100 - 13300 kW
Design
Oilon burners are designed for easy operation and maintenance
without forgetting environmental friendliness and safety.
Applications
Oilon burners are suitable for various applications, such as hot
water boilers, steam boilers, air heaters and different process
applications.
Fuels
Oilon burners are suitable for various liquid and gaseous fuels
such as light fuel oil, heavy fuel oil for viscosities up to 700
8 mm2/s at 50 °C, natural gas (2nd family gases, groups H and
E) and LPG. Burners using other fuels are available on request.
Connectivity
Digital combustion management enables communication
with external systems. Remote monitoring and diagnostics
optimize operational efficiency.
Standards
Gas burners comply with the EN 676 standard, oil burners
with the EN 230 and EN 267 standards, and dual fuel We reserve the right to make technical alterations.
burners with all of these. Burners are EU type tested. Burners
complying with marine classification society requirements,
such as ABS, BV, CCS, DNV, GL, KR, LR, NKK, RINA and RS,
are also available.
A. Procedure
1 Define relevant boiler and application information
• boiler capacity and efficiency, or required burner capacity
• furnace back pressure
• fuel/fuels to be used B. Equations and rules of thumb
• burner inlet fuel pressure 1. Burner capacity = boiler capacity / 0.9 (when boiler efficiency is 90 %)
• burner capacity control method 2. Steam boilers: 1 ton/h steam ≈ 700 kW boiler capacity
2 Calculate the burner capacity. Burner capacity = 3. Light oil: 1 kg/h ≈ 11.86 kW burner capacity
with calorific value 42.7 MJ/kg
boiler capacity / efficiency
4. Heavy oil: 1 kg/h ≈ 11.22 kW burner capacity
Example: boiler capacity of 2,500 kW, efficiency of 90 % → with calorific value 40.5 MJ/kg
burner capacity = 2,500 kW / 0.9 = 2,780 kW 5. Natural gas: 1 m3n/h ≈ 10 kW burner capacity
3 Gas burners: Required gas flow [m3n/h] = (burner capacity with calorific value 35.84 MJ/m3n
[kW] x 3.6) / gas’s calorific value [MJ/m3n]. 6. The amount of combustion air:
Example: required burner capacity = 2,780 kW → required • Gas burners: required amount of combustion air for
gas flow = (2,780 kW x 3.6) / 35.8 MJ/m3n = 280 m3n/h, each 10 kW of burner capacity is 12 to 13 m3/h.
where 35.8 MJ/m3n is the calorific value of natural gas. • Oil burners: required amount of combustion air for
Oil burners: Calculate the required oil flow [kg/h]. Required each kilo of oil burned [kg/h] is 13.5 m3/h.
oil flow [kg/h] = (burner capacity [kW] x 3.6) / the oil’s calorific 7. Oil pumping, filtering, and preheating unit (Oilon HotBox) is
value [MJ/kg]. Example: required burner capacity = 2,780 required with heavy fuel oil. The required minimum pump
kW → required oil flow = (2,780 kW x 3.6) / 42.7 MJ/kg = 234 output [kg/h] can be calculated as follows:
kg/h, where 42.7 MJ/kg is the calorific value of light oil. Required minimum output [kg/h] = (oil flow to be burned in kg/h
+ 150 to 200 kg/h)* 1.25 to 1.3, where the expression inside
4. See working diagrams for burner operating range. The
the parentheses indicates the preheated oil flow to each burner.
graphs indicate the burner operating range. For example, the
boiler back pressure with a burner capacity of 2,780 kW is
12 mbar. Looking at the adjoining diagram, see your burner
capacity along the horizontal axis. On the vertical axis figure
out your boiler back-pressure. The point, where the two lines
meet, defines the required burner type. The optimum burner
9
is best chosen by ensuring that the defined operating point
is as close as possible to the right hand edge of the graph. An example of burner selection
Note that different fuels and capacity control methods re-
quire separate graphs.
20 2000
5. Gas and dual fuel burner valve selection: Select a suitable GP-280 M GP-280 M
18 1800
GP-250 M
valve, using the gas valve selection table. Note that the val- GP
-25 GP-150 M
16 0M 1600
ues in the selection table apply when the furnace back pres- GP
GP-140 M
GP-140 H
-1
sure is 0 mbar. Therefore, you must subtract the furnace back 14 40
M
1400
pressure from the actual gas inlet pressure and choose the 12 GP-140 H 1200
GP
mbar
Pa
10 1000
50M
Nitrogen oxides (NOx) are compounds of nitrogen and Effect of combustion head on NOx emissions,
oxygen, the most important of which are NO and NO2.
Small amounts of nitrogen oxides also occur in nature, natural gas
but the majority of them originate from human actions,
mainly from traffic and energy production.
180
160
Nitrogen oxides form during all combustion processes, 140
when the nitrogen present in the combustion air and/ 120
100
or fuel and the oxygen present in the combustion air,
mg/kWh
80 NOx
react at high temperatures.
60 NOx FGR
40
Nitrogen oxides are harmful to humans and the en- 20
vironment in many ways. They are toxic and harmful 0
Standard LN80 LN60
to the respiratory system. Nitrogen oxides cause acidi-
fication and eutrophication of the environment, form Combustion head
ground-level ozone and harmful particulate emissions.
We are especially committed to reducing nitrous oxide Low NOx emissions are achieved by innovative gas and
(NOx) and particulate emissions. One of our most im- air distribution and staging in the combustion head.
10 portant goals when developing our products is lower
emission levels. NOx emissions are also reduced with the use of inter-
nal/external FGR in order to reduce flame peak temper-
atures and combustion reaction speed. Emission values
depend on the furnace geometry, the furnace load and
the temperature of the boiler medium. Low NOx levels
are mainly achieved on 3-pass boilers.
When the burner is designed to operate on 2nd family gases and/or 3rd family gases and/or LFO,
the maximum NOx-values shall be according to the table.
Note that the calculated NOx-value shall not exceed 170 mg/kWh for 2nd family gases nor 230 mg/kWh for 3rd
family gases.
FGR - Flue Gas Recirculation
External Flue Gas Recirculation, FGR, is an effective low
The effect of FGR in natural gas combustion
cost solution to achieve very low NOx emissions with 80
various fuels.
70
%
peratures to cool down and combustion reactions to
NOx reduction
50
slow down, which reduces NOx emissions.
NOx-reduction, %
40
Achievable reduction depends on many factors includ- Amount to be defined in
ing burner type, boiler, combustion air temperature 30
each application separately
and the amount of recirculated flue gas, see relevant
curve. When designing the assembly, it is important to 20
FGR 10%
60
55
50
45
40
Recommended
35
working range
30
100 120 140 160 180 200 220
Flue gas temperature, °C
User interface
Control unit
Example of application
12
Burner control systems
INTERMITTENT
BURNER SERIES CONTROL CONTINUOUS USE GAS OIL DUAL FUEL
USE
50/80 H INTERNAL X - LME LAL -
INTERNAL X - LME LAL -
50...150 H
INTERNAL - X LGK LOK -
50...90 M/MH INTERNAL X X WD3x WD3x WD3x
INTERNAL X X WD3x WD3x WD3x
130...280 M/MH
EXTERNAL X X WDx00 WDx00 WDx00
INTERNAL X X WD3x WD3x WD3x
300...700 M-III
EXTERNAL X X WDx00 WDx00 WDx00
1000...1200 M EXTERNAL X X WDx00 WDx00 WDx00
Check the burner specific automation options on the burner’s technical data pages.
High efficiency
13
Electronic fuel/air ratio control improves combustion
efficiency and lowers emissions. The greatest benefits
are achieved in dual fuel burners where the combus-
tion of both the main and reserve fuels can be adjust-
ed optimally and the O2 control is in use. Significant
energy savings can also be achieved by using variable
speed drive (VSD) in the combustion air fan.
A versatile system
Oilon WiseDrive system can be connected to external systems via fieldbus connection. Data regarding burner status
and combustion process can be read remotely. Also remote control (start, stop, reset) and settings (capacity controller,
fuel selection) can be performed via fieldbus.
Electronic fuel/air ratio control of the burner brings the benefits of lower flue gas emissions, decreased consumption
of energy and improved technical characteristics of the burner, such as more accurate regulation.
WiseDrive includes control sequences, fuel/air ratio and capacity control as well as leak testing of gas valves and
much more in a single package.
CAN BUS
Gas pressure
Oil pressure
Gas valves
Oil valves
detector
switch
Flame
Motor
Remote
M
Vision Control Speed sensor Frequency converter for
variable speed drive
FS
VSM100
SYSTEM BUS
Control System
Control unit
User interface
Pictures are for illustration purpose.
Example of Oilon WiseDrive WD100
Electronic fuel/air ratio control system
CAN BUS
CAN BUS - Servomotor
Gas pressure
Oil pressure
Gas valves
Oil valves
detector
switch
switch
Flame
15
Control room
MOD-BUS
Boiler pressure/
Boiler temperature Examples of WiseDrive’s functions
• Control sequences and safety
functions
Safety devices • Fuel/air ratio control
O sensor (option) • Combustion head control (option)
• Load control with inbuilt PID
controller, control also by an external
O module 4...20 mA signal
• Can be connected with external
Flue gas damper
plant automation via bus. Modbus
Air damper Combustion head regulation/
RTU as standard.
Oil regulator • Different access levels
Gas damper • Input of parameters via text display
operating panel or/and PC (check
software and hardware require-
ments)
Air pressure switch
Oil pressure
Oil valves
CAN BUS
CAN BUS
detector
switch
16 Motor O2 sensor)
• Flue gas temperature reading
M (requires temperature sensor)
Speed sensor
• Combustion air temperature
Frequency converter for
Control room FS variable speed drive reading (requires temperature sensor)
MOD-BUS
Method of control:
H = Two-stage
M = Modulating
MH = Modulating gas, two-stage oil
Burner frame size categorization:
50…1200
Fuel:
GP = Gas
GKP = Gas, light fuel oil
KP = Light fuel oil
RP = Heavy fuel oil
GRP = Gas, heavy fuel oil
19
Gas Burners
100 - 13 300 kW
GP-50...90 H/M
Technical Data
BURNER GP-50 H GP-80 H GP-90 H GP-50 M GP-90 M
Capacity kW 200 - 800 350 - 1000 350 - 1500 100 - 800 250 - 1500
Burner
motor
3~ 400 V 50 Hz
Capacity kW 0,75 1,5 2,2 0,75 2,2
Current A 2,0 3,2 4,4 2,0 4,4
Speed r/min 2900 2900 2900 2900 2900
Control unit LME LME LME/LGK WD33 WD33
NOx class 1 1 1 1 1
Weight kg 40 63 63 40 63
8 Dimensions 7 6 5 4 3 2
L1 L2 B3
Näkymät
View posit
D1
H1
H2
L4
H3
G
D063380
20 L3 B2 B1
E
R2
R1
B4
G = Gas inlet
E = Electrical connection
G = Gas inle
E = Electric
BURNER L1 L2 L3 L4 H1 H2 H3 B1 B2 B3 B4 ØD1 R1 R2
GP-50 H 710 240 300 185 Burner
90 445 L1
325 L2
165 210 L3 310L4 H1
131 H2
240 H3
160 B1605 B2 - B3 B4 øD
GP-50 H 710 240 300 185 90 445 325 165 210 310 131 240 16
GP-80 H 690 300 400 120 GP-80
65 H 480 690
330 300182 400 246120 36065 480
155 330
272 182
200 246665 360640 155 272 20
GP-90 H 690 300 400 120 65 480 330 182 246 395 155 272 20
GP-90 H 690 300 400 120 GP-50 M 480
65 330
745 240182 300 246185 39590 155
510 272
325 200
165 210665 310665 131 240 16
GP-50 M 745 240 300 185
GP-90
90
M 510 725
325
300165 400 210120 31065 545
131
330
240
182
160
246635
395 - 155 272 20
│ ││││ │
1ST REV. SCALE
GP-90 M 725 300 400 120 65 545 330 182 246 jhaverinen
395 23/11/2017
155 272 200 695 665
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
*D06
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D06338
WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
125
MITTAKUVA ESITE A038169
GP-50...90 H/M
ITEM
DocID:A038169AD063380A
GP-9
0H
10 G P- 1000
8 0H
8 800
GP
mbar
-50
Pa
H
6 600
4 400
GP50H...90H
2 200
0 0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
kW
10 1000
GP-90 M 21
9 GP-50 M 900
G
P-
8
50 -9 0M 800
M GP
7 700
6 600
mbar
Pa
5 500
4 400
3 300
2 200
GP50M...90M
1 100
0 0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
kW
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
D1
Näkym
H1
H5
View p
H2
L4
H3
E
G D063492
L5
B2 B1
22 E L3
R1
D G = Gas inlet
B4
E = Electrical connection
F = FGR - Flue Gas Recirculation G = Gas inlet
R2
E = Electrical c
F = FGR - Flue
F
C L2 L2
Burner L1 L2 L3 L4 L5 H1 H2 H3 H5 B1 B2 B3 B4
BURNER L1 L2 C1L3 C2 L4 L5
GP-140 HC1 1230 C2220 260 129 880 625 400 210 195 305 430 210 360
GP-140 M 1285 220 260 129 880 625 400 210 195 305 430 210 360
GP-140 H 1230 220GP-150 M - -
1285 230 260 129260 880
129 880 625 400 210 195 305 480 210 360
GP-140 M 1285 220GP-250 M - 1320 -300 260 129260 130
880 890 675 446 235 215 340 490 250 440
GP-280 M 1320 312 260 130 890 675 446 235 215 340 490 250 440
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
THIS DOCUMENT IS PROPERTY OF OILON OY, LAHTI FINLAND.
GP-140 M LN80 1285 - 260 430 129260 129 880 625 400 210 195 305 430 210 360
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
*D
APPROVED BY
jhaverinen
CUSTOMER
GP-250 M LN80 1320 - 420 550 260 130 890 GENERAL TOLERANCES
PROJECT
GP-280 M LN80 1320 - 420 550 260 130 890 MARK
DRW.NO
TITLE
POLTIN , BURNER
D06
A WEIGHT (KG) SUPERSEDES DRW. 3D-MOD
Rev
BURNER H1 H2 Comment
H3 H5 B1 B2Modified By
B3 Date
B4 ØD1 R1 R2
154
MITTAKUVA ESITE A038
GP-140 H...280 M
GP-140 H 625 400 210 195 305 430 210 360 240
ITEM 1000 1000
GP-140 M 625 400 210 195 305 430 210 360 240 1050
DocID:A038232AD063492A1150
GP-150 M 625 400 210 195 305 480 210 360 270 1050 1150
GP-250 M 675 446 235 215 340 490 250 440 270 1100 1200
GP-280 M 675 446 235 215 340 490 250 440 300 1100 1200
GP-140 M LN80 625 400 210 195 305 430 210 360 240 1050 1150
GP-250 M LN80 675 446 235 215 340 490 250 440 256 1100 1200
GP-280 M LN80 675 446 235 215 340 490 250 440 276 1100 1200
Oilon Monoblock 2.0/022018
Working Diagram
20 2000
GP-280 M GP-280 M
18 1800
GP GP-250 M
-25 GP-150 M
16 0M 1600
GP-140 M
GP GP-140 H
14 -1 1400
40
M
12 GP-140 H 1200
GP
mbar
-1
Pa
10 1000
5 0M
8 800
6 600
GP140H...280M
4 400
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
20 2000
23
18
GP-280 M LN80 1800
GP-250 M LN80
GP-140 M LN80
16 1600
GP
-28
14 GP 0M 1400
-2 LN
50 80
12 M 1200
GP LN
mbar
-1 80
10 40 1000
M Pa
8 LN 800
80
GP140M...280M_LN80
6 600
4 400
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
Dimensions
8 7 6 5 4 3 2
F L1 L2
D1
Näkymät lukittu
View position lo
H5
H1
H2
L3
E
H3
L5 D063648
24 B2 B1
D
B4
G = Gas inlet
E = Electrical connection
G = Gas inlet
E F = FGR - Flue Gas Recirculation E = Electrical co
F = FGR- Flue Ga
C F
BURNER L1 L2 L3 L5 H1 H2
Burner H3 L1H5 L2 B1L3 B2
L5 H1B4 H2 ØD1
H3 H5 B1 B
GP-350 M 1360 350 195 810 940 GP-350
695 M 355 1360
345 350 490
195 810
580 940490 695 320
355 345 490 5
GP-450 M 1470 350 195 910 1050 770 395 420 510 6
GP-450 M 1470 350 195 910 1050 770 395 420 510 650 550 370
GP-320 M LN80 1360 500 195 810 940 695 355 345 490 4
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
940 GP-350
695 M LN80 1360 480 490
195 810 940490 695 302
355 345 490 5
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
*D06
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D06364
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
177
MITTAKUVA ESITE A038300
GP-350M...450M LN80
ITEM
DocID:A038300AD063648A
GP-450 M
GP-350 M
20 G P- 2000
350 GP
M -45
0M
15 1500
mbar
Pa
10 1000
GP350M...450M
5 500
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
kW
25 2500
25
GP-450 M LN80
GP-350 M LN80
GP-320 M LN80
20 2000
GP
-45
ML N80 0 M
GP-350 LN
80
M LN80
15 GP-320 1500
mbar
Pa
10 1000
GP320M...450M LN80
5 500
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
kW
Technical Data
BURNER GP-500 M GP-600 M GP-700 M GP-700 M-II GP-700 M-III
Capacity kW 870 - 6070 970 - 6750 1200 - 8400 1350 - 9500 1500 - 10 500
Fan motor
3~ 400 V 50 Hz
Output kW 11,0 15,0 18,5 22,0 30,0
Current A 19,5 26,0 34,0 38,0 52,0
Speed rpm 2900 2900 2900 2900 2900
Control unit WD33 WD33 WD33 WD33 WD33
NOx class 1 1 1 1 1
Weight kg 450 460 535 565 675
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
D1
øD2
KUVANNOT LUKIT
H5
VIEW POSITION LO
H1
H2
L4
H3
E G
L5 D063623
B2 B1
26 L3
E
R2
D G = Gas inlet
B4
E = Electrical connect
G = Gas inlet F = FGR - Flue Gas Rec
E = Electrical connection
R1 F = FGR - Flue Gas Recirculation
F
*D063
APPROVED BY
GP-500 M 1060 780 420 365 435 645 270 550Ltuominen370 425
CUSTOMER
1440 1400
GENERAL TOLERANCES
GP-600 M 1060 780 420 365 435 645 270 550 395 425
PROJECT 1440 1400
DRW.NO
MARK
GP-700 M 1060 780 420 365 490 700 270 550 395 425 TITLE 1460
POLTIN , BURNER
1400
D063623
A GP-700 M-II 1060 780 420 365 490 760 270
WEIGHT (KG)
550 395
SUPERSEDES DRW.
425 1460 1400 3D-MODEL.NO
Rev Comment Modified By Date
GP-700 M-III 1060 780 420 365 490 845 270
312 550 425 -MITTAKUVA ESITE
1460 1400 A038288
GP-500 M...700 M-III
ITEM
DocID:A038288AD063623A
GP
25 -60 2500
0 M
20 2000
GP
mbar
Pa
-50
0M
15 1500
10 1000
GP500M...600M
5 500
0
0 1000 2000 3000 4000 5000 6000 7000 8000
kW
35 3500
27
GP-700 M-III GP-700 M-III
30 GP-7 GP-700 M-II 3000
00 M
-II GP-700 M
GP-700
25
M 2500
20 2000
mbar
Pa
15 1500
10 1000
GP700...700MIII
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
kW
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F D1
øD2
KUVANNOT LUKITT
H5
VIEW POSITION LO
H1
H2
L4
H3
E G
L5 D063623
28 B2 B1
L3
E
R2
D G = Gas inlet
B4
*D0636
APPROVED BY
Ltuominen
BURNER H1 H2 H3 H5 B1 B2 B3 B4 ØD1 ØD2
CUSTOMER R1 R2
GENERAL TOLERANCES
GP-600 M LN60 1060 780 420 365 435 645 270 550 408 PROJECT- 1440 1400
DRW.NO
MARK
GP-700 M-III LN60 1060 780 420 365 490 845 270 550 445 TITLE -
POLTIN , BURNER
1460 1400 D063623
A GP-600 M LN80 1060 780 420 365 435 645 270
WEIGHT (KG) 550 384
SUPERSEDES DRW. - 1440 1400 3D-MODEL.NO
Rev Comment Modified By Date
GP-700 M-II LN80 1060 780 420 365 490 760 312270 550 406
MITTAKUVA ESITE A038288
GP-500- M...700 M-III
1460 1400
ITEM
GP-700 M-III LN80 1060 780 420 365 490 845 270 550 406 - 1460 1400
DocID:A038288AD063623A
0M
Pa
-II
LN
15 80 1500
GP600M...700MIII_LN80
10 1000
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
kW
40 4000
29
0 GP-700 M-III LN60
35 -III LN6 GP-600 M LN60 3500
M
700
G P-
30 3000
G
25 2500
P-
60
0
mbar
Pa
20 2000
LN
60
15 1500
GP600M...700MLN60
10 1000
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000
kW
Dimensions
8 7 6 5 4 3 2
L1 L2
F
øD1
Näkym
H1
H5
View p
E L3
H2
E
G
H3
30
L5 D063634
B2 B1
G = Gas in
E = Electri
F = FGR -
B4
C
G = Gas inlet
E = Electrical connection
F = FGR - Flue Gas Recirculation
Burner L1 L2 L3 L5 H1 H2 H3 H5 B1
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
GP-1000 M 1600 434 303 1000 1470 1100 510 585 800 8
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
F
GP-1200 M 1600 434 303 1000 1470 1100 510 585 940 9
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
B GP-1000 M LN80 1600 650 303 1000 1470 1100 510 585 800 8
BURNER L1 L2 L3 L5 H1 H2 H3 H5│
│ ││││ B1 B2 B4 ØD1
1ST REV. SCA
jhaverinen 04/12/2017
GP-1000 M 1600 434 303 1000 1470 1100 510 585
MODIFIED BY
800 880 750 496
BAR CODE
Ltuominen 22/03/2018
*D0
APPROVED BY
GP-1200 M 1600 434 303 1000 1470 1100 510 585 940
Ltuominen 930 750 520
CUSTOMER
GENERAL TOLERANCES
GP-1000 M LN80 1600 650 303 1000 1470 1100 510 585 800 880 PROJECT 750 454
DRW.NO
MARK
TITLE
POLTIN , BURNER
D0636
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
571
MITTAKUVA ESITE A038294
GP-1000 M...-1200 M
ITEM
DocID:A038294AD063634A
20 2000
mbar
Pa
15 1500
GP1000M...1200M_LN80
10 1000
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000
kW
31
Ignition transformer x x x x x x
Flame sensor x x x x x x
Gas nozzle x x x x x x
Elbow 90° x x x x x x
FGR - - o o o o
Frequency converter - o o o o o
O2 control - o o o o o
O2+CO control - o o o o -
Manual x x x x x x
x Standard
o Option
8
Dimensions
7 6 5 4 3 2
F L1 L2 B3
D1
Näkymät lu
H1
View positio
H2
L4
E
H3
34 G
O D063399
B2 B1
L3
R2 E
D
R1
B4
G = Gas inlet
O = Oil inlet/Retur
G = Gas inlet E = Electrical con
O= Oil inlet/return
E = Electrical connection
C
BURNER L1 L2 L3 L4 H1 H2 H3 B1 B2 B3 B4 ØD1 R1 R2
GKP-50 MH 745 240 300 185 Burner
90 L1
510 325 L2 165 L3 275 L4 310H1 H2
131 H3
240 B1160 B2 635 B3 -B4 øD1
GKP-90 MH 725 300 400 120
GKP-5065
MH 545
745 240
330
300
182
185315 90 395510 325
155
165
272
275200 310 695131 240
665
160
B GKP-90 MH 725 300 400 120 65 545 330 182 315 395 155 272 200
│ ││││ │
1ST REV. SCALE
jhaverinen 24/11/2017 1:
MODIFIED BY BAR CODE
Ltuominen 21/03/2018
*D063
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063399
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
125
MITTAKUVA ESITE A038169
GKP-50...90 H/M
ITEM
DocID:A038169AD063399A
H
M
10 1000
90
P-
H
GK
M
8 800
50
mbar
Pa
P-
0 M GK
H
0M
6 600
H
P-9
GK
P-5
4 400
GK
GKP50...90 MH
2 200
0 0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
kW
35
36
D1
Näkym
View p
H1
H5
H2
L4
H3
E G
O L5 D063583
L3 B2 B1
E
R1
B4
D G = Gas inlet
O= Oil inlet/return
E = Electrical connection G = Gas in
O = Oil inle
F = FGR - Flue Gas Recirculation E = Electric
When FGR is needed, oil pump unit F = FGR - F
R2
will be relocated.
F
C
L2
BURNER L1 L2 Burner L3 L1
L4 L2 L5 L3 L4 L5 H1 H2 H3 H5 B1 B2 B3 B
C1 C2
GKP-140 MH 1285 220 260 129 880 625 400 210 195 430 430 210 3
GKP-140 MH 1285 220 - GKP-150
- MH
260 1285
129 230880 260 129 880 625 400 210 195 430 480 210 3
GKP-250 MH 1320 300 260 130 890 675 446 235 215 465 490 250 4
GKP-150 MH 1285 230 - -
GKP-280 260
MH 129
1320 312880 260 130 890 675 446 235 215 465 490 250 4
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
THIS DOCUMENT IS PROPERTY OF OILON OY, LAHTI FINLAND.
GKP-140 M 260
LN80 1285 430890 260 129 880 625 400 210 195 430 430 210 3
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
- Ei vielä- julkaista
1ST REV.
GKP-140 M LN80 1285 430 260 129 880 jhaverinen 01/12/2017
MODIFIED BY BAR
Ltuominen 22/03/2018
GKP-250 M LN80 1320 - 420 550 260 130 890
*
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW
MARK
GKP-250 MH 675 446 235 215 465 490 250 440 270 1100 1200
DocID:A038232AD063583A
GKP-280 MH 675 446 235 215 465 490 250 440 300 1100 1200
GKP-140 M LN80 625 400 210 195 430 430 210 360 240 1050 1150
GKP-250 M LN80 675 446 235 215 465 490 250 440 256 1100 1200
GKP-150 MH
18 GAS GKP-140 MH 1800
GKP-150 MH
16 GK OIL GKP-140 MH 1600
P-
14
14 0 1400
M
H
12 1200
GK
mbar
P-
10 1000
15
Pa
0M
8 800
H
6 600
GKP140...150MH
4 400
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
20 2000
GKP-280
38 MH GKP-280 MH
18 GAS GKP-250 MH 1800
GK
P-2 GKP-280 MH
16 50 OIL GKP-250 MH 1600
MH
14 1400
12 1200
mbar
10 1000
8 800 Pa
6 600
4 400
GKP250...280MH
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
GK
P-2
20 50 2000
M
LN
80
mbar
Pa
15 1500
80
10 GKP-140 M LN 1000
GKP140...280 LN80
5 500
0
0 500 1000 1500 2000 2500
kW
39
8
Dimensions
7 6 5 4 3 2
F L1 L2
40
D1
Näkymät luk
View positio
H5
H1
H2
L3
E
H3
L5 D064045
O B2 B1
D
G = Gas inlet
B4
O= Oil inlet/return
E = Electrical connection
E F = FGR - Flue Gas Recirculation G = Gas inlet
O = Oil inlet/retu
E = Electrical co
F = FGR - Flue G
C F
BURNER L1 L2 L3 L5 H1 H2 H3 H5 B1 B2 B4 ØD1
GKP-350 M 1360 350 195 810 940 695Burner355 L1
345 L2
490 L3 580 L5 490H1 H2
320 H3 H5 B1 B
GKP-450 M 1470 350 195 910 1050 GKP-350395
770 M 1360
420 350
510 195650 810 550
940 695
370 355 345 490 5
GKP-450 M 1470 350 195 910 1050 770 395 420 510 6
GKP-320 M LN80 1360 500 195 810 940 GKP-320
695 M355
LN80 1360
345 500
490 195580 810 490
940 695
302 355 345 490 4
B GKP-450 M LN80 1470 480 195 910 1050 770 395 420 510 65
GKP-450 M LN80 1470 480 195 910 1050 770 395 420
│ ││││ │
510 650 550 324
1ST REV. SCALE
Ltuominen 19/12/2017
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
*D06
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D06404
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
177
MITTAKUVA ESITE A038300
GKP-320M...450M LN80
ITEM
Pa
10 1000
GKP350...450MIII
5 500
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
kW
25 2500
GKP-450 M LN80 41
GAS GKP-320 M LN80
GKP-450 M LN80
20 OIL 2000
GK GKP-320 M LN80
P-4
50
80 M
GKP-3 20 M LN LN
80
15 1500
mbar
Pa
10 1000 GKP320...450M LN80
5 500
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
kW
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
42
D1
Kuvannot lukit
øD2
View position
H1
H5
H2
L4
H3
O
G
E
L5 D064041
L3 B2 B1
R2 E
G = Gas inlet
D O= Oil inlet/return
B4
G = Gas inlet
E = Electrical connection O = Oil inlet/ return
F = FGR - Flue Gas RecirculationEF == FGR
Electrical conn
- Flue Gas
R1
F
C BURNER L1 L2 L3 L4 L5
GKP-500 M 1650 290 295 145 1090
*D064
GKP-500 M 1060 780 420 365 465 645 270 550
APPROVED BY 370
Ltuominen 425 1440 1400
CUSTOMER
GENERAL TOLERANCES
GKP-600 M 1060 780 420 365 465 645 270 550 395 425 1440 1400
PROJECT
DRW.NO
MARK
GKP-700 M 1060 780 420 365 515 700 270 550 395 425 1460 1400
TITLE
POLTIN , BURNER
D064041
A GKP-700 M-II 1060 780 420 365 515 760 270 550
WEIGHT (KG)
395 425
SUPERSEDES DRW.
1460 1400 3D-MODEL.NO
Rev Comment Modified By Date
GKP-700 M-III 1060 780 420 365 515 845 270 312550 425 - MITTAKUVA
1460 ESITE
1400 A038288
GKP-500M...700M-III
ITEM
Oilon Monoblock 2.0/022018
Working Diagram
35 3500
GAS GKP-600 M
30
GKP-500 M 3000
GKP-600 M
OIL GKP-500 M
GKP
25 -60 2500
0M
20 GK 2000
P-5
mbar
00
Pa
M
15 1500
10 1000
GKP500...600M
5 500
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000
kW
35 3500
43
GKP-700 M-III GKP-700 M-III
30 GKP GAS GKP-700 M-II 3000
-700
M-II GKP-700 M
GKP- GKP-700 M-III
700
25
M OIL GKP-700 M-II 2500
GKP-700 M
20 2000
mbar
Pa
15 1500
10 1000
GKP700...700MIII
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000
kW
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
44
D1
Kuvannot luki
øD2
View position
H1
H5
H2
L4
H3
O
G
E
L5 D064041
L3 B2 B1
R2 E
G = Gas inlet
D
B4
C BURNER L1 L2 L3 L4 L5
GKP-700 M-II LN80 1650 530 295 145 1090
Burner L1 L2 L3 L4 L5 H1 H2 H3 H5 B1 B2 B3 B4 øD1 øD2
GKP-500 M 1650 290 295 145 1090 1060 780 420 365 465 645 270 550 370 425
GKP-600 M 1650 310 295 145 1090 1060 780 420 365 465 645 270 550 395 425
GKP-700 M 1650 310 295 145 1090 1060 780 420 365 515 700 270 550 395 425
BURNER H1 GKP-700
H2 M-IIH3 H5
1650 310 B1295 B2
145 B3
1090 B4
1060 780ØD1 420 ØD2
365 R1
515 760R2 270 550 395 425
1060 GKP-700
780 M-III 1650 400 515295 145 1090 1060 780 406420 365 515 8451400 270 550 425
B
GKP-700 M-II LN80 420
GKP-700 M-II LN80
365
1650 530 295
760
145
270
1090
550
1060 780 420 -
365
1460
515 760 270 550 406
│ ││││ │
1ST REV. SCALE
Ltuominen 19/12/2017 1:
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
*D064
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D064041
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date Oilon Monoblock 2.0/022018
312
MITTAKUVA ESITE A038288
GKP-500M...700M-III
Working Diagram
35 3500
GAS GKP-700 M-II LN80
OIL
30 3000
25 2500
GKP-700 M-II LN80
20 2000
mbar
Pa
15 1500
GKP600...700M LN80
10 1000
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
kW
45
Dimensions
8 7 6 5 4 3 2
L1 L2
F
Näkym
View p
øD1
O
H1
H5
L4
H2
E
E
G
46
H3
L5 D064048
B2 B1
D
B4
G = Gas inlet
O = Oil inlet/return
E = Electrical con
F = FGR - Flue G
C
G = Gas inlet
O= Oil inlet/return
E = Electrical connection
F = FGR - Flue Gas Recirculation
F Burner L1 L2 L4 L5 H1 H2 H3 H5 B1 B
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
GKP-1000 M 1600 434 303 1000 1470 1100 510 585 800 88
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
B BURNER L1 L2 L4 L5 H1 H2 GKP-1200
H3 M H5 1600 B1434
│ ││││ │
303
B2 1000
B4 1470 1100
ØD1 510 585 940 93
1ST REV. SCALE
GKP-1000 M 1600 434 303 1000 1470 1100 510 585 Ltuominen 880
800 20/12/2017
750 496
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
GKP-1200 M 1600 434 303 1000 1470 1100 510 585 940 930 750 520
*D06
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D06404
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
571
MITTAKUVA ESITE A038294
GKP-1000 M...-1200 M
ITEM
DocID:A038294AD064048A
GKP-1200 M
GAS/OIL
30 GKP-1000 M 3000
GK GK
25 P-1 P-1 2500
00 20
0M 0M
20 2000
mbar
Pa
15 1500
10 1000
GKP1000...1200 M
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000
kW
47
Ignition transformer x x x x x
Flame sensor x x x x x
Gas nozzle x x x x x
Elbow 90° x x x x x
Oil nozzle x x x x x
2 oil hoses x x x x o
Deaerator - o o o -
FGR - o o o o
Frequency converter o o o o o
O2 control o o o o o
O2+CO control o o o o -
Manual x x x x x
x Standard
o Option
*) Not in 50 burners
**)Always in LN80 burners
***) Separate booster unit PKYK
8 Dimensions
7 6 5 4 3 2
L1 L2 B3
F
Näkymä
View po
øD1
H1
H2
50
H3
O D063418
B2 B1
R1
E
D
B4
R2
O= Oil inlet/return
E = Electrical connection
O = Oil inlet/R
C E = Electrical
BURNER L1 L2 H1 H2 H3 B1 B2 B3 B4 ØD1 R1 R2
KP-50 H 590 160 240 510 325 165 275 310 110 225 160 605 -
*D06
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063418
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
123
MITTAKUVA ESITE A038183
KP-50-90 H
ITEM
DocID:A038183AD063418A
8 800
KP
mbar
-50
Pa
H
6 600
4 400
2 200
KP50...90 H
0 0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600
kW
51
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
D1
Näky
View
H5
H1
H2
H3
E
52 O L5 D063798
B2 B1
E
R1
D
O= Oil inlet/return
E = Electrical connection
R2 F = FGR - Flue Gas Recirculation
O = Oil inlet/
When FGR is needed, oil pump unit will be relocated.
E = Electrica
F = FGR- Flue
F
C
BURNER L1 L2 L5 H1 H2 H3 H5 B1 B2 B3 ØD1 R1 R2
Burner L1 L2 L5 H1 H2 H3 H5 B1 B2 B3
KP-140 H 1075 220 668 625 400 KP-130 M
210 195 1075
410 200430 668 210625 400
240 210
1030 1951150 410 380 210
KP-140 H 1075 220 668 625 400 210 195 410 430 210
KP-150 H 1075 230 668 625 400 210 195
KP-140 M 410
1075 220480 668 210625 270
400 1030
210 1951150 410 430 210
KP-150 195
H 1075 230380 668 210625 400 210 1951150 410 480 210
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
KP-130 M 1075 200 668 625 400 210 410 200 1030
KP-150 M 1075 230 668 625 400 210 195 410 480 210
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
KP-250 M 1100 300430 675 210675 446 235 2151150 495 490 250
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
KP-140 M 1075 220 668 625 400 210 195 410 240 1030
B KP-280 M 1100 312 675 675 446 235 215 495 490 250
KP-150 M 1075 230 668 625 400 210 195 410 │ ││││ 480
│ 210 270 1030 1150
1ST REV. S
Ltuominen 12/12/2017
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
*D
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.N
Rev Comment Modified By Date
382
MITTAKUVA ESITE A0383
KP-140 H...280 M
ITEM
DocID:A038377AD063798A
14 1400
KP-140 H
12 KP 1200
-1
5
mbar
0
10 H 1000
Pa
8 800
6 600
4 400
KP140M...150H
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
20 2000
53
18 KP-150 M 1800
KP-140 M
16 KP-130 M 1600
KP-14
14 0M 1400
12 1200
KP
-15
KP
mbar
0M
Pa
10 1000
-1
30
M
8 800
6 600
KP130M...150M
4 400
2 200
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
kW
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
D1
Näky
View
H5
H1
H2
H3
E
L5 D063798
O
54 B2 B1
E
R1
O= Oil inlet/return
D
E = Electrical connection
F = FGR - Flue Gas Recirculation
R2 When FGR is needed, oil pump unit will be relocated.
O = Oil inlet/
E = Electrica
F = FGR- Flu
F
C
BURNER L1 L2 L5 H1 H2 H3 H5 B1 B2 B3 ØD1 R1 R2
Burner L1 L2 L5 H1 H2 H3 H5 B1 B2 B3
KP-250 M 1100 300 675 675 446 KP-130 215
235 M 1075
495 200
490 668 250625 400
270 210
1050 195
1200 410 380 210
KP-140 H 1075 220 668 625 400 210 195 410 430 210
KP-280 M 1100 312 675 675 446 235 215 495 490 250 300 1050 1200
KP-140 M 1075 220 668 625 400 210 195 410 430 210
KP-150 H 1075 230 668 625 400 210 195 410 480 210
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
KP-150 M 1075 230 668 625 400 210 195 410 480 210
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
KP-250 M 1100 300 675 675 446 235 215 495 490 250
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
B KP-280 M 1100 312 675 675 446 235 215 495 490 250
│ ││││ │
1ST REV.
Ltuominen 12/12/2017
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
*D
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.
Rev Comment Modified By Date
382
MITTAKUVA ESITE A0383
KP-140 H...280 M
ITEM
DocID:A038377AD063798A
14 1400
12 1200
mbar
Pa
10 1000
8 800
6 600
KP250M...280M
4 400
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
55
8
Dimensions
7 6 5 4 3 2
F L1 L2
D1
56
H1
H5
H2
näkymät luk
E view positio
H3
L5 D063804
O B2 B1
D
B4
O= Oil inlet/return
E = Electrical connection O = Oil inlet/re
E E = Electrical
F = FGR - Flue Gas Recirculation
C F
BURNER L1 L2 L5 H1 H2 H3 H5 B1 B2 B4 ØD1
KP-350 M 1360 350 810 940 695 355 345 490 530 490 320
KP-450 M 1470 350 910 1050 770 395 420 510 650 550 370
Burner L1 L2 L5 H1 H2 H3 H5 B1 B
KP-350 M 1360 350 810 940 695 355 345 490 5
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
*D06
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D06380
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
177
MITTAKUVA ESITE A038300
KP-350M...450M
ITEM
DocID:A038300AD063804A
20 2000
KP-350 KP
M -45
0M
15 1500
mbar
Pa
10 1000
5 500
KP350...450M
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
kW
57
8
Dimensions
7 6 5 4 3 2
L1 L2 B3
D1
58
H1
H5
Näkymät lu
H2
View positio
H3
L5 D063811
B2 B1
BURNER L1 L2 L5 H1 H2 H3 H5 B1 B2 B3 ØD1 R1
KP-500 M 1450 264 885 1060 780 420 365 440 640 350 340 1450
KP-600 M 1450 285 885 1060 780 420 365 440 640 350 370 1450
Burner L1 L2 L5 H1 H2 H3 H5 B1 B2 B3
KP-700 M 1450 350 985 1075 800 KP-500
420 M 335 1450520264 885
700 1060
350 780 395420 365
1450 440 640 350
KP-600 M 1450 285 885 1060 780 420 365 440 640 350
KP-700 M-II 1450 350 985 1075 800 420 M 335 1450520350
KP-700 765
985 350
1075 800 395420 1450
335 520 700 350
KP-700 M-II 1450 350 985 1075 800 420 335 520 765 350
│ ││││ │
1ST REV. SCALE
Ltuominen 13/12/2017 1:
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
*D063
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063811
WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
389
MITTAKUVA ESITE A038390
KP-500 M...700 M-II
ITEM
DocID:A038390AD063811A
Oilon Monoblock 2.0/022018
Working Diagram
35 3500
KP-700 M-II
30 KP-700 M 3000
KP-700 KP-600 M
M-II
KP-7 KP-500 M
25 KP 00 M 2500
-60
0M
20 KP 2000
-5
mbar
00
Pa
M
15 1500
10 1000
KP500...700MII
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
kW
59
Dimensions
8 7 6 5 4 3 2
L1 L2
F
øD1
O Näkym
View p
H1
H5
H2
E
E
60
H3
L5 D063831
B2 B1
D
B4
O = Oil inlet/return
E = Electrical conne
C F = FGR - Flue Gas
O= Oil inlet/return
E = Electrical connection
F = FGR - Flue Gas Recirculation
Burner L1 L2 L5 H1 H2 H3 H5 B1
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
*D0
APPROVED BY
KP-1200 M 1600 434 1000 1470 1100 510 585 940 930 Ltuominen
750 520 CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.N
Rev Comment Modified By Date
571
MITTAKUVA ESITE A03829
KP-1000 M...-1200 M
ITEM
DocID:A038294AD063831A
KP-1200 M
30 KP-1000 M 3000
KP KP
25 -10 -12 2500
00 00
M M
20 2000
mbar
Pa
15 1500
10 1000
KP1000...1200 M
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000
kW
61
Ignition transformer x x x x x x
Flame sensor x x x x x x
Oil nozzle x x x x x x
2 oil hoses x x x x x o
Oil filter x x x x x *
Deaerator - - o o o -
FGR - - o o o o
62
Turbo combustion head o o o o o o
Frequency converter - o o o o o
O2 control - o o o o o
O2+CO control - o o o o -
Manual x x x x x x
x Standard
o Option
*) Separate booster unit PKYK
Dimensions
8 7 6 5 4 3 2
L1 L2 B3
F
D1
64
Näky
View
H1
H5
H2
H3
E
O D063996
L5
B2 B1
E
R1
D
R2 O= Oil inlet/return
E = Electrical connection
O = Oil inlet/ret
E = Electrical c
C
BURNER L1 L2 L5 H1 H2 H3 H5 B1 B2 B3 ØD1 R1 R2
RP-130 M 1075 220 668 625 400 210 195 500 430 210 200 1030 1150
RP-140 M 1075 220 668 625 400 210 Burner
195 500 L1 430 L2 L5
210 H1
240 H21030 H3 1150H5 B1 B2
RP-130 M 1075 220 668 625 400 210 195 500 430
RP-150 M 1075 230 668 700 470 230 RP-140
195 M 500 1075480220 668
210 625
270 400
1030 210 1150195 500 430
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
THIS DOCUMENT IS PROPERTY OF OILON OY, LAHTI FINLAND.
RP-150 M 1075 230 668 700 470 230 195 500 480
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
B RP-280 M RP-280 M 1100 312 675 675 450 235 215 540 490
1100 312 675 675 450 235 215 540 490
│ ││││ │
250 300 1050 1200
1ST REV.
Ltuominen 18/12/2017
MODIFIED BY B
Ltuominen 22/03/2018
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
D
MARK
TITLE
POLTIN , BURNER
D
A WEIGHT (KG) SUPERSEDES DRW. 3
Rev Comment Modified By Date
403
MITTAKUVA ESITE A
RP-140 M...280 M
ITEM
Oilon Monoblock 2.0/022018
Working Diagram
20 2000
RP-280 M
RP-280 M
18 RP-250 M 1800
RP RP-150 M
-25
16 0M RP-140 M 1600
RP-130 M
RP
14 -1 1400
40
RP M
RP
12 1200
-1
-1
30
mbar
05
M
Pa
10 1000
M
8 800
6 600
4 400
RP130...280M
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
65
8
Dimensions
7 6 5 4 3 2
L1 L2 B3
D1
Näkymät luki
View position
H1
66
H2
H3
O D063937
B2 B1
O = Oil inlet/return
E = Electrical connec
R1
O= Oil inlet/return
E = Electrical connection
BURNER L1 L2 H1 H2 H3 B1 B2 Burner
B3 ØD1L1 R1
L2 H1 H2 H3 B1 B2 B3
RP-300 M-II 1350 200 925 665 360 590 RP-300300
580 M-II 1350 1400
300 200 925 665 360 590 580 300
RP-400 M-I 1450 264 1060 780 420 655 640 350
RP-400 M-I 1450 264 1060 780 420 655 640RP-500 M
350 1450 1450
340 264 1060 780 420 655 640 350
RP-600 M 1450 285 1060 780 420 655 640 350
RP-500 M 1450 264 1060 780 420 655 640RP-700
350
M 340
1450 1450
350 1060 780 420 655 730 350
RP-600 M 1450 285 1060 780 420 655 RP-700350
640 M-II 1450 1450
370 350 1060 780 420 655 765 350
│ ││││ │
1ST REV. SCALE
RP-700 M 1450 350 1060 780 420 655 730 395 18/12/2017
350Ltuominen 1470 1:20
MODIFIED BY BAR CODE
Ltuominen 22/03/2018
RP-700 M-II 1450 350 1060 780 420 655 765APPROVED350 395 1620
*D0639
BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO
MARK
TITLE
POLTIN , BURNER
D063937
WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.NO
Rev Comment Modified By Date
277
MITTAKUVA ESITE A038468
RP-300M-II...700M-II
ITEM
DocID:A038468AD063937A
RP-500 M
RP-400 M-I
RP
RP-300 M-II
-3
20 2000
00
M
-II
15 RP 1500
RP
-4 -5
mbar
00 00
Pa
M M
-I
10 1000
RP300MII...500M
5 500
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000
kW
35 3500
67
RP-700 M-II
30 RP-700 M 3000
RP-700 M RP-600 M
-II
25 RP 2500
-60
0M
20 2000
mbar
RP-
Pa
700
15 1500
M
10 1000
RP600...700MIII
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
kW
140...280 300...700
Hinge flange with limit switch x x
Ignition transformer x x
Flame sensor x x
Oil nozzle x x
Non-return valve x x
2 oil hoses x x
Oil filter x x
Deaerator x x
Thermometer x x
68
Electric preheater incl: x x
- limit thermostat
- temperature sensor
Frequency converter o o
O2 control o o
O2+CO control o o
Manual x x
x Standard
o Option
8
Dimensions
7 6 5 4 3 2
L1 L2 B3
F
70
D1
Näkymät l
H1
H5
View posit
H2
L4
H3
E G
L5 D063861
O B2 B1
E
L3
R1
B4
D
G = Gas inlet
O= Oil inlet/return
E = Electrical connection
G = Gas inlet
O = Oil inlet/r
R2 E = Electrica
C
BURNER L1 L2 L3 L4 L5 H1 H2 H3 H5
GRP-130 M 1285 200 260 129 880 625 400 210 195
*D0
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
GRP-140 M 600 430 210 360 240 1050 1160
PROJECT
DRW.NO
GRP-150 M 600 480 210 360 270 1050 1160 MARK
TITLE
POLTIN , BURNER
D063
GRP-250 M 635 490 250 440 270 1100 1200
A WEIGHT (KG) SUPERSEDES DRW. 3D-MODEL.N
Rev Comment Modified By Date
GRP-280 M 635 490 250 440 300 1100 1200
150
MITTAKUVA ESITE A03842
GRP-140 M...280 M
ITEM Oilon Monoblock 2.0/022018
Working Diagram
16 1600
GRP-150 M
GR
14 GAS GRP-140 M 1400
P-
GRP-130 M
GR
14
GRP-150 M
P-
0
15
M
12 OIL GRP-140 M 1200
0
GRP-130 M
M
10 1000
mbar
0M
Pa
8 800
P -13
6 600
GR
4 400
GRP130...150M
2 200
0 0
0 500 1000 1500 2000 2500 3000
kW
20 2000
GRP-28
0M 71
GRP-280 M
18 GAS GRP-250 M 1800
GR GRP-280 M
P-2 OIL
16 50 GRP-250 M 1600
M
14 1400
12 1200
mbar
10 1000
Pa
8 800
6 600
GRP250M...280M
4 400
2 200
0 0
0 500 1000 1500 2000 2500 3000 3500 4000
kW
72
Dimensions
8 7 6 5 4 3 2 1
L1 L2 B3
D1
D2
Näkymät lukittu
H1
View position lo
H2
L4
H3
G
O D063898
B2 B1
E L3
R2
B4
G = Gas inlet
O= Oil inlet/return
R1 E = Electrical connection G = Gas inlet
O = Oil inlet / return
E = Electrical connection
*D06389
APPROVED BY
Ltuominen
CUSTOMER
GENERAL TOLERANCES
PROJECT
MARK
Oilon Monoblock 2.0/022018
DRW.NO
TITLE
Working Diagram
25 2500
GR GRP-500 M
P- GAS/OIL GRP-400 M-I
30 GRP-300 M-II
0M
20 -II 2000
GR
P-5
GR 00
M
15 P- 1500
40
0
mbar
M
-I
Pa
10 1000
GRP300MII...500M
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000
kW
35 3500
73
GRP GRP-700 M-II
-700
30 M-II GAS/OIL GRP-700 M 3000
GRP- GRP-600 M
700
M
25 GR 2500
P-6
00
M
20 2000
mbar
Pa
15 1500
10 1000
GRP600M...700MIII
5 500
0 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
kW
Ignition transformer x x
Flame sensor x x
Gas nozzle x x
Elbow 90° x x
Oil nozzle x x
Non-return valve x x
2 oil hoses x x
Oil filter x x
Deaerator x x
Thermometer x x
Frequency converter o o
O2 control o o
O2+CO control o o
Manual x x
PROJECT
10 MARK
1. Double solenoid valve
CHECKED APPROVED TITLE E3. PROJECT NO.
12
DRW. REV.
1.1 Solenoid valve
1.2 Pressure regulation valve
STATUS SUPERSEDES DRW. PRODUCT DOC. ID SHEET
GP-50 ... 140 H, MB-ZRDLE 2. Pressure switch
2.1 Pressure switch (only burner type WDx00)
DPS 2.2 Pressure switch (burner types WDx00 and WD3x)
3. Gas butterfly valve
11
4. Servomotor
5. Pressure switch, max.
1.1
1.2
6. Solenoid valve, ignition gas, 75
5 *) depends on burner`s type
PS
7. Air damper
8. Servomotor
9. Combustion air fan
10. Electric motor
PI000645/4
PS PS
11. Differential air pressure switch
12. Flame detector
2.1 2.2
A = Gas supply
B = Air supply
DESIGNED DATE DIAGRAM TYPE SIZE
A3
CHECKED DATE BAR CODE
PROJECT
PROJECT
MARK
15 17
1. Double solenoid valve
20 19 1.1 Solenoid valve
1.2 Pressure regulation valve
14 16
2. Pressure switch
2.1 Pressure switch (burner type WDx00)
DPS
2.2 Pressure switch (burner types WDx00 and WD3x)
3. Gas butterfly valve, primary gas
PS
18 4. Servomotor, primary gas
5. Pressure switch, max., primary gas
1.1 1.2 6. Gas butterfly valve, tertiary gas
5 7. Servomotor, tertiary gas
PS 8. Pressure switch, max., tertiary gas
14. Air damper
15. Servomotor
16. Combustion air fan
PI000645/1
PS PS
17. Electric motor
18. Differential air pressure switch
2.1 2.2 19. Flame detector
20.. Flame detector
PROJECT
1. Oil hose, loose delivery
15 17 MARK
19 2. Oil filter, loose delivery
DATE DESIGNED CHECKED APPROVED TITLE E3. PROJECT NO. DRW. REV.
3. Oil pump
STATUS 14
SUPERSEDES DRW. 16 PRODUCT
GP-600 ... -700 M-III LN60, VGD-valve
DOC. ID SHEET 4. Solenoid valve, NC
5. Solenoid valve, NC
6. Solenoid valve, NC
DPS
14. Air damper
18 15. Servomotor
16. Combustion air fan
17. Electric motor
18. Differential air pressure switch,
5
not for KP-50...150 H burners
and GKP-50/90 MH burners
19. Flame detector
76 PI000645/5
A = Oil supply 0...5 bar
B = Oil return
C = Air supply
PROJECT
DATE DESIGNED CHECKED APPROVED TITLE E3. PROJECT NO. DRW. REV.
DATE DESIGNED CHECKED APPROVED TITLE E3. PROJECT NO. DRW. REV.
A = Oil supply
B = Oil return
C = Air supply
HEAVY FUEL OIL, M BURNER SERIES 140...280
DESIGNED DATE DIAGRAM TYPE SIZE
A3
CHECKED DATE BAR CODE 1. Oil filter, loose delivery
APPROVED DATE
23CUSTOMER 2. Oil hose, loose delivery
3. Oil pump, plugged
PROJECT
4. Electric motor
20 22
MARK 5. Pressure gauge
DESIGNED CHECKED APPROVED TITLE E3. PROJECT NO. DRW. REV. 6. Solenoid valve, NC
STATUS SUPERSEDES DRW.
DPS
PRODUCT 16 DOC. ID
PI 13
SHEET
7. Preheater
14
KP-1000 ... 1200 M 7 8. Temperature regulation / lower limit
PS 15
9. Limit thermostat
18
17
12
10. Thermometer
11. Solenoid valve, NC
5 12. Solenoid valve, NO
mm PI TS 13. Pressure qauge
TIC
10 11 14. Oil regulator valve
15. Servomotor
16. Non-return valve, throttle plug ø1,2mm 77
PI000645/9 17. Pressure switch, max.
TZA 18. Deaerator
19 19. Drilled ball valve
20. Air damper
21. Servomotor
22. Combustion air fan
DESIGNED DATE DIAGRAM TYPE SIZE 23. Electric motor
A3
CHECKED DATE BAR CODE 24. Differential air pressure switch, only GRP burners
APPROVED DATE CUSTOMER
25. Flame detector
PROJECT
A = Oil supply
HEAVY FUEL OIL, M BURNER SERIES 300...700 MARK
B = Oil return
DATE DESIGNED CHECKED APPROVED TITLE E3. PROJECT NO. DRW. REV.
C = Air supply
23 STATUS SUPERSEDES DRW. PRODUCT DOC. ID SHEET
RP-140 ... 280 M 9
20 22
1. Oil filter, loose delivery
2. Oil hose, loose delivery
DPS 16 PI 13 3. Oil pump, plugged
19 14
4. Electric motor
PS 15
5. Pressure gauge
17
12
6. Preheater
7. Temperature regulation / lower limit
5
8. Limit thermostat
PI TS
11 9. Thermometer
18 10. Solenoid valve, NC
TIC
11. Solenoid valve, NC
12. Solenoid valve, NO
PI000645/10
13. Pressure qauge
TZA 10 14. Oil regulator valve
15. Servomotor
16. Non-return valve, throttle plug ø1,2mm
17. Pressure switch, max.
18. Deaerator
DESIGNED DATE DIAGRAM TYPE SIZE 19. Drilled ball valve
CHECKED DATE BAR CODE
A3 20. Air damper
21. Servomotor
APPROVED DATE CUSTOMER
22. Combustion air fan
PROJECT
23. Electric motor
MARK
24. Differential air pressure switch
DATE DESIGNED CHECKED APPROVED TITLE E3. PROJECT NO. DRW. REV. 25. Flame detector
STATUS SUPERSEDES DRW. PRODUCT DOC. ID SHEET
RP-300 M-I ... 700 M-II 10
A = Oil supply
B = Oil return
C = Air supply
Oilon Monoblock 2.0/022018
Combustion head and masonry dimensions
4 3 2 1
Rev
Mounting plate Comment Modified By Date
4 3 2 1
Rev Comment Modified By Date
2 2
D D 660
D5 540
B6 180
M20
10 x
660
320
H6
Burner mounting
140 ...
WITHOUT A WRITTEN AUTHORIZATION BY THE OWNER.
150 │ ││││ │
1ST REV.
jhaverinen 15/12/2017 SCALE
1:10 PAPER SIZE
A4
150 MODIFIED BY
jhaverinen 15/12/2017 BAR CODE
280
*D063900*
APPROVED BY
jhaverinen
CUSTOMER
300 GENERAL TOLERANCES
PROJECT
... MARK
DRW.NO REV
A ...
TITLE
D063900 A
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
THIS DOCUMENT IS PROPERTY OF OILON OY, LAHTI FINLAND.
2 KIINNITYSLEVY , MOUNTING
2
78
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
1 BROCHURE P066913 A
1
8171.45 1000/1200 M
│ ││││ │ ITEM
BAR CODE
α
jhaverinen 15/12/2017
°
*D063874*
APPROVED BY
jhaverinen
CUSTOMER
GENERAL TOLERANCES
PROJECT
DRW.NO REV
ØD1
ØD4
MARK
ØD1
ØD4
TITLE
KIINNITYSLEVY , MOUNTING
D063874 A
WEIGHT (KG) SUPERSEDES DRW. PLATE 3D-MODEL.NO REV
2886.98
BROCHURE P066893 A
50...700 M-III
ITEM
3
DocID:P066893AD063874A OILON CAD 3
4
4
L2
L6
L2
1. Gasket, thickness 8 mm
2. Mounting plate
3. Ceramic wool or equivalent
4. Masonry
GP/GKP/KP/RP/GRP-130 H/M/MH 275 275 230 - 4xM16 200 200 60° - 90°
GP/GKP/KP/RP/GRP-140 H/M/MH 275 275 270 - 4xM16 240 220 60° - 90°
GP/GKP/KP/RP/GRP-150 H/M/MH 275 275 300 - 4xM16 270 230 60° - 90°
KP/RP-250 M 365 365 300 - 4xM16 270 300 60° - 90°
GP/GKP/GRP-250 M/MH 365 365 300 - 4xM16 270 300 60° - 90°
KP/RP-280 M 365 365 330 - 4xM16 300 312 60° - 90°
GP/GKP/GRP-280 M/MH 365 365 330 - 4xM16 300 312 60° - 90°
GP/GKP/KP-1000 M See figure mounting plate 1000/1200 496 434 60° - 90°
GP/GKP/KP-1200 M See figure mounting plate 1000/1200 520 434 60° - 90°
L2 L6
BURNER SERIE B6 H6 ØD4 M ØD1 C1 C2 C1 C2
GP/GKP-140 M LN80 275 275 270 4xM16 240 - 430 - 240-380
GP/GKP-250 M LN80 365 365 290 4xM16 256 420 550 240-365 365-495
GP-280 M LN80 365 365 310 4xM16 276 420 550 240-365 365-495
GP-1000 LN80 See figure mounting plate 1000/1200 454 - 650 - 290-570
5000
4000
mm
3000
2000
Flame dimensions
1000
0
0 2000 4000 6000 8000 10000 12000 14000 16000
kW
The diagram shows the flame dimension of an Oilon burner in a regular firetube boiler.
80
Case 1
D6
L6
L7
Case 2
D6 D7
81
L6
L7
Minimum dimensions to meet EN676 class 3 NOx emissions (LN80) and FprEN676 class 4 NOx emissions (LN60).
D7 minimum ≥ D6 * 0.7
L1 is an overall boiler front wall thickness, including refractory, steel front wall and a possible burner mounting plate.
R2” MB-ZRDLE 420 350 - 680 350 - 780 350 - 1000 350 - 1000 360
B01 S20
GP-90 H R1½” MB-ZRDLE 415 350 - 600 350 - 650 350 - 870 350 - 1200 360
B01 S20
R2” MB-ZRDLE 420 350 - 680 350 - 780 350 - 1160 350 - 1500 360
B01 S20
GP-90 M R1 ½" DMV-D 512 250 - 600 250 - 650 250 - 870 250 - 1500 500
82 GKP-90 MH R2" DMV-D 520 250 - 850 250 - 1000 250 - 1500 250 - 1500 500
R2" VGD20.5011 250 - 850 250 - 1000 250 - 1500 250 - 1500 500
NOTE! When the burner is firing other gases than previously mentioned or when the gas inlet pressure is below 20 mbar every
case must be checked separately.
*) The max. capacities given in the table are achieved at a boiler backpressure of 0 and air pressure of 1013 mbar.
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 20 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using DMV-D valve
*) The max. capacities given in the table are achieved at a boiler back - max. 360 mbar when using MB valve 83
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 50 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using VGD valve.
*) The max. capacities given in the table are achieved at a boiler back
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 20 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using DMV(D) valve.
*) The max. capacities given in the table are achieved at a boiler back
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 50 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using VGD valve.
*) The max. capacities given in the table are achieved at a boiler back
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 20 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using DMV(D) valve.
*) The max. capacities given in the table are achieved at a boiler back 85
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 50 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using VGD valve.
*) The max. capacities given in the table are achieved at a boiler back
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 100 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using DMV valve
*) The max. capacities given in the table are achieved at a boiler back - max. 700 mbar when using VGD40 valve
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
86 GP/GKP-1000 M...1200 M
BURNER GAS VALVE BURNER MAX. CAPACITY kW*)
GAS INLET PRESSURE mbar
SIZE TYPE**) 100 150 200 250
GP/GKP-1000 M DN100 DMV-5100/11 7500 10000 11100 11100
DN125 DMV-5125/11 11100 11100 11100 11100
GP/GKP-1200 M DN100 DMV-5100/11 8000 10500 13300 13300
DN125 DMV-5125/11 12000 13300 13300 13300
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 100 mbar every case must be checked
separately. Gas inlet pressure (Pmax) at burner
*) The max. capacities given in the table are achieved at a boiler - max. 500 mbar when using DMV valve
backpressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
GP-1000 M LN80
BURNER GAS VALVE BURNER MAX. CAPACITY kW*
GAS INLET PRESSURE, mbar
SIZE TYPE** 50 100 150 250 350
GP-1000 M LN80 DN80 VGD 40 4750 7250 9200 11000 11000
DN100 VGD 40 6000 9000 11000 11000 11000
DN125 VGD 40 6500 10000 11000 11000 11000
NOTE! When the burner is firing other gases than previously mentioned or
when the gas inlet pressure is below 50 mbar every case must be checked Gas inlet pressure (Pmax) at burner
separately. - max. 500 mbar when using VGD valve
*) The max. capacities given in the table are achieved at a boiler back
pressure of 0 and air pressure of 1013 mbar.
Natural gas 1 m3n/h ≈ 10 kW
**) or corresponding type
1. Gas valve
C
2. Gas elbow
L D064441
│ │ │ │
mdanelon 24/01/2018 1:5 A3
mdanelon 24/01/2018
E
DN/6
DN/6
Burner øD L B
130...150 DN125 475 190
D
250...280 DN150 490 190
6 320...600 DN200 530 125
B
D 6
B
min. 200
D064059 D064103
3
min. 200
C
88
1. Butterfly valve FGR 1. Butterfly valve FGR
2. Servomotor 2. Servomotor
3. FGR pipe, not included in the delivery 3. FGR pipe, not included in the delivery
MULTIPLICATION OR INFORMATION OF ITS CONTENTS TO THE
THIS DOCUMENT IS PROPERTY OF OILON OY, LAHTI FINLAND.
4. Sleeve 1/2”, not included in the delivery 4. Sleeve 1/2”, not included in the delivery
THIRD PARTIES IN ANY FORM WHATEVER IS NOT ALLOWED
│ ││││ │
6. Burner B 1ST REV.
jhaverinen 20/12/2017 6. Burner SCALE
1:8 PAPER SIZE
A3
│ ││││ │
MODIFIED BY BAR CODE 1ST REV.
jhaverinen 05/01/2018 jhaverinen 21
8 7 6 5 BY 4 3 2 1 BY
*D064059*
APPROVED MODIFIED
Burner ØD L B jhaverinen Burner ØD L B jhaverinen 05
CUSTOMER
A
GENERAL TOLERANCES APPROVED BY
130...150 DN125 475 190 700 DN250 520 155 jhaverinen
F PROJECT
DRW.NO
GENERAL TOLERANCES
REV
250...280 DN150 490 190 MARK
1000 DN300 555 183
320...600 DN200 530 125 1200
TITLE
LÄPPÄVENTTIILI DN350
, BUTTERFLY
D064059
585 183
B
WEIGHT (KG) SUPERSEDES DRW. VALVE 3D-MODEL.NO REV
Comment Modified By Date
A FGR DIMENS. BROCHURE A038560 B
Rev 16 Comment 130...1200 Modified By Date
WEIGHT (KG) SUPERSEDE
ITEM
31
E Turbo combustion head for flame shaping A ITEM
DocID:A038560BD064059B OILON CAD
Example A-A
DocID:A038587BD064103B
2 1
D061147
1. Combustion head
2. Turbo
ON OF ITS CONTENTS TO THE
ATEVER IS NOT ALLOWED
ATION BY THE OWNER.
B
│ ││││ │
1ST REV. SCALE PAPER SIZE
mdanelon 04/07/2017 1:10 A3
MODIFIED BY
jhaverinen 03/04/2018 Oilon Monoblock 2.0/022018
BAR CODE
APPROVED BY
jhaverinen
Silencer
2 1
Air intake silencer Hood silencer
3 2 1
5 9
Construction 4 8 3 Construction 2 1
The silencer is made of steel plate lined with fire- The silencer is made of steel plate lined with fireproof
proof dampening8wool. The silencer is connected to dampening wool. This wheel-equipped silencer iso-
the burner’s suction side via a screw connection. The lates the burner from four sides. Silencer reduces the
silencer reduces the high-pitched sound13 15 by 12
produced 3
sounds produced when the burner operates.
the air flow. Delivered in plate parts.
1.
2.
Butterfly valve FGR
Servo motor
A
3. FGR pipe, not included delivery
4. Sleeve 1/2", not included delivery
5. Temperature sensor
943
6. Burner
B
Burner øD L B
1
700 DN2503 520 155 18
1000 DN300 545 155
1200 DN350 570 155
1001
25 11
1669 89
L W L
PROJECT
*D064103*
DRW.NO REV
H
MARK
TITLE
LÄPPÄVENTTIILI , BUTTERFLY
D064103 B
ED VALVE 3D-MODEL.NO REV
ES DRW.
W
FGR DIMENS. BROCHURE
130...1200
A A038587
(1 : 5) B
OILON CAD
SCALE PAPER SIZE
1:5 A3
Burner BAR W
CODE L H Burner W L H
*D059368*
130...150 427 391 230 130...150 1328 1307 1100...1650
400...700 560 720 505 280...700 1669 1533 1500...2000
1000/1200 35682003525
│ STEEL PLATE
800 │ 1,5mm
665 │ DC01 │ EN 10130
1000/1200 2173 1883 1950...2450
1. REV. DRW.NO REV SUHDE PAPERIKOKO
1ST REV. vmikkola 30/01/2013 SCALE
1:20 PAPER SIZE
A3
NVAIMENNIN ,
MUOKANNUT
D05936811/03/2013
MODIFIED BY vmikkola A VIIVAKOODI , BAR CODE
OILON OY
*D034519*
CER YLEISTOLERANSSIT , GENERAL TOLERANCES
3D-MODEL.NO REV
ISO 2768-m NIMITYS , TITLE
N ÄÄNENVAIMEN A035464 A
PIIR.NO , DRW.NO REV
D034519 A
3D-MAL.NO , 3D-MODEL.NO REV
By Date OILON CAD
a 14.01.2013 MASSA (KG) KORVAA N:ON ÄÄNIERISTYSVAUNU A021688 A
WEIGHT
Oilon Monoblock 2.0/022018 SUPERSEDES DRW. NIMIKE , ITEM
30461110
Booster unit
B
D
540
4 x Ø 13
A C
1 Oil filter
2. Pressure gauge
3. Oil pump
390
440
4. Electric motor
5. Pressure regulating valve
6. Drilled ball valve
940
A. Inlet to the booster unit DN25,
1000
1...5 bar 4...12 mm2/s
B. Return from the booster unit R1/2”
C. Inlet to the burner Ø 22
The booster unit is used for pumping light fuel
D. Return from the burner Ø 22
oil with viscosity of 4...12 mm2/s +20 °C. The oil
coming to the booster unit must be filtered, max.
90 filtration degree is 150 µm.
The output has been calculated using a density of 850 kg/m3 for the light fuel oil.
Diagram 1
Selection of the booster unit for light fuel oil
1400
1300
1200
1100 PKYK3
1000
900
800
PKYK2
700
600
Example
1. Ball valve
2. Gas filter
3. Pressure regulator with safety shut-off valve
and safety relief valve 91
4. Bellows compensator/gas hose
5. Pressure gauge valve
6. Pressure gauge, high pressure
7. Pressure gauge valve
8. Pressure gauge, low pressure
9. Ball valve, blow-off
A Gas inlet
B Gas to burner
92