Zapi ACE2 User Manual
Zapi ACE2 User Manual
Zapi ACE2 User Manual
EQUIPMENTS CONSTRUCTION
Via Parma, 59 – 42028 – POVIGLIO (RE) – ITALY
Tel +39 0522 960050 (r.a.) – Fax +39 0522 960259
e-mail: [email protected] – web: www.zapispa.it
EN
User Manual
ACE2
INVERTER
The contents of this publication is a ZAPI S.p.A. property; all related authorizations are covered
by Copyright. Any partial or total reproduction is prohibited.
Under no circumstances will Zapi S.p.A. be held responsible to third parties for damage caused
by the improper use of the present publication and of the device/devices described in it.
Zapi spa reserves the right to make changes or improvements to its products at any time and
without notice.
The present publication reflects the characteristics of the product described at the moment of
distribution. The publication therefore does not reflect any changes in the characteristics of the
product as a result of updating.
NOTES LEGEND
APPROVAL SIGNS
PROJECT MANAGER FG
TECHNICAL ELECTRONIC
PP
MANAGER VISA
2) SenseCoils version: using special auxiliary windings inside the motor instead
of an encoder is realised the motor speed and torque control.
3.1 Microswitches
- The microswitches must have a contact resistance lower than 0.1 Ω and a
leakage current lower than 100 µA.
- When full load connected, the voltage drop between the key switch contacts
must be lower than 0.1 V.
- The microswitches send a voltage signal to the microprocessor when a
function request (for ex.: running request) is made.
The Procedure for automatic potentiometer signal acquisition is carried out using
the Console. This enables adjustment of the minimum and maximum useful
signal level (PROGRAM VACC function), in either direction. This function is
unique when it is necessary to compensate for asymmetry with the mechanical
The two graphs show the output voltage from a non-calibrated potentiometer with
respect to the mechanical “zero” of the control lever. MI and MA indicate the point
where the direction switches close. 0 represents the mechanical zero of the
rotation.
The Left Hand graph shows the relationship of the motor voltage without signal
acquisition being made. The Right Hand Graph shows the same relationship after
signal acquisition of the potentiometer.
2) Connections A22 (PTHERM) and A23 (NTHERM) are used for a motor
thermal sensor. It can be digital (on/off sensor, normally closed) or analog.
See also chapter 8.4 for more explanation.
4 Note: The encoder resolution and the motor poles pair (the controller can
handle), is specified in the home page display of the handset showing following
headline:
AE2T2B ZP1.13
That means:
AE2T= ACE-2 traction controller
(AE2P= ACE-2 pump controller)
2 = motor’s poles pair number
B = 64 pulses/rev encoder
The encoder resolution is given by the last letter in the following list:
A = 32 pulses/rev
B = 64 pulses/rev
C = 80 pulses/rev
D = 128 pulses/rev
U Before doing any operation, ensure that the battery is disconnected and
when all the installation is completed start the machine with the drive
wheels raised from the floor to ensure that any installation error do not
compromise safety.
After operation, even with the Key Switch open, the internal capacitors may
remain charged for some time. For safe operation, we recommend that the
battery is disconnected, and a short circuit is made between Battery
Positive and Battery Negative power terminals of the inverter using a
Resistor between 10 ohm and 100 ohm.
4 CAN stands for Controller Area Network. It is a communication protocol for real
time control applications. CAN operates at data rate of up to 1 Megabits per
second.
It was invented by the German company Bosch to be used in the car industry to
permit communication among the various electronic modules of a vehicle,
connected as illustrated in this image:
- The best cable for can connections is the twisted pair; if it is necessary to
increase the immunity of the system to disturbances, a good choice would
be to use a cable with a shield connected to the frame of the truck.
Sometimes it is sufficient a simple double wire cable or a duplex cable not
shielded.
- In a system like an industrial truck, where power cables carry hundreds of
Ampere, there are voltage drops due to the impedance of the cables, and
that could cause errors on the data transmitted through the can wires. In the
following figures there is an overview of wrong and right layouts of the cables
routing.
U Wrong Layout:
R
Can Bus
Power cables
Module Module
1 2
Module
3
R
This is apparently a good layout, but can bring to errors in the can line.
The best solution depends on the type of nodes (modules) connected in the
network.
If the modules are very different in terms of power, then the preferable
connection is the daisy chain.
U Correct Layout:
R
Can Bus
Power cables
Module
Module
1
2
Module
3
R
The chain starts from the –BATT post of the controller that works with the
highest current, and the others are connected in a decreasing order of power.
Otherwise, if two controllers are similar in power (for example a traction and a
pump motor controller) and a third module works with less current, the best way
to deal this configuration is to create a common ground point (star configuration).
U Correct Layout:
R
Can Bus
Power cables
Module
Module
1
2
Module
3
R
In this case the power cables starting from the two similar controllers must be as
short as possible. Of course also the diameter of the cable concurs in the voltage
drops described before (higher diameter means lower impedance), so in this last
example the cable between the minus of the Battery and the common ground
point (pointed by the arrow in the image) must be dimensioned taking into
4 Can advantages:
The complexity of today systems needs more and more data, signal and
information must flow from a node to another. CAN is the solution to different
problems that arise from this complexity
- simplified design (readily available, multi sourced components and tools)
- lower costs (less and smaller cables )
- improved reliability (fewer connections)
- analysis of problems improved (easy connection with a pc to read the data
flowing through the cable).
U A cable connected to the wrong pin can lead to short circuits and failure;
so, before turning on the truck for the first time, verify with a multimeter the
continuity between the starting point and the end of a signal wire.
- For information about the mating connector pin assignment see the
paragraph “description of the connectors”.
4.2.5 Connection of the encoder
1) ACE2 card is fit for different types of encoder. To control AC motor with Zapi
inverter, it is necessary to install an incremental encoder with 2 phases
shifted of 90°. The encoder power supply can be +5 or +12 V. It can have
different electronic output.
U VERY IMPORTANT
It is necessary to specify in the order the type of encoder used, in terms of
power supply, electronic output and n° of pulses for revolution, because
the logic unit must be set in the correct way by Zapi.
- The connection of the battery line switches must be carried out following
ZAPI instructions.
- If a mechanical battery line switch is installed, it is necessary that the key
supply to the inverter is open together with power battery line; if not, the
inverter may be damaged if the switch is opened during a regenerative
braking.
- An intrinsic protection is present inside the logic when the voltage on the
battery power connection overtakes 40% more than the battery nominal
voltage or if the key is switched off before the battery power line is
disconnected.
4.2.7 Insulation of truck frame
4.4 EMC
EMC stands for Electromagnetic Compatibility, and it represents the studies and
the tests on the electromagnetic energy generated or received by an electrical
device.
So the analysis works in two directions:
2) The study of the immunity can be divided in two main branches: protection
from electromagnetic fields and from electrostatic discharge.
The electromagnetic immunity concern the susceptibility of the controller with
regard to electromagnetic fields and their influence on the correct work made
by the electronic device.
There are well defined tests which the machine has to be exposed to.
These tests are carried out at determined levels of electromagnetic fields, to
3) The second type of immunity, ESD, concerns the prevention of the effects of
electric current due to excessive electric charge stored in an object. In fact,
when a charge is created on a material and it remains there, it becomes an
“electrostatic charge”; ESD happens when there is a rapid transfer from a
charged object to another. This rapid transfer has, in turn, two important
effects:
- this rapid charge transfer can determine, by induction, disturbs on the
signal wiring and thus create malfunctions; this effect is particularly
critical in modern machines, with serial communications (canbus) which
are spread everywhere on the truck and which carry critical information.
- in the worst case and when the amount of charge is very high, the
discharge process can determine failures in the electronic devices; the
type of failure can vary from an intermittently malfunction to a completely
failure of the electronic device.
4 IMPORTANT NOTE: it is always much easier and cheaper to avoid ESD from
being generated, than to increase the level of immunity of the electronic devices.
There are different solutions for EMC issues, depending on level of emissions/
immunity required, the type of controller, materials and position of the wires and
electronic components.
Diagnosis is provided in two ways. The digital console can be used, which gives
a detailed information about the failure; the failure code is also sent on the Can-
Bus.
1) DISPLAY TYPE
This parameter decides wich display is connected to the inverter.
0: No Display
1: MDI PRC connected
2: ECO DISPLAY connected
3: SMART DISPLAY connected
4: MDI CAN connected
2) TILLER SWITCH
This option handles the input CNA#6 . This input opens when the operator
leaves the truck. It is connected to a key voltage when the operator is
present. There are two levels:
- HANDLE: CNA#6 is managed as tiller input (no delay when released).
- SEAT: CNA#6 is managed as seat input (with a delay when released -
debouncing function)
3) HOUR COUNTER
- RUNNING: the counter registers travel time only.
- KEY ON: the counter registers when the "key" switch is closed.
4) CUTBACK MODE
OPTION#1, PRESENT or OPTION#2.
- If option 2.5 POT is ON:
OPTION#1: A13 is a handbrake.
PRESENT: A13 is a speed reduction request.
OPTION#2: no function for A13.
- If option 2.5 POT is OFF:
OPTION#1: A13 is a handbrake.
PRESENT: A13 is a speed reduction request.
OPTION#2: A13 is enable input.
5) BATTERY CHECK
- ON: the battery discharge level check is carried out; when the battery
level reaches 10%, an alarm is signalled and the maximum current is
reduced to the half of the programmed value.
- OFF: the battery discharge level check is carried out but no alarm is
signalled.
6) STOP ON RAMP
- ON: the stop on ramp feature (truck electrically hold on a ramp) is
managed for a time established by "auxiliary time" parameter. After this
time, the behaviour depends on the "aux output #1" option programming
(see also the following table).
7) AUX OUTPUT #1
- BRAKE: output A18 drives an electromagnetic brake coil which is
activated every time the traction motor is driven.
- FREE: No function.
- OPTION#1: Reverse Alarm. A18 is active when input REVERSE is
active or when motor is drived in reverse direction.
9) AUX INPUT#1
This parameter decide if input A10 is used for brake or for quick inversion.
BRAKE: A10 is used like brake pedal.
BELLY: A10 is used like quick inversion input. There’s inversion until A10 is
closed.
TIMED: A10 is used for quick inversion request and inversion is timed.
11) BACKING:
ON: Inching function is available. Enable input on A19, Forward direction
request input on A4, reverse direction request input on A5.
12) EPS
ON: EPS is present.
SUBMENU "ADJUSTMENTS"
4) ADJUST BATTERY
Fine adjustment of the battery voltage measured by the controller.
6) THROTTLE X POINT
This parameter changes the characteristic of the accelerator input curve.
7) THROTTLE Y POINT
This parameter changes the characteristic of the accelerator input curve.
VACC MIN and VACC MAX are values programmable by the "Program
Vacc" function.
1) ADJUSTMENT#01
Reserved.
2) ADJUSTMENT#02
Reserved.
3) SET CURRENT
It adjusts the regolation of maximum current. It shouldn’t be changed.
4) HIGH ADRESS
Reserved.
5) DEBUG MODE
Reserved.
6) INVERTER TYPE
It decides what kind of inverter is used.
0 and 1: traction.
2 and 3: pump.
The change of this parameter changes the other parameters at the next
keyoff.
7) SAFETY IN
0: input allways closed (bridged)
1: safety_in_drived: safety came from a different controller, need a can
handshake.
2: general purpose input (not jet defined. Need hardware change)
8) SAFETY OUT
0: none : fa comunque la diag all'init per verificare il funzionamento.
1: driver: is for drive a safety in.
2: general purpose: standard function: reverse direction indicator.
9) MAIN CONTACTOR
OFF No main contactor (directly connect to +Battery)
ON Main contactor in stand alone config
OPTION#1 Traction +pump 1 only MC
OPTION#2 Traction +pump 2 MC
1) DISPLAY TYPE
This parameter decides wich display is connected to the inverter.
0: No Display
1: MDI PRC connected
2: ECO DISPLAY connected
2) TILLER SWITCH
This option handles the input CNA#6 . This input opens when the operator
leaves the truck. It is connected to a key voltage when the operator is
present. There are two levels:
- HANDLE: CNA#6 is managed as tiller input (no delay when released).
- SEAT: CNA#6 is managed as seat input (with a delay when released -
debouncing function)
3) HOUR COUNTER
- RUNNING: the counter registers travel time only.
- KEY ON: the counter registers when the "key" switch is closed.
4) CUTBACK MODE
OPTION#1: A13 is third speed request
PRESENT: A13 is speed reduction request
OPTION#2: A13 has no function.
5) BATTERY CHECK
- ON: the battery discharge level check is carried out; when the battery
level reaches 10%, an alarm is signalled and the maximum current is
reduced to the half of the programmed value.
- OFF: the battery discharge level check is carried out but no alarm is
signalled.
U Very important:
In the combi system (pump + traction), the battery discharge calculation for
the complete system is carried out by the traction inverter; the information
about the pump inverter consumption is sent on the can-bus line from the
pump inverter to the traction inverter. So the correct programming for the
"Battery check" option is:
traction inverter: ON
pump inverter: OFF.
6) STOP ON RAMP
- ON: the stop on ramp feature (truck pump electrically hold on with load)
is managed for a time established by "auxiliary time" parameter.
- OFF: the stop on ramp feature is not performed.
7) AUX OUTPUT #1
Not used.
2) ADJUST BATTERY
Fine adjustment of the battery voltage measured by the controller.
3) THROTTLE 0 ZONE
It establishes a dead band in the lift potentiometer input curve (see also
curve below).
4) THROTTLE X POINT
This parameter, together with the THROTTLE Y POINT, changes the
characteristic of the lift potentiometer input curve : when the potentiometer is
depressed to X point per cent, the corresponding pump speed is Y point per
cent of the Maximum pump speed. The relationship between the lift
potentiometer position and the pump speed is linear between the THROTTLE
0 ZONE and the X point and also between the X point and the maximum
potentiometer position but with two different slopes.
5) THROTTLE Y POINT
This parameter, together with the THROTTLE X POINT, changes the
characteristic of the lift potentiometer input curve (see also paragraph 13.5):
when the potentiometer is de-pressed to X point per cent, the corresponding
pump speed is Y point per cent of the Maximum pump speed. The
relationship between the potentiometer position and the pump speed is linear
between the THROTTLE 0 ZONE and the X point and also between the X
point and the maximum accelerator position but with two different slope.
VACC MIN and VACC MAX are values programmable by the "Program
Vacc" function.
8) ADJUSTMENT #03
This parameter adjusts the updating of battery charge after Key-On.
Decreasing this parameter the minimum difference between the battery
voltage measured after Key-On and the last stored value, necessary to
update the charge with the new value measured, decrease. It is used to
calibrate the discharge algorithm with the battery of the application. See
chapter 9.5 for more information.
1) ADJUSTMENT#01
Reserved.
2) ADJUSTMENT#02
Reserved.
3) SET CURRENT
It adjust the regolation of maximum current. It shouldn’t be changed.
4) HIGH ADRESS
Reserved.
5) DEBUG MODE
Reserved.
6) INVERTER TYPE
It decides what kind of inverter is used.
0 and 1: traction.
2 and 3: pump.
The change of this parameter changes the other parameters at the next
keyoff.
7) SAFETY IN
0: input allways closed (bridged)
1: safety_in_drived: safety came from a different controller, need a can
handshake.
2: general purpose input (not jet defined. Need hardware change).
8) SAFETY OUT
0: none : fa comunque la diag all'init per verificare il funzionamento.
1: driver: is for drive a safety in.
2: general purpose: standard function: reverse direction indicator.
9) MAIN CONTACTOR
OFF No main contactor (directly connect to +Battery)
ON Main contactor in stand alone config
OPTION#1 Traction +pump 1 only MC
OPTION#2 Traction +pump 2 MC
AE2T2B ZP0.12
1) Opening Zapi Menu. 24V 400A 00000
CONFIG MENU
3) The Display will show: SET MODEL. SET MODEL
CONFIG MENU
5) SET OPTIONS appears on the display. SET OPTIONS
' % '
6) Press ENTER to go into the SET MODEL Menu. ' ' '
HOUR COUNTER
7) The display will shows the first OPTION. RUNNING
BATTERY CHECK
9) Desired OPTION appears. OFF
BATTERY CHECK
11) New OPTION appears. ON
14) Press ENTER to accept the changes, or press ' % ' ' ' '
OUT if you do not accept the changes. ' ' ' ' % '
CONFIG MENU
15) SET OPTIONS Menu appears. SET OPTIONS
16) Press OUT again. Display now show the ' ' '
Opening Zapi Menu. ' % '
AE2T2B ZP0.12
1) Opening Zapi Menu. 24V 400A 00000
CONFIG MENU
3) The display will show: SET MODEL. SET MODEL
CONFIG MENU
5) ADJUSTMENTS appears on the display. ADJUSTMENTS
BATTERY TYPE
7) The display will shows SET BATTERY TYPE. 48V
TROTTLE 0 ZONE
9) The desired parameter appears. 3%
TROTTLE 0 ZONE
7%
' % '
12) Press ENTER to confirm. ' ' '
13) Repeat the same from 5 to 12 points for the
other adjustments.
AE2T2B ZP0.12
1) Opening Zapi Menu. 24V 400A 00000
CONFIG MENU
3) The Display will show: SET MODEL. SET MODEL
CONFIG MENU
5) ADJUSTMENTS appears on the display. ADJUSTMENTS
12) Press ENTER to accept the changes, or press ' % ' ' ' '
OUT if you do not accept the changes. ' ' ' ' % '
13) Press OUT. Display now shows the Opening ' ' '
Zapi Menu. ' % '
AE2T2B ZP0.12
1) Opening Zapi Menu. 24V 400A 00000
CONFIG MENU
3) The Display will show: SET MODEL. SET MODEL
CONFIG MENU
5) ADJUSTMENTS appears on the display. ADJUSTMENTS
ADJUSTMENT BATTERY
9) ADJUST BATTERY appears. 50.2V
ADJUSTMENT BATTERY
11) Battery value appears on the display. 50.6V
14) Press ENTER to accept the changes, or press ' % ' ' ' '
OUT if you do not accept the changes. ' ' ' ' % '
CONFIG MENU
15) ADJUSTMENTS Menu appears. ADJUSTMENT
16) Press OUT. Display now show the Opening ' ' '
Zapi Menu. ' % '
1) ACCELERATION 0
It specifies the motor acceleration at 0 Hz. At level 0 the acceleration is
maximum. Increasing the parameter’s level the acceleration decreases.
2) INV. ACCEL 0
It specifies the motor acceleration at 0 Hz after an inversion of direction. At
level 0 the acceleration is maximum. Increasing the parameter’s level the
acceleration decreases.
3) ACCELERATION 1
It specifies the motor acceleration at ACC PROF. FREQ 1 [Hz]. At level 0 the
acceleration is maximum. Increasing the parameter’s level the acceleration
decreases.
4) ACCELERATION 2
It specifies the motor acceleration at ACC PROF. FREQ 2 [Hz]. At level 0 the
acceleration is maximum. Increasing the parameter’s level the acceleration
decreases.
5) ACCELERATION 3
It specifies the motor acceleration at ACC PROF. FREQ 3 [Hz]. At level 0 the
acceleration is maximum. Increasing the parameter’s level the acceleration
decreases.
4 (*) The acceleration time shown is the time from 0 Hz to 100 Hz. This is the ideal
ramp calculated by the software; the real ramp could change as a function of
motor control parameter setting and, obviously, as a function of the load.
4 (**) The braking feature is based upon deceleration ramps. The value shown in
the table is the time to decrease the speed from 100 Hz to 0 Hz. This is the ideal
ramps calculated by the software; the real ramp could change as a function of
motor control parameter setting and, obviously, as a function of the load.
1) ACCELERATION 0
It specifies the motor acceleration at 0 Hz. At level 0 the acceleration is
maximum. Increasing the parameter’s level the acceleration decreases.
2) ACCELERATION 1
It specifies the motor acceleration at ACC PROF. FREQ 1 [Hz]. At level 0 the
acceleration is maximum. Increasing the parameter’s level the acceleration
decreases.
3) ACCELERATION 2
It specifies the motor acceleration at ACC PROF. FREQ 2 [Hz]. At level 0 the
acceleration is maximum. Increasing the parameter’s level the acceleration
decreases.
4) ACCELERATION 3
It specifies the motor acceleration at ACC PROF. FREQ 3 [Hz]. At level 0 the
acceleration is maximum. Increasing the parameter’s level the acceleration
decreases.
8) RELEASE BRAKING
Seconds. It controls the deceleration ramp when the pump request is
released. The parameter sets the time needed to decelerate the traction
motor from 100Hz to 0Hz.
The following table shows the minimum / maximum programmable value for
each parameter. In the table is also present the parameters resolution.
AE2T2B ZP0.12
1) Opening Zapi Display. 24V 400A 00000
' % '
2) Press ENTER to go into the General Menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
ACCELERATION 0
5) The Display will show the first parameter. 2
INV. ACCEL 0
9) The Display will show the New Level. 2
10) When you are satisfied with the results of the ' ' '
changes you have made, Press OUT. ' % '
MAIN MENU
13) The Display will show: PARAMETER CHANGE
TRACTION PUMP
battery voltage (V) battery voltage (V)
motor voltage (%) motor voltage (%)
voltage booster (%) voltage booster (%)
frequency (Hz) frequency (Hz)
encoder (Hz) encoder (Hz)
slip value (Hz) slip value (Hz)
current rms (A) current rms (A)
motor power (W) motor power (W)
battery charge (%) battery charge (%)
temperature (°C) temperature (°C)
motor temperat. (°C) motor temperature (°C)
accelerator (V) handle/seat switch (ON/OFF)
handle/seat switch (ON/OFF) lifting control (V)
forward switch (ON/OFF) lifting enable (ON/OFF)
st
backward switch (ON/OFF) 1 speed switch (ON/OFF)
cutback switch (ON/OFF) 2nd speed switch (ON/OFF)
hand brake (ON/OFF) 3rd speed switch (ON/OFF)
Brakepedal pot. (%) hydro speed req. (ON/OFF)
ND
2 hourmeters 2nd hourmeters
AE2T2B ZP0.12
1) Opening Zapi Display. 24V 400A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display shows: TESTER
' % '
6) Press ENTER to go into the TESTER function. ' ' '
FREQUENCY
10) The Display shows: Hz
11) Press OUT again and return to Opening Zapi ' ' '
Display. ' % '
MAIN MENU
TESTER
Remember it is not possible to make any changes using TESTER. All you
can do is measure as if you were using a pre-connected multimeter.
21) Other functions
AE2T2B ZP0.12
1) Opening Zapi Display. 24V 400A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: SAVE PARAM.
' % '
6) Press ENTER to go into the SAVE function. ' ' '
SELECT: MOD. 01
FREE
' % '
9) Press ENTER to commence SAVE routine. ' ' '
10) You can see the items that are being stored READING …
whilst the SAVE routine is happening. ACCEL. DELAY (ECC.)
MAIN MENU
11) When finished, the Console shows: SAVE PARAM
12) Press OUT to return to the Opening Zapi ' ' '
Display. ' % '
U ATTENTION: When the RESTORE operation is made, all data in the inverter
memory will be written over and replace with data being restored.
Flow Chart showing how to use the RESTORE function of the Digital Console.
AE2T2B ZP0.12
1) Opening Zapi Display. 24V 400A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: RESTORE PARAM.
SELECT : MOD. 01
AE2T ZAPI V1
10) The Display will ask “ARE YOU SURE?”. ARE YOU SURE?
YES=ENTER NO=OUT
MAIN MENU
13) When finished the Console displays: RESTORE PARAM.
14) Press OUT to return to the Opening Zapi ' ' '
Display. ' % '
The two graphs show the output voltage from a non-calibrated potentiometer with
respect to the mechanical “zero” of the control lever. MI and MA indicate the point
where the direction switches close. 0 represents the mechanical zero of the
rotation.
The Left Hand graph shows the relationship of the motor voltage without signal
acquisition being made. The Right Hand Graph shows the same relationship after
signal acquisition of the potentiometer.
This function looks for and remembers the minimum and maximum potentiometer
wiper voltage over the full mechanical range of the pedal. It enables
compensation for non symmetry of the mechanical system between directions.
The operation is performed by operating the pedal after entering the PROGRAM
VACC function.
' % '
2) Press ENTER to go into the General Menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: PROGRAM VACC
11) Select the Reverse Direction and repeat Item MIN VACC MAX
10. 0.6 ↑ 4.4
' % '
14) Press ENTER for yes, or OUT for NO. ' % '
MAIN MENU
15) When finished, the Console shows: PROGRAM VACC
16) Press OUT again to return to the Opening Zapi ' ' '
Menu. ' % '
This function permits a deeper diagnosis of problems as the recent history can be
revised.
4 NOTE: if the same alarm is continuously happening, the controller does not use
new memory of the logbook, but only updates the last memory cell increasing the
related counter (point 2) of previous list). Nevertheless, the hourmeter indicated
in this memory refers to the first time the alarm occurred. In this way, comparing
this hourmeter with the controller hourmeter, it is possible to determine:
- When this alarm occurred the first time.
- How many hours are elapsed from the first occurrence to now.
- How many times it has occurred in said period.
AE2T2B ZP0.12
1) Opening Zapi Display. 24V 400A 00000
' % '
2) Press ENTER to go into the General menu. ' ' '
MAIN MENU
3) The Display will show: PARAMETER CHANGE
MAIN MENU
5) The Display will show: ALARMS
' % '
6) Press ENTER to go into the ALARMS function. ' ' '
CODE
7) The Display will show the most recent Alarm. 00005 #02 20°C
10) When you have finished looking at the Alarms, ' ' '
press OUT to exit the ALARMS menu. ' % '
CLEAR LOGBOOK?
11) The Display will ask “CLEAR LOGBOOK?”. YES=ENTER NO=OUT
13) Press OUT to return to the Opening Zapi ' ' '
Display. ' % '
ALARMS: these are the faults which open the power section, which means the
power bridge is opened and, when possible, the LC is opened and EB is applied.
These are faults related to:
- failures in the motor/controller that the power system is not anymore able to
drive the truck
- safety related failures
2) ANALOG
Cause:
This alarm occurs when the A/D conversion of the analog inputs gives frozen
value, on all of the converted signals, for more than 400msec. The goal of
this diagnosis is to detect a failure of the A/D converter or a problem in the
code flow that omits the refreshing of the analog signal conversion.
Troubleshooting:
If the problem occurs permanently it is necessary to substitute ACE logic
board.
4) CAPACITOR CHARGE
Follows the charging capacitor system:
5) COIL SHORT HW KO
Cause:
The hardware circuits which manages short circuits protection of LC and
EB/AUX coils has a problem.
Troubleshooting:
This type of fault is not related to external components; replace the ACE logic
board.
6) DRIVER SHORTED
Cause:
The driver of the main contactor coil is shorted.
Troubleshooting:
- Check if there is a short or a low impedance pull-down between NMC
(CNA#16) and –BATT.
- The driver circuit is damaged in the logic board, which has to be
replaced.
8) SAFETY IN
Cause:
The safety input is opened and accordingly the MC is opened an EB/AUX
OUT coil is driven.
Troubleshooting:
Check the CAN#11 input, if it is connected to –Batt and the alarm is
generated then there is a fault in the SAFETY IN hardware circuit. Replace
the logic board.
9) SAFETY OUT
Cause:
10) WATCHDOG#1
Cause:
At start-up the watch dog signal is already active before the software has
generated it. At stby or running condition the watch dog signal is not active
(in alarm status).
Troubleshooting:
The WD hardware circuit or microcontroller output port are damaged. In both
cases no external component are involved. Replace the logic board.
11) WATCHDOG#2
Cause:
At start-up the watch dog signal is already active before the software has
generated it. At stby or running condition the watch dog signal is not active
(in alarm status).
Troubleshooting:
The WD hardware circuit or microcontroller output port are damaged. In both
cases no external component are involved. Replace the logic board.
Current Gain The Maximum current gain Controller works, but Start-up, stand-
MDI code parameters are the default with low maximum by
allarm 92 values, which means the current
maximum current adjustment
procedure has not been
carried out yet
Sens mot The output of the motor The maximum current Continuous
temp Ko thermal sensor is out of is reduced to half and
MDI code range. speed is reduced
allarm 65
Thermic sens The output of the controller The maximum current Continuous
Ko thermal sensor is out of is reduced to half and
MDI code range. speed is reduced
allarm 61
Slip profile Error on the parameters of Traction/Pump motor Start-up, stand- Traction/ Pump
MDI code the slip profile setting. is stopped by, running request
allarm 99
EEPROM KO Error is detected in Eeprom Controller works continuous
MDI code or in Eeprom management using default
allarm 71 parameters
Forward + The travel demands are Traction is stopped Start-up, stand- Traction
Backward active in both directions at by, running request
MDI code the same time
allarm 80
2) INCORRECT START
Cause:
This is a warning for an incorrect starting sequence.
Troubleshooting:
The possible reasons for this alarm are (use the readings in the TESTER to
facilitate the troubleshooting):
- A travel demand active at key on
- Presence man sensor active at key on
Check the wirings. Check the micro switches. It could be also an error
sequence made by the operator. A failure in the logic is possible too; so
when all of the above conditions were checked and nothing was found,
replace the ACE logic board.
4) TEMPERATURE
Cause:
This alarm occurs when the temperature of the base plate is higher than 85°.
Then the maximum current decreases proportionally with the temperature
increases from 85° up to 105°. At 105° the Current is limited to 0 Amps.
Troubleshooting:
It is necessary to improve the controller cooling. For realise an adequately
cooling in case of finned heat sink are important factor the flux [m3/h] and
temperature [°C] of cooling air. In case of thermal dissipation realised with
the controller base plate installed on truck frame it is important the thickness
of frame and the planarity and roughness of its surface. If the alarm is
signalled when the controller is cold, the possible reasons are a thermal
sensor failure or a failure in the logic card. In this case, it is necessary to
replace the controller.
7) HAND BRAKE
Cause:
The hand brake input is active when a traction request is done.
Troubleshooting:
The possible reasons for this alarm are (use the readings in the TESTER to
facilitate the troubleshooting):
- The HB switch is damaged so it does not close the input CNA#13 to –
Batt. Replace it.
- The HB switch work correctly but in the tester menu the HB input is
always ON. In this case the failure is in the logic board, replace it.
8) CURRENT GAIN
Cause:
The Maximum current gain parameters are at the default values, which
means the maximum current adjustment procedure has not been carried out
yet.
Troubleshooting:
Ask the assistance of a Zapi technician to do the correct adjustment
procedure of the current gain parameters
12) EEPROM KO
Cause:
It’s due to a HW or SW defect of the non-volatile embedded memory
supporting the controller parameters. This alarm does not inhibit the machine
operations, but the truck will work with the default values.
Troubleshooting:
Try to execute a CLEAR EEPROM operation (refer to Console manual).
Switch the key off and on to check the result. If the alarm occurs
permanently, it is necessary to replace the controller. If the alarm disappears,
the previously stored parameters will have been replaced by the default
parameters.
13) FORW+BACK
Cause:
This alarm occurs when both the travel demands (Fwd and Bwd) are active
at the same time.
Troubleshooting:
Check the wiring of the Fwd and Rev travel demand inputs (use the readings
in the TESTER to facilitate the troubleshooting). Check the microswitches for
failures.
A failure in the logic is possible too. So, when you have verified the travel
demand switches are fine working and the wiring is right, it is necessary to
replace the ACE-2 logic board.
Check the Foot pedal or Tiller microswitch. Using a suitable test meter, confirm
that there is no electrical resistance between the contacts by measuring the volt
drop between the terminals. Switches should operate with a firm click sound.
Microswitches should be checked every 3 months.
Check the Battery cables, cables to the inverter, and cables to the motor. Ensure
the insulation is sound and the connections are tight.
Cables should be checked every 3 months.
Check the mechanical operation of the pedal or tiller. Are the return springs ok ?
Do the potentiometers wind up to their full or programmed level ?
Check every 3 months.
Checks should be carried out by qualified personnel and any replacement parts
used should be original. Beware of NON ORIGINAL PARTS.
The installation of this electronic controller should be made according to the
diagrams included in this Manual. Any variations or special requirements should
be made after consulting a Zapi Agent. The supplier is not responsible for any
problem that arises from wiring methods that differ from information included in
this Manual.
During periodic checks, if a technician finds any situation that could cause
damage or compromise safety, the matter should be bought to the attention of a
Zapi Agent immediately. The Agent will then take the decision regarding
operational safety of the machine.