480W Single Output Industrial DIN RAIL With PFC Function: Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

480W Single Output Industrial DIN RAIL with PFC Function DRP-480 series

■ Features :
•Built-in passive PFC function compliance to EN61000-3-2
•High efficiency 89% and low dissipation
•Protections: Short circuit / Overload / Over voltage / Over temperature
•Cooling by free air convection
•Built-in constant current limiting circuit
•Can be installed on DIN rail TS-35/7.5 or 15
•UL 508(industrial control equipment)approved
•EN61000-6-2(EN50082-2) industrial immunity level
•100% full load burn-in test
•3 years warranty
..

SPECIFICATION
MODEL DRP-480-24 DRP-480-48
DC VOLTAGE 24V 48V
RATED CURRENT 20A 10A
CURRENT RANGE 0 ~ 20A 0 ~ 10A
RATED POWER 480W 480W
RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p
OUTPUT VOLTAGE ADJ. RANGE 24 ~ 28V 48 ~ 53V
VOLTAGE TOLERANCE Note.3 ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±1.0%
SETUP, RISE TIME 1200ms, 40ms/230VAC at full load
HOLD UP TIME (Typ.) 16ms/230VAC at full load
VOLTAGE RANGE 180 ~ 264VAC 250 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.) ≧0.7
INPUT EFFICIENCY (Typ.) 89%
AC CURRENT (Typ.) 4A/230VAC
INRUSH CURRENT (Typ.) COLD START 40A/230VAC
LEAKAGE CURRENT <3.5mA / 240VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
30 ~ 36V 54 ~ 60V
PROTECTION OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
100℃±5℃ (TSW : detect on heatsink of power switch)
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP. -20 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS UL508, UL60950-1, TUV EN60950-1 approved
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25J/ 70% RH
(Note 4) EMC EMISSION Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF 180.9Khrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 227*125.2*100mm (W*H*D)
PACKING 2.4Kg; 6pcs/15Kg/1.75CUFT
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.

File Name:DRP-480-SPEC 2011-06-17


480W Single Output Industrial DIN RAIL with PFC Function DRP-480 series
Mechanical Specification Case No.930 Unit:mm

100 227

125.2
TB1 TB2
3 2 1 LED 4 3 2 1

+V ADJ.
Terminal Pin No. Assignment (TB1)
Pin No. Assignment
1 AC/L(DC+)
2 AC/N(DC-)
35
3 FG
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1,2 DC OUTPUT +V
3,4 DC OUTPUT -V

Block Diagram fosc : 70KHz

EMI PASSIVE RECTIFIERS POWER RECTIFIERS +V


I/P FILTER PFC & SWITCHING &
-V
FILTER FILTER

DETECTION
CIRCUIT
FG
CURRENT
LIMIT
O.L.P. PWM
CONTROL
O.T.P. O.V.P.

Derating Curve Output Derating VS Input Voltage

100
100
90
80
80

60 70
LOAD (%)

60
LOAD (%)

40
50
20
40

-20 0 10 20 30 40 50 60 70 (VERTICAL) 180 190 200 264

AMBIENT TEMPERATURE (℃) INPUT VOLTAGE (V) 60Hz

File Name:DRP-480-SPEC 2011-06-17