MICROFLAT SERIES

TYPES C...F S...F


M...F T...F
APPLICATION
AUTOMATIC CONTROL SYSTEMS FOR This range of electronic gas burner control systems has
been specifically designed for atmospheric burners for
GAS BURNERS AND GAS BURNING intermittent operation (systems for non-permanent
APPLIANCES WITH OR WITHOUT FAN operation), with or without fan in the combustion circuit.
AND WITH BUILT-IN ANTI-EMISSIONS These controls are provided with both non-volatile lockout
and volatile lockout: in the first case restart from the safety
FILTER shutdown condition can only be accomplished by a manual
reset of the system; in the second case restart from the
safety shutdown condition can only be accomplished by an
interruption of the main power and its subsequent
restoration.
The automatic burner control units of this series are
suitable for:
-combi boilers;
-heating boilers;
-warm air generators;
-radiant heaters;
-water heaters.
Thanks to their design and variety of models, they can also
be used for the automation of ovens, cookers and in gas
firing installations with atmospheric burner in general.

FEATURES
Table 1 shows the main features of this series. Other
important features are:
− EC certification (CE Reg. N°0694BP0669) in
accordance with Gas Appliance Directives 90/396 and
93/68;
− in accordance with EN 298 (European standard for
automatic gas burner control systems and flame
detectors);
− completely solid and high efficient inbuilt ignition device
with built-in E.M. filter;
− possibility of mounting a resistor (0 ÷ 220 ohm) in series
to the valve output, in case the valves operate with
direct current obtained through the rectification of the
supply alternate current by means of one or more
diodes.
This resistor allows to reduce electromagnetic
disturbances generated by diodes switching;
− possibility of mounting a resistor (0 ÷ 470 Kohm) in
series to the lockout signal output, to avoid possible
damages to the control in case the connections of the
reset button and the connections of the lockout signal
are inverted;
− two independent safety contacts in series on the gas
valve output (only for non-volatile lockout types);
− auxiliary contact for low power ignition or main gas
valve control for intermittent pilot systems; this contact
is not isolated from the main supply voltage by
reinforced isolation, therefore the relay contact is not
suitable to supply SELV circuits - Safety Extra Low
Voltage, e.g.24V;
− flame monitoring by the rectification property of the
flame (ionization).

3997_r02 1/13
Table 1 TECHNICAL DATA
Burner Features Supply voltage: 220/240V @ 50/60Hz
On request: 110/120V @ 50/60Hz
Operatine temperature range: -20°C ÷ +60°C
Ambient humidity: 95% MAX @ 40°C
Protection degree: IP 00

Classification code according to EN 298 


Times:
- prepurge or waiting time (TW):
1.5 … 40 s

Safety thermostat provision 

According to EN 298 :2003 


- safety time (TS):

According to EN 298 :1993


3 ... 120 s
Atmospheric without fan

Connector type molex 


Atmospheric with fan - response time on running flame failure (TR):
<1s
Non-volatile lockout

Auxiliary contact 
Volatile lockout

Monoelectrode
The times given on the burner control label correspond to the
Single flame

values guaranteed. The actual values slightly differ from the values
Dual flame

given, pre-purge and waiting time is in fact longer and safety time
shorter than their nominal values.
Power consumption, at starting up:
CM11F * * * * * * AMCLXN types without burner 10VA
CM12F * * * * * * ATCLXN types with burner 12VA
CM31F * * * * * * FMCLXN
CM32F * * * * * * FTCLXN Power consumption, running:
SM11F * * * * * * * ATCLXN types without burner 7VA
SM31F * * * * * * * FTCLXN types with burner 9VA
MM11F * * * * * * * AMCLXN
MM12F * * * * * * * ATCLXN Contact rating:
MM51F * * * * * * * * ATCLXN - Thermostat: 4A cosϕ ≥ 0.4
MM31F * * * * * * * FMCLXN
MM32F * * * * * * * FTCLXN
- VG1: 0.5A cosϕ ≥ 0.4
TM11F * * * * * * AMCLXN - VG2: 0.5A cosϕ ≥ 0.4
TM12F * * * * * * * ATCLXN - Fan motor: 1A cosϕ ≥ 0.4
TM31F * * * * * * FMCLXN
- Lock-out signalling: 1A cosϕ = 1
TM32F * * * * * * * FTCLXN
CE11F * * * * * AMCVXN - Auxiliary contact: 0.5A cosϕ ≥ 0.4
CE12F * * * * * ATCVXN
CE31F * * * * * FMCVXN Max. length of the cables of external components:
CE32F * * * * * FTCVXN 1m
SE11F * * * * * * ATCVXN
SE31F * * * * * * FTCVXN Internal fuse rating: 4A fast
ME11F * * * * * * AMCVXN External fuse rating: 3.15A fast
ME12F * * * * * * ATCVXN
ME51F * * * * * * * ATCVXN Flame control:
ME31F * * * * * * FMCVXN
ME32F * * * * * * FTCVXN The ionization flame detection device makes use of the
TE11F * * * * * AMCVXN rectification property of the flame.
TE12F * * * * * * ATCVXN
The ionization flame detector device is not a safe to touch
output (no provision with protective impedances).
NOTE
- Minimum ionization current: 0.5µA
 This contact is not isolated from the main supply voltage by on request:
1.2µA / 2.5µA
reinforced isolation, therefore the relay contact is not suitable to - Max ionization current @ 230V: 8.5µA DC
supply SELV circuits – Safety Extra Low Voltage. - Recommended ionization current: 3÷5 times the
 Safety thermostat opening causes cycle repetition and
volatile/non-volatile lockout. minimum value
 Standard connectors are Stelvio-Stocko models, as shown in - Max. length of the cable: 1m
Fig.2. - Minimum insulation resistance of the ≥ 50 MΩ
 Flame failure durino TS causes spark restoration. cable and the flame
.
 Device is compliant only if the note “EN 298:2003 compliant” detector device to earth:
and the option “#” are report on the label. ≤ 1 nF
- Max. parasitic capacitance of the
detection probe:
- Max. short circuit current: < 200µA AC

2/13 3997_r02
Ignitor: RESET BUTTON DRILLING PLAN

- Peak ignition voltage: 15KV con carico di


30pF
on request: 12/18 KV
- Peak current: 800 mA
- Spark repetition rate: 25 Hz
on request: 1 ... 8/10/12/16 Hz
- Max. length of the cable: 2m
- Spark gap recommended: 2-4 mm
- Consumption: 2.5 VA
- Spark energy: 20 mJ
NEUTRAL
Weight: 170 g RESET

LOCK-OUT SIG.

CONSTRUCTION
The enclosure made of plastic material and the varnishing
of the circuit board protect the control from mechanical
damages, dust and dirt from the conditions of installation.
Through the use of a board assembled with surface FEMALE CONNECTOR TERMINALS
mounted components and of a new patented circuit
generating the ignition spark which limits the EM to a
minimum, it has been possible to reduce the printed circuit Fig. 2
board dimensions and to realize even the most complex
executions with extremely compact dimensions.
A varistor protects the control from voltage transient on the
main supply, caused for example by discharges such as
thunderbolds. An internal fuse protects the relays of the
FEMALE CONNECTOR TERMINALS
control box in case of short circuits on the outputs (valves,
fan and lockout signal). In any case the control must be
Fig. 3
protected with a fast blow external fuse suitable to the load
connected and never exceeding 3.15 A.
CONNECTION
The use of non-reversible connectors with a different
OVERALL DIMENSIONS
number of poles makes the connection easy and reliable.
The control units of the MICROFLAT series can be
One-way fast-on connectors of different sizes for ignition
supplied in different executions but with the same
and detection electrodes permit their easy installation and
enclosure. The following figure (Fig. 1) shows the overall
replacement.
dimensions of the controls.
The dual output ignition device allows spark generation on
one point (3a), two points (3b) or between two electrodes
isolated from the metal frame of the burner (3c), see Fig.4.
The configuration (3c) assures a limited EM emission.

CLIP TO
EXTRACT
THE INTERNAL
FUSE

Fig. 4
Fig. 1
Provisions such as strain relieves, sufficient earth terminals
POSSIBLE FIXING and neutral terminals should be present in the appliance or
in external connection boxes. With all types it is possible to
top: self-tapping screw UNI 6951AB 2,9x22 execute the connection with a J3 connector as shown in
M3x22 screw UNI6107 Fig.5.
bottom: Screwplast self-forming screw ISO0003 F 3.5x13 Types TM..F are prearranged for the connection of a safety
Screwplast self-forming screw ISO0003 F 3.9x13 thermostat ST which stops the supply to the gas valve VG1
and causes a safety shutdown after a delay which is the
sum of waiting (pre-purge) and safety times.
ACCESSORI
The control units are usually supplied with a kit of female
connectors and/or a reset button (see Fig.2 and Fig.3).
Do not fit terminals and female connectors of different
types.

3997_r02 3/13
Then make sure that:
− if the starting attempt occurs without gas supply the
control performs a non-volatile lockout after TS;
− when stopping the gas flow while the control is in
running state the supply to the gas valve is interrupted
within 1 second, and after a recycling the control
proceeds to a non-volatile lockout;
− operating times and sequence are suitable;
(4a) W ith safety therm ostat (4b) W ithout safety therm ostat − the level of the flame signal is sufficient, see Fig.6 for
Fig. 5 the measuring test;
− the ignition probe(s) is (are) adjusted in the most
DIRECTIONS FOR USE stable way for a spark gap between 2-4 mm;
− For technical and safety reasons a regulation shutdown − the intervention of limiters or safety devices causes a
must occur every 24 hours (systems for non-permanent safety shutdown according to the application.
operation);
− automatic controls are safety devices and must not be
opened. The manufacturer’s responsibility and
guarantee are invalidated if the control is opened;
− the control must be connected and disconnected only
after switching off the main power;
− the control can be mounted in any position;
− avoid exposing the control unit to dripping water;
− ventilation and the lowest temperature ensures the
longest life of the control;
− make sure that the type (code and times) you are using
is correct before installing or replacing the control; Fig. 6
− the gas appliance on which the control is installed must
provide adequate protection against the risk of electrical
OPERATION
shock (at least IP20).
At every start the control unit proceeds to a self-checking of
its own components. During the waiting or prepurge time
ELECTRICAL INSTALLATION
(TW) the operation of the flame signal amplifier is checked:
− The applicable national regulation and the European the internal circuit makes a test of the flame signal amplifier
standards (e.g. EN 60335-1/prEN 50165) regarding circuit. A parasitic flame signal or a fault in the amplifier
electrical safety must be respected; prevent the control from starting.
− live and neutral should be connected correctly, a In the types with fan control, before the elapsing of the
mistake could cause a dangerous situation, i.e. the prepurge time, the air pressure switch contacts are
valves would still be live with the thermostats and limits checked to prove their "no air flow" state.
switched off. If live-neutral polarity is not respected the Only if the test is positive the fan is started and with the air
control performs a non-volatile lockout at the end of the pressure switch in "air flow" state the prepurge time begins.
safety time at starting up; At the end of the waiting or prepurge time the VG1 gas
− before starting the system check the cables carefully. valve is energized and the ignition device is operated. In
Wrong connections can damage the control and this way the safety time (TS) begins. If the presence of
compromise the safety; flame is detected during the safety time the ignition device
− the earth terminal of the control, the metal frame of the is inhibited and, in the suitable models, the main valve
burner and the earth on the main supply must be well (VG2) is supplied or the independent auxiliary contact will
connected; switch from off to flame detected position.
− avoid putting the detection cable close to power or On the contrary, if the control detect no presence of flame
ignition cables; by the end of TS, it proceeds to non-volatile lockout, the
− use a heat resistant cable for the detection probe, well VG1 gas valve and the ignition device are switched off
insulated to the ground and protected from possible while the lockout signal output is supplied.
moisture (or water in general); Flame failure during the safety time causes the ignition
− use an ignition cable as short and straight as possible device to be activated within one second.
and keep it far from other conductors to reduce the The attached diagrams are useful to understand how each
emission of interference (max.length <2m and control operates.
insulation voltage >25KV).
In case of live-neutral network with unearthed neutral or NON-VOLATILE LOCKOUT - RESET OF THE CONTROL
live-live network (with centre of the star not earthed) the When a control has gone to non-volatile lockout, a ten-
control can operate correctly by means of a built-in resistor. second delay should be allowed before attempting to reset
In case of "partial" short circuits or bad insulation between the control unit; if this time is not observed the control may
live and earth the voltage on the ionization probe can be not reset correctly.
reduced until it causes the lockout of the control, because
of the impossibility of detecting the flame signal. VOLATILE LOCKOUT – RESET OF THE CONTROL
In the presence of this kind of network it is advisable to use The restart from the safety shut-down condition can only be
our step-up transformer type AR1. accomplished by an interruption of the main power and it
subsequent restoration.
CHECKING AT START This types of burner control units do not contain an
Always check the control before the first start and also after independent manual reset function. The application of
any substitutions or a long period of non-operation of the these types of controls is therefore restricted to only those
system. Before any ignition attempt make sure that the appliances where resetting by switching off the heat
combustion chamber is free from gas. demand is allowed by European standards.

4/13 3997_r02
In general, resetting of the appliance must occur in sight
and in the near vicinity of the appliance. Resetting must
also occur by means of a conscious manual action and not
by means of automatic device like thermostats or timers.
Please note that it is allowed to combine the reset button
together with the main switch on the appliance. In this case
the alarm light will have to be installed too.

CONTROLS DENOMINATION
Type Options
(1) (2) (3) (4) F (5) (6) (7) (8) (9) (10) (11) (12) (13)

Types description
(1) Installations
C Wall boilers
S General uses
M Monoelectrode
T With safety thermostat
(2) Reset
M Manual
E Electrical
(3) Type of burner
1 Without fan
3 With fan
5 Special types
(4) Gas valves
1 Single flame
2 Dual flame

Options description
(5) Compliance
According to EN 298:1993
# According to EN 298:2003
(6) Kind of connectors
Stocco-Stelvio connectors
X Molex connectors
(7) Internal fuse
Not-accessible internal fuse
F Accessible internal fuse
(8) Resistor in series with VG2
Not present
W Present
(9) Resistor in series with VG1
Not present
V Present
(10) Protection against the inversion of the connections of the lockout signal and the connections of the reset button
Not present
R Present
(11) Protection against air pressure switch reversal connection
Not present
P Present
(12) Ignition coltage
15 Kv (standard)
H 18 kV
L 12 kV
(13) Spark repetition rate
25 Hz (standard)
nn Number represents the discharge frequency

3997_r02 5/13
CONNECTION DIAGRAM
TYPES WITH MANUAL RESET WITHOUT FAN

TYPE CM11F TYPE SM11F

TYPE MM11F TYPE TM11F

TYPE CM12F TYPE MM51F

TYPE MM12F TYPE TM12F

THERMOSTAT FUSE BURNER LOCK-OUT FIRST GAS SECOND GAS SAFETY RESET MAIN
SIGNAL VALVE VALVE THERMOSTAT SWITCH

NOTA: the limit thermostat has to be wired in series to the live.

6/13 3997_r02
TYPES WITH MANUAL RESET AND FAN

TYPE CM31F TYPE SM31F

TYPE MM31F TYPE TM31F

TYPE CM32F TYPE MM32F

TYPE TM32F

THERMOSTAT FAN AIR PRESSURE FUSE BURNER LOCK-OUT FIRST GAS SECOND GAS SAFETY RESET MAIN
SIGNAL VALVE VALVE THERMOSTAT SWITCH

NOTA: the limit thermostat has to be wired in series to the live.

3997_r02 7/13
TYPES WITH ELECTRICAL RESET WITHOUT FAN

TYPE CE11F TYPE SE11F

TYPE ME11F TYPE TE11F

TYPE CE12F TYPE ME51F

TYPE ME12F TYPE TE12F

THERMOSTAT FUSE BURNER LOCK-OUT FIRST GAS SECOND GAS SAFETY MAIN
SIGNAL VALVE VALVE THERMOSTAT SWITCH

NOTA: the limit thermostat has to be wired in series to the live.

8/13 3997_r02
TYPES WITH ELECTRICAL RESET AND FAN

TYPE CE31F TYPE SE31F

TYPE ME31F TYPE TE31F

TYPE CE32F TYPE ME32F

TYPE TE32F

THERMOSTAT FAN AIR PRESSURE FUSE BURNER LOCK-OUT FIRST GAS SECOND GAS SAFETY MAIN
SIGNAL VALVE VALVE THERMOSTAT SWITCH

NOTA: the limit thermostat has to be wired in series to the live.

3997_r02 9/13
OPERATING CYCLES
TYPES WITH MANUAL RESET WITHOUT FAN

10/13 3997_r02
TYPES WITH MANUAL RESET AND FAN

3997_r02 11/13
TYPES WITH ELECTRICAL RESET WITHOUT FAN

12/13 3997_r02
TYPES WITH ELECTRICAL RESET AND FAN

TYPE CE31F - ME31F TYPE TE31F

TYPE CE32F - ME32F TYPE TE32F

TYPE SE31F

THERMOSTAT FAN AIR PRESSURE IGNITION FLAME LOCK-OUT FIST GAS SECOND GAS AUXILIARY SAFETY
SWITCH SIGNAL SIGNAL VALVE VALVE CONTACT THERMOSTAT

ATTENTION ->Company Brahma S.p.A. declines any responsibility for any damage resulting from the Customer’s interfering with the device.

BRAHMA S.p.A.
Via del Pontiere, 31
37045 Legnago (VR)
Tel. +39 0442 635211 - Telefax +39 0442 25683 07/04/04 Subject to amendments without notice
http://www.brahma.it
E-mail : [email protected]

3997_r02 13/13

You might also like