GENERAL DESCRIPTION
The DAT 3014 device is able to acquire up to 4 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol on the RS-485 network
(RS-232 interface is available).
It is possible to connect RTD , Potentiometers or Resistance signals.
By means of a 16 bit converter, the device guarantee a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the device even in the heavy
environmental conditions.
DAT 3014 is in compliance with the Directive 2004/108/EC on the electromagnetic compatibility.
The device is housed in a rough self-extinguishing plastic container which, thanks to its thin profile of 17.5mm only, allows a high density mounting on EN-50022
standard DIN rail.
COMMUNICATION PROTOCOLS
The DAT3014 is designed to work with the MODBUS RTU/ASCII protocol: standard protocol in field-bus; allows to directly interface DAT3000 series devices to
the larger part of PLCs and SCADA applications available on the market.
For the protocol instructions, see the relative User Guide.
USER INSTRUCTIONS
Before to install the device, please read the “Installation Instruction” section.
If the module configuration is unknown, it can be hardly to establish a communication with them; connecting the INIT terminal to the GND terminal (ground), at
the next power-up the device will be auto-configured in the default settings (see Operating User Guide).
Connect power supply, serial bus and analog inputs as shown in the “Wiring” section.
The “PWR” LED state depending to the working condition of the device: see the "Light Signalling" section to verify the device working state.
To perform configuration and calibration operations, read the instructions in the Operating User Guide.
To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.
Make sure that sufficient air flow is provided for the device avoiding to place 3 6 9 12
raceways or other objects which could obstruct the ventilation slits. Moreover
it is suggested to avoid that devices are mounted above appliances
generating heat; their ideal place should be in the lower part of the panel. RTD/RES 3 WIRES
Install the device in a place without vibrations.
INPUT 0 INPUT 1 INPUT 2 INPUT 3
Moreover it is suggested to avoid routing conductors near power signal 1 4 7 10
cables (motors, induction ovens, inverters etc...) and to use shielded cable
for connecting signals.
2 5 8 11
3 6 9 12
CABLING
SHIELD POTENTIOMETER
POWER INPUT 0 INPUT 1 INPUT 2 INPUT 3
D+ SUPPLY
10÷30 V 1 4 7 10
D-
RS -485 V- V+
2 5 8 11
INIT
3 6 9 12
B
C
D
J
I
A
A (-) RS-485 E TX
D- RX RS-232
network
1
2
3
7
8
9
4
5
6
RX
1
B (+) F
0
1
2
1
TX
D+
C
GND
C
GND
GND
INPUT 0
INPUT 1 INIT WIRING
POWER SUPPLY WIRING
INPUT 2
INPUT 3 INIT
+V D
J +
10÷30 Vdc ON: short-circuit
- to GND
LIGHT SIGNALLING C
I
-V GND
LED COLOUR STATE DESCRIPTION
PWR GREEN ON Device powered
OFF Device not powered / Wrong RS-485 cabling.
ISOLATION STRUCTURE
Communication in progress (blink frequency
FAST BLINK depends to baud-rate)
1 second BLINK Watch-Dog Alarm condition
ANALOG RS485
INPUTS (RS232)
MECHANICAL DIMENSIONS (mm)
POWER SUPPLY
HOW TO ORDER
100
In the order phase, it is mandatory to specify the interface type (RS485 or RS232) .
DAT3014 can be supplied with the configuration specified by the customer.
Please refer to the “Technical Specification” section for the output type available.
ORDER CODE:
DAT 3014 / 485 / Pt100