A Novel Method of Using A Control Valve For Measurement and Control of Flow - Instrumentation and Measurement, IEEE Transactions On
A Novel Method of Using A Control Valve For Measurement and Control of Flow - Instrumentation and Measurement, IEEE Transactions On
A Novel Method of Using A Control Valve For Measurement and Control of Flow - Instrumentation and Measurement, IEEE Transactions On
6, DECEMBER 1999
Abstract—The control of flow through a pipe requires mainly For the control of fluid flow, it is essential to introduce
three devices—a flowmeter for the measurement of flow, a control a variable restriction in the flow. A control valve precisely
valve to control the flow, and a controller. The controller gives does this [5]. Control valves were in use for a very long time,
an appropriate signal to the control valve depending upon the
difference between the measured flow rate and the set flow beginning perhaps from the time when dams and irrigation
rate. Conventional flowmeters produce a differential pressure systems were first designed [6]. Even though, due to advances
in the flow, which is measured and suitably scaled to get the in mechanical engineering, many of the latest types of control
flow rate. Incidentally, a control valve uses the principle of valves have been developed, the basic principle of the control
restricting the area for flow which in turn produces a differential valve (i.e., introducing a variable restriction in the flow) has
pressure. From the above, it is seen that if a relationship is
developed between the differential pressure produced by the remained the same. This method of flow control introduces a
control valve and the flow through it, the valve itself could differential pressure across the control valve.
function as a flow meter also, apart from acting as a control valve.
A relationship for this was established based on the equation II. PRINCIPLE
for control valve capacity (Cv ) for different valve positions. The
expression requires knowledge of the differential pressure across For a fluid flow control loop, however sophisticated a
the valve, the static pressure, temperature, the valve position, flowmeter is, it is essential to have a control valve that
and the Cv Vs valve position characteristics in order to measure operates in a conventional way. Thus, in a flow control loop, a
and control the flow rate. Error analysis is performed for the
expression and to suggest means to improve the accuracy level. An
differential pressure is generated across the system due to the
iterative approach is necessary in order to obtain a particular flow control valve. If this differential pressure itself can be related
rate using this method. This necessitates the use of a computer to the flow rate through the valve, then the flowmeter can
or a processor-based system, similar to present day intelligent be entirely eliminated from the flow control loop. This idea
controllers, to implement the scheme. A prototype was made in has been developed mathematically and experimentally. Even
the laboratory using a 50-mm conventional control valve with
pneumatic actuator, working as the control valve and flowmeter.
though the idea can be implemented for all types of fluid flow
An HP data acquisition and control system (DACS), used as the control, for the sake of this paper only, flow control of air is
controller, was also used to provide the appropriate output signal considered.
to achieve the necessary flow control. The unit was calibrated at The flow rate through a conventional differential
the air flow laboratory to an accuracy of 61:5%. pressure-producing flowmeter is given by
(1)
I. INTRODUCTION
where is the discharge coefficient, and is the differ-
M EASUREMENT and control of fluid flow is very much
essential in any process-control plant. Many types of
flowmeters, both inferential and noninferential, have evolved
ential pressure measured across the meter. Fig. 1 shows the
schematic of a conventional flow control loop.
A salient parameter of a control valve, called the control
over the years [1]. Flowmeters which produce a differential
valve capacity states that the flow capacity of a valve is the
pressure in the flow, which in turn is related to the flow rate,
U.S gallons per minute of water at a temperature of 60 F that
were some of the first kind of flow meters [2]. Orifice plates,
will flow through the valve with a pressure loss of one pound
venturi meters, and the like fall into this category [3]. Due to
per square inch at a specific opening [7]. Even though the units,
the advent of modern electronics, many types of flow meters
for the sake of definition, are given in the foot-pound-second
like the electromagnetic flowmeter, coriolis mass flowmeter,
(FPS) system, they are appropriately converted to SI units for
cross-correlation flow meter, etc., have been developed and
the purpose of calculations. For the valve in the fully open
are widely used in process plants [4]. The major advantage
condition, for compressible fluid flow, the equation relating the
of some of the latest flowmeters is that they do not introduce
control valve capacity to the flow rate , differential pressure
a differential pressure for measurement of flow unlike their
across the valve, static pressure , temperature in
conventional counterparts. This amounts to a saving in energy
the line, expansion factor , compressibility factor and
for pumping of the fluids.
gas specific gravity for compressible fluid is given by
Manuscript received February 1, 1998; revised September 16, 1999.
M. A. Atmanand is with the National Institute of Ocean Technology, Indian (2)
Institute of Technology, Madras 600 036, India (e-mail: [email protected]).
M. S. Konnur is with the Fluid Control Research Institute, Palghat 678 623,
India. where and is a numerical constant to take care
Publisher Item Identifier S 0018-9456(99)09593-5. of the appropriate units [8].
0018–9456/99$10.00 1999 IEEE
ATMANAND: NOVEL METHOD OF USING A CONTROL VALVE 1225
TABLE I
CALIBRATION RESULTS OF PROTOTYPE FLOWMETER
TABLE II
COMPARISON OF COMPONENT REQUIREMENTS FOR NORMAL FLOW CONTROL LOOP AND FOR THE PROTOTYPE DEVELOPED
VI. RESULTS various data, perform the necessary computation, and provide
The system developed was calibrated at the air flow lab- appropriate signals for actuating the control valve. This system
oratory of the Institute against a servo positive-displacement as described could also be modified for gas flow measurement
flowmeter having an accuracy of %. An overall accuracy in custody transfer, wherein the flow rate measured is to be
of the order of % was obtained for the system. Table I converted to the standard temperature and pressure (STP) or
shows the results obtained. As seen from the error analysis, the the normal temperature and pressure (NTP) condition. The
major cause of the error is due to the errors involved in the necessary equations derived from the gas law could be fed
measurement of differential pressure, pressure, and position. into the system. This processor-based system, installed in the
By using transmitters of higher accuracy, the overall accuracy field, could be integrated with the field-bus system, which is
can be improved. being standardized internationally.