Mep Boq

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 41

Kingdom of Saudi Arabia - Ministry of Health

Al Suhaimi Charity Center for Children


Dammam
Bill No.(01): Building

CONTENTS

PREAMBLE TO THE BILL OF QUANTITIES


0
Division 15a : PLUMBING works

Division 15b : FIRE PROTECTION works

Division 15c : HVAC works

Division 16 : Electrical works

Grand Total

Rev. No. : (00) Page 1 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
DIVISION 15a: Mechanical
PLUMBING SYSTEMS
WATER SUPPLY WORKS

1 For cold/hot water pipes inside the building


Polypropylene(PN16) piping system as specified
including all fittings, valves, water hammer
arrestors, automatic air vent & all required
accessories to complete the installation for the
following Outer Diameters:

1.1 20 mm dia. m 165


1.2 25 mm dia. m 90
1.3 32 mm dia. m 35
1.4 40 mm dia. m 80

1.5 50 mm dia. m 60
1.6 63 mm dia. m 30

2 For pipes outside the building of UPVC Class 5


as specified including all fittings (e.g. stainless
steel couplers, bends, branches supports),
excavation, bedding, warning tape, back filling &
all required accessories to complete the
installation for the following Outer Diameters:

2.1 63 mm dia. m 40

2.1 110 mm dia. m 20

Individual electric water heater including all


accessories as specified and as shown on
3
project general details with the following
capacities:

3.1 30 liter storage and 1.5 KW power, ref. EWH-1 No. 33

3.2 50 liter storage and 4.5 KW power, ref. EWH-2 No. 4

Carried to collection

Rev. No. : (00) Page 2 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Drainage, Waste & Vent works

UPVC class-4 drainage, vent & storm drianage


pipes as specified including Vent Throught Roof
with cover, clean outs, floor cleanouts and all
4
required fittings and Hangers necessary to
complete the installation for the following Outer
Diameters :

4.1 50 mm dia. m 195


4.2 75 mm dia. m 90
4.3 110 mm dia. m 210

Underground UPVC class-4 drainage & storm


drianage pipes as specified including excavation,
bedding, backfilling, warning tape for pipes
5
outside the buildings and all required fittings and
all necessary to complete the installation for the
following Outer Diameters :

5.1 50 mm dia. m 50
5.2 75 mm dia. m 20
5.3 110 mm dia m 80

Floor drain (FD) including trap as specified for


6
the following sizes:
6.1 50 mm dia. No. 38

Roof drain (RD) as specified for the following


7
diameters:
7.1 110 mm dia, ref RD-2 No. 4

Side Outlet Roof drain (SRD) as specified for the


8
following diameters:
8.1 75 mm dia, ref SRD-2 No. 1

50 mm dia. funnel floor drain as per tender


9 No. 4
documents.

10 110 mm dia, Ground Cleanout (GCO) No. 2

Condensate drain pipe inside the building (UPVC


Class 4), for A/C units complete with cleanouts,
11 funnel drains, insulation, indirect waste and
fittings, as per drawing and specification of the
following Outside Diameters:

11.1 25 mm dia. m 460


11.2 50 mm dia. m 30

Rev. No. : (00) Page 3 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Plumbing fixtures and trim as specified including


angle valves, mixers, traps, flexible
12 connections,water supply, driange and vent short
pipes and all accessories to complete the
installation for the following types:
12.1 Shower head with shower tray, ref (SH-1) No. 3
12.2 Counter top Lavatory, ref (LAV-1) No. 26
12.3 Wall Hung Lavatory, ref (LAV-2) No. 21
12.4 Pantry Sink - Single bowel, ref (PS) No. 5
12.5 Handicapped countertop lavatory, ref (LAV-H) No. 1
12.6 Handicapped Water Closet, ref (WC-H) No. 1
12.7 Water Closet, ref (WC-1) No. 23
12.8 Hose Bibb, ref (HB) No. 2
12.9 Clinic Sink - , ref (CS) No. 17

Supplying, installing, connecting, testing and


commissioning an automatic factory packaged,
prefabricated, tested certified and guaranteed
four-pump, variable frequency drive, constant
pressure domestic water booster pumping
system complete, inculding all controls, motors,
valves suction and discharge pipe manifold with
13
all interconnecting piping and wiring, as well as,
copper tubing with shutoff cocks for gauges,
pressure switches and vibration-isolating
mounts, .. etc., all mounted on a common
structural steel base prior to shipment. price
should be inclusive operation spare parts, all as
per tender documents.

DWP 01,02,03 Each pump With 40 GPM & 80


13.1 No. 1
PSI.
Supplying, installing, connecting, testing and
commissioning sump pumps complete including
14 pumps, valves, control panel, spare parts,
accessories and all ancillary work as specfied
and as shown on drawings.
Duplex packaged waste water submersible
14.1 pumps. SWP-01,02 Each Pump With 45 GPM & No. 1
20 PSI.

Carried to collection

Rev. No. : (00) Page 4 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Supplying, installing, connecting and testing all


galvanized steel domestic water piping system
within pump room including including pipes,
fittings, flanges, unions and all other accessories
as per tender documents. The item shall include
as well all water tank connections and
15 accessories, including but not limited to filling LS 1
modulating float valves, isolating valves, alarm
probe system, vent pipe with wire mesh, tank
overflow and drain, pump room trench drain, and
all other required pipe connections with valves
and water level alarm system all as specified and
as shown on drawings.

Carried to collection

Rev. No. : (00) Page 5 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Collection

Total of page 1of 5

Total of page 2of 5

Total of page3of 5

Total of page 4of 5

Total of Division 15a - Carried to Project summary

Rev. No. : (00) Page 6 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
DIVISION 15b: Mechanical
FIRE PROTECTION SYSTEMS
1 Black seamless steel pipe sch. 40, work includes
all fittings such as elbows, tees, bend, unions,
reducers, Automatic air vents, pipe connection
with fittings which shall be mechanical coupling
type for pipe size 50 mm and larger, screwed or
welded joints for pipe size less than 50 mm dia.
The item includes hangers and other supports for
pipes as needed.
This items includes all required to finalize the
works as specified and in accordance with NFPA
& fire department regulations for the following
diameters:-

1.1 25 mm dia. m 550


1.2 32 mm dia. m 136
1.3 40 mm dia. m 150
1.4 50 mm dia. m 60

1.5 65 mm dia. m 155


1.6 80 mm dia. m 18
1.7 100 mm dia. m 60
1.8 150 mm dia. m 45

2 UPVC Class-5 underground fire water pipes,


work includes all fittings such as elbows, tees,
bend, unions, reducers.
The item includes excavation, bedding, warning
tape, backfilling and all needed.
This items includes all required to finalize the
works as specified and in accordance with NFPA
& fire department regulations for the following
diameters:-

2.1 160 mm dia. m 30

Fire hose cabinet with 40mm 30 meter hose reel


& 30 meters 65mm hose and nozzle length with
3 No. 7
6 kg. portable fire extinguisher as per approved
design drawings and specifications. Ref (FHC)

Rev. No. : (00) Page 7 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Main Alarm Check Valve as shown on drawings


4
and as specified
4.1 150mm dia No. 1

Zone Control Valve as shown on drawings and


as specified. The Item includes the following:
1- OS&Y Gate Valve with tamper switch.
5 2- Check Valve.
3- Pressure Gauge.
4- Flow Switch.
5- Test & Drain Valve Assembly.

5.1 100 mm dia. No. 2


5.2 65 mm dia. No. 4
5.3 40 mm dia. No. 1

Two way siamese connection as per design


6 drawings and specifications. Item includes check No. 1
valve.

Automatic sprinkler heads as specified and as


7
follows:-

Pendent fully concealed sprinkler head, quick


7.1 response, 1/2 inch orifice, 1/2 inch thread with K No. 220
factor = 5.6, working temperature = 68 deg. C.

Upright sprinkler head, quick response, 1/2 inch


7.2 orifice, 1/2 inch thread with K factor = 5.6, No. 15
working temperature = 68 deg. C.

8 Fire extinguishers as specifeid and as follows:


8.1 Dry Chemical Powder, 6 KG. REF(PFE-1) No. 13
8.2 Carbon Dioxide, 5 KG. REF(PFE-2) No. 9
On Wheel Foam Extinguisher, 45 Liters.
8.3 No. 1
REF(WFE-1)

Carried to collection

Rev. No. : (00) Page 8 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Automatic clean agent fire extinguishing system (


using FM-200 agent), including agent cylinders),
fire alarm panel, discharge nozzles, piping
complete with fittings and accessories, required
9
to finalize the works for automatic operation.
The work shall be as specifed, as shown on the
drawings, and in accordance with NFPA & Civil
defence requirements.

Complete FM-200 system


9.1 Effective quantity = 8 kg No. 1
for room 05-017
Complete FM-200 system
9.2 Effective quantity = 9 kg No. 1
for room 04-018
Complete FM-200 system
9.3 Effective quantity = 8 kg No. 1
for room 03-022
Complete FM-200 system
9.4 Effective quantity = 8 kg No. 1
for room 02-019
Complete FM-200 system
9.5 Effective quantity = 15 kg No. 1
for room 01-033
Complete FM-200 system
9.6 Effective quantity = 33 kg No. 1
for room Gr-013
Complete FM-200 system
9.7 Effective quantity = 15 kg No. 1
for room Gr-014

Supplying, installing, connecting, testing and


commissioning an automatic, factory assembled
wired and tested electric driven fire pump system
(EFP-1) consisting of the pump, motor, and
controller, (pump & motor) to be mounted on a
common base prior to shipment. Fire pump shall
10 No. 1
be horizontal split case bronze fitted, double
suction. The pump complete package shall be
UL listed and FM approved including all
accessories and fittings all as specified and as
shown on drawings.
Pump design capacity = 500 GPM @ 160 PSI.

Rev. No. : (00) Page 9 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Supplying, installing, connecting, testing and


commissioning an automatic, factory assembled
wired and tested Diesel engine driven fire pump
system consisting of the pump, engine, relief
valve , and controller, all mounted on a common
base, pump, engine, and controller shall be
tested prior to shipment. Fire pump shall be
horizontal split case bronze fitted, double suction
and centrifugal, the pump shall be UL listed and
11 No. 1
FM approved- complete including but not limited
to all accessories and fittings conforming to all
requirements of NFPA #20 and as shown on
drawings, the engine shall be complete including
the duel lead acid batteries , muffler
,controller(UL & FM),fuel system with tank and all
accessories and fittings all as specified and as
shown on drawings.
Pump design capacity = 500 GPM @ 160 PSI.

Supplying, installing, connecting, testing and


commissioning an automatic packaged vertical
multistage jockey pump , complete including the
12 No. 1
UL listed controller and all other accessories as
specified and as shown on drawings.
Pump design capacity = 25 GPM @ 170 PSI.

Carried to collection

Rev. No. : (00) Page 10 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Rev. No. : (00) Page 11 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Collection

Total of page 1of 5

Total of page 2of 5

Total of page 3of 5

Total of page 4of 5

Rev. No. : (00) Page 12 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Total of Division 15 b - Carried to Project summary

Rev. No. : (00) Page 13 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
DIVISION 15c: HVAC
Drawings, B.O.Q & specifications are one unit.

All items including supply and installation unless otherwise mentioned.

1 Roof Top Package Air Conditioning Unit


Package Air Conditioning Units with refrigerant 410A complete with
cooling coil, volume dampers,pre and bag filters, supply fans, valves,
stainless steel drain pan, concrete base, vibration isolators, supports,
flexible connection and complete with controls and required
accessories for proper installation and operation, all as per specs and
drawings.

Ref No. Air Flow Cooling


[L/s] KW
1.1 PU-01 1000 21.5 No. 1 17,000 17,000
1.2 PU-02 1400 27 No. 1 20,000 20,000
1.3 PU-03 1550 29 No. 1 20,000 20,000

2 Decorative-Split air conditioning unit


Supply, install, test and commission High Wall DX split room air
conditioning units with Refrigerant R22, and including remote
control, indoor unit,Steel Stand, outdoor unit, all required REF. pipes,
cables ;power & control all as per specs and drawings.

Ref No. Cooling Capacity KW


2.1 SRAC-01 4.2 No. 6
2.2 SRAC-02 5.7 No. 4

3 Concealed-Split air conditioning unit


Supply, install, test and commission DX-Concealed air conditioning
units with Refrigerant R22, and including wall thermostat, indoor
unit,Steel Stand, outdoor unit, all required REF. pipes, cables ;power
& control all as per specs and drawings.

Ref No. Cooling Capacity KW


3.1 I.U-01 4.75 No. 4 4,500 18,000
3.2 I.U-02 6.00 No. 78 4,500 351,000
3.3 I.U-03 7.2 No. 8 6,000 48,000

Carried to collection 474,000

Rev. No. : (00) Page 14 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Rev. No. : (00) Page 15 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
4 Air Handling Unit
Supply, install, connect, test and commission, DX-air handling unit 100
% Fresh Air with refrigerant R22 connected to Condensing unit.
complete with sand trap louver, inlet box, pre and bag filters, supply
fans, valves, stainless steel drain pan, concrete base, vibration isolators,
supports, flexible connection and complete with controls and required
accessories for proper installation and operation, all as per specs and
drawings.

4.1 F.AHU-01 No. 1

5 Air cooled Condencing unit


Air cooled Condencing units, include all Accessors all required REF.
pipes, cables ;power & control , safe installations, testing, balancing
and start upall as per specs and drawings @ outdoor temperature 46
c.
5.1 FA-CU-01 No. 1

6 Exhaust air centrifugal inline fan

Supply, install, connect, test and commission fans including steel bases
with vibration isolator, frames, rubber pads, sealers for leakage,
flexible connections, guard screens and all required accessories for
proper installation and operation as per specs and drawings

Ref No. Air flow [L/s] static(Pa)


6.1 EAF-01 1170 150 No. 1 1,500 1,500
6.2 EAF-02 275 150 No. 1 500 500
6.3 EAF-03 200 100 No. 1 800 800
6.4 EAF-04 200 200 No. 1 800 800
6.5 EAF-05 420 200 No. 1 800 800
6.6 EAF-06 245 200 No. 1 600 600
6.7 EAF-07 70 150 No. 1 350 350

7 Pressurization air Axial inline fan

Supply, install, connect, test and commission axial inline fans including
rubber pads, sealers for leakage, flexible connections ,steel bases with
vibration isolator and all required accessories for proper installation
and operation as per specs , schedule of equipment and drawings.

Ref No. Air flow [L/s] static(Pa)


7.1 PF-01 4850 250 No. 1 7,500 7,500
0
8 Galvanized sheet metal Rectangular duct work 0
Supply, install, connect, test and commission galvanized sheet metal
duct (G90) works including hangers, supports, rods, bolts, duct
mounted access doors and panels, sealant, internal turning vanes, kg 10,000 22 220,000
flexible connectors, balancing dampers , fire damper and all required
accessories for proper installation and operation.

Carried to collection 232,850

Rev. No. : (00) Page 16 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
9 Thermal insulation

Supply, and install 25 mm thick glass wool thermal insulation 24


kg/cm3 density for indoor supply, return and treated fresh air ducts
with one coat of foster 30-36 coats and this is for ducts in indoor areas
9.1 m2 2,000 25 50,000
complete with adhesives, tapes, wire banding, fixing pins and any other
accessories needed for proper installation and operation all as per specs
and drawings.

Supply, and install 50 mm thick glass wool thermal insulation rigid


duct insulation 24 kg/cm3 with canvas cloth and three coats of foster
30-36 coats and 0.6 mm aluminum cladding protection for outdoor
9.2 m2 500 35 17,500
supply, return and treated fresh air ducts complete with adhesive, tapes,
wire banding, fixing pins and any other accessories needed for proper
installation and operation, all as per specs and drawings.

11 Air Outletes
Supply ceiling diffuser fabricated of extruded aluminum and polyester
powder coated square type complete with opposed blade volume
11.1
damper acoustical insulated plenum box and all accessories according
to the drawings and specifications.

11.1.1 225mm X 225mm No. 59 150 8,850


11.1.2 250mm X 250mm No. 14 200 2,800
11.1.3 300mm X 300mm No. 48 250 12,000
0
Return ceiling diffuser fabricated of extruded aluminum and polyester
11.2 powder coated square type complete with all accessories according to 0
the drawings and specifications.
0
11.1.1 225mm X 225mm No. 59 100 5,900
11.1.2 250mm X 250mm No. 14 150 2,100
11.1.3 300mm X 300mm No. 48 200 9,600

Supply air grilles/register fabricated of extruded aluminum and are


11.3 polyester powder coated complete with opposed blade volume damper
and all accessories according to the drawings and specifications.

950 mm × 300 mm No. 7 450 3,150

Exahust air grills fabricated of extruded aluminum and are polyester


11.4 powder coated complete with opposed blade volume damper and all
accessories according to the drawings and specifications.

150mm X 150mm No. 3 80 240


200mm X 150mm No. 1 100 100

Carried to collection 112,240

Rev. No. : (00) Page 17 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Supply Linear Slot Diffuser fabricated of extruded aluminum and


polyester powder coated complete , opposed blade volume dampers
11.5 0
,plenum box with acoustical internal insulation, the spigot flexible duct
shall control the flow from face of linear diffuser
0
2 slots/ 1200 mm width No. 47 170 7,990
0
Return Linear Slot Diffuser fabricated of extruded aluminum and
11.6 polyester powder coated complete , and all accessories according to 0
specification and drawings.
0
2 slots/ 1200 mm width No. 47 110 5,170
0
Exhaust air ceiling diffuser fabricated of extruded aluminum and are
11.7 polyester powder coated complete all accessories according to the 0
drawings and specifications.
0
150mm X 150mm No. 33 100 3,300
0
12 Testing And Commissioning 0
Balancing, Testing, Commissioning of HVAC System: Shall include all
equipment's and tools required in performing Testing, commissioning
12.1 L.S 1 10,000 10,000
and operation of HVAC equipment, adjusting and air balancing of
HVAC system.

Rev. No. : (00) Page 18 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Carried to collection 26,460

Rev. No. : (00) Page 19 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Collection

Total of page 1of 5 474,000

Total of page 2of 5 232,850

Total of page3of 5 112,240

Total of page 4of 5 26,460

Total of Division 15c - Carried to Project summary 845 550.00

Rev. No. : (00) Page 20 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
DIVISION 16: Electrical
Supply, installation, testing and commissioning of
13.8 KV RMU with circuit breaker 200A , fuses and
load break switch 400A, 60Hz, including cable seal
end for 13.8 KV XLPE cables.As specified and shown
on drawings.
0.1 RMU No. 0

2 MEDIUM VOLTAGE CABLES


Supply and installation medium voltage Armored
XLPE-insulated, copper conductors, multicore cables
(15KV) from RMU to transformer as specified below
including fitting & fixation accessories as per
specifications and drawings comprising the
followings.
2.1 3C x 70 mm² XLPE M 0

3 13.8KV TRANSFORMER
Supply, installation, testing and commissioning of Oil
immersed sealed transformer complete with
temperature supervision devices, protective relays &
all other accessories as specification & drawings in
accordance with (SEC) standards, including all
necessary civil works.Refer to power single line
diagram.

3.1 TR, 1000KVA, 13.8KV-400/231V, 3PH, 60HZ No. 0


4 WIRE AND CABLE 600V AND BELOW
Supply, installation, testing and commissioming of low
voltage steel tape armored XLPE-insulated, PVC
sheathed, copper conductors, single or multicore
cables (0.6/1KV) as specified below including all
conduits or cable trays , handhole, pull boxes,
termination, identification, related civil works, fitting &
fixation accessories as per specifications and
drawings comprising the followings.

4.1 4.5C-300 mm2 M 0


4.2

Rev. No. : (00) Page 22 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection Canceld Canceld

Rev. No. : (00) Page 23 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
5 WIRE AND CABLE 600V AND BELOW
Supply, installation, testing and commissioming of low
voltage un-armored XLPE-insulated, PVC sheathed,
copper conductors, single or multicore cables
(0.6/1KV) as specified below including all conduits or
cable trays , handhole, pull boxes, termination,
identification, related civil works, fitting & fixation
accessories as per specifications and drawings
comprising the followings.

5.1 4C-6 mm2 M 70


5.2 4C-10 mm2 M 150
5.3 4C-16 mm2 M 200
5.7 4.5C-95 mm2 M 20
5.8 4.5C-150 mm2 M 30

4.11 4.5C-300 mm2 M 80


5 GROUNDING CABLES
Supply and instalation, testing and commissioning of
copper grounding cable in conduits or cable trays
including splicing, termination, identification, and
related civil works.
5.1 1C-6 mm² PVC insulated M 70
5.2 1C-10 mm² PVC insulated M 150
5.3 1C-16 mm² PVC insulated M 200
5.7 1C-70 mm² PVC insulated M 30
5.9 1C-150 mm² PVC insulated M 80

PANEL BOARDS& DISTRIBUTION BOARDS


6 MAIN DISTRIBUTION PANEL
Supply, installation,testing and commissioning of
main distribution panel, 400V, 3-phase, 5-wire, 60Hz,
floor mounted fully wired, tested and put into
operation in accordance with specifications and
drawings including ground bus, all instruments and
protection devices cables termination, and necessary
civil works.

6.1 MDB,1600AT / 2000AF ACB No. 1


6.2 EMDB,200AT / 250AF MCCB No. 1

7 DISTRIBUTION PANEL
Supply,installation,testing and commissioning of
distribution panel, 400V, 3-phase, 5-wire, 60Hz, floor
mounted fully wired, tested and put into operation in
accordance with specifications and drawings
including ground bus, all instruments and protection
devices cables termination, and necessary civil
works.IP 54

7.1 MCC-1,250AT / 630AF MCCB No. 1


7.2 MCC-2, 630AT / 630AF MCCB No. 1
STANDBY POWER GENERATOR SYSTEM

Carried to collection

Rev. No. : (00) Page 24 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Rev. No. : (00) Page 25 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
8 EMERGENCY STANDBY GENERATOR
Supply,installation,testing and commissioning of
emergency standby diesel generator, 400V, 3 phase-
4 wire, 60Hz, concrete foundation, exhaust and
cooling system, day tank system of 24 hours
capacity,control panel, plant exerciser, generator
mounted circuit breaker, checker plates and cable
trench as shown in drawing, generator grounding
complete with all componenets and accessories for
fully functional generator in the event of mains failure
in the following capacities:

8.1 85kW (106kVA) ( Standby Rating) No. 1


9 Fuel Tank With Transfer Pump
Supply and installation of underground fuel storage
tank having capacity of at least 72 hours continuous
operations of generator at rated load, with necessary
transfer pumps, piping, level switches, level gauges, No. 1
ladder , all accessories and all necessary civil works.

10 AUTOMATIC TRANSFER SWITCH


Supply,installation,connecting,testing and
commissioning of automatic transfer switch, 4-poles,
4 wire, 400V including enclosure, circuit breakers,
contactors, auto-off manual selector switch, control
circuit and all protections required, grounding,
concrete pad, civil works with all associated hardware
and accessories as per drawings and specifications.

10.1 ATS, 200A rating. NO 1

11 POWER FACTOR CORRECTION


Supply,installation,testing and commissioning of
capacitor bank for 400V power supply system on
MDB in compliance with Standard. Cells shall be
sealed type in steel case incorporating pressure
sensitive intruppter to improve power factor of the
system to 0.95
11.1 300 KVAR rating. No. 2

PANELBOARDS & DISTRIBUTION BOARDS

Carried to collection

Rev. No. : (00) Page 26 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
12 LIGHTING AND POWER PANELBOARDS
Supply,installation,testing and commissioning of
lighting and power panels , 400V, 3PH, 60Hz,
wall/floor mounted fully wired, tested and put into
operation in accordance with specifications and
drawings including ground bus, contactors, indication
lamp, ON/OFF pushbutton, protection devices, cables
termination and necessary civil works.

12.1 LPP-GRD,50AT / 100AF MCCB No. 1


12.2 LPP-1ST,40AT / 100AF MCCB No. 1
12.3 LPP-2ND, 32AT / 100AF MCCB No. 1
12.4 LPP-3RD, 32AT / 100AF MCCB No. 1
12.5 LPP-4TH, 32AT / 100AF MCCB No. 1
12.6 LPP-5TH, 32AT / 100AF MCCB No. 1
12.7 ELPP-GRD,20MCB No. 1
12.8 ELPP-1ST,20MCB No. 1
12.9 ELPP-2ND,20MCB No. 1
12.10 ELPP-3RD,20MCB No. 1
12.11 ELPP-4TH, 20MCB No. 1
12.12 ELPP-5TH, 20 MCCB No. 1
12.13 UPP-GRD, 50AT / 100AF MCCB No. 1
12.14 UPP-2ND, 50AT / 100AF MCCB No. 1

WIRING DEVICES
13 RECEPTACLES
Supply,installation,testing and commissioning of
power receptacles wired not less than 4.0 mm² in
conduit, including devices, wires, conduits, boxes, all
fixings supports, from the panel boards to receptacles
points and as per specifications.
13.1 Single Receptacle,13A,230V,1-Ph,2P, 3Wire, Wall
No. 327
Mounted Grounding type
13.1 Single Receptacle,13A,230V,1-Ph,2P,3Wire, Wall
No. 58
Mounted Grounding type, Weatherproof Type
13.2 Duplex Receptacle, 13A, 230V, 1-Ph, 2P, 3Wire, Wall
No. 101
Mounted Grounding type

14 SPECIAL PURPOSE RECEPTACLES


Supply,installation,testing and commissioning of
special purpose receptacles wired not less than 6.0
mm² in conduit, including devices, wires, conduits, all
fixings supports, from the panel boards to receptacles
points and as per specifications.

14.1 30 A, 230 V, 1 PH, 3wire grounded spaecial purpose


No. 22
receptacle.

Rev. No. : (00) Page 27 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Rev. No. : (00) Page 28 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
15 DISCONNECT SWITCHES
Supply,installation,testing and commissioning of
Disconnect Switches, Heavy duty type with all fixing
and flexible metallic/liquidtight conduit, accessories in
following capacities.
15.1 32 A, 250 V, 2P, NEMA 4X No. 210
0.1 20 A, 250 V, 2P, NEMA 4X No. 40
15.2 25 A, 600 V, 3P, NEMA 4X No. 1
0.2 32 A, 600 V, 3P, NEMA 4X No. 1
15.3 40 A, 600 V, 3P, NEMA 4X No. 1
0.3 50 A, 600 V, 3P, NEMA 4X No. 2
16 LIGHTING POINTS
Supply,installation,testing and commissioning of
lighting point and including rigid heavy gauge PVC or
EMT conduits, conduit fittings, boxes with not less
than 3 mm² wiring for lighting point, earthing
terminations, accessories and all necessary civil work

16.1 Lighting Points. No. 993


17 LIGHTING FIXTURES
Supply,installation, connecting , testing , and
commissioning of lighting fixtures including all lamps,
mounting brackets, suspension cords, accessories
and all necessary auxiliary works as specified and as
shown on the drawings.
17.1 Type F1 No. 70
17.2 Type F2 No. 36
17.3 Type F3 No. 125
17.4 Type F4 No. 36
17.5 Type F5 No. 48
17.6 Type F6 No. 20
17.7 Type F7 No. 14
17.8 Type F8 No. 57
17.9 Type F9 No. 80
18.10 Type F10 No. 31
18.11 Type F11 No. 72
18.12 Type F12 No. 32
18.13 Type F13 No. 26
18.14 Type F14 No. 16
18.15 Type F15 No. 330
WIRING DEVICES
18 SWITCHES
Supply,installation, connecting , testing , and
commissioning of lighting control switches / push
button 10 Amp., 230 V, including all conduit pvc
sheathed and copper conductor 3mm² wires upto
switches / push button. As shown on drawings and
as per specifications.

18.1 One way,One gang switch,10A. No. 180


18.2 One way,One gang switch,10A weatherproof No. 82
18.3 Divider-one gang lighting switch No. 16
18.4 dimmer one gang lighting switch No. 12

Rev. No. : (00) Page 29 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Rev. No. : (00) Page 30 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

GENERAL PROVISIONS FOR ELECTRICAL WORK


& WIRE AND CABLE - 600 VOLT AND BELOW

19 Power Points of Exhuast Fans , Roll Up Doors,


Air CurtainUnits, Electric Water Heaters, Bypass
Damper &Condensing Units.
Supply,installation, connecting and testing power
points of condensing units, exhaust fans,by pass
damper, roll up door, air curtain, water heaters and
with wires size mentioned below and shown in the
panelboard schedules, including wires with boxes,
conduits with all associated hardware, fixings and
accessories.

19.1 2x6.0mm² + 6.0mm²G for condensing units No. 205


19.2 2x4mm² + 4mm²G for exhaust fans No. 5
19.3 2x4.0mm² + 4.0mm²G for electric water heater No. 40
19.3 4x6.0mm² mm²G for A/C units N0. 3
19.4 4x10mm² mm²G for A/C units N0. 2
20 GROUNDING AND BONDING
Supply, install, & test earthing system (TN-S)
according to specs and drawings, completely installed
including earth pits, test links, clips conduits, fittings
and all related accessories.

20.1 Power earthing system:


Earthing system including copper rods, plates
according to drawings and specs to verify earthing LS 1
resistance of 5 ohm.
20.2 Low current earthing system:
Earthing system including copper rods, plates
according to drawings and specs to verify earthing LS 1
resistance of 0.5 ohm.

21 LIGHTNING PROTECTION SYSTEM


Supply, installation, testing and commissioning of
complete lightning protection system as specified and LS 1
as shown on the drawings.

22 IP FIRE ALARM SYSTEM


22.1 Supply, installation, testing and handing over the
following:

22.1.1 Fire alarm point including cables, conduits boxes & all
accessories up to next device and/or up to respective 187
fire alarm control panel

22.1.2 Addressable fire alarm control panel 4 loops including


NO 1
complete interface with BMS system.

22.1.3 Addressable smoke detector NO 111

22.1.4 Addressable Multi detector NO 8

22.1.5 Addressable heat detector NO 2

Rev. No. : (00) Page 31 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Rev. No. : (00) Page 32 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

22.1.7 Addressable manual pull station NO 14

22.1.8 Addressable monitor module NO 16

22.1.9 Addressable control module NO 14

26.1.11 Magnetic door holder


NO 7

26.1.12 Indoor Fire alarm bell.


NO 14

27 IP CLOCK SYSTEM
Supply, installation, testing and handing over the
following:

27.1 Single face wall mounted 16" IP analog clock NO 15


27.2 Double face ceiling mounted 16" IP analog clock NO 6
28 IP TELEPHONE SYSTEM & DATA NETWORK
ACTIVE COMPONENT
28.1 Supply, installation, testing and handing over
according to the specifications & drawings the
following:
28.1.1 Telephone Sets
a. IP telephone set wall mounted. NO 81

28.1.2 Wireless Access Point NO 19

29 IP SECURITY SYSTEMS
IP Closed circuit TV.(CCTV)

29.1 Supply, installation, testing and handing over the IP-


CCTV system including workstation, cabling, outlets,
conduits, boxes and all necessary accessories
according to the specification and drawings the
following:

29.1.1 Ceiling mounted dome colored IP camera. NO 29

30.0 IP Access Control System


30.1.1 Systems software & interfacing with CCTV system
including workstation hardware and conduits, cables
& all accessories for complete system performance.

a. IP-based intelligent access system controller (IASC)


NO 1

b. Proximity card reader NO 8

d. Electro magnetic door lock NO 7

e. Exit Push button NO 6

Rev. No. : (00) Page 33 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Rev. No. : (00) Page 34 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

31 PUBLIC ADDRESS/AUDIO VISUAL


31.1 Supply, installation, testing and handing over the
following:
31.1.1 Public address rack (LAR) including:
- 19 inch rack, 15U
- Moniter unit
- Zone selector
- Desktop paging mic NO 1
- Fire alarm voice call unit
- Power supply assembly with main switch
-Mixer unit
-Network Audio Adapter

Speakers
32 Supply, installation, testing and handing over the
following:

32.1 Ceiling mounted loudspeaker (1.5/3/6)W NO 53

32.3 Public address console with microphone NO 1


Audio Visual System
33 Supply, installation, testing and handing over the
following:
33.1 Video projector 3000 ansi lumen NO 1

33.3 LAVELIER MICROPHONE NO 1

33.4 DYNAMIC MICROPHONE NO 1

Projection system
37 Supply, installation, testing and handing over the
following:
37.1 Wall mounted projector outlet including conduits,
NO 1
boxes, cables and all other accessories
40 STRUCTURE CABLING SYSTEM
Supply, installation, testing and handing over the
following:
Outlets:
40.1 Supply, installation, testing the following outlet
including CAT 6 UTP cables, conduits, back boxes,
faceplate and patch cords and all necessary
accessories, from the outlet to the respective IT rack.

40.1.1 Wall mounted quad outlet loaded with two CAT 6 RJ-
N0 178
45 jack for desk type telephone & data

40.1.6 Ditto, as above but for IPTV system .

Rev. No. : (00) Page 35 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS
Carried to collection

Rev. No. : (00) Page 36 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

40.1.7 Ditto, as above but for ACCESS CONTROL system.


N0 20

40.1.8 Ditto, as above but for clock system . N0 3

40.1.9 Ditto, as above but for Public Address system N0 55

40.1.10 Ditto, as above but for Fire Alarm system


N0 187

40.1.11 Ditto, as above but for Audio Visual system


N0 5

40.1.13 Ceiling mounted outlet loaded with double CAT 6 RJ-


N0 21
45 jack for clock system.

40.1.14 Ditto, as above but for wireless network (access


N0 19
point).

40.1.15 Ditto, as above but for CCTV system


N0 29

41 Standard 19" cabinets complete with management


& earthing kits.

41.1 Supply and installation of 19" Cabinet free standing


type/ wall mounted type with front Glass Cover and
rare metallic plates with fixed mounting shelf for
server and ventilation fans tray including 6 ways
power socket stripe with caster wheels . IT Rack
equiped with rack mounted UPS System having
Single Phase , 60Hz

41.1.1 42U size, free standing 600x600mm dimemsion with


NO 1
UPS of 25 KVA having 15 MIN backup time.

42 Fiber optic patch panels with patch cords,


management panels.
42.1 Supply, installation, testing and handing over the
following:

42 Main fiber optic patch panel loaded with (48) single


N0 2
mode connectors & couplers

43 Ditto, as above but 96.

Carried to collection

Rev. No. : (00) Page 37 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

44 UTP Cat-6 patch panels with patch cords &


management panels

44.1 Supply, installation, testing and handing over the


following:

45 UTP CAT 6 patch panel 48 port N0 6

46 Fiber optic cables

46.1 Supply, installation, testing and uncoil, test and


connect the cables from handhole to data rack inside LS 1
the building handing over the following:-
Nurse call system
Supply, install, connect, test, commission and
guarantee of nurse call system and all necessary
items and accessories, conduits, trunks, fittings…etc
for a complete operative system as specified
LS 1
Supply, install, connect, test, commission and
guarantee the required network including (and not
limited) conduit, fittings, wiring, termination and all
necessary works.
Master clock system
Supply, install, connect, test, commission and
guarantee of Master clock system and all necessary
items and accessories, conduits, trunks, fittings…etc
for a complete operative system as specified
LS 1
Supply, install, connect, test, commission and
guarantee the required network including (and not
limited) conduit, fittings, wiring, termination and all
necessary works.

Carried to collection

Rev. No. : (00) Page 38 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Collection

Total of page 1of 1

Total of page 2of 11

Total of page3of11

Total of page 4of 11

Total of page 5of 11

Total of page 6of 11

Total of page 7 of 11

Total of page 8of 11

Total of page 9of 11

Total of page 10of 11

Rev. No. : (00) Page 39 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Rate Amount
Item Description Unit Quantity
RS RS

Total of Division 16- Carried to Project summary

Rev. No. : (00) Page 40 of 41


Issue Date: April, 2017
Kingdom of Saudi Arabia - Ministry of Health
Al Suhaimi Charity Center for Children
Dammam
Bill No.(01): Building

Division Total by SR

GRAND TOTAL for BILL no.(01) - Part 2/2

Total of Division 15a : PLUMBING works

Total of Division 15b : FIRE PROTECTION works

. Total of Division 15c : HVAC works

Total of Division 16 : Electrical works

Part 2/2 Total SR

PROJECT TOTAL

Total BILL no.(01) - Part 1/2

Total BILL no.(01) - Part 2/2

PROJECT Total SR .00

Rev. No. : (00) Page 41 of 41


Issue Date: April, 2017