OHMSLAW
1 2 3
2 2
POWER P=VxI V/R I XR
FORMULAS
4 5 6
2 2
RESISTANCE R = V /I V/P, P/I
FORMULAS
7 8 9
10 11 12
1 R.SRIDHAR CPWD,MADURAI
HP FORMULA FOR MOTOR PUMP
14 P = (Q x Pw ) / 6356 x U )
15 P = (Q x p) / 229 x U )
16 P = (Q x PF ) / 33000 x U )
where
P = Power, hp
2 R.SRIDHAR CPWD,MADURAI
FORMULAS FOR FINDING HP, KVA,KW
19 20
21 22 HP x 746
HP x 746
V x P.F x 2 x %EFF V x p.f x 3 x %EFF
23 24
25 26
KW X 1000 KW X 1000
V x P.F x 2 x %EFF V x P.F x 3 x %EFF
3 R.SRIDHAR CPWD,MADURAI
WHEN KVA KNOWN
CURRENT REQUIRED
AC THREE PHASE
29 KVA X 1000
V x 3 x %EFF
HP OUTPUT FORMULAE
30 31
V x %EFF x I V x P.F x %EFF x I
746 746
32 33
4 R.SRIDHAR CPWD,MADURAI
KW FORMULAS
34 35
VxI V x P.F x I
1000 1000
AC THREE PHASE
AC TWO PHASE
36 37
V x P.F x 2 x I V x P.F x 3 x I
1000 1000
KVA FORMULAS
38 39
VxI Vx2xI
1000
1000
AC THREE PHASE
40
Vx3xI
1000
5 R.SRIDHAR CPWD,MADURAI
41 KILOWATT HOUR(AC) V x P.F x 3 x I x HOURS
1000
1
43 CAPACITANCE =
2 FC
POWERFACTOR = KILOWATT
44
KILOVOLT AMPERE
45 INDUCTANCE = 2 XL
2 2
48 IMPEDENCE Z = R +XL
49 POWER = V x I x P.F x 3
6 R.SRIDHAR CPWD,MADURAI
ILLUMINATION CALCULATION AND CONVERSION FORMULAS
2
51 LUX TO LUMENS = 0.09290304 x LUX x AREA IN FT
2
54 WATTS TO LUX = 10.76391 x WATTS x AREA IN FT / (LUMENS/WATTS)
7 R.SRIDHAR CPWD,MADURAI
TRANSFORMER FORMULAS
2
65 TRANSFORMER VOLTAGE TRANSMISSION RATIO = SECOUNDRY
PRIMARY
2
66 TRANSFORMER INDUCTANCE TRANSMISSION RATIO = SECOUNDRY
PRIMARY
2 2
70 KVAR = KVA - KW
8 R.SRIDHAR CPWD,MADURAI
71 HP TO KW = (HP X 746) / 1000
72 KW TO HP = KW/0.746
75 KW TO KVA = KW/PF
76 KVA TO KW = KVA x PF
9 R.SRIDHAR CPWD,MADURAI
81 OHMS TO AMPS (R) = V / I
83 KW TO AMPS = KW x1000/VOLT
84 AMPS TO KW = I x V / 1000
87 VA TO KW = VA x PF / 1000
88 KW TO VA = KW x 1000 / PF
89 KW TO KWH = KW x T (HR)
91 VA TO KVA = VA / 1000
93 VA TO AMPS = VA / V
94 AMPS TO VA = I x V
96 VA TO KVA = VA / 1000
97 AH TO WH = AH x V
98 WH TO AH = WH / V
10 R.SRIDHAR CPWD,MADURAI
99 WATTS TO VA = WATT / PF
100 VA TO WATTS = VA x PF
11 R.SRIDHAR CPWD,MADURAI
111 MAH TO WH = MAH x VOLT / 1000
12 R.SRIDHAR CPWD,MADURAI
125 RT(TON) TO KW = RT x 3.5168
126 KW TO RT = RT/3.5168
134 1 VA = 0.0001 KW
13 R.SRIDHAR CPWD,MADURAI
135 1 AH = 3600 COLUMB
-4
138 1 COLUMB = 2.7778 .10
0.09290304 FOOTCANDELA
4
140 1KWH = 36 x 10 JOULES
14 R.SRIDHAR CPWD,MADURAI
10
145 DECIBAL TO MILLIWATTS = 10 x LOG (m/w/Imw)
9
152 GEGAVOLT TO ELECTROVOLT = GEV- 10 EV
155 RESISTANCE R = L
A
15 R.SRIDHAR CPWD,MADURAI
156 1 AMPS = 1COLUMB / 1 SECOUND
2
159 1 JOULE = 1 KG x M / SEC
2
163 1 TESELA = 1 WB / 1 METER
16 R.SRIDHAR CPWD,MADURAI
166 CHARGE (Q) = COLUMB x VOLT
175 I = (K X I x V ) / 1000
17 R.SRIDHAR CPWD,MADURAI
STAR TO DELTA
R1
DELTA TO STAR
B
R
179 R1 = RB RC
RA+RB+RC
Y
180 R2 = RA RC
RA+RB+RC
R
181 R3 = RA RB
B Y
RA+RB+RC
STAR CONNECTION
18 R.SRIDHAR CPWD,MADURAI
DELTA CONNECTION
IMPEDANCE FORMULA
2 2
188 ZRX = R + XL
2 2
189 ZRC = R + XC
2
191 ZRLC = R2+ (XL - XC)
RX
192 2
R2+ XL
19 R.SRIDHAR CPWD,MADURAI
REACTANCE FORMULA
2 2
198 L = 1/4 FL L mirohendry =25.330/F c
2 2
199 C = 1/4 FC C mirofarads =25.330/F c
200 HP = T x N
5250 T = TORQUE
202 NS = HP X 5250
T
20 R.SRIDHAR CPWD,MADURAI
RELATION BETWEEN SPEED, FREQUENCY AND NO POLES
21 R.SRIDHAR CPWD,MADURAI
POWER FACTOR SINGLE PHASE & THREE PHASE FORMULA
2
216 SINGLE PHASE CF =KVAR x 1000 / (2 FC x V )
22 R.SRIDHAR CPWD,MADURAI
AMPS TO KVA CONVERSION SINGLE PHASE & THREE PHASE
232
AC THREE Ph TO HP TO AMPS = HP x 746 / ( V x %EFF x PF x 3 VL - L(V) )
23 R.SRIDHAR CPWD,MADURAI
AMPHERE TO HP CONVERSION SINGLE PHASE & THREE PHASE
24 R.SRIDHAR CPWD,MADURAI
249 TWO WATT METER METHOD
( I2 x V2 x COS 0 (30 + 0 ) + (I3 x V3x COS 0 (30 + 0 )
253 PERMEANCE = 1
RELECTANCE
254 CONDUCTANCE = 1
RESISTANCE
255 PERMEABILITY = 1
RELECTIVITY
256 CONDUCTIVITY = 1
RESISTIVITY
25 R.SRIDHAR CPWD,MADURAI
257 FORM FACTOR = ROOT MEAN SQUARE
AVERAGE VALUE
2
263 GENTRAL FORMULA HEATING = I RT x N = (M+W) (T2- T1)
JOULE
26 R.SRIDHAR CPWD,MADURAI
267 Cable Sizing Formula
( 2 x L X I) / ( K x VD)
I = Load current L = Length of cable
K = Conducitivity of Copper 58%
K = Conducitivity of Aluminium 36%
% Voltage drop 6.9% for 230 Volt
% voltage drop 12% for 400 Volt
268
Unity Power factor E= (V+ IaRa ) + (Ia x S)
27
R.SRIDHAR CPWD,MADURAI
278 Single Phase formula CFM = (Volts x Amps x 3.412) / (Temp x 1.08)
For purpose of estimating the eff of Fan or blower may be assumed to be 0.65
28
R.SRIDHAR CPWD,MADURAI
Electrical Specification Key
Capacity of Circuits
Lighting Circuit means light/fan/bell point each shall not more than 800 watts or 10 Points which ever is
lessIn case CFL Points load where load per point may be less and No point will suitably increased
Load More than 1 KW Controled by Suitable rated MCB
Power circuit in Non residential building will have only one outlet only
Insulation : copper conductor cable PVC insulated conforming to BIS Specification
Multistanded: Cables are permitted to be used.
Wiring
Submain wiring mean the wiring from one main/distribution switchboard to another
Circuit wiring shall mean the wiring from the distribution board to the 1st tapping point inside box from
where point wiring starts.
Each Power Circuit in residential Building can feed the following outlets
Socket outlets = 2 Nos 16Amps Not more than
a) 3 Nos 6 Amps Not more than
b) 2 Nos 16 Amps and 1 No 6 Amps Not more than
c) Socket outlet in modular type shall be 3pin 6A, 3 pin 16A, 3 pin 6A/16A . and 2 pin 5 pin will not be
permitted
Socket of power outlet rating above 1 KW shall be industrial type associated with plug top and
controlled MCB
5A/16A socket will be in the following Position
Non Residential Building - 23 cm above the floor Level
a) Kitchen - 23 cm above the Platform away from stove or sink
b) Bathroom Socket was not permitted, for connecting portable appliance MCB/IC switch may be
provided above 2 meter and 1 meter way from the shower
6A or 16A switch kept along with socket outlet
5 Amps ,15 Amps Socket Outlet Rated 100 watts and 1000 Watts unless actual load specified
Group ‘A’ Means = Type 1 to Type 3 Qtrs in Residential Building
Group ‘B’ Means = Type IV Qtrs and above
Group ‘C’ Means = Non Residential Building
Light Point - 1.5 sqmm
Power Point - 4 sqmm
Fan Fitting height – 2.75 Meter above from the floor level
Switch Broad/ Regulator – 1.25m above from the floor level
Fan the capacity of ceiling fan meet the requirement room with longer dimension d meter should about 55
Dm^3/Min
Fan blade minimum distance 0.3 meters from ceiling
The Minimum servive value of fans shall be 3.5m^3/Min/W and Air delivery 200m^3/min
The height of fan blades above the floor (3H+W)/ 4 Where H is the height of the room and W is the height of the
Room.
Ceiling Rose : Ceiling Rose shall not be used in the Circuit the voltage of which normaly exceed 250Volts
Cubical Panel – CRCA not less than 2.0 mm thick 1.6mm for doors LT panel operating handle 1.7 Mtrs height over
all height not exceed 2.3 meters
LT Panel Earthing – 2 Nos 20 x 3 copper strip LT panel up to 400 Amps capacity or 2 Nos 20 x 5mm copper strip of
higher capacity shall be fixed all around the panel connected to 2 nos earth bus copper strips connected to
incoming earth conductors.
Rising Mains – It is used for 2 Store and above this used indoor application & vertical application it is capable of
with standing 660 volts
Two number of Copper Strips 20 x 3mm ( For Rising main up to 400 amp) and 20 x 5mm for raising above 400 amp
and up to 800 amp
Bus bar clearence – Phase to phase 32mm and Earth to Phase 26mm
Over Head Busbar system
Enclosure Sheet metal used for fabrication of side channels have the 1.6mm thick and top and bottom 1.2mm
thick Bus Trucking shall suspended at a uniform heighjt 2.4m above from floor level
Note: For strip Connection Busbars to switch gear the above clearence don’t apply
Earthing
Electrode Materials and Dimensions
GI pipe electrode shall be cut tapered at the bottom and provided with holes of 12mm dia drilled not less
than 7.5cm from each other up to 2m of length from the bottom. The length of the burried strip or
conductor earth electrode shall not be not less than 15m , the length shall suitable be incresed if
necessary on the basis of information available about soil resistance so that the required earth resistance
obtained.
Materials & size of earth electrode
Pipe G.I Medium 40mmdia 4.5 long (without joint)
GI Plate 60cm x 60cm x 6mm thick
Copper Plate 60cm x 60cm x 3mm thick
GI Strip 100 Sqmm section
Copper Strip 40 Sqmm section
Copper Conductor 4mm Dia (8 SWG)
Earth Continuity/Loop Earthing Conductor & Sizes
Size of Conductor up to 4 Sqmm = Same size of conductor
Above 4 Sqmm up to 16 Sqmm = Same size of conductor
Above 16 Sqmm up to 35 Sqmm = 16 Sqmm
Above 35 Sqmm = Half of the phase of the Conductor
G.I Plate - For Fire Fighting pumps and water supply pumps and Lighting Conductor
Copper Plate – Neutral Earthing of transformer/ Genset
Strip / Conductor – Locations where it is not possible to use other types
Lighting Design
Middle aged people – 350 lux
Aged person 55 to 66 requires – 500 lux
All rigid conduit pipes shall be sheet be ISI Metal. The wall thickness shall be not less than 1.6mm (16SWG) for conduit up to 32mm
dia and not less than 2mm (14SWG) for conduit above 32mm dia. No steel conduit less than 20mm in diameter shall be used, Saddles
for surface conduit work on wall shall not be less than 0.55mm (24 gauge) for conduit up to 25mm dia not less than 0.9mm (20 gauge)
for larger diameter, the corresponding width shall be 19mm & 25mm
METALIC CONDUIT WIRING SYSTEM Maximum Numberof PVC Insulated 650/1100 volt Grade Alu/Cu
Conductor cable
The colums headed 'S' apply to runs of conduit which have distance exceeding 4.25m between draw in boxes and which donot deflect
from the stright angle by an angle more than 15 degrees . The colums headed 'B' apply of runs of conduit which deflect from stright by
an angle more than 15 degrees
NON METALIC CONDUIT WIRING SYSTEM TABLE - III
Nominal out side diameter (in Maximum outside Diameter Minimum Inside Diameter Minimum Permissible Maximum Permissible
SL MM) (in MM) (inMM) Ovality (inMM) eccentricity (inMM)
Trunking Cable Management system Maximum Numberof PVC Insulated 650/1100 volt grade Alu/Cu Conductor
cable
busbar shall be sufficient cross serction so that a current density of 130A/sq.cm(800A/sq.inch) is not exceed at nominal Correct rating
for Aluminium busbar and 160A/sq(1000A/sq.inch) for copper busbar the cros section netural busbar shall bethat if phase busbar for
busbar capcities up to 200A for heigher capacities the netural busbar cross section will be half of the phase bus bar
Bus bar supports class 'F' insulation made of non hydroscopic, noncombustible track resistant and heigh strength
FRP/SMC/DMC Material
Aluminium Copper BusBar section
Recommented Rectangular cross section
Current Aluminium Copper
Rating Size in mm No Size in mm
Amps No strip/ strip/ph
phase ase
100 1 20 x 5 1 20 x 3
200 1 30 x 5 1 25 x 5
300 1 50 x 5 1 40 x 5
400 1 50 x 6 1 50 x 5
500 1 75 x 6 1 60 x 5
600 1 80 x 6 - -
800 1 100 x 6 - -
1000 1 100 x 10 - -
1200 1 125 x 10 - -
1600 2 100 x 10 - -
2000 2 125 x 10 - -
2500 3 125 x 10 - -
The Size of earthing conductor shall be specified but this shall not be less the following size
a) 4mm dia (8 SWG) Copper wire
b) 25mm x 4mm in the case of GI strip, or
c) 20mm x 3mm in the case of Copper Strip
Earthing conductor larger then the following sectional areas need to be used unless otherwise
specified.
a) 150 Sqmm in case of GI
b) 100 Sqmm in case of Copper
Installation Electrodes
Various types of electrodes
a) Pipe electrodes shall be barried in ground vertically with its top at not less than 20cm below the
ground level
b) Plate electrode shall be burried in ground with its faces and top is not less than 0.3m below the
ground level when more than one electrode( mplate or Pipe instaled seprately not less than 2 m
distance between two adjacent electrodes
The trip or conductor electrode shall be baried in trench not less than 0.5m deep. If the Continious
necessitate the use of more than one strip or Conductor electrode they shall be laid as widely disturbed as
possible in a single straight trench here feasible or preferably in a number of trenches radiating from one
point , If the electrode cannot be laid a straight it may be laid in a ziggag manner a deviation up to 45
degrees from the axis of the strip It can also laid in the form of arc with curvature more than 1 M or a
Polygon.
Watering arrangement
In case of Plate earth electrodes a watering pipe 20cm dia medium class provided and attached a funel mesh
in top for watering
In case of pipe electrodes a 40mm x 30mm reducer shall be used for fixing the funnel with mesh
The watering funnel attachment shall be housed in a masonary enclosure not less than 30cm x 30cm x 30cm
A cast Iron/Ms frame with Ms cover 6mm thick and having locking arrangement
Earthing conductor(Main earth lead)
In case of plate earth electrode wire type earthing conductors shall be secured as indicated using bolts ,
nuts and washers and terminating socket.
Double C- clamp arrangement shall provided for terminating tape type earthing conductor with GI watering
pipe copled to the pipe earth electrode, galvanished"C" shaped strips bolts nuts and checknetsd shall be
used.
Earth Resistance - Greater than 5 Ohms Resis and Rocky soil may having 8 ohm Resis
UG Cable selection of Aluminium Conductor cable peak load current rating 8% of voltage drop cable grading 1.1 KV
S.No Distance in Mtrs for the following size in sqmm
Current Amps 6 10 16 25 35 50 70 95 120 150 185 240 300
1 5 165 260 415 725 895 1300 1925 2360 3065 3555 4300 5770 6460
2 10 80 130 205 360 450 650 960 1180 1530 1775 2150 2885 3230
3 15 55 85 140 240 300 430 640 785 1020 1185 1430 1920 2155
4 20 40 65 100 180 225 325 480 590 765 890 1075 1440 1615
5 25 30 50 80 145 180 260 385 470 610 710 860 1150 1290
6 30 25 40 70 120 150 215 320 390 570 590 715 960 1075
7 40 20 30 50 90 110 160 240 295 380 445 535 720 805
8 50 25 40 70 90 130 190 235 305 355 430 575 645
9 60 35 60 75 110 160 195 255 295 355 480 535
10 70 30 50 65 90 135 165 215 255 305 410 460
11 80 45 55 80 120 145 190 220 265 360 405
12 90 40 50 70 105 130 170 195 235 320 360
13 100 35 45 65 95 115 150 175 215 290 320
14 110 40 60 85 105 140 160 195 260 290
15 120 35 55 80 95 125 145 180 240 270
16 130 50 75 90 115 135 165 220 250
17 140 45 70 80 110 125 150 205 230
18 150 65 75 100 115 140 190 215
19 160 60 70 95 110 130 180 200
20 170 55 70 90 105 125 170 190
21 180 50 65 85 100 120 160 180
22 190 60 80 90 110 150 170
23 200 60 75 90 105 145 160
24 225 65 80 95 125 145
25 250 70 85 115 130
26 275 80 105 115
27 300 70 95 105
Air Temperature'C' 40 45 50
Rating factor(XLPE) 1.00 0.94 0.88
Rating Factor(PVC) 1.00 0.9 0.81
Current rating in ground for XLPE insulated for 1.1 KV Grade Cable (Table - 2)
Nominal Area Aluminium Conductor Copper Conductor
of the Cond Single core Multi Core Single core Multi Core Unity
mm^2 PVC XLPE PVC XLPE PVC XLPE PVC XLPE
10 51 55 46 50 65 71 60 65
16 66 74 60 68 85 95 77 87
25 86 98 76 90 110 125 99 115
35 100 118 92 108 130 150 120 138
50 120 137 110 126 155 175 145 161
70 140 172 135 158 190 220 175 202
95 175 204 165 187 220 260 210 239
120 195 234 185 215 250 301 240 276
150 220 262 210 240 280 336 270 308
185 240 298 235 273 305 381 300 350
240 270 344 275 316 345 441 345 405
300 295 387 305 355 375 496 385 455
400 325 458 335 420 400 586 425 538
500 345 495 425 635
630 390 555 470 710
800 440 625
1000 490 685
Permissible Maxium Short Circuit Current rating for XLPE cables
Conductor Area in sqm Short Circuit Rating for one secound
Duration
Cu A Alu B
16 2570 1730
25 3970 2670
35 5500 3690
50 7800 5220
70 10850 7400
95 14600 9740
120 18400 12200
150 23000 15200
185 28200 18700
240 36400 24200
300 45300 30100
400 60200 39900
500 74800 49800
630 92700 62000
800 - 78800
1000 - 97800
Table -6
Class of Insulation for ( Electric Motor)
Max Operating Temp
Y 90 ' C
A 105' C
E 120 ' C
B 130 ' C
F 155 'C
H 180 ' C
C Above 180'
Lighting fixture : 0% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
Low Residential Area: Design exterior lighting so that all side and building mounted illuminance produce a maximum illiance
value no greater than 0.01 horizontal and vertical foot candles all the side boundry and no greater than 0.01 horizontal foot
candles 10 feet beyound the side boundary
Lighting fixture : 2% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
Medimum Residential Area : Design exterior lighting so that all side and building mounted illuminance produce a maximum
illiance value no greater than 0.20 horizontal and vertical foot candles all the side boundry and no greater than 0.01 horizontal
foot candles 15 feet beyound the side boundary
Lighting fixture : 5% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
High major city center, entertainment district : Design exterior lighting so that all side and building mounted luminaries
produce a maximum illiance value no greater than 0.60 horizontal and vertical foot candles all the side boundry and no greater
than 0.01 horizontal foot candles 15 feet beyound the side boundary
Lighting fixture : 10% of the total initial fixtures are emitted at an angle of 90 ' degree or higher from nidir
The present pratice in CPwd While designing indoor lighting is to use T5 lamp in rooms and CFL used in Corridor and other
common areas due to keeping good CRI and to maximize usable lumen per watt HPSV lamp metal halide are being used for
outdoor lighting.
The following Technical parameter of T5 , CRI, HPSV , Metal Halide
LED LED T5 LAMP CFL HPSV METAL
WARM COOL LAMP LAMP HALIDE
WHITE WHITE
CRI 80-85 75 85 85 22 60 - 90
95 -
Efficacy in im/w 80 132 90 70 110 65 - 70
Usable im/w 55-65 >100 75-85 50 -60 55 - 65 35 - 40
10K -
life (Hrs) 50K+ 50K+ 30K 8 - 10K 24K 20K
SELECTION OF LAMPS
LAMP TYPE RANGE LUMINOUS FLUX EFFICACY IN Average Life Hr Colour Rendering
(im/w)
CFL 18W-36W 1200 - 2900 60 -80 15000 75-85
FLUT5 28W-54W 2900 - 4850 90 -104 24000 80 - 90
FLUT8 18W - 36W 750 - 3250 50 - 90 20000 80 - 85
FLUUT12 20W-40W 950 - 2450 48-61 12000 50 - 75
HALOGEN 50W 1200 24 2000 75-90
METAL HALIDE 70W - 250W 5300-25000 76-100 12000 70-90
HIGH PRESSURE
SODIUM VAPOUR
70W-1000W 5600-130000 80-130 20000 20-65
LOW PRESSURE
SODIUM VAPOUR
55W - 135W 8100-32000 100 - 230 20000 20 - 65
AC22/DC22 - switching of mixed resistive inductive loads i/c moderate over load.suitable for mixed
resistive loade load device can switch 300% of its rated current under fault conditions.
AC23/DC23 - Switching of highly inductive loads. Device complying with AC23/DC23 are provided mainly as
backup to other means of switching eg. Contacts. In the event of failure of functional devices on
AC23/DC23 type device can safely interrupt a stalled motor current where device are the only means of
controlling individual motors, they should comply with the requirements of appendix A of standard.
Revised Yard stick Type - 1 Type - 2 Type - 3 Type - 4 Type - 5 Type - 6 servent Qtrs
Description Exist Revis Exist Revis Exist Revis Exist Revis Exist Revis Exist Revis Exist Revis
Power Points 15 Amps 6 p 3 2 3 3 3 4 3 5 4 6 7 1
mcb 1 1 1 2 4 5
MCB connected socket
outlet for ac unit/gyser
Ceiling fan fan 2 2 3 3 4 4 5 5 5 6 7 1
Exhaust fan exfan 1 1 1 1 1 1
call bells 1 1 1 1 1 1 1 1 1 2 3
Light/fan/call/5A 17 17 20 20 23 23 24 27 33 38 44 5 5
F.I Fitting exclu tube & 2 2 2 3 3 4 4 5 7 8
Single Phase 1 1 1 1 1 1 1 1 1
3 Phase 1 1 1
TV 1 1 1 1 2 2
Telephone 1 2 2
a) Air termination b) Down Conductors c) joint and Bonds d) Testing Joints e) Earthing termination f) earth electrode
i) Copper Flat strip or Solid 98% conductivity
ii) Copper Clad steel not less tha 30% of conductance of solid copper of the same total cross sectional area
iii) Galvanished steel protected against corrosion by Zinc Coating
iv) Aluminium 99% pure for sufficient
Height spacing
e
width
Staggered
Height = 0.8 times width
Spacing 3.5 to 4 times Height
Height spacing
width
Opposite Side
Height = 0.5 times Width
Spacing = 3.5 to 4 times Height
spacing
Height
width
Central Side
width
100MM
10MM
400 300 350
300MM
GL
300MM
In all Fabrication will be done out of 2mm thick CRCA sheet with double door and in built locking arrangement
All connections incoming and outgoing will be taken out in cabley alloy with suitable rated solid conductor
The feeder pillar will have supplied with suitable pedestal (Ms angle iron frame of MS channel base for generating in RCC and proper
gland at the bottom
The feeder pillar will have one 10 Ampos 3 pin Socket out with 10 Amp switch and one brass holder fitted in metering panel
compartment and directly fed from incoming.
The deep of feeder pillar is 40mm the bus made of hand drawn tinned copper are fitted on insulated DMC support.The size
arrangement decided by NIT Authority
The feeder pillar should be provided with termined blocks for incoming & outgoing cables from MCCB to terminated block wiring will
be done with copper conductor/ suitable cable in coming/outgoing UG cable will be terminated intermind block this will very much
All Dimensions are in mm
AC Calculation