Grounding Considerations For Large kVA Pad-Mount Transformers
Grounding Considerations For Large kVA Pad-Mount Transformers
Grounding Considerations For Large kVA Pad-Mount Transformers
Pad-Mount Transformers
Ruwan Weeransundara P.E.
Member, IEEE
ESC Engineering Senior Planning Engineer
3540 JFK Parkway, Fort Collins, Colorado 80525, USA
Phone 970-212-1525
[email protected]
Abstract - Utilities in the United States and Canada have done Although not common for utility application, grounded-wye primary
extensive analysis of the ground grid design for substations in order to with impedance grounded secondary are used for industrial
limit step and touch potentials to safe values; however, few have applications to limit phase-to-ground fault currents. The primary Ho
analyzed the potential hazard and designed grounding systems for and secondary Xo are separated when the secondary Xo bushing is
pad-mount transformers. Since the kVA size and voltage ratings of grounded through impedance.
pad-mounts have increased and the exterior of these facilities are
accessible not only to qualified electric utility workers but also the
general public, there is a need to analyze and properly design and III. ASSUMPTIONS
construct grounding systems which will render these facilities safe for The following assumptions were used to determine the adequacy of
switching and fault conditions. This paper analyzes and develops the various grounding systems for different kVA size and voltage rated
design for several different pad-mount transformer voltages and kVA pad-mount transformers. These assumptions are conservative for
sizes through 5,000kVA. most conditions but should be checked for particular installations to
insure they are applicable and provide safe results.
I. INTRODUCTION Pad-mount transformers rated 750kVA and larger were assumed
The primary purpose of grounding is to limit voltages across to have 5.75 percent impedance.
insulated or non-insulated portions of equipment within a person’s Top soil resistivity of 2,000 m was used. This is typical for
reaching capabilities and the potential differences between different sand, gravel and dry soil.
points on the ground within one step. These voltages are known as Lower soil resistivity of 1,000 m was used.
“touch” and “step potentials,” respectively. The evaluation of these
voltages is required not only during normal operating conditions, but The weight of the person is 50 kilograms (110 lbs.)
also during abnormal situations such as lightning strikes, faults and Thickness of the surface material is 0.5 ft.
switching surges. Fault duration is 0.5 seconds
A large Ground Potential Rise (GPR), with respect to remote earth The maximum secondary line-to-ground fault currents for different
potential, can occur during abnormal conditions if the fault current (I) kVA size and voltage transformers were assumed to have nearly an
and ground (Rg) are high (GPR = I x Rg). Voltage potential rises infinite primary source:
during fault conditions can be significant even when established
grounding practices are used. 5,000kVA with 12.47/7.2kV secondary, available fault current
4,000 amps.
Pad-mount transformers are being used in ever increasing kVA
sizes and with higher primary and secondary voltages. Pad-mount 2,500kVA with 12.47/7.2kV secondary, available fault current
transformers are now available in sizes up through 5,000kVA. 2,000 amps.
Pad-mount transformers are frequently used in lieu of smaller kVA 5,000kVA with 4.16/2.4kV secondary, available fault current
size traditional substations when the primary voltage is 34.5kV and 12,000 amps.
lower. Secondary voltages up to 24.9/14.4kV are available. These
2,500kVA with 4.16/2.4kV secondary, available fault current
trends necessitate a review of established grounding practices for
6,000 amps.
pad-mount transformer installations to ensure that the grounding
system will limit step voltage and touch potential to safe levels. The current distribution factor equals 1.0 (i.e., all fault current goes
Limiting the maximum step potential is especially important for these into the grid and none returns through the source distribution circuit).
transformer installations because they are often placed in locations
where the general public can be exposed to danger. The touch and step potential values calculated from the equations
specified in IEEE Guide for Safety in AC Substations Grounding
Std. 80-2000 are the maximum values which should be allowed for
II. PAD-MOUNT TRANSFORMER CONNECTIONS pad-mount transformer installations.
The large majority of three-phase pad-mount transformers are IEEE Std 80 provides equations for the allowable touch and step
connected grounded-wye on the secondary. Secondary voltages potentials for both 50 and 70 kilograms persons. The weight of 50 kg
include 208/120 volts, 480/277 volts, and common distribution was used because the potential limits for the lighter person are more
primary voltages (4.16/2.4, 12.47/7.2, 13.2/7.6, 24.9/14.4 kV). Delta restrictive.
connected primary connections are not common due to the Two types of ground grid were initially investigated: the two
susceptibility of this connection to ferro-resonance over voltages. ground rod schemes required by Rural Utilities Services (RUS) for all
three-phase underground pad-mounted equipment applications in their The actual step and touch voltages, metal to touch and step to step
unit UM 48-2 and the Canadian Standards Association Rule 36-302 in voltages, should be less than the respective maximum allowable
the Electrical Safety Authority, which requires a ground rod on each voltage limits to ensure safety.
of the four corners around the pad-mount transformer. These
grounding schemes are shown in Figures 2 and 3, respectively. It should be noted that the above calculations assume 0.5 seconds
fault duration. With a square root of ts in the denominator of equations
In addition, a suggested sample design (Figure 4) for a 5000kVA, (6) and (7) above, the allowable step and touch voltages will both be
34.5/4.16kV pad-mount transformer is included. The potential decreased with an increase in fault clearing time. Increasing the fault
contour for the grounding arrangement is shown in Graph 4. duration time from 0.5 seconds to 2.0 seconds will reduce the above
values by one-half.
IV. CALCULATIONS Although not common in the electric utility industry, some
industrial electrical users separate the primary H0 and secondary X0
The ground potential rise (GPR), maximum allowable touch connection points to obtain an impedance grounded secondary
( and step ( potential calculations were performed using system. When this is done, the maximum voltages during fault
the equations specified in IEEE Std 80-2000. The grounding analysis conditions will not be limited by the secondary windings and the
was performed for different kVA sizes and voltage ratings of pad- touch potentials as well as the step potentials will exceed those which
mount transformers with both the RUS and Canadian Standards. The would occur for a grounded wye to grounded wye connection with the
EDSA Advanced Ground Mat Program V4.70.00 was used to perform H0 and X0 points bonded.
sample calculations on pad-mount transformers, ranging from
500kVA to 5000kVA. These calculations were compared with the
maximum allowable values calculated from the equations specified in
IEEE Standard 80-2000.
Step and Touch Voltage Criteria
The safety of a person depends on preventing the critical amount of
shock energy from being absorbed before the fault is cleared and the
system is de-energized. The maximum driving voltage of any
accidental circuit should not exceed the limits defined as follows.
The limit for Step Voltage is: 1
Figure 1 Human Tolerances Model
2 (1)
For body weight of 50kg:
.
1000 6 1 (2)
V. RESULTS
Table 1 shows the comparison of maximum surface voltage on both
RUS Std and Canadian Standard for different sizes and voltages of pad mount
transformers. The maximum allowable touch and step voltages are 656.2V and
2312.6V respectively.
Table 1
RUS Standard Canadian Standard
Maximum
Transformer
Size Line-Ground Maximum Maximum
Secondary Meets the Meets the
(KVA) Fault Surface Surface
Voltage (kV) Safety Safety
Current (A) Potential Potential
Requirement Requirement
(V) (V)
VII. REFERENCES
[1] IEEE for Safety in AC Substation Grounding IEEE
Standard 80-2000.
[2] Canadian Electrical Safety Code, 2009, by Electrical Safety
Authority.
[3] RUS Standard 1728F-806, June 2000, Specifications and
Drawings for Underground Electric Distribution.
[4] IEEE Recommended Practice for Grounding of Industrial &
Commercial Power Systems, ANSI/IEEE Std 142-1982