTANCE = 1
RESISTANCE

255 PERMEABILITY = 1
RELECTIVITY

256 CONDUCTIVITY = 1
RESISTIVITY

25 R.SRIDHAR CPWD,MADURAI
257 FORM FACTOR = ROOT MEAN SQUARE
AVERAGE VALUE

258 PITCH FACTOR = MAXIMUN VALUE


ROOT MEAN SQUARE VALUE

259 FLUX DENSITY = (WEBER/METER SQUARE)

260 CURRENT DENSITY = (AMPER/METER SQUARE)

261 AMPER HOUR EFFICIENCY = AMPHER HOURS ON DISCHARGE


AMPHER HOURS ON CHARGE

262 WATT HOUR EFFICIENCY = WATT HOURS ON DISCHARGE


WATT HOURS ON CHARGE

2
263 GENTRAL FORMULA HEATING = I RT x N = (M+W) (T2- T1)
JOULE

264 WATT HOUR EFFICIENCY


WH = WATT- HOUR ON DISCHARGE
WATT- HOUR ON CHARGE

265 THE GENERAL EQUATION ALTERNATING VOLTAGE AND CURRENT

V = Vm SIN (Wt + 0 ) i = ImSIN (Wt +0 )

THE VOLTAGE EQUATION OF MOTOR


266 V = Eb + IaRa. Eb = back e.m.f
armature ohmic drop IaRa

26 R.SRIDHAR CPWD,MADURAI
267 Cable Sizing Formula
( 2 x L X I) / ( K x VD)
I = Load current L = Length of cable
K = Conducitivity of Copper 58%
K = Conducitivity of Aluminium 36%
% Voltage drop 6.9% for 230 Volt
% voltage drop 12% for 400 Volt

Voltage Regulation of Alternator

268
Unity Power factor E= (V+ IaRa ) + (Ia x S)

269 Lagging power factor E = ( Vcos0 + IaRa) + (Vsin0 + Ia x S)

270 Leading power factor E = ( Vcos0 + IaRa) + ( Vsin0 - Ia x S)

271 The gentral equation of alternating voltage & current


v = Vm Sin (wt + 0 ) i = Im(wt + 0)

272 The equation of induced current of Alternator is i = Imsin0 = Im wt = Imsin2 ft

273 E.m.f equation of Transformer = E1 = 4.44fN1 0m volt = 4.44fN Bm


1
A volt

274 The voltage drop of transformer as refered to secoundty is I (R02cos0+X02sin0)

275 The voltage equation of shunt generator is E = V+I Ra +a brush drop

276 Electric Heat - Temperature rise Method


g
CFM = BTU / ( TEMPERATURE x 1.08)
Input Temperature('F) x Volt x Amps

27
R.SRIDHAR CPWD,MADURAI
278 Single Phase formula CFM = (Volts x Amps x 3.412) / (Temp x 1.08)

279 Three Phase formula CFM = (Volts/3) x (Amps/3) x 1.732x 3.412


(Temperature('F) x 1.08)

280 HP = Volume (CFM) x Pressure (Ib per Sq Inch)


229 x Mechnical efficiency of fan

For purpose of estimating the eff of Fan or blower may be assumed to be 0.65

281 1 BTU = 0.0000833333 TON


282 1 WATTS = 0.0013596 HP

283 1 TON = 155633.85 FOOOD POUND - FORCE /MINIUTE

284 1 TON = 12660.67 KJ/HOUR

285 1 HP = 2647.79 KJ/HOUR


286 1 HP = 0.209135 TON
287 1 HP = 2509.62 BTU/HOUR
288 1 HP = 632.83 KILOCALORIE / MINIUTE
289 1 HP = 10547 CALORIE/MINIUTE

28
R.SRIDHAR CPWD,MADURAI
Electrical Specification Key
Capacity of Circuits

Lighting Circuit means light/fan/bell point each shall not more than 800 watts or 10 Points which ever is
lessIn case CFL Points load where load per point may be less and No point will suitably increased
Load More than 1 KW Controled by Suitable rated MCB
Power circuit in Non residential building will have only one outlet only
Insulation : copper conductor cable PVC insulated conforming to BIS Specification
Multistanded: Cables are permitted to be used.
Wiring
Submain wiring mean the wiring from one main/distribution switchboard to another
Circuit wiring shall mean the wiring from the distribution board to the 1st tapping point inside box from
where point wiring starts.
Each Power Circuit in residential Building can feed the following outlets
Socket outlets = 2 Nos 16Amps Not more than
a) 3 Nos 6 Amps Not more than
b) 2 Nos 16 Amps and 1 No 6 Amps Not more than
c) Socket outlet in modular type shall be 3pin 6A, 3 pin 16A, 3 pin 6A/16A . and 2 pin 5 pin will not be
permitted
Socket of power outlet rating above 1 KW shall be industrial type associated with plug top and
controlled MCB
5A/16A socket will be in the following Position
Non Residential Building - 23 cm above the floor Level
a) Kitchen - 23 cm above the Platform away from stove or sink
b) Bathroom Socket was not permitted, for connecting portable appliance MCB/IC switch may be
provided above 2 meter and 1 meter way from the shower
6A or 16A switch kept along with socket outlet

5 Amps ,15 Amps Socket Outlet Rated 100 watts and 1000 Watts unless actual load specified
Group ‘A’ Means = Type 1 to Type 3 Qtrs in Residential Building
Group ‘B’ Means = Type IV Qtrs and above
Group ‘C’ Means = Non Residential Building
Light Point - 1.5 sqmm
Power Point - 4 sqmm
Fan Fitting height – 2.75 Meter above from the floor level
Switch Broad/ Regulator – 1.25m above from the floor level
Fan the capacity of ceiling fan meet the requirement room with longer dimension d meter should about 55
Dm^3/Min
Fan blade minimum distance 0.3 meters from ceiling
The Minimum servive value of fans shall be 3.5m^3/Min/W and Air delivery 200m^3/min
The height of fan blades above the floor (3H+W)/ 4 Where H is the height of the room and W is the height of the
Room.
Ceiling Rose : Ceiling Rose shall not be used in the Circuit the voltage of which normaly exceed 250Volts

Cubical Panel – CRCA not less than 2.0 mm thick 1.6mm for doors LT panel operating handle 1.7 Mtrs height over
all height not exceed 2.3 meters
LT Panel Earthing – 2 Nos 20 x 3 copper strip LT panel up to 400 Amps capacity or 2 Nos 20 x 5mm copper strip of
higher capacity shall be fixed all around the panel connected to 2 nos earth bus copper strips connected to
incoming earth conductors.
Rising Mains – It is used for 2 Store and above this used indoor application & vertical application it is capable of
with standing 660 volts
Two number of Copper Strips 20 x 3mm ( For Rising main up to 400 amp) and 20 x 5mm for raising above 400 amp
and up to 800 amp
Bus bar clearence – Phase to phase 32mm and Earth to Phase 26mm
Over Head Busbar system
Enclosure Sheet metal used for fabrication of side channels have the 1.6mm thick and top and bottom 1.2mm
thick Bus Trucking shall suspended at a uniform heighjt 2.4m above from floor level
Note: For strip Connection Busbars to switch gear the above clearence don’t apply
Earthing
Electrode Materials and Dimensions
GI pipe electrode shall be cut tapered at the bottom and provided with holes of 12mm dia drilled not less
than 7.5cm from each other up to 2m of length from the bottom. The length of the burried strip or
conductor earth electrode shall not be not less than 15m , the length shall suitable be incresed if
necessary on the basis of information available about soil resistance so that the required earth resistance
obtained.
Materials & size of earth electrode
Pipe G.I Medium 40mmdia 4.5 long (without joint)
GI Plate 60cm x 60cm x 6mm thick
Copper Plate 60cm x 60cm x 3mm thick
GI Strip 100 Sqmm section
Copper Strip 40 Sqmm section
Copper Conductor 4mm Dia (8 SWG)
Earth Continuity/Loop Earthing Conductor & Sizes
Size of Conductor up to 4 Sqmm = Same size of conductor
Above 4 Sqmm up to 16 Sqmm = Same size of conductor
Above 16 Sqmm up to 35 Sqmm = 16 Sqmm
Above 35 Sqmm = Half of the phase of the Conductor

Selection of Type of Electrode


G.I Pipe – Internal Electrical Installations like DB and meter board (in Residential Qtrs)
feeder pillers and poles etc.

G.I Plate - For Fire Fighting pumps and water supply pumps and Lighting Conductor
Copper Plate – Neutral Earthing of transformer/ Genset
Strip / Conductor – Locations where it is not possible to use other types

Lighting Design
Middle aged people – 350 lux
Aged person 55 to 66 requires – 500 lux

Minimum Luminus efficacy (im/iw)


CFL -65
T-5 Tubular Flu -100
Metal Halide Lamp -75
High pressure sodium vapour lamp -90
LED warm day light -80
LED cool day light -90
Fan Room Length
Room width 4m 5m 6m 7m 8m 9m 10m 11m 12m 14m 16m
3 1200/1 1400/1 1500/1 1050/2 1200/2 1400/2 1400/2 1400/2 1200/3 1400/3 1400/3
4 1200/1 1400/1 1200/2 1200/2 1200/2 1400/2 1400/2 1500/2 1200/3 1400/3 1500/3
5 1400/1 1400/1 1400/2 1400/2 1400/2 1400/2 1400/2 1500/2 1400/3 1400/3 1500/3
6 1200/2 1400/2 900/4 1050/4 1200/4 1400/4 1400/4 1500/4 1200/6 1400/6 1500/6
7 1200/2 1400/2 1050/4 1050/4 1200/4 1400/4 1400/4 1500/4 1200/6 1400/6 1500/6
8 1200/2 1400/2 1200/4 1200/4 1200/4 1400/4 1400/4 1500/4 1200/6 1400/6 1500/6
9 1400/2 1400/2 1400/4 1400/4 1400/4 1400/4 1400/4 1500/4 1400/6 1400/6 1500/6
10 1400/2 1400/2 1400/4 1400/4 1400/4 1400/4 1400/4 1500/4 1400/6 1400/6 1500/6
11 1500/2 1500/2 1500/4 1500/4 1500/4 1500/4 1500/4 1500/4 1500/6 1500/6 1500/6
12 1200/3 1400/3 1200/6 1200/6 1200/6 1400/6 1400/6 1500/6 1200/7 1400/9 1400/9
13 1400/3 1400/3 1200/6 1200/6 1200/6 1400/6 1400/6 1500/6 1400/9 1400/9 1500/9
14 1400/3 1400/3 1400/6 1400/6 1400/6 1400/6 1400/6 1500/6 1400/9 1400/9 1500/9

All rigid conduit pipes shall be sheet be ISI Metal. The wall thickness shall be not less than 1.6mm (16SWG) for conduit up to 32mm
dia and not less than 2mm (14SWG) for conduit above 32mm dia. No steel conduit less than 20mm in diameter shall be used, Saddles
for surface conduit work on wall shall not be less than 0.55mm (24 gauge) for conduit up to 25mm dia not less than 0.9mm (20 gauge)
for larger diameter, the corresponding width shall be 19mm & 25mm
METALIC CONDUIT WIRING SYSTEM Maximum Numberof PVC Insulated 650/1100 volt Grade Alu/Cu
Conductor cable

Nominal Cross 20MM 25MM 32MM 38MM 51MM 64MM


Section Area
S B S B S B S B S B S B
1 2 3 4 5 6 7 8 9 10 11 12 13
1.5 5 4 10 8 18 12 - - - - - -
2.5 5 3 8 6 12 10 - - - - - -
4 3 2 6 5 10 8 - - - - - -
6 2 - 5 4 8 7 - - - - - -
10 2 - 4 3 6 5 8 6 - - - -
16 - - 2 2 3 3 6 5 10 7 12 8
25 - - - 3 2 5 3 8 6 9 7
35 - - - - - - 3 2 6 5 8 6
60 - - - - - - - - 5 3 6 5
70 - - - - - - - - 4 3 5 4

The colums headed 'S' apply to runs of conduit which have distance exceeding 4.25m between draw in boxes and which donot deflect
from the stright angle by an angle more than 15 degrees . The colums headed 'B' apply of runs of conduit which deflect from stright by
an angle more than 15 degrees
NON METALIC CONDUIT WIRING SYSTEM TABLE - III
Nominal out side diameter (in Maximum outside Diameter Minimum Inside Diameter Minimum Permissible Maximum Permissible
SL MM) (in MM) (inMM) Ovality (inMM) eccentricity (inMM)

1 20 20 +0.3 17.2 0.2 0.5


2 25 25+0.3 21.6 0.2 0.5
3 32 32+0.3 28.2 0.2 0.5
4 40 40+0.3 35.8 0.2 0.5
5 50 50+0.3 45 4 0.6
TABLE -IV
ORDINARY CLIPS OR GRIDER CLIPS
SIZE OF CONDUIT WIDTH THICKNESS
20 MM & 25 MM 19 MM 20 SWG (0.9144) IN MM
32 MM & ABOVE 25 MM 18 SWG (1.219) IN MM
Special Precations
In Concealed/inaccessible places of combustible construction where ambient temperature exceeds 60 degrees C.
In places where ambient temperature is less 5 degree C.For Suspension of Flu fitting (d) in areas exposed to Sunlight.
Non Metalic conduit less than 20 mm in diameter is not used
Wiring capacity - The maximum number of PVC insulated Alu/Cu Conductor cable of 650/1100V Grade conforming to is 694 . 1990
that can be drawn in one of various sizes in given table -1
For all sizes of conducit the size of clamping rod shall be 4.5mm (7swg) diameter
The thickness of the walls and base of PVC boxes shall not be less than 2mm. The clear depth of PVC boxes shall not less than
60M
3mm thickness phenolic laminated sheet covers for all types shall sa per requirement
The radius of the bend conduit pipes shall not less than 7.5cm the left of the conduit shall have more than equivalent of fopur quarter
bent to outlet to outlet

Trunking Cable Management system Maximum Numberof PVC Insulated 650/1100 volt grade Alu/Cu Conductor
cable

Nominal Cross 10/15MM 20/15M 25/15MM 32MM 40MM 40MM


Section Area X 10 MM M X 10 X 16 MM / X 60 X 25 X
MM MM MM 40MM
1.5 3 5 6 8 12 18
2.5 2 4 5 6 9 15
4 2 3 4 5 8 12
6 2 3 4 6 9
10 1 2 3 5 8
16 1 2 4 6
25 1 3 5
35 2 4
50 1 3
70 1 2
The Table Shown the outer diameter of the Mini tunking
Bus Bar
Busbar shall be aluminium or alu alloy or electric gade copper rating 100A, 200A,300A,400A,500A,600A or 800A Current density

busbar shall be sufficient cross serction so that a current density of 130A/sq.cm(800A/sq.inch) is not exceed at nominal Correct rating

for Aluminium busbar and 160A/sq(1000A/sq.inch) for copper busbar the cros section netural busbar shall bethat if phase busbar for

busbar capcities up to 200A for heigher capacities the netural busbar cross section will be half of the phase bus bar

Bus bar supports class 'F' insulation made of non hydroscopic, noncombustible track resistant and heigh strength
FRP/SMC/DMC Material
Aluminium Copper BusBar section
Recommented Rectangular cross section
Current Aluminium Copper
Rating Size in mm No Size in mm
Amps No strip/ strip/ph
phase ase
100 1 20 x 5 1 20 x 3
200 1 30 x 5 1 25 x 5
300 1 50 x 5 1 40 x 5
400 1 50 x 6 1 50 x 5
500 1 75 x 6 1 60 x 5
600 1 80 x 6 - -
800 1 100 x 6 - -
1000 1 100 x 10 - -
1200 1 125 x 10 - -
1600 2 100 x 10 - -
2000 2 125 x 10 - -
2500 3 125 x 10 - -

A Earth Continiuity Strip for Protective Earthing of Substation equipment


SL.No Type of Installation Earth Electrode Earth strip from Earth
electrode to earth bus &
looping equipment
1 Indoor substation with H.T Copper plate 25 x 5mm Copper Strip
panelTransformer capacity up to
1600 KVA LT Panel Generating
Set
2 Indoor substation with H.T panel Copper plate 32mm x 5mm Copper strip
Transformer capacity above 1600
KVA LT Panel Generating Set

3 HT Outdoor Substation Copper plate 25mm x 5mm Copper strip

4 LT Indoor substation with Copper plate


Genrator 25mm x 5mm Copper strip
5 LT Switch room having main LT Copper plate 20 x 3mm copper strip
switchboard

B.Earth Continiuity Strip for Bus Trunking and Rising main


SL.No Type of Installation Material of Earth strip from Earth
Main Conductor Station to Netural

1 Bus Trunking up to 2500 Amp Copper / 2 Nos 25mm x 5mm


capacity Aluminium Copper strip
2 Bus Trunking above 2500 Amp Copper / 2 Nos 32mm x 5mm Copper
capacity Aluminium strip
3 Copper /
Bus Trunking for Connecting Aluminium 2 Nos 25mm x 5mm Copper
Generating set and LT Panel strip
4 Copper / 2 Nos 20mm x 3mm Copper
Rising main up to 400A Capacity Aluminium strip
5 Rising main above 400A Capacity Copper / 2 Nos 20mm x 5mm Copper
and upto 800A Aluminium strip
C. Netural Earthing of Trans former and Generator
SL.No Equipment Earth Electrode Earth strip from Earth
Station to Netural
1 Transformer Capacity up to 1600 Copper plate 25mm x 5mm Copper Strip
KVA
2 Transformer Capacity above Copper plate 32mm x 5mm Copper Strip
1600 KVA

3 Copper plate 25mm x 5mm Copper Strip


Generator set for all capacity

Earthing Conductor Size

The Size of earthing conductor shall be specified but this shall not be less the following size
a) 4mm dia (8 SWG) Copper wire
b) 25mm x 4mm in the case of GI strip, or
c) 20mm x 3mm in the case of Copper Strip
Earthing conductor larger then the following sectional areas need to be used unless otherwise
specified.
a) 150 Sqmm in case of GI
b) 100 Sqmm in case of Copper
Installation Electrodes
Various types of electrodes
a) Pipe electrodes shall be barried in ground vertically with its top at not less than 20cm below the
ground level
b) Plate electrode shall be burried in ground with its faces and top is not less than 0.3m below the
ground level when more than one electrode( mplate or Pipe instaled seprately not less than 2 m
distance between two adjacent electrodes
The trip or conductor electrode shall be baried in trench not less than 0.5m deep. If the Continious
necessitate the use of more than one strip or Conductor electrode they shall be laid as widely disturbed as
possible in a single straight trench here feasible or preferably in a number of trenches radiating from one
point , If the electrode cannot be laid a straight it may be laid in a ziggag manner a deviation up to 45
degrees from the axis of the strip It can also laid in the form of arc with curvature more than 1 M or a
Polygon.
Watering arrangement
In case of Plate earth electrodes a watering pipe 20cm dia medium class provided and attached a funel mesh
in top for watering

In case of pipe electrodes a 40mm x 30mm reducer shall be used for fixing the funnel with mesh

The watering funnel attachment shall be housed in a masonary enclosure not less than 30cm x 30cm x 30cm
A cast Iron/Ms frame with Ms cover 6mm thick and having locking arrangement
Earthing conductor(Main earth lead)
In case of plate earth electrode wire type earthing conductors shall be secured as indicated using bolts ,
nuts and washers and terminating socket.
Double C- clamp arrangement shall provided for terminating tape type earthing conductor with GI watering
pipe copled to the pipe earth electrode, galvanished"C" shaped strips bolts nuts and checknetsd shall be
used.
Earth Resistance - Greater than 5 Ohms Resis and Rocky soil may having 8 ohm Resis
UG Cable selection of Aluminium Conductor cable peak load current rating 8% of voltage drop cable grading 1.1 KV
S.No Distance in Mtrs for the following size in sqmm
Current Amps 6 10 16 25 35 50 70 95 120 150 185 240 300
1 5 165 260 415 725 895 1300 1925 2360 3065 3555 4300 5770 6460
2 10 80 130 205 360 450 650 960 1180 1530 1775 2150 2885 3230
3 15 55 85 140 240 300 430 640 785 1020 1185 1430 1920 2155
4 20 40 65 100 180 225 325 480 590 765 890 1075 1440 1615
5 25 30 50 80 145 180 260 385 470 610 710 860 1150 1290
6 30 25 40 70 120 150 215 320 390 570 590 715 960 1075
7 40 20 30 50 90 110 160 240 295 380 445 535 720 805
8 50 25 40 70 90 130 190 235 305 355 430 575 645
9 60 35 60 75 110 160 195 255 295 355 480 535
10 70 30 50 65 90 135 165 215 255 305 410 460
11 80 45 55 80 120 145 190 220 265 360 405
12 90 40 50 70 105 130 170 195 235 320 360
13 100 35 45 65 95 115 150 175 215 290 320
14 110 40 60 85 105 140 160 195 260 290
15 120 35 55 80 95 125 145 180 240 270
16 130 50 75 90 115 135 165 220 250
17 140 45 70 80 110 125 150 205 230
18 150 65 75 100 115 140 190 215
19 160 60 70 95 110 130 180 200
20 170 55 70 90 105 125 170 190
21 180 50 65 85 100 120 160 180
22 190 60 80 90 110 150 170
23 200 60 75 90 105 145 160
24 225 65 80 95 125 145
25 250 70 85 115 130
26 275 80 105 115
27 300 70 95 105
Air Temperature'C' 40 45 50
Rating factor(XLPE) 1.00 0.94 0.88
Rating Factor(PVC) 1.00 0.9 0.81

Current rating in ground for XLPE insulated for 1.1 KV Grade Cable (Table - 2)
Nominal Area Aluminium Conductor Copper Conductor
of the Cond Single core Multi Core Single core Multi Core Unity
mm^2 PVC XLPE PVC XLPE PVC XLPE PVC XLPE
10 51 55 46 50 65 71 60 65
16 66 74 60 68 85 95 77 87
25 86 98 76 90 110 125 99 115
35 100 118 92 108 130 150 120 138
50 120 137 110 126 155 175 145 161
70 140 172 135 158 190 220 175 202
95 175 204 165 187 220 260 210 239
120 195 234 185 215 250 301 240 276
150 220 262 210 240 280 336 270 308
185 240 298 235 273 305 381 300 350
240 270 344 275 316 345 441 345 405
300 295 387 305 355 375 496 385 455
400 325 458 335 420 400 586 425 538
500 345 495 425 635
630 390 555 470 710
800 440 625
1000 490 685
Permissible Maxium Short Circuit Current rating for XLPE cables
Conductor Area in sqm Short Circuit Rating for one secound
Duration
Cu A Alu B
16 2570 1730
25 3970 2670
35 5500 3690
50 7800 5220
70 10850 7400
95 14600 9740
120 18400 12200
150 23000 15200
185 28200 18700
240 36400 24200
300 45300 30100
400 60200 39900
500 74800 49800
630 92700 62000
800 - 78800
1000 - 97800

Table -6
Class of Insulation for ( Electric Motor)
Max Operating Temp
Y 90 ' C
A 105' C
E 120 ' C
B 130 ' C
F 155 'C
H 180 ' C
C Above 180'

Lighting Power Density


The installed lighting poer density for building exterior lighting applications mentioned in the table shall not exceed
the limits specified in the table below.
l
Exterior lighting Applications Power Limits
Building entrance (With canopy) 13w/m^2 (1.3w/ft^2) of canopied area
Building entrance (Without canopy) 90 w/lin m (30w/linf) of door width
Building Exit 60 w/lin m (20w/linf) of door width
Building Facades 2 w/m^2(0.2w/ft^2) of vertical façade area
Night Sky pollution &Light Tress pass
All exterior lighting should be designed to minimize night sky pollution those areas shall be lighted that are required
for safety and comport Installatioion of luminaries on lift and building shall be sucvh that no light tresspassing occurs
on the neighboring site and building
For Interior lighting
The angle minimum candela from each interior luminaries as located in the building shall intersect opaque building
interior surface and not exit out throught windows.
For Extrior lighting
The Design extrior lighting so that all side and building mounted luminaries produce a maximum initial illumance
value no greater than 0.01 Horizontal value and vertiucal foot candles at the site boundary beyound.

Lighting fixture : 0% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
Low Residential Area: Design exterior lighting so that all side and building mounted illuminance produce a maximum illiance
value no greater than 0.01 horizontal and vertical foot candles all the side boundry and no greater than 0.01 horizontal foot
candles 10 feet beyound the side boundary
Lighting fixture : 2% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
Medimum Residential Area : Design exterior lighting so that all side and building mounted illuminance produce a maximum
illiance value no greater than 0.20 horizontal and vertical foot candles all the side boundry and no greater than 0.01 horizontal
foot candles 15 feet beyound the side boundary
Lighting fixture : 5% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
High major city center, entertainment district : Design exterior lighting so that all side and building mounted luminaries
produce a maximum illiance value no greater than 0.60 horizontal and vertical foot candles all the side boundry and no greater
than 0.01 horizontal foot candles 15 feet beyound the side boundary
Lighting fixture : 10% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
The present pratice in CPwd While designing indoor lighting is to use T5 lamp in rooms and CFL used in Corridor and other
common areas due to keeping good CRI and to maximize usable lumen per watt HPSV lamp metal halide are being used for
outdoor lighting.
The following Technical parameter of T5 , CRI, HPSV , Metal Halide
LED LED T5 LAMP CFL HPSV METAL
WARM COOL LAMP LAMP HALIDE
WHITE WHITE
CRI 80-85 75 85 85 22 60 - 90
95 -
Efficacy in im/w 80 132 90 70 110 65 - 70
Usable im/w 55-65 >100 75-85 50 -60 55 - 65 35 - 40
10K -
life (Hrs) 50K+ 50K+ 30K 8 - 10K 24K 20K

SELECTION OF LAMPS
LAMP TYPE RANGE LUMINOUS FLUX EFFICACY IN Average Life Hr Colour Rendering
(im/w)
CFL 18W-36W 1200 - 2900 60 -80 15000 75-85
FLUT5 28W-54W 2900 - 4850 90 -104 24000 80 - 90
FLUT8 18W - 36W 750 - 3250 50 - 90 20000 80 - 85
FLUUT12 20W-40W 950 - 2450 48-61 12000 50 - 75
HALOGEN 50W 1200 24 2000 75-90
METAL HALIDE 70W - 250W 5300-25000 76-100 12000 70-90
HIGH PRESSURE
SODIUM VAPOUR
70W-1000W 5600-130000 80-130 20000 20-65
LOW PRESSURE
SODIUM VAPOUR
55W - 135W 8100-32000 100 - 230 20000 20 - 65

INDUCTION LAMP 70W - 150W 6500 - 12000 80 - 95 100000 65-90


LED 3W-120W 750-14000 80 -100 80000 65-90

Tripping Characteristic of MCB


Based on the tripping Charcteristics MCB are available bin 'B' and 'C' Cure to Suit different types of
applications
'B' curve for protection of electroc circuits with eqipment that does not cause surge cuirrent (liughting &
socket outlet circuit) short circuit release is set to 3 - 5In
'C' curve for protection of electric circuits with equipment that cause surge current (inductive and motor
circuits) short circuit release is set to 5 - 10 In
D' Curve for protection of electric circuits which cause high in rush current when they are switched on,
typically 15 times the normal running current
(transformer heavy start motors 2 pole motors)

Duty Categery of switches


Utilization Category Typical Applications
AC20/DC20 - Connecting and disconnecting under no-load assumes all switching operators are carried out
by other applicable devices before this device is operated.
AC21/DC21 - Switching of resistive loads i/c moderate overload suitable for purely resistive type loads
device can switch 150% of its rated current under fault conditions

AC22/DC22 - switching of mixed resistive inductive loads i/c moderate over load.suitable for mixed
resistive loade load device can switch 300% of its rated current under fault conditions.

AC23/DC23 - Switching of highly inductive loads. Device complying with AC23/DC23 are provided mainly as
backup to other means of switching eg. Contacts. In the event of failure of functional devices on
AC23/DC23 type device can safely interrupt a stalled motor current where device are the only means of
controlling individual motors, they should comply with the requirements of appendix A of standard.
Revised Yard stick Type - 1 Type - 2 Type - 3 Type - 4 Type - 5 Type - 6 servent Qtrs
Description Exist Revis Exist Revis Exist Revis Exist Revis Exist Revis Exist Revis Exist Revis
Power Points 15 Amps 6 p 3 2 3 3 3 4 3 5 4 6 7 1
mcb 1 1 1 2 4 5
MCB connected socket
outlet for ac unit/gyser
Ceiling fan fan 2 2 3 3 4 4 5 5 5 6 7 1
Exhaust fan exfan 1 1 1 1 1 1
call bells 1 1 1 1 1 1 1 1 1 2 3
Light/fan/call/5A 17 17 20 20 23 23 24 27 33 38 44 5 5
F.I Fitting exclu tube & 2 2 2 3 3 4 4 5 7 8
Single Phase 1 1 1 1 1 1 1 1 1
3 Phase 1 1 1
TV 1 1 1 1 2 2
Telephone 1 2 2

Principal components of lighting Conductor

a) Air termination b) Down Conductors c) joint and Bonds d) Testing Joints e) Earthing termination f) earth electrode
i) Copper Flat strip or Solid 98% conductivity

ii) Copper Clad steel not less tha 30% of conductance of solid copper of the same total cross sectional area
iii) Galvanished steel protected against corrosion by Zinc Coating
iv) Aluminium 99% pure for sufficient

Shape & Mimimum size of Conductor for use above ground


1. Round copper wire or copper clad steel use = 6mm diameter
2. Standard copper Wire = 50 Sqmm or (7/3.00 mm dia)
3. Copper strip = 20mm x 3mm
4. Galvanished iron Strip = 20mm x 3mm
5. Round Aluminium = 8mm dia
6. Aluminium Strip = 25mm x 3mm
Shape & Mimimum Size of Conductor for use below ground
1. Round copper wire or copper clad steel use = 8mm diameter
2. Copper Strip = 32mm x 6mm
3. Round Galvanished iron used = 10mm x 6mm
4. Galvanished iron Strip = 32mm x 6mm
Road Lighting
Sigle sided
Height = width
Spacing = 3.5 to 4 times Height

Height spacing
e

width
Staggered
Height = 0.8 times width
Spacing 3.5 to 4 times Height
Height spacing

width

Opposite Side
Height = 0.5 times Width
Spacing = 3.5 to 4 times Height
spacing
Height

width

Central Side

Height = 0.8 times width


Height Spacing Spacing = 3.5 to 4 times Height

width

GA DRG FOR FEEDER PILLER

100MM

160 A 160 A 160 A 450MM


TPNMCCB TPNMCCB TPNMCCB

400A TPN ALU BUSBAR 400MM

INCOMING 400A 160 A


VACCANT
TPMCCB TPNMCCB 450MM

10MM
400 300 350
300MM
GL

300MM
In all Fabrication will be done out of 2mm thick CRCA sheet with double door and in built locking arrangement
All connections incoming and outgoing will be taken out in cabley alloy with suitable rated solid conductor
The feeder pillar will have supplied with suitable pedestal (Ms angle iron frame of MS channel base for generating in RCC and proper
gland at the bottom
The feeder pillar will have one 10 Ampos 3 pin Socket out with 10 Amp switch and one brass holder fitted in metering panel
compartment and directly fed from incoming.
The deep of feeder pillar is 40mm the bus made of hand drawn tinned copper are fitted on insulated DMC support.The size
arrangement decided by NIT Authority
The feeder pillar should be provided with termined blocks for incoming & outgoing cables from MCCB to terminated block wiring will
be done with copper conductor/ suitable cable in coming/outgoing UG cable will be terminated intermind block this will very much
All Dimensions are in mm

AC Calculation

1 The room is 10 feet wide by 15 feet long


2 That means 10 x 15 = 150 square feet
3 Take the sqrt (150)/10
4 We get 1.247
5 Choose an AC which is 1.2 tonnes

You might also like