Tank Padding Summary Sheet

Data Entry

Stored Material Amines Tank T-C-2


Flash Point F 55 MAWP inWC 15.5
Boiling Point F 239 Max Vacuum oz/in2 5
Latent Heat vapbtu/lb 150.5 Diameter ft 9.969
mole wt 101 Max fill ft 17.5

Inflows
Max Head Flow, GPM
Tag Service Line F-1- Value Units Note 1
P-C-127 T-C-6 63 PSIG 300
P-C-34 T-C-29/30 82 PSIG 100
P-C-92 T-C-31 112 PSIG 260
P-C-90A F-C-3 BTMS 69 PSIG 600
P-C-47 F-C-3 OH 64 PSIG 90

Total 1350
or Sonic Flow in Pipe
or Pipe Flow at Maximum DP 112 psi 1000
or Other (Attach Method)
Use for Relief 1000
Normal Maximum 250

Outflows, Note 1
Tag
P-C-52 gpm 130
gpm
gpm
Total 130

Notes:
1) Pumps at zero head flowrate, CVs at max trim size
Tank Padding Summary Sheet
Design Sheet

Stored Material Amines Tank T-C-2


Flash Point F 55 MAWP inWC 15.5
Boiling Point F 239 Max Vacuum oz/in2 5
Latent Heat vap btu/lb 150.5 Diameter ft 9.969
mole wt 101 Max fill ft 17.5
Max fill gal 10217.2
Inflows, gpm Wetted Area ft2 548.1
Normal 250
Relief 2137 Outflows, gpm 130

Breathing, Note 1 Fire


Out gpm 30.7 Conductivity BTU/hr-ft2 12907.8
In gpm 30.7 Required gpm 47652.0

Vent Valve set at 4" WC


Required gpm 280.7 Normal max inflow + out breathing
selected gpm 593 from table 3

Nitrogen Valve set at 2" WC


Required gpm 753.7 sum of outflows + in breathing + vent valve
selected gpm 1756 from table 2

Conservation Vent
Pressure side set at 8 in WC, Rated at 12 inWC
Required gpm 3,924 Relief inflows + out breathing + selected N2 valve
selected gpm 26,803 each from table 4; total number 2 Total 53,606
Vacuum Side set a 1/2 oz Vac, rated at 2 oz Vac.
Required gpm 754 sum of outflows + in Breathing + selected vent valve
selected gpm 6,732 each from table 4; total number 2 Total 13,464

Emergency Relief, Note 2


Set at in WC, Rated at inWC
Required gpm 0 Required Fire - Excess Conservation Vent
selected gpm 0

Selected Units Tag Manufacturer Model Trim, in Spring


N2 Pressure Reducer
Nitrogen Valve PCV-C509 Fisher 201P2 1 3/16 Brown
Vent Back Pressure PCV-C502 Fisher Y696 1 Red
Conservation Vent 3 PSV-C552 Shand & Jurs 94020 6
Emergency Vent Not Required

Notes:
1) For Tanks larger than 840,000 gal see API-2000 for breathing requirements.
2) Fire hatch is not required if: cone roof tank with weak roof seam or Conservation Vent has capacity.
3)Two required
Tank Padding Summary Sheet

Stored Material Amines Tank T-C-2


Flash Point F 55 MAWP inWC 15.5
Boiling Point F 239 Max Vacuum oz/in2 5
Latent Heat vap btu/lb 150.5 Diameter ft 9.969
mole wt 101 Max fill ft 17.5
Max fill gal 10217.2
Wetted Area ft2 548.1

Inflows, gpm 1000 Outflows, gpm 130

Breathing, Note 1 Fire


Out gpm 229.3 Conductivity BTU/hr-ft2 12907.8 MSW Memo
In gpm 229.3 Required gpm 47652.0 21493.76

Nitrogen Valve set at 2" WC


Required gpm 359.3 sum of outflows + in breathing
selected gpm from table 2

Vent Valve set at 4" WC


Required gpm 1229.3 sum of inflows + out breathing
selected gpm from table 3

Conservation Vent
Pressure side set at 8" WC, rate at MAWP
Required gpm 359.3 sum of inflows + out breathing + selected N2 valve
selected gpm from table 4
Vacuum Side set a 1/2 oz Vac, rate at max vacuum
Required gpm 1229.3 sum of outflows + in Breathing + selected vent valve
selected gpm from table 4

Fire Hatch, Note 2


Required gpm 47652.0
selected gpm

Selected Units Tag Manufacturer Model Trim Spring


N2 Pressure Rducer
Vent Back Pressure
Conservation Vent
Fire Hatch

Notes:
1) For Tanks larger than 840,000 gal see API-2000 for breathing requirements.
2) Fire hatch is not required if: cone roof tank with weak roof seam or Conservation Vent has capacity.
Attachment 2

Tank Padding Summary Sheet


Input Form

Stored Material Tank


Flash PoiF MAWP inWC
Boiling PF Max Vacuum oz/in2
Latent Hebtu/lb Diameter ft
mole wt Max fill ft

Inflows
Max Head Flow, GPM
Tag Service Line F-1- Value Units Note 1

Total 0
or Sonic Flow in Pipe 0
or Pipe Flow at Maximum DP psi
or Other (Attach Method) 0
USE 1E+10

Outflows, Note 1
Tag
gpm
gpm
gpm
Total 0

Notes:
1) Pumps at zero head flowrate, CVs at max trim size
Conversions

bbl scfh gal gpm gpm/1000 ft2 btu/hr


100 100 4,200 12 2.97 2800 14089282.61
20,000 20,000 840,000 2,493 2.97
1000 9949623.383
100 60 4,200 7 1.78
20,000 12,000 840,000 1,496 1.78

Page 5
Conversions

btu/hr-ft2
5031.8866455

9949.6233831

Page 6